CODES

ADOPTS WITH AMENDMENTS:

International Fire Code 2009 (IFC 2009)

Ohio Administrative Code 1301:7-7-01 Administration

Ohio Administrative Code 1301:7-7-02 Definitions

Ohio Administrative Code 1301:7-7-03 General Requirements

Ohio Administrative Code 1301:7-7-04 Emergency Planning and Preparedness

Ohio Administrative Code 1301:7-7-05 Fire Service Features

Ohio Administrative Code 1301:7-7-06 Building Services and Systems

Ohio Administrative Code 1301:7-7-07 Fire-Resistance-Rated Construction

Ohio Administrative Code 1301:7-7-08 Interior Finish, Decorative Materials and Furnishings

Ohio Administrative Code 1301:7-7-09 Fire Protection Systems

Ohio Administrative Code 1301:7-7-10 Means of Egress

Ohio Administrative Code 1301:7-7-11 Aviation Facilities

Ohio Administrative Code 1301:7-7-12 Dry Cleaning

Ohio Administrative Code 1301:7-7-13 Combustible Dust-Producing Operations

Ohio Administrative Code 1301:7-7-14 Fire Safety During Construction and Demolition

Ohio Administrative Code 1301:7-7-15 Flammable Finishes

Ohio Administrative Code 1301:7-7-16 Fruit and Crop Ripening

Ohio Administrative Code 1301:7-7-17 Fumigation and Thermal Insecticidal Fogging

Ohio Administrative Code 1301:7-7-18 Semiconductor Fabrication Facilities

Ohio Administrative Code 1301:7-7-19 Lumber Yards and Woodworking Facilities

Ohio Administrative Code 1301:7-7-20 Manufacture of Organic Coatings

Ohio Administrative Code 1301:7-7-21 Industrial Ovens

Ohio Administrative Code 1301:7-7-22 Motor Fuel-Dispensing Facilities and Repair Garages

Ohio Administrative Code 1301:7-7-23 High-Piled Combustible Storage

Ohio Administrative Code 1301:7-7-24 Tents and Other Membrane Structures

Ohio Administrative Code 1301:7-7-25 Tire Rebuilding and Tire Storage

Ohio Administrative Code 1301:7-7-26 Welding and Other Hot Work

Ohio Administrative Code 1301:7-7-27 Hazardous Materials—general Provisions

Ohio Administrative Code 1301:7-7-28 Aerosols

Ohio Administrative Code 1301:7-7-29 Combustible Fibers

Ohio Administrative Code 1301:7-7-30 Compressed Gases

Ohio Administrative Code 1301:7-7-31 Corrosive Materials

Ohio Administrative Code 1301:7-7-32 Cryogenic Fluids

Ohio Administrative Code 1301:7-7-33 Explosives and Fireworks

Ohio Administrative Code 1301:7-7-34 Flammable and Combustible Liquids

Ohio Administrative Code 1301:7-7-35 Flammable Gases and Flammable Cryogenic Fluids

Ohio Administrative Code 1301:7-7-36 Flammable Solids

Ohio Administrative Code 1301:7-7-37 Highly Toxic and Toxic Materials

Ohio Administrative Code 1301:7-7-38 Liquefied Petroleum Gases

Ohio Administrative Code 1301:7-7-39 Organic Peroxides

Ohio Administrative Code 1301:7-7-40 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids

Ohio Administrative Code 1301:7-7-41 Pyrophoric Materials

Ohio Administrative Code 1301:7-7-42 Pyroxylin (Cellulose Nitrate) Plastics

Ohio Administrative Code 1301:7-7-43 Unstable (Reactive) Materials

Ohio Administrative Code 1301:7-7-44 Water-Reactive Solids and Liquids

Ohio Administrative Code 1301:7-7-45 Marinas

Ohio Administrative Code 1301:7-7-46 Construction Requirements for Existing Buildings

Ohio Administrative Code 1301:7-7-47 Referenced Standards

Appendix A

Appendix B Fire-Flow Requirements for Buildings

Appendix C Fire Hydrant Locations and Distribution

Appendix D Fire Apparatus Access Roads

Appendix E Hazard Categories

Appendix F Hazard Ranking

Appendix G Cryogenic Fluids—weight and Volume Equivalents

The storage and use of water-reactive solids and liquids shall be in accordance with this rule.

Exceptions:

1. Display and storage in Group M and storage in Group S occupancies complying with paragraph (C)(11)(2703.11) of rule 1301:7-7-27 of the Administrative Code.

2. Detonable water-reactive solids and liquids shall be stored in accordance with rule 1301:7-7-33 of the Administrative Code.

Permits shall be required as set forth in rule 1301:7-7-01 of the Administrative Code.

The following word and term shall, for the purposes of this rule and as used elsewhere in this code, have the meaning shown herein.

“Water-reactive material.” A material that explodes; violently reacts; produces flammable, toxic or other hazardous gases; or evolves enough heat to cause autoignition or ignition of combustibles upon exposure to water or moisture. Water-reactive materials are subdivided as follows:

“Class 3.” Materials that react explosively with water without requiring heat or confinement.
“Class 2.” Materials that react violently with water or have the ability to boil water. Materials that produce flammable, toxic or other hazardous gases, or evolve enough heat to cause autoignition or ignition of combustibles upon exposure to water or moisture.
“Class 1.” Materials that react with water with some release of energy, but not violently.
The storage and use of water-reactive solids and liquids in amounts not exceeding the maximum allowable quantity per control area indicated in paragraph (C)(1)(2703.1) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701) and (C)(2703) of rule 1301:7-7-27 of the Administrative Code and paragraphs (A)(4401) and (C)(4403) of this rule.
The storage and use of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in paragraph (C)(1)(2703.1) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with rule 1301:7-7-27 of the Administrative Code and this rule.
Indoor storage of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(1) of rule 1301:7-7-27 of the Administrative Code, shall be in accordance with paragraphs (A)(2701), (C)(2703) and (D)(2704) of rule 1301:7-7-27 of the Administrative Code and this rule.
Storage of water-reactive solids and liquids shall be in detached buildings when required by paragraph (C)(8)(b)(2703.8.2) of rule 1301:7-7-27 of the Administrative Code.
In addition to the provisions of paragraph (D)(12)(2704.12) of rule 1301:7-7-27 of the Administrative Code, floors in storage areas for water-reactive solids and liquids shall be of liquid-tight construction.
Rooms or areas used for the storage of water-reactive solids and liquids shall be constructed in a manner which resists the penetration of water through the use of waterproof materials. Piping carrying water for other than approved automatic sprinkler systems shall not be within such rooms or areas.
When Class 3 water-reactive solids and liquids are stored in areas equipped with an automatic sprinkler system, the materials shall be stored in closed water-tight containers.

Water-reactive solids and liquids stored in quantities greater than 500 cubic feet (14 m3) shall be separated into piles, each not larger than 500 cubic feet (14 m3). Aisle widths between piles shall not be less than the height of the pile or 4 feet (1219 mm), whichever is greater.

Exception: Water-reactive solids and liquids stored in tanks.
Class 2 water-reactive solids and liquids shall not be stored in basements unless such materials are stored in closed water-tight containers or tanks.
Class 3 water-reactive solids and liquids shall not be stored in basements.
Class 2 or 3 water-reactive solids and liquids shall not be stored with flammable liquids.
Indoor storage rooms, areas and buildings containing Class 2 or 3 water-reactive solids and liquids shall be provided with explosion control in accordance with paragraph (K)(911) of rule 1301:7-7-09 of the Administrative Code.
Outdoor storage of water-reactive solids and liquids in quantities exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(3) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701), (C)(2703) and (D)(2704) of rule 1301:7-7-27 of the Administrative Code and this rule.
Outdoor storage of water-reactive solids and liquids shall be within tanks or closed water-tight containers and shall be in accordance with paragraphs (D)(2)(b)(4404.2.2) to (D)(2)(e)(4404.2.5) of this rule.
Outdoor storage of Class 3 water-reactive solids and liquids shall not be within 75 feet (22 860 mm) of buildings, lot lines, public streets, public alleys, public ways or means of egress.
Outdoor storage of Class 2 water-reactive solids and liquids shall not be within 20 feet (6096 mm) of buildings, lot lines, public streets, public alleys, public ways or means of egress. A 2-hour fire barrier wall without openings or penetrations, and extending not less than 30 inches (762 mm) above and to the sides of the storage area, is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.

Class 3 water-reactive solids and liquids shall be limited to piles not greater than 500 cubic feet (14 m3).

Class 2 water-reactive solids and liquids shall be limited to piles not greater than 1,000 cubic feet (28 m3).
Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
Secondary containment shall be provided in accordance with the provisions of paragraph (D)(2)(b)(2704.2.2) of rule 1301:7-7-27 of the Administrative Code.

The use of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(1) or 2703.1.1(3) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701), (C)(2703) and (E)(2705) of rule 1301:7-7-27 of the Administrative Code and this rule.

Effective Date: November 1, 2011

Prior Effective Dates: 7/1/79; 6/1/85; 6/15/92; 7/1/93; 9/1/95; 3/30/98; 9/1/05; 7/1/07