ADOPTS WITH AMENDMENTS:

International Fire Code 2009 (IFC 2009)

Heads up: There are no amended sections in this chapter.

The storage and use of flammable gases shall be in accordance with this rule. Compressed gases shall also comply with rule 1301:7-7-30 of the Administrative Code and cryogenic fluids shall also comply with rule 1301:7-7-32 of the Administrative Code. Bulk hydrogen compressed gas systems and bulk liquefied hydrogen gas systems shall comply with NFPA 55 as listed in rule 1301:7-7-47 of the Administrative Code. Hydrogen motor fuel-dispensing stations and repair garages and their associated above-ground hydrogen storage systems shall also be designed and constructed in accordance with rule 1301:7-7-22 of the Administrative Code.

Exceptions:
  1. Gases used as refrigerants in refrigeration systems (see paragraph (F)(606) of rule 1301:7-7-06 of the Administrative Code).
  2. Liquefied petroleum gases and natural gases regulated by rule 1301:7-7-38 of the Administrative Code.
  3. Fuel-gas systems and appliances regulated under the International Fuel Gas Code as listed in rule 1301:7-7-47 of the Administrative Code other than gaseous hydrogen systems and appliances.
  4. Pyrophoric gases in accordance with rule 1301:7-7-41 of the Administrative Code.
Permits shall be required as set forth in rule 1301:7-7-01 of the Administrative Code.

The following words and terms shall, for the purposes of this rule and as used elsewhere in this code, have the meanings shown herein.

"Bulk hydrogen compressed gas system." An assembly of equipment, consisting of, but not limited to, storage containers, pressure regulators, pressure relief devices, vaporizers, manifolds and piping, with a storage capacity of more than 400 ft3 (scf)(11 m3) of compressed hydrogen gas, including unconnected reserves integral to the system. The bulk system terminates at the point where the gas supply, at service pressure, first enters the supply line. The containers are either stationary or portable, and the gas is stored as a compressed gas.

"Bulk liquefied hydrogen gas system." An assembly of equipment, consisting of, but not limited to, storage containers, pressure regulators, pressure relief devices, vaporizers, manifolds and piping, with a storage capacity of more than 39.7 gallons (150 L) of liquefied hydrogen, including unconnected reserves integral to the system. The bulk system terminates at the point where the gas supply, at service pressure, first enters the supply line. The containers are either stationary or portable, and the gas is stored as a cryogenic fluid.

"Flammable gas." A material which is a gas at 68°F (20°C) or less at 14.7 pounds per square inch atmosphere (psia) (101 kPa) of pressure [a material that has a boiling point of 68°F (20°C) or less at 14.7 psia (101 kPa)] which:

  1. Is ignitable at 14.7 psia (101 kPa) when in a mixture of 13 per cent or less by volume with air; or
  2. Has a flammable range at 14.7 psia (101 kPa) with air of at least 12 per cent, regardless of the lower limit.

The limits specified shall be determined at 14.7 psi (101 kPa) of pressure and a temperature of 68°F (20°C) in accordance with ASTM E 681 as listed in rule 1301:7-7-47 of the Administrative Code.

"Flammable liquefied gas." A liquefied compressed gas which, under a charged pressure, is partially liquid at a temperature of 68°F (20°C) and which is flammable.

"Metal hydride." A generic name for compounds composed of metallic element(s) and hydrogen.

"Metal hydride storage system." A closed system consisting of a group of components assembled as a package to contain metal-hydrogen compounds for which there exists an equilibrium condition where the hydrogen-absorbing metal alloy(s), hydrogen gas, and the metal-hydrogen compound(s) coexist and where only hydrogen gas is released from the system in normal use.

The storage and use of flammable gases in amounts not exceeding the maximum allowable quantity per control area indicated in paragraph (C)(1)(2703.1) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701) and (C)(2703) of rule 1301:7-7-27 of the Administrative Code, and paragraphs (A)(3501) and (C)(3503) of this rule.

Flammable gases shall not be stored or used in Group A, E, I or R occupancies or in offices in Group B occupancies.

Exceptions:
  1. Cylinders of nonliquefied compressed gases not exceeding a capacity of 250 cubic feet (7.08 m3) or liquefied gases not exceeding a capacity of 40 pounds (18 kg) each at normal temperature and pressure (NTP) used for maintenance purposes, patient care or operation of equipment.
  2. Food service operations in accordance with paragraph (C)(2)(a)(vii)(3803.2.1.7) of rule 1301:7-7-38 of the Administrative Code.
Medical gas system supply cylinders shall be located in medical gas storage rooms or gas cabinets as set forth in paragraph (F)(3006) of rule 1301:7-7-30 of the Administrative Code.
The aggregate quantities of flammable gases used for maintenance purposes and operation of equipment shall not exceed the maximum allowable quantity per control area indicated in Table 2703.1.1(1) of rule 1301:7-7-27 of the Administrative Code.
Cylinders and pressure vessels for flammable gases shall be designed, constructed, installed, tested and maintained in accordance with rule 1301:7-7-30 of the Administrative Code.
Compressed gas systems conveying flammable gases shall be provided with approved manual or automatic emergency shutoff valves that can be activated at each point of use and at each source.
A manual or automatic fail-safe emergency shutoff valve shall be installed on supply piping at the cylinder or bulk source. Manual or automatic cylinder valves are allowed to be used as the required emergency shutoff valve when the source of supply is limited to unmanifolded cylinder sources.
A manual or automatic emergency shutoff valve shall be installed on the supply piping at the point of use or at a point where the equipment using the gas is connected to the supply system.

Ignition sources in areas containing flammable gases in storage or in use shall be controlled in accordance with paragraph (C)(7)(2703.7) of rule 1301:7-7-27 of the Administrative Code.

Exception: Fuel gas systems connected to building service utilities in accordance with the International Fuel Gas Code as listed in rule 1301:7-7-47 of the Administrative Code.
Static-producing equipment located in flammable gas storage areas shall be grounded.
"No Smoking" signs shall be posted at entrances to rooms and in areas containing flammable gases in accordance with paragraph (C)(7)(a)(2703.7.1) of rule 1301:7-7-27 of the Administrative Code.
Electrical wiring and equipment shall be installed and maintained in accordance with paragraph (E)(605) of rule 1301:7-7-06 of the Administrative Code and NFPA 70 as listed in rule 1301:7-7-47 of the Administrative Code.
Exposed noncurrent-carrying metal parts, including metal gas piping systems, that are part of flammable gas supply systems located in a hazardous (electrically classified) location shall be bonded to a grounded conductor in accordance with the provisions of NFPA 70 as listed in rule 1301:7-7-47 of the Administrative Code.
Static-producing equipment located in flammable gas storage or use areas shall be grounded.

Containers of liquefied flammable gases and flammable gases in solution shall be positioned in the upright position or positioned so that the pressure relief valve is in direct contact with the vapor space of the container.

Exceptions:
  1. Containers of flammable gases in solution with a capacity of 1.3 gallons (5 L) or less.
  2. Containers of flammable liquefied gases, with a capacity not exceeding 1.3 gallons (5 L), designed to preclude the discharge of liquid from safety relief devices.
The storage and use of flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in paragraph (C)(1)(2703.1) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with rule 1301:7-7-27 of the Administrative Code and this rule.
Indoor storage of flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(1) of rule 1301:7-7-27 of the Administrative Code, shall be in accordance with paragraphs (A)(2701), (C)(2703) and (D)(2704) of rule 1301:7-7-27 of the Administrative Code, and this rule.
Buildings or portions thereof containing flammable gases shall be provided with explosion control in accordance with paragraph (K)(911) of rule 1301:7-7-09 of the Administrative Code.
Outdoor storage of flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(3) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701), (C)(2703) and (D)(2704) of rule 1301:7-7-27 of the Administrative Code, and this rule.

Outdoor storage or use of flammable compressed gases shall be located from a lot line, public street, public alley, public way or building not associated with the manufacture or distribution of such gases in accordance with Table 3504.2.1 of this rule.

TABLE 3504.2.1
FLAMMABLE GASES-DISTANCE FROM STORAGE TO EXPOSURES

MAXIMUM AMOUNT
PER STORAGE AREA
(cubic feet)
MINIMUM
DISTANCE
BETWEEN
STORAGE AREAS
(feet)
MINIMUM
DISTANCE TO LOT
LINES OF
PROPERTY THAT
CAN BE BUILT
UPON (feet)a
MINIMUM
DISTANCE TO
PUBLIC STREETS,
PUBLIC ALLEYS
OR PUBLIC WAYS
(feet)a
MINIMUM DISTANCE TO BUILDINGS ON THE SAME PROPERTY
Nonrated construction
or openings within
25 feet
2-hour construction
and no openings
within 25 feet
4-hour construction
and no openings
within 25 feet
0-4,255555500
4,226-21,1251010101050
21,126-50,7001015152050
50,701-84,5001020202050
84,501 or greater2025252050
For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m3.
a. The minimum required distances shall not apply when fire barriers without openings or penetrations having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the storage and the exposure. The configuration of the fire barrier shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.
Where weather protection is provided for sheltering outdoor flammable gas storage or use areas, such areas shall be constructed in accordance with paragraph (D)(13)(2704.13) of rule 1301:7-7-27 of the Administrative Code and the building code as listed in rule 1301:7-7-47 of the Administrative Code. Outdoor storage or use of flammable compressed gases shall be located from a lot line, public street, public alley or public way in accordance with Table 3504.2.1 of this rule, except that note a of Table 3504.2.1 of this rule shall not apply to areas sheltered by weather protection.
The use of flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(1) or 2703.1.1(3) of rule 1301:7-7-27 of the Administrative Code shall be in accordance with paragraphs (A)(2701), (C)(2703) and (E)(2705) of rule 1301:7-7-27 of the Administrative Code, and this rule.
The storage and use of flammable cryogenic fluids shall be in accordance with paragraph (F)(2)(3506.2) to (F)(4)(g)(iii)(3506.4.8.3) of this rule and rule 1301:7-7-32 of the Administrative Code.
Storage of flammable cryogenic fluids in stationary containers outside of buildings is prohibited within the limits established by law as the limits of districts in which such storage is prohibited.
Above-ground tanks for the storage of liquid hydrogen shall be in accordance with paragraphs (F)(3)(3506.3) to (F)(3)(b)(i)(3506.3.2.1) of this rule.
The inner vessel of storage tanks in liquid hydrogen service shall be designed and constructed in accordance with Section VIII, Division 1 of the ASME Boiler and Pressure Vessel Code as listed in rule 1301:7-7-47 of the Administrative Code and shall be vacuum jacketed in accordance with paragraph (F)(3)(b)(3506.3.2) of this rule.
The vacuum jacket used as an outer vessel for storage tanks in liquid hydrogen service shall be of welded steel construction designed to withstand the maximum internal and external pressure to which it will be subjected under operating conditions to include conditions of emergency pressure relief of the annular space between the inner and outer vessel. The jacket shall be designed to withstand a minimum collapsing pressure differential of 30 psi (207 kPa).
A connection shall be provided on the exterior of the vacuum jacket to allow measurement of the pressure within the annular space between the inner and outer vessel. The connection shall be fitted with a bellows-sealed or diaphragm-type valve equipped with a vacuum gauge tube that is shielded to protect against damage from impact.
Underground tanks for the storage of liquid hydrogen shall be in accordance with paragraphs (F)(4)(a)(3506.4.1) to (F)(4)(g)(iii)(3506.4.8.3) of this rule.
Storage tanks for liquid hydrogen shall be designed and constructed in accordance with ASME Boiler and Pressure Vessel Code (Section VIII, Division 1) as listed in rule 1301:7-7-47 of the Administrative Code and shall be vacuum jacketed in accordance with paragraph (F)(4)(g)(3506.4.8) of this rule.

Storage tanks shall be located outside in accordance with the following:

(i) Tanks and associated equipment shall be located with respect to foundations and supports of other structures such that the loads carried by the latter cannot be transmitted to the tank.

(ii) The distance from any part of the tank to the nearest wall of a basement, pit, cellar or lot line shall not be less than 3 feet (914 mm).

(iii) A minimum distance of 1 foot (305 mm), shell to shell, shall be maintained between underground tanks.

The tank shall be buried such that the top of the vacuum jacket is covered with a minimum of 1 foot (305 mm) of earth and with concrete a minimum of 4 inches (102 mm) thick placed over the earthen cover. The concrete shall extend a minimum of 1 foot (305 mm) horizontally beyond the footprint of the tank in all directions. Underground tanks shall be set on firm foundations constructed in accordance with the building code as listed in rule 1301:7-7-47 of the Administrative Code and surrounded with at least 6 inches (152 mm) of noncorrosive inert material, such as sand.

Exception: The vertical extension of the vacuum jacket as required for service connections.
Tanks and systems shall be secured against accidental dislodgement in accordance with this rule.
Vent pipes for underground storage tanks shall be in accordance with paragraph (I)(5)(d)(2209.5.4) of rule 1301:7-7-22 of the Administrative Code and paragraph (C)(3)(3203.3) of rule 1301:7-7-32 of the Administrative Code.
Underground liquid hydrogen piping shall be vacuum jacketed or protected by an approved means and designed in accordance with rule 1301:7-7-32 of the Administrative Code.
An approved means or method shall be provided to prevent the overfill of all storage tanks.
The vacuum jacket shall be designed and constructed in accordance with Section VIII of ASME Boiler and Pressure Vessel Code as listed in rule 1301:7-7-47 of the Administrative Code and shall be designed to withstand the anticipated loading, including loading from vehicular traffic, where applicable. Portions of the vacuum jacket installed below grade shall be designed to withstand anticipated soil, seismic and hydrostatic loading.
The vacuum jacket shall be constructed of stainless steel or other approved corrosion-resistant material.
The vacuum jacket shall be protected by approved or listed corrosion-resistant materials or an engineered cathodic protection system. Where cathodic protection is utilized, an approved maintenance schedule shall be established. Exposed components shall be inspected at least twice a year. Maintenance and inspection events shall be recorded and those records shall be maintained on the premises for a minimum of three years and made available to the fire code official upon request.
An approved method shall be provided to indicate loss of vacuum within the vacuum jacket(s).
The storage and use of metal hydride storage systems shall be in accordance with paragraphs (A)(3501), (C)(3503), (D)(3504), (E)(3505) and (G)(3507) of this rule. Those portions of the system that are used as a means to store or supply hydrogen shall also comply with rules 1301:7-7-27 and 1301:7-7-30 of the Administrative Code as applicable.
The hazard classification of the metal hydride storage system, as required by paragraph (A)(2)(b)(2701.2.2) of rule 1301:7-7-27 of the Administrative Code, shall be based on the hydrogen stored without regard to the metal hydride content.
Metal hydride storage systems shall be listed or approved for the application and designed in a manner that prevents the addition or removal of the metal hydride by other than the original equipment manufacturer.
Compressed gas containers, cylinders and tanks shall be designed and constructed in accordance with paragraph (C)(2)(3003.2) of rule 1301:7-7-30 of the Administrative Code.
Metal hydride storage system cylinders, containers or tanks shall be inspected, tested and requalified for service at not less than five year intervals.
Marking and labeling of cylinders, containers, tanks and systems shall be in accordance with paragraph (C)(4)(3003.4) of rule 1301:7-7-30 of the Administrative Code and paragraphs (G)(1)(e)(i) (3507.1.5.1) to (G)(1)(e)(iv)(3507.1.5.4) of this rule.

Metal hydride storage systems shall be marked with the following:

(a) Manufacturer's name;

(b) Service life indicating the last date the system can be used;

(c) A unique code or serial number specific to the unit;

(d) System name or product code that identifies the system by the type of chemistry used in the system;

(e) Emergency contact name, telephone number or other contact information; and

(f) Limitations on refilling of containers to include rated charging pressure and capacity.

Metal hydride storage system valves shall be marked with the following:

(a) Manufacturer's name;

(b) Service life indicating the last date the valve can be used; and

(c) Metal hydride service in which the valve can be used, or a product code that is traceable to this information.

Metal hydride storage system pressure relief devices shall be marked with the following:

  1. Manufacturer's name;
  2. Metal hydride service in which the device can be used, or a product code that is traceable to this information; and
  3. Activation parameters to include temperature, pressure or both.

(a) 3507.1.5.3.1 Pressure relief devices integral to container valves.
The required markings for pressure relief devices that are integral components of valves used on cylinders, containers and tanks shall be allowed to be placed on the valve.

Cylinders, containers and tanks used in metal hydride storage systems shall be marked with the following:

(a) Manufacturer's name;

(b) Design specification to which the vessel was manufactured;

(c) Authorized body approving the design and initial inspection and test of the vessel;

(d) Manufacturer's original test date;

(e) Unique serial number for the vessel.

(f) Service life identifying the last date the vessel can be used; and

(g) System name or product code that identifies the system by the type of chemistry used in the system.

Metal hydride storage systems, whether full or partially full, shall not be exposed to artificially created high temperatures exceeding 125°F (52°C) or subambient (low) temperatures unless designed for use under the exposed conditions.
Metal hydride storage systems shall not be placed in areas where they are capable of being damaged by falling objects.
Piping, including tubing, valves, fittings and pressure regulators, serving metal hydride storage systems shall be maintained gas tight to prevent leakage.
Leaking systems shall be removed from service.
The refilling of listed or approved metal hydride storage systems shall be in accordance with the listing requirements and manufacturers' instructions.
The refilling of metal hydride storage systems serving powered industrial trucks shall be in accordance with paragraph (I)(309) of rule 1301:7-7-03 of the Administrative Code.
The purity of hydrogen used for the purpose of refilling containers shall be in accordance with the listing and the manufacturer's instructions.
Electrical components for metal hydride storage systems shall be designed, constructed, and installed in accordance with NFPA 70 as listed in rule 1301:7-7-47 of the Administrative Code.
Portable containers or systems shall comply with paragraphs (F)(2)(a) (3507.2.1) to (F)(2)(b)(3507.2.2) of this rule.
Containers, cylinders and tanks shall be secured in accordance with paragraph (C)(5)(c)(3003.5.3) of rule 1301:7-7-30 of the Administrative Code.
Where a metal hydride storage system is used on mobile equipment, the equipment shall be designed to restrain containers, cylinders or tanks from dislodgement, slipping or rotating when the equipment is in motion.

Metal hydride storage systems used on motorized equipment, shall be installed in a manner that protects valves, pressure regulators, fittings and controls against accidental impact.

(a) 3507.2.1.2.1 Protection from damage.
Metal hydride storage systems, including cylinders, containers, tanks and fittings, shall not extend beyond the platform of the mobile equipment.

Valves on containers, cylinders and tanks shall remain closed except when containers are connected to closed systems and ready for use.

Effective Date: November 1, 2011

Prior Effective Dates: 7/1/79; 6/1/85; 6/15/92; 7/1/93; 9/1/95; 3/30/98; 9/1/05; 7/1/07

UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING