ADOPTS WITH AMENDMENTS:

International Mechanical Code 2015 (IMC 2015)

Heads up: There are no amended sections in this chapter.

1301.1 Scope

AMENDMENT
This section has been amended at the state or city level.
This chapter shall govern the design, installation, construction and repair of fuel-oil and diesel oil storage and piping systems supplying and piped to building service equipment. The storage of fuel oil and flammable and combustible liquids not associated with building service equipment shall be in accordance with Chapters 6 and 57 of the fire code and enforced by the fire official.

1301.2 Storage and Piping Systems

AMENDMENT
This section has been amended at the state or city level.
Fuel-oil and diesel oil storage systems supplying and piped to building service equipment shall comply with Section 1308. Fuel-oil and diesel oil piping systems shall comply with the requirements of this chapter.
An appliance shall be designed for use with the type of fuel to which it will be connected. Such appliance shall not be converted from the fuel specified on the rating plate for use with a different fuel without securing reapproval from the code official.
The tank, piping and valves for appliances burning oil shall be installed in accordance with the requirements of this chapter. Where an oil burner is served by a tank, any part of which is above the level of the burner inlet connection and where the fuel supply line is taken from the top of the tank, an approved antisiphon valve or other siphon-breaking device shall be installed in lieu of the shutoff valve.

1301.5 Tanks Abandoned or Removed

AMENDMENT
This section has been amended at the state or city level.
All exterior abovegrade fill piping shall be removed when tanks are abandoned or removed. Tank abandonment and removal shall be in accordance with Section 5704.2.13 of the Fire Code.
Piping materials shall conform to the standards cited in this section.
All materials shall be rated for the operating temperatures and pressures of the system, and shall be compatible with the type of liquid.

1302.3 Pipe Standards

AMENDMENT
This section has been amended at the state or city level.
Fuel oil pipe shall comply with one of the standards listed in Table 1302.3.

TABLE 1302.3 FUEL OIL PIPING

MATERIAL STANDARD (see Chapter 15)
Copper or copper-alloy pipe ASTM B 42; ASTM B 43;
ASTM B 302
Copper or copper-alloy tubing
(Type K, L or M)
ASTM B 75; ASTM B 88;
ASTM B 280;
Labeled pipe (See Section 1302.4)
Nonmetallic pipe ASTM D 2996
Steel pipe ASTM A 53; ASTM A 106
Steel tubing ASTM A 254; ASTM A 539
Nonmetallic pipe shall be listed and labeled as being acceptable for the intended application for flammable and combustible liquids. Nonmetallic pipe shall be installed only outside, underground.
Fittings and valves shall be approved for the piping systems, and shall be compatible with, or shall be of the same material as, the pipe or tubing.
Pipe shall be approved for bending. Pipe bends shall be made with approved equipment. The bend shall not exceed the structural limitations of the pipe.
Pumps that are not part of an appliance shall be of a positive-displacement type. The pump shall automatically shut off the supply when not in operation. Pumps shall be listed and labeled in accordance with UL 343.
Flexible connectors and hoses shall be listed and labeled in accordance with UL 536.
Joints and connections shall be approved and of a type approved for fuel-oil piping systems. Threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Unions requiring gaskets or packings, right or left couplings, and sweat fittings employing solder having a melting point of less than 1,000°F (538°C) shall not be used in oil lines. Cast-iron fittings shall not be used. Joints and connections shall be tight for the pressure required by test.
Joints between different piping materials shall be made with approved adapter fittings. Joints between different metallic piping materials shall be made with approved dielectric fittings or brass converter fittings.
Pipe shall be cut square, reamed and chamfered and be free from all burrs and obstructions. Pipe ends shall have full-bore openings and shall not be undercut.
Where required by Sections 1303.4 through 1303.10, the preparation and installation of brazed, mechanical, threaded and welded joints shall comply with Sections 1303.3.1 through 1303.3.4.
All joint surfaces shall be cleaned. An approved flux shall be applied where required. The joints shall be brazed with a filler metal conforming to AWS A5.8.
Mechanical joints shall be installed in accordance with the manufacturer's instructions. Press connect joints shall conform to one of the standards listed in Table 1302.3.
Threads shall conform to ASME B1.20.1. Pipe-joint compound or tape shall be applied on the male threads only.
All joint surfaces shall be cleaned by an approved procedure. The joint shall be welded with an approved filler metal.
Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Section 1303.3.
Joints between brass tubing or fittings shall be brazed or mechanical joints complying with Section 1303.3.
Joints between copper or copper-alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Section 1303.3.
Joints between copper or copper-alloy tubing or fittings shall be brazed, mechanical joints complying with Section 1303.3, press connect joints that conform to one of the standards in Table 1302.3 or flared joints. Flared joints shall be made by a tool designed for that operation.
Joints between nonmetallic pipe or fittings shall be installed in accordance with the manufacturer's instructions for the labeled pipe and fittings.
Joints between steel pipe or fittings shall be threaded or welded joints complying with Section 1303.3 or mechanical joints complying with Section 1303.9.1.
Joints shall be made with an approved elastomeric seal. Mechanical joints shall be installed in accordance with the manufacturer's instructions. Mechanical joints shall be installed outside, underground, unless otherwise approved.
Joints between steel tubing or fittings shall be mechanical or welded joints complying with Section 1303.3.
Proper allowance shall be made for expansion, contraction, jarring and vibration. Piping other than tubing, connected to underground tanks, except straight fill lines and test wells, shall be provided with flexible connectors, or otherwise arranged to permit the tanks to settle without impairing the tightness of the piping connections.
Pipe supports shall be in accordance with Section 305.
The fuel oil system shall be sized for the maximum capacity of fuel oil required. The minimum size of a supply line shall be 3/8-inch (9.5 mm) inside diameter nominal pipe or 3/8-inch (9.5 mm) od tubing. The minimum size of a return line shall be 1/4-inch (6.4 mm) inside diameter nominal pipe or 5/16-inch (7.9 mm) outside diameter tubing. Copper tubing shall have 0.035-inch (0.9 mm) nominal and 0.032-inch (0.8 mm) minimum wall thickness.

1305.2.1 Flood Hazard

AMENDMENT
This section has been amended at the state or city level.
Fuel oil pipe, equipment and appliances located in flood hazard areas shall be located above the elevation required by Section 1612 of the Building Code for utilities and attendant equipment or shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to such elevation.
Supply piping shall connect to the top of the fuel oil tank. Fuel oil shall be supplied by a transfer pump or automatic pump or by other approved means.
Exception: This section shall not apply to inside or aboveground fuel oil tanks.
Return piping shall connect to the top of the fuel oil tank. Valves shall not be installed on return piping.
The system shall be designed for the maximum pressure required by the fuel-oil-burning appliance. Air or other gases shall not be used to pressurize tanks.
A fill pipe shall terminate outside of a building at a point not less than 2 feet (610 mm) from any building opening at the same or lower level. A fill pipe shall terminate in a manner designed to minimize spilling when the filling hose is disconnected. Fill opening shall be equipped with a tight metal cover designed to discourage tampering.
Liquid fuel vent pipes shall terminate outside of buildings at a point not less than 2 feet (610 mm) measured vertically or horizontally from any building opening. Outer ends of vent pipes shall terminate in a weatherproof vent cap or fitting or be provided with a weatherproof hood. Vent caps shall have a minimum free open area equal to the cross-sectional area of the vent pipe and shall not employ screens finer than No. 4 mesh. Vent pipes shall terminate sufficiently above the ground to avoid being obstructed with snow or ice. Vent pipes from tanks containing heaters shall be extended to a location where oil vapors discharging from the vent will be readily diffused. If the static head with a vent pipe filled with oil exceeds 10 pounds per square inch (psi) (69 kPa), the tank shall be designed for the maximum static head that will be imposed.

Liquid fuel vent pipes shall not be cross connected with fill pipes, lines from burners or overflow lines from auxiliary tanks.
Tanks in which a constant oil level is not maintained by an automatic pump shall be equipped with a method of determining the oil level.
Test wells shall not be installed inside buildings. For outside service, test wells shall be equipped with a tight metal cover designed to discourage tampering.
The gauging of inside tanks by means of measuring sticks shall not be permitted. An inside tank provided with fill and vent pipes shall be provided with a device to indicate either visually or audibly at the fill point when the oil in the tank has reached a predetermined safe level.
Gauging devices such as liquid level indicators or signals shall be designed and installed so that oil vapor will not be discharged into a building from the liquid fuel supply system. Liquid-level indicating gauges shall comply with UL 180.
A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge which, when broken, will permit the escape of oil from the tank.
A shutoff valve shall be installed on the fuel-oil supply line at the entrance to the building. Inside or above-ground tanks are permitted to have valves installed at the tank. The valve shall be capable of stopping the flow of fuel oil to the building or to the appliance served where the valve is installed at a tank inside the building. Valves shall comply with UL 842.
A shutoff valve shall be installed at the connection to each appliance where more than one fuel-oil-burning appliance is installed.
A relief valve shall be installed on the pump discharge line where a valve is located downstream of the pump and the pump is capable of exceeding the pressure limitations of the fuel oil system.
A relief valve shall be installed on the discharge line of fuel-oil-heating appliances.
The relief valve shall discharge fuel oil when the pressure exceeds the limitations of the system. The discharge line shall connect to the fuel oil tank.

Section 1308 Testing

AMENDMENT
This section has been amended at the state or city level.

Section 1308 Fuel Oil and Diesel Oil Storage

AMENDMENT
This section has been amended at the state or city level.

1308.1 Testing Required

AMENDMENT
This section has been amended at the state or city level.

1308.1 Fuel Oil and Diesel Oil Storage Systems

AMENDMENT
This section has been amended at the state or city level.
Fuel oil and diesel oil storage systems supplying and piped to building service equipment, including emergency and standby generators, shall be installed in accordance with one of the following:
  1. NFPA 30;
  2. NFPA 31 for fuel-oil burning heating appliances;
  3. NFPA 37 for diesel-oil burning stationary combustion engines; or
  4. Sections 1308.2 to 1308.4, as applicable.

1308.2 Fuel Oil and Diesel Oil Storage in Outside, Above-Ground Tanks

AMENDMENT
This section has been amended at the state or city level.
Where connected to a fuel oil or diesel oil piping system, the maximum amount of fuel oil or diesel oil storage allowed outside above-ground without additional protection shall be 660 gallons (2498 L). The outside, above-ground storage of fuel oil or diesel oil in quantities exceeding 660 gallons (2498 L) and connected to and serving building service equipment shall comply with Chapter 22 of NFPA 30.

1308.3 Fuel Oil and Diesel Oil Storage Inside Buildings

AMENDMENT
This section has been amended at the state or city level.
Fuel oil storage inside of buildings shall comply with Sections 1308.3.1 to 1308.3.5.

1308.3.1 Quantity Limits

AMENDMENT
This section has been amended at the state or city level.
One or more fuel oil or diesel oil storage tanks containing a Class II or III combustible liquid shall be permitted in a building. The aggregate capacity of all such tanks shall not exceed 660 gallons (2498 L).

Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons (11356 L) of a Class II or III liquid for storage in protected above-ground tanks listed in accordance with UL 2085 when all of the following conditions are met:
  1. The entire 3,000-gallon (11356 L) quantity shall be stored in protected above-ground tanks listed in accordance with UL 2085;
  2. The 3,000-gallon (11356 L) capacity shall be permitted to be stored in a single tank or multiple smaller tanks;
  3. Normal and emergency venting shall be provided in accordance with NFPA 30 except that the vent capacity reduction factors shall not be allowed;
  4. Flame arrestors or pressure vacuum breather valves shall be installed in normal vents;
  5. Secondary containment, drainage control or diking shall be provided in accordance with Section 2704.2 of the fire code;
  6. An overfill prevention system that prevents the tank from being filled in excess of 95 percent of its capacity shall be provided for each tank. Filling procedure information shall be available and accessible to the person filling the tanks;
  7. The fill pipe shall be provided with a means for making a direct connection to the fuel delivery hose so that the delivery of fuel is not exposed to the open air during the filling operation;
  8. A noncombustible fixed spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. The spill container shall be equipped with a manual drain valve that drains into the primary tank;
  9. Approved anti-siphon devices shall be installed in each external pipe connected to the protected above-ground tank when the pipe extends below the level of the top of the tank; and
  10. The tanks shall be located in a room protected by an automatic sprinkler system complying with Section 903.3.1.1 of the building code.

1308.3.2 Restricted Use and Connection

AMENDMENT
This section has been amended at the state or city level.
Tanks installed in accordance with Section 1308.3 of this rule shall be used only to supply fuel oil to fuel-burning or generator equipment installed in accordance with Section 1308.3.4. Connections between tanks and equipment supplied by such tanks shall be made using closed piping systems.

1308.3.3 Applicability of Maximum Allowable Quantity and Control Area Requirements

AMENDMENT
This section has been amended at the state or city level.
The quantity of combustible liquid stored in tanks complying with Section 1308.3 of this rule shall not be counted towards the maximum allowable quantity set forth in Table 307.1(1) of the building code, and such tanks shall not be required to be located in a control area.

1308.3.4 Installation

AMENDMENT
This section has been amended at the state or city level.
Tanks and piping systems shall be installed and separated from other uses in accordance with one of the applicable compliance paths prescribed in Section 1308.1.

Exception: Protected above-ground tanks listed in accordance with UL 2085 and complying with Section 1308.3.1 shall not be required to be separated from surrounding areas.

1308.3.5 Tanks in Basements

AMENDMENT
This section has been amended at the state or city level.
Tanks in basements shall be located not more than two stories below grade plane.

1308.4 Underground Storage of Fuel Oil

AMENDMENT
This section has been amended at the state or city level.
The design, installation, registration, and inspection of regulated underground storage tanks shall be in accordance with the fire code and rules adopted by the state fire marshal and enforced by the fire official, in accordance with Sections 3737.87 to 3737.89 of the Revised Code. Underground storage tanks not regulated by the state fire marshal's Bureau of Underground Storage tanks shall comply with NFPA 30.

Section 1309 Testing

AMENDMENT
This section has been amended at the state or city level.

1309.1 Testing Required

AMENDMENT
This section has been amended at the state or city level.
Fuel oil piping shall be tested in accordance with NFPA 31.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING