ADOPTS WITH AMENDMENTS:

International Fire Code 2015 (IFC 2015)

Part VII Appendices

Heads up: There are no amended sections in this chapter.
The provisions of paragraphs (A)(5601) to (G)(5607) of this rule shall govern the possession, manufacture, storage, handling, sale and use of explosives, explosive materials, matters described in section 3743.80 of the Revised Code and small arms ammunition. The provisions referencing fireworks in paragraphs (A)(5601) to (E)(5605), (H)(5608) to (J)(5610) and (L)(5612) to (Y)(5625) of this rule shall govern the possession, manufacture, storage, handling, sale and use of fireworks. The provisions of paragraph (K)(5611) of this rule shall govern the operation of flame effects.
Exceptions:
  1. The Armed Forces of the United States, Coast Guard or National Guard.
  2. Explosives in forms prescribed by the official United States Pharmacopoeia.
  3. The possession, storage and use of small arms ammunition where packaged in accordance with DOTn packaging requirements.
  4. The possession, storage and use of not more than 1 pound (0.454 kg) of commercially manufactured sporting black powder, 20 pounds (9 kg) of smokeless powder and 10,000 small arms primers for hand loading of small arms ammunition for personal consumption.
  5. The use of explosive materials by federal, state and local regulatory, law enforcement and fire agencies acting in their official capacities.
  6. Special industrial explosive devices that in the aggregate contain less than 50 pounds (23 kg) of explosive materials.
  7. The possession, storage and use of blank industrial— power load cartridges where packaged in accordance with DOTn packaging regulations.
  8. Transportation in accordance with DOTn 49 CFR Parts 100-185 as listed in rule 1301:7-7-80 of the Administrative Code.
  9. Items preempted by federal regulations.
In addition to the requirements of this rule, NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code shall govern the manufacture, transportation, storage, sale, handling and use of explosive materials.
In addition to the requirements of this rule, the operation of explosive material terminals shall conform to the provisions of NFPA 498 as listed in rule 1301:7-7-80 of the Administrative Code.
The possession, manufacture, storage, sale, handling, exhibition and use of fireworks are prohibited except as permitted in accordance with Chapter 3743. of the Revised Code and this rule. Matters relating to the construction and operation of a fireworks retail showroom subject to sections 3743.04 (B) or 3743.25 of the Revised Code, including matters not address in NFPA 1124 (2015 edition) shall comply with NFPA 1124 (2006 Edition) as listed in rule 1301:7-7-80 of the Administrative Code. All other references to NFPA 1124 in this rule shall mean NFPA 1124 (2015 Edition) as listed in rule 1301:7-7-80 of the Administrative Code.
In addition to the authority to grant modifications in accordance with paragraph (D)(8)(104.8) of rule 1301:7-7-01 of the Administrative Code, the state fire marshal may grant a variance to any provision of this code promulgated under the authority of Chapter 3743. of the Revised Code upon written application by an affected party and upon demonstration by that party of all of the following:
  1. That a literal enforcement of the provision will result in a practical difficulty in complying with the requirements of this code; and
  2. That the variance will not threaten the public health, safety or welfare.
A request for variance submitted pursuant to this rule shall only be considered upon production of any information or documentation requested by the state fire marshal. The particulars of such variance when granted shall be in writing, entered upon the records of the state fire marshal and furnished to the applicant and the authority having jurisdiction, if said authority is other than the state fire marshal.
Unless otherwise stipulated by the state fire marshal upon the granting of a variance, each variance granted pursuant to this rule shall automatically terminate one year from the date of its issuance.
There shall be no automatic renewals of any variance granted pursuant to this rule. Each variance shall be specifically applied for in writing by the requesting party and independently considered by the state fire marshal.
The storage, handling and use of model and high-power rockets shall comply with the requirements of NFPA 1122, NFPA 1125 and NFPA 1127 as listed in rule 1301:7-7-80 of the Administrative Code.
The storage and handling of ammonium nitrate shall comply with the requirements of NFPA 400 as listed in rule 1301:7-7-80 of the Administrative Code and rule 1301:7-7-63 of the Administrative Code.
Exception: Storage of ammonium nitrate in magazines with blasting agents shall comply with the requirements of NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Permits shall be required as set forth in rule 1301:7-7-01 of the Administrative Code and regulated in accordance with this rule. Permits required for manufacture, processing and explosives storage and explosive material storage as set forth in rule 1301:7-7-01 of the Administrative Code shall be obtained from the state fire marshal. No permit shall be required under this code for any actions by a law enforcement agency taken pursuant to section 3743.68 of the Revised Code, including the confiscation, verification and testing, storage, or destruction of fireworks.
No permit shall be issued for the manufacturing, processing or storage of explosives or explosive materials unless the following conditions are met:
  1. The applicant submits an application for permit on a form prescribed by the state fire marshal.
  2. The applicant pays the required fees and satisfies the background check and financial responsibility requirements as required by this rule.
  3. The applicant provides a list of all explosives and explosive materials to be manufactured, processed or stored under the permit.
  4. The applicant provides a map showing the distances between the locations of the activities subject to the permit and any adjacent structures, lot lines, railroads and roadways.
  5. The activities and locations subject to the permit have been inspected by the fire code official having jurisdiction and found to be in compliance with NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code and this code.
Persons shall not keep or store, nor shall any permit be issued to keep or store, any explosives at any place of habitation, or within 100 feet (30 480 mm) thereof.
Exception: Storage of smokeless propellant, black powder and small arms primers for personal use and not for resale in accordance with paragraph (F)(5606) of this rule.
Persons shall not construct a retail display nor offer for sale explosives, explosive materials or fireworks upon highways, sidewalks, public property or in Group A or E occupancies.
The fire code official is authorized to limit the quantity of explosives, explosive materials or fireworks permitted at a given location. Persons, possessing a permit for storage of explosives at any place, shall not keep or store an amount greater than authorized in such permit. Only the kind of explosive specified in such a permit shall be kept or stored.
Exception: Permit limitations on the quantity of fireworks possessed or stored at a licensed premises for fireworks, as that term is defined in section 3743.01 (BB) of the Revised Code, shall be approved by the state fire marshal before any enforcement of such provisions by a local fire code official.
Before a permit for the storage of explosives or explosive materials is issued, as required by paragraph (A)(2)(5601.2) of this rule, the applicant shall file with the jurisdiction a corporate surety bond in the principal sum of $100,000 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property that arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. Before a permit for the manufacture or processing of explosives or explosive materials, the applicant shall file with the jurisdiction a corporate surety bond in the principal sum of $1,000,000 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property that arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. The fire code official is authorized to specify a greater or lesser amount when, in his or her opinion, conditions at the location of use indicate a greater or lesser amount is required. Government entities shall be exempt from the requirements of paragraph (A)(2)(e)(5601.2.5) of this rule, but are not exempt from the blasting or fireworks exhibition requirements of paragraph (A)(2)(e)(i)(5601.2.5.1) or (A)(2)(e)(ii)(5601.2.5.2).
Before approval to do blasting is issued, the applicant for approval shall file a bond or submit a certificate of insurance in such form, amount and coverage as determined by the legal department of the jurisdiction to be adequate in each case to indemnify the jurisdiction against any and all damages arising from permitted blasting.
The applicant for a fireworks exhibition permit shall provide to the local fire official and law enforcement officer an indemnity bond in the amount of at least one million dollars with surety satisfactory to the fire official and law enforcement officer of the jurisdiction, conditioned for payment of all final judgments that may be rendered against the exhibitor on account of injury, death, or loss to persons or property emanating from the fireworks exhibition, or proof of insurance coverage of at least one million dollars for liability arising from injury, death, or loss to persons or property emanating from the fireworks exhibition.
No person shall be eligible for a permit for the manufacture, processing or storage of explosives under this code if the individual has been convicted of or pled guilty to a felony under the laws of this state, another state, or the United States. All persons seeking a permit for the storage of explosives or explosive materials shall complete a civilian background check for criminal history as administered or approved by the state fire marshal. The state fire marshal may accept a currently valid "Certificate of Clearance" or other similar documentation issued by the bureau of alcohol, tobacco, firearms and explosives as satisfactory documentation of a person's criminal history. Applicants shall, upon request of the state fire marshal, provide the state fire marshal with certified copies, or other similar documentation, relating to the individual's civilian criminal background check.
Permits shall not be issued or renewed for possession, manufacture, storage, handling, sale or use of the following materials and such materials currently in storage or use shall be disposed of in an approved manner.
  1. Liquid nitroglycerin
  2. Dynamite containing more than 60-per cent liquid explosive ingredient.
  3. Dynamite having an unsatisfactory absorbent or one that permits leakage of a liquid explosive ingredient under any conditions liable to exist during storage.
  4. Nitrocellulose in a dry and uncompressed condition in a quantity greater than 10 pounds (4.54 kg) of net weight in one package.
  5. Fulminate of mercury in a dry condition and fulminate of all other metals in any condition except as a component of manufactured articles not hereinafter forbidden.
  6. Explosive compositions that ignite spontaneously or undergo marked decomposition, rendering the products of their use more hazardous, when subjected for 48 consecutive hours or less to a temperature of 167°F (75°C).
  7. New explosive materials until approved by DOTn, except that permits are allowed to be issued to educational, governmental or industrial laboratories for instructional or research purposes.
  8. Explosive materials forbidden for transport by DOTn.
  9. Explosive materials containing an ammonium salt and a chlorate.
  10. Explosives not packed or marked as required by DOTn 49 CFR, Parts 100-185 as listed in rule 1301:7-7-80 of the Administrative Code.
    Exception: Gelatin dynamite.
Persons in charge of magazines, blasting, fireworks exhibition or pyrotechnic special effect operations shall not be under the influence of alcohol or drugs that impair sensory or motor skills, shall be not less than 21 years of age and shall demonstrate knowledge of all safety precautions related to the storage, handling or use of explosives, explosive materials or fireworks.
The fire code official is authorized to require operations permitted under the provisions of paragraph (A)(2)(5601.2) of this rule to be supervised at any time by the fire code official in order to determine compliance with all safety and fire regulations.
Whenever a new explosive material storage or manufacturing site is established, including a temporary job site, the local law enforcement agency, fire department and local emergency planning committee shall be notified 48 hours in advance, not including Saturdays, Sundays and holidays, of the type, quantity and location of explosive materials at the site.
The fire code official is authorized to remove or cause to be removed or disposed of in an approved manner, at the expense of the owner, explosives, explosive materials offered or exposed for sale, stored, possessed or used in violation of this rule. The fire code official may seize fireworks in accordance with division (B) of section 3743.68 of the Revised Code.
The authority seizing any fireworks shall notify the state fire marshal not more than three days following the date of the seizure and shall state the reason for the seizure, as well as the quantity, type, and location of the fireworks. Any fireworks seized pursuant to division (B) of section 3743.68 of the Revised Code shall be made in accordance with statutory and constitutional provisions governing searches and seizures by law enforcement officers. The state fire marshal's or certified fire safety inspector's office shall keep the seized fireworks pending the time they are no longer needed as evidence. A sample of the seized fireworks is sufficient for evidentiary purposes. The remainder of the seized fireworks may be disposed of pursuant to an order from a court of competent jurisdiction after notice and a hearing. The state fire marshal's or certified fire safety inspector's office may impound seized fireworks at the site where they were seized and cause them to be secured and held pending the time they are no longer needed as evidence.
Fireworks disposed of by the state fire marshal or certified fire safety inspector or law enforcement officer shall be in a manner prescribed by the state fire marshal after final determination by the court or upon final termination of proceedings, whichever is later and the state fire marshal or that office is not liable for claims for the loss of or damages to the seized fireworks. If no proceedings are commenced pursuant to the rule, the state fire marshal may dispose of or order the disposal of the fireworks pursuant to Chapter 2981. of the Revised Code after all of the following:
  1. A random sampling of the fireworks has been taken.
  2. An inventory list has been taken of all types and kinds of fireworks.
  3. An analysis of the random sampling has been completed by the state fire marshal.
  4. Photographs have been taken of the fireworks to be destroyed.
  5. The state fire marshal has given written approval for the destruction of the fireworks at least ten days prior to the date of disposal.
  6. A disposal form shall be provided by the state fire marshal and such form shall be completed and state the specific total weight of the fireworks seized, the total weight of fireworks to be destroyed, and the total weight of the fireworks not to be destroyed.
The quantity of explosives and distances shall be in accordance with paragraphs (A)(8)(a)(5601.8.1) to (A)(8)(a)(iv)(5601.8.1.4) of this rule.
The quantity-distance (Q-D) tables in paragraphs (D)(5)(5604.5) and (E)(3)(5605.3) of this rule shall be used to provide the minimum separation distances from potential explosion sites as set forth in Tables 5601.8.1(1) to 5601.8.1(3) of this rule. The classification and the weight of the explosives are primary characteristics governing the use of these tables. The net explosive weight shall be determined in accordance with paragraphs (A)(8)(a)(i)(5601.8.1.1) to (A)(8)(a)(iv)(5601.8.1.4) of this rule.
APPLICATION OF SEPARATION DISTANCE (Q-D) TABLES—DIVISION 1.1, 1.2 AND 1.5 EXPLOSIVESa,b,c
ITEM MAGAZINE Q-D OPERATING
BUILDING
Q-D INHABITED
BUILDING
Q-D PUBLIC TRAFFIC
ROUTE
Q-D
Magazine Table 5604.5.2(1)
of this rule
IMD Table 5605.3
of this rule
ILD
or IPD
Table 5604.5.2(1)
of this rule
IBD Table 5604.5.2(1)
of this rule
PTR
Operating
building
Table 5604.5.2(1)
of this rule
ILD
or IPD
Table 5605.3
of this rule
ILD
or IPD
Table 5604.5.2(1)
of this rule
IBD Table 5604.5.2(1)
of this rule
PTR
Inhabited
building
Table 5604.5.2(1)
of this rule
IBD Table 5604.5.2(1)
of this rule
IBD Not
applicable
Not
applicable
Not
applicable
Not
applicable
Public traffic route Table 5604.5.2(1)
of this rule
PTR Table 5604.5.2(1)
of this rule
PTR Not
applicable
Not
applicable
Not
applicable
Not
applicable
For SI: 1 foot = 304.8 mm.
  1. The minimum separation distance (D0) shall be 60 feet. Where a building or magazine containing explosives is barricaded, the minimum distance shall be 30 feet.
  2. Linear interpolation between tabular values in the referenced Q-D tables shall not be allowed. Nonlinear interpolation of the values shall be allowed subject to an approved technical opinion and report prepared in accordance with paragraph (D)(7)(b)(104.7.2) of rule 1301:7-7-01 of the Administrative Code.
  3. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
APPLICATION OF SEPARATION DISTANCE (Q-D) TABLES—DIVISION 1.3 EXPLOSIVESa,b,c
ITEM MAGAZINE Q-D OPERATING
BUILDING
Q-D INHABITED
BUILDING
Q-D PUBLIC TRAFFIC
ROUTE
Q-D
Magazine Table 5604.5.2(2)
of this rule
IMD Table 5604.5.2(2)
of this rule
ILD
or IPD
Table 5604.5.2(2)
of this rule
IBD Table 5604.5.2(2)
of this rule
PTR
Operating
building
Table 5604.5.2(2)
of this rule
ILD
or IPD
Table 5604.5.2(2)
of this rule
ILD
or IPD
Table 5604.5.2(2)
of this rule
IBD Table 5604.5.2(2)
of this rule
PTR
Inhabited
building
Table 5604.5.2(2)
of this rule
IBD Table 5604.5.2(2)
of this rule
IBD Not
applicable
Not
applicable
Not
applicable
Not
applicable
Public traffic
route
Table 5604.5.2(2)
of this rule
PTR Table 5604.5.2(2)
of this rule
PTR Not
applicable
Not
applicable
Not
applicable
Not
applicable
For SI: 1 foot = 304.8 mm.
  1. The minimum separation distance (D0) shall be not less than 50 feet.
  2. Linear interpolation between tabular values in the referenced Q-D tables shall not be allowed.
  3. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
APPLICATION OF SEPARATION DISTANCE (Q-D) TABLES—DIVISION 1.4 EXPLOSIVESa,b,c,d
ITEM MAGAZINE Q-D OPERATING
BUILDING
Q-D INHABITED
BUILDING
Q-D PUBLIC TRAFFIC
ROUTE
Q-D
Magazine Table 5604.5.2(3)
of this rule
IMD Table 5604.5.2(3)
of this rule
ILD
or IPD
Table 5604.5.2(3)
of this rule
IBD Table 5604.5.2(3)
of this rule
PTR
Operating
building
Table 5604.5.2(3)
of this rule
ILD
or IPD
Table 5604.5.2(3)
of this rule
ILD
or IPD
Table 5604.5.2(3)
of this rule
IBD Table 5604.5.2(3)
of this rule
PTR
Inhabited
building
Table 5604.5.2(3)
of this rule
IBD Table 5604.5.2(3)
of this rule
IBD Not
applicable
Not
applicable
Not
applicable
Not
applicable
Public traffic
route
Table 5604.5.2(3)
of this rule
PTR Table 5604.5.2(3)
of this rule
PTR Not
applicable
Not
applicable
Not
applicable
Not
applicable
For SI: 1 foot = 304.8 mm.
  1. The minimum separation distance (D0) shall be not less than 50 feet.
  2. Linear interpolation between tabular values in the referenced (Q-D) table shall not be allowed.
  3. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
  4. This table shall not apply to consumer fireworks, 1.4G.
The total net explosive weight of massdetonating explosives (Division 1.1, 1.2 or 1.5) shall be used. See Table 5604.5.2(1) or Table 5605.3 of this rule as appropriate.
Exception: Where the TNT equivalence of the explosive material has been determined, the equivalence is allowed to be used to establish the net explosive weight.
Nonmass detonating explosives (excluding Division 1.4) shall be as follows:
  1. Division 1.3 propellants. The total weight of the propellants alone shall be the net explosive weight. The net weight of propellant shall be used. See Table 5604.5.2(2) of this rule.
  2. Combinations of bulk metal powder and pyrotechnic compositions. The sum of the net weights of metal powders and pyrotechnic compositions in the containers shall be the net explosive weight. See Table 5604.5.2(2) of this rule.
Combination of mass-detonating and nonmass-detonating explosives (excluding Division 1.4) shall be as follows:
  1. Where Division 1.1 and 1.2 explosives are located in the same site, determine the distance for the total quantity considered first as 1.1 and then as 1.2. The required distance is the greater of the two. Where the Division 1.1 requirements are controlling and the TNT equivalence of the 1.2 is known, the TNT equivalent weight of the 1.2 items shall be allowed to be added to the total explosive weight of Division 1.1 items to determine the net explosive weight for Division 1.1 distance determination. See Table 5604.5.2(2) or Table 5605.3 of this rule as appropriate.
  2. Where Division 1.1 and 1.3 explosives are located in the same site, determine the distances for the total quantity considered first as 1.1 and then as 1.3. The required distance is the greater of the two. Where the Division 1.1 requirements are controlling and the TNT equivalence of the 1.3 is known, the TNT equivalent weight of the 1.3 items shall be allowed to be added to the total explosive weight of Division 1.1 items to determine the net explosive weight for Division 1.1 distance determination. See Table 5604.5.2(1), 5604.5.2(2) or 5605.3 of this rule, as appropriate.
  3. Where Division 1.1, 1.2 and 1.3 explosives are located in the same site, determine the distances for the total quantity considered first as 1.1, next as 1.2 and finally as 1.3. The required distance is the greatest of the three. As allowed by paragraphs (A)(8)(a)(iii)(a) and (A)(8)(a)(iii)(b) above of this rule, TNT equivalent weights for 1.2 and 1.3 items are allowed to be used to determine the net weight of explosives for Division 1.1 distance determination. Table 5604.5.2(1) or 5605.3 of this rule shall be used where TNT equivalency is used to establish the net explosive weight.
  4. For composite pyrotechnic items Division 1.1 and Division 1.3, the sum of the net weights of the pyrotechnic composition and the explosives involved shall be used. See Tables 5604.5.2(1) and 5604.5.2(2) of this rule.
For Division 1.4 explosives the total weight of the explosive material alone is the net weight. The net weight of the explosive material shall be used.
The following terms are defined in rule 1301:7-7-02 of the Administrative Code.
In accordance with section 3743.75 of the Revised Code, the following terms, only as used in paragraph (P)(10)(5616.10), have the following exclusive meanings:
"Particular location." A licensed premises and, regardless of when approved, any storage location approved in accordance with section 3743.04 or 3743.17 of the Revised Code and this rule.
"Person." Any person or entity, in whatever form or name, that acquires possession of a manufacturer or wholesaler of fireworks license issued pursuant to this rule by transfer of possession of license, whether that transfer occurs by purchase, assignment, inheritance, bequest, stock transfer, or any other type of transfer, on the condition that the transfer is in accordance with division (D) of section 3743.04 of the Revised Code or division (D) of section 3743.17 of the Revised Code and is approved by the state fire marshal.
Records of the receipt, handling, use or disposal of explosive materials, and reports of any accidents, thefts or unauthorized activities involving explosive materials shall conform to the requirements of this paragraph. Records relating to the manufacturing, sale, transportation, shipping, storage and possession of fireworks shall be created, maintained and disposed of in accordance with the Revised Code and this rule.
The permittee shall maintain a record of all transactions involving receipt, removal, use or disposal of explosive materials. Such records shall be maintained for a period of 5 years.
Exception: Where only Division 1.4G (consumer fireworks) are handled, records need only be maintained for a period of three years.
The loss, theft or unauthorized removal of explosive materials from a magazine or permitted facility shall be reported to the fire code official, local law enforcement authorities, and the U.S. Department of Treasury, Bureau of Alcohol, Tobacco, Firearms and Explosives within 24 hours.
Exception: Loss of Division 1.4G (consumer fireworks) need not be reported to the Bureau of Alcohol, Tobacco, Firearms and Explosives
Manufacturers, wholesalers, shippers and exhibitors shall report any theft or loss of any fireworks to the local law enforcement agency within twenty-four hours after the discovery of the theft or loss and shall send a copy of the report prepared by the local law enforcement agency to the state fire marshal. If such report is unavailable, the manufacturer, wholesaler, shipper or exhibitor shall notify the state fire marshal of the investigating law enforcement agency. In the event of such theft or loss of any fireworks or pyrotechnic devices, the local fire code official shall cooperate with the state fire marshal in conducting a joint investigation of the circumstances.
Accidents involving the use of explosives, explosive materials and fireworks that result in injuries or property damage shall be reported to the fire code official immediately.
The local fire code official shall immediately make a report to the state fire marshal when any fireworks related fire, explosion, unauthorized discharge, personal injury, or other significant fireworks incident occurs, including all fires, explosions, personal injuries received or resulting from fireworks at a manufacturing plant, wholesale facility, from a shipment of fireworks in transit, or from fireworks at an exhibition. The report shall provide the location where the fire, explosion, or injury occurred and the name, address and telephone number of any person injured as a result when such information is available. The scene must be held until released by the state fire marshal.
The licensed exhibitor of fireworks or blaster in charge shall keep a record of all aerial shells that fail to fire or charges that fail to detonate.
Manufacturers of explosive materials and fireworks shall maintain records of chemicals, chemical compounds and mixtures required by DOL 29 CFR, Part 1910.1200 as listed in rule 1301:7-7-80 of the Administrative Code, and paragraph (G)(407) of rule 1301:7-7-04 of the Administrative Code.
Current safety rules covering the operation of magazines, as described in paragraph (D)(7)(5604.7) of this rule, shall be posted on the interior of the magazine in a visible location.
Storage of explosives and explosive materials, small arms ammunition, small arms primers, propellant-actuated cartridges and smokeless propellants in magazines shall comply with the provisions of this paragraph.
Explosives and explosive materials, and Division 1.3G fireworks shall be stored in magazines constructed, located, operated and maintained in accordance with the provisions of paragraph (D)(5604) of this rule and NFPA 495 or NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
Exceptions:
  1. Storage of fireworks at display sites in accordance with paragraph (J)(5610) of this rule and NFPA 1123 or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
  2. Portable or mobile magazines not exceeding 120 square feet (11 m2) in area shall not be required to comply with the requirements of the building code as listed in rule 1301:7-7-80 of the Administrative Code.
The storage of explosives and explosive materials in magazines shall comply with Table 5604.3 of this rule.
STORAGE AMOUNTS AND MAGAZINE REQUIREMENTS FOR EXPLOSIVES, EXPLOSIVE MATERIALS AND FIREWORKS, 1.3G MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA
NEW UN/
DOTn
DIVISION
OLD DOTn
CLASS
ATF/OSHA
class
INDOORa (pounds) OUTDOOR
(pounds)
MAGAZINE TYPE REQUIRED
Unprotected Cabinet Sprinklers Sprinklers &
cabinet
1 2 3 4 5
1.1b A High 0 0 1 2 1 X X X
1.2 A High 0 0 1 2 1 X X X
1.2 B Low 0 0 1 1 1 X X X X
1.3 B Low 0 0 5 10 1 X X X X
1.4c B Low 0 0 50 100 1 X X X X
1.5 C Low 0 0 1 2 1 X X X X
1.5 Blasting
Agent
Blasting
Agent
0 0 1 2 1 X X X X X
1.6 Not applicable Not applicable 0 0 1 2 1 X X X X X
For SI: 1 pound = 0.454 kg, 1 pound per gallon = 0.12 kg per liter, 1 ounce = 28.35 g.
  1. A factor of 10 pounds per gallon shall be used for converting pounds (solid) to gallons (liquid) in accordance with paragraph (C)(1)(b)(5003.1.2) of rule 1301:7-7-50 of the Administrative Code.
  2. Black powder shall be stored in a Type 1, 2, 3 or 4 magazine as provided for in paragraph (D)(3)(a)(5604.3.1) of this rule.
  3. This table shall not apply to consumer fireworks, 1.4G.
Explosive materials classified as Division 1.1 or 1.2 or formerly classified as Class A by the U.S. Department of Transportation shall be stored in Type 1, 2 or 3 magazines.
Exceptions:
  1. Black powder shall be stored in a Type 1, 2, 3 or 4 magazine.
  2. Cap-sensitive explosive material that is demonstrated not to be bullet sensitive shall be stored in a Type 1, 2, 3, 4 or 5 magazine.
Explosive materials that are not cap sensitive shall be stored in a Type 1, 2, 3, 4 or 5 magazine.
For quantity and distance purposes, detonating cord of 50 grains per foot shall be calculated as equivalent to 8 pounds (4 kg) of high explosives per 1,000 feet (305 m). Heavier or lighter core loads shall be rated proportionally.
Detonators shall be stored in a separate magazine for blasting supplies and shall not be stored in a magazine with other explosive materials.
The use of magazines for storage of explosives and explosive materials shall comply with paragraphs (D)(5)(a)(5604.5.1) to (D)(5)(c)(iii)(5604.5.3.3) of this rule.
The use of indoor magazines for storage of explosives and explosive materials shall comply with the requirements of paragraphs (D)(5)(a)(i)(5604.5.1.1) to (D)(5)(a)(vii)(5604.5.1.7) of this rule.
The use of indoor magazines for storage of explosives and explosive materials shall be limited to occupancies in Group F, H, M or S, and research and development laboratories.
Indoor magazines shall comply with the following construction requirements:
  1. Construction shall be fire resistant and theft resistant.
  2. Exterior shall be painted red.
  3. Base shall be fitted with wheels, casters or rollers to facilitate removal from the building in an emergency.
  4. Lid or door shall be marked with conspicuous white lettering not less than 3 inches (76 mm) high and minimum 1/2 inch (12.7 mm) stroke, reading "EXPLOSIVES-KEEP FIRE AWAY".
  5. The least horizontal dimension shall not exceed the clear width of the entrance door.
Not more than 50 pounds (23 kg) of explosives or explosive materials shall be stored within an indoor magazine.
Exception: Day boxes used for the storage of in-process material in accordance with paragraph (E)(6)(d)(i)(5605.6.4.1) of this rule.
Indoor magazines shall not be used within buildings containing Group R occupancies.
Indoor magazines shall be located within 10 feet (3048 mm) of an entrance and only on floors at or having ramp access to the exterior grade level.
Not more than two indoor magazines shall be located in the same building. Where two such magazines are located in the same building, one magazine shall be used solely for the storage of not more than 5,000 detonators.
Where two magazines are located in the same building, they shall be separated by a distance of not less than 10 feet (3048 mm).
Outdoor magazines other than Type 3 shall be located so as to comply with Table 5604.5.2(2) or Table 5604.5.2(3) of this rule as set forth in Tables 5601.8.1(1) to 5601.8.1(3) of this rule. Where a magazine or group of magazines, as described in paragraph (D)(5)(b)(ii)(5604.5.2.2) of this rule, contains different classes of explosive materials, and Division 1.1 materials are present, the required separations for the magazine or magazine group as a whole shall comply with Table 5604.5.2(2) of this rule.
AMERICAN TABLE OF DISTANCES FOR STORAGE OF EXPLOSIVES AS APPROVED BY THE INSTITUTE OF MAKERS OF EXPLOSIVES AND REVISED JUNE 1991a
QUANTITY OF EXPLOSIVE
MATERIALSc
DISTANCES IN FEET
Inhabited buildings Public highways with traffic
volume less than 3,000
vehicles per day
Public highways with traffic
volume greater than 3,000
vehicles per day and
passenger railways
Separation of magazinesd
Pounds over Pounds not
over
Barricaded Unbarricaded Barricaded Unbarricaded Barricaded Unbarricaded Barricaded Unbarricaded
0 5 70 140 30 60 51 102 6 12
5 10 90 180 35 70 64 128 8 16
10 20 110 220 45 90 81 162 10 20
20 30 125 250 50 100 93 186 11 22
30 40 140 280 55 110 103 206 12 24
40 50 150 300 60 120 110 220 14 28
50 75 170 340 70 140 127 254 15 30
75 100 190 380 75 150 139 278 16 32
100 125 200 400 80 160 150 300 18 36
125 150 215 430 85 170 159 318 19 38
150 200 235 470 95 190 175 350 21 42
200 250 255 510 105 210 189 378 23 46
250 300 270 540 110 220 201 402 24 48
300 400 295 590 120 240 221 442 27 54
400 500 320 640 130 260 238 476 29 58
500 600 340 680 135 270 253 506 31 62
600 700 355 710 145 290 266 532 32 64
700 800 375 750 150 300 278 556 33 66
800 900 390 780 155 310 289 578 35 70
900 1,000 400 800 160 320 300 600 36 72
1,000 1,200 425 850 165 560 318 636 39 78
1,200 1,400 450 900 170 340 336 672 41 82
1,400 1,600 470 940 175 350 351 702 43 86
1,600 1,800 490 980 180 360 366 732 44 88
1,800 2,000 505 1,010 185 370 378 756 45 90
2,000 2,500 545 1,090 190 380 408 816 49 98
2,500 3,000 580 1,160 195 390 432 864 52 104
3,000 4,000 635 1,270 210 420 474 948 58 116
4,000 5,000 685 1,370 225 450 513 1,026 61 122
5,000 6,000 730 1,460 235 470 546 1,092 65 130
6,000 7,000 770 1,540 245 490 573 1,146 68 136
7,000 8,000 800 1,600 250 500 600 1,200 72 144
8,000 9,000 835 1,670 255 510 624 1,248 75 150
9,000 10,000 865 1,730 260 520 645 1,290 78 156
10,000 12,000 875 1,750 270 540 687 1,374 82 164
12,000 14,000 885 1,770 275 550 723 1,446 87 174
14,000 16,000 900 1,800 280 560 756 1,512 90 180
16,000 18,000 940 1,880 285 570 786 1,572 94 188
18,000 20,000 975 1,950 290 580 813 1,626 98 196
20,000 25,000 1,055 2,000 315 630 876 1,752 105 210
25,000 30,000 1,130 2,000 340 680 933 1,866 112 224
30,000 35,000 1,205 2,000 360 720 981 1,962 119 238
35,000 40,000 1,275 2,000 380 760 1,026 2,000 124 248
40,000 45,000 1,340 2,000 400 800 1,068 2,000 129 258
45,000 50,000 1,400 2,000 420 840 1,104 2,000 135 270
50,000 55,000 1,460 2,000 440 880 1,140 2,000 140 280
55,000 60,000 1,515 2,000 455 910 1,173 2,000 145 290
60,000 65,000 1,565 2,000 470 940 1,206 2,000 150 300
65,000 70,000 1,610 2,000 485 970 1,236 2,000 155 310
70,000 75,000 1,655 2,000 500 1,000 1,263 2,000 160 320
75,000 80,000 1,695 2,000 510 1,020 1,293 2,000 165 560
80,000 85,000 1,730 2,000 520 1,040 1,317 2,000 170 340
85,000 90,000 1,760 2,000 530 1,060 1,344 2,000 175 350
90,000 95,000 1,790 2,000 540 1,080 1,368 2,000 180 360
95,000 100,000 1,815 2,000 545 1,090 1,392 2,000 185 370
100,000 110,000 1,835 2,000 550 1,100 1,437 2,000 195 390
110,000 120,000 1,855 2,000 555 1,110 1,479 2,000 205 410
120,000 130,000 1,875 2,000 560 1,120 1,521 2,000 215 430
130,000 140,000 1,890 2,000 565 1,130 1,557 2,000 225 450
140,000 150,000 1,900 2,000 570 1,140 1,593 2,000 235 470
150,000 160,000 1,935 2,000 580 1,160 1,629 2,000 245 490
160,000 170,000 1,965 2,000 590 1,180 1,662 2,000 255 510
170,000 180,000 1,990 2,000 600 1,200 1,695 2,000 265 530
180,000 190,000 2,010 2,010 605 1,210 1,725 2,000 275 550
190,000 200,000 2,030 2,030 610 1,220 1,755 2,000 285 570
200,000 210,000 2,055 2,055 620 1,240 1,782 2,000 295 590
210,000 230,000 2,100 2,100 635 1,270 1,836 2,000 315 630
230,000 250,000 2,155 2,155 650 1,300 1,890 2,000 335 670
250,000 275,000 2,215 2,215 670 1,340 1,950 2,000 360 720
275,000 300,000b 2,275 2,275 690 1,380 2,000 2,000 385 770
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
  1. This table applies only to the manufacture and permanent storage of commercial explosive materials. It is not applicable to transportation of explosives or any handling or temporary storage necessary or incident thereto. It is not intended to apply to bombs, projectiles or other heavily encased explosives.
  2. Storage in excess of 300,000 pounds of explosive materials in one magazine is not allowed.
  3. Where a manufacturing building on an explosive materials plant site is designed to contain explosive materials, such building shall be located with respect to its proximity to inhabited buildings, public highways and passenger railways based on the maximum quantity of explosive materials permitted to be in the building at one time.
  4. Where two or more storage magazines are located on the same property, each magazine shall comply with the minimum distances specified from inhabited buildings, railways and highways, and, in addition, they should be separated from each other by not less than the distances shown for separation of magazines, except that the quantity of explosives in detonator magazines shall govern in regard to the spacing of said detonator magazines from magazines containing other explosive materials. Where any two or more magazines are separated from each other by less than the specified separation of magazines distances, then two or more such magazines, as a group, shall be considered as one magazine, and the total quantity of explosive materials stored in such group shall be treated as if stored in a single magazine located on the site of any magazine in the group and shall comply with the minimum distances specified from other magazines, inhabited buildings, railways and highways.
TABLE OF DISTANCES (Q-D) FOR BUILDINGS AND MAGAZINES CONTAINING EXPLOSIVES—DIVISION 1.3 MASS-FIRE HAZARDa, b, c
QUANTITY OF DIVISION 1.3 EXPLOSIVES
(NET EXPLOSIVES WEIGHT)
DISTANCES IN FEET
Pounds over Pounds not over Inhabited Building
Distance (IBD)
Distance to Public Traffic
Route (PTR)
Intermagazine Distance
(IMD)
Intraline Distance (ILD)
or Intraplant Distance
(IPD)
0 1,000 75 75 50 50
1,000 5,000 115 115 75 75
5,000 10,000 150 150 100 100
10,000 20,000 190 190 125 125
20,000 30,000 215 215 145 145
30,000 40,000 235 235 155 155
40,000 50,000 250 250 165 165
50,000 60,000 260 260 175 175
60,000 70,000 270 270 185 185
70,000 80,000 280 280 190 190
80,000 90,000 295 295 195 195
90,000 100,000 300 300 200 200
100,000 200,000 375 375 250 250
200,000 300,000 450 450 300 300
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg
  1. Black powder, where stored in magazines, is defined as low explosive by the Bureau of Alcohol, Tobacco, Firearms and Explosives (BATF).
  2. For quantities less than 1,000 pounds, the required distances are those specified for 1,000 pounds. The use of lesser distances is allowed where supported by approved test data and/or analysis.
  3. Linear interpolation of explosive quantities between table entries is allowed.
TABLE OF DISTANCES (Q-D) FOR BUILDINGS AND MAGAZINES CONTAINING EXPLOSIVES—DIVISION 1.4c
QUANTITY OF DIVISION 1.4 EXPLOSIVES
(NET EXPLOSIVES WEIGHT)
DISTANCES IN FEET
Pounds over Pounds not over Inhabited Building
Distance (IBD)
Distance to Public
Traffic Route (PTR)
Intermagazine
Distancea, b (IMD)
Intraline Distance (ILD)
or Intraplant Distancea
(IPD)
50 Not Limited 100 100 50 50
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
  1. A separation distance of 100 feet is required for buildings other than Type I or Type II construction as defined in the building code listed in rule 1301:7-7-80 of the Administrative Code.
  2. For earth-covered magazines, specific separation is not required.
    1. Earth cover material used for magazines shall be relatively cohesive. Solid or wet clay and similar types of soil are too cohesive and shall not be used. Soil shall be free from unsanitary organic matter, trash, debris and stones heavier than 10 pounds or larger than 6 inches in diameter. Compaction and surface preparation shall be provided, as necessary, to maintain structural integrity and avoid erosion. Where cohesive material cannot be used, as in sandy soil, the earth cover over magazines shall be finished with a suitable material to ensure structural integrity.
    2. The earth fill or earth cover between earth-covered magazines shall be either solid or sloped, in accordance with the requirements of other construction features, but not less than 2 feet of earth cover shall be maintained over the top of each magazines. To reduce erosion and facilitate maintenance operations, the cover shall have a slope of 2 horizontal to 1 vertical.
  3. Restricted to articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpacked articles used in process operations that do not propagate a detonation or deflagration between articles. This table shall not apply to consumer fireworks, 1.4G.
Where two or more storage magazines are located on the same property, each magazine shall comply with the minimum distances specified from inhabited buildings, public transportation routes and operating buildings. Magazines shall be separated from each other by not less than the intermagazine distances (IMD) shown for the separation of magazines.
Where two or more magazines are separated from each other by less than the intermagazine distances (IMD), such magazines as a group shall be considered as one magazine and the total quantity of explosive materials stored in the group shall be treated as if stored in a single magazine. The location of the group of magazines shall comply with the intermagazine distances (IMD) specified from other magazines or magazine groups, inhabited buildings (IBD), public transportation routes (PTR) and operating buildings (ILD or IPD) as required.
Type 3 magazines shall comply with paragraphs (D)(5)(c)(i)(5604.5.3.1) to (D)(5)(c)(iii)(5604.5.3.3) of this rule.
Wherever practicable, Type 3 magazines shall be located away from neighboring inhabited buildings, railways, highways and other magazines in accordance with Table 5604.5.2(2) or 5604.5.2(3) of this rule as applicable.
Type 3 magazines shall be attended when explosive materials are stored within. Explosive materials shall be removed to appropriate storage magazines for unattended storage at the end of the work day.
Not more than two Type 3 magazines shall be located at the same blasting site. Where two Type 3 magazines are located at the same blasting site, one magazine shall be used solely for the storage of detonators.
Magazines shall be constructed in accordance with paragraphs (D)(6)(a)(5604.6.1) to (D)(6)(e)(ii)(5604.6.5.2) of this rule.
The ground around a magazine shall be graded so that water drains away from the magazine.
Magazines requiring heat shall be heated as prescribed in NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code by either hot water radiant heating within the magazine or by indirect warm air heating.
Where lighting is necessary within a magazine, electric safety flashlights or electric safety lanterns shall be used, except as provided in NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
In other than Type 5 magazines, there shall not be exposed ferrous metal on the interior of a magazine containing packages of explosives.
Property upon which Type 1 magazines and outdoor magazines of Types 2, 4 and 5 are located shall be posted with signs stating: "EXPLOSIVES-KEEP OFF." These signs shall be of contrasting colors with a minimum letter height of 3 inches (76 mm) with a minimum brush stroke of 1/2 inch (12.7 mm). The signs shall be located to minimize the possibility of a bullet shot at the sign hitting the magazine.
At the entrance to explosive material manufacturing and storage sites, all access roads shall be posted with the following warning sign or other approved sign:
"DANGER!
NEVER FIGHT EXPLOSIVE FIRES.
EXPLOSIVES ARE STORED ON THIS SITE
CALL ___________"
The sign shall be weather-resistant with a reflective surface and have lettering not less than 2 inches (51 mm) high.
Type 5 magazines containing Division 1.5 blasting agents shall be prominently placarded as required during transportation by DOTn 49 CFR, Part 172 and DOTy 27 CFR, Part 55 as listed in rule 1301:7-7-80 of the Administrative Code.
Magazines shall be operated in accordance with paragraphs (D)(7)(a)(5604.7.1) to (D)(7)(i) (5604.7.9) of this rule.
Magazines shall be kept locked in the manner prescribed in NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code at all times except during placement or removal of explosives or inspection.
Smoking, matches, flame-producing devices, open flames, firearms and firearms cartridges shall not be allowed inside of or within 50 feet (15 240 mm) of magazines.
The area located around a magazine shall be kept clear of brush, dried grass, leaves, trash, debris and similar combustible materials for a distance of 25 feet (7620 mm).
Combustible materials shall not be stored within 50 feet (15 240 mm) of magazines.
Containers of explosive materials, except fiberboard containers, and packages of damaged or deteriorated explosive materials or fireworks shall not be unpacked or repacked inside or within 50 feet (15 240 mm) of a magazine or in close proximity to other explosive materials.
Packages of explosive materials that have been opened shall be closed before being placed in a magazine.
Tools used for the opening and closing of packages of explosive materials, other than metal slitters for opening paper, plastic or fiberboard containers, shall be made of nonsparking materials.
Empty containers and paper and fiber packaging materials that previously contained explosive materials shall be disposed of or reused in an approved manner.
Metal tools, other than nonferrous transfer conveyors and ferrous metal conveyor stands protected by a coat of paint, shall not be stored in a magazine containing explosive materials or detonators.
Magazines shall be used exclusively for the storage of explosive materials, blasting materials and blasting accessories.
Corresponding grades and brands of explosive materials shall be stored together and in such a manner that the grade and brand marks are visible. Stocks shall be stored so as to be easily counted and checked. Packages of explosive materials shall be stacked in a stable manner not exceeding 8 feet (2438 mm) in height.
When explosive material is removed from a magazine for use, the oldest usable stocks shall be removed first.
Maintenance of magazines shall comply with paragraphs (D)(8)(a)(5604.8.1) to (D)(8)(c) (5604.8.3) of this rule.
Magazine floors shall be regularly swept and be kept clean, dry and free of grit, paper, empty packages and rubbish. Brooms and other cleaning utensils shall not have any spark-producing metal parts. Sweepings from magazine floors shall be disposed of in accordance with the manufacturers' approved instructions.
Explosive materials shall be removed from the magazine before making repairs to the interior of a magazine. Explosive materials shall be removed from the magazine before making repairs to the exterior of the magazine where there is a possibility of causing a fire. Explosive materials removed from a magazine under repair shall either be placed in another magazine or placed a safe distance from the magazine, where they shall be properly guarded and protected until repairs have been completed. Upon completion of repairs, the explosive materials shall be promptly returned to the magazine. Floors shall be cleaned before and after repairs.
Magazine floors stained with liquid shall be dealt with in accordance with instructions obtained from the manufacturer of the explosive material stored in the magazine.
Magazines containing explosive materials shall be opened and inspected by the permit holder at maximum intervals of seven days. The inspection shall determine whether there has been an unauthorized or attempted entry into a magazine or an unauthorized removal of a magazine or its contents. The permit holder shall document said inspections including the date of inspection, name of person conducting inspection and a verification of the inventory. The permit holder shall maintain such records for a minimum of one year and provide such documentation to the state fire marshal upon request.
If in the state fire marshal's discretion, the state fire marshal determines that conditions affecting the security of explosives exist that require more frequent inventory inspections, the permit holder shall conduct such inspections on a daily basis unless otherwise notified by the state fire marshal for the duration of the prevailing conditions. Such conditions would exist when the United States department of homeland security threat advisory system, or a similar system of the United States government or the state of Ohio, reaches a high or severe level or the governor of Ohio declares a state of emergency pursuant to section 5502.21 of the Revised Code or the governor otherwise activates the Ohio militia in accordance with Ohio Constitution Article 9, Section 4.
Explosive materials shall be disposed of in accordance with paragraphs (D)(10)(a)(5604.10.1) to (D)(10)(g)(5604.10.7) of this rule.
The fire code official shall be notified immediately where deteriorated or leaking explosive materials are determined to be dangerous or unstable and in need of disposal.
Where an explosive material has deteriorated to an extent that it is in an unstable or dangerous condition, or when a liquid has leaked from an explosive material, the person in possession of such material shall immediately contact the material's manufacturer to obtain disposal and handling instructions.
The work of destroying explosive materials shall be directed by persons experienced in the destruction of explosive materials.
Explosive materials and fireworks recovered from blasting or display misfires shall be placed in a magazine until an experienced person has determined the proper method for disposal.
Sites for the destruction of explosive materials and fireworks shall be approved and located at the maximum practicable safe distance from inhabited buildings, public highways, operating buildings and all other exposures to ensure keeping air blast and ground vibration to a minimum. The location of disposal sites shall not be closer to magazines, inhabited buildings, railways, highways and other rights-of-way than is allowed by Tables 5604.5.2(1), 5604.5.2(2) and 5604.5.2(3) of this rule. Where possible, barricades shall be utilized between the destruction site and inhabited buildings. Areas where explosives are detonated or burned shall be posted with adequate warning signs.
Unless an approved burning site has been thoroughly saturated with water and has passed a safety inspection, 48 hours shall elapse between the completion of a burn and the placement of scrap explosive materials for a subsequent burn.
Once an explosive burn operation has been started, personnel shall relocate to a safe location where adequate protection from air blast and flying debris is provided. Personnel shall not return to the burn area until the person in charge has inspected the burn site and determined that it is safe for personnel to return.
The manufacture, assembly and testing of explosives, ammunition, blasting agents and fireworks shall comply with the requirements of this paragraph and NFPA 495 or NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
Exceptions:
  1. The hand loading of small arms ammunition prepared for personal use and not offered for resale.
  2. The mixing and loading of blasting agents at blasting sites in accordance with NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
  3. The use of binary explosives or plosophoric materials in blasting or pyrotechnic special effects applications in accordance with NFPA 495 or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
Emergency plans, emergency drills, employee training and hazard communication shall conform to the provisions of this paragraph and paragraphs (D)(404), (E)(405), (F)(406) and (G)(407) of rule 1301:7-7-04 of the Administrative Code.
Detailed hazardous materials management plans (HMMP) and hazardous materials inventory statements (HMIS) complying with the requirements of paragraph (G)(407) of rule 1301:7-7-04 of the Administrative Code shall be prepared and submitted to the local emergency planning committee, the fire code official and the local fire department.
A copy of the required HMMP and HMIS shall be maintained on site and furnished to the fire code official on request.
Workers who handle explosives or explosive charges or dispose of explosives shall be trained in the hazards of the materials and processes in which they are to be engaged and with the safety rules governing such materials and processes.
Approved emergency procedures shall be formulated for each plant and shall include personal instruction in any anticipated emergency. Personnel shall be made aware of an emergency warning signal.
Explosives manufacturing buildings and fireworks manufacturing buildings, including those where explosive charges are assembled, manufactured, prepared or loaded utilizing Division 1.1, 1.2, 1.3, 1.4 or 1.5 explosives, shall be separated from all other buildings, including magazines, within the confines of the manufacturing plant at a distance not less than those shown in Table 5605.3 or 5604.5.2(3) of this rule, as appropriate.
Exception: Fireworks manufacturing buildings separated in accordance with NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
The quantity of explosives in an operating building shall be the net weight of all the explosives contained therein. Distances shall be based on the hazard division requiring the greatest separation, unless the aggregate explosive weight is divided by approved walls or shields designed for that purpose. Where dividing a quantity of explosives into smaller stacks, a suitable barrier or adequate separation distance shall be provided to prevent propagation from one stack to another.
Where distance is used as the sole means of separation within a building, such distance shall be established by testing. Testing shall demonstrate that propagation between stacks will not result. Barriers provided to protect against explosive effects shall be designed and installed in accordance with approved standards.
MINIMUM INTRALINE (INTRAPLANT) SEPARATION DISTANCES (ILD OR IPD) BETWEEN BARRICADED OPERATING BUILDINGS CONTAINING EXPLOSIVES—DIVISION 1.1, 1.2 OR 1.5 MASS-EXPLOSION HAZARDa
NET EXPLOSIVE WEIGHT NET EXPLOSIVE WEIGHT
Pounds
over
Pounds
not over
Intraline Distance (ILD) or
Intraplant Distance (IPD) (feet)
Pounds
over
Pounds
not over
Intraline Distance (ILD) or
Intraplant Distance (IPD) (feet)
0 50 30 20,000 25,000 265
50 100 40 25,000 30,000 280
100 200 50 30,000 35,000 295
200 300 60 35,000 40,000 310
300 400 65 40,000 45,000 320
400 500 70 45,000 50,000 330
500 600 75 50,000 55,000 340
600 700 80 55,000 60,000 350
700 800 85 60,000 65,000 360
800 900 90 65,000 70,000 370
900 1,000 95 70,000 75,000 385
1,000 1,500 105 75,000 80,000 390
1,500 2,000 115 80,000 85,000 395
2,000 3,000 130 85,000 90,000 400
3,000 4,000 140 90,000 95,000 410
4,000 5,000 150 95,000 100,000 415
5,000 6,000 160 100,000 125,000 450
6,000 7,000 170 125,000 150,000 475
7,000 8,000 180 150,000 175,000 500
8,000 9,000 190 175,000 200,000 525
9,000 10,000 200 200,000 225,000 550
10,000 15,000 225 225,000 250,000 575
15,000 20,000 245 250,000 275,000 600
275,000 300,000 635
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
  1. Where a building or magazine containing explosives is not barricaded, the intraline distances shown in this table shall be doubled.
Where an operating building on an explosive materials plant site is designed to contain explosive materials, such a building shall be located away from inhabited buildings, public traffic routes and magazines in accordance with Table 5604.5.2(2) or 5604.5.2(3) of this rule as appropriate, based on the maximum quantity of explosive materials permitted to be in the building at one time (see paragraph (A)(8)(5601.8) of this rule).
Exception: Fireworks manufacturing buildings constructed and operated in accordance with NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
In addition to the requirements of paragraph (A)(8)(5601.8) of this rule to determine the net explosive weight for materials stored or used in operating buildings, quantities of explosive materials stored in magazines located at distances less than intraline distances from the operating building shall be added to the contents of the operating building to determine the net explosive weight for the operating building.
The storage of explosive materials located in indoor magazines in operating buildings shall be limited to a net explosive weight not to exceed 50 pounds (23 kg).
The storage of explosive materials in outdoor magazines located at less than intraline distances from operating buildings shall be limited to a net explosive weight not to exceed 50 pounds (23 kg).
The storage of explosive materials in outdoor magazines in quantities exceeding 50 pounds (23 kg) net explosive weight shall be limited to storage in outdoor magazines located not less than intraline distances from the operating building in accordance with paragraph (D)(5)(b)(5604.5.2) of this rule.
The aggregate quantity of explosive materials stored in any combination of indoor magazines or outdoor magazines located at less than the intraline distances from an operating building shall not exceed 50 pounds (23 kg).
Buildings or rooms that exceed the maximum allowable quantity per control area of explosive materials shall be operated in accordance with this paragraph and constructed in accordance with the requirements of the building code as listed in rule 1301:7-7-80 of the Administrative Code for Group H occupancies.
Exception: Fireworks manufacturing buildings constructed and operated in accordance with NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
Explosives dust shall not be exhausted to the atmosphere.
When collecting explosives dust, a wet collector system shall be used. Wetting agents shall be compatible with the explosives. Collector systems shall be interlocked with process power supplies so that the process cannot continue without the collector systems also operating.
Explosives dust shall be removed from the collection chamber as often as necessary to prevent overloading. The entire system shall be cleaned at a frequency that will eliminate hazardous concentrations of explosives dust in pipes, tubing and ducts.
Squirrel cage blowers shall not be used for exhausting hazardous fumes, vapors or gases. Only nonferrous fan blades shall be used for fans located within the ductwork and through which hazardous materials are exhausted. Motors shall be located outside the duct.
Work stations shall be separated by distance, barrier or other approved alternatives so that fire in one station will not ignite material in another work station. Where necessary, the operator shall be protected by a personnel shield located between the operator and the explosive device or explosive material being processed. This shield and its support shall be capable of withstanding a blast from the maximum amount of explosives allowed behind it.
Operations involving explosives shall comply with paragraphs (E)(6)(a)(5605.6.1) to (E)(6)(j)(5605.6.10) of this rule.
Where the type of material and processing warrants, mechanical operations involving explosives in excess of 1 pound (0.454 kg) shall be carried on at isolated stations or at intraplant distances, and machinery shall be controlled from remote locations behind barricades or at separations so that workers will be at a safe distance while machinery is operating.
The work area where the screening, grinding, blending and other processing of static-sensitive explosives or pyrotechnic materials is done shall be provided with approved static controls.
Bulk explosives shall be kept in approved, nonsparking containers when not being used or processed. Explosives shall not be stored or transported in open containers.
The quantity of explosives at any particular work station shall be limited to that posted on the load limit signs for the individual work station. The total quantity of explosives for multiple workstations shall not exceed that established by the intraplant distances in Table 5605.3 or 5604.5.2(3) of this rule, as appropriate.
Magazines used for storage in processing areas shall be in accordance with the requirements of paragraph (D)(5)(a)(5604.5.1) of this rule. Explosive materials shall be removed to appropriate storage magazines for unattended storage at the end of the work day. The contents of indoor magazines shall be added to the quantity of explosives contained at individual workstations and the total quantity of material stored, processed or used shall be utilized to establish the intraplant separation distances indicated by Table 5605.3 or 5604.5.2(3) of this rule, as appropriate.
Approved receptacles with covers shall be provided for each location for disposing of waste material and debris. These waste receptacles shall be emptied and cleaned as often as necessary but not less than once each day or at the end of each shift.
General safety rules and operating instructions governing the particular operation or process conducted at that location shall be available at each location.
The number of occupants in each process building and in each magazine shall not exceed the number necessary for proper conduct of production operations.
Not more than 500 pounds (227 kg) of pyrotechnic or explosive composition, including not more than 10 pounds (5 kg) of salute powder shall be allowed at one time in any process building or area. Compositions not in current use shall be kept in covered nonferrous containers.
Exception: Composition that has been loaded or pressed into tubes or other containers as consumer fireworks.
The maximum number of occupants and maximum weight of pyrotechnic and explosive composition permitted in each process building shall be posted in a conspicuous location in each process building or magazine.
Fireworks, explosives or explosive charges in explosive materials manufacturing, assembly or testing shall not be stored near any source of heat.
Exception: Approved drying or curing operations.
Maintenance and repair of explosives manufacturing facilities and areas shall comply with paragraph (D)(8)(5604.8) of this rule.
Detonation of explosive materials or ignition of fireworks for testing purposes shall be done only in isolated areas at sites where distance, protection from missiles, shrapnel or flyrock, and other safeguards provides protection against injury to personnel or damage to property.
Protective clothing and equipment shall be provided to protect persons engaged in the testing, ignition or detonation of explosive materials.
Where tests are being conducted or explosives are being detonated, only authorized persons shall be present. Areas where explosives are regularly or frequently detonated or burned shall be approved and posted with adequate warning signs. Warning devices shall be activated before burning or detonating explosives to alert persons approaching from any direction that they are approaching a danger zone.
Disposal of explosive materials waste from manufacturing, assembly or testing operations shall be in accordance with paragraph (D)(10)(5604.10) of this rule.
Indoor storage and display of black powder, smokeless propellants, small arms primers and small arms ammunition shall comply with this paragraph and NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Small arms ammunition shall not be stored together with Division 1.1, Division 1.2 or Division 1.3 explosives unless the storage facility is suitable for the storage of explosive materials.
Smokeless propellants shall be stored in approved shipping containers conforming to DOTn 49 CFR, Part 173 as listed in rule 1301:7-7-80 of the Administrative Code.
The bulk repackaging of smokeless propellants, black powder and small arms primers shall not be performed in retail establishments.
Damaged containers shall not be repackaged.
Exception: Approved repackaging of damaged containers of smokeless propellant into containers of the same type and size as the original container.
The storage of small arms ammunition components in Group R occupancies shall comply with paragraphs (F)(4)(a)(5606.4.1) to (F)(4)(c)(5606.4.3) of this rule.
Black powder for personal use in quantities not exceeding 20 pounds (9 kg) shall be stored in original containers in occupancies limited to Group R-3. Quantities exceeding 20 pounds (9 kg) shall not be stored in any Group R occupancy.
Smokeless propellants for personal use in quantities not exceeding 20 pounds (9 kg) shall be stored in original containers in occupancies limited to Group R-3. Smokeless propellants in quantities exceeding 20 pounds (9 kg) but not exceeding 50 pounds (23 kg) and kept in a wooden box or cabinet having walls of not less than 1 inch (25 mm) nominal thickness shall be allowed to be stored in occupancies limited to Group R-3. Quantities exceeding these amounts shall not be stored in any Group R occupancy.
Not more than 10,000 small arms primers shall be stored in occupancies limited to Group R-3.
The display and storage of small arms ammunition components in Group M occupancies shall comply with paragraphs (F)(5)(a)(5606.5.1) to (F)(5)(b)(iii)(5606.5.2.3) of this rule.
Display of small arms ammunition components in Group M occupancies shall comply with paragraphs (F)(5)(a)(i)(5606.5.1.1) to (F)(5)(a)(iii)(5606.5.1.3) of this rule.
Not more than 20 pounds (9 kg) of smokeless propellants, in containers of 1 pound (0.454 kg) or less capacity each, shall be displayed in Group M occupancies.
Not more than 1 pound (0.454 kg) of black powder shall be displayed in Group M occupancies.
Not more than 10,000 small arms primers shall be displayed in Group M occupancies.
Storage of small arms ammunition components shall comply with paragraphs (F)(5)(b)(i)(5606.5.2.1) to (F)(5)(b)(iii)(5606.5.2.3) of this rule.
Commercial stocks of smokeless propellants shall be stored as follows:
  1. Quantities exceeding 20 pounds (9 kg), but not exceeding 100 pounds (45 kg) shall be stored in portable wooden boxes having walls of not less than 1 inch (25 mm) nominal thickness.
  2. Quantities exceeding 100 pounds (45 kg), but not exceeding 800 pounds (363 kg), shall be stored in nonportable storage cabinets having walls not less than 1 inch (25 mm) nominal thickness. Not more than 400 pounds (182 kg) shall be stored in any one cabinet, and cabinets shall be separated by a distance of not less than 25 feet (7620 mm) or by a fire partition having a fire-resistance rating of not less than 1 hour.
  3. Storage of quantities exceeding 800 pounds (363 kg), but not exceeding 5,000 pounds (2270 kg) in a building shall comply with all of the following:
    1. The warehouse or storage room is unaccessible to unauthorized personnel.
    2. Smokeless propellant shall be stored in nonportable storage cabinets having wood walls not less than 1 inch (25 mm) nominal thickness and having shelves with not more than 3 feet (914 mm) of separation between shelves.
    3. Not more than 400 pounds (182 kg) is stored in any one cabinet.
    4. Cabinets shall be located against walls of the storage room or warehouse with not less than 40 feet (12 192 mm) between cabinets.
    5. The minimum required separation between cabinets shall be 20 feet (6096 mm) provided that barricades twice the height of the cabinets are attached to the wall, midway between each cabinet. The barricades must extend not less than 10 feet (3048 mm) outward, be firmly attached to the wall and be constructed of steel not less than 1/4 inch thick (6.4 mm), 2-inch (51 mm) nominal thickness wood, brick or concrete block.
    6. Smokeless propellant shall be separated from materials classified as combustible liquids, flammable liquids, flammable solids or oxidizing materials by a distance of 25 feet (7620 mm) or by a fire partition having a fire-resistance rating of 1 hour.
    7. The building shall be equipped throughout with an automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
  4. Smokeless propellants not stored in accordance with paragraph (F)(5)(b)(i)(a)(5606.5.2.1), (F)(5)(b)(i)(b)(5606.5.2.1), or (F)(5)(b)(i)(c)(5606.5.2.1) of this rule shall be stored in a Type 2 or 4 magazine in accordance with paragraph (D)(5604) of this rule and NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Commercial stocks of black powder in quantities less than 50 pounds (23 kg) shall be allowed to be stored in Type 2 or 4 indoor or outdoor magazines. Quantities greater than 50 pounds (23 kg) shall be stored in outdoor Type 2 or 4 magazines. When black powder and smokeless propellants are stored together in the same magazine, the total quantity shall not exceed that permitted for black powder.
Commercial stocks of small arms primers shall be stored as follows:
  1. Quantities not to exceed 750,000 small arms primers stored in a building shall be arranged such that not more than 100,000 small arms primers are stored in any one pile and piles are not less than 15 feet (4572 mm) apart.
  2. Quantities exceeding 750,000 small arms primers stored in a building shall comply with all of the following:
    1. The warehouse or storage building shall not be accessible to unauthorized personnel.
    2. Small arms primers shall be stored in cabinets. Not more than 200,000 small arms primers shall be stored in any one cabinet.
    3. Shelves in cabinets shall have vertical separation of not less than 2 feet (610 mm).
    4. Cabinets shall be located against walls of the warehouse or storage room with not less than 40 feet (12 192 mm) between cabinets. The minimum required separation between cabinets shall be allowed to be reduced to 20 feet (6096 mm) provided that barricades twice the height of the cabinets are attached to the wall midway between each cabinet. The barricades shall be firmly attached to the wall and shall be constructed of steel not less than 1/4 inch thick (6.4 mm), 2-inch (51 mm) nominal thickness wood, brick or concrete block.
    5. Small arms primers shall be separated from materials classified as combustible liquids, flammable liquids, flammable solids or oxidizing materials by a distance of 25 feet (7620 mm) by a fire partition having a fire-resistance rating of 1 hour.
    6. The building shall be protected throughout with an automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
  3. Small arms primers not stored in accordance with paragraph (F)(5)(b)(iii)(a)(5606.5.2.3) or (F)(5)(b)(iii)(b)(5606.5.2.3) of this rule shall be stored in a magazine meeting the requirements of paragraph (D)(5604) of this rule and NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Blasting operations shall be conducted only by approved, competent operators familiar with the required safety precautions and the hazards involved and in accordance with the provisions of NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Blasting operations shall be performed in accordance with the instructions of the manufacturer of the explosive materials being used.
Where blasting is done in a congested area or in close proximity to a structure, railway or highway, or any other installation, precautions shall be taken to minimize earth vibrations and air blast effects. Blasting mats or other protective means shall be used to prevent fragments from being thrown.
Surface-blasting operations shall only be conducted during daylight hours between sunrise and sunset. Other blasting shall be performed during daylight hours unless otherwise approved by the fire code official.
Where blasting is being conducted in the vicinity of utility lines or rights-of-way, the blaster shall notify the appropriate representatives of the utilities not less than 24 hours in advance of blasting, specifying the location and intended time of such blasting. Verbal notices shall be confirmed with written notice.
Exception: In an emergency situation, the time limit shall not apply where approved.
Precautions shall be taken to prevent accidental discharge of electric detonators from currents induced by radar and radio transmitters, lightning, adjacent power lines, dust and snow storms, or other sources of extraneous electricity.
Precautions shall be taken to prevent accidental initiation of nonelectric detonators from stray currents induced by lightning or static electricity.
During the time that holes are being loaded or are loaded with explosive materials, blasting agents or detonators, only authorized persons engaged in drilling and loading operations or otherwise authorized to enter the site shall be allowed at the blast site. The blast site shall be guarded or barricaded and posted. Blast site security shall be maintained until after the post-blast inspection has been completed.
Holes drilled for the loading of explosive charges shall be made and loaded in accordance with NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
After loading for a blast is completed and before firing, excess explosive materials shall be removed from the area and returned to the proper storage facilities.
The initiation of blasts shall be by means conforming to the provisions of NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
The blaster shall supervise the connecting of the blastholes and the connection of the loadline to the power source or initiation point. Connections shall be made progressively from the blasthole back to the initiation point.
Blasting lead lines shall remain shunted (shorted) and shall not be connected to the blasting machine or other source of current until the blast is to be fired.
A blast shall not be fired until the blaster has made certain that all surplus explosive materials are in a safe place in accordance with paragraph (G)(10)(5607.10) of this rule, all persons and equipment are at a safe distance or under sufficient cover and that an adequate warning signal has been given.
After the blast, the following procedures shall be observed.
  1. No person shall return to the blast area until allowed to do so by the blaster in charge.
  2. The blaster shall allow sufficient time for smoke and fumes to dissipate and for dust to settle before returning to or approaching the blast area.
  3. The blaster shall inspect the entire blast site for misfires before allowing other personnel to return to the blast area.
Where a misfire is suspected, all initiating circuits shall be traced and a search made for unexploded charges. Where a misfire is found, the blaster shall provide proper safeguards for excluding all personnel from the blast area. Misfires shall be reported to the blasting supervisor immediately. Misfires shall be handled under the direction of the person in charge of the blasting operation in accordance with NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
This paragraph applies to any exhibition of 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0432), 1.4S fireworks (UN0337) and 1.4S special effects fireworks (UN0432). No 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335) or 1.4G fireworks (UN0336) may be displayed or otherwise discharged indoors.
A permit shall be obtained from the local fire official and law enforcement officer of the jurisdiction for any outdoor exhibition of 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0432), 1.4S fireworks (UN0337) and 1.4S special effects fireworks (UN0432) fireworks and any indoor exhibition of 1.4G special effects fireworks (UN0432), 1.4S fireworks (UN0337) and 1.4S special effects fireworks (UN0432) pursuant to the applicable provisions of section 3743.54 of the Revised Code. The permit shall bear the signatures of the fire official and law enforcement official having jurisdiction and the licensed exhibitor applying to conduct the fireworks exhibition. The permit shall identify the certified fire safety inspector, fire chief, or fire prevention officer who will be present before, during, and after the fireworks exhibition, where appropriate.
The form for exhibition permit as prescribed by the state fire marshal shall be legibly and fully completed by the licensed exhibitor to clearly indicate the circumstances of the public fireworks exhibition the exhibitor wishes to conduct.
Before any fireworks exhibition permit issued under this rule is considered to be a valid permit to allow the licensed exhibitor to acquire fireworks and conduct a fireworks exhibition, the permit must be signed and dated by the local officials having jurisdiction.
A fireworks exhibition permit should be obtained from such local officials at least five days in advance of the fireworks exhibition. Failure to obtain the exhibition permit prior to five days in advance of the fireworks exhibition may result in denial of the approval required to conduct the fireworks exhibition.
When the legislative authority of the political subdivision has prescribed a fee for the issuance of a permit for a fireworks exhibition, the fire official and law enforcement officer shall not issue such permit until the exhibitor pays the requisite fee and meets the financial responsibility requirements of paragraph (A)(2)(d)(ii)(5601.2.4.2) of this rule.
The fire chief or fire prevention officer of the authority having jurisdiction shall inspect the premises where the fireworks exhibition is to take place and determine whether the fireworks exhibition is in compliance with Chapter 3743. of the Revised Code and NFPA 1123 (Chapter 5, site selection) and the applicable portions of NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code. The radius of separation distance between all mortars, racks or other points of fireworks discharge and any members of the public shall be measured, regardless of obstruction or other topographical features, as a direct point to point line of sight measurement. All such separation distances shall be measured from the same horizontal plane of elevation between the fireworks discharge point and members of the public. No members of the public shall, regardless of their relative difference in elevation from the horizontal plane of measurement, be permitted within the required radius of separation. For the purposes of this paragraph, the radius of separation extends infinitely above and below the horizontal plane of measurement. The inspection shall be conducted prior to the issuance of the permit for a fireworks exhibition.
At the time of the required site inspection, the fire chief or fire prevention officer, shall complete the required detailed inspection checklist as prescribed by the state fire marshal and set forth in the appendix to this rule. If the exhibition is to be inspected is an outdoor exhibition, the fire chief or fire prevention officer shall complete the detailed inspection checklist, in consultation with a police chief or other similar chief law enforcement officer of a municipal corporation, township, or township police district or with a designee of such a police chief or other similar chief law enforcement officer. No exhibition of fireworks shall occur in this state until the licensed exhibitor possesses a copy of the appropriate checklist signed by the fire official and the licensed exhibitor.
No permit for a fireworks exhibition shall be granted unless the applicant is in possession of a valid license to exhibit fireworks issued by the state fire marshal. Each applicant for a permit shall show the applicant's license as an exhibitor of fireworks to the fire chief or fire prevention officer and, upon request to the police chief or other similar law enforcement officer.
Fireworks exhibition permit application detailed information required.
When an Ohio licensed exhibitor applies for the permit required by paragraph (H)(1)(5608.1) of this rule, the licensed exhibitor shall submit all of the following information to the local officials having jurisdiction over the exhibition. Such information shall include but not be limited to:
The name of the organization sponsoring the fireworks exhibition together with the names of persons actually in charge of the fireworks exhibition.
The date and time of day when the fireworks exhibition is to be held.
The exact location planned for the fireworks exhibition.
The name and license number of the fireworks exhibitor who is to supervise the discharge of fireworks and of all personnel assisting within the discharge perimeter.
The class of fireworks to be discharged with the number of set pieces and shells (specify single- or multiple-break), including experimental rockets or missiles.
For the indoor exhibition of fireworks, the requirements for pyrotechnic product information in accordance with Chapter 7 of NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
The manner and place of storage of all fireworks prior to and during the fireworks exhibition for all fireworks storage shall be in accordance with paragraph (J)(1)(5610.1) of this rule.
A diagram of the premises on which the fireworks exhibition is to be held, showing the point at which the fireworks are to be discharged, the location of all buildings, highways, railroads, or other inhabited structures within one thousand feet of the discharge and potential landing site. The diagram shall also show the line barriers behind which the audience will be restrained.
For the indoor exhibition of fireworks, the diagram must include:
  1. The interior of the structure to be used for the exhibition and the layout of all devices to be used at the exhibition.
  2. A description of the direction the devices shall be fired and the fallout radius for each device.
  3. The lines behind which the audience shall be restrained.
For the indoor exhibition of fireworks, certifications that the set, scenery and rigging materials are treated with appropriate flame retardant.
Proof that general liability insurance or indemnity bond issued by a company licensed to provide such coverages in the state of Ohio, for an amount no less than one million dollars or as otherwise required in a higher amount by the authority having jurisdiction, is in force for the applicant and includes acts of all employees.
A copy of each exhibitor's license and proof of assistant's registration for all individuals proposed to operate within the discharge perimeter.
The name and license number of the fireworks manufacturer, wholesaler or out-of-state shipper who supplied all items in the fireworks exhibition.
The licensed exhibitor reflected on the fireworks exhibition permit at the time of the fireworks exhibition shall be responsible for compliance with the provisions under which the fireworks exhibition permit was granted.
A copy of the issued permit and the completed inspection checklist shall be sent to the state fire marshal by the fire official no later than five days after the date of the fireworks exhibition. In the event of any incident resulting in an investigation or other inquiry by the state fire marshal or other authority having jurisdiction, the completed permit and the completed inspection checklist shall be made immediately available to the state fire marshal or other authority having jurisdiction upon request.
The local fire official and, for the outdoor exhibition of fireworks a law enforcement officer of the jurisdiction may deny or revoke a fireworks exhibition permit for any of the following:
The applicant/exhibitor does not possess a valid exhibitor's license issued by the state fire marshal.
The site on which the fireworks exhibition is to take place does not conform to the applicable rules.
The applicant has failed to pay the permit fee or provide the required information.
The applicant has failed to provide the required indemnity bond or proof of insurance.
The exhibitor has failed to postpone a fireworks exhibition when so ordered due to unsafe conditions or operations, inclement weather, wind conditions, unsafe spectator conditions, or any other condition in violation of this rule.
The exhibitor has failed to store the fireworks in a safe manner prior to or during the fireworks exhibition or is firing the fireworks exhibition in an unsafe manner.
The licensed exhibitor present at the fireworks exhibition is not the licensed exhibitor that was designated to be present pursuant to paragraph (H)(7)(a)(iv)(5608.7.1.4) of this rule. The authority having jurisdiction is authorized to approve a substitution of another licensed exhibitor under extenuating circumstances prior to the fireworks exhibition provided that the substitute licensed exhibitor:
Demonstrates to the authority having jurisdiction possession of a valid fireworks exhibitors license;
Signs the fireworks exhibition permit and thereby accepts the full responsibility and liability for conducting the fireworks exhibition as initially approved;
Produces proof that general liability insurance or indemnity bond issued by a company licensed to provide such coverages in the state of Ohio, for an amount no less than one million dollars or as otherwise required in a higher amount by the authority having jurisdiction, is in force for the applicant and includes acts of all employees;
Demonstrates to the authority having jurisdiction that they are authorized by the initial exhibitor to conduct the fireworks exhibition;
Follows the initially approved conditions of the fireworks exhibition permit;
Conducts the fireworks exhibition in accordance with the requirements of this rule.
Operations shall immediately cease and the fireworks exhibition shall be postponed when so ordered by the authority having jurisdiction or the licensed fireworks exhibitor due to unsafe conditions or operations, inclement weather, wind conditions, unsafe spectator conditions, or any other condition in violation of this rule. The orders to cease operations, postpone the fireworks exhibition and the revocation of the fireworks exhibition permit may be communicated verbally by the authority having jurisdiction. When so ordered or when the fireworks exhibition permit has been revoked, the exhibitor shall cease firing of the fireworks exhibition immediately. The exhibitor may reapply for a new permit for the fireworks exhibition when the fire official and, for an outdoor exhibition, a law enforcement officer are satisfied that all rules, conditions, and operations are safe or have been complied with.
All fireworks exhibitions shall be conducted in accordance with the following as applicable to the type of exhibition:
All mortars used in a fireworks exhibition that are greater than or equal to eight inches in diameter shall be equipped with electronic ignition equipment in accordance with NFPA 1123 as listed in rule 1301:7-7-80 of the Administrative Code.
All fireworks mortars and mortar racks used at a fireworks exhibition shall conform to the requirements of NFPA 1123 as listed in rule 1301:7-7-80 of the Administrative Code and this paragraph to ensure stability.
All mortar racks shall be securely positioned in accordance with the requirements of NFPA 1123 as listed in rule 1301:7-7-80 of the Administrative Code. The methods used to securely position the mortar rack shall not include the use of items such as plastic ties, string, twine, tape, or any other material that may easily break, dislodge, ignite, or otherwise permit the repositioning of the mortar rack.
All mortars, bundles, box items, cakes, candle placements, and mortar racks shall be inherently stable or be properly secured and braced to prevent repositioning. It is not acceptable to create inherent stability of mortar racks only by connection to other mortar racks.
All mortar racks shall be individually secured by one or more approved method. Approved methods include but are not limited to: utilizing steel stakes, sturdy wood stakes, or spikes securely attached to the rack frame with approved materials; utilizing sand bags of sufficient quantity and height placed on each side of and in direct contact with the rack frame; utilizing wood or steel feet of sufficient length, strength, and durability, securely attached in a perpendicular orientation to the ends of the rack frame; utilizing sideboards securely mounted in a perpendicular orientation to both ends of the rack frame; or by the construction of A-frame braces of sufficient strength and durability securely attached to both ends of the rack frame.
The stability of all mortars, bundles, box items, cakes, candle placements and mortar racks shall be verified by the licensed fireworks exhibitor and fire official immediately prior to the fireworks exhibition. Each such item shall be individually addressed in an appropriate manner to ensure its integrity and stability prior to providing affirmative documentation of such stability on the required inspection checklist.
Each licensed exhibitor shall display prominently upon their person any visible identification required by the fire code official at all times when within the discharge perimeter or otherwise at the exhibition site. Each licensed exhibitor shall make their exhibitor license available for review to any fire or law enforcement officer upon request.
Only fire officials, licensed fireworks exhibitors or persons who are employees of licensed exhibitors of fireworks and who are registered with the state fire marshal under section 3743.56 of the Revised Code shall be permitted within the discharge perimeter during a fireworks exhibition.
Only fire officials, licensed fireworks exhibitors, or persons who are employees of licensed exhibitors of fireworks and who are registered with the state fire marshal under section 3743.56 of the Revised Code shall be permitted within the fall out area during a fireworks exhibition. If approved by the fire official, persons associated with a theatrical or other similar performance related to the exhibition may also be permitted within the fall out area during an indoor fireworks exhibition.
An inspection of all affected premises shall be conducted immediately following a fireworks exhibition for purposes of locating and disposing of defective or unexploded fireworks. If an outdoor fireworks exhibition is conducted at night, an inspection shall also be conducted at sunrise the following morning.
The governing authority having jurisdiction in the location where an outdoor exhibition is to take place shall require that a certified fire safety inspector, fire chief, or fire prevention officer be present before, during, and after the outdoor fireworks exhibition. The fire safety inspector, fire chief or fire prevention officer shall complete the detailed inspection checklist as prescribed by the state fire marshal and set forth in the appendix of this rule. If the exhibition to be inspected is an outdoor exhibition, the fire chief or fire prevention officer shall complete the detailed inspection checklist, in consultation with a police chief or other similar chief law enforcement officer of a municipal corporation, township, or township police district or with a designee of such a police chief or other similar chief law enforcement officer.
No licensed exhibitor of fireworks shall permit an employee to assist the licensed exhibitor in conducting fireworks exhibitions unless the employee is registered with the state fire marshal under section 3743.56 of the Revised Code.
Unless otherwise specifically directed by this rule, the Administrative Code, or the Revised Code, all fireworks used in any type of exhibit shall be used in accordance with the instructions provided by the manufacturer.
As used in this paragraph, "fireworks" includes 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0432), 1.4S fireworks (UN0337) and 1.4S special effects fireworks (UN0432). All fireworks transported on the highways in this state and all wholesale and commercial sales of fireworks shall be packaged, shipped, placarded, and transported in accordance with DOTn regulations applicable to the transportation, and the offering for transportation, of hazardous materials and NFPA 1123, 1124 and 1126 as listed in rule 1301:7-7-80 of the Administrative Code. All fireworks otherwise transported into or through this state shall be transported in accordance with applicable law. For purposes of this paragraph, "wholesale and commercial sales" includes all sales for resale and any nonretail sale made in furtherance of a commercial enterprise. For purposes of enforcement of these regulations under section 4905.83 of the Revised Code, any sales transaction exceeding one thousand pounds shall be presumed to be a wholesale or commercial sale.
No person shall ship fireworks into this state by mail, parcel post, or common carrier unless the person possesses a valid shipping permit issued under section 3743.40 of the Revised Code, and the fireworks are shipped directly to the holder of a license issued under section 3743.03 or 3743.16 of the Revised Code or to the holder of a license issued under section 3743.51 of the Revised Code who possesses a valid exhibition permit issued in accordance with section 3743.54 of the Revised Code and the fireworks being shipped are to be used at that specifically permitted exhibition.
No person shall ship fireworks within this state by mail, parcel post, or common carrier unless the fireworks are shipped directly to the holder of a license issued under section 3743.03 or 3743.16 of the Revised Code or to the holder of a license issued under section 3743.51 of the Revised Code who possesses a valid exhibition permit issued in accordance with section 3743.54 of the Revised Code and the fireworks being shipped are to be used at that specifically permitted exhibition.
The storage of fireworks at the exhibition site shall comply with the requirements of this paragraph and NFPA 1123 and NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code. All fireworks to be used at a fireworks exhibition shall be stored in an approved magazine at the exhibition site until immediately prior to their use. Such magazine shall be located in an area approved by the local fire official and shall meet the table of distances requirements of this rule. Magazines shall be constructed in accordance with this rule. No fireworks may be acquired or stored by an exhibitor until the permit for the specific exhibition that the fireworks will be used at has been issued. Such storage shall not exceed a period of seventy-two hours prior to the start of the fireworks exhibition as provided for in the approved permit unless all of the following apply:
  1. The fire code official having jurisdiction over the exhibition approves the extended time period for storage as part of the exhibition permit.
  2. All fireworks are stored at the exhibition site as that site is described in the permit.
  3. The fireworks stored at the exhibition site in accordance with this rule shall only be those fireworks approved by the fire code official having jurisdiction as necessary for the specific exhibition listed in the exhibition permit that describes the extended storage period.
  4. The extended time period for storage shall not exceed a maximum of fourteen days.
Beginning as soon as fireworks have been delivered to the exhibition site, they shall not be left unattended.
Fireworks shall be kept dry after delivery to the exhibition site.
Fireworks shall be inspected by the operator or assistants after delivery to the exhibition site. Fireworks having tears, leaks, broken fuses or signs of having been wet shall be set aside and shall not be fired. Aerial shells shall be checked for proper fit in mortars prior to discharge. Aerial shells that do not fit properly shall not be fired. After the fireworks exhibition, damaged, deteriorated or dud fireworks shall either be returned to the supplier or destroyed in accordance with the supplier's instructions and paragraph (D)(10)(5604.10) of this rule.
Exception: Minor repairs to fuses shall be allowed. For electrically ignited exhibitions, attachment of electric matches and similar tasks shall be allowed.
After delivery to the exhibition site and prior to the fireworks exhibition, all aerial shells shall be separated according to size and their designation as salutes.
Exception: For electrically fired fireworks exhibitions, or exhibitions where all shells are loaded into mortars prior to the show, there is no requirement for separation of shells according to size or their designation as salutes.
Fireworks that will be temporarily stored at the site during the fireworks exhibition shall be stored in ready boxes located upwind and at least 25 feet (7620 mm) from the mortar placement and separated according to size and their designation as salutes.
Exception: For electrically fired fireworks exhibitions, or exhibitions where all shells are loaded into mortars prior to the show, there is no requirement for separation of shells according to size, their designation as salutes, or for the use of ready boxes.
This paragraph shall apply to the following:
  1. Use of flame effects for entertainment, exhibition, demonstration or simulation before an audience;
  2. Design, fabrication, installation, testing, control, operation, and maintenance of equipment, materials, procedures, and systems used to produce flame effects;
  3. Rehearsal, videotaping, audio taping, or filming of any television, radio, or movie production if such production is before an audience and includes the use of flame effects;
  4. Rehearsal of any production incorporating flame effects intended to be presented before an audience;
  5. Storage and holding at a venue where flammable and combustible materials are used to create flame effects;
This rule shall not apply to:
  1. Flame effects produced solely by pyrotechnic special effects devices;
  2. Use of pyrotechnic special effects;
  3. Storage of flammable solids, liquids, and gases not to be used to create flame effects;
  4. Manufacture, off-site storage, and transportation of materials and equipment used to produce flame effects;
  5. Use of flame effects in fire training, except where there is an audience that is not part of the training;
  6. Manufacture, transportation, storage, sale, or use of model or high-power rocket motors;
  7. Traditional non-theatrical public display of flames such as the following:
    1. Use of lighted candles in restaurants or religious services;
    2. Fireplace in areas open to the public;
    3. Restaurant cooking visible to the patrons;
    4. Listed Group II flame effects.
  8. Use of motor vehicles in races or sanctioned competitive sporting events.
A permit shall be obtained from the local fire code official of the jurisdiction for the use of indoor and outdoor flame effects as set forth in paragraph (K)(1)(5611.1) of this rule at least five days in advance of the production, exhibition, demonstration, or simulation using the flame effects. Failure to obtain a permit prior to five days in advance of the production or non-compliance with the requirements of this rule and NFPA 160 as listed in rule 1301:7-7-80 of the Administrative Code may, in the discretion of the local fire code official, result in denial or revocation of the permit.
Before any flame effects exhibition permit issued under this rule is considered to be a valid permit to allow the licensed flame effects exhibitor to conduct a flame effects exhibition, the permit, upon approval, must be signed and dated by the local fire code official having jurisdiction. As required by the local fire code official to confirm compliance with this paragraph, receipt of the permit and/or any conditions associated thereto, the flame effects exhibitor shall sign and date the permit application, the permit and/or any other required documentation.
When a permit is required by this rule, a local fire code official shall be present during the production, exhibition, demonstration, or simulation using flame effects.
Exception: When issuing a permit for a group I or group II flame effects production, exhibition, demonstration, or simulation using flame effects, the local fire code official may determine that a local fire code official need not be present during such an exhibition.
If a permit is required by this rule, the permit shall identify the local fire code official who will be present before, during, and after the flame effects exhibition.
If any portion of the fire protection or life safety systems of a structure are interrupted during the operation of flame effects, a local fire code official must grant a prior approval of and be present during such interruptions.
Any performance adding flame effects different from the performance described in the permittee's plan shall require approval by the local fire code official having jurisdiction.
The application form for exhibition permit as prescribed by the state fire marshal shall be legibly and fully completed by the licensed flame effects exhibitor to clearly indicate the circumstances and class of the flame effects exhibition the flame effects exhibitor wishes to conduct.
Before the performance of any production, the permit applicant shall submit a plan for the use of flame effects to the local fire code official. The plan shall be made in writing in such form as is acceptable to the local fire code official and shall demonstrate compliance with this rule and NFPA 160 listed in rule 1301:7-7-80 of the Administrative Code. The plan shall include but is not limited to the following:
  1. The name of the person, group, or organization sponsoring the production;
  2. The date and time of day of the production;
  3. The exact location of the production;
  4. The name of the flame effects exhibitor and proof of valid flame effects exhibitor license issued by the state fire marshal;
  5. The number, names, and ages of all assistants that will be present;
  6. The qualifications and experience of the flame effects exhibitor;
  7. The flame effects classification and design criteria in accordance with NFPA 160 listed in rule 1301:7-7-80 of the Administrative Code;
  8. A diagram of the site indicating the location of all flame effects devices, the areas effected by each device, location of the audience and separation distances, means of egress, and information on all fuels and ventilation for each effect;
  9. A narrative description of the flame effects, controls, and control sequences of all devices, and emergency response procedures;
  10. If applicable, a valid Material Safety Data Sheet (MSDS) for each fuel utilized;
  11. Documentation that the set, scenery, and rigging materials are treated with appropriate flame retardant.
After a permit has been granted, the permittee shall keep the plan available at the site for safety inspectors or other designated agents of each authority having jurisdiction.
When the legislative authority of the political subdivision has prescribed a fee for the issuance of a permit for a flame effects exhibition, the local fire code official shall not issue such permit until the flame effects exhibitor pays the requisite fees as required by the local legislative enactment setting forth such fee.
Prior to issuance, the local fire code official having jurisdiction shall inspect the premises where the flame effects exhibition is to take place and determine whether the exhibition, demonstration, or simulation using flame effects is in compliance with this rule, Chapter 3743.of the Revised Code, and NFPA 160 (Annex C, Inspection Guidelines) as listed in rule 1301:7-7-80 of the Administrative Code.
At the time of the required site inspection, the local fire code official having jurisdiction shall complete the required detailed inspection checklist as prescribed by the state fire marshal. No production, exhibition, demonstration, or simulation using flame effects shall occur in this state until the licensed flame effects exhibitor possesses a copy of the appropriate checklist signed by the local fire code official.
No person shall engage in the production, exhibition, demonstration, or simulation using flame effects unless the person obtains a permit in accordance with this rule. No permit for a flame effects exhibition shall be granted unless the applicant is in possession of a valid flame effects exhibitor's license in accordance with paragraph (S)(5619) of this rule to exhibit, demonstrate, or simulate using flame effects. Each applicant for a permit shall show the applicant's license as a flame effects exhibitor's license to the local fire code official and, upon request, to the police chief or other similar law enforcement officer.
The local fire code official may deny or revoke a flame effects exhibition permit for any of the following:
  1. The applicant/exhibitor does not possess a valid flame effects exhibitor's license issued by the state fire marshal.
  2. The site on which the flame effects exhibition is to take place does not conform to the applicable rules.
  3. The applicant has failed to pay the permit fee or provide the required information.
  4. The applicant has failed to provide the required indemnity bond or proof of insurance, if such indemnity bond or proof of insurance is required by the local fire code official at the local fire code official's discretion.
  5. The flames effects exhibitor has failed to postpone a flame effects exhibition when so ordered due to unsafe conditions or operations, unsafe spectator conditions, or any other condition in violation of this rule.
  6. The flames effects exhibitor has failed to store the flame effects in a safe manner prior to or during the flame effects exhibition or is firing the flame effects exhibition in an unsafe manner.
  7. The licensed flames effects exhibitor present at the flame effects exhibition is not the licensed flame effects exhibitor that was designated to be present pursuant to paragraph (K)(2)(5611.2) and (K)(4)(5611.4) of this rule. The local fire code official is authorized to approve a substitution of another licensed flame effects exhibitor under extenuating circumstances prior to the flame effects exhibition provided that the substitute licensed flame effects exhibitor:
    1. Demonstrates to the local fire code official possession of a valid flame effects exhibitor's license;
    2. Signs the flame effects exhibition permit and thereby accepts the full responsibility and liability for conducting the flame effects exhibition as initially approved;
    3. If required by the local fire code official, produces proof that general liability insurance or indemnity bond issued by a company licensed to provide such coverage in the state of Ohio, for an amount no less than one million dollars or as otherwise required in a higher amount by the local fire code official, is in force for the applicant and includes acts of all employees;
    4. Demonstrates to the local fire official that they are authorized by the initial flame effects exhibitor to conduct the flame effects exhibition;
    5. Follows the initially approved conditions of the flame effects exhibition permit;
    6. Conducts the flame effects exhibition in accordance with the requirements of this rule.
  8. The licensed flame effects exhibitor failed to produce, exhibit, demonstrate, or simulate using flame effects in accordance with this rule or otherwise failed to comply with the requirements set forth in this rule.
Operations shall immediately cease and the flame effects exhibition shall be postponed by the licensed flame effects exhibitor when so ordered by the local fire code official or due to unsafe conditions or operations, unsafe spectator conditions, or any other condition in violation of this rule.
The local fire code official shall order the immediate cessation of the flame effects exhibition due to unsafe conditions or operations, unsafe spectator conditions, or any other condition in violation of this rule. The orders to cease operations, postpone the flame effects exhibition and the revocation of the flame effects exhibition permit may be communicated verbally by the local fire code official. When so ordered or when the flame effects exhibition permit has been revoked, the flame effects exhibitor shall cease the flame effects exhibition immediately. The flame effects exhibitor may reapply for a new permit for the flame effects exhibition when the local fire code official is satisfied that all rules, conditions, and operations are safe or have been complied with.
All flame effects control systems shall be designed and installed to prevent accidental firing and unintentional release of fuel.
All flame effect materials and devices not connected for use shall be stored in accordance with applicable codes and standards and any state and local regulations.
All flammable flame effect materials and loaded devices that have been removed from storage areas in anticipation of use shall be stored in a holding area acceptable to the local fire code official.
The maximum quantity of flammable flame effect materials and loaded devices stored in a holding area shall be that quantity used in one day.
Quantities of flammable flame effect materials and devices in excess of those used in one day shall be permitted to be stored in holding areas with the approval of the local fire official.
Flammable flame effect materials and loaded devices in holding areas shall be secured or supervised continuously by an attendant trained in emergency response procedures.
All flame effects and flame effects exhibitors shall comply with NFPA 160 and the NFPA 160 annexes as listed in rule 1301:7-7-80 of the Administrative Code.
The local fire code official having jurisdiction may require the applicant to maintain valid general liability insurance or an indemnity bond in force for the applicant and includes acts of all employees that is issued by a company licensed to provide such coverage in the state of Ohio, for an amount no less than one million dollars or as otherwise required in a higher amount by the local fire official.
All flame effects devices and materials shall have drawings, manuals, or written descriptions to describe the type of item and performance specifications of the flame effects created. This documentation shall be on site and available to the local fire official.
All flame effects shall have written operating instructions including start-up, show operations normal shutdown procedures, and emergency shutdown procedures. Operating instructions shall be available to the operator.
All licensed manufacturers, wholesalers, shippers, and fireworks exhibitors shall comply with the applicable requirements listed in this rule, the building code, NFPA 1123, NFPA 1124 and NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, relating to operation, record keeping and reporting, site security, separation distances, heating, lighting, electrical equipment, smoking regulations, fire and explosion prevention, fire protection and emergency procedures, transportation, and operations of fireworks exhibits.
All manufacturing or processing of fireworks must be in accordance with Chapter 3743. of the Revised Code, the applicable provisions of NFPA 1123, NFPA 1124 and NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code and, to the extent not addressed by the Revised Code or NFPA 1123, NFPA 1124 and NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, in accordance with paragraph (E)(5605) of this rule.
Licensed manufacturers and licensed wholesalers need not comply with any requirements of paragraph (M)(5613) of this rule which concern the distance requirements of division (G) of section 3743.06 or division (H) of section 3743.19 of the Revised Code if the buildings were erected on or before May 30, 1986 and were occupied by a licensee with a license for that location prior to December 1, 1990.
Each licensed manufacturer, wholesaler, or exhibitor shall comply with the applicable continuing education requirements as follows:
Each licensed manufacturer of fireworks that possesses fireworks for sale and sells fireworks under division (C) of section 3743.04 of the Revised Code, or a designee of the manufacturer, whose identity is provided to the state fire marshal by the manufacturer, annually shall attend a continuing education program. The state fire marshal shall develop the program and the state fire marshal or a person or public agency approved by the state fire marshal shall conduct it. A licensed manufacturer or the manufacturer's designee who attends a required program, within one year after attending the program, shall conduct in-service training for other employees of the licensed manufacturer regarding the information obtained in the program. A licensed manufacturer shall provide the state fire marshal with notice of the date, time, and place of all in-service training. The state fire marshal shall establish the subjects to be taught, the length of the classes, and the standards for approval, and the time periods for notification by the licensee to the state fire marshal of any in-service training.
Exception: If approved by the state fire marshal, any licensed manufacturer of fireworks that possesses fireworks for sale and sells fireworks under division (C) of section 3743.04 of the Revised Code, or a designee of the manufacturer, whose identity is provided to the state fire marshal by the manufacturer, who serves as an instructor at a continuing education program outlined above shall not have to attend an additional continuing education program as a student during that same licensing year.
Each licensed wholesaler of fireworks or a designee of the wholesaler, whose identity is provided to the state fire marshal by the wholesaler, annually shall attend a continuing education program. The state fire marshal shall develop the program and the state fire marshal or a person or public agency approved by the state fire marshal shall conduct it. A licensed wholesaler or the wholesaler's designee who attends a required program, within one year after attending the program, shall conduct in-service training for other employees of the licensed wholesaler regarding the information obtained in the program. A licensed wholesaler shall provide the state fire marshal with notice of the date, time, and place of all in-service training. The state fire marshal shall establish the subjects to be taught, the length of the classes, and the standards for approval, and the time periods for notification by the licensee to the state fire marshal of any in-service training.
Exception: If approved by the state fire marshal, any licensed wholesaler of fireworks or a designee of the wholesaler, whose identity is provided to the state fire marshal by the wholesaler, who serves as an instructor at a continuing education program as outlined above shall not have to attend an additional continuing education program as a student during that same licensing year.
Each licensed exhibitor of fireworks or a designee of the exhibitor, whose identity is provided to the state fire marshal by the exhibitor, shall attend a continuing education program consisting of not less than six hours of instruction once every three years. The state fire marshal shall develop the program and the state fire marshal or a person or public agency approved by the state fire marshal shall conduct it. A licensed exhibitor or the exhibitor's designee who attends a required program, within one year after attending the program, and on an annual basis during the following two years, shall conduct in-service training for other employees of the licensee regarding the information obtained in the program. After each in-service training, the licensed exhibitor shall provide a roster to the state fire marshal's office listing all those that attended the in-service training. A licensed exhibitor shall provide the state fire marshal with certified proof of full compliance with all applicable annual training requirements of the United States Department of Transportation and of the Occupational Safety and Health Administration. A licensed exhibitor shall provide the state fire marshal with notice of the date, time, and place of all in-service training not less than thirty days prior to an in-service training event. An individual exhibitor who has no employees shall not fulfill continuing education requirements through a designee. An exhibitor who fulfills the continuing education requirements through a designee shall provide the identity and exhibitor license number of the designee to the state fire marshal prior to the training program. Each licensed exhibitor shall provide documentation evidencing compliance with the continuing education requirements in the manner prescribed in the license renewal application material.
Upon approval of the state fire marshal, any licensed exhibitor of fireworks or a designee of the exhibitor whose identity is provided to the state fire marshal by the exhibitor, who serves as an instructor at a continuing education program as outlined above may count any hour(s) spent instructing as credit toward the exhibitor's or the designee's continuing education requirements as long as the hours of instruction were performed during the licensure period for which credit is sought.
All records documenting the completion of the continuing education required by this rule shall be maintained for a period of three years and shall be available for inspection by the state fire marshal or his/her designee when requested.
If there is reason to believe that the explosive composition or the pyrotechnic mixture of a particular fireworks device of the manufacturer, wholesaler, shipper, or exhibitor does not meet the DOTn classification regulations, such person shall furnish a random sampling of such fireworks device to the state fire marshal for testing to determine compliance of the device with DOTn classification regulations.
  1. Fireworks shall be evaluated and tested by the state fire marshal by written request or by seizure.
  2. The classification test shall not be construed as conferring classification to any other item, nor shall the trade name of any item be changed without notifying the state fire marshal thirty days prior to such change.
  3. Fireworks or pyrotechnic devices that have not been classified by DOTn classification standards shall not be used, stored, or sold for use within this state.
Fireworks or pyrotechnic devices that are submitted to the state fire marshal for classification by licensed manufacturers, wholesalers, shippers, or exhibitors shall be accompanied by a fee of twenty dollars for each item.
When required by the state fire marshal, live samples shall be submitted to the state fire marshal for testing. The number of samples necessary shall be determined by the state fire marshal, but in no case shall the number of samples be less than ten.
No person, other than the state fire marshal, a licensed manufacturer, licensed wholesaler or a licensed exhibitor pursuant to a properly issued exhibition permit, shall test fireworks. All testing of fireworks shall be in accordance with Chapter 3743. of the Revised Code, this rule and, to the extent not addressed by the Revised Code or this rule, in accordance with the applicable provisions of NFPA 1123, NFPA 1124 and NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
Pursuant to Chapter 3743. of the Revised Code, including section 3743.05 of the Revised Code, the state fire marshal establishes the following fireworks categories and uses:
A licensed manufacturer of fireworks may manufacture or process only the following categories of fireworks in accordance with Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
In accordance with Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, a licensed manufacturer may offer for sale and sell at wholesale or retail fireworks if manufactured by the licensee or fireworks manufactured by another, and may conduct other fireworks related activities on its licensed premises, for only the following categories of fireworks: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
In accordance with Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, a licensed wholesaler may offer for sale and sell fireworks at wholesale or retail, and may conduct other fireworks related activities on its licensed premises, for only the following categories of fireworks: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
Out of state residents acquiring and taking possession of fireworks while such persons are in Ohio may obtain only the following category of fireworks from a licensed manufacturer or licensed wholesaler in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code: 1.4G fireworks (UN0336).
Out of state persons acquiring fireworks while such persons are not located in Ohio may obtain the following categories of fireworks from a licensed manufacturer or licensed wholesaler in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
Ohio residents acquiring and taking possession of fireworks while such persons are in Ohio may obtain only the following category of fireworks in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code: 1.4G fireworks (UN0336).
Licensed manufacturers and licensed wholesalers may acquire, in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, the following categories of fireworks from other licensed manufacturers and licensed wholesalers or licensed out of state shippers: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
A licensed exhibitor of fireworks may acquire, in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, only the following categories of fireworks for a properly permitted exhibition only from a licensed manufacturer, a licensed wholesaler or, if such fireworks are shipped directly to an exhibition site, from a licensed out of state shipper:
For an outdoor display exhibition: 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
For an indoor display exhibition: 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
Ignition, discharge and display of fireworks. Other than the testing of fireworks described in paragraph (M)(5613) of this rule, only a licensed exhibitor acting in accordance with a properly issued exhibition permit and in accordance with the federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, may ignite, discharge or display only the following categories of fireworks:
1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
Only the following categories of fireworks may be shipped into Ohio:
1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432).
All such shipments must be in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
The possession, transportation and storage of 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432) shall be in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
No other types of fireworks may be manufactured, sold, purchased, shipped, transported, possessed, ignited, displayed, stored or otherwise used in Ohio.
All fireworks manufactured, sold, shipped, transported, or displayed in this state shall be labeled in accordance with the CPSC regulations and other applicable laws, rules or regulations, including regulations promulgated by the United States Department of Transportation.
A licensed manufacturer or wholesaler shall only sell fireworks that meet the standards set by the consumer product safety commission or by the American fireworks standard laboratories or that have received an EX number from the United States Department of Transportation or an FC Number from a Department of Transportation approved fireworks certification agency. The state fire marshal may publish and maintain a listing of the specific EX numbers from the United States Department of Transportation or FC Numbers from a Department of Transportation approved fireworks certification agency of fireworks that can be sold in Ohio. At least thirty days prior to publishing or updating such a list, the state fire marshal shall distribute it to all Ohio licensed manufacturers and wholesalers of fireworks for comment.
Every license fee required in accordance with this rule shall be paid with cash or by money order, postal note, cashier's check, credit card, certified check or personal check payable to the "Treasurer, State of Ohio."
Every required license fee shall be paid at or mailed to the "Division of State Fire Marshal," at the address specified on the application material.
Renewal applications received after the required submittal dates shall be considered new applications and shall meet the examination requirement of paragraph (S)(7)(5619.7) of this rule.
In the event that a valid license is lost or accidentally destroyed, an application for a duplicate license shall be made in writing to the state fire marshal. The application for a duplicate license shall be accompanied by a ten-dollar fee.
No person who has been issued a manufacturer's or wholesaler's license shall give or permit any other person to use such license in violation of division (D) of section 3743.04 and division (D) of section 3743.17 of the Revised Code. No person who has been issued a shipping permit shall give or permit any other person to use such permit in violation of division (F) of section 3743.40 of the Revised Code. No person who has been issued an exhibitor's license shall give or permit any other person to use such license in violation of division (B) of section 3743.52 of the Revised Code. Any license or permit is not transferable or assignable to any other holder at the same location without the written permission of the state fire marshal, nor shall any license be extended beyond the dates set out therein.
Exception: A permit for a fireworks exhibition may be transferred to a substitute licensed exhibitor as provided for in paragraph (H)(8)(g)(5608.8.7) of this rule.
When a license has been denied, revoked or suspended pursuant to this rule and Chapter 119. of the Revised Code, the fee for such license shall be forfeited and deposited into the state fire marshal's rotary fund and applied as a fee for license processing.
The state fire marshal shall not issue an initial or renewal license, permit or registration authorized by Chapter 3743. of the Revised Code, if the applicant for the license or permit, or any individual holding, owning, or controlling a five per cent or greater beneficial or equity interest in the applicant for the license or permit, has been convicted of or pleaded guilty to, after June 30, 1997, a felony under the laws of this state, another state, or the United States.
Upon receipt of an application and the required accompanying matter, the state fire marshal shall forward to the superintendent of the bureau of criminal identification and investigation a request that the bureau conduct an investigation of the applicant and, if applicable, additional individuals who hold, own, or control five per cent or greater beneficial or equity interest in the applicant, to determine whether the applicant or the additional associated individuals have been convicted of or pled guilty to a felony under the laws of this state, another state, or the United States. If the applicant for initial licensure has resided in this state for less than five continuous years immediately prior to the date the applicant submits an initial application, the superintendent also shall request that the Federal Bureau of Investigation conduct an investigation of the applicant and, if applicable, additional individuals who hold, own or control a five per cent or greater beneficial or equity interest in the applicant, to determine whether the applicant or the additional associated individuals have been convicted of or pled guilty to a felony under the laws of this state, another state, or the United States. The superintendent shall forward the results of the investigation to the state fire marshal and may charge a reasonable fee for providing the results. The state fire marshal shall also assess the applicant any fee charged by the superintendent for the results to the applicant.
The state fire marshal shall not place the license of a manufacturer or wholesaler in a temporarily inactive status while the holder of the license is attempting to qualify to retain the license.
Upon application by a licensed wholesaler of fireworks, a wholesaler license may be transferred from one geographic location to another within the same municipal corporation or within the unincorporated area of the same township, but only if all of the following apply:
  1. The identity of the holder of the license remains the same in the new location.
  2. The former location is closed prior to the opening of the new location and no fireworks business of any kind is conducted at the former location after the transfer of the license.
  3. The new location has received a local certificate of zoning compliance and a local certificate of occupancy, and otherwise is in compliance with all local building regulations.
  4. Every building or structure at the new location is separated from occupied residential and nonresidential buildings or structures, railroads, highways, or any other buildings or structures located on the licensed premises in accordance with the distances specified in NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
  5. Neither the licensee nor any person holding, owning, or controlling a five per cent or greater beneficial or equity interest in the license has been convicted of or has pleaded guilty to a felony under the laws of this state, any other state, or the United States after July 1, 1997.
  6. The state fire marshal approves the request for the transfer. The new locations shall comply with the requirements specified in divisions (A)(1) and (A)(2) of section 3743.25 of the Revised Code whether or not the fireworks showroom at the new location is constructed, expanded, or first begins operating on and after July 1, 1997.
Upon application by a licensed manufacturer or wholesaler of fireworks, a manufacturer or wholesaler license may be transferred to another person for the same particular location for which the license was issued if the assets of the manufacturer or wholesaler are transferred to that person by inheritance or by a sale approved by the state fire marshal. The state fire marshal shall not approve any transfer applications under this paragraph unless:
  1. The state fire marshal receives a satisfactory application for such a transfer on a form approved by the state fire marshal.
  2. The person seeking to transfer the license is the verified owner of the license and is otherwise permitted by law to transfer its ownership interests in such license.
  3. The person receiving ownership of the license meets the requirements of the Revised Code and this code for the possession of such a license.
  4. The licensed premises for the particular location is inspected by the state fire marshal.
  5. The license and the licensed premises are in compliance with the provisions of the Revised Code and this code.
Application by a manufacturer or wholesaler for an original license or a renewal license shall be made prior to the first day of October preceding the license year for which the original application or renewal application is being made. The application form shall be as prescribed by the state fire marshal. Failure to submit the application and license fee prior to the first day of October may require that the applicant wait until the following year to make another application. The original and renewal fee for a manufacturer or wholesaler license shall be two thousand seven hundred fifty dollars. The manufacturer or wholesaler license is effective for one year beginning on the first day of December. The state fire marshal shall issue or renew a license only on that date and at no other time.
If an applicant has any storage locations approved in accordance with the Revised Code or this code, the applicant also shall submit a fee of one hundred dollars per storage location for the inspection of each storage location.
A manufacturer or wholesaler license may be denied or revoked pursuant to Chapter 119. of the Revised Code when any of the following occur:
The applicant has failed to submit proof of comprehensive general liability insurance or licensee has failed to maintain the same.
The applicant has failed to provide the required information on the application form provided by the state fire marshal including, but not limited to failure to include, the identification of a statutory agent if applicable or other designated agent for service of process at the time of application and prompt notification of any changes in the statutory agent.
The applicant has failed to include the required fee for the license with the application.
The applicant withdraws his or her application prior to an investigation or inspection by the state fire marshal to determine if the license shall be issued.
The applicant or licensee has made a misrepresentation or filed false statements.
There is substantial evidence that the fireworks premises are not in full compliance with Chapters 3781. and 3791. of the Revised Code, or any applicable building or zoning regulations.
The state fire marshal shall revoke or deny renewal of a license or permit first issued under Chapter 3743. of the Revised Code on or after July 1, 1997, if the holder of the license or permit, or any individual holding, owning, or controlling a five per cent or greater beneficial or equity interest in the holder of the license or permit, is convicted of or pleads guilty to a felony under the laws of this state, another state, or the United States.
The licensed premises fails to comply with the requirements as set forth in paragraph (W)(5623) of this rule.
The applicant, licensee or premises fails to comply with the requirements or any provision of the Ohio Revised Code, Ohio Administrative Code or NFPA standards as listed in rule 1301:7-7-80 of the Administrative Code, or any order of the state fire marshal.
Applicants for all manufacturer or wholesaler licenses shall submit with their application to the state fire marshal a complete detailed list of all types of fireworks that they intend to wholesale, sell, offer for sale, transport, process, or otherwise dispose of. The list shall contain the following information:
The classification of all fireworks, including 1.1G fireworks (UN0333), 1.2G fireworks (UN0334), 1.3G fireworks (UN0335), 1.4G fireworks (UN0336), 1.4G special effects fireworks (UN0431), 1.4S fireworks (UN0337) or 1.4S special effects fireworks (UN0432) materials in accordance with the regulations of the U.S. Department of Transportation (DOTn 49 CFR as listed in rule 1301:7-7-80 of the Administrative Code), the type of all fireworks, and the names of each device in the inventory. Records of the amount of each type of device kept in the inventory shall be made available for inspection by the state fire marshal or his designee or fire code official upon request.
Applicants for a manufacturer or wholesaler license shall notify the state fire marshal in writing of any changes in content, construction, additions of, or deletion of any fireworks device on the submitted list. All lists shall be updated annually for license renewal.
All applicants for an initial manufacturer or wholesaler license, and thereafter at the discretion of the state fire marshal, shall submit a map showing the premises, all premises boundaries, building locations, building dimensions, distances between buildings, distance of the buildings from lot lines, railroads, roadways and habitable structures on adjoining properties. The map shall be sufficient to clearly delineate the boundaries, dimensions and all structures or other temporary or permanent fixtures located thereon that constitute the licensed premises. All buildings and structures shall be numbered and a list shall be attached to the map that corresponds to the building and structure number assigned to each, indicating the type of construction, date of construction (if erected after May 30, 1986) and actual use of each building and structure. Maps shall be drawn to scale by an architect, engineer or cartographer.
If a licensed premises consists of more than one parcel of real estate, those parcels shall be contiguous unless an exception is allowed pursuant to Chapter 3743. of the Revised Code and this rule for storage locations. The boundaries of a licensed premises, including the boundaries of an approved storage location, shall not change unless the license holder has first obtained written approval from the state fire marshal. The state fire marshal shall approve the change to such licensed premises boundaries only when the applicant clearly shows all of the following:
The proposed change would not be contrary to public health, safety or welfare.
The proposed area of premises expansion or premises contraction shall maintain the contiguity of the approved boundaries for the licensed premises or storage location.
Applications for such change shall include the submission of all of the following items:
A tax or appraisal map and/or a survey plot or other professionally prepared map.
Property deeds, lease agreements, and/or other appropriate proof of ownership or control. If the applicant does not own the licensed premises in fee simple, then the applicant must submit documentation, such as a copy of the current lease or rental agreement for the property, that the conduct of fireworks sales or related activity is an approved use of the premises by the owner.
A narrative description of all properties, structures, lot lines, and boundaries of the licensed premises involved and in the proposed change thereto.
All other relevant information requested by the state fire marshal.
Applicants for all manufacturer and wholesaler licenses shall submit with their application the parcel number and a copy of the deed of ownership or land contract for all of the parcels constituting the licensed premises. If the applicant does not own the licensed premises in fee simple, then the applicant must submit documentation, such as a copy of the current lease or rental agreement for the property, that the conduct of fireworks sales or related activity is an approved use of the premises by the owner.
The application for a manufacturer or wholesaler license shall be signed by the applicant. If the application is made by a partnership, it shall be signed by each partner of the partnership. If the application is made by a corporation, it shall be signed by the president of the corporation. The original or a certified copy of the articles of incorporation filed with the office of the secretary of state, stating each officer and statutory agent by name, and the letter of good standing shall be included with the application. Any change in the name of the identified officers of a corporation or the name of the identified statutory agent if applicable or other designated agent for service of process for each manufacturer or wholesaler that occurs during the licensure period shall be immediately submitted in writing to the state fire marshal.
For a manufacturer of fireworks license, each fireworks plant shall have at least one Class 1 magazine that is approved by the Bureau of Alcohol, Tobacco, and Firearms of the United States Department of the Treasury and that is otherwise in conformity with federal law. Such approval shall be evidenced only by a license issued by the Bureau of Alcohol, Tobacco, and Firearms of the United States Department of the Treasury.
Exception: This requirement does not apply to fireworks plants existing on or before August 3, 1931.
Each manufacturer or wholesaler of fireworks shall submit with each application for licensure one set of the applicant's fingerprints and a set of fingerprints of any individual holding, owning, or controlling a five per cent or greater beneficial or equity interest in the applicant for the license. The state fire marshal shall retain the fingerprints or similar identifying information submitted with each licensure application. On renewal, the applicant must submit fingerprints or similar identifying information for all new owners or shareholders of five per cent or more of the beneficial interest of the license. Persons who have previous fingerprint sets or similar identifying information on file with the state fire marshal shall resubmit new fingerprint sets or updated similar identifying information no later than thirty-six months from the date the previous fingerprint set or similar identifying information was submitted.
Each applicant for a fireworks wholesaler license shall submit proof of comprehensive general liability insurance coverage, specifically including fire and smoke casualty on premises, in an amount not less than one million dollars for each occurrence for bodily injury liability and wrongful death at its business location. Proof of such insurance shall be submitted together with proof of coverage in an amount not less than one million dollars for products liability on all inventory located at the business location. All applicants shall submit evidence of comprehensive general liability insurance coverage verified by the insurer and certified as to its provision of the minimum coverage required. The insurer who issued such insurance policy shall comply with all applicable Ohio laws or all applicable laws of the state where the insurer is located.
Each applicant for a fireworks manufacturer license shall submit proof of comprehensive general liability insurance coverage, specifically including fire and smoke casualty on premises and products, in an amount not less than one million dollars for each occurrence for bodily injury liability and wrongful death liability at the fireworks plant. All applicants shall submit evidence of comprehensive general liability insurance coverage verified by the insurer and certified as to its provision of the minimum coverage required. The insurer who issued such insurance policy shall comply with all applicable Ohio laws or all applicable laws of the state where the insurer is located.