Heads up:
There are no amended sections in this chapter.
Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter.
Words used in the present tense include the future; words stated in the masculine gender include the feminine and neuter; the singular number includes the plural and the plural, the singular.
Where terms are not defined in this code and are defined in the International Fuel Gas Code, fire code, mechanical code or plumbing code, such terms shall have the meanings ascribed to them as in those codes.
Where terms are not defined through the methods authorized by this section, such terms shall have ordinarily accepted meanings such as the context implies.
24-HOUR CARE. The actual time that a person is an occupant within a facility for the purpose of receiving care. It shall not include a facility that is open for 24 hours and is capable of providing care to someone visiting the facility during any segment of the 24 hours.
AAC MASONRY. See Section 2102.1.
ABOVE-GROUND STORAGE TANK. A vessel, intended for fixed installation above grade, at grade, or below grade without backfill, used for the purpose of bulk storage, dispensing, handling or processing of hazardous, flammable or combustible liquids or gases and not connected to and utilized for the operation of building service equipment.
ACCESSIBLE. See Section 1102.1.
ACCREDITATION BODY. See Section 2302.1.
ACTIVE SHOOTER DRILL. An exercise performed by staff and occupants to evaluate their efficiency and effectiveness in executing an adopted school safety plan to respond to an active shooter event by sheltering and securing occupants in place within a building when normal evacuation would put occupants at risk. See Section 1008.1.9.11.
ADDITION. An extension or increase in floor area or height of a building or structure.
ADMINISTRATIVE AUTHORITY OF A SCHOOL BUILDING. The superintendent, principal, chief administrative officer, or other person having supervisory authority of a school building. See Section 1008.1.9.11.
AEROSOL. See Section 307.2.
AGGREGATE. See Section 1502.1.
AGRICULTURAL, BUILDING. A structure designed and constructed to house farm implements, hay, grain, poultry, livestock or other horticultural products (see "AGRICULTURAL PURPOSES," Section 101.2, and Section 312 of this code).
AGRICULTURAL LABOR CAMPS. Camps as defined in Section 3733.41 of the Revised Code.
AGRICULTURAL PURPOSES. Includes agriculture, farming, dairying, pasturage, apiculture, horticultural, floriculture, viticulture, ornamental horticulture, olericulture, pomiculture, animal and poultry husbandry, etc.
Double skin. See Section 3102.2.
Single skin. See Section 3102.2.
AIRCRAFT HANGER, RESIDENTIAL. See Section 412.3.1.
AISLE. See Section 1002.1.
ALARM SIGNAL. See Section 902.1.
ALLOWABLE STRESS DESIGN. See Section 1602.1.
AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation by the services provided.
AMUSEMENT RIDE. Any mechanical, aquatic, or inflatable device, or combination of those devices that carries or conveys passengers on, along, around, over, or through a fixed or restricted course or within a defined area for the purpose of providing amusement, pleasure, or excitement and includes carnival rides, bungee jumping facilities, and fair rides but does not include passenger tramways as defined in Section 4169.01 of the Revised Code or amusement rides operated solely at trade shows for a limited period of time. For regulation and definitions, see Sections 1711.50 to 1711.57 of the Revised Code. Amusement rides are not regulated by this code but are regulated by the Ohio department of agriculture. Also see Section 411, Special Amusement Buildings.
ANCHOR. See Section 2102.1.
ANCHOR BUILDING. See Section 402.2.
ANNULAR SPACE. See Section 702.1.
ANNUNCIATOR. See Section 902.1.
APPROVED. Determined to be in compliance by the authority having jurisdiction in accordance with the rules of the board.
APPROVED AGENCY. An established and accredited testing laboratory, listing agency, inspection body, or field evaluation body recognized by the board of building standards providing services consistent with their accreditation and the code section requiring the approved agency service.
APPROVED NATIONAL AND ACCREDITATION SERVICE. An established and nationally recognized service regularly engaged in evaluating the competency of agencies to conduct tests and inspections required by the rules of the board.
APPROVED SOURCE. Deleted.
AREA (for masonry). See Section 2102.1.
AREA, BUILDING. See Section 502.1.
AREA OF REFUGE. See Section 1002.1.
AREAWAY. A subsurface space adjacent to a building open at the top or protected at the top by a grating or guard.
ATRIUM. See Section 404.1.1.
AUTOMATIC. See Section 902.1.
AWNING. An architectural projection that provides weather protection, identity or decoration and is wholly supported by the building to which it is attached. An awning is comprised of a lightweight frame structure over which a covering is attached.
BACKING. See Section 1402.1.
BALED COTTON. See Section 307.2.
BALLAST. See Section 1502.1.
BARRICADE. See Section 307.2.
BASE FLOOD. See Section 1612.2.
BASEMENT (for other than flood loads). See Section 502.1.
BASEMENT (for flood loads). See Section 1612.2.
BED JOINT. See Section 2102.1.
BLEACHERS. See Section 1002.1.
BOARDING HOUSE. See Section 310.2.
BOILING POINT. See Section 307.2.
BOND BEAM. See Section 2102.1.
BRACED WALL LINE. See Section 2302.1.
BRACED WALL PANEL. See Section 2302.1.
BRICK. See Section 2102.1.
BUILDING. Any structure consisting of foundations, walls, columns, girders, beams, floors, and roof, or a combination of any number of these parts, with or without other parts or appurtenances.
BUILDING DEPARTMENT. An agency, department or division of the state or of the government of a municipal corporation, township, or county, which has been created and authorized in conformity with law for the purpose of enforcing construction code provisions of the board's rules applicable to structures specified in Section 3781.06 of the Revised Code.
BUILDING ELEMENT. See Section 702.1.
BUILDING LINE. The line established by law, beyond which a building shall not extend, except as specifically provided by law.
BUILDING OFFICIAL. The superintendent of the division of industrial compliance of the Ohio department of commerce or the person appointed by the superintendent to enforce this code in that division, or the designated authority charged with the administration and enforcement of this code, approved by the board in accordance with Section 103 of this code, in a municipal corporation, township or county having a building department, certified by the board pursuant to Section 3781.10 of the Revised Code, or the health commissioner or his authorized representative in health districts, whichever one has jurisdiction.
BUILDING SERVICE EQUIPMENT.Equipment, appliances, materials, devices, and systems integrated into a building which provide space heating, air conditioning, ventilation, fire protection, lighting, electricity, sanitation, water, heating, cooking, medical gas, medical vacuum, and clothes drying. Building service equipment begins from the connected stored source of liquid or gas fuel or electrical power supplying the equipment or the utility service point/point of delivery and extends through the point of use but does not include process equipment that may also be connected to the same source.
BUILDING SERVICES PIPING. All piping systems and their component parts that are part of a building system and that promote the safe, sanitary, and energy efficient occupancy of a building. Building services piping includes, but is not limited to, cold and hot potable water distribution for plumbing fixtures; sanitary lines from plumbing fixtures; nonflammable medical gas systems; medical oxygen systems; medical vacuum systems; fire protection piping systems and compressed air in dry systems; refrigeration, chilled water, condenser and cooling tower water, brine, and water/antifreeze systems; steam, steam condensate, and hot water piping systems; and fuel oil piping and fuel gas piping for heating, cooling, and cooking applications.
CANOPY. A permanent structure or architectural projection of rigid construction over which a covering is attached that provides weather protection, identity or decoration, and shall be structurally independent or supported by attachment to a building on one end and by not less than one stanchion on the outer end.
CAST STONE. See Section 2102.1.
CEILING LIMIT. See Section 902.1.
CELL. See Section 408.1.1.
CELL (masonry). See Section 2102.1.
CELL TIER. See Section 408.1.1.
CEMENT PLASTER. See Section 2502.1.
CHILD CARE FACILITIES. See Section 308.3.1. Also see Type A Family Day-care Home and Type B Family Day-care Home.
CHIMNEY. See Section 2102.1.
CHIMNEY TYPES. See Section 2102.1.
CLEAN AGENT. See Section 902.1.
CLEANOUT. See Section 2102.1.
CLINIC, OUTPATIENT. See Section 304.1.1.
CLOSED SYSTEM. See Section 307.2.
COLLAR JOINT. See Section 2102.1.
COLLECTOR. See Section 2302.1.
COMBUSTIBLE MATERIAL. See Section 703.4.
COMMERCIAL COOKING RECIRCULATING SYSTEM. Self-contained system consisting of the exhaust hood, the cooking equipment, the filters, and the fire suppression system. The system is designed to capture cooking vapors and residues generated from commercial cooking equipment. The system removes contaminants from the exhaust air and recirculates the air to the space from which it was withdrawn.
COMMON USE. See Section 1102.1.
COMPRESSED GAS. See Section 307.2.
CONNECTOR. See Section 2102.1.
CONSTRUCTION DOCUMENTS. Written, graphic and pictorial documents prepared or assembled for describing the design, location and physical characteristics of the elements of a project necessary for obtaining plan approval in accordance with Section 106.
CONSTRUCTION TYPES. See Section 602.
Type I. See Section 602.2.
Type II. See Section 602.2.
Type III. See Section 602.3.
Type IV. See Section 602.4.
Type V. See Section 602.5.
CONTROL AREA. See Section 307.2.
CONTROLLED LOW-STRENGTH MATERIAL. A self-compacted, cementitious material used primarily as a backfill in place of compacted fill.
CONVENTIONAL LIGHT-FRAME CONSTRUCTION. See Section 2302.1.
CORRIDOR. See Section 1002.1.
CORROSION RESISTANCE. The ability of a material to withstand deterioration of its surface or its properties when exposed to its environment.
CORROSIVE. See Section 307.2.
COURT. An open, uncovered space, unobstructed to the sky, bounded on three or more sides by exterior building walls or other enclosing devices.
COVER. See Section 2102.1.
CREDENTIALS. The badge of office, certificate, or letter issued by a governmental department to an employee for the identification of said employee in the performance of his duties.
CRIPPLE WALL. See Section 2302.1.
CRYOGENIC FLUID. See Section 307.2.
CUSTODIAL CARE. Assistance with day-to-day living tasks; such as assistance with cooking, taking medication, bathing, using toilet facilities and other tasks of daily living. Custodial care includes care for occupants that have the ability to respond to emergency situations and evacuate at a slower rate and/or who have mental and psychiatric complications.
DALLE GLASS. See Section 2402.1.
DAMPER. See Section 702.1.
DANGEROUS. See Section 3402.1.
DAY BOX. See Section 307.2.
DEAD LOADS. See Section 1602.1.
DECORATIVE MATERIALS. All materials applied over the building interior finish for decorative, acoustical or other effect (such as curtains, draperies, fabrics, streamers and surface coverings), and all other materials utilized for decorative effect (such as batting, cloth, cotton, hay, stalks, straw, vines, leaves, trees, moss and similar items), including foam plastics and materials containing foam plastics. Decorative materials do not include floor coverings, ordinary window shades, interior finish and materials 0.025 inch (0.64 mm) or less in thickness applied directly to and adhering tightly to a substrate.
DEEP FOUNDATION. See Section 1802.1.
DEFLAGRATION. See Section 307.2.
DELUGE SYSTEM. See Section 902.1.
DESIGN DISPLACEMENT. See Section 1908.1.1.
DESIGN FLOOD. See Section 1612.2.
DESIGN STRENGTH. See Section 1602.1.
DETAILED PLAIN CONCRETE STRUCTURAL WALL. See Section 1908.1.1.
DETECTOR, HEAT. See Section 902.1.
DETONATION. See Section 307.2.
DETOXIFICATION FACILITY. See Section 308.3.1.
Diaphragm, blocked. See Section 1602.1.
Diaphragm, boundary. See Section 1602.1.
Diaphragm, chord. See Section 1602.1.
Diaphragm, flexible. See Section 1602.1.
Diaphragm, rigid. See Section 1602.1.
Diaphragm, unblocked. See Section 2302.1.
DIMENSIONS. See Section 2102.1.
DISPENSING. See Section 307.2.
DOOR, BALANCED. See Section 1002.1.
DORMITORY. See Section 310.2.
DRAFTSTOP. See Section 702.1.
DRAG STRUT. See Section 2302.1.
DRILLED SHAFT. See Section 1802.1.
Socketed drilled shaft. See Section 1802.1.
DRY-CHEMICAL EXTINGUISHING AGENT. See Section 902.1.
DURATION OF LOAD. See Section 1602.1.
DWELLING. Any building that exclusively contains one, two, or three dwelling units, each of which may be occupied by a family and no more than five lodgers or boarders, intended, or designed to be built, used, rented, leased, let or hired out to be occupied, or that is occupied for living purposes, physically separated from adjacent structures, and with an independent exit from each dwelling unit.
DWELLING UNIT. A single unit providing complete, independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation. The dwelling unit may include any accessory space intended for the exclusive use of the occupants of an individual dwelling unit such as a private garage, greenhouse, etc.
EGRESS COURT. See Section 1002.1.
ELEVATOR GROUP. See Section 902.1.
EMERGENCY SITUATION. An incident requiring a response to prevent loss of life or injury at a school building involving an active shooter or similar occurrence where normal evacuation could put occupants at risk, but shall not include fire, tornado/earthquake, building collapse, boiler failure, or similar occurrence caused by natural activity or building failure. See Section 1008.1.9.11.
ENGINE-MOUNTED TANK. A fuel tank furnished by the engine manufacturer or the emergency power system supplier and mounted on the engine, the engine-frame, or under as a subbase.
ESSENTIAL FACILITIES. See Section 1602.1.
EXISTING STRUCTURE. A structure regulated by this code that was erected or one for which a plan approval has been issued. See also Section 1612.2.
EXIT. See Section 1002.1.
EXIT ACCESS. See Section 1002.1.
EXIT DISCHARGE. See Section 1002.1.
EXIT ENCLOSURE. See Section 1002.1.
EXPLOSION. See Section 307.2.
EXPLOSIVE. See Section 307.2.
High explosive. See Section 307.2.
Low explosive. See Section 307.2.
Mass detonating explosives. See Section 307.2.
Division 1.1. See Section 307.2.
Division 1.2. See Section 307.2.
Division 1.3. See Section 307.2.
Division 1.4. See Section 307.2.
Division 1.5. See Section 307.2.
Division 1.6. See Section 307.2.
EXTERIOR INSULATION AND FINISH SYSTEM (EIFS). See Section 1402.1.
EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) WITH DRAINAGE. See Section 1402.1.
EXTERIOR WALL. See Section 1402.1.
F RATING. See Section 702.1.
FABRIC PARTITION. See Section 1602.1.
FACILITY. See Section 1102.1.
FACTORED LOAD. See Section 1602.1.
FIBER CEMENT SIDING. See Section 1402.1.
FIBERBOARD. See Section 2302.1.
FIRE ALARM BOX, MANUAL. See Section 902.1.
FIRE AREA. See Section 902.1.
FIRE BARRIER. See Section 702.1.
FIRE DAMPER. See Section 702.1.
FIRE DOOR. See Section 702.1.
FIRE LANE. A road or other passageway developed to allow the passage of fire apparatus. A fire lane is not necessarily intended for vehicular traffic other than fire apparatus.
FIRE PARTITION. See Section 702.1.
FIRE PREVENTION. The preventative measures which provide for the safe conduct and operation of hazardous processes, storage of combustible and flammable materials, conducting of fire drills and the maintenance of fire protection, detection and extinguishing service equipment and good housekeeping conditions.
FIRE RESISTANCE. See Section 702.1.
FIRE WALL. See Section 702.1.
FIREBLOCKING. See Section 702.1.
FIREPLACE. See Section 2102.1.
FIREWORKS. See Section 307.2.
Fireworks, 1.3G. See Section 307.2.
Fireworks, 1.4G. See Section 307.2.
FIXED BASE OPERATOR (FBO). See Section 412.2.
FLAME SPREAD. See Section 802.1.
FLAMMABLE GAS. See Section 307.2.
FLAMMABLE LIQUEFIED GAS. See Section 307.2.
FLAMMABLE SOLID. See Section 307.2.
FLASH POINT. See Section 307.2.
FLIGHT. See Section 1002.1.
FLOODWAY. See Section 1612.2.
FLY GALLERY. See Section 410.2.
FOOD COURT. See Section 402.2.
FUEL TANK. A tank containing fuel for an engine(s) or appliance.
FURNACE ROOM. A room primarily utilized for the installation of fuel-burning space-heating and water-heating appliances other than boilers.
GAS CABINET. See Section 415.2.
GAS ROOM. See Section 415.2.
GLUED BUILT-UP MEMBER. See Section 2302.1.
GRADE FLOOR OPENING. A window or other opening located such that the sill height of the opening is not more than 44 inches (1118 mm) above or below the finished ground level adjacent to the opening.
GRADE (LUMBER). See Section 2302.1.
GRADE PLANE. See Section 502.1.
GRANDSTAND. See Section 1002.1.
GRIDIRON. See Section 410.2.
GUARD. See Section 1002.1.
GYPSUM BOARD. See Section 2502.1.
GYPSUM PLASTER. See Section 2502.1.
HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces.
HANDLING. See Section 307.2.
HANDRAIL. See Section 1002.1.
HARDBOARD. See Section 2302.1.
HEAD JOINT. See Section 2102.1.
HEALTH HAZARD. See Section 307.2.
HEIGHT, WALLS. See Section 2102.1.
HELICAL PILE. See Section 1802.1.
HELIPORT. See Section 412.2.
HELISTOP. See Section 412.2.
HIGH-RISE BUILDING. A building with an occupied floor located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access.
HIGHLY TOXIC. See Section 307.2.
HISTORIC BUILDINGS. Buildings that are listed in or eligible for listing in the "National Register of Historic Places," or designated as historic by certified local governments in accordance with the National Historic Preservation Act of 1966 as amended. See Section 3409.
HOME. An institution, residence, or facility, required to be licensed by the Ohio Department of Health, that provides, for a period of more than twenty-four hours, whether for a consideration or not, accommodations to three or more unrelated individuals who are dependent upon the services of others, including a nursing home, residential care facility, home for the aging, a veterans' home operated under Chapter 5907. of the Revised Code, and a county home or district home that is or has been licensed as a residential care facility. For the purposes of licensure of homes, pursuant to Chapter 3721. of the Revised Code, any residence, institution, hotel, congregate housing project, or similar facility that meets the definition of a home under this section is such a home regardless of how the facility holds itself out to the public.
HOME, COUNTY AND DISTRICT. A county home or district home operated under Chapter 5155. of the Revised Code.
HOME FOR THE AGING. A home that provides services as a residential care facility and a nursing home, except that the home provides its services only to individuals who are dependent on the services of others by reason of both age and physical or mental impairment. The part or unit of a home for the aging that provides services only as a residential care facility is required to be licensed by the Ohio Department of Health as a residential care facility. The part or unit that may provide skilled nursing care beyond the extent authorized by Section 3721.011 [3721.01.1] of the Revised Code is required to be licensed as a nursing home.
HOME, NURSING. A home used for the reception and care of individuals who by reason of illness or physical or mental impairment require skilled nursing care and of individuals who require personal care services but not skilled nursing care. A nursing home is required to be licensed by the Ohio Department of Health to provide personal care services and skilled nursing care.
HOME, TYPE A FAMILY DAY-CARE. A home where the administrator permanently resides and where care is provided for seven to twelve children under six years of age or four to twelve children when at least four are under two years of age. Licensure is required of these homes by the Ohio Department of Job and Family Services when at least one of the children cared for is not a sibling of the others and the home is not the permanent residence of the children. These homes are also referred to as Type A Homes and Type A Child Care and are exempt from the rules of the board. Also see Chapter 5104. of the Revised Code
HOME, TYPE B FAMILY DAY-CARE. A home where the administrator permanently resides and where care is provided for one to six children under six years of age with no more than three children under two years of age when at least one of the children cared for is not a sibling of the others and the home is not the permanent residence of the children. These homes are also referred to as Type B Homes and Type B Child Care and are exempt from the rules of the board. Also see Chapter 5104. of the Revised Code.
HOUSING UNIT. See Section 408.1.1.
HPM ROOM. See Section 415.2.
IMPACT LOAD. See Section 1602.1.
INCAPABLE OF SELF-PRESERVATION. Persons because of age, physical limitations, mental limitations, chemical dependency, or medical treatment who cannot respond as an individual to an emergency situation.
INDUSTRIALIZED UNITS. See Section 117.
INERT GAS. See Section 307.2.
INSTITUTION OF HIGHER EDUCATION. A state institution of higher education as defined in Section 3345.011 of the Revised Code, a private nonprofit college or university located in this state that possesses a certificate of authorization issued pursuant to Chapter 1713 of the Revised Code, or a school located in this state that possesses a certificate of registration and one or more program authorizations issued by the state board of career colleges and schools under Chapter 3322 of the Revised Code. See School Building.
INTERIOR FINISH. See Section 802.1.
INTERLAYMENT. See Section 1502.1.
JOINT. See Section 702.1.
JURISDICTION. The authority to enforce this code by municipal corporations, townships or counties certified by the board in accordance with Section 3781.10 of the Revised Code or the division of industrial compliance in the department of commerce.
LABEL. An identification applied on a product by the manufacturer that contains the name of the manufacturer, the function and performance characteristics of the product or material, and the name and identification of an approved agency and that indicates that the representative sample of the product or material has been tested and evaluated by an approved agency (see Section 1703.5 and "Inspection certificate," "Manufacturer's designation" and "Mark").
LABELED. Equipment, materials or products to which has been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory, inspection agency or other organization concerned with product evaluation that maintains periodic inspection of the production of the above-labeled items and whose labeling indicates either that the equipment, material or product meets identified standards or has been tested and found suitable for a specified purpose.
LIGHT-FRAME CONSTRUCTION. A type of construction whose vertical and horizontal structural elements are primarily formed by a system of repetitive wood or cold-formed steel framing members.
LIMIT STATE. See Section 1602.1.
LIMITED SPRAYING SPACE. An area in which spraying operations for touch-up or spot painting of a surface area of nine square feet (0.84 m2) or less are conducted.
LIQUID. See Section 415.2.
LISTED. Equipment, materials, products or services included in a list published by an organization acceptable to the code official and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services and whose listing states either that the equipment, material, product or service meets identified standards or has been tested and found suitable for a specified purpose.
LIVE LOADS. See Section 1602.1.
LIVE LOADS (ROOF). See Section 1602.1.
LIVE/WORK UNIT. A dwelling unit or sleeping unit in which a significant portion of the space includes a nonresidential use that is operated by the tenant. See Section 419.
LOAD AND RESISTANCE FACTOR DESIGN (LRFD). See Section 1602.1.
LOAD EFFECTS. See Section 1602.1.
LOAD FACTOR. See Section 1602.1.
LOADS. See Section 1602.1.
LOT. A portion or parcel of land considered as a unit.
LOT LINE. A line dividing one lot from another, or from a street or any public place.
LOWER FLAMMABLE LIMIT (LFL). See Section 415.2.
LOWEST FLOOR. See Section 1612.2.
MANUFACTURER'S DESIGNATION. An identification applied on a product by the manufacturer indicating that a product or material complies with a specified standard or set of rules (see also "Inspection certificate," "Label" and "Mark").
MARK. An identification applied on a product by the manufacturer indicating the name of the manufacturer and the function of a product or material (see also "Inspection certificate," "Label" and "Manufacturer's designation").
MARQUEE. A permanent roofed structure projecting over an entrance attached to and supported by a building for the purpose of supporting a marquee sign.
MASONRY. See Section 2102.1.
MASONRY UNIT. See Section 2102.1.
Clay. See Section 2102.1.
Concrete. See Section 2102.1.
Hollow. See Section 2102.1.
Solid. See Section 2102.1.
MECHANICAL CODE. The "Ohio Mechanical Code."
MECHANICAL EQUIPMENT SCREEN. See Section 1502.1.
MENTAL HOSPITALS. See Section 308.3.1.
METAL COMPOSITE MATERIAL (MCM) SYSTEM. See Section 1402.1.
MEZZANINE. See Section 502.1.
MICROPILE. See Section 1802.1.
MINERAL BOARD. See Section 721.1.1.
MINERAL FIBER. See Section 702.1.
MINERAL WOOL. See Section 702.1.
MORTAR. See Section 2102.1.
NAILING, BOUNDARY. See Section 2302.1.
NAILING, EDGE. See Section 2302.1.
NAILING, FIELD. See Section 2302.1.
NATURAL GAS PROCESSING FACILITIES. Installations, including
associated buildings, pipes, valves, tanks, and other equipment, used to separate
various fluids, hydrocarbons, natural gas liquids, and impurities from the raw natural gas, manufacturing residue gas suitable for transmission and distribution
to end users.
NATURAL GAS LIQUIDS FRACTIONATION FACILITIES. Installations,
including associated buildings, pipes, valves, tanks, and other equipment, used for
the separation of mixtures of light hydrocarbons or natural gas liquids into
individual, purity natural gas liquid products, which include ethane, propane,
normal butane, isobutane, and natural gasolines.
NATURALLY DURABLE WOOD. See Section 2302.1.
Decay resistant. See Section 2302.1.
Termite resistant. See Section 2302.1.
NOMINAL LOADS. See Section 1602.1.
NOMINAL SIZE (LUMBER). See Section 2302.1.
NOSING. See Section 1002.1.
[F] NUISANCE ALARM. See Section 902.1.
NURSING HOMES. See Section 308.3.1.
OCCUPANCY. The purpose for which a building, or portion thereof, is used.
OCCUPANCY, CHANGE OF. See Section 3402.
OCCUPANCY CATEGORY. See Section 1602.1.
OCCUPANT LOAD. See Section 1002.1.
OCCUPIABLE SPACE. A room or enclosed space designed for human occupancy in which individuals congregate for amusement, educational or similar purposes or in which occupants are engaged at labor, and which is equipped with means of egress and light and ventilation facilities meeting the requirements of this code.
OPEN SYSTEM. See Section 307.2.
ORDINARY PRECAST STRUCTURAL WALL. See Section 1908.1.1.
ORDINARY REINFORCED CONCRETE STRUCTURAL WALL. See Section 1908.1.1.
ORDINARY STRUCTURAL PLAIN CONCRETE WALL. See Section 1908.1.1.
Class I. See Section 307.2.
Class II. See Section 307.2.
Class III. See Section 307.2.
Class IV. See Section 307.2.
Class V. See Section 307.2.
ORTHOGONAL. See Section 1613.2.
OTHER STRUCTURES. See Section 1602.1.
OXIDIZER. See Section 307.2.
Class 4. See Section 307.2.
Class 3. See Section 307.2.
Class 2. See Section 307.2.
Class 1. See Section 307.2.
OXIDIZING GAS. See Section 307.2.
PANEL (PART OF A STRUCTURE). See Section 1602.1.
PANIC HARDWARE. See Section 1002.1.
PARTICLEBOARD. See Section 2302.1.
PENTHOUSE. See Section 1502.1.
PERMIT. Deleted.
PERSON. An individual, heirs, executors, administrators or assigns, and also includes a firm, partnership or corporation, its or their successors or assigns, or the agent of any of the aforesaid. Whenever the word "person" is used in any section of this code prescribing a penalty or fine, as to partnerships or associations, the word shall include the partners or members thereof, and as to corporations, shall include the officer, agents or members thereof who are responsible for any violation of such section.
PHOTOLUMINESCENT. See Section 1002.1.
PHYSICAL HAZARD. See Section 307.2.
PINRAIL. See Section 410.2.
PLATFORM. See Section 410.2.
PLUMBING CODE. The "Ohio Plumbing Code."
POWER PIPING. Piping systems and their component parts that are not building services piping systems, and that may be installed within electric power generating stations, industrial and institutional plants, utility geothermal heating systems, and central and district heating and cooling systems. Power piping includes, but is not limited to, piping used in the distribution of plant and process steam at boiler pressures greater than fifteen pounds per square inch gauge, high temperature water piping from high pressure and high temperature boilers, power boiler steam condensate piping, high pressure and high temperature water condensate piping, and compressed air and hydraulic piping upstream of the first stop valve off a system distribution header.
PREFABRICATED WOOD I-JOIST. See Section 2302.1.
PREMISES. A lot, plot or parcel of land, including any structure thereon.
PRIMARY STRUCTURAL FRAME. The primary structural frame shall include all of the following structural members:
- The columns;
- Structural members having direct connections to the columns, including girders, beams, trusses and spandrels;
- Members of the floor construction and roof construction having direct connections to the columns; and
- Bracing members that are essential to the vertical stability of the primary structural frame under gravity loading shall be considered part of the primary structural frame whether or not the bracing member carries gravity loads.
PRISM. See Section 2102.1.
PRIVATE SCHOOL. A chartered nonpublic school or a nonchartered nonpublic school. See School Building.
PROCESS PIPING. Piping systems and their component parts that are not building services or power piping systems and that may be installed in petroleum refineries; chemical, pharmaceutical, textile, paper, semiconductor, and cryogenic plants; and related processing plants and terminals.
PROCESSING EQUIPMENT. Equipment, machinery and devices specifically intended and used exclusively for manufacturing and other similar purposes. Processing equipment does not include the building electrical service and distribution system, mechanical and plumbing systems related to space heating, air conditioning, ventilation, water distribution and sanitation or other systems regulated by board rules.
PROSCENIUM WALL. See Section 410.2.
PUBLIC ENTITY. (1) Any state or local government; (2)Any department, agency, special purpose district, or other instrumentality of Ohio or local government; and (3) The national railroad passenger corporation, and any commuter authority (as defined in Section 103(8) of the "Rail Passenger Service Act").
PUBLIC SCHOOL. Any school operated by a school district board of education, any community school established under Chapter 3314. of the Revised Code, any STEM school established under Chapter 3326. of the Revised Code, and any college-preparatory boarding school established under Chapter 3328. of the Revised Code. See School Building.
PUBLIC WAY. See Section 1002.1.
PYROPHORIC. See Section 307.2.
RAMP. See Section 1002.1.
RECORD DRAWINGS. See Section 902.1.
REFLECTIVE PLASTIC CORE FOIL INSULATION. An insulation material packaged in rolls that is less than 0.5 inch (12.7 mm) thick, with at least one exterior low emittance surface (0.1 perm or less) and a core material containing voids or cells.
REGISTERED DESIGN PROFESSIONAL. Any architect holding a certificate issued under Sections 4703.10 and 4703.36 of the Revised Code or any engineer holding a certificate issued under Section 4733.14 of the Revised Code.
RELIGIOUS WORSHIP, PLACE OF. A building or portion thereof intended for the performance of religious services.
REPAIR. The reconstruction or renewal of any part of an existing building for the purpose of its maintenance.
REPAIR, MINOR. The reconstruction or renewal of any part of an existing building for the purpose of its maintenance when the work has limited impact on access, safety or health. Minor repairs do not include the cutting away of any wall, partition or portions of walls, the removal or cutting of any structural beam or load bearing support, or the removal or change of any required element of accessibility, means of egress, or rearrangement of parts of a structure affecting the egress requirements. Minor repairs do not include addition to, alteration of, replacement or relocation of any standpipe, water supply, sewer, drainage, drain leader, gas, soil, waste, vent or similar piping, electric wiring or mechanical or other work affecting public health or general safety.
REROOFING. See Section 1502.1.
RESIDENTIAL AIRCRAFT HANGAR. See Section 412.2.
RESISTANCE FACTOR. See Section 1602.1.
REVISED CODE. All statutes of a permanent and general nature of this state as revised and consolidated into general provisions, titles, chapters, and sections.
ROOF ASSEMBLY. See Section 1502.1.
ROOF COVERING. See Section 1502.1.
ROOF COVERING SYSTEM. See Section 1502.1.
ROOF DECK. See Section 1502.1.
ROOF RECOVER. See Section 1502.1.
ROOF REPAIR. See Section 1502.1.
ROOF REPLACEMENT. See Section 1502.1.
RUBBLE MASONRY. See Section 2102.1.
RUNNING BOND. See Section 2102.1.
SAFE. As applied to a building, means free from danger or hazard to the life, safety, health or welfare of persons occupying or frequenting it, or of the public, and from danger of settlement, movement, disintegration, or collapse, whether such danger arises from the method or materials of its construction or from equipment installed therein, for the purpose of lighting, heating, the transmission or utilization of electric current, or from its location or otherwise.
SALLYPORT. See Section 408.1.1.
SANITARY. As applied to a building, means free from danger or hazard to the health of persons occupying or frequenting it or to that of the public, if such danger arises from the method or materials of its construction or from any equipment installed therein for the purpose of lighting, heating, ventilating, or plumbing.
SCHOOL BUILDING. A structure used for the instruction of students by a public or private school or institution of higher education.
SCISSOR STAIR. See Section 1002.1.
SCUPPER. See Section 1502.1.
SECONDARY MEMBERS. The following structural members shall be considered secondary members and not part of the primary structural frame:
- Structural members not having direct connections to the columns;
- Members of the floor construction not having direct connections to the columns; and
- Bracing members other than those that are part of the primary structural frame.
SELF-CLOSING. See Section 702.1.
SELF-LUMINOUS. See Section 1002.1.
SERIOUS HAZARD. A hazard of considerable consequence to safety or health through the design, location, construction, or equipment of a building, or the condition thereof, which hazard has been established through experience to be of certain or probable consequence, or which can be determined to be, or which is obviously such a hazard.
SHAFT. See Section 702.1.
SHAFT ENCLOSURE. See Section 702.1.
SHALLOW FOUNDATION. See Section 1802.1.
Perforated shear wall. See Section 2302.1.
Perforated shear wall segment. See Section 2302.1.
SHELL. See Section 2102.1.
SITE. See Section 1102.1.
SITE CLASS. See Section 1613.2.
SKYLIGHT, UNIT. A factory-assembled, glazed fenestration unit, containing one panel of glazing material that allows for natural lighting through an opening in the roof assembly while preserving the weather-resistant barrier of the roof.
SKYLIGHTS AND SLOPED GLAZING. Glass or other transparent or translucent glazing material installed at a slope of 15 degrees (0.26 rad) or more from vertical. Glazing material in skylights, including unit skylights, solariums, sunrooms, roofs and sloped walls, are included in this definition.
SLEEPING UNIT. A room or space in which people sleep, which can also include permanent provisions for living, eating, and either sanitation or kitchen facilities but not both. Such rooms and spaces that are also part of a dwelling unit are not sleeping units.
SMOKE ALARM. See Section 902.1.
SMOKE BARRIER. See Section 702.1.
SMOKE COMPARTMENT. See Section 702.1.
SMOKE DAMPER. See Section 702.1.
SMOKE DETECTOR. See Section 902.1.
SOLID. See Section 415.2.
SPECIAL AMUSEMENT BUILDING. See Section 411.2.
SPECIAL STRUCTURAL WALL. See Section 1908.1.1.
SPECIFIED. See Section 2102.1.
SPECIFIED COMPRESSIVE STRENGTH OF MASONRY (f m). See Section 2102.1.
SPLICE. See Section 702.1.
SPRAY BOOTH. A mechanically ventilated appliance of varying dimensions and construction provided to enclose or accommodate a spraying operation and to confine and limit the escape of spray vapor and residue and to exhaust it safely.
SPRAY ROOM. A room designed to accommodate spraying operations constructed in accordance with this code and separated from the remainder of the building by a minimum one-hour fire barrier.
SPRAYING SPACE. An area in which dangerous quantities of flammable vapors or combustible residues, dusts or deposits are present due to the operation of spraying processes. The building official is authorized to define the limits of the spraying space in any specific case.
SRO (Single room occupancy) FACILITY. A facility with more than five sleeping rooms that is kept, used, maintained, advertised or held out to the public as a place where each individual is provided with separate sleeping accommodations which is intended to be the permanent residence of a single occupant. SRO facilities are required to be licensed by the Ohio Fire Marshal and do not include agricultural labor camps, apartment houses, lodging houses, rooming houses or college dormitories.
STACK BOND. See Section 2102.1.
STAGE. See Section 410.2.
STAIR. See Section 1002.1.
STAIRWAY. See Section 1002.1.
Class I system. See Section 902.1.
Class II system. See Section 902.1.
Class III system. See Section 902.1.
Automatic dry. See Section 902.1.
Automatic wet. See Section 902.1.
Manual dry. See Section 902.1.
Manual wet. See Section 902.1.
STEEL JOIST. See Section 2202.1.
STEEP SLOPE. A roof slope greater than two units vertical in 12 units horizontal (17-percent slope).
STONE MASONRY. See Section 2102.1.
STORM SHELTER. See Section 423.2.
STORY. That portion of a building included between the upper surface of a floor and the upper surface of the floor or roof next above (also see "Basement," "Mezzanine" and Section 502.1). It is measured as the vertical distance from top to top of two successive tiers of beams or finished floor surfaces and, for the topmost story, from the top of the floor finish to the top of the ceiling joists or, where there is not a ceiling, to the top of the roof rafters.
STORY ABOVE GRADE PLANE. Any story having its finished floor surface entirely above grade plane, or in which the finished surface of the floor next above is:
- More than 6 feet (1829 mm) above grade plane; or
- More than 12 feet (3658 mm) above the finished ground level at any point.
STRENGTH. See Section 2102.1.
Design strength. See Section 2102.1.
STRENGTH DESIGN. See Section 1602.1.
STRUCTURAL COMPOSITE LUMBER. See Section 2302.1.
Laminated veneer lumber (LVL). See Section 2302.1.
Parallel strand lumber (PSL). See Section 2302.1.
STRUCTURAL GLUED-LAMINATED TIMBER. See Section 2302.1.
STRUCTURE. That which is built or constructed.
SUBDIAPHRAGM. See Section 2302.1.
SUBSTANTIAL IMPROVEMENT. See Section 1612.2.
SUITE. See Section 1002.1.
SUNROOM. See Section 1202.1.
SWIMMING POOLS. See Section 3109.2.
T RATING. See Section 702.1.
TEMPORARY DOOR LOCKING DEVICE. An assembly of parts intended to be engaged by a trained school staff member in a school building for the purpose of preventing both ingress and egress through a door in a school building for a finite period of time in an emergency situation and during active shooter drills. See Section 1008.1.9.11.
TENT. A structure, enclosure or shelter, with or without sidewalls or drops, constructed of fabric or pliable material supported in any manner except by air or the contents it protects.
THROUGH PENETRATION. See Section 702.1.
TIE-DOWN (HOLD-DOWN). See Section 2302.1.
TIE, LATERAL. See Section 2102.1.
TIE, WALL. See Section 2102.1.
TILE. See Section 2102.1.
TOWNHOUSE. A single-family dwelling unit constructed in a group of three or more attached units in which each unit extends from the foundation to roof and with open space on at least two sides.
TOXIC. See Section 307.2.
TRANSIENT, PRIMARILY. See Section 310.2.
TREATED WOOD. See Section 2302.1.
Fire-retardant-treated wood. See Section 2302.1.
Preservative-treated wood. See Section 2302.1.
TRIM. See Section 802.1.
TROUBLE SIGNAL. See Section 902.1.
TYPE A FAMILY DAY-CARE HOME. See "Home, Type A Family Day-care."
TYPE B FAMILY DAY-CARE HOME. See "Home, Type B Family Day-care."
TYPE A UNIT. See Section 1102.1.
TYPE B UNIT. See Section 1102.1.
UNDERLAYMENT. See Section 1502.1.
Class 4. See Section 307.2.
Class 3. See Section 307.2.
Class 2. See Section 307.2.
Class 1. See Section 307.2.
USE (MATERIAL). See Section 415.2.
VAPOR AREA. An area containing flammable vapors in the vicinity of dip tanks, drain boards or associated drying, conveying or other equipment during operation or shutdown periods. The code official is authorized to determine the extent of the vapor area, taking into consideration the characteristics of the liquid, the degree of sustained ventilation and the nature of the operations.
VAPOR-PERMEABLE MEMBRANE. A material or covering having a permeance rating of 5 perms (52.9 ×10-10 kg/Pa • s • m2) or greater, when tested in accordance with the dessicant method using Procedure A of ASTM E 96. A vapor-permeable material permits the passage of moisture vapor.
VAPOR RETARDER CLASS. A measure of a material or assembly's ability to limit the amount of moisture that passes through that material or assembly. Vapor retarder class shall be defined using the desiccant method of ASTM E 96 as follows:
Class I: 0.1 perm or less.
Class II: 0.1 < perm ≤ 1.0 perm.
Class III: 1.0 < perm ≤ 10 perm.
VEHICLE BARRIER SYSTEM. See Section 1602.1.
VEHICULAR GATE. See Section 3110.2.
VENEER. See Section 1402.1.
VENTILATION. The natural or mechanical process of supplying conditioned or unconditioned air to, or removing such air from, any space.
VINYL SIDING. See Section 1402.1.
WALKWAY, PEDESTRIAN. A walkway used exclusively as a pedestrian trafficway.
WALL. See Section 2102.1.
WALL, LOAD-BEARING. Any wall meeting either of the following classifications:
WALL PIER. See Section 1908.1.1.
WEB. See Section 2102.1.
WINDER. See Section 1002.1.
WIRE BACKING. See Section 2502.1.
WOOD SHEAR PANEL. See Section 2302.1.
WOOD STRUCTURAL PANEL. See Section 2302.1.
Composite panels. See Section 2302.1.
Oriented strand board (OSB). See Section 2302.1.
Plywood. See Section 2302.1.
WORKSTATION. See Section 415.2.
WYTHE. See Section 2102.1.
YARD. An open space, other than a court, unobstructed from the ground to the sky, except where specifically provided by this code, on the lot on which a building is situated.
ZONE. See Section 902.1.