UpCodes logo
Table of contentsContents
The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated construction separation of adjacent spaces to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings.
The following words and terms shall, for the purposes of this chapter, and as used elsewhere in this code, have the meanings shown herein.
ANNULAR SPACE. The opening around the penetrating item.
BUILDING ELEMENT. A fundamental component of building construction, listed in Table 601, which may or may not be of fire-resistance-rated construction and is constructed of materials based on the building type of construction.
CEILING RADIATION DAMPER. A listed device installed in a ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly to limit automatically the radiative heat transfer through an air inlet/outlet opening.
COMBINATION FIRE/SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon the detection of heat and resist the passage of flame and smoke. The device is installed to operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a fire command center.
COMBUSTIBLE MATERIAL. Any material not defined as noncombustible.
DRAFTSTOP. A material, device or construction installed to restrict the movement of air within open spaces of concealed areas of building components such as crawl spaces, floor/ceiling assemblies, roof/ceiling assemblies and attics.
F RATING. The time period that the through-penetration firestop system limits the spread of fire through the penetration when tested in accordance with ASTM E 814 or UL 1479.
FIRE BARRIER. A fire-resistance-rated wall assembly of materials designed to restrict the spread of fire in which continuity is maintained.
FIRE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon detection of heat and resist the passage of flame. Fire dampers are classified for use in either static systems that will automatically shut down in the event of a fire, or in dynamic systems that continue to operate during a fire. A dynamic fire damper is tested and rated for closure under elevated temperature airflow.
FIRE DOOR. The door component of a fire door assembly.
FIRE DOOR ASSEMBLY. Any combination of a fire door, frame, hardware and other accessories that together provide a specific degree of fire protection to the opening.
FIRE PARTITION. A vertical assembly of materials designed to restrict the spread of fire in which openings are protected.
FIRE PROTECTION RATING. The period of time that an opening protective will maintain the ability to confine a fire as determined by tests prescribed in Section 715. Ratings are stated in hours or minutes.
FIRE RESISTANCE. That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use.
FIRE-RESISTANCE RATING. The period of time a building element, component or assembly maintains the ability to confine a fire, continues to perform a given structural function, or both, as determined by the tests, or the methods based on tests, prescribed in Section 703.
FIRE-RESISTANT JOINT SYSTEM. An assemblage of specific materials or products that are designed, tested and fire-resistance rated in accordance with either ASTM E 1966 or UL 2079 to resist for a prescribed period of time the passage of fire through joints made in or between fire-resistance-rated assemblies.
FIRE SEPARATION DISTANCE. The distance measured from the building face to one of the following:
  1. The closest interior lot line;
  2. To the centerline of a street, an alley or public way; or
  3. To an imaginary line between two buildings on the property.
The distance shall be measured at right angles from the face of the wall.
FIRE WALL. A fire-resistance-rated wall having protected openings, which restricts the spread of fire and extends continuously from the foundation to or through the roof, with sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall.
FIRE WINDOW ASSEMBLY. A window constructed and glazed to give protection against the passage of fire.
FIREBLOCKING. Building materials or materials approved for use as fireblocking, installed to resist the free passage of flame to other areas of the building through concealed spaces.
FLOOR FIRE DOOR ASSEMBLY. A combination of a fire door, a frame, hardware and other accessories installed in a horizontal plane, which together provide a specific degree of fire protection to a through-opening in a fire-resistance-rated floor (see Section 712.8).
HORIZONTAL ASSEMBLY. A fire-resistance-rated floor or roof assembly of materials designed to restrict the spread of fire in which continuity is maintained.
JOINT. The linear opening in or between adjacent fire-resistance-rated assemblies that is designed to allow independent movement of the building in any plane caused by thermal, seismic, wind or any other loading.
MEMBRANE PENETRATION. An opening made through one side (wall, floor or ceiling membrane) of an assembly.
MEMBRANE-PENETRATION FIRESTOP. A material, device or construction installed to resist for a prescribed time period the passage of flame and heat through openings in a protective membrane in order to accommodate cables, cable trays, conduit, tubing, pipes or similar items.
MINERAL FIBER. Insulation composed principally of fibers manufactured from rock, slag or glass, with or without binders.
MINERAL WOOL. Synthetic vitreous fiber insulation made by melting predominately igneous rock or furnace slag, and other inorganic materials, and then physically forming the melt into fibers.
NONCOMBUSTIBLE MATERIALS. Materials that, when tested in accordance with ASTM E 136, have at least three of four specimens tested meeting all of the following criteria:
The recorded temperature of the surface and interior thermocouples shall not at any time during the test rise more than 54°F (30°C) above the furnace temperature at the beginning of the test.
There shall not be flaming from the specimen after the first thirty seconds.
If the weight loss of the specimen during testing exceeds fifty percent, the recorded temperature of the surface and the interior thermocouples shall not at any time during the test rise above the furnace air temperature at the beginning of the test, and there shall not be flaming of the specimen.
SELF-CLOSING. As applied to a fire door or other opening protective, means equipped with a device that will ensure closing after having been opened.
SHAFT. An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and roof.
SHAFT ENCLOSURE. The walls or construction forming the boundaries of a shaft.
SMOKE BARRIER. A continuous membrane, either vertical or horizontal, such as a wall, floor or ceiling assembly, that is designed and constructed to restrict the movement of smoke.
SMOKE COMPARTMENT. A space within a building enclosed by smoke barriers on all sides, including the top and bottom.
SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to resist the passage of smoke. The device is installed to operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a fire command center.
SPLICE. The result of a factory and/or field method of joining or connecting two or more lengths of a fire-resistant joint system into a continuous entity.
T RATING. The time period that the penetration firestop system, including the penetrating item, limits the maximum temperature rise to 325°F (163°C) above its initial temperature through the penetration on the nonfire side when tested in accordance with ASTM E 814 or UL 1479.
THROUGH PENETRATION. An opening that passes through an entire assembly.
THROUGH-PENETRATION FIRESTOP SYSTEM. An assemblage of specific materials or products that are designed, tested and fire-resistance rated to resist for a prescribed period of time the spread of fire through penetrations. The F and T rating criteria for penetration firestop systems shall be in accordance with ASTM E 814 or UL 1479. See definitions of "F rating" and "T rating."
Materials prescribed herein for fire resistance shall conform to the requirements of this chapter.
The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire-resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating.
Exception: In determining the fire-resistance rating of exterior bearing walls, compliance with the ASTM E 119 or UL 263 criteria for unexposed surface temperature rise and ignition of cotton waste due to passage of flame or gases is required only for a period of time corresponding to the required fire-resistance rating of an exterior nonbearing wall with the same fire separation distance, and in a building of the same group. When the fire-resistance rating determined in accordance with this exception exceeds the fire-resistance rating determined in accordance with ASTM E 119 or UL 263, the fire exposure time period, water pressure and application duration criteria for the hose stream test of ASTM E 119 or UL 263 shall be based upon the fire-resistance rating determined in accordance with this exception.
Interior walls and partitions of nonsymmetrical construction shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests conducted in compliance with ASTM E 119 or UL 263. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side (see Section 705.5 for exterior walls).
Combustible aggregates are permitted in gypsum and portland cement concrete mixtures for fire-resistance-rated construction. Any component material or admixture is permitted in assemblies if the resulting tested assembly meets the fire-resistance test requirements of this code.
Fire-resistance-rated assemblies tested under ASTM E 119 or UL 263 shall not be considered to be restrained unless evidence satisfactory to the building official is furnished by the registered design professional showing that the construction qualifies for a restrained classification in accordance with ASTM E 119 or UL 263. Restrained construction shall be identified on the plans.
Upcodes Diagrams
The application of any of the alternative methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E 119 or UL 263. The required fire resistance of a building element, component or assembly shall be permitted to be established by any of the following methods or procedures:
  1. Fire-resistance designs documented in referenced publications approved in accordance with this code.
  2. Prescriptive designs of fire-resistance-rated building elements, components or assemblies as prescribed in Section 720.
  3. Calculations in accordance with Section 721.
  4. Engineering analysis based on a comparison of building element, component or assemblies designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E 119 or UL 263.
  5. Alternative protection methods as allowed by Sections 106.5 or 114.3.
Upcodes Diagrams
The tests indicated in Sections 703.4.1 and 703.4.2 shall serve as criteria for acceptance of building materials as set forth in Sections 602.2, 602.3 and 602.4 in Type I, II, III and IV construction. The term "noncombustible" does not apply to the flame spread characteristics of interior finish or trim materials. A material shall not be classified as a noncombustible building construction material if it is subject to an increase in combustibility or flame spread beyond the limitations herein established through the effects of age, moisture or other atmospheric conditions.
Materials required to be noncombustible shall be tested in accordance with ASTM E 136.
Materials having a structural base of noncombustible material as determined in accordance with Section 703.4.1 with a surfacing not more than 0.125 inch (3.18 mm) thick that has a flame spread index not greater than 50 when tested in accordance with ASTM E 84 or UL 723 shall be acceptable as noncombustible materials.
Fire-resistance-rated glazing, when tested in accordance with ASTM E 119 or UL 263 and complying with the requirements of Section 707, shall be permitted. Fire-resistance-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and the identifier "W-XXX," where the "XXX" is the fire-resistance rating in minutes. Such label or identification shall be issued by an approved agency and shall be permanently affixed to the glazing.
The fire-resistance ratings of structural members and assemblies shall comply with this section and the requirements for the type of construction as specified in Table 601. The fire-resistance ratings shall not be less than the ratings required for the fire-resistance-rated assemblies supported by the structural members.
Exception: Fire barriers, fire partitions, smoke barriers and horizontal assemblies as provided in Sections 707.5, 709.4, 710.4 and 712.4, respectively.
Where columns are required to be fire-resistance rated, the entire column shall be provided individual encasement protection by protecting it on all sides for the full column length, including connections to other structural members, with materials having the required fire-resistance rating. Where the column extends through a ceiling, the encasement protection shall be continuous from the top of the foundation or floor/ceiling assembly below through the ceiling space to the top of the column.
Members of the primary structural frame other than columns that are required to have a fire-resistance rating and support more than two floors or one floor and roof, or support a load-bearing wall or a nonload-bearing wall more than two stories high, shall be provided individual encasement protection by protecting them on all sides for their full length, including connections to other structural members, with materials having the required fire-resistance rating.
Exception: Individual encasement protection on all sides shall be permitted on all exposed sides provided the extent of protection is in accordance with the required fire-resistance rating, as determined in Section 703.
Secondary members that are required to have a fire-resistance rating shall be protected by individual encasement protection, by the membrane or ceiling of a horizontal assembly in accordance with Section 712, or by a combination of both.
Upcodes Diagrams
King studs and boundary elements that are integral elements in load-bearing walls of light-frame construction shall be permitted to have required fire-resistance ratings provided by the membrane protection provided for the load-bearing wall.
The required thickness and construction of fire-resistance-rated assemblies enclosing trusses shall be based on the results of full-scale tests or combinations of tests on truss components or on approved calculations based on such tests that satisfactorily demonstrate that the assembly has the required fire resistance.
The edges of lugs, brackets, rivets and bolt heads attached to structural members shall be permitted to extend to within 1 inch (25 mm) of the surface of the fire protection.
Thickness of protection for concrete or masonry reinforcement shall be measured to the outside of the reinforcement except that stirrups and spiral reinforcement ties are permitted to project not more than 0.5-inch (12.7 mm) into the protection.
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protective covering of a structural member that is required to be individually encased.
Where the fire protective covering of a structural member is subject to impact damage from moving vehicles, the handling of merchandise or other activity, the fire protective covering shall be protected by corner guards or by a substantial jacket of metal or other noncombustible material to a height adequate to provide full protection, but not less than 5 feet (1524 mm) from the finished floor.
Exception: Corner protection is not required on concrete columns in open or enclosed parking garages.
Load-bearing structural members located within the exterior walls or on the outside of a building or structure shall be provided with the highest fire-resistance rating as determined in accordance with the following:
  1. As required by Table 601 for the type of building element based on the type of construction of the building;
  2. As required by Table 601 for exterior bearing walls based on the type of construction; and
  3. As required by Table 602 for exterior walls based on the fire separation distance.
Fire protection is not required at the bottom flange of lintels, shelf angles and plates, spanning not more than 6 feet (1829 mm) whether part of the primary structural frame or not, and from the bottom flange of lintels, shelf angles and plates not part of the primary structural frame, regardless of span.
Fire-resistance ratings for the isolation system shall meet the fire-resistance rating required for the columns, walls or other structural elements in which the isolation system is installed in accordance with Table 601. Isolation systems required to have a fire-resistance rating shall be protected with approved materials or construction assemblies designed to provide the same degree of fire resistance as the structural element in which it is installed when tested in accordance with ASTM E 119 or UL 263 (see Section 703.2).
Such isolation system protection applied to isolator units shall be capable of retarding the transfer of heat to the isolator unit in such a manner that the required gravity load-carrying capacity of the isolator unit will not be impaired after exposure to the standard time-temperature curve fire test prescribed in ASTM E 119 or UL 263 for a duration not less than that required for the fire-resistance rating of the structure element in which it is installed.
Such isolation system protection applied to isolator units shall be suitably designed and securely installed so as not to dislodge, loosen, sustain damage or otherwise impair its ability to accommodate the seismic movements for which the isolator unit is designed and to maintain its integrity for the purpose of providing the required fire-resistance protection.
The application of SFRM shall be consistent with the fire-resistance rating and the listing, including, but not limited to, minimum thickness and dry density of the applied SFRM, method of application, substrate surface conditions and the use of bonding adhesives, sealants, reinforcing or other materials.
The application of SFRM shall be in accordance with the manufacturer's installation instructions. The instructions shall include, but are not limited to, substrate temperatures and surface conditions and SFRM handling, storage, mixing, conveyance, method of application, curing and ventilation.
The SFRM shall be applied to a substrate in compliance with Sections 704.13.3.1 through 704.13.3.2.
Substrates to receive SFRM shall be free of dirt, oil, grease, release agents, loose scale and any other condition that prevents adhesion. The substrates shall also be free of primers, paints and encapsulants other than those fire tested and listed by a nationally recognized testing agency. Primed, painted or encapsulated steel shall be allowed, provided that testing has demonstrated that required adhesion is maintained.
Where the SFRM is to be applied over primers, paints or encapsulants other than those specified in the listing, the material shall be field tested in accordance with ASTM E 736. Where testing of the SFRM with primers, paints or encapsulants demonstrates that required adhesion is maintained, SFRM shall be permitted to be applied to primed, painted or encapsulated wide flange steel shapes in accordance with the following conditions:
  1. The beam flange width does not exceed 12 inches (305 mm); or
  2. The column flange width does not exceed 16 inches (400 mm); or
  3. The beam or column web depth does not exceed 16 inches (400 mm).
  4. The average and minimum bond strength values shall be determined based on a minimum of five bond tests conducted in accordance with ASTM E 736. Bond tests conducted in accordance with ASTM E 736 shall indicate a minimum average bond strength of 80 percent and a minimum individual bond strength of 50 percent, when compared to the bond strength of the SFRM as applied to clean uncoated 1/8-inch-thick (3 mm) steel plate.
A minimum ambient and substrate temperature of 40°F (4.44°C) shall be maintained during and for a minimum of 24 hours after the application of the SFRM, unless the manufacturer's installation instructions allow otherwise.
The finished condition of SFRM applied to structural members or assemblies shall not, upon complete drying or curing, exhibit cracks, voids, spalls, delamination or any exposure of the substrate. Surface irregularities of SFRM shall be deemed acceptable.
Exterior walls shall comply with this section.
Cornices, eave overhangs, exterior balconies and similar projections extending beyond the exterior wall shall conform to the requirements of this section and Section 1406. Exterior egress balconies and exterior exit stairways shall also comply with Sections 1019 and 1026, respectively. Projections shall not extend beyond the distance determined by the following three methods, whichever results in the lesser projection:
  1. A point one-third the distance from the exterior face of the wall to the lot line where protected openings or a combination of protected and unprotected openings are required in the exterior wall.
  2. A point one-half the distance from the exterior face of the wall to the lot line where all openings in the exterior wall are permitted to be unprotected or the building is equipped throughout with an automatic sprinkler system installed under the provisions of Section 705.8.2.
  3. More than 12 inches (305 mm) into areas where openings are prohibited.
Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with this section.
Upcodes Diagrams
Projections from walls of Type I or II construction shall be of noncombustible materials or combustible materials as allowed by Sections 1406.3 and 1406.4.
Projections from walls of Type III, IV or V construction shall be of any approved material.
Combustible projections located where openings are not permitted or where protection of openings is required shall be of at least 1-hour fire-resistance-rated construction, Type IV construction, fire-retardant-treated wood or as required by Section 1406.3.
Exception: Type V construction shall be allowed for R-3 occupancies.
For the purposes of determining the required wall and opening protection and roof-covering requirements, buildings on the same lot shall be assumed to have an imaginary line between them.
Where a new building is to be erected on the same lot as an existing building, the location of the assumed imaginary line with relation to the existing building shall be such that the exterior wall and opening protection of the existing building meet the criteria as set forth in Sections 705.5 and 705.8.
Exception: Two or more buildings on the same lot shall either be regulated as separate buildings or shall be considered as portions of one building if the aggregate area of such buildings is within the limits specified in Chapter 5 for a single building. Where the buildings contain different occupancy groups or are of different types of construction, the area shall be that allowed for the most restrictive occupancy or construction.
Exterior walls shall be of materials permitted by the building type of construction.
Upcodes Diagrams
Exterior walls shall be fire-resistance rated in accordance with Tables 601 and 602 and this section. The required fire-resistance rating of exterior walls with a fire separation distance of greater than 10 feet (3048 mm) shall be rated for exposure to fire from the inside. The required fire-resistance rating of exterior walls with a fire separation distance of less than or equal to 10 feet (3048 mm) shall be rated for exposure to fire from both sides. Where referenced in Section 705, an unoccupied space on an adjoining property may be included in the required fire separation distance, provided that the adjoining property is dedicated or deeded so as to preclude, for the life of the structure, the erection of any building or structure on such space (see Section 3781.02 of the Revised Code).
Upcodes Diagrams
The wall shall extend to the height required by Section 705.11 and shall have sufficient structural stability such that it will remain in place for the duration of time indicated by the required fire-resistance rating or shall be constructed as double fire walls in accordance with NFPA 221.
Where protected openings are not limited by Section 705.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 or UL 263 shall not apply. Where protected openings are limited by Section 705.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 or UL 263 shall not apply provided that a correction is made for radiation from the unexposed exterior wall surface in accordance with the following formula:
(Equation 7-1)
where:
Ae=Equivalent area of protected openings.
A=Actual area of protected openings.
Af=Area of exterior wall surface in the story under consideration exclusive of openings, on which the temperature limitations of ASTM E 119 or UL 263 for walls are exceeded.
Feo=An "equivalent opening factor" derived from Figure 705.7 based on the average temperature of the unexposed wall surface and the fire-resistance rating of the wall.
For SI: °C = [(°F) - 32] / 1.8.
FIGURE 705.7
EQUIVALENT OPENING FACTOR
Openings in exterior walls shall comply with Sections 705.8.1 through 705.8.6.
MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING PROTECTION
FIRE SEPARATION DISTANCE
(feet)
DEGREE OF OPENING PROTECTIONALLOWABLE AREAa
0 to less than 3b, cUnprotected, Nonsprinklered (UP, NS)Not Permitted
Unprotected, Sprinklered (UP, S)iNot Permitted
Protected (P)Not Permitted
3 to less than 5d, eUnprotected, Nonsprinklered (UP, NS)Not Permitted
Unprotected, Sprinklered (UP, S)i15%
Protected (P)15%
5 to less than 10e, fUnprotected, Nonsprinklered (UP, NS)10%h
Unprotected, Sprinklered (UP, S)i25%
Protected (P)25%
10 to less than 15e, f, gUnprotected, Nonsprinklered (UP, NS)15%h
Unprotected, Sprinklered (UP, S)i45%
Protected (P)45%
15 to less than 20f, gUnprotected, Nonsprinklered (UP, NS)25%
Unprotected, Sprinklered (UP, S)i75%
Protected (P)75%
20 to less than 25f, gUnprotected, Nonsprinklered (UP, NS)45%
Unprotected, Sprinklered (UP, S)iNo Limit
Protected (P)No Limit
25 to less than 30f, gUnprotected, Nonsprinklered (UP, NS)70%
Unprotected, Sprinklered (UP, S)iNo Limit
Protected (P)No Limit
30 or greaterUnprotected, Nonsprinklered (UP, NS)No Limit
Unprotected, Sprinklered (UP, S)iNot Required
Protected (P)Not Required
For SI: 1 foot = 304.8 mm.
UP, NS =Unprotected openings in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
UP, S =Unprotected openings in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
P=Openings protected with an opening protective assembly in accordance with Section 705.8.2.
  1. Values indicated are the percentage of the area of the exterior wall, per story.
  2. For the requirements for fire walls of buildings with differing heights, see Section 706.6.1.
  3. For openings in a fire wall for buildings on the same lot, see Section 706.8.
  4. The maximum percentage of unprotected and protected openings shall be 25 percent for Group R-3 occupancies.
  5. Unprotected openings shall not be permitted for openings with a fire separation distance of less than 15 feet for Group H-2 and H-3 occupancies.
  6. The area of unprotected and protected openings shall not be limited for Group R-3 occupancies, with afire separation distance of 5 feet or greater.
  7. The area of openings in an open parking structure with a fire separation distance of 10 feet or greater shall not be limited.
  8. Includes buildings accessory to Group R-3.
  9. Not applicable to Group H-1, H-2 and H-3 occupancies.
The maximum area of unprotected and protected openings permitted in an exterior wall in any story of a building shall not exceed the percentages specified in Table 705.8.
Exceptions:
  1. In other than Group H occupancies, unlimited unprotected openings are permitted in the first story above grade either:
    1. Where the wall faces a street and has a fire separation distance of more than 15 feet (4572 mm); or
    2. Where the wall faces an unoccupied space. The unoccupied space shall be on the same lot or dedicated for public use, shall not be less than 30 feet (9144 mm) in width and shall have access from a street by a posted fire lane in accordance with the fire code.
  2. Buildings whose exterior bearing walls, exterior nonbearing walls and exterior primary structural frame are not required to be fire-resistance rated shall be permitted to have unlimited unprotected openings.
Where openings are required to be protected, fire doors and fire shutters shall comply with Section 715.4 and fire window assemblies shall comply with Section 715.5.
Exception: Opening protectives are not required where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and the exterior openings are protected by a water curtain using automatic sprinklers approved for that use.
Where unprotected openings are permitted, windows and doors shall be constructed of any approved materials. Glazing shall conform to the requirements of Chapters 24 and 26.
Where both unprotected and protected openings are located in the exterior wall in any story of a building, the total area of openings shall be determined in accordance with the following:
(Equation 7-2)
where:
Ap=Actual area of protected openings, or the equivalent area of protected openings, Ae (see Section 705.7).
ap=Allowable area of protected openings.
Au=Actual area of unprotected openings.
au=Allowable area of unprotected openings.
Openings in exterior walls in adjacent stories shall be separated vertically to protect against fire spread on the exterior of the buildings where the openings are within 5 feet (1524 mm) of each other horizontally and the opening in the lower story is not a protected opening with a fire protection rating of not less than 3/4 hour. Such openings shall be separated vertically at least 3 feet (914 mm) by spandrel girders, exterior walls or other similar assemblies that have a fire-resistance rating of at least 1 hour or by flame barriers that extend horizontally at least 30 inches (762 mm) beyond the exterior wall. Flame barriers shall also have a fire-resistance rating of at least 1 hour. The unexposed surface temperature limitations specified in ASTM E 119 or UL 263 shall not apply to the flame barriers or vertical separation unless otherwise required by the provisions of this code.
Exceptions:
  1. This section shall not apply to buildings that are three stories or less above grade plane.
  2. This section shall not apply to buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
  3. Open parking garages.
For buildings on the same lot, opening protectives having a fire protection rating of not less than 3/4 hour shall be provided in every opening that is less than 15 feet (4572 mm) vertically above the roof of an adjacent building or structure based on assuming an imaginary line between them. The opening protectives are required where the fire separation distance between the imaginary line and the adjacent building or structure is less than 15 feet (4572 mm).
Exceptions:
  1. Opening protectives are not required where the roof assembly of the adjacent building or structure has a fire-resistance rating of not less than 1 hour for a minimum distance of 10 feet (3048 mm) from the exterior wall facing the imaginary line and the entire length and span of the supporting elements for the fire-resistance-rated roof assembly has a fire-resistance rating of not less than 1 hour.
  2. Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with Section 705.8.6.
Upcodes Diagrams
Joints made in or between exterior walls required by this section to have a fire-resistance rating shall comply with Section 714.
Exception: Joints in exterior walls that are permitted to have unprotected openings.
The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 714.4.
Penetrations by air ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings shall comply with Section 716.
Exception: Foundation vents installed in accordance with this code are permitted.
Parapets shall be provided on exterior walls of buildings.
Exceptions: A parapet need not be provided on an exterior wall where any of the following conditions exist:
  1. The wall is not required to be fire-resistance rated in accordance with Table 602 because of fire separation distance.
  2. The building has an area of not more than 1,000 square feet (93 m2) on any floor.
  3. Walls that terminate at roofs of not less than 2-hour fire-resistance-rated construction or where the roof, including the deck or slab and supporting construction, is constructed entirely of noncombustible materials.
  4. One-hour fire-resistance-rated exterior walls that terminate at the underside of the roof sheathing, deck or slab, provided:
    1. Where the roof/ceiling framing elements are parallel to the walls, such framing and elements supporting such framing shall not be of less than 1-hour fire-resistance-rated construction for a width of 4 feet (1220 mm) for Groups R and U and 10 feet (3048 mm) for other occupancies, measured from the interior side of the wall.
    2. Where roof/ceiling framing elements are not parallel to the wall, the entire span of such framing and elements supporting such framing shall not be of less than 1-hour fire-resistance-rated construction.
    3. Openings in the roof shall not be located within 5 feet (1524 mm) of the 1-hour fire-resistance-rated exterior wall for Groups R and U and 10 feet (3048 mm) for other occupancies, measured from the interior side of the wall.
    4. The entire building shall be provided with not less than a Class B roof covering.
  5. In Groups R-2 and R-3 where the entire building is provided with a Class C roof covering, the exterior wall shall be permitted to terminate at the underside of the roof sheathing or deck in Type III, IV and V construction, provided:
    1. The roof sheathing or deck is constructed of approved noncombustible materials or of fire-retardant-treated wood for a distance of 4 feet (1220 mm); or
    2. The roof is protected with 0.625-inch (16 mm) Type X gypsum board directly beneath the underside of the roof sheathing or deck, supported by a minimum of nominal 2-inch (51 mm) ledgers attached to the sides of the roof framing members for a minimum distance of 4 feet (1220 mm).
  6. Where the wall is permitted to have at least 25 percent of the exterior wall areas containing unprotected openings based on fire separation distance as determined in accordance with Section 705.8.
Upcodes Diagrams
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have noncombustible faces for the uppermost 18 inches (457 mm), including counterflashing and coping materials. The height of the parapet shall not be less than 30 inches (762 mm) above the point where the roof surface and the wall intersect. Where the roof slopes toward a parapet at a slope greater than two units vertical in 12 units horizontal (16.7-percent slope), the parapet shall extend to the same height as any portion of the roof within a fire separation distance where protection of wall openings is required, but in no case shall the height be less than 30 inches (762 mm).
Upcodes Diagrams
Upcodes Diagrams
Each portion of a building separated by one or more fire walls that comply with the provisions of this section shall be considered a separate building. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply.
Any wall located on a lot line between adjacent buildings, which is used or adapted for joint service between the two buildings, shall be constructed as a fire wall in accordance with Section 706. Party walls shall be constructed without openings and shall create separate buildings.
Exception: Openings in a party wall separating an anchor building and a mall shall be in accordance with Section 402.7.3.1.
Fire walls shall have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall for the duration of time indicated by the required fire-resistance rating or shall be constructed as double fire walls in accordance with NFPA 221.
Fire walls shall be of any approved noncombustible materials.
Exception: Buildings of Type V construction.
Fire walls shall have a fire-resistance rating of not less than that required by Table 706.4.
GROUPFIRE-RESISTANCE RATING (hours)
A, B, E, H-4, I, R-1, R-2, U3a
F-1, H-3b, H-5, M, S-13
H-1, H-24b
F-2, S-2, R-3, R-42
  1. In Type II or V construction, walls shall be permitted to have a 2-hour fire-resistance rating.
  2. For Group H-1, H-2 or H-3 buildings, also see Sections 415.4 and 415.5.
Upcodes Diagrams
Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 18 inches (457 mm) beyond the exterior surface of exterior walls.
Exceptions:
  1. Fire walls shall be permitted to terminate at the interior surface of combustible exterior sheathing or siding provided the exterior wall has a fire-resistance rating of at least 1 hour for a horizontal distance of at least 4 feet (1220 mm) on both sides of the fire wall. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour.
  2. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing, exterior siding or other noncombustible exterior finishes provided the sheathing, siding, or other exterior noncombustible finish extends a horizontal distance of at least 4 feet (1220 mm) on both sides of the fire wall.
  3. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing where the building on each side of the fire wall is protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Upcodes Diagrams
Where the fire wall intersects exterior walls, the fire-resistance rating and opening protection of the exterior walls shall comply with one of the following:
  1. The exterior walls on both sides of the fire wall shall have a 1-hour fire-resistance rating with 3/4-hour protection where opening protection is required by Section 705.8. The fire-resistance rating of the exterior wall shall extend a minimum of 4 feet (1220 mm) on each side of the intersection of the fire wall to exterior wall. Exterior wall intersections at fire walls that form an angle equal to or greater than 180 degrees (3.14 rad) do not need exterior wall protection.
  2. Buildings or spaces on both sides of the intersecting fire wall shall assume to have an imaginary lot line at the fire wall and extending beyond the exterior of the fire wall. The location of the assumed line in relation to the exterior walls and the fire wall shall be such that the exterior wall and opening protection meet the requirements set forth in Sections 705.5 and 705.8. Such protection is not required for exterior walls terminating at fire walls that form an angle equal to or greater than 180 degrees (3.14 rad).
Fire walls shall extend to the outer edge of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees and similar projections that are within 4 feet (1220 mm) of the fire wall.
Exceptions:
  1. Horizontal projecting elements without concealed spaces, provided the exterior wall behind and below the projecting element has not less than 1-hour fire-resistance-rated construction for a distance not less than the depth of the projecting element on both sides of the fire wall. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour.
  2. Noncombustible horizontal projecting elements with concealed spaces, provided a minimum 1-hour fire-resistance-rated wall extends through the concealed space. The projecting element shall be separated from the building by a minimum of 1-hour fire-resistance-rated construction for a distance on each side of the fire wall equal to the depth of the projecting element. The wall is not required to extend under the projecting element where the building exterior wall is not less than 1-hour fire-resistance rated for a distance on each side of the fire wall equal to the depth of the projecting element. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour.
  3. For combustible horizontal projecting elements with concealed spaces, the fire wall need only extend through the concealed space to the outer edges of the projecting elements. The exterior wall behind and below the projecting element shall be of not less than 1-hour fire-resistance-rated construction for a distance not less than the depth of the projecting elements on both sides of the fire wall. Openings within such exterior walls shall be protected by opening protectives having a fire-protection rating of not less than 3/4 hour.
Upcodes Diagrams
Fire walls shall extend from the foundation to a termination point at least 30 inches (762 mm) above both adjacent roofs.
Exceptions:
  1. Stepped buildings in accordance with Section 706.6.1.
  2. Two-hour fire-resistance-rated walls shall be permitted to terminate at the underside of the roof sheathing, deck or slab, provided:
    1. The lower roof assembly within 4 feet (1220 mm) of the wall has not less than a 1-hour fire-resistance rating and the entire length and span of supporting elements for the rated roof assembly has a fire-resistance rating of not less than 1 hour.
    2. Openings in the roof shall not be located within 4 feet (1220 mm) of the fire wall.
    3. Each building shall be provided with not less than a Class B roof covering.
  3. Walls shall be permitted to terminate at the underside of noncombustible roof sheathing, deck or slabs where both buildings are provided with not less than a Class B roof covering. Openings in the roof shall not be located within 4 feet (1220 mm) of the fire wall.
  4. In buildings of Type III, IV and V construction, walls shall be permitted to terminate at the underside of combustible roof sheathing or decks, provided:
    1. There are no openings in the roof within 4 feet (1220 mm) of the fire wall,
    2. The roof is covered with a minimum Class B roof covering, and
    3. The roof sheathing or deck is constructed of fire-retardant-treated wood for a distance of 4 feet (1220 mm) on both sides of the wall or the roof is protected with 5/8-inch (15.9 mm) Type X gypsum board directly beneath the underside of the roof sheathing or deck, supported by a minimum of 2-inch (51 mm) nominal ledgers attached to the sides of the roof framing members for a minimum distance of 4 feet (1220 mm) on both sides of the fire wall.
  5. In buildings designed in accordance with Section 509.2, fire walls located above the 3-hour horizontal assembly required by Section 509.2, Item 1 above shall be permitted to extend from the top of this horizontal assembly.
Where a fire wall serves as an exterior wall for a building and separates buildings having different roof levels, such wall shall terminate at a point not less than 30 inches (762 mm) above the lower roof level, provided the exterior wall for a height of 15 feet (4572 mm) above the lower roof is not less than 1-hour fire-resistance-rated construction from both sides with openings protected by fire assemblies having a fire protection rating of not less than 3/4 hour.
Exception: Where the fire wall terminates at the underside of the roof sheathing, deck or slab of the lower roof, provided:
  1. The lower roof assembly within 10 feet (3048 mm) of the wall has not less than a 1-hour fire-resistance rating and the entire length and span of supporting elements for the rated roof assembly has a fireresistance rating of not less than 1 hour.
  2. Openings in the lower roof shall not be located within 10 feet (3048 mm) of the fire wall.
Upcodes Diagrams
Adjacent combustible members entering into a concrete or masonry fire wall from opposite sides shall not have less than a 4-inch (102 mm) distance between embedded ends. Where combustible members frame into hollow walls or walls of hollow units, hollow spaces shall be solidly filled for the full thickness of the wall and for a distance not less than 4 inches (102 mm) above, below and between the structural members, with noncombustible materials approved for fireblocking.
Upcodes Diagrams
Each opening through a fire wall shall be protected in accordance with Section 715.4 and shall not exceed 156 square feet (15 m2). The aggregate width of openings at any floor level shall not exceed 25 percent of the length of the wall.
Exceptions:
  1. Openings are not permitted in party walls constructed in accordance with Section 706.1.1.
  2. Openings shall not be limited to 156 square feet (15 m2) where both buildings are equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
Upcodes Diagrams
Penetrations of fire walls shall comply with Section 713.
Joints made in or between fire walls shall comply with Section 714.
Ducts and air transfer openings shall not penetrate fire walls.
Exception: Penetrations by ducts and air transfer openings of fire walls that are not on a lot line shall be allowed provided the penetrations comply with Section 716. The size and aggregate width of all openings shall not exceed the limitations of Section 706.8.
Fire barriers installed as required elsewhere in this code or the fire code shall comply with this section.
Upcodes Diagrams
Fire barriers shall be of materials permitted by the building type of construction.
Upcodes Diagrams
The fire-resistance rating of fire barriers shall comply with this section.
Upcodes Diagrams
The fire-resistance rating of the fire barrier separating building areas from a shaft shall comply with Section 708.4.
Upcodes Diagrams
The fire-resistance rating of the separation between building areas connected by a horizontal exit shall comply with Section 1025.1.
The fire-resistance rating of the fire barrier separating atriums shall comply with Section 404.6.
The fire barrier separating incidental accessory occupancies from other spaces in the building shall have a fire-resistance rating of not less than that indicated in Table 508.2.5.
Fire barriers separating control areas shall have a fire-resistance rating of not less than that required in Section 414.2.4.
Upcodes Diagrams
Where the provisions of Section 508.4 are applicable, the fire barrier separating mixed occupancies shall have a fire-resistance rating of not less than that indicated in Table 508.4 based on the occupancies being separated.
Upcodes Diagrams
The fire barriers or horizontal assemblies, or both, separating a single occupancy into different fire areas shall have a fire-resistance rating of not less than that indicated in Table 707.3.9. The fire barriers or horizontal assemblies, or both, separating fire areas of mixed occupancies shall have a fire-resistance rating of not less than the highest value indicated in Table 707.3.9 for the occupancies under consideration.
OCCUPANCY GROUPFIRE-RESISTANCE RATING (hours)
H-1, H-24
F-1, H-3, S-13
A, B, E, F-2, H-4, H-5,
I, M, R, S-2
2
U1
Upcodes Diagrams
Where exterior walls serve as a part of a required fire-resistance-rated shaft or exit enclosure, or separation, such walls shall comply with the requirements of Section 705 for exterior walls and the fire-resistance-rated enclosure or separation requirements shall not apply.
Exception: Exterior walls required to be fire-resistance rated in accordance with Section 1019 for exterior egress balconies, Section 1022.6 for exit enclosures and Section 1026.6 for exterior exit ramps and stairways.
Upcodes Diagrams
Fire barriers shall extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above and shall be securely attached thereto. Such fire barriers shall be continuous through concealed spaces, such as the space above a suspended ceiling.
Upcodes Diagrams
The supporting construction for a fire barrier shall be protected to afford the required fire-resistance rating of the fire barrier supported. Hollow vertical spaces within a fire barrier shall be fireblocked in accordance with Section 717.2 at every floor level.
Exceptions:
  1. The maximum required fire-resistance rating for assemblies supporting fire barriers separating tank storage as provided for in Section 415.6.2.1 shall be 2 hours, but not less than required by Table 601 for the building construction type.
  2. Shaft enclosures shall be permitted to terminate at a top enclosure complying with Section 708.12.
  3. Supporting construction for 1-hour fire barriers required by Table 508.2.5 in buildings of Type IIB, IIIB and VB construction is not required to be fire-resistance rated unless required by other sections of this code.
Upcodes Diagrams
Openings in a fire barrier shall be protected in accordance with Section 715. Openings shall be limited to a maximum aggregate width of 25 percent of the length of the wall, and the maximum area of any single opening shall not exceed 156 square feet (15 m2). Openings in exit enclosures and exit passageways shall also comply with Sections 1022.3 and 1023.5, respectively.
Exceptions:
  1. Openings shall not be limited to 156 square feet (15 m2) where adjoining floor areas are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Openings shall not be limited to 156 square feet (15 m2) or an aggregate width of 25 percent of the length of the wall where the opening protective is a fire door serving an exit enclosure.
  3. Openings shall not be limited to 156 square feet (15 m2) or an aggregate width of 25 percent of the length of the wall where the opening protective has been tested in accordance with ASTM E 119 or UL 263 and has a minimum fire-resistance rating not less than the fire-resistance rating of the wall.
  4. Fire window assemblies permitted in atrium separation walls shall not be limited to a maximum aggregate width of 25 percent of the length of the wall.
  5. Openings shall not be limited to 156 square feet (15 m2) or an aggregate width of 25 percent of the length of the wall where the opening protective is a fire door assembly in a fire barrier separating an exit enclosure from an exit passageway in accordance with Section 1022.2.1.
Upcodes Diagrams
Penetrations of fire barriers shall comply with Section 713.
Penetrations into an exit enclosure or an exit passageway shall be allowed only when permitted by Section 1022.4 or 1023.6, respectively.
Joints made in or between fire barriers, and joints made at the intersection of fire barriers with underside of the floor or roof sheathing, slab or deck above, shall comply with Section 714.
Upcodes Diagrams
Penetrations in a fire barrier by ducts and air transfer openings shall comply with Section 716.
The provisions of this section shall apply to shafts required to protect openings and penetrations through floor/ceiling and roof/ceiling assemblies. Shaft enclosures shall be constructed as fire barriers in accordance with Section 707 or horizontal assemblies in accordance with Section 712, or both.
Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section.
Exceptions:
  1. A shaft enclosure is not required for openings totally within an individual residential dwelling unit and connecting four stories or less.
  2. A shaft enclosure is not required in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 for an escalator opening or stairway that is not a portion of the means of egress protected according to Item 2.1 or 2.2.
    1. Where the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalator or stairway and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. In other than Groups B and M, this application is limited to openings that do not connect more than four stories.
    2. Where the opening is protected by approved power-operated automatic shutters at every penetrated floor. The shutters shall be of noncombustible construction and have a fire-resistance rating of not less than 1.5 hours. The shutter shall be so constructed as to close immediately upon the actuation of a smoke detector installed in accordance with Section 907.3 and shall completely shut off the well opening. Escalators shall cease operation when the shutter begins to close. The shutter shall operate at a speed of not more than 30 feet per minute (152.4 mm/s) and shall be equipped with a sensitive leading edge to arrest its progress where in contact with any obstacle, and to continue its progress on release therefrom.
  3. A shaft enclosure is not required for penetrations by pipe, tube, conduit, wire, cable and vents protected in accordance with Section 713.4.
  4. A shaft enclosure is not required for penetrations by ducts protected in accordance with Section 716.6. Grease ducts shall be protected in accordance with the mechanical code.
  5. In other than Group H occupancies, a shaft enclosure is not required for floor openings complying with the provisions for atriums in Section 404.
  6. A shaft enclosure is not required for approved masonry chimneys where annular space is fireblocked at each floor level in accordance with Section 717.2.5.
  7. In other than Groups I-2 and I-3, a shaft enclosure is not required for a floor opening or an air transfer opening that complies with the following:
    1. Does not connect more than two stories.
    2. Is not part of the required means of egress system.
    3. Is not concealed within the construction of a wall or a floor/ceiling assembly.
    4. Is not open to a corridor in Group I and R occupancies.
    5. Is not open to a corridor on nonsprinklered floors in any occupancy.
    6. Is separated from floor openings and air transfer openings serving other floors by construction conforming to required shaft enclosures.
    7. Is limited to the same smoke compartment.
  8. A shaft enclosure is not required for automobile ramps in open and enclosed parking garages constructed in accordance with Sections 406.3 and 406.4, respectively.
  9. A shaft enclosure is not required for floor openings between a mezzanine and the floor below.
  10. A shaft enclosure is not required for joints protected by a fire-resistant joint system in accordance with Section 714.
  11. A shaft enclosure shall not be required for floor openings created by unenclosed stairs or ramps in accordance with Exception 3 or 4 in Section 1016.1.
  12. Floor openings protected by floor fire doors in accordance with Section 712.8.
  13. In Group I-3 occupancies, a shaft enclosure is not required for floor openings in accordance with Section 408.5.
  14. A shaft enclosure is not required for elevator hoistways in open or enclosed parking garages that serve only the parking garage.
  15. In open or enclosed parking garages a shaft enclosure is not required to enclose mechanical exhaust or supply duct systems when such duct system is contained within and serves only the parking garage.
  16. Where permitted by other sections of this code.
The shaft enclosure shall be of materials permitted by the building type of construction.
Shaft enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more, and not less than 1 hour where connecting less than four stories. The number of stories connected by the shaft enclosure shall include any basements but not any mezzanines. Shaft enclosures shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours. Shaft enclosures shall meet the requirements of Section 703.2.1.
Upcodes Diagrams
Shaft enclosures shall be constructed as fire barriers in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both, and shall have continuity in accordance with Section 707.5 for fire barriers or Section 712.4 for horizontal assemblies as applicable.
Where exterior walls serve as a part of a required shaft enclosure, such walls shall comply with the requirements of Section 705 for exterior walls and the fire-resistance-rated enclosure requirements shall not apply.
Exception: Exterior walls required to be fire-resistance rated in accordance with Section 1019.2 for exterior egress balconies, Section 1022.6 for exit enclosures and Section 1026.6 for exterior exit ramps and stairways.
Upcodes Diagrams
Openings in a shaft enclosure shall be protected in accordance with Section 715 as required for fire barriers. Doors shall be self- or automatic-closing by smoke detection in accordance with Section 715.4.8.3.
Openings other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures.
Penetrations in a shaft enclosure shall be protected in accordance with Section 713 as required for fire barriers.
Penetrations other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures.
Joints in a shaft enclosure shall comply with Section 714.
Upcodes Diagrams
Penetrations of a shaft enclosure by ducts and air transfer openings shall comply with Section 716.
Shafts that do not extend to the bottom of the building or structure shall comply with one of the following:
  1. They shall be enclosed at the lowest level with construction of the same fire-resistance rating as the lowest floor through which the shaft passes, but not less than the rating required for the shaft enclosure.
  2. They shall terminate in a room having a use related to the purpose of the shaft. The room shall be separated from the remainder of the building by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both. The fire-resistance rating and opening protectives shall be at least equal to the protection required for the shaft enclosure.
  3. They shall be protected by approved fire dampers installed in accordance with their listing at the lowest floor level within the shaft enclosure.
Exceptions:
  1. The fire-resistance-rated room separation is not required, provided there are no openings in or penetrations of the shaft enclosure to the interior of the building except at the bottom. The bottom of the shaft shall be closed off around the penetrating items with materials permitted by Section 717.3.1 for draftstopping, or the room shall be provided with an approved automatic fire suppression system.
  2. A shaft enclosure containing a refuse chute or laundry chute shall not be used for any other purpose and shall terminate in a room protected in accordance with Section 708.13.4.
  3. The fire-resistance-rated room separation and the protection at the bottom of the shaft are not required provided there are no combustibles in the shaft and there are no openings or other penetrations through the shaft enclosure to the interior of the building.
Upcodes Diagrams
A shaft enclosure that does not extend to the underside of the roof sheathing, deck or slab of the building shall be enclosed at the top with construction of the same fire-resistance rating as the topmost floor penetrated by the shaft, but not less than the fire-resistance rating required for the shaft enclosure.
Refuse and laundry chutes, access and termination rooms and incinerator rooms shall meet the requirements of Sections 708.13.1 through 708.13.6.
Exception: Chutes serving and contained within a single dwelling unit.
A shaft enclosure containing a refuse or laundry chute shall not be used for any other purpose and shall be enclosed in accordance with Section 708.4. Openings into the shaft, including those from access rooms and termination rooms, shall be protected in accordance with this section and Section 715. Openings into chutes shall not be located in corridors. Doors shall be self- or automatic-closing upon the actuation of a smoke detector in accordance with Section 715.4.8.3, except that heat-activated closing devices shall be permitted between the shaft and the termination room.
A shaft enclosure containing a refuse or laundry chute shall be constructed of materials as permitted by the building type of construction.
Access openings for refuse and laundry chutes shall be located in rooms or compartments enclosed by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both. Openings into the access rooms shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. Doors shall be self- or automatic-closing upon the detection of smoke in accordance with Section 715.4.8.3.
Refuse and laundry chutes shall discharge into an enclosed room separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both. Openings into the termination room shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. Doors shall be self- or automatic-closing upon the detection of smoke in accordance with Section 715.4.8.3. Refuse chutes shall not terminate in an incinerator room. Refuse and laundry rooms that are not provided with chutes need only comply with Table 508.2.5.
Incinerator rooms shall comply with Table 508.2.5.
Elevator, dumbwaiter and other hoistway enclosures shall be constructed in accordance with Section 708 and Chapter 30.
An enclosed elevator lobby shall be provided at each floor where an elevator shaft enclosure connects more than three stories. The lobby enclosure shall separate the elevator shaft enclosure doors from each floor by fire partitions. In addition to the requirements in Section 709 for fire partitions, doors protecting openings in the elevator lobby enclosure walls shall also comply with Section 715.4.3 as required for corridor walls and penetrations of the elevator lobby enclosure by ducts and air transfer openings shall be protected as required for corridors in accordance with Section 716.5.4.1. Elevator lobbies shall have at least one means of egress complying with Chapter 10 and other provisions within this code.
Exceptions:
  1. Enclosed elevator lobbies are not required at the street floor, provided the entire street floor is equipped with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Elevators not required to be located in a shaft in accordance with Section 708.2 are not required to have enclosed elevator lobbies.
  3. Enclosed elevator lobbies are not required where additional doors are provided at the hoistway opening in accordance with Section 3002.6. Such doors shall be tested in accordance with UL 1784 without an artificial bottom seal.
  4. Enclosed elevator lobbies are not required where the building is protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. This exception shall not apply to the following:
    1. Group I-2 occupancies;
    2. Group I-3 occupancies; and
    3. High-rise buildings.
  5. Smoke partitions shall be permitted in lieu of fire partitions to separate the elevator lobby at each floor where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. In addition to the requirements in Section 711 for smoke partitions, doors protecting openings in the smoke partitions shall also comply with Sections 711.5.2, 711.5.3, and 715.4.8 and duct penetrations of the smoke partitions shall be protected as required for corridors in accordance with Section 716.5.4.1.
  6. Enclosed elevator lobbies are not required where the elevator hoistway is pressurized in accordance with Section 708.14.2.
  7. Enclosed elevator lobbies are not required where the elevator serves only open parking garages in accordance with Section 406.3.
Where elevator hoistway pressurization is provided in lieu of required enclosed elevator lobbies, the pressurization system shall comply with this section.
Elevator hoistways shall be pressurized to maintain a minimum positive pressure of 0.10 inch of water (25 Pa) and a maximum positive pressure of 0.25 inch of water (67 Pa) with respect to adjacent occupied space on all floors. This pressure shall be measured at the midpoint of each hoistway door, with all elevator cars at the floor of recall and all hoistway doors on the floor of recall open and all other hoistway doors closed. The opening and closing of hoistway doors at each level must be demonstrated during this test. The supply air intake shall be from an outside, uncontaminated source located a minimum distance of 20 feet (6096 mm) from any air exhaust system or outlet.
Exception: Hoistway venting required by Section 3004 need not be provided for pressurized elevator shafts.
A rational analysis complying with Section 909.4 shall be submitted with the construction documents.
Any duct system that is part of the pressurization system shall be protected with the same fire-resistance rating as required for the elevator shaft enclosure.
The fan system provided for the pressurization system shall be as required by this section.
When located within the building, the fan system that provides the pressurization shall be protected with the same fire-resistance rating required for the elevator shaft enclosure.
The fan system shall be equipped with a smoke detector that will automatically shut down the fan system when smoke is detected within the system.
A separate fan system shall be used for each elevator hoistway.
The supply fan shall either be adjustable with a capacity of at least 1,000 cfm (0.4719 m3/s) per door, or that specified by a registered design professional to meet the requirements of a designed pressurization system.
The pressurization system shall be provided with standby power from the same source as other required emergency systems for the building.
The elevator pressurization system shall be activated upon activation of the building fire alarm system or upon activation of the elevator lobby smoke detectors. Where both a building fire alarm system and elevator lobby smoke detectors are present, each shall be independently capable of activating the pressurization system.
Special inspection for performance shall be required in accordance with Section 909.18.8. System acceptance shall be in accordance with Section 909.19.
Detection and control systems shall be marked in accordance with Section 909.14.
Control diagrams shall be provided in accordance with Section 909.15.
A control panel complying with Section 909.16 shall be provided.
Hoistway pressurization systems shall comply with the requirements for smoke control system response time in Section 909.17.
The following wall assemblies shall comply with this section.
  1. Walls separating dwelling units in the same building as required by Section 420.2.
  2. Walls separating sleeping units in the same building as required by Section 420.2.
  3. Walls separating tenant spaces in covered mall buildings as required by Section 402.7.2.
  4. Corridor walls as required by Section 1018.1.
  5. Elevator lobby separation as required by Section 708.14.1.
Upcodes Diagrams
The walls shall be of materials permitted by the building type of construction.
Upcodes Diagrams
Fire partitions shall have a fire-resistance rating of not less than 1 hour.
Exceptions:
  1. Corridor walls permitted to have a 1/2-hour fire-resistance rating by Table 1018.1.
  2. Dwelling unit and sleeping unit separations in buildings of Type IIB, IIIB and VB construction shall have fire-resistance ratings of not less than 1/2-hour in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Upcodes Diagrams
Fire partitions shall extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above or to the fire-resistance-rated floor/ceiling or roof/ceiling assembly above, and shall be securely attached thereto. If the partitions are not continuous to the sheathing, deck or slab, and where constructed of combustible construction, the space between the ceiling and the sheathing, deck or slab above shall be fireblocked or draftstopped in accordance with Sections 717.2 and 717.3 at the partition line. The supporting construction shall be protected to afford the required fire-resistance rating of the wall supported, except for walls separating tenant spaces in covered mall buildings, walls separating dwelling units, walls separating sleeping units and corridor walls, in buildings of Type IIB, IIIB and VB construction.
Exceptions:
  1. The wall need not be extended into the crawl space below where the floor above the crawl space has a minimum 1-hour fire-resistance rating.
  2. Where the room-side fire-resistance-rated membrane of the corridor is carried through to the underside of the floor or roof sheathing, deck or slab of a fire-resistance-rated floor or roof above, the ceiling of the corridor shall be permitted to be protected by the use of ceiling materials as required for a 1-hour fire-resistance-rated floor or roof system.
  3. Where the corridor ceiling is constructed as required for the corridor walls, the walls shall be permitted to terminate at the upper membrane of such ceiling assembly.
  4. The fire partitions separating tenant spaces in a covered mall building, complying with Section 402.7.2, are not required to extend beyond the underside of a ceiling that is not part of a fire-resistance-rated assembly. A wall is not required in attic or ceiling spaces above tenant separation walls.
  5. Fireblocking or draftstopping is not required at the partition line in Group R-2 buildings that do not exceed four stories above grade plane, provided the attic space is subdivided by draftstopping into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller.
  6. Fireblocking or draftstopping is not required at the partition line in buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 or 903.3.1.2, provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces.
Upcodes Diagrams
Where exterior walls serve as a part of a required fire-resistance-rated separation, such walls shall comply with the requirements of Section 705 for exterior walls, and the fire-resistance-rated separation requirements shall not apply.
Exception: Exterior walls required to be fire-resistance rated in accordance with Section 1019.2 for exterior egress balconies, Section 1022.6 for exit enclosures and Section 1026.6 for exterior exit ramps and stairways.
Openings in a fire partition shall be protected in accordance with Section 715.
Upcodes Diagrams
Penetrations of fire partitions shall comply with Section 713.
Joints made in or between fire partitions shall comply with Section 714.
Penetrations in a fire partition by ducts and air transfer openings shall comply with Section 716.
Smoke barriers shall comply with this section.
Smoke barriers shall be of materials permitted by the building type of construction.
A 1-hour fire-resistance rating is required for smoke barriers.
Exception: Smoke barriers constructed of minimum 0.10-inch-thick (2.5 mm) steel in Group I-3 buildings.
Smoke barriers shall form an effective membrane continuous from outside wall to outside wall and from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, deck or slab above, including continuity through concealed spaces, such as those found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction shall be protected to afford the required fire-resistance rating of the wall or floor supported in buildings of other than Type IIB, IIIB or VB construction.
Exceptions:
  1. Smoke-barrier walls are not required in interstitial spaces where such spaces are designed and constructed with ceilings that provide resistance to the passage of fire and smoke equivalent to that provided by the smoke-barrier walls.
  2. Smoke barriers used for elevator lobbies in accordance with Sections 405.4.3, 3007.4.2 and 3008.11.2 are not required to extend from outside wall to outside wall.
  3. Smoke barriers used for areas of refuge in accordance with Section 1007.6.2 are not required to extend from outside wall to outside wall.
Upcodes Diagrams
Openings in a smoke barrier shall be protected in accordance with Section 715.
Exceptions:
  1. In Group I-2, where doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with fire-protection-rated glazing materials in fire-protection-rated frames, the area of which shall not exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts in excess of 3/4-inch, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and shall be automatic-closing by smoke detection in accordance with Section 715.4.8.3. Where permitted by the door manufacturer's listing, positive-latching devices are not required.
  2. In Group I-2, horizontal sliding doors installed in accordance with Section 1008.1.4.3 and protected in accordance with Section 715.
Penetrations of smoke barriers shall comply with Section 713.
Joints made in or between smoke barriers shall comply with Section 714.
Penetrations in a smoke barrier by ducts and air transfer openings shall comply with Section 716.
Smoke partitions installed as required elsewhere in the code shall comply with this section.
The walls shall be of materials permitted by the building type of construction.
Unless required elsewhere in the code, smoke partitions are not required to have a fire-resistance rating.
Smoke partitions shall extend from the top of the foundation or floor below to the underside of the floor or roof sheathing, deck or slab above or to the underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke.
Windows shall be sealed to resist the free passage of smoke or be automatic-closing upon detection of smoke. Doors in smoke partitions shall comply with this section.
Doors in smoke partitions shall not include louvers.
Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot [0.015424 m3/(s • m2)] of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature test and the elevated temperature exposure test. Installation of smoke doors shall be in accordance with NFPA 105.
Where required elsewhere in the code, doors in smoke partitions shall be self- or automatic-closing by smoke detection in accordance with Section 715.4.8.3.
The space around penetrating items and in joints shall be filled with an approved material to limit the free passage of smoke.
The space around a duct penetrating a smoke partition shall be filled with an approved material to limit the free passage of smoke. Air transfer openings in smoke partitions shall be provided with a smoke damper complying with Section 716.3.2.2.
Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.
Floor and roof assemblies required to have a fire-resistance rating shall comply with this section. Nonfire-resistance-rated floor and roof assemblies shall comply with Section 713.4.2.
The floor and roof assemblies shall be of materials permitted by the building type of construction.
The fire-resistance rating of floor and roof assemblies shall not be less than that required by the building type of construction. Where the floor assembly separates mixed occupancies, the assembly shall have a fire-resistance rating of not less than that required by Section 508.4 based on the occupancies being separated. Where the floor assembly separates a single occupancy into different fire areas, the assembly shall have a fire-resistance rating of not less than that required by Section 707.3.9. Horizontal assemblies separating dwelling units in the same building and horizontal assemblies separating sleeping units in the same building shall be a minimum of 1-hour fire-resistance-rated construction.
Exception: Dwelling unit and sleeping unit separations in buildings of Type IIB, IIIB and VB construction shall have fire-resistance ratings of not less than 1/2 hour in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Upcodes Diagrams
Where the weight of lay-in ceiling panels, used as part of fire-resistance-rated floor/ceiling or roof/ceiling assemblies, is not adequate to resist an upward force of 1 pound per square foot (48 Pa), wire or other approved devices shall be installed above the panels to prevent vertical displacement under such upward force.
Access doors shall be permitted in ceilings of fire-resistance-rated floor/ceiling and roof/ceiling assemblies provided such doors are tested in accordance with ASTM E 119 or UL 263 as horizontal assemblies and labeled by an approved agency for such purpose.
In 1-hour fire-resistance-rated floor assemblies, the ceiling membrane is not required to be installed over unusable crawl spaces. In 1-hour fire-resistance-rated roof assemblies, the floor membrane is not required to be installed where unusable attic space occurs above.
Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 708.2, 713.4, 714 and 1022.1. Skylights and other penetrations through a fire-resistance-rated roof deck or slab are permitted to be unprotected, provided that the structural integrity of the fire-resistance-rated roof assembly is maintained. Unprotected skylights shall not be permitted in roof assemblies required to be fire-resistance rated in accordance with Section 705.8.6. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported.
Exception: In buildings of Type IIB, IIIB or VB construction, the construction supporting the horizontal assembly is not required to be fire-resistance-rated at the following:
  1. Horizontal assemblies at the separations of incidental uses as specified by Table 508.2.5, provided the required fire-resistance rating does not exceed 1 hour.
  2. Horizontal assemblies at the separations of dwelling units and sleeping units as required by Section 420.3.
  3. Horizontal assemblies at smoke barriers constructed in accordance with Section 710.
Penetrations of horizontal assemblies shall comply with Section 713.
Joints made in or between horizontal assemblies shall comply with Section 714. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 714.4.
Penetrations in horizontal assemblies by ducts and air transfer openings shall comply with Section 716.
Floor fire door assemblies used to protect openings in fire-resistance-rated floors shall be tested in accordance with NFPA 288, and shall achieve a fire-resistance rating not less than the assembly being penetrated. Floor fire door assemblies shall be labeled by an approved agency. The label shall be permanently affixed and shall specify the manufacturer, the test standard and the fire-resistance rating.
Where horizontal assemblies are required to resist the movement of smoke by other sections of this code in accordance with the definition of smoke barrier, penetrations and joints in such horizontal assemblies shall be protected as required for smoke barriers in accordance with Sections 713.5 and 714.6. Regardless of the number of stories connected by elevator shaft enclosures, doors located in elevator shaft enclosures that penetrate the horizontal assembly shall be protected by enclosed elevator lobbies complying with Section 708.14.1. Openings through horizontal assemblies shall be protected by shaft enclosures complying with Section 708. Horizontal assemblies shall not be allowed to have unprotected vertical openings.
The provisions of this section shall govern the materials and methods of construction used to protect through penetrations and membrane penetrations of horizontal assemblies and fire-resistance-rated wall assemblies.
Penetrations of fire-resistance-rated walls by ducts that are not protected with dampers shall comply with Sections 713.2 through 713.3.3. Penetrations of horizontal assemblies not protected with a shaft as permitted by Exception 4 of Section 708.2, and not required to be protected with fire dampers by other sections of this code, shall comply with Sections 713.4 through 713.4.2.2. Ducts and air transfer openings that are protected with dampers shall comply with Section 716.
Where sleeves are used, they shall be securely fastened to the assembly penetrated. The space between the item contained in the sleeve and the sleeve itself and any space between the sleeve and the assembly penetrated shall be protected in accordance with this section. Insulation and coverings on or in the penetrating item shall not penetrate the assembly unless the specific material used has been tested as part of the assembly in accordance with this section.
Penetrations into or through fire walls, fire barriers, smoke barrier walls and fire partitions shall comply with Sections 713.3.1 through 713.3.3. Penetrations in smoke barrier walls shall also comply with Section 713.5.
Upcodes Diagrams
Through penetrations of fire-resistance-rated walls shall comply with Section 713.3.1.1 or 713.3.1.2.
Exception: Where the penetrating items are steel, ferrous or copper pipes, tubes or conduits, the annular space between the penetrating item and the fire-resistance-rated wall is permitted to be protected as follows:
  1. In concrete or masonry walls where the penetrating item is a maximum 6-inch (152 mm) nominal diameter and the area of the opening through the wall does not exceed 144 square inches (0.0929 m2), concrete, grout or mortar is permitted where it is installed the full thickness of the wall or the thickness required to maintain the fire-resistance rating; or
  2. The material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 or UL 263 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
Penetrations shall be installed as tested in an approved fire-resistance-rated assembly.
Through penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water and shall have an F rating of not less than the required fire-resistance rating of the wall penetrated.
Membrane penetrations shall comply with Section 713.3.1. Where walls or partitions are required to have a fire-resistance rating, recessed fixtures shall be installed such that the required fire-resistance will not be reduced.
Exceptions:
  1. Membrane penetrations of maximum 2-hour fire-resistance-rated walls and partitions by steel electrical boxes that do not exceed 16 square inches (0.0103 m2) in area, provided the aggregate area of the openings through the membrane does not exceed 100 square inches (0.0645 m2) in any 100 square feet (9.29 m2) of wall area. The annular space between the wall membrane and the box shall not exceed 1/8 inch (3.1 mm). Such boxes on opposite sides of the wall or partition shall be separated by one of the following:
    1. By a horizontal distance of not less than 24 inches (610 mm) where the wall or partition is constructed with individual noncommunicating stud cavities;
    2. By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose-fill, rockwool or slag mineral wool insulation;
    3. By solid fireblocking in accordance with Section 717.2.1;
    4. By protecting both outlet boxes with listed putty pads; or
    5. By other listed materials and methods.
  2. Membrane penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. The annular space between the wall membrane and the box shall not exceed 1/8 inch (3.1 mm) unless listed otherwise. Such boxes on opposite sides of the wall or partition shall be separated by one of the following:
    1. By the horizontal distance specified in the listing of the electrical boxes;
    2. By solid fireblocking in accordance with Section 717.2.1;
    3. By protecting both boxes with listed putty pads; or
    4. By other listed materials and methods.
  3. Membrane penetrations by electrical boxes of any size or type, which have been listed as part of a wall opening protective material system for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
  4. Membrane penetrations by boxes other than electrical boxes, provided such penetrating items and the annular space between the wall membrane and the box, are protected by an approved membrane penetration firestop system installed as tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water, and shall have an F and T rating of not less than the required fire-resistance rating of the wall penetrated and be installed in accordance with their listing.
  5. The annular space created by the penetration of an automatic sprinkler, provided it is covered by a metal escutcheon plate.
  6. Noncombustible items that are cast into concrete building elements and that do not penetrate both top and bottom surfaces of the element.
  7. The ceiling membrane of 1- and 2-hour fire-resistance-rated horizontal assemblies is permitted to be interrupted with the double wood top plate of a fire-resistance-rated wall assembly, provided that all penetrating items through the double top plates are protected in accordance with Section 713.4.1.1.1 or 714.3.1.1.2. The fire-resistance rating of the wall shall not be less than the rating of the horizontal assembly.
Noncombustible penetrating items shall not connect to combustible items beyond the point of firestopping unless it can be demonstrated that the fire-resistance integrity of the wall is maintained.
Penetrations of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly not required to be enclosed in a shaft by Section 708.2 shall be protected in accordance with Sections 713.4.1 through 713.4.2.2.
Penetrations of the fire-resistance-rated floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall comply with Sections 713.4.1.1 through 713.4.1.4. Penetrations in horizontal smoke barriers shall also comply with 713.5.
Through penetrations of fire-resistance-rated horizontal assemblies shall comply with Section 713.4.1.1.1 or 713.4.1.1.2.
Exceptions:
  1. Penetrations by steel, ferrous or copper conduits, pipes, tubes or vents or concrete or masonry items through a single fire-resistance-rated floor assembly where the annular space is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 or UL 263 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. Penetrating items with a maximum 6-inch (152 mm) nominal diameter shall not be limited to the penetration of a single fire-resistance-rated floor assembly, provided the aggregate area of the openings through the assembly does not exceed 144 square inches (92 900 mm2) in any 100 square feet (9.3 m2) of floor area.
  2. Penetrations in a single concrete floor by steel, ferrous or copper conduits, pipes, tubes or vents with a maximum 6-inch (152 mm) nominal diameter, provided the concrete, grout or mortar is installed the full thickness of the floor or the thickness required to maintain the fire-resistance rating. The penetrating items shall not be limited to the penetration of a single concrete floor, provided the area of the opening through each floor does not exceed 144 square inches (92 900 mm2).
  3. Penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated assemblies and installed in accordance with the instructions included in the listing.
Upcodes Diagrams
Through penetrations shall be installed as tested in the approved fire-resistance-rated assembly.
Upcodes Diagrams
Through penetrations shall be protected by an approved through-penetration firestop system installed and tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch of water (2.49 Pa). The system shall have an F rating/T rating of not less than 1 hour but not less than the required rating of the floor penetrated.
Exception: Floor penetrations contained and located within the cavity of a wall above the floor or below the floor do not require a T rating.
Upcodes Diagrams
Penetrations of membranes that are part of a horizontal assembly shall comply with Section 713.4.1.1.1 or 713.4.1.1.2. Where floor/ceiling assemblies are required to have a fire-resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced.
Exceptions:
  1. Membrane penetrations by steel, ferrous or copper conduits, pipes, tubes or vents, or concrete or masonry items where the annular space is protected either in accordance with Section 713.4.1.1 or to prevent the free passage of flame and the products of combustion. The aggregate area of the openings through the membrane shall not exceed 100 square inches (64 500 mm2) in any 100 square feet (9.3 m2) of ceiling area in assemblies tested without penetrations.
  2. Ceiling membrane penetrations of maximum 2-hour horizontal assemblies by steel electrical boxes that do not exceed 16 square inches (10 323 mm2) in area, provided the aggregate area of such penetrations does not exceed 100 square inches (44 500 mm2) in any 100 square feet (9.29 m2) of ceiling area, and the annular space between the ceiling membrane and the box does not exceed 1/8 inch (3.2 mm).
  3. Membrane penetrations by electrical boxes of any size or type, which have been listed as part of an opening protective material system for use in horizontal assemblies and are installed in accordance with the instructions included in the listing.
  4. Membrane penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. The annular space between the ceiling membrane and the box shall not exceed 1/8 inch (3.2 mm) unless listed otherwise.
  5. The annular space created by the penetration of a fire sprinkler, provided it is covered by a metal escutcheon plate.
  6. Noncombustible items that are cast into concrete building elements and that do not penetrate both top and bottom surfaces of the element.
  7. The ceiling membrane of 1- and 2-hour fire-resistance-rated horizontal assemblies is permitted to be interrupted with the double wood top plate of a fire-resistance-rated wall assembly, provided that all penetrating items through the double top plates are protected in accordance with Section 713.4.1.1.1 or 714.3.1.1.2. The fire-resistance rating of the wall shall not be less than the rating of the horizontal assembly.
Penetrations of horizontal assemblies by ducts and air transfer openings shall comply with Section 716.
Noncombustible penetrating items shall not connect to combustible materials beyond the point of firestopping unless it can be demonstrated that the fire-resistance integrity of the horizontal assembly is maintained.
Penetrations of nonfire-resistance-rated floor or floor/ceiling assemblies or the ceiling membrane of a nonfire-resistance-rated roof/ceiling assembly shall meet the requirements of Section 708 or shall comply with Section 713.4.2.1 or 713.4.2.2.
Noncombustible penetrating items that connect not more than three stories are permitted, provided that the annular space is filled to resist the free passage of flame and the products of combustion with an approved noncombustible material or with a fill, void or cavity material that is tested and classified for use in through-penetration firestop systems.
Penetrating items that connect not more than two stories are permitted, provided that the annular space is filled with an approved material to resist the free passage of flame and the products of combustion.
Penetrations in smoke barriers shall be tested in accordance with the requirements of UL 1479 for air leakage. The air leakage rate of the penetration assemblies measured at 0.30 inch (7.47 Pa) of water in both the ambient temperature and elevated temperature tests, shall not exceed:
  1. 5.0 cfm per square foot (0.025m3 / s • m2) of penetration opening for each through-penetration firestop system; or
  2. A total cumulative leakage of 50 cfm (0.024m3/s) for any 100 square feet (9.3 m2) of wall area, or floor area.
Joints installed in or between fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be tested in accordance with Section 714.3. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 714.4.
Exception: Fire-resistant joint systems shall not be required for joints in all of the following locations:
  1. Floors within a single dwelling unit.
  2. Floors where the joint is protected by a shaft enclosure in accordance with Section 708.
  3. Floors within atriums where the space adjacent to the atrium is included in the volume of the atrium for smoke control purposes.
  4. Floors within malls.
  5. Floors and ramps within open and enclosed parking garages or structures constructed in accordance with Sections 406.3 and 406.4, respectively.
  6. Mezzanine floors.
  7. Walls that are permitted to have unprotected openings.
  8. Roofs where openings are permitted.
  9. Control joints not exceeding a maximum width of 0.625 inch (15.9 mm) and tested in accordance with ASTM E 119 or UL 263.
Upcodes Diagrams
Fire-resistant joint systems shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to resist the passage of fire and hot gases.
Fire-resistant joint systems shall be tested in accordance with the requirements of either ASTM E 1966 or UL 2079. Nonsymmetrical wall joint systems shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side.
Exception: For exterior walls with a horizontal fire separation distance greater than 5 feet (1524 mm), the joint system shall be required to be tested for interior fire exposure only.
Where fire resistance-rated floor or floor/ceiling assemblies are required, voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies shall be sealed with an approved system to prevent the interior spread of fire. Such systems shall be securely installed and tested in accordance with ASTM E 2307 to prevent the passage of flame for the time period at least equal to the fire-resistance rating of the floor assembly and prevent the passage of heat and hot gases sufficient to ignite cotton waste. Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 705.8.5.
Exception: Voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies where the vision glass extends to the finished floor level shall be permitted to be sealed with an approved material to prevent the interior spread of fire. Such material shall be securely installed and capable of preventing the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch (0.254 mm) of water column (2.5 Pa) for the time period at least equal to the fire-resistance rating of the floor assembly.
Voids created at the intersection of exterior curtain wall assemblies and nonfire-resistance-rated floor or floor/ceiling assemblies shall be sealed with an approved material or system to retard the interior spread of fire and hot gases between stories.
Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 705.8.5. Where Section 705.8.5 does not require a fire-resistance-rated spandrel wall, the requirements of Section 714.4 shall still apply to the intersection between the spandrel wall and the floor.
Fire-resistant joint systems in smoke barriers, and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The air leakage rate of the joint shall not exceed 5 cfm per linear foot (0.00775 m3/s • m) of joint at 0.30 inch (7.47 Pa) of water for both the ambient temperature and elevated temperature tests.
Upcodes Diagrams
Opening protectives required by other sections of this code shall comply with the provisions of this section.
Fire-resistance-rated glazing tested as part of a fire-resistance-rated wall assembly in accordance with ASTM E 119 or UL 263 and labeled in accordance with Section 703.5 shall be permitted in fire doors and fire window assemblies in accordance with their listings and shall not otherwise be required to comply with this section.
The application of any of the alternative methods listed in this section shall be based on the fire exposure and acceptance criteria specified in NFPA 252, NFPA 257 or UL 9. The required fire resistance of an opening protective shall be permitted to be established by any of the following methods or procedures:
  1. Designs documented in referenced publications approved in accordance with this code.
  2. Calculations performed in accordance with Section 106.5.
  3. Engineering analysis based on a comparison of opening protective designs having fire protection ratings as determined by the test procedures set forth in NFPA 252, NFPA 257 or UL 9.
  4. Alternative protection methods as allowed by Section 106.5.
Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 715.4.1, 715.4.2 or 715.4.3 and the fire protection rating indicated in Table 715.4. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 715.4.5. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80.
Exceptions:
  1. Labeled protective assemblies that conform to the requirements of this section or UL 10A, UL 14B and UL 14C for tin-clad fire door assemblies.
  2. Floor fire door assemblies in accordance with Section 712.8.
TYPE OF ASSEMBLYREQUIRED
ASSEMBLY
RATING
(hours)
MINIMUM FIRE
DOOR AND FIRE
SHUTTER
ASSEMBLY
RATING (hours)
Fire walls and fire barriers havinggreater than 1 hour43
33a
211/2
11/211/2
Fire barriers having a required
Shaft, exit enclosure and exit
passageway walls
11
Other fire barriers13/4
Fire partitions:
Corridor walls11/3b
0.51/3b
Other fire partitions13/4
0.51/3
Exterior walls311/2
211/2
13/4
Smoke barriers11/3b
  1. Two doors, each with a fire protection rating of 11/2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door.
  2. For testing requirements, see Section 715.4.3.
Fire door assemblies with side-hinged and pivoted swinging doors shall be tested in accordance with NFPA 252 or UL 10C. After 5 minutes into the NFPA 252 test, the neutral pressure level in the furnace shall be established at 40 inches (1016 mm) or less above the sill.
Fire door assemblies with other types of doors, including swinging elevator doors and fire shutter assemblies, shall be tested in accordance with NFPA 252 or UL 10B. The pressure in the furnace shall be maintained as nearly equal to the atmospheric pressure as possible. Once established, the pressure shall be maintained during the entire test period.
Fire door assemblies required to have a minimum fire protection rating of 20 minutes where located in corridor walls or smoke barrier walls having a fire-resistance rating in accordance with Table 715.4 shall be tested in accordance with NFPA 252 or UL 10C without the hose stream test.
Exceptions:
  1. Viewports that require a hole not larger than 1 inch (25 mm) in diameter through the door, have at least a 0.25-inch-thick (6.4 mm) glass disc and the holder is of metal that will not melt out where subject to temperatures of 1,700°F (927°C).
  2. Corridor door assemblies in occupancies of Group I-2 shall be in accordance with Section 407.3.1.
  3. Unprotected openings shall be permitted for corridors in multitheater complexes where each motion picture auditorium has at least one-half of its required exit or exit access doorways opening directly to the exterior or into an exit passageway.
  4. Horizontal sliding doors in smoke barriers that comply with Sections 408.3 and 408.8.4 in occupancies in Group I-3.
Fire door assemblies shall also meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot [0.01524 m3/(s • m2)] of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature and elevated temperature tests. Louvers shall be prohibited. Installation of smoke doors shall be in accordance with NFPA 105.
In a 20-minute fire door assembly, the glazing material in the door itself shall have a minimum fire-protection-rated glazing of 20 minutes and shall be exempt from the hose stream test. Glazing material in any other part of the door assembly, including transom lights and sidelights, shall be tested in accordance with NFPA 257 or UL 9, including the hose stream test, in accordance with Section 715.5.
Fire door assemblies in exit enclosures and exit passageways shall have a maximum transmitted temperature end point of not more than 450°F (250°C) above ambient at the end of 30 minutes of standard fire test exposure.
Exception: The maximum transmitted temperature rise is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Fire-protection-rated glazing in excess of 100 square inches (0.065 m2) shall be permitted in fire door assemblies when tested as components of the door assemblies and not as glass lights, and shall have a maximum transmitted temperature rise of 450°F (250°C) in accordance with Section 715.4.4.
Exception: The maximum transmitted temperature rise is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Door frames with transom lights, sidelights, or both, shall be permitted where a 3/4-hour fire protection rating or less is required in accordance with Table 715.4. Where a fire protection rating exceeding 3/4-hour is required in accordance with Table 715.4, fire door frames with transom lights, sidelights, or both, shall be permitted where installed with fire-resistance-rated glazing tested as an assembly in accordance with ASTM E119 or UL 263.
Fire door assemblies shall be labeled by an approved agency. The labels shall comply with NFPA 80, and shall be permanently affixed to the door or frame.
Fire doors shall be labeled showing the name of the manufacturer or other identification readily traceable back to the manufacturer, the name or trademark of the approved inspection agency, the fire protection rating and, where required for fire doors in exit enclosures and exit passageways by Section 715.4.4, the maximum transmitted temperature end point. Smoke and draft control doors complying with UL 1784 shall be labeled as such and shall also comply with Section 715.4.6.3. Labels shall be approved and permanently affixed. The label shall be applied at the factory or location where fabrication and assembly are performed.
Oversized fire doors shall bear an oversized fire door label by an approved agency or shall be provided with a certificate of inspection furnished by an approved testing agency. When a certificate of inspection is furnished by an approved testing agency, the certificate shall state that the door conforms to the requirements of design, materials and construction, but has not been subjected to the fire test.
Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 715.4.6.1 and shall show the letter "S" on the fire rating label of the door. This marking shall indicate that the door and frame assembly are in compliance when listed or labeled gasketing is also installed.
Fire door frames shall be labeled showing the names of the manufacturer and the third-party inspection agency.
Fire-protection-rated glazing conforming to the opening protection requirements in Section 715.4 shall be permitted in fire door assemblies.
Fire-protection-rated glazing used in fire doors shall comply with the size limitations of NFPA 80.
Exceptions:
  1. Fire-protection-rated glazing located in fire walls shall be prohibited except where serving in a fire door in a horizontal exit, a self-closing swinging door shall be permitted to have a vision panel of not more than 100 square inches (0.065 m2) without a dimension exceeding 10 inches (254 mm).
  2. Fire-protection-rated glazing shall not be installed in fire doors having a 11/2-hour fire protection rating intended for installation in fire barriers, unless the glazing is not more than 100 square inches (0.065 m2) in area.
Approved fire-protection-rated glazing used in fire door assemblies in elevator and exit enclosures shall be so located as to furnish clear vision of the passageway or approach to the elevator, ramp or stairway.
Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and information required in Section 715.5.9.1 that shall be issued by an approved agency and shall be permanently affixed to the glazing.
For fire protection-rated glazing, the label shall bear the following four-part identification: "D — H or NH — T or NT — XXX." "D" indicates that the glazing shall be used in fire door assemblies and that the glazing meets the fire protection requirements of NFPA 252. "H" shall indicate that the glazing meets the hose stream requirements of NFPA 252. "NH" shall indicate that the glazing does not meet the hose stream requirements of the test. "T" shall indicate that the glazing meets the temperature requirements of Section 715.4.4.1. "NT" shall indicate that the glazing does not meet the temperature requirements of Section 715.4.4.1. The placeholder "XXX" shall specify the fire-protection-rating period, in minutes.
Fire-protection-rated glazing installed in fire doors in areas subject to human impact in hazardous locations shall comply with Chapter 24.
Fire doors shall be self- or automatic-closing in accordance with this section.
Exceptions:
  1. Fire doors located in common walls separating sleeping units in Group R-1 shall be permitted without automatic- or self-closing devices.
  2. The elevator car doors and the associated hoistway enclosure doors at the floor level designated for recall in accordance with Section 3003.2 shall be permitted to remain open during Phase I emergency recall operation.
Unless otherwise specifically permitted, single fire doors and both leaves of pairs of side-hinged swinging fire doors shall be provided with an active latch bolt that will secure the door when it is closed.
Automatic-closing doors installed in the following locations shall be automatic-closing by the actuation of smoke detectors installed in accordance with Section 907.3 or by loss of power to the smoke detector or hold-open device. Doors that are automatic-closing by smoke detection shall not have more than a 10-second delay before the door starts to close after the smoke detector is actuated:
  1. Doors installed across a corridor.
  2. Doors that protect openings in exits or corridors required to be of fire-resistance-rated construction.
  3. Doors that protect openings in walls that are capable of resisting the passage of smoke in accordance with Section 508.2.5.2.
  4. Doors installed in smoke barriers in accordance with Section 710.5.
  5. Doors installed in fire partitions in accordance with Section 709.6.
  6. Doors installed in a fire wall in accordance with Section 706.8.
  7. Doors installed in shaft enclosures in accordance with Section 708.7.
  8. Doors installed in refuse and laundry chutes and access and termination rooms in accordance with Section 708.13.
  9. Doors installed in the walls for compartmentation of underground buildings in accordance with Section 405.4.2.
  10. Doors installed in the elevator lobby walls of underground buildings in accordance with Section 405.4.3.
  11. Doors installed in smoke partitions in accordance with Section 711.5.3.
Vertical sliding or vertical rolling steel fire doors in openings through which pedestrians travel shall be heat activated or activated by smoke detectors with alarm verification.
Where fire shutters of the swinging type are installed in exterior openings, not less than one row in every three vertical rows shall be arranged to be readily opened from the outside, and shall be identified by distinguishing marks or letters not less than 6 inches (152 mm) high.
Where fire shutters of the rolling type are installed, such shutters shall include approved automatic-closing devices.
Glazing in fire window assemblies shall be fire-protection rated in accordance with this section and Table 715.5. Glazing in fire door assemblies shall comply with Section 715.4.7. Fire-protection-rated glazing shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 or UL 9. Fire-protection-rated glazing shall also comply with NFPA 80. Openings in nonfire-resistance-rated exterior wall assemblies that require protection in accordance with Section 705.3, 705.8, 705.8.5 or 705.8.6 shall have a fire-protection rating of not less than 3/4 hour.
Exceptions:
  1. Wired glass in accordance with Section 715.5.4.
  2. Fire protection-rated glazing in 0.5-hour fire-resistance-rated partitions is permitted to have an 0.33-hour fire-protection rating.
TYPE OF ASSEMBLYREQUIRED
ASSEMBLY
RATING (hours)
MINIMUM FIRE
WINDOW
ASSEMBLY
RATING (hours)
Interior walls:Fire wallsAllNPa
Fire barriers> 1NPa
13/4
Smoke barriers13/4
Fire partitions13/4
1/21/3
Exterior walls> 111/2
13/4
Party wallAllNP
NP = Not Permitted.
  1. Not permitted except as specified in Section 715.2.
NFPA 257 or UL 9 shall evaluate fire-protection-rated glazing under positive pressure. Within the first 10 minutes of a test, the pressure in the furnace shall be adjusted so at least two-thirds of the test specimen is above the neutral pressure plane, and the neutral pressure plane shall be maintained at that height for the balance of the test.
Nonsymmetrical fire-protection-rated glazing systems in fire partitions, fire barriers or in exterior walls with a fire separation distance of 5 feet (1524 mm) or less pursuant to Section 705 shall be tested with both faces exposed to the furnace, and the assigned fire protection rating shall be the shortest duration obtained from the two tests conducted in compliance with NFPA 257 or UL 9.
Fire-protection-rated glazing installed in fire window assemblies in areas subject to human impact in hazardous locations shall comply with Chapter 24.
Steel window frame assemblies of 0.125-inch (3.2 mm) minimum solid section or of not less than nominal 0.048-inch-thick (1.2 mm) formed sheet steel members fabricated by pressing, mitering, riveting, interlocking or welding and having provision for glazing with 1/4-inch (6.4 mm) wired glass where securely installed in the building construction and glazed with 1/4-inch (6.4 mm) labeled wired glass shall be deemed to meet the requirements for a 3/4-hour fire window assembly. Wired glass panels shall conform to the size limitations set forth in Table 715.5.4.
LIMITING SIZES OF WIRED GLASS PANELS
OPENING FIRE
PROTECTION
RATING
MAXIMUM
AREA
(square inches)
MAXIMUM
HEIGHT
(inches)
MAXIMUM
WIDTH
(inches)
3 hours000
11/2-hour doors in exterior walls000
1 and 11/2 hours1003310
3/4 hour1,2965454
20 minutesNot LimitedNot LimitedNot Limited
Fire window assemblies1,2965454
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2.
Glazing other than wired glass in fire window assemblies shall be fire-protection-rated glazing installed in accordance with and complying with the size limitations set forth in NFPA 80.
Fire-protection-rated glazing shall be in the fixed position or be automatic-closing and shall be installed in approved frames.
Metal mullions that exceed a nominal height of 12 feet (3658 mm) shall be protected with materials to afford the same fire-resistance rating as required for the wall construction in which the protective is located.
Fire-protection-rated glazing used in fire window assemblies located in fire partitions and fire barriers shall be limited to use in assemblies with a maximum fire-resistance rating of 1 hour in accordance with this section.
Fire-protection-rated glazing requiring 45-minute opening protection in accordance with Table 715.5 shall be limited to fire partitions designed in accordance with Section 709 and fire barriers utilized in the applications set forth in Sections 707.3.6 and 707.3.8 where the fire-resistance rating does not exceed 1 hour.
The total area of windows shall not exceed 25 percent of the area of a common wall with any room.
Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and information required in Section 715.5.9.1 that shall be issued by an approved agency and shall be permanently affixed to the glazing.
For fire-protection-rated glazing, the label shall bear the following two-part identification: "OH — XXX." "OH" indicates that the glazing meets both the fire protection and the hose-stream requirements of NFPA 257 or UL 9 and is permitted to be used in openings. "XXX" represents the fire-protection rating period, in minutes, that was tested.
The provisions of this section shall govern the protection of duct penetrations and air transfer openings in assemblies required to be protected.
Ducts that penetrate fire-resistance-rated assemblies and are not required by this section to have dampers shall comply with the requirements of Sections 713.2 through 713.3.3. Ducts that penetrate horizontal assemblies not required to be contained within a shaft and not required by this section to have dampers shall comply with the requirements of Sections 713.4 through 713.4.2.2.
The space around a duct penetrating a nonfire-resistance-rated floor assembly shall comply with Section 716.6.3.
Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers located within air distribution and smoke control systems shall be installed in accordance with the requirements of this section, the manufacturer's installation instructions and the dampers' listing.
Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized. Where mechanical systems including ducts and dampers utilized for normal building ventilation serve as part of the smoke control system, the expected performance of these systems in smoke control mode shall be addressed in the rational analysis required by Section 909.4.
Fire dampers for hazardous exhaust duct systems shall comply with the mechanical code.
Damper testing, ratings and actuation shall be in accordance with Sections 716.3.1 through 716.3.3.
Dampers shall be listed and bear the label of an approved testing agency indicating compliance with the standards in this section. Fire dampers shall comply with the requirements of UL 555. Only fire dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-conditioning systems designed to operate with fans on during a fire. Smoke dampers shall comply with the requirements of UL 555S. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. Ceiling radiation dampers shall comply with the requirements of UL 555C or shall be tested as part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly in accordance with ATSTM E119 or UL 263.
Damper ratings shall be in accordance with Sections 716.3.2.1 through 716.3.2.3.
Upcodes Diagrams
Fire dampers shall have the minimum fire protection rating specified in Table 716.3.2.1 for the type of penetration.
TYPE OF
PENETRATION
MINIMUM
DAMPER
RATING
(hours)
Less than 3-hour fire-resistance-rated assemblies1.5
3-hour or greater fire-resistance-rated assemblies3
Smoke damper leakage ratings shall not be less than Class II. Elevated temperature ratings shall not be less than 250°F (121°C).
Combination fire/smoke dampers shall have the minimum fire protection rating specified for fire dampers in Table 716.3.2.1 for the type of penetration and shall also have a minimum Class II leakage rating and a minimum elevated temperature rating of 250°F (121°C).
Damper actuation shall be in accordance with Sections 716.3.3.1 through 716.3.3.4 as applicable.
Upcodes Diagrams
The fire damper actuation device shall meet one of the following requirements:
  1. The operating temperature shall be approximately 50°F (10°C) above the normal temperature within the duct system, but not less than 160°F (71°C).
  2. The operating temperature shall be not more than 350°F (177°C) where located in a smoke control system complying with Section 909.
Upcodes Diagrams
The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 907.3 and one of the following methods, as applicable:
  1. Where a smoke damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate.
  2. Where a smoke damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector listed for releasing service shall be installed on either side of the smoke barrier door opening.
  3. Where a smoke damper is installed within an air transfer opening in a wall, a spot-type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper.
  4. Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.
  5. Where a total-coverage smoke detector system is provided within areas served by a heating, ventilation and air-conditioning (HVAC) system, smoke dampers shall be permitted to be controlled by the smoke detection system.
Upcodes Diagrams
Combination fire/smoke damper actuation shall be in accordance with Sections 716.3.3.1 and 716.3.3.2. Combination fire/smoke dampers installed in smoke control system shaft penetrations shall not be activated by local area smoke detection unless it is secondary to the smoke management system controls.
Upcodes Diagrams
The operating temperature of a ceiling radiation damper actuation device shall be 50°F (27.8°C) above the normal temperature within the duct system, but not less than 160°F (71°C).
Fire and smoke dampers shall be provided with an approved means of access, which is large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 1/2 inch (12.7 mm) in height reading: FIRE/SMOKE DAMPER, SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction.
Fire dampers, smoke dampers and combination fire/smoke dampers shall be provided at the locations prescribed in Sections 716.5.1 through 716.5.7 and 716.6. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and a smoke damper shall be required.
Upcodes Diagrams
Ducts and air transfer openings permitted in fire walls in accordance with Section 706.11 shall be protected with listed fire dampers installed in accordance with their listing.
Upcodes Diagrams
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire wall that serves as a horizontal exit.
Ducts and air transfer openings of fire barriers shall be protected with approved fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate exit enclosures and exit passageways except as permitted by Sections 1022.4 and 1023.6, respectively.
Exception: Fire dampers are not required at penetrations of fire barriers where any of the following apply:
  1. Penetrations are tested in accordance with ASTM E 119 or UL 263 as part of the fire-resistance-rated assembly.
  2. Ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire damper would interfere with the operation of a smoke control system.
  3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than No. 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals.
Upcodes Diagrams
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a fire barrier that serves as a horizontal exit.
Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
Exceptions:
  1. Fire dampers are not required at penetrations of shafts where:
    1. Steel exhaust subducts are extended at least 22 inches (559 mm) vertically in exhaust shafts, provided there is a continuous airflow upward to the outside; or
    2. Penetrations are tested in accordance with ASTM E 119 or UL 263 as part of the fire-resistance-rated assembly; or
    3. Ducts are used as part of an approved smoke control system designed and installed in accordance with Section 909 and where the fire damper will interfere with the operation of the smoke control system; or
    4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
  2. In Group B and R occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, smoke dampers are not required at penetrations of shafts where:
    1. Kitchen, clothes dryer, bathroom and toilet room exhaust openings are installed with steel exhaust subducts, having a minimum wall thickness of 0.0187-inch (0.4712 mm) (No. 26 gage);
    2. The subducts extend at least 22 inches (559 mm) vertically; and
    3. An exhaust fan is installed at the upper terminus of the shaft that is powered continuously in accordance with the provisions of Section 909.11, so as to maintain a continuous upward airflow to the outside.
  3. Smoke dampers are not required at penetration of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.
  4. Smoke dampers are not required at penetrations of shafts where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 and where the smoke damper will interfere with the operation of the smoke control system.
  5. Fire dampers and combination fire/smoke dampers are not required in kitchen and clothes dryer exhaust systems when installed in accordance with the mechanical code.
Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing.
Exceptions: In occupancies other than Group H, fire dampers are not required where any of the following apply:
  1. Corridor walls in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and the duct is protected as a through penetration in accordance with Section 713.
  2. Tenant partitions in covered mall buildings where the walls are not required by provisions elsewhere in the code to extend to the underside of the floor or roof sheathing, slab or deck above.
  3. The duct system is constructed of approved materials in accordance with the mechanical code and the duct penetrating the wall complies with all of the following requirements:
    1. The duct shall not exceed 100 square inches (0.06 m2).
    2. The duct shall be constructed of steel a minimum of 0.0217 inch (0.55 mm) in thickness.
    3. The duct shall not have openings that communicate the corridor with adjacent spaces or rooms.
    4. The duct shall be installed above a ceiling.
    5. The duct shall not terminate at a wall register in the fire-resistance-rated wall.
    6. A minimum 12-inch-long (305 mm) by 0.060-inch-thick (1.52 mm) steel sleeve shall be centered in each duct opening. The sleeve shall be secured to both sides of the wall and all four sides of the sleeve with minimum 11/2-inch by 11/2-inch by 0.060-inch (38 mm by 38 mm by 1.52 mm) steel retaining angles. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. The annular space between the steel sleeve and the wall opening shall be filled with mineral wool batting on all sides.
  4. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, and are in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure's HVAC system. Such a duct system shall be constructed of sheet steel not less than No. 26 gage thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals.
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 715.4.3.
Exceptions:
  1. Smoke dampers are not required where the building is equipped throughout with an approved smoke control system in accordance with Section 909, and smoke dampers are not necessary for the operation and control of the system.
  2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and there are no openings serving the corridor.
A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 716.3.3.2.
Exception: Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel.
Ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings in accordance with Section 705.10 shall be protected with listed fire dampers installed in accordance with their listing.
A listed smoke damper designed to resist the passage of smoke shall be provided at each point that an air transfer opening penetrates a smoke partition. Smoke dampers and smoke damper actuation methods shall comply with Section 716.3.3.2.
Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized.
Penetrations by ducts and air transfer openings of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 708 or shall comply with Sections 716.6.1 through 716.6.3.
In occupancies other than Groups I-2 and I-3, a duct constructed of approved materials in accordance with the mechanical code that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection, provided a listed fire damper is installed at the floor line or the duct is protected in accordance with Section 713.4. For air transfer openings, see Exception 7 to Section 708.2.
Exception: A duct is permitted to penetrate three floors or less without a fire damper at each floor, provided such duct meets all of the following requirements:
  1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel having a minimum wall thickness of 0.0187 inch (0.4712 mm) (No. 26 gage).
  2. The duct shall open into only one dwelling or sleeping unit and the duct system shall be continuous from the unit to the exterior of the building.
  3. The duct shall not exceed 4-inch (102 mm) nominal diameter and the total area of such ducts shall not exceed 100 square inches (0.065 m2) in any 100 square feet (9.3 m2) of floor area.
  4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 or UL 263 time-temperature conditions under a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
  5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a listed ceiling radiation damper installed in accordance with Section 716.6.2.1.
Ducts and air transfer openings constructed of approved materials in accordance with the mechanical code that penetrate the ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with one of the following:
  1. A shaft enclosure in accordance with Section 708.
  2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fireresistance-rated floor/ceiling or roof/ceiling assembly.
  3. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire-resistance-rated floor/ ceiling or roof/ceiling assembly.
Ceiling radiation dampers shall be tested in accordance with Section 716.3.1. Ceiling radiation dampers shall be installed in accordance with the details listed in the fire-resistance-rated assembly and the manufacturer's installation instructions and the listing. Ceiling radiation dampers are not required where either of the following applies:
  1. Tests in accordance with ASTM E 119 or UL 263 have shown that ceiling radiation dampers are not necessary in order to maintain the fire-resistance rating of the assembly.
  2. Where exhaust duct penetrations are protected in accordance with Section 713.4.1.2, are located within the cavity of a wall and do not pass through another dwelling unit or tenant space.
Duct systems constructed of approved materials in accordance with the mechanical code that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods:
  1. A shaft enclosure in accordance with Section 708.
  2. The duct connects not more than two stories, and the annular space around the penetrating duct is protected with an approved noncombustible material that resists the free passage of flame and the products of combustion.
  3. The duct connects not more than three stories, and the annular space around the penetrating duct is protected with an approved noncombustible material that resists the free passage of flame and the products of combustion and a fire damper is installed at each floor line.
    Exception: Fire dampers are not required in ducts within individual residential dwelling units.
Flexible ducts and air connectors shall not pass through any fire-resistance-rated assembly. Flexible air connectors shall not pass through any wall, floor or ceiling.
Fireblocking and draftstopping shall be installed in combustible concealed locations in accordance with this section. Fireblocking shall comply with Section 717.2. Draftstopping in floor/ceiling spaces and attic spaces shall comply with Sections 717.3 and 717.4, respectively. The permitted use of combustible materials in concealed spaces of buildings of Type I or II construction shall be limited to the applications indicated in Section 717.5.
In combustible construction, fireblocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fireblocking shall be installed in the locations specified in Sections 717.2.2 through 717.2.7.
Upcodes Diagrams
Fireblocking shall consist of the following materials:
  1. Two-inch (51 mm) nominal lumber.
  2. Two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints.
  3. One thickness of 0.719-inch (18.3 mm) wood structural panels with joints backed by 0.719-inch (18.3 mm) wood structural panels.
  4. One thickness of 0.75-inch (19.1 mm) particleboard with joints backed by 0.75-inch (19 mm) particleboard.
  5. One-half-inch (12.7 mm) gypsum board.
  6. One-fourth-inch (6.4 mm) cement-based millboard.
  7. Batts or blankets of mineral wool, mineral fiber or other approved materials installed in such a manner as to be securely retained in place.
Upcodes Diagrams
Batts or blankets of mineral wool or mineral fiber or other approved nonrigid materials shall be permitted for compliance with the 10-foot (3048 mm) horizontal fireblocking in walls constructed using parallel rows of studs or staggered studs.
Unfaced fiberglass batt insulation used as fireblocking shall fill the entire cross section of the wall cavity to a minimum height of 16 inches (406 mm) measured vertically. When piping, conduit or similar obstructions are encountered, the insulation shall be packed tightly around the obstruction.
Loose-fill insulation material, insulating foam sealants and caulk materials shall not be used as a fireblock unless specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and to retard the spread of fire and hot gases.
The integrity of fireblocks shall be maintained.
Batts or blankets of mineral or glass fiber or other approved nonrigid materials shall be allowed as fireblocking in walls constructed using parallel rows of studs or staggered studs.
Fireblocking shall be provided in concealed spaces of stud walls and partitions, including furred spaces, and parallel rows of studs or staggered studs, as follows:
  1. Vertically at the ceiling and floor levels.
  2. Horizontally at intervals not exceeding 10 feet (3048 mm).
Upcodes Diagrams
Fireblocking shall be provided at interconnections between concealed vertical stud wall or partition spaces and concealed horizontal spaces created by an assembly of floor joists or trusses, and between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings, cove ceilings and similar locations.
Upcodes Diagrams
Fireblocking shall be provided in concealed spaces between stair stringers at the top and bottom of the run. Enclosed spaces under stairs shall also comply with Section 1009.6.3.
Upcodes Diagrams
Where required by Exception 6 of Section 708.2, Exception 1 of Section 713.4.1.2 or Section 713.4.2, fireblocking of the annular space around vents, pipes, ducts, chimneys and fireplaces at ceilings and floor levels shall be installed with a material specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and resist the free passage of flame and the products of combustion.
Upcodes Diagrams
Factory-built chimneys and fireplaces shall be fireblocked in accordance with UL 103 and UL 127.
Fireblocking shall be installed within concealed spaces of exterior wall finish and other exterior architectural elements where permitted to be of combustible construction as specified in Section 1406 or where erected with combustible frames, at maximum intervals of 20 feet (6096 mm), so that there will be no open space exceeding 100 square feet (9.3 m3). Where wood furring strips are used, they shall be of approved wood of natural decay resistance or preservative-treated wood. If noncontinuous, such elements shall have closed ends, with at least 4 inches (102 mm) of separation between sections.
Exceptions:
  1. Deleted.
  2. Fireblocking shall not be required where installed on noncombustible framing and the face of the exterior wall finish exposed to the concealed space is covered by one of the following materials:
    1. 2.1. Aluminum having a minimum thickness of 0.019 inch (0.5 mm).
    2. 2.2. Corrosion-resistant steel having a base metal thickness not less than 0.016 inch (0.4 mm) at any point.
    3. 2.3. Other approved noncombustible materials.
Where wood sleepers are used for laying wood flooring on masonry or concrete fire-resistance-rated floors, the space between the floor slab and the underside of the wood flooring shall be filled with an approved material to resist the free passage of flame and products of combustion or fireblocked in such a manner that there will be no open spaces under the flooring that will exceed 100 square feet (9.3 m2) in area and such space shall be filled solidly under permanent partitions so that there is no communication under the flooring between adjoining rooms.
Exceptions:
  1. Fireblocking is not required for slab-on-grade floors in gymnasiums.
  2. Fireblocking is required only at the juncture of each alternate lane and at the ends of each lane in a bowling facility.
Upcodes Diagrams
In combustible construction, draftstopping shall be installed to subdivide floor/ceiling assemblies in the locations prescribed in Sections 717.3.2 through 717.3.3.
Draftstopping materials shall not be less than1/2-inch (12.7 mm) gypsum board, 3/8-inch (9.5 mm) wood structural panel, 3/8-inch (9.5 mm) particleboard, 1-inch (25-mm) nominal lumber, cement fiberboard, batts or blankets of mineral wool or glass fiber, or other approved materials adequately supported. The integrity of draftstops shall be maintained.
Upcodes Diagrams
Draftstopping shall be provided in floor/ceiling spaces in Group R buildings. Draftstopping shall be located above and in line with the dwelling unit and sleeping unit separations.
Exceptions:
  1. Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces.
In other groups, draftstopping shall be installed so that horizontal floor areas do not exceed 1,000 square feet (93 m2).
Exception: Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
In combustible construction, draftstopping shall be installed to subdivide attic spaces and concealed roof spaces in the locations prescribed in Sections 717.4.2 and 717.4.3. Ventilation of concealed roof spaces shall be maintained in accordance with Section 1203.2.
Materials utilized for draftstopping of attic spaces shall comply with Section 717.3.1.
Openings in the partitions shall be protected by self-closing doors with automatic latches constructed as required for the partitions.
Draftstopping shall be provided in attics, mansards, overhangs or other concealed roof spaces of Group R-1 and Group R-2 buildings with three or more dwelling units and in all Group R-1 buildings. Draftstopping shall be installed above, and in line with, sleeping unit and dwelling unit separation walls that do not extend to the underside of the roof sheathing above.
Exceptions:
  1. Where corridor walls provide a sleeping unit or dwelling unit separation, draftstopping shall only be required above one of the corridor walls.
  2. Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  3. In occupancies in Group R-2 that do not exceed four stories above grade plane, the attic space shall be subdivided by draftstops into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller.
  4. Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces.
Draftstopping shall be installed in attics and concealed roof spaces, such that any horizontal area does not exceed 3,000 square feet (279 m2).
Exception: Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Combustible materials shall not be permitted in concealed spaces of buildings of Type I or II construction.
Exceptions:
  1. Combustible materials in accordance with Section 603.
  2. Combustible materials exposed within plenums complying with Section 602 of the mechanical code.
  3. Class A interior finish materials classified in accordance with Section 803.
  4. Combustible piping within partitions or shaft enclosures installed in accordance with the provisions of this code.
  5. Combustible piping within concealed ceiling spaces installed in accordance with the mechanical code and the plumbing code.
  6. Combustible insulation and covering on pipe and tubing, installed in concealed spaces other than plenums, complying with Section 719.7.
The minimum thickness of gypsum plaster or portland cement plaster used in a fire-resistance-rated system shall be determined by the prescribed fire tests. The plaster thickness shall be measured from the face of the lath where applied to gypsum lath or metal lath.
For fire-resistance purposes, 1/2 inch (12.7 mm) of unsanded gypsum plaster shall be deemed equivalent to 3/4 inch (19.1 mm) of one-to-three gypsum sand plaster or 1 inch (25 mm) of portland cement sand plaster.
In buildings of Type I and II construction, plaster shall be applied directly on concrete or masonry or on approved noncombustible plastering base and furring.
Plaster protection more than 1 inch (25 mm) in thickness shall be reinforced with an additional layer of approved lath embedded at least 3/4 inch (19.1 mm) from the outer surface and fixed securely in place.
Exception: Solid plaster partitions or where otherwise determined by fire tests.
In reinforced concrete construction, gypsum plaster or portland cement plaster is permitted to be substituted for 1/2 inch (12.7 mm) of the required poured concrete protection, except that a minimum thickness of 3/8 inch (9.5 mm) of poured concrete shall be provided in reinforced concrete floors and 1 inch (25 mm) in reinforced concrete columns in addition to the plaster finish. The concrete base shall be prepared in accordance with Section 2510.7.
Insulating materials, including facings such as vapor retarders and vapor-permeable membranes, similar coverings and all layers of single and multilayer reflective foil insulations, shall comply with the requirements of this section. Where a flame spread index or a smoke-developed index is specified in this section, such index shall be determined in accordance with ASTM E 84 or UL 723. Any material that is subject to an increase in flame spread index or smoke-developed index beyond the limits herein established through the effects of age, moisture or other atmospheric conditions shall not be permitted.
Exceptions:
  1. Fiberboard insulation shall comply with Chapter 23.
  2. Foam plastic insulation shall comply with Chapter 26.
  3. Duct and pipe insulation and duct and pipe coverings and linings in plenums shall comply with the mechanical code.
  4. All layers of single and multilayer reflective plastic core insulation shall comply with Section 2613.
Insulating materials, where concealed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450.
Exception: Cellulose loose-fill insulation that is not spray applied, complying with the requirements of Section 719.6, shall only be required to meet the smoke-developed index of not more than 450.
Where such materials are installed in concealed spaces in buildings of Type III, IV or V construction, the flame spread and smoke-developed limitations do not apply to facings, coverings, and layers of reflective foil insulation that are installed behind and in substantial contact with the unexposed surface of the ceiling, wall or floor finish.
Exception: All layers of single and multilayer reflective plastic core insulation shall comply with Section 2613.
Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450.
Exception: Cellulose loose-fill insulation that is not spray applied complying with the requirements of Section 719.6 shall only be required to meet the smoke-developed index of not more than 450.
Exposed insulation materials installed on attic floors shall have a critical radiant flux of not less than 0.12 watt per square centimeter when tested in accordance with ASTM E 970.
Loose-fill insulation materials that cannot be mounted in the ASTM E 84 or UL 723 apparatus without a screen or artificial supports shall comply with the flame spread and smoke-developed limits of Sections 719.2 and 719.3 when tested in accordance with CAN/ULC S102.2.
Exception: Cellulose loose-fill insulation shall not be required to be tested in accordance with CAN/ULC S102.2, provided such insulation complies with the requirements of Section 719.2 or 719.3, as applicable, and Section 719.6.
The use of combustible roof insulation not complying with Sections 719.2 and 719.3 shall be permitted in any type of construction provided it is covered with approved roof coverings directly applied thereto.
Cellulose loose-fill insulation shall comply with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404. Each package of such insulating material shall be clearly labeled in accordance with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404.
Insulation and covering on pipe and tubing shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450.
Exceptions:
  1. Insulation and covering on pipe and tubing installed in plenums shall comply with the mechanical code.
  2. Materials installed for protection against heat and sharp edges to comply with the accessibility provisions.
The provisions of this section contain prescriptive details of fire-resistance-rated building elements, components or assemblies. The materials of construction listed in Tables 720.1(1), 720.1(2), and 720.1(3) shall be assumed to have the fire-resistance ratings prescribed therein. Where materials that change the capacity for heat dissipation are incorporated into a fire-resistance-rated assembly, fire test results or other substantiating data shall be made available to the building official to show that the required fire-resistance-rating time period is not reduced.
MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSm
STRUCTURAL
PARTS TO BE
PROTECTED
ITEM
NUMBER
INSULATING MATERIAL USEDMINIMUM THICKNESS OF
INSULATING MATERIAL
FOR THE FOLLOWING
FIRE-RESISTANCE
PERIODS (inches)
4 hour3 hour2 hour1 hour
1. Steel columns
and all of
primary trusses
1-1.1Carbonate, lightweight and sand-lightweight aggregate concrete, members 6" × 6" or
greater (not including sandstone, granite and siliceous gravel).a
21/2211/21
1-1.2Carbonate, lightweight and sand-lightweight aggregate concrete, members 8" × 8" or
greater (not including sandstone, granite and siliceous gravel).a
211/211
1-1.3Carbonate, lightweight and sand-lightweight aggregate concrete, members
12" × 12" or greater (not including sandstone, granite and siliceous gravel).a
11/2111
1-1.4Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 6" × 6"
or greater.a
3211/21
1-1.5Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 8" × 8"
or greater.a
21/2211
1-1.6Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members
12" × 12" or greater.a
2111
1-2.1Clay or shale brick with brick and mortar fill.a33/421/4
1-3.14" hollow clay tile in two 2" layers; 1/2" mortar between tile and column; 3/8" metal
mesh 0.046 " wire diameter in horizontal joints; tile fill.a
4
1-3.22" hollow clay tile; 3/4" mortar between tile and column; 3/8" metal mesh 0.046" wire
diameter in horizontal joints; limestone concrete fill;a plastered with 3/4"
gypsum plaster.
3
1-3.32" hollow clay tile with outside wire ties 0.08 " diameter at each course of tile or 3/8"
metal mesh 0.046 " diameter wire in horizontal joints; limestone or trap-rock
concrete filla extending 1" outside column on all sides.
3
1-3.42" hollow clay tile with outside wire ties 0.08" diameter at each course of tile with or
without concrete fill; 3/4" mortar between tile and column.
2
1-4.1Cement plaster over metal lath wire tied to 3/4" cold-rolled vertical channels with
0.049" (No.18 B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed
1:2 1/2 by volume, cement to sand.
21/2b7/8
1-5.1Vermiculite concrete, 1:4 mix by volume over paperbacked wire fabric lath wrapped
directly around column with additional 2" × 2" 0.065"/0.065" (No. 16/16 B.W. gage)
wire fabric placed 3/4" from outer concrete surface. Wire fabric tied with 0.049" (No.
18 B.W. gage) wire spaced 6" on center for inner layer and 2" on center for
outer layer.
2
1-6.1Perlite or vermiculite gypsum plaster over metal lath wrapped around column and
furred 11/4" from column flanges. Sheets lapped at ends and tied at 6" intervals with
0.049" (No. 18 B.W. gage) tie wire. Plaster pushed through to flanges.
11/21
1-6.2Perlite or vermiculite gypsum plaster over self-furring metal lath wrapped directly
around column, lapped 1" and tied at 6" intervals with 0.049" (No. 18 B.W. gage)
wire.
13/413/81
1-6.3Perlite or vermiculite gypsum plaster on metal lath applied to 3/4" cold-rolled
channels spaced 24" apart vertically and wrapped flatwise around column.
11/2
1-6.4Perlite or vermiculite gypsum plaster over two layers of 1/2" plain full-length gypsum
lath applied tight to column flanges. Lath wrapped with 1" hexagonal mesh of No.
20 gage wire and tied with doubled 0.035" diameter (No. 18 B.W. gage) wire ties
spaced 23" on center. For three-coat work, the plaster mix for the second coat shall
not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate for the
3-hour system.
21/22
1-6.5Perlite or vermiculate gypsum plaster over one layer of 1/2" plain full-length gypsum
lath applied tight to column flanges. Lath tied with doubled 0.049" (No. 18 B.W.
gage) wire ties spaced 23" on center and scratch coat wrapped with 1" hexagonal
mesh 0.035" (No. 20 B.W. gage) wire fabric. For three-coat work, the plaster mix for
the second coat shall not exceed 100 pounds of gypsum to 21/2 cubic feet
of aggregate.
2
1-7.1Multiple layers of 1/2" gypsum wallboardc adhesivelyd secured to column flanges and
successive layers. Wallboard applied without horizontal joints. Corner edges of each
layer staggered. Wallboard layer below outer layer secured to column with doubled
0.049" (No. 18 B.W. gage) steel wire ties spaced 15" on center. Exposed corners
taped and treated.
21
1-7.2Three layers of 5/8" Type X gypsum wallboard.c First and second layer held in place
by 1/8" diameter by 13/8" long ring shank nails with 5/16" diameter heads spaced 24"
on center at corners. Middle layer also secured with metal straps at mid-height and
18" from each end, and by metal corner bead at each corner held by the metal straps.
Third layer attached to corner bead with 1" long gypsum wallboard screws
spaced 12" on center.
17/8
1-7.3Three layers of 5/8" Type X gypsum wallboard,c each layer screw attached to 15/8"
steel studs 0.018" thick (No. 25 carbon sheet steel gage) at each corner of column.
Middle layer also secured with 0.049" (No. 18 B.W. gage) double-strand steel wire
ties, 24" on center. Screws are No. 6 by 1" spaced 24" on center for inner layer, No.
6 by 15/8" spaced 12" on center for middle layer and No. 8 by 21/4" spaced 12" on
center for outer layer.
17/8
1-8.1Wood-fibered gypsum plaster mixed 1:1 by weight gypsum-to-sand aggregate
applied over metal lath. Lath lapped 1" and tied 6" on center at all end, edges and
spacers with 0.049" (No. 18 B.W. gage) steel tie wires. Lath applied over 1/2" spacers
made of 3/4" furring channel with 2" legs bent around each corner. Spacers located 1"
from top and bottom of member and a maximum of 40" on center and wire tied with
a single strand of 0.049" (No. 18 B.W. gage) steel tie wires. Corner bead tied to the
lath at 6" on center along each corner to provide plaster thickness.
15/8
1-9.1Minimum W8x35 wide flange steel column (w/d ≥ 0.75) with each web cavity filled
even with the flange tip with normal weight carbonate or siliceous aggregate
concrete (3,000 psi minimum compressive strength with 145 pcf ± 3 pcf unit
weight). Reinforce the concrete in each web cavity with a minimum No. 4 deformed
reinforcing bar installed vertically and centered in the cavity, and secured to the
column web with a minimum No. 2 horizontal deformed reinforcing bar welded to
the web every 18" on center vertically. As an alternative to the No. 4 rebar, 3/4"
diameter by 3" long headed studs, spaced at 12" on center vertically, shall be welded
on each side of the web midway between the column flanges.
See Note n
2. Webs or
flanges of steel
beams and
girders
2-1.1Carbonate, lightweight and sand-lightweight aggregate concrete (not including
sandstone, granite and siliceous gravel) with 3" or finer metal mesh placed 1" from
the finished surface anchored to the top flange and providing not less than 0.025
square inch of steel area per foot in each direction.
211/211
2-1.2Siliceous aggregate concrete and concrete excluded in Item 2-1.1 with 3" or finer
metal mesh placed 1" from the finished surface anchored to the top flange and
providing not less than 0.025 square inch of steel area per foot in each direction.
21/2211/21
2-2.1Cement plaster on metal lath attached to 3/4" cold-rolled channels with 0.04" (No. 18
B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 1:2 1/2 by volume,
cement to sand.
21/2b7/8
2-3.1Vermiculite gypsum plaster on a metal lath cage, wire tied to 0.165" diameter (No. 8
B.W. gage) steel wire hangers wrapped around beam and spaced 16" on center.
Metal lath ties spaced approximately 5" on center at cage sides and bottom.
7/8
2-4.1Two layers of 5/8" Type X gypsum wallboardc are attached to U-shaped brackets
spaced 24" on center. 0.018" thick (No. 25 carbon sheet steel gage) 15/8" deep by 1"
galvanized steel runner channels are first installed parallel to and on each side of the
top beam flange to provide a 1/2" clearance to the flange. The channel runners are
attached to steel deck or concrete floor construction with approved fasteners spaced
12" on center. U-shaped brackets are formed from members identical to the channel
runners. At the bent portion of the U-shaped bracket, the flanges of the channel are
cut out so that 15/8" deep corner channels can be inserted without attachment parallel
to each side of the lower flange.
11/4
As an alternate, 0.021" thick (No. 24 carbon sheet steel gage) 1"× 2" runner and
corner angles may be used in lieu of channels, and the web cutouts in the U-shaped
brackets may be omitted. Each angle is attached to the bracket with 1/2"-long No. 8
self-drilling screws. The vertical legs of the U-shaped bracket are attached to the
runners with one 1/2" long No. 8 self-drilling screw. The completed steel framing
provides a 21/8" and 11/2" space between the inner layer of wallboard and the sides
and bottom of the steel beam, respectively. The inner layer of wallboard is attached
to the top runners and bottom corner channels or corner angles with 11/4"-long No. 6
self-drilling screws spaced 16" on center. The outer layer of wallboard is applied
with 13/4"-long No. 6 self-drilling screws spaced 8" on center. The bottom corners
are reinforced with metal corner beads.
2-4.2Three layers of 5/8" Type X gypsum wallboardc attached to a steel suspension system
as described immediately above utilizing the 0.018" thick (No. 25 carbon sheet steel
gage) 1"× 2" lower corner angles. The framing is located so that a 21/8" and 2" space
is provided between the inner layer of wallboard and the sides and bottom of the
beam, respectively. The first two layers of wallboard are attached as described
immediately above. A layer of 0.035" thick (No. 20 B.W. gage) 1" hexagonal
galvanized wire mesh is applied under the soffit of the middle layer and up the sides
approximately 2". The mesh is held in position with the No. 6 15/8"-long screws
installed in the vertical leg of the bottom corner angles. The outer layer of wallboard
is attached with No. 6 21/4"-long screws spaced 8" on center. One screw is also
installed at the mid-depth of the bracket in each layer. Bottom corners are finished as
described above.
17/8
3. Bonded
pretensioned
reinforcement in
prestressed
concretee
3-1.1Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete
Beams or girders
4g3g21/211/2
Solid slabsh211/21
4. Bonded or
unbonded
post-tensioned
tendons in
prestressed
4-1.1Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete
Unrestrained members:
Solid slabsh211/2
Beams and girdersj
8" wide41/221/213/4
greater than 12" wide321/2211/2
4-1.2Carbonate, lightweight, sand-lightweight and siliceous aggregate
Restrained members:k
Solid slabsh11/413/4
Beams and girdersj
8" wide21/2213/4
greater than 12" wide213/411/2
5. Reinforcing
steel in reinforced
concrete columns,
beams girders and
trusses
5-1.1Carbonate, lightweight and sand-lightweight aggregate concrete, members 12"
or larger, square or round. (Size limit does not apply to beams and girders
monolithic with floors.)
11/211/211/211/2
Siliceous aggregate concrete, members 12" or larger, square or round. (Size limit
does not apply to beams and girders monolithic with floors.)
211/211/211/2
6. Reinforcing
steel in reinforced
concrete joistsl
6-1.1Carbonate, lightweight and sand-lightweight aggregate concrete.11/411/413/4
6-1.2Siliceous aggregate concrete.13/411/213/4
7. Reinforcing and
tie rods in floor
and roof slabsl
7-1.1Carbonate, lightweight and sand-lightweight aggregate concrete.113/43/4
7-1.2Siliceous aggregate concrete.11/4113/4
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2, 1 cubic foot = 0.0283 m3, 1 pound per cubic foot = 16.02 kg/m3.
  1. Reentrant parts of protected members to be filled solidly.
  2. Two layers of equal thickness with a 3/4-inch airspace between.
  3. For all of the construction with gypsum wallboard described in Table 720.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard and the joints on the face layer are reinforced, and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  4. An approved adhesive qualified under ASTM E 119 or UL 263.
  5. Where lightweight or sand-lightweight concrete having an oven-dry weight of 110 pounds per cubic foot or less is used, the tabulated minimum cover shall be permitted to be reduced 25 percent, except that in no case shall the cover be less than 3/4 inch in slabs or 11/2 inches in beams or girders.
  6. For solid slabs of siliceous aggregate concrete, increase tendon cover 20 percent.
  7. Adequate provisions against spalling shall be provided by U-shaped or hooped stirrups spaced not to exceed the depth of the member with a clear cover of 1 inch.
  8. Prestressed slabs shall have a thickness not less than that required in Table 720.1(3) for the respective fire-resistance time period.
  9. Fire coverage and end anchorages shall be as follows: Cover to the prestressing steel at the anchor shall be 1/2 inch greater than that required away from the anchor. Minimum cover to steel-bearing plate shall be 1 inch in beams and 3/4 inch in slabs.
  10. For beam widths between 8 inches and 12 inches, cover thickness shall be permitted to be determined by interpolation.
  11. Interior spans of continuous slabs, beams and girders shall be permitted to be considered restrained.
  12. For use with concrete slabs having a comparable fire endurance where members are framed into the structure in such a manner as to provide equivalent performance to that of monolithic concrete construction.
  13. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in GA 600 shall be accepted as if herein listed.
  14. No additional insulating material is required on the exposed outside face of the column flange to achieve a 1-hour fire-resistance rating.
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, o, p
MATERIALITEM
NUMBER
CONSTRUCTIONMINIMUM FINISHED
THICKNESS FACE-TO-FACEb
(inches)
4 hour3 hour2 hour1 hour
1. Brick of clay or
shale
1-1.1Solid brick of clay or shalec.64.93.82.7
1-1.2Hollow brick, not filled.5.04.33.42.3
1-1.3Hollow brick unit wall, grout or filled with perlite vermiculite or expanded shale
aggregate.
6.65.54.43.0
1-2.14" nominal thick units at least 75 percent solid backed with a hat-shaped metal
furring channel 3/4" thick formed from 0.021" sheet metal attached to the brick
wall on 24" centers with approved fasteners, and 1/2" Type X gypsum wallboard
attached to the metal furring strips with 1"-long Type S screws spaced 8" on
center.
5d
2. Combination of
clay brick and
load-bearing
2-1.14" solid brick and 4" tile (at least 40 percent solid).8
2-1.24" solid brick and 8" tile (at least 40 percent solid).12
3. Concrete masonry units3-1.1f, gExpanded slag or pumice.4.74.03.22.1
3-1.2f, gExpanded clay, shale or slate.5.14.43.62.6
3-1.3fLimestone, cinders or air-cooled slag.5.95.04.02.7
3-1.4f, gCalcareous or siliceous gravel.6.25.34.22.8
4. Solid concreteh, i4-1.1Siliceous aggregate concrete.7.06.25.03.5
Carbonate aggregate concrete.6.65.74.63.2
Sand-lightweight concrete.5.44.63.82.7
Lightweight concrete.5.14.43.62.5
5. Glazed or
unglazed facing
tile, nonload-
bearing
5-1.1One 2" unit cored 15 percent maximum and one 4" unit cored 25 percent
maximum with 3/4" mortar-filled collar joint. Unit positions reversed in alternate
courses.
63/8
5-1.2One 2" unit cored 15 percent maximum and one 4" unit cored 40 percent
maximum with 3/4" mortar-filled collar joint. Unit positions side with 3/4" gypsum
plaster. Two wythes tied together every fourth course with No. 22 gage
corrugated metal ties.
63/4
5-1.3One unit with three cells in wall thickness, cored 29 percent maximum.6
5-1.4One 2" unit cored 22 percent maximum and one 4" unit cored 41 percent
maximum with 1/4" mortar-filled collar joint. Two wythes tied together every
third course with 0.030" (No. 22 galvanized sheet steel gage) corrugated metal
ties.
6
5-1.5One 4" unit cored 25 percent maximum with 3/4" gypsum plaster on one side.43/4
5-1.6One 4" unit with two cells in wall thickness, cored 22 percent maximum.4
5-1.7One 4" unit cored 30 percent maximum with 3/4" vermiculite gypsum plaster on
one side.
41/2
5-1.8One 4" unit cored 39 percent maximum with 3/4" gypsum plaster on one side.41/2
6. Solid gypsum
plaster
6-1.13/4" by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16"
on center with 2.6-pound flat metal lath applied to one face and tied with 0.049"
(No. 18 B.W. Gage) wire at 6" spacing. Gypsum plaster each side mixed 1:2 by
weight, gypsum to sand aggregate.
2d
6-1.23/4" by 0.05" (No. 16 carbon sheet steel gage) cold-rolled channels 16" on center
with metal lath applied to one face and tied with 0.049" (No. 18 B.W. gage) wire
at 6" spacing. Perlite or vermiculite gypsum plaster each side. For three-coat
work, the plaster mix for the second coat shall not exceed 100 pounds of gypsum
to 21/2 cubic feet of aggregate for the 1-hour system.
21/2d2d
6-1.33/4" by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16"
on center with 3/8" gypsum lath applied to one face and attached with sheet metal
clips. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate.
2d
6-2.1Studless with 1/2" full-length plain gypsum lath and gypsum plaster each side.
Plaster mixed 1:1 for scratch coat and 1:2 for brown coat, by weight, gypsum to
sand aggregate.
2d
6-2.2Studless with 1/2" full-length plain gypsum lath and perlite or vermiculite gypsum
plaster each side.
21/2d2d
6-2.3Studless partition with 3/8" rib metal lath installed vertically adjacent edges tied
6" on center with No. 18 gage wire ties, gypsum plaster each side mixed 1:2 by
weight, gypsum to sand aggregate.
2d
7. Solid perlite
and portland
cement
7-1.1Perlite mixed in the ratio of 3 cubic feet to 100 pounds of portland cement and
machine applied to stud side of 11/2" mesh by 0.058-inch (No. 17 B.W. gage)
paper-backed woven wire fabric lath wire-tied to 4" -deep steel trussed wirej studs
16" on center. Wire ties of 0.049" (No. 18 B.W. gage) galvanized steel wire 6" on
center vertically.
31/8d
8. Solid neat wood
fibered gypsum
plaster
8-1.13/4" by 0.055-inch (No. 16 carbon sheet steel gage) cold-rolled channels, 12" on
center with 2.5-pound flat metal lath applied to one face and tied with 0.049"
(No. 18 B.W. gage) wire at 6" spacing. Neat gypsum plaster applied each side.
2d
9. Solid wallboard
partition
9-1.1One full-length layer 1/2" Type X gypsum wallboarde laminated to each side of 1"
full-length V-edge gypsum coreboard with approved laminating compound.
Vertical joints of face layer and coreboard staggered at least 3".
2d
10. Hollow (
studless) gypsum
wallboard
partition
10-1.1One full-length layer of 5/8" Type X gypsum wallboarde attached to both sides of
wood or metal top and bottom runners laminated to each side of 1" × 6"
full-length gypsum coreboard ribs spaced 2" on center with approved laminating
compound. Ribs centered at vertical joints of face plies and joints staggered 24"
in opposing faces. Ribs may be recessed 6" from the top and bottom.
21/4d
10-1.21" regular gypsum V-edge full-length backing board attached to both sides of
wood or metal top and bottom runners with nails or 15/8" drywall screws at 24"
on center. Minimum width of rumors 15/8". Face layer of 1/2" regular full-length
gypsum wallboard laminated to outer faces of backing board with approved
laminating compound.
45/8d
11. Noncombustible
studs—interior
partition with plaster
each side
11-1.131/4" × 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 24" on center.
5/8" gypsum plaster on metal lath each side mixed 1:2 by weight, gypsum to
sand aggregate.
43/4d
11-1.233/8" × 0.055" (No. 16 carbon sheet steel gage) approved nailablek studs spaced
24" on center. 5/8" neat gypsum wood-fibered plaster each side over 3/8" rib
metal lath nailed to studs with 6d common nails, 8" on center. Nails driven 11/4"
and bent over.
55/8
11-1.34" × 0.044" (No. 18 carbon sheet steel gage) channel-shaped steel studs at 16"
on center. On each side approved resilient clips pressed onto stud flange at 16"
vertical spacing, 1/4" pencil rods snapped into or wire tied onto outer loop of
clips, metal lath wire-tied to pencil rods at 6" intervals, 1" perlite gypsum
plaster, each side.
75/8d
11-1.421/2" × 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 16" on center.
Wood fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate
applied on 3/4-pound metal lath wire tied to studs, each side. 3/4" plaster applied
over each face, including finish coat.
41/4d
12. Wood studs
interior partition
with plaster each
side
12-1.1l, m2" × 4" wood studs 16" on center with 5/8" gypsum plaster on metal lath. Lath
attached by 4d common nails bent over or No. 14 gage by 11/4" by 3/4" crown
width staples spaced 6" on center. Plaster mixed 1:11/2 for scratch coat and 1:3
for brown coat, by weight, gypsum to sand aggregate.
51/8
12-1.2l2" × 4" wood studs 16" on center with metal lath and 7/8" neat wood-fibered
gypsum plaster each side. Lath attached by 6d common nails, 7" on center.
Nails driven 11/4" and bent over.
51/2d
12-1.3 l2" × 4" wood studs 16" on center with 3/8" perforated or plain gypsum lath and
1/2" gypsum plaster each side. Lath nailed with 11/8" by No. 13 gage by 19/64"
head plasterboard blued nails, 4" on center. Plaster mixed 1:2 by weight,
gypsum to sand aggregate.
51/4
12-1.4 l2" × 4" wood studs 16" on center with 3/8" Type X gypsum lath and 1/2"
gypsum plaster each side. Lath nailed with 1 1/8" by No. 13 gage by 19/64" head
plasterboard blued nails, 5" on center. Plaster mixed 1:2 by weight, gypsum to
sand aggregate.
51/4
13.Noncombustible
studs—interior
partition with
gypsum wallboard
each side
13-1.10.018" (No. 25 carbon sheet steel gage) channel-shaped studs 24" on center
with one full-length layer of 5/8" Type X gypsum wallboarde applied vertically
attached with 1" long No. 6 drywall screws to each stud. Screws are 8" on
center around the perimeter and 12" on center on the intermediate stud. The
wallboard may be applied horizontally when attached to 35/8" studs and the
horizontal joints are staggered with those on the opposite side. Screws for the
horizontal application shall be 8" on center at vertical edges and 12" on center
at intermediate studs.
27/8d
13-1.20.018" (No. 25 carbon sheet steel gage) channel-shaped studs 25" on center
with two full-length layers of 1/2" Type X gypsum wallboarde applied vertically
each side. First layer attached with 1"-long, No. 6 drywall screws, 8" on center
around the perimeter and 12" on center on the intermediate stud. Second layer
applied with vertical joints offset one stud space from first layer using 15/8"
long, No. 6 drywall screws spaced 9" on center along vertical joints, 12" on
center at intermediate studs and 24" on center along top and bottom runners.
35/8d
13-1.30.055" (No. 16 carbon sheet steel gage) approved nailable metal studse 24" on
center with full-length 5/8" Type X gypsum wallboarde applied vertically and
nailed 7" on center with 6d cement-coated common nails. Approved metal
fastener grips used with nails at vertical butt joints along studs.
47/8
14.Wood
studs—interior
partition with
gypsum wallboard
each side
14-1.1h, m2" × 4" wood studs 16" on center with two layers of 3/8" regular gypsum
wallboarde each side, 4d coolern or wallboardn nails at 8" on center first layer, 5d
coolern or wallboardn nails at 8" on center second layer with laminating
compound between layers, joints staggered. First layer applied full length
vertically, second layer applied horizontally or vertically.
5
14-1.2l, m2" × 4" wood studs 16" on center with two layers 1/2" regular gypsum wallboarde
applied vertically or horizontally each sidek, joints staggered. Nail base layer
with 5d coolern or wallboardn nails at 8" on center face layer with 8d coolern or
wallboardn nails at 8" on center.
51/2
14-1.3l, m2" × 4" wood studs 24" on center with 5/8" Type X gypsum wallboarde applied
vertically or horizontally nailed with 6d coolern or wallboardn nails at 7" on
center with end joints on nailing members. Stagger joints each side.
43/4
14-1.4l2" × 4" fire-retardant-treated wood studs spaced 24" on center with one layer of
5/8" Type X gypsum wallboarde applied with face paper grain (long dimension)
parallel to studs. Wallboard attached with 6d coolern or wallboardn nails at 7" on
center.
43/4d
14-1.5l, m2" × 4" wood studs 16" on center with two layers 5/8" Type X gypsum
wallboarde each side. Base layers applied vertically and nailed with 6d coolern
or wallboardn nails at 9" on center. Face layer applied vertically or horizontally
and nailed with 8d coolern or wallboardn nails at 7" on center. For nail-adhesive
application, base layers are nailed 6" on center. Face layers applied with coating
of approved wallboard adhesive and nailed 12" on center.
6
14-1.6l2" × 3" fire-retardant-treated wood studs spaced 24" on center with one layer of
5/8 " Type X gypsum wallboarde applied with face paper grain (long dimension)
at right angles to studs. Wallboard attached with 6d cement-coated box nails
spaced 7" on center.
35/8d
15. Exterior or
interior walls
15-1.1l, mExterior surface with 3/4" drop siding over 1/2" gypsum sheathing on 2" × 4"
wood studs at 16" on center, interior surface treatment as required for
1-hour-rated exterior or interior 2" × 4" wood stud partitions. Gypsum sheathing
nailed with 13/4" by No. 11 gage by 7/16" head galvanized nails at 8" on center.
Siding nailed with 7d galvanized smooth box nails.
Varies
15-1.2l, m2" × 4" wood studs 16" on center with metal lath and 3/4" cement plaster on each
side. Lath attached with 6d common nails 7" on center driven to 1" minimum
penetration and bent over. Plaster mix 1:4 for scratch coat and 1:5 for brown
coat, by volume, cement to sand.
53/8
15-1.3l, m2" × 4" wood studs 16" on center with 7/8" cement plaster (measured from the
face of studs) on the exterior surface with interior surface treatment as required
for interior wood stud partitions in this table. Plaster mix 1:4 for scratch coat and
1:5 for brown coat, by volume, cement to sand.
Varies
15-1.435/8" No. 16 gage noncombustible studs 16" on center with 7/8" cement plaster
(measured from the face of the studs) on the exterior surface with interior
surface treatment as required for interior, nonbearing, noncombustible stud
partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat,
by volume, cement to sand.
Variesd
15-1.5m21/4" × 33/4" clay face brick with cored holes over 1/2" gypsum sheathing on
exterior surface of 2" × 4" wood studs at 16" on center and two layers 5/8" Type
X gypsum wallboarde on interior surface. Sheathing placed horizontally or
vertically with vertical joints over studs nailed 6" on center with 13/4" × No. 11
gage by 7/16" head galvanized nails. Inner layer of wallboard placed horizontally
or vertically and nailed 8" on center with 6d coolern or wallboardn nails. Outer
layer of wallboard placed horizontally or vertically and nailed 8" on center with
8d coolern or wallboardn nails. All joints staggered with vertical joints over
studs. Outer layer joints taped and finished with compound. Nail heads covered
with joint compound. 0.035 inch (No. 20 galvanized sheet gage) corrugated
galvanized steel wall ties 3/4" by 65/8" attached to each stud with two 8d coolern
or wallboardn nails every sixth course of bricks.
10
15-1.6l, m2" × 6" fire-retardant-treated wood studs 16" on center. Interior face has two
layers of 5/8" Type X gypsum with the base layer placed vertically and attached
with 6d box nails 12" on center. The face layer is placed horizontally and
attached with 8d box nails 8" on center at joints and 12" on center elsewhere.
The exterior face has a base layer of 5/8" Type X gypsum sheathing placed
vertically with 6d box nails 8" on center at joints and 12" on center elsewhere.
An approved building paper is next applied, followed by self-furred exterior lath
attached with 21/2", No. 12 gage galvanized roofing nails with a 3/8" diameter
head and spaced 6" on center along each stud. Cement plaster consisting of a 1/2"
brown coat is then applied. The scratch coat is mixed in the proportion of 1:3 by
weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of
approved additives or admixtures per sack of cement. The brown coat is mixed
in the proportion of 1:4 by weight, cement to sand with the same amounts of
hydrated lime and approved additives or admixtures used in the scratch coat.
81/4
15-1.7l, m2" × 6" wood studs 16" on center. The exterior face has a layer of 5/8" Type X
gypsum sheathing placed vertically with 6d box nails 8" on center at joints and
12" on center elsewhere. An approved building paper is next applied, followed
by 1" by No. 18 gage self-furred exterior lath attached with 8d by 21/2" long
galvanized roofing nails spaced 6" on center along each stud. Cement plaster
consisting of a 1/2" scratch coat, a bonding agent and a 1/2" brown coat and a
finish coat is then applied. The scratch coat is mixed in the proportion of 1:3 by
weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of
approved additives or admixtures per sack of cement. The brown coat is mixed
in the proportion of 1:4 by weight, cement to sand with the same amounts of
hydrated lime and approved additives or admixtures used in the scratch coat.
The interior is covered with 3/8" gypsum lath with 1" hexagonal mesh of 0.035
inch (No. 20 B.W. gage) woven wire lath furred out 5/16" and 1" perlite or
vermiculite gypsum plaster. Lath nailed with 11/8" by No. 13 gage by 19/64" head
plasterboard glued nails spaced 5" on center. Mesh attached by 13/4" by No. 12
gage by 3/8" head nails with 3/8" furrings, spaced 8" on center. The plaster mix
shall not exceed 100 pounds of gypsum to 21/2 cubic feet of aggregate.
83/8
15-1.8l, m2" × 6" wood studs 16" on center. The exterior face has a layer of 5/8" Type X
gypsum sheathing placed vertically with 6d box nails 8" on center at joints and
12" on center elsewhere. An approved building paper is next applied, followed
by 11/2" by No. 17 gage self-furred exterior lath attached with 8d by 21/2" long
galvanized roofing nails spaced 6" on center along each stud. Cement plaster
consisting of a 1/2" scratch coat, and a 1/2" brown coat is then applied. The
plaster may be placed by machine. The scratch coat is mixed in the proportion of
1:4 by weight, plastic cement to sand. The brown coat is mixed in the proportion
of 1:5 by weight, plastic cement to sand. The interior is covered with 3/8"
gypsum lath with 1" hexagonal mesh of No. 20 gage woven wire lath furred out
5/16" and 1" perlite or vermiculite gypsum plaster. Lath nailed with 11/8" by No.
13 gage by 19/64" head plasterboard glued nails spaced 5" on center. Mesh
attached by 13/4" by No. 12 gage by 3/8" head nails with 3/8" furrings, spaced 8"
on center. The plaster mix shall not exceed 100 pounds of gypsum to 21/2 cubic
feet of aggregate.
83/8
15-1.94" No. 18 gage, nonload-bearing metal studs, 16" on center, with 1" portland
cement lime plaster [measured from the back side of the 3/4-pound expanded
metal lath] on the exterior surface. Interior surface to be covered with 1" of
gypsum plaster on 3/4-pound expanded metal lath proportioned by weight—1:2
for scratch coat, 1:3 for brown, gypsum to sand. Lath on one side of the partition
fastened to 1/4" diameter pencil rods supported by No. 20 gage metal clips,
located 16" on center vertically, on each stud. 3" thick mineral fiber insulating
batts friction fitted between the studs.
61/2d
15-1.10Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, with 1/2" Glass Fiber
Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex
anchors at 24" on center, with 5" leg welded to studs with two 1/2"-long
flare-bevel welds, and 4" foot attached to the GFRC skin with 5/8" thick GFRC
bonding pads that extend 21/2" beyond the flex anchor foot on both sides. Interior
surface to have two layers of 1/2" Type X gypsum wallboard.e The first layer of
wallboard to be attached with 1"-long Type S buglehead screws spaced 24" on
center and the second layer is attached with 15/8"-long Type S screws spaced at
12" on center. Cavity is to be filled with 5" of 4 pcf (nominal) mineral fiber batts.
GFRC has 11/2" returns packed with mineral fiber and caulked on the exterior.
61/2
15-1.11Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, respectively, with
1/2" Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is
attached with flex anchors at 24" on center, with 5" leg welded to studs with two
1/2"-long flare-bevel welds, and 4" foot attached to the GFRC skin with 5/8"-thick
GFRC bonding pads that extend 21/2" beyond the flex anchor foot on both sides.
Interior surface to have one layer of 5/8" Type X gypsum wallboarde, attached
with 11/4"-long Type S buglehead screws spaced 12" on center. Cavity is to be
filled with 5" of 4 pcf (nominal) mineral fiber batts. GFRC has 11/2" returns
packed with mineral fiber and caulked on the exterior.
61/8
15-1.12q2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and
exterior sides covered with 5/8" Type X gypsum wallboard, 4' wide, applied
horizontally or vertically with vertical joints over studs, and fastened with 21/4"
Type S drywall screws, spaced 12" on center. Cavity to be filled with 51/2"
mineral wool insulation.
63/4
15-1.13q2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and
exterior sides covered with 5/8" Type X gypsum wallboard, 4' wide, applied
vertically with all joints over framing or blocking and fastened with 21/4" Type S
drywall screws, spaced 12" on center. R-19 mineral fiber insulation installed in
stud cavity.
63/4
15-1.14q2" × 6" wood studs at 16" with double top plates, single bottom plate; interior and
exterior sides covered with 5/8" Type X gypsum wallboard, 4' wide, applied
horizontally or vertically with vertical joints over studs, and fastened with 21/4"
Type S drywall screws, spaced 7" on center.
63/4
15-1.15q2" × 4" wood studs at 16" with double top plates, single bottom plate; interior and
exterior sides covered with 5/8" Type X gypsum wallboard and sheathing,
respectively, 4' wide, applied horizontally or vertically with vertical joints over
studs, and fastened with 21/4" Type S drywall screws, spaced 12" on center.
Cavity to be filled with 31/2" mineral wool insulation.
43/4
15-1.16q2" × 6" wood studs at 24" centers with double top plates, single bottom plate;
interior and exterior side covered with two layers of 5/8" Type X gypsum
wallboard, 4' wide, applied horizontally with vertical joints over studs. Base
layer fastened with 21/4" Type S drywall screws, spaced 24" on center and face
layer fastened with Type S drywall screws, spaced 8" on center, wallboard joints
covered with paper tape and joint compound, fastener heads covered with joint
compound. Cavity to be filled with 51/2" mineral wool insulation.
73/4
15-2.1d35/8" No. 16 gage steel studs at 24" on center or 2" × 4" wood studs at 24" on
center. Metal lath attached to the exterior side of studs with minimum 1" long
No. 6 drywall screws at 6" on center and covered with minimum 3/4" thick
portland cement plaster. Thin veneer brick units of clay or shale complying with
ASTM C 1088, Grade TBS or better, installed in running bond in accordance
with Section 1405.10. Combined total thickness of the portland cement plaster,
mortar and thin veneer brick units shall be not less than 13/4". Interior side
covered with one layer of 5/8" thick Type X gypsum wallboard attached to studs
with 1" long No. 6 drywall screws at 12" on center.
6
15-2.2d35/8" No. 16 gage steel studs at 24" on center or 2" × 4" wood studs at 24" on
center. Metal lath attached to the exterior side of studs with minimum 1" long
No. 6 drywall screws at 6" on center and covered with minimum 3/4" thick
portland cement plaster. Thin veneer brick units of clay or shale complying with
ASTM C 1088, Grade TBS or better, installed in running bond in accordance
with Section 1405.10. Combined total thickness of the portland cement plaster,
mortar and thin veneer brick units shall be not less than 2". Interior side covered
with two layers of 5/8" thick Type X gypsum wallboard. Bottom layer attached to
studs with 1" long No. 6 drywall screws at 24" on center. Top layer attached to
studs with 15/8" long No. 6 drywall screws at 12" on center.
67/8
15-2.3d35/8" No. 16 gage steel studs at 16" on center or 2" × 4" wood studs at 16" on
center. Where metal lath is used, attach to the exterior side of studs with
minimum 1" long No. 6 drywall screws at 6" on center. Brick units of clay or
shale not less than 25/8" thick complying with ASTM C 216 installed in
accordance with Section 1405.6 with a minimum 1" air space. Interior side
covered with one layer of 5/8" thick Type X gypsum wallboard attached to studs
with 1" long No. 6 drywall screws at 12" on center.
77/8
15-2.4d35/8" No. 16 gage steel studs at 16" on center or 2" × 4" wood studs at 16" on
center. Where metal lath is used, attach to the exterior side of studs with
minimum 1" long No. 6 drywall screws at 6" on center. Brick units of clay or
shale not less than 25/8" thick complying with ASTM C 216 installed in
accordance with Section 1405.6 with a minimum 1" air space. Interior side
covered with two layers of 5/8" thick Type X gypsum wallboard. Bottom layer
attached to studs with 1" long No. 6 drywall screws at 24" on center. Top layer
attached to studs with 15/8" long No. 6 drywall screws at 12" on center.
81/2
16. Exterior walls
rated for fire
resistance from
the inside only in
accordance with
16-1.1q2"× 4" wood studs at 16" centers with double top plates, single bottom plate;
interior side covered with 5/8" Type X gypsum wallboard, 4' wide, applied
horizontally unblocked, and fastened with 21/4" Type S drywall screws, spaced
12" on center, wallboard joints covered with paper tape and joint compound,
fastener heads covered with joint compound. Exterior covered with 3/8" wood
structural panels, applied vertically, horizontal joints blocked and fastened with
6d common nails (bright) — 12" on center in the field, and 6" on center panel
edges. Cavity to be filled with 31/2" mineral wool insulation. Rating established
for exposure from interior side only.
41/2
16-1.2q2" × 6" (51mm x 152 mm) wood studs at 16 " centers with double top plates, single
bottom plate; interior side covered with 5/8" Type X gypsum wallboard, 4' wide,
applied horizontally or vertically with vertical joints over studs and fastened with
21/4" Type S drywall screws, spaced 12" on center, wallboard joints covered with
paper tape and joint compound, fastener heads covered with joint compound, exterior
side covered with 7/16" wood structural panels fastened with 6d common nails (bright)
spaced 12" on center in the field and 6" on center along the panel edges. Cavity to be
filled with 51/2" mineral wool insulation. Rating established from the gypsum-covered
side only.
69/16
16-1.32" × 6" wood studs at 16" centers with double top plates, single bottom plates;
interior side covered with 5/8" Type X gypsum wallboard, 4' wide, applied
vertically with all joints over framing or blocking and fastened with 21/4" Type S
drywall screws spaced 7" on center. Joints to be covered with tape and joint
compound. Exterior covered with 3/8" wood structural panels, applied vertically
with edges over framing or blocking and fastened with 6d common nails (bright)
at 12" on center in the field and 6" on center on panel edges. R-19 mineral fiber
insulation installed in stud cavity. Rating established from the gypsum-covered
side only.
61/2
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2, 1 cubic foot = 0.0283 m3, 1 foot = 304.8 mm.
  1. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing.
  2. Thickness shown for brick and clay tile is nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and clay masonry is equivalent thickness defined in Section 721.3.1 for concrete masonry and Section 721.4.1.1 for clay masonry. Where all cells are solid grouted or filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalent thickness shall be the thickness of the block or brick using specified dimensions as defined in Chapter 21. Equivalent thickness may also include the thickness of applied plaster and lath or gypsum wallboard, where specified.
  3. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sectional area measured in the same plane.
  4. Shall be used for nonbearing purposes only.
  5. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  6. The fire-resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire-resistance rating in Item 3, and having a thickness of not less than 75/8 inches is 4 hours when cores which are not grouted are filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, sand or slag having a maximum particle size of 3/8 inch.
  7. The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete masonry shall be determined in accordance with ACI 216.1/TMS 0216. Lightweight aggregates shall have a maximum combined density of 65 pounds per cubic foot.
  8. See also Note b. The equivalent thickness shall be permitted to include the thickness of cement plaster or 1.5 times the thickness of gypsum plaster applied in accordance with the requirements of Chapter 25.
  9. Concrete walls shall be reinforced with horizontal and vertical temperature reinforcement as required by Chapter 19.
  10. Studs are welded truss wire studs with 0.18 inch (No. 7 B.W. gage) flange wire and 0.18 inch (No. 7 B.W. gage) truss wires.
  11. Nailable metal studs consist of two channel studs spot welded back to back with a crimped web forming a nailing groove.
  12. Wood structural panels shall be permitted to be installed between the fire protection and the wood studs on either the interior or exterior side of the wood frame assemblies in this table, provided the length of the fasteners used to attach the fire protection is increased by an amount at least equal to the thickness of the wood structural panel.
  13. The design stress of studs shall be reduced to 78 percent of allowable F'c with the maximum not greater than 78 percent of the calculated stress with studs having a slenderness ratio le/d of 33.
  14. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667.
  15. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed.
  16. NCMA TEK 5-8A shall be permitted for the design of fire walls.
  17. The design stress of studs shall be equal to a maximum of 100 percent of the allowable F'c calculated in accordance with Section 2306.
MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q
FLOOR OR ROOF
CONSTRUCTION
ITEM
NUMBER
CEILING CONSTRUCTIONTHICKNESS OF FLOOR
OR ROOF SLAB
(inches)
MINIMUM THICKNESS
OF CEILING
(inches)
4
hour
3
hour
2
hour
1
hour
4
hour
3
hour
2
hour
1
hour
1. Siliceous
aggregate concrete
1-1.1Slab (no ceiling required). Minimum cover
over nonprestressed reinforcement shall not be less than
3/4"b.
7.06.25.03.5
2. Carbonate
aggregate concrete
2-1.16.65.74.63.2
3. Sand-lightweight concrete3-1.15.44.63.82.7
4. Lightweight concrete4-1.15.14.43.62.5
5. Reinforced 5-1.1Slab with suspended ceiling of vermiculite gypsum
plaster over metal lath attached to 3/4" cold-rolled
channels spaced 12" on center. Ceiling located 6"
minimum below joists.
3213/4
5-2.13/8" Type X gypsum wallboardc attached to 0.018
inch (No. 25 carbon sheet steel gage) by 7/8" deep by
25/8" hat-shaped galvanized steel channels with
1"-long No. 6 screws. The channels are spaced 24"
on center, span 35" and are supported along their
length at 35" intervals by 0.033" (No. 21 galvanized
sheet gage) galvanized steel flat strap hangers
having formed edges that engage the lips of the
channel. The strap hangers are attached to the side
of the concrete joists with 5/32" by 11/4" long
power-driven fasteners. The wallboard is installed
with the long dimension perpendicular to the
channels. All end joints occur on channels and
supplementary channels are installed parallel to the
main channels, 12" each side, at end joint
occurrences. The finished ceiling is located
approximately 12" below the soffit of the floor slab.
21/25/8
6. Steel joists constructed with
a poured reinforced concrete
slab on metal lath forms or
steel form unitsd, e
6-1.1Gypsum plaster on metal lath attached to the bottom
cord with single No. 16 gage or doubled No. 18
gage wire ties spaced 6" on center. Plaster mixed 1:2
for scratch coat, 1:3 for brown coat, by weight,
gypsum-to-sand aggregate for 2-hour system. For
3-hour system plaster is neat.
21/221/43/45/8
6-2.1Vermiculite gypsum plaster on metal lath attached to
the bottom chord with single No.16 gage or doubled
0.049-inch (No. 18 B.W. gage) wire ties 6" on center.
25/8
6-3.1Cement plaster over metal lath attached to the
bottom chord of joists with single No. 16 gage or
doubled 0.049" (No. 18 B.W. gage) wire ties spaced
6" on center. Plaster mixed 1:2 for scratch coat, 1:3
for brown coat for 1-hour system and 1:1 for scratch
coat, 1:1 1/2 for brown coat for 2-hour system, by
weight, cement to sand.
25/8f
6-4.1Ceiling of 5/8" Type X wallboardc attached to 7/8"
deep by 25/8" by 0.021 inch (No. 25 carbon sheet
steel gage) hat-shaped furring channels 12" on
center with 1" long No. 6 wallboard screws at 8" on
center. Channels wire tied to bottom chord of joists
with doubled 0.049 inch (No. 18 B.W. gage) wire or
suspended below joists on wire hangers.g
21/25/8
6-5.1Wood-fibered gypsum plaster mixed 1:1 by weight
gypsum to sand aggregate applied over metal lath.
Lath tied 6" on center to 3/4" channels spaced 131/2"
on center. Channels secured to joists at each
intersection with two strands of 0.049 inch (No. 18
B.W. gage) galvanized wire.
21/23/4
7. Reinforced concrete slabs
and joists with hollow clay tile
fillers laid end to end in rows
21/2" or more apart;
reinforcement placed between
rows and concrete cast around
and over tile.
7-1.15/8" gypsum plaster on bottom of floor or roof
construction.
8h5/8
7-1.2None51/2i
8. Steel joists constructed with
a reinforced concrete slab on
top poured on a 1/2" deep steel
deck.e
8-1.1Vermiculite gypsum plaster on metal lath attached
to 3/4" cold-rolled channels with 0.049" (No. 18
B.W. gage) wire ties spaced 6" on center.
21/2j3/4
9. 3" deep cellular steel deck
with concrete slab on top. Slab
thickness measured to top.
9-1.1Suspended ceiling of vermiculite gypsum plaster
base coat and vermiculite acoustical plaster on metal
lath attached at 6" intervals to 3/4" cold-rolled
channels spaced 12" on center and secured to 11/2"
cold-rolled channels spaced 36" on center with
0.065" (No. 16 B.W. gage) wire. 11/2" channels
supported by No. 8 gage wire hangers at 36" on
center. Beams within envelope and with a 21/2"
airspace between beam soffit and lath have a 4-hour
rating.
21/211/8k
10. 11/2"-deep steel roof deck
on steel framing. Insulation
board, 30 pcf density,
composed of wood fibers with
cement binders of thickness
shown bonded to deck with
unified asphalt adhesive.
Covered with a Class A or B
roof covering.
10-1.1Ceiling of gypsum plaster on metal lath. Lath
attached to 3/4" furring channels with 0.049" (No. 18
B.W. gage) wire ties spaced 6" on center. 3/4"
channel saddle tied to 2" channels with doubled
0.065" (No. 16 B.W. gage) wire ties. 2" channels
spaced 36" on center suspended 2" below steel
framing and saddle-tied with 0.165" (No. 8 B.W.
gage) wire. Plaster mixed 1:2 by weight,
gypsum-to-sand aggregate.
17/813/4l3/4l
11. 11/2"-deep steel roof deck
on steel-framing wood fiber
insulation board, 17.5 pcf
density on top applied over a
15-lb asphalt-saturated felt.
Class A or B roof covering.
11-1.1Ceiling of gypsum plaster on metal lath. Lath
attached to 3/4" furring channels with 0.049" (No. 18
B.W. gage) wire ties spaced 6" on center. 3/4"
channels saddle tied to 2" channels with doubled
0.065" (No. 16 B.W. gage) wire ties. 2" channels
spaced 36" on center suspended 2" below steel
framing and saddle tied with 0.165" (No. 8 B.W.
gage) wire. Plaster mixed 1:2 for scratch coat and
1:3 for brown coat, by weight, gypsum-to-sand
aggregate for 1-hour system. For 2-hour system,
plaster mix is 1:2 by weight, gypsum-to-sand
aggregate.
11/217/8g3/4l
12. 11/2" deep steel roof deck
on steel-framing insulation of
rigid board consisting of
expanded perlite and fibers
impregnated with integral
asphalt waterproofing; density
9 to 12 pcf secured to metal
roof deck by 1/2" wide ribbons
of waterproof, cold-process
liquid adhesive spaced 6"
apart. Steel joist or light steel
construction with metal roof
deck, insulation, and Class A
12-1.1Gypsum-vermiculite plaster on metal lath wire tied
at 6" intervals to 3/4" furring channels spaced 12" on
center and wire tied to 2" runner channels spaced
32" on center. Runners wire tied to bottom chord of
steel joists.
17/8
13. Double wood floor over
wood joists spaced 16" on
center.m,n
13-1.1Gypsum plaster over 3/8" Type X gypsum lath. Lath
initially applied with not less than four 11/8" by No.
13 gage by 19/64" head plasterboard blued nails per
bearing. Continuous stripping over lath along all
joist lines. Stripping consists of 3" wide strips of
metal lath attached by 11/2" by No. 11 gage by 1/2"
head roofing nails spaced 6" on center. Alternate
stripping consists of 3" wide 0.049" diameter wire
stripping weighing 1 pound per square yard and
attached by No.16 gage by 11/2" by 3/4" crown width
staples, spaced 4" on center. Where alternate
stripping is used, the lath nailing may consist of two
nails at each end and one nail at each intermediate
bearing. Plaster mixed 1:2 by weight,
gypsum-to-sand aggregate.
7/8
13-1.2Cement or gypsum plaster on metal lath. Lath
fastened with 11/2" by No. 11 gage by 7/16"head
barbed shank roofing nails spaced 5" on center.
Plaster mixed 1:2 for scratch coat and 1:3 for brown
coat, by weight, cement to sand aggregate.
5/8
13-1.3Perlite or vermiculite gypsum plaster on metal lath
secured to joists with 11/2" by No. 11 gage by 7/16"
head barbed shank roofing nails spaced 5" on center.
5/8
13-1.41/2" Type X gypsum wallboardc nailed to joists with
5d coolero or wallboardo nails at 6" on center. End
joints of wallboard centered on joists.
1/2
14. Plywood stressed skin
panels consisting of 5/8"-thick
interior C-D (exterior glue)
top stressed skin on 2" × 6"
nominal (minimum) stringers.
Adjacent panel edges joined
with 8d common wire nails s
paced 6" on center. Stringers
spaced 12" maximum on
center.
14-1.11/2"-thick wood fiberboard weighing 15 to 18
pounds per cubic foot installed with long dimension
parallel to stringers or 3/8" C-D (exterior glue)
plywood glued and/or nailed to stringers. Nailing to
be with 5d coolero or wallboardo nails at 12" on
center. Second layer of 1/2" Type X gypsum
wallboardc applied with long dimension
perpendicular to joists and attached with 8d coolero
or wallboardo nails at 6" on center at end joints and
8" on center elsewhere. Wallboard joints staggered
with respect to fiberboard joints.
1
15. Vermiculite concrete slab
proportioned 1:4 (portland
cement to vermiculite
aggregate) on a 11/2"-deep
steel deck supported on
individually protected steel
framing. Maximum span of
deck 6'-10" where deck is less
than 0.019 inch (No. 26
carbon steel sheet gage) or
greater. Slab reinforced with
4" × 8" 0.109/0.083" (No. 12/14
B.W. gage) welded wire mesh.
15-1.1None3j
16. Perlite concrete slab
proportioned 1:6 (portland
cement to perlite aggregate)
on a 11/4"-deep steel deck
supported on individually
protected steel framing. Slab
reinforced with 4" × 8"
0.109/0.083" (No. 12/14 B.W.
gage) welded wire mesh.
16-1.1None31/2j
17. Perlite concrete slab
proportioned 1:6 (portland
cement to perlite aggregate)
on a 9/16"-deep steel deck
supported by steel joists 4' on
center. Class A or B roof
covering on top.
17-1.1Perlite gypsum plaster on metal lath wire tied to 3/4"
furring channels attached with 0.065" (No. 16 B.W.
gage) wire ties to lower chord of joists.
2p2p7/83/4
18. Perlite concrete slab
proportioned 1:6 (portland
cement to perlite aggregate)
on 11/4"-deep steel deck
supported on individually
protected steel framing.
Maximum span of deck 6'-10"
where deck is less than 0.019"
(No. 26 carbon sheet steel
gage) and 8'-0" where deck is
0.019" (No. 26 carbon sheet
steel gage) or greater. Slab
reinforced with 0.042" (No. 19
B.W. gage) hexagonal wire
mesh. Class A or B roof
covering on top.
18-1.1None21/4p21/4p
19. Floor and beam
construction consisting of
3"-deep cellular steel floor
unit mounted on steel
members with 1:4
(proportion of portland
cement to perlite
aggregate) perlite-concrete
floor slab on top.
19-1.1Suspended envelope ceiling of perlite
gypsum plaster on metal lath attached to
3/4" cold-rolled channels, secured to 11/2"
cold-rolled channels spaced 42" on center
supported by 0.203 inch (No. 6 B.W. gage)
wire 36" on center. Beams in envelope with
3" minimum airspace between beam soffit
and lath have a 4-hour rating.
2p1l
20. Perlite concrete
proportioned 1:6 (portland
cement to perlite
aggregate) poured to 1/8"
thickness above top of
corrugations of 15/16"-deep
galvanized steel deck
maximum span 8'-0" for
0.024" (No. 24 galvanized
sheet gage) or 6' 0" for
0.019" (No. 26 galvanized
sheet gage) with deck
supported by individually
protected steel framing.
Approved polystyrene board having a flame
spread not exceeding 75
(1" to 4" thickness) with
vent holes that
approximate 3 percent of
the board surface area
placed on top of perlite
slurry. A 2' by 4' insulation
board contains six 23/4"
diameter holes. Board
covered with 21/4"slab. Slab reinforced with mesh
consisting of 0.042" (No. 19
B.W. gage) galvanized steel
wire twisted together to form
2" hexagons with straight
0.065" (No. 16 B.W. gage)
galvanized steel wire woven
into mesh and spaced 3".
Alternate slab reinforcement
shall be permitted to consist of
4" × 8", 0.109/0.238" (No. 12/4
B.W. gage), or 2" × 2",
0.083/0.083" (No. 14/14 B.W.
gage) welded wire fabric. Class
A or B roof covering on top.
20-1.1NoneVaries
21. Wood joists, wood I-joists,
floor trusses and flat or pitched
roof trusses spaced a maximum
24" o.c. with 1/2" wood
structural panels with exterior
glue applied at right angles to
top of joist or top chord of
trusses with 8d nails. The wood
structural panel thickness shall
not be less than nominal 1/2"
nor less than required by
21-1.1Base layer 5/8" Type X gypsum wallboard applied
at right angles to joist or truss 24" o.c. with 11/4"
Type S or Type W drywall screws 24" o.c. Face
layer 5/8" Type X gypsum wallboard or veneer
base applied at right angles to joist or truss
through base layer with 17/8" Type S or Type W
drywall screws 12" o.c. at joints and intermediate
joist or truss. Face layer Type G drywall screws
placed 2" back on either side of face layer end
joints, 12" o.c.
Varies11/4
22. Steel joists, floor trusses
and flat or pitched roof trusses
spaced a maximum 24" o.c.
with 1/2" wood structural panels
with exterior glue applied at
right angles to top of joist or
top chord of trusses with No. 8
screws. The wood structural
panel thickness shall not be less
than nominal 1/2" nor less than
required by Chapter 23.
22-1.1Base layer 5/8" Type X gypsum board applied at
right angles to steel framing 24" on center with 1"
Type S drywall screws spaced 24" on center. Face
layer 5/8" Type X gypsum board applied at right
angles to steel framing attached through base
layer with 15/8" Type S drywall screws 12" on
center at end joints and intermediate joints and
11/2" Type G drywall screws 12 inches on center
placed 2" back on either side of face layer end
joints. Joints of the face layer are offset 24" from
the joints of the base layer.
Varies11/4
23. Wood I-joist (minimum
joist depth 91/4" with a
minimum flange depth of 15/16"
and a minimum flange cross-
sectional area of 2.3 square
inches) at 24" o.c. spacing with
1 inch by 4 inch (nominal)
wood furring strip spacer
applied parallel to and covering
the bottom of the bottom flange
of each member, tacked in
place. 2" mineral wool
insulation, 3.5 pcf (nominal)
installed adjacent to the bottom
flange of the I-joist and
supported by the 1" × 4"
furring strip spacer.
23-1.11/2" deep single leg resilient channel 16" on center
(channels doubled at wallboard end joints), placed
perpendicular to the furring strip and joist and
attached to each joist by 17/8" Type S drywall
screws. 5/8" Type C gypsum wallboard applied
perpendicular to the channel with end joints
staggered at least 4' and fastened with 11/8" Type
S drywall screws spaced 7" on center. Wallboard
joints to be taped and covered with joint
compound.
Varies5/8
24. Wood I-joist (minimum
I-joist depth 91/4" with a
minimum flange depth of 11/2"
and a minimum flange
cross-sectional area of 5.25
square inches; minimum web
thickness of 3/8") @ 24" o.c.,
11/2" mineral wool insulation
(2.5 pcf—nominal) resting on
hat-shaped furring channels.
24-1.1Minimum 0.026" thick hat-shaped channel 16"
o.c. (channels doubled at wallboard end joints),
placed perpendicular to the joist and attached to
each joist by 15/8" Type S drywall screws. 5/8"
Type C gypsum wallboard applied
perpendicular to the channel with end joints
staggered and fastened with 11/8" Type S
drywall screws spaced 12" o.c. in the field and
8" o.c. at the wallboard ends. Wallboard joints
to be taped and covered with joint compound.
Varies5/8
25. Wood I-joist (minimum
I-joist depth 91/4" with a
minimum flange depth of 11/2"
and a minimum flange
cross-sectional area of 5.25
square inches; minimum web
thickness of 7/16") @ 24" o.c.,
11/2" mineral wool insulation
(2.5 pcf—nominal) resting on
resilient channels.
25-1.1Minimum 0.019" thick resilient channel 16" o.c.
(channels doubled at wallboard end joints),
placed perpendicular to the joist and attached to
each joist by 15/8" Type S drywall screws. 5/8"
Type C gypsum wallboard applied
perpendicular to the channel with end joints
staggered and fastened with 1" Type S drywall
screws spaced 12" o.c. in the field and 8" o.c. at
the wallboard ends. Wallboard joints to be taped
and covered with joint compound.
Varies5/8
26. Wood I-joist (minimum
I-joist depth 91/4" with a
minimum flange thickness of
11/2" and a minimum flange
cross-sectional area of 2.25
square inches; minimum web
thickness of 3/8") @ 24" o.c.
26-1.1Two layers of 1/2" Type X gypsum wallboard
applied with the long dimension perpendicular
to the I-joists with end joints staggered. The
base layer is fastened with 15/8" Type S drywall
screws spaced 12" o.c. and the face layer is
fastened with 2" Type S drywall screws spaced
12" o.c. in the field and 8" o.c. on the edges.
Face layer end joints shall not occur on the same
I-joist as base layer end joints and edge joints
shall be offset 24" from base layer joints. Face
layer to also be attached to base layer with 11/2"
Type G drywall screws spaced 8" o.c. placed 6"
from face layer end joints. Face layer wallboard
joints to be taped and covered with joint
compound.
Varies1
27. Wood I-joist (minimum
I-joist depth 91/2" with a
minimum flange depth of 15/16"
and a minimum flange
cross-sectional area of 1.95
square inches; minimum web
thickness of 3/8") @ 24" o.c.
27-1.1Minimum 0.019" thick resilient channel 16" o.c.
(channels doubled at wallboard end joints),
placed perpendicular to the joist and attached to
each joist by 15/8" Type S drywall screws. Two
layers of 1/2" Type X gypsum wallboard applied
with the long dimension perpendicular to the
I-joists with end joints staggered. The base layer
is fastened with 11/4" Type S drywall screws
spaced 12" o.c. and the face layer is fastened
with 15/8" Type S drywall screws spaced 12"
o.c. Face layer end joints shall not occur on the
same I-joist as base layer end joints and edge
joints shall be offset 24" from base layer joints.
Face layer to also be attached to base layer with
11/2" Type G drywall screws spaced 8" o.c.
placed 6" from face layer end joints. Face layer
wallboard joints to be taped and covered with
joint compound.
Varies1
28. Wood I-joist (minimum
I-joist depth 91/4" with a
minimum flange depth of
11/2" and a minimum flange
cross-sectional area of 2.25
square inches; minimum web
thickness of 3/8") @ 24" o.c.
Unfaced fiberglass insulation
is installed between the
I-joists supported on the
upper surface of the flange by
stay wires spaced 12" o.c.
28-1.1Base layer of 5/8" Type C gypsum wallboard
attached directly to I-joists with 15/8" Type S
drywall screws spaced 12" o.c. with ends
staggered. Minimum 0.0179" thick hat-shaped
7/8-inch furring channel 16" o.c. (channels
doubled at wallboard end joints), placed
perpendicular to the joist and attached to each
joist by 15/8" Type S drywall screws after the
base layer of gypsum wallboard has been
applied. The middle and face layers of 5/8" Type
C gypsum wallboard applied perpendicular to
the channel with end joints staggered. The
middle layer is fastened with 1" Type S drywall
screws spaced 12" o.c. The face layer is applied
parallel to the middle layer but with the edge
joints offset 24" from those of the middle layer
and fastened with 15/8" Type S drywall screws
8" o.c. The joints shall be taped and covered
with joint compound.
Varies23/4
29. Channel-shaped 18 gage
steel joists (minimum depth
8") spaced a maximum 24"
o.c. supporting
tongue-and-groove wood
structural panels (nominal
minimum 3/4" thick) applied
perpendicular to framing
members. Structural panels
attached with 1-5/8" Type
S-12 screws spaced 12" o.c.
29-1.1Base layer 5/8" Type X gypsum board applied
perpendicular to bottom of framing members
with 11/8" Type S-12 screws spaced 12" o.c.
Second layer 5/8" Type X gypsum board
attached perpendicular to framing members with
15/8" Type S-12 screws spaced 12" o.c. Second
layer joints offset 24" from base layer. Third
layer 5/8" Type X gypsum board attached
perpendicular to framing members with 23/8"
Type S-12 screws spaced 12" o.c. Third layer
joints offset 12" from second layer joints.
Hat-shaped 7/8-inch rigid furring channels
applied at right angles to framing members over
third layer with two 23/8" Type S-12 screws at
each framing member. Face layer 5/8" Type X
gypsum board applied at right angles to furring
channels with 11/8" Type S screws spaced 12"
o.c.
Varies33/8
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 cubic foot = 0.0283m3, 1 pound per square inch = 6.895 kPa, 1 pound per linear foot = 1.4882 kg/m.
  1. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing.
  2. When the slab is in an unrestrained condition, minimum reinforcement cover shall not be less than 15/8 inches for 4-hour (siliceous aggregate only); 11/4 inches for 4- and 3-hour; 1 inch for 2-hour (siliceous aggregate only); and 3/4 inch for all other restrained and unrestrained conditions.
  3. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster.
  4. Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units.
    1. The maximum allowable stress level for H-Series joists shall not exceed 22,000 psi.
    2. The allowable stress for K-Series joists shall not exceed 26,000 psi, the nominal depth of such joist shall not be less than 10 inches and the nominal joist weight shall not be less than 5 pounds per linear foot.
  5. Cement plaster with 15 pounds of hydrated lime and 3 pounds of approved additives or admixtures per bag of cement.
  6. Gypsum wallboard ceilings attached to steel framing shall be permitted to be suspended with 11/2-inch cold-formed carrying channels spaced 48 inches on center, which are suspended with No. 8 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire (double strand) and spaced as required for direct attachment to the framing. This alternative is also applicable to those steel framing assemblies recognized under Note q.
  7. Six-inch hollow clay tile with 2-inch concrete slab above.
  8. Four-inch hollow clay tile with 11/2-inch concrete slab above.
  9. Thickness measured to bottom of steel form units.
  10. Five-eighths inch of vermiculite gypsum plaster plus 1/2 inch of approved vermiculite acoustical plastic.
  11. Furring channels spaced 12 inches on center.
  12. Double wood floor shall be permitted to be either of the following:
    1. Subfloor of 1-inch nominal boarding, a layer of asbestos paper weighing not less than 14 pounds per 100 square feet and a layer of 1-inch nominal tongue-and-groove finished flooring; or
    2. Subfloor of 1-inch nominal tongue-and-groove boarding or 15/32-inch wood structural panels with exterior glue and a layer of 1-inch nominal tongue-and-groove finished flooring or 19/32-inch wood structural panel finish flooring or a layer of Type I Grade M-1 particleboard not less than 5/8-inch thick.
  13. The ceiling shall be permitted to be omitted over unusable space, and flooring shall be permitted to be omitted where unusable space occurs above.
  14. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667.
  15. Thickness measured on top of steel deck unit.
  16. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed.
Upcodes Diagrams
The thickness of fire-resistant materials required for protection of structural members shall be not less than set forth in Table 720.1(1), except as modified in this section. The figures shown shall be the net thickness of the protecting materials and shall not include any hollow space in back of the protection.
Where required, metal ties shall be embedded in bed joints of unit masonry for protection of steel columns. Such ties shall be as set forth in Table 720.1(1) or be equivalent thereto.
Cast-in-place concrete protection for steel columns shall be reinforced at the edges of such members with wire ties of not less than 0.18 inch (4.6 mm) in diameter wound spirally around the columns on a pitch of not more than 8 inches (203 mm) or by equivalent reinforcement.
The finish coat is not required for plaster protective coatings where they comply with the design mix and thickness requirements of Tables 720.1(1), 720.1(2) and 720.1(3).
For members having a single tendon or more than one tendon installed with equal concrete cover measured from the nearest surface, the cover shall not be less than that set forth in Table 720.1(1). For members having multiple tendons installed with variable concrete cover, the average tendon cover shall not be less than that set forth in Table 720.1(1), provided:
  1. The clearance from each tendon to the nearest exposed surface is used to determine the average cover.
  2. In no case can the clear cover for individual tendons be less than one-half of that set forth in Table 720.1(1). A minimum cover of 3/4 inch (19.1 mm) for slabs and 1 inch (25 mm) for beams is required for any aggregate concrete.
  3. For the purpose of establishing a fire-resistance rating, tendons having a clear covering less than that set forth in Table 720.1(1) shall not contribute more than 50 percent of the required ultimate moment capacity for members less than 350 square inches (0.226 m2) in cross-sectional area and 65 percent for larger members. For structural design purposes, however, tendons having a reduced cover are assumed to be fully effective.
The provisions of this section contain procedures by which the fire resistance of specific materials or combinations of materials is established by calculations. These procedures apply only to the information contained in this section and shall not be otherwise used. The calculated fire resistance of concrete, concrete masonry and clay masonry assemblies shall be permitted in accordance with ACI 216.1/TMS 0216. The calculated fire resistance of steel assemblies shall be permitted in accordance with Chapter 5 of ASCE 29. The calculated fire resistance of exposed wood members and wood decking shall be permitted in accordance with Chapter 16 of ANSI/AF&PA; National Design Specification for Wood Construction (NDS).
The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.
CERAMIC FIBER BLANKET. A mineral wool insulation material made of alumina-silica fibers and weighing 4 to 10 pounds per cubic foot (pcf) (64 to 160 kg/m3).
CONCRETE, CARBONATE AGGREGATE. Concrete made with aggregates consisting mainly of calcium or magnesium carbonate, such as limestone or dolomite, and containing 40 percent or less quartz, chert or flint.
CONCRETE, CELLULAR. A lightweight insulating concrete made by mixing a preformed foam with portland cement slurry and having a dry unit weight of approximately 30 pcf (480 kg/m3).
CONCRETE, LIGHTWEIGHT AGGREGATE. Concrete made with aggregates of expanded clay, shale, slag or slate or sintered fly ash or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fire-resistance properties and weighing 85 to 115 pcf (1360 to 1840 kg/m3).
CONCRETE, PERLITE. A lightweight insulating concrete having a dry unit weight of approximately 30 pcf (480 kg/m3) made with perlite concrete aggregate. Perlite aggregate is produced from a volcanic rock which, when heated, expands to form a glass-like material of cellular structure.
CONCRETE, SAND-LIGHTWEIGHT. Concrete made with a combination of expanded clay, shale, slag, slate, sintered fly ash, or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fire-resistance properties and natural sand. Its unit weight is generally between 105 and 120 pcf (1680 and 1920 kg/m3).
CONCRETE, SILICEOUS AGGREGATE. Concrete made with normal-weight aggregates consisting mainly of silica or compounds other than calcium or magnesium carbonate, which contains more than 40-percent quartz, chert or flint.
CONCRETE, VERMICULITE. A lightweight insulating concrete made with vermiculite concrete aggregate which is laminated micaceous material produced by expanding the ore at high temperatures. When added to a portland cement slurry the resulting concrete has a dry unit weight of approximately 30 pcf (480 kg/m3).
GLASS FIBERBOARD. Fibrous glass roof insulation consisting of inorganic glass fibers formed into rigid boards using a binder. The board has a top surface faced with asphalt and kraft reinforced with glass fiber.
MINERAL BOARD. A rigid felted thermal insulation board consisting of either felted mineral fiber or cellular beads of expanded aggregate formed into flat rectangular units.
The provisions of this section contain procedures by which the fire-resistance ratings of concrete assemblies are established by calculations.
Upcodes Diagrams
Cast-in-place and precast concrete walls shall comply with Section 721.2.1.1. Multiwythe concrete walls shall comply with Section 721.2.1.2. Joints between precast panels shall comply with Section 721.2.1.3. Concrete walls with gypsum wallboard or plaster finish shall comply with Section 721.2.1.4.
Upcodes Diagrams
The minimum equivalent thicknesses of cast-in-place or precast concrete walls for fire-resistance ratings of 1 hour to 4 hours are shown in Table 721.2.1.1. For solid walls with flat vertical surfaces, the equivalent thickness is the same as the actual thickness. The values in Table 721.2.1.1 apply to plain, reinforced or prestressed concrete walls.
MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE WALLS, LOAD-BEARING OR NONLOAD-BEARING
CONCRETE
TYPE
MINIMUM SLAB THICKNESS (inches)
FOR FIRE-RESISTANCE RATING OF
1-hour11/2-hour2-hour3-hour4-hour
Siliceous3.54.35.06.27.0
Carbonate3.24.04.65.76.6
Sand-lightweight2.73.33.84.65.4
Lightweight2.53.13.64.45.1
For SI: 1 inch = 25.4 mm.
For hollow-core precast concrete wall panels in which the cores are of constant cross section throughout the length, calculation of the equivalent thickness by dividing the net cross-sectional area (the gross cross section minus the area of the cores) of the panel by its width shall be permitted.
Where all of the core spaces of hollow-core wall panels are filled with loose-fill material, such as expanded shale, clay, or slag, or vermiculite or perlite, the fire-resistance rating of the wall is the same as that of a solid wall of the same concrete type and of the same overall thickness.
The thickness of panels with tapered cross sections shall be that determined at a distance 2t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.
The equivalent thickness of panels with ribbed or undulating surfaces shall be determined by one of the following expressions:
For s ≥ 4t, the thickness to be used shall be t
For s ≤ 2t, the thickness to be used shall be te
For 4t > s > 2t, the thickness to be used shall be
(Equation 7-3)
where:
s=Spacing of ribs or undulations.
t=Minimum thickness.
te=Equivalent thickness of the panel calculated as the net cross-sectional area of the panel divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t.
For walls that consist of two wythes of different types of concrete, the fire-resistance ratings shall be permitted to be determined from Figure 721.2.1.2.
VALUES OF Rn0.59 FOR USE IN EQUATION 7-4
TYPE OF MATERIALTHICKNESS OF MATERIAL (inches)
11/2221/2331/2441/2551/2661/27
Siliceous aggregate concrete5.36.58.19.511.313.014.916.918.820.722.825.1
Carbonate aggregate concrete5.57.18.910.412.014.016.218.120.321.924.727.2c
Sand-lightweight concrete6.58.210.512.815.518.120.723.326.0cNote cNote cNote c
Lightweight concrete6.68.811.213.716.519.121.924.727.8cNote cNote cNote c
Insulating concretea9.313.316.618.323.126.5cNote cNote cNote cNote cNote cNote c
Airspaceb
For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.02 kg/m3.
  1. Dry unit weight of 35 pcf or less and consisting of cellular, perlite or vermiculite concrete.
  2. The Rn0.59 value for one 1/2" to 31/2" airspace is 3.3. The Rn0.59 value for two 1/2" to 3 1/2" airspaces is 6.7.
  3. The fire-resistance rating for this thickness exceeds 4 hours.
R a, MINUTESR 0.59
6011.20
12016.85
18021.41
24025.37
  1. Based on Equation 7-4.
For SI: 1 inch = 25.4 mm.
FIGURE 721.2.1.2
The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula:
(Equation 7-4)
where:
R=The fire endurance of the assembly, minutes.
R1, R2, and Rn=The fire endurances of the individual wythes, minutes.Values of Rn0.59 for use in Equation 7-4 are given in Table 721.2.1.2(1). Calculated fire-resistance ratings are shown in Table 721.2.1.2(2).
The fire-resistance ratings of precast concrete wall panels consisting of a layer of foam plastic insulation sandwiched between two wythes of concrete shall be permitted to be determined by use of Equation 7-4. Foam plastic insulation with a total thickness of less than 1 inch (25 mm) shall be disregarded. The Rn value for thickness of foam plastic insulation of 1 inch (25 mm) or greater, for use in the calculation, is 5 minutes; therefore Rn0.59 = 2.5.
Joints between precast concrete wall panels which are not insulated as required by this section shall be considered as openings in walls. Uninsulated joints shall be included in determining the percentage of openings permitted by Table 705.8. Where openings are not permitted or are required by this code to be protected, the provisions of this section shall be used to determine the amount of joint insulation required. Insulated joints shall not be considered openings for purposes of determining compliance with the allowable percentage of openings in Table 705.8.
Figure 721.2.1.3.1 shows thicknesses of ceramic fiber blankets to be used to insulate joints between precast concrete wall panels for various panel thicknesses and for joint widths of 3/8 inch (9.5 mm) and 1 inch (25 mm) for fire-resistance ratings of 1 hour to 4 hours. For joint widths between 3/8 inch (9.5 mm) and 1 inch (25 mm), the thickness of ceramic fiber blanket is allowed to be determined by direct interpolation. Other tested and labeled materials are acceptable in place of ceramic fiber blankets.
For SI: 1 inch = 25.4 mm.
FIGURE 721.2.1.3.1
CERAMIC FIBER JOINT PROTECTION
The fire-resistance rating of cast-in-place or precast concrete walls with finishes of gypsum wallboard or plaster applied to one or both sides shall be permitted to be calculated in accordance with the provisions of this section.
MULTIPLYING FACTOR FOR FINISHES ON NONFIRE-EXPOSED SIDE OF WALL
TYPE OF FINISH APPLIED TO CONCRETE OR
CONCRETE MASONRY WALL
TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY
Concrete: siliceous
or carbonate
Concrete Masonry:
siliceous or carbonate;
solid clay brick
Concrete: sand-lightweight
Concrete Masonry: clay tile;
hollow clay brick; concrete
masonry units of expanded
shale and <20% sand
Concrete: lightweight
Concrete Masonry:
concrete masonry units
of expanded shale,
expanded clay,
expanded slag, or
pumice < 20% sand
Concrete Masonry:
concrete masonry units
of expanded slag,
expanded clay, or pumice
Portland cement-sand plaster1.000.75a0.75a0.50a
Gypsum-sand plaster1.251.001.001.00
Gypsum-vermiculite or perlite plaster1.751.501.251.25
Gypsum wallboard3.002.252.252.25
For SI: 1 inch = 25.4 mm.
  1. For portland cement-sand plaster 5/8 inch or less in thickness and applied directly to the concrete or concrete masonry on the nonfire-exposed side of the wall, the multiplying factor shall be 1.00.
TIME ASSIGNED TO FINISH MATERIALS ON FIRE-EXPOSED SIDE OF WALL
FINISH DESCRIPTIONTIME (minute)
Gypsum wallboard
3/8 inch10
1/2 inch15
5/8 inch20
2 layers of 3/8 inch25
1 layer 3/8 inch, 1 layer 1/2 inch35
2 layers 1/2 inch40
Type X gypsum wallboard
1/2 inch25
5/8 inch40
Portland cement-sand plaster applied directly to concrete masonrySee Note a
Portland cement-sand plaster on metal lath
3/4 inch20
7/8 inch25
1 inch30
Gypsum sand plaster on 3/8-inch gypsum lath
1/2 inch35
5/8 inch40
3/4 inch50
Gypsum sand plaster on metal lath
3/4 inch50
7/8 inch60
1 inch80
For SI: 1 inch = 25.4 mm.
  1. The actual thickness of portland cement-sand plaster, provided it is 5/8 inch or less in thickness, shall be permitted to be included in determining the equivalent thickness of the masonry for use in Table 721.3.2.
Upcodes Diagrams
Where the finish of gypsum wallboard or plaster is applied to the side of the wall not exposed to fire, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The thickness of the finish shall first be corrected by multiplying the actual thickness of the finish by the applicable factor determined from Table 721.2.1.4(1) based on the type of aggregate in the concrete. The corrected thickness of finish shall then be added to the actual or equivalent thickness of concrete and fire-resistance rating of the concrete and finish determined from Table 721.2.1.1, Figure 721.2.1.2 or Table 721.2.1.2(1).
Where gypsum wallboard or plaster is applied to the fire-exposed side of the wall, the contribution of the finish to the total fireresistance rating shall be determined as follows: The time assigned to the finish as established by Table 721.2.1.4(2) shall be added to the fire-resistance rating determined from Table 721.2.1.1 or Figure 721.2.1.2, or Table 721.2.1.2(1) for the concrete alone, or to the rating determined in Section 721.2.1.4.1 for the concrete and finish on the nonfire-exposed side.
For a wall having no finish on one side or different types or thicknesses of finish on each side, the calculation procedures of Sections 721.2.1.4.1 and 721.2.1.4.2 shall be performed twice, assuming either side of the wall to be the fire-exposed side. The fire-resistance rating of the wall shall not exceed the lower of the two values.
Exception: For an exterior wall with a fire separation distance greater than 5 feet (1524 mm) the fire shall be assumed to occur on the interior side only.
Where finishes applied to one or both sides of a concrete wall contribute to the fire-resistance rating, the concrete alone shall provide not less than one-half of the total required fire-resistance rating. Additionally, the contribution to the fire resistance of the finish on the nonfire-exposed side of a load-bearing wall shall not exceed one-half the contribution of the concrete alone.
Finishes on concrete walls that are assumed to contribute to the total fire-resistance rating of the wall shall comply with the installation requirements of Section 721.3.2.5.
Reinforced and prestressed floors and roofs shall comply with Section 721.2.2.1. Multicourse floors and roofs shall comply with Sections 721.2.2.2 and 721.2.2.3, respectively.
Upcodes Diagrams
The minimum thicknesses of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 721.2.2.1.
MINIMUM SLAB THICKNESS (inches)
CONCRETE TYPEFIRE-RESISTANCE RATING (hour)
111/2234
Siliceous3.54.35.06.27.0
Carbonate3.24.04.65.76.6
Sand-lightweight2.73.33.84.65.4
Lightweight2.53.13.64.45.1
For SI: 1 inch = 25.4 mm.
For hollow-core prestressed concrete slabs in which the cores are of constant cross section throughout the length, the equivalent thickness shall be permitted to be obtained by dividing the net cross-sectional area of the slab including grout in the joints, by its width.
The thickness of slabs with sloping soffits (see Figure 721.2.2.1.2) shall be determined at a distance 2t or 6 inches (152 mm), whichever is less, from the point of minimum thickness, where t is the minimum thickness.
For SI: 1 inch = 25.4 mm.
FIGURE 721.2.2.1.2
DETERMINATION OF SLAB THICKNESS FOR SLOPING SOFFITS
The thickness of slabs with ribbed or undulating soffits (see Figure 721.2.2.1.3) shall be determined by one of the following expressions, whichever is applicable:
For s > 4t, the thickness to be used shall be t
For s ≤ 2t, the thickness to be used shall be te
For 4t > s > 2t, the thickness to be used shall be
(Equation 7-5)
where:
s=Spacing of ribs or undulations.
t=Minimum thickness.
te=Equivalent thickness of the slab calculated as the net area