ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.

301.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter shall control the classification of all buildings and structures as to use and occupancy and are established to organize and prescribe the appropriate features of construction and occupant safety requirements for buildings and are not established for compliance with any conditions of licensure which are outside the jurisdiction of this code.

There may be other requirements owners may be required to meet as set forth by other licensing agencies such as the Ohio State Fire Marshal, Ohio Department of Health, the Ohio Department of Jobs and Family Services, Ohio Department of Mental Health and Addiction Services, Ohio Department of Developmental Disabilities, federal agencies, or other licensing authorities. Owners and designers should investigate these additional licensing agency requirements to ensure they are incorporated into the building design before submitting to the certified building department for plan approval.
Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed in this section. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically provided for in this code, such structure shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved.
  1. Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5.
  2. Business (see Section 304): Group B.
  3. Educational (see Section 305): Group E.
  4. Factory and Industrial (see Section 306): Groups F-1 and F-2.
  5. High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5.
  6. Institutional (see Section 308): Groups I-1, I-2, I-3 and I-4.
  7. Mercantile (see Section 309): Group M.
  8. Residential (see Section 310): Groups R-1, R-2, R-3 and R-4.
  9. Storage (see Section 311): Groups S-1 and S-2.
  10. Utility and Miscellaneous (see Section 312): Group U.
Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation.
A building or tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B occupancy.
The following rooms and spaces shall not be classified as Assembly occupancies:
  1. A room or space used for assembly purposes with an occupant load of less than 50 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
  2. A room or space used for assembly purposes that is less than 750 square feet (70 m2) in area and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy.
Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100 per room or space are not considered separate occupancies.
Group A-1 occupancy includes assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:

  • Motion picture theaters
  • Symphony and concert halls
  • Television and radio studios admitting an audience
  • Theaters

303.3 Assembly Group A-2

AMENDMENT
This section has been amended at the state or city level.
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to:

Banquet halls

Casinos (gaming areas)

Nightclubs

Restaurants, cafeterias and similar dining facilities (including associated commercial food service establishments)

Taverns and bars
Group A-3 occupancy includes assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:

  • Amusement arcades
  • Art galleries
  • Bowling alleys
  • Community halls
  • Courtrooms
  • Dance halls (not including food or drink consumption)

    Exhibition halls
  • Funeral parlors
  • Gymnasiums (without spectator seating)
  • Indoor swimming pools (without spectator seating)

    Indoor tennis courts (without spectator seating)
  • Lecture halls
  • Libraries
  • Museums
  • Places of religious worship
  • Pool and billiard parlors
  • Waiting areas in transportation terminals
Group A-4 occupancy includes assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:

Group A-5 occupancy includes assembly uses intended for participation in or viewing outdoor activities including, but not limited to:

304.1 Business Group B

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following:

Airport traffic control towers

Ambulatory care facilities

Animal hospitals, kennels and pounds

Banks

Barber and beauty shops

Car wash

Civic administration

Clinic, outpatient

Dry cleaning and laundries: pick-up and delivery stations and self-service

Educational occupancies for students above the 12th grade

Electronic data processing

Food processing establishments and commercial food service establishments not associated with restaurants, cafeterias and similar dining facilities not more than 2,500 square feet (232 m2) in area.

Laboratories: testing and research

Motor vehicle showrooms

Post offices

Print shops

Professional services (architects, attorneys, dentists, physicians, engineers, etc.)

Radio and television stations

Telephone exchanges

Training and skill development not in a school or academic program (this shall include, but not be limited to, tutoring centers, martial arts studios, gymnastics and similar uses regardless of the ages served, and where not classified as a Group A occupancy).
Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade.
Religious educational rooms and religious auditoriums, which are accessory to places of religious worship in accordance with Section 303.1.4 and have occupant loads of less than 100 per room or space, shall be classified as Group A-3 occupancies.

305.2 Group E, Day Care Facilities-more than 21/2 years of age

AMENDMENT
This section has been amended at the state or city level.
Except for a Type A or Type B Family Day care facility, this group includes buildings and structures or portions thereof occupied by more than five children older than 21/2 years of age who receive educational, supervision or personal care services for fewer than 24 hours per day.
Rooms and spaces within places of religious worship providing such day care during religious functions shall be classified as part of the primary occupancy.

305.2.2 Five or Fewer Children

AMENDMENT
This section has been amended at the state or city level.
Except for a Type A or Type B Family Day care facility, a facility having five or fewer children receiving such day care shall be classified as part of the primary occupancy.

305.2.3 Five or Fewer Children in a Dwelling Unit

AMENDMENT
This section has been amended at the state or city level.
Except for a Type A or Type B Family Day care facility, a facility such as the above within a dwelling unit and having five or fewer children receiving such day care shall be classified as a Group R-3. The facility may comply with the construction requirements of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings."

305.3 Group E, day care facilities - 21/2 years or less of age

AMENDMENT
This section has been amended at the state or city level.
A day care facility that provides care for more than five but no more than 100 children 21/2 years or less of age and the day care facilities are at the level of exit discharge, and where every room where care is provided has no fewer than one exterior exit door for which the exit access and exit discharge do not require the traversing of stairs.
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H hazardous or Group S storage occupancy.

306.2 Moderate-Hazard Factory Industrial, Group F-1

AMENDMENT
This section has been amended at the state or city level.
ILLUSTRATION
Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:

Aircraft (manufacturing, not to include repair) Appliances

Athletic equipment

Automobiles and other motor vehicles

Bakeries

Beverages: over 16-percent alcohol content

Bicycles

Boats

Brooms or brushes

Business machines

Cameras and photo equipment

Canvas or similar fabric

Carpets and rugs (includes cleaning)

Clothing

Construction and agricultural machinery

Disinfectants

Dry cleaning and dyeing

Electric generation plants

Electronics

Engines (including rebuilding)

Food processing establishments and commercial food service establishments not associated with restaurants, cafeterias and similar dining facilities more than 2,500 square feet (232 m2) in area.

Furniture

Hemp products

Jute products

Laundries

Leather products

Machinery

Metals

Millwork (sash and door)

Motion pictures and television filming (without spectators)

Musical instruments

Optical goods

Paper mills or products

Photographic film

Plastic products

Printing or publishing

Recreational vehicles

Refuse incineration

Shoes

Soaps and detergents

Textiles

Tobacco

Trailers

Upholstering

Wood; distillation

Woodworking (cabinet)
Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:

  • Beverages: up to and including 16-percent alcohol content
  • Brick and masonry
  • Ceramic products
  • Foundries
  • Glass products
  • Gypsum
  • Ice
  • Metal products (fabrication and assembly)

[F] 307.1 High-Hazard Group H

AMENDMENT
This section has been amended at the state or city level.
High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the fire code. Hazardous materials stored, or used on top of roofs or canopies, shall be classified as outdoor storage or use and shall comply with the fire code.

TABLE 307.1(1)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, p
MATERIAL CLASS GROUP WHEN
THE MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
STORAGEb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas cubic
feet at NTP
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas cubic
feet at NTP
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Combustible dust NA H-2 See
Note q
NA NA See
Note q
NA NA See
Note q
NA
Combustible fiberq Loose
Baledo
H-3 (100)
(1,000)
NA NA (100)
(1,000)
NA NA (20)
(200)
NA
Combustible liquidc, i II
IIIA
IIIB
H-2 or H-3
H-2 or H-3
NA
NA 120d, e
330d, e
13,200e, f
NA NA 120d
330d
13,200f
NA NA 30d
80d
3,300f
Consumer fireworks 1.4G H-3 0 NA NA NA NA NA NA NA
Cryogenic flammable NA H-2 NA 45d NA NA 45d NA NA 10d
Cryogenic inert NA NA NA NA NL NA NA NL NA NA
Cryogenic oxidizing NA H-3 NA 45d NA NA 45d NA NA 10d
Explosives Division 1.1 H-1 1e, g (1)e, g NA 0.25g (0.25)g NA 0.25g (0.25)g
Division 1.2 H-1 1e, g (1)e, g 0.25g (0.25)g 0.25g (0.25)g
Division 1.3 H-1 or H-2 5e, g (5)e, g 1g (1)g 1g (1)g
Division 1.4 H-3 50e, g (50)e, g 50g (50)g NA NA
Division 1.4G H-3 0 NA NA NA NA NA
Division 1.5 H-1 1e, g (1)e, g 0.25g (0.25)g 0.25g (0.25)g
Division 1.6 H-1 1e, g NA NA NA NA NA
Flammable gas Gaseous
Liquefied
H-2 NA NA
(150)d, e
1,000d, e
NA
NA NA
(150)d, e
1,000d, e
NA
NA NA
Flammable liquidc IA
IB and IC
H-2
or H-3
NA 30d, e
120d, e
NA NA 30d
120d
NA NA 10d
30d
Flammable liquid,
combination
(IA, IB, IC)
NA H-2
or H-3
NA 120d, e, h NA NA 120d, h NA NA 30d, h
Flammable solid NA H-3 125d, e NA NA 125d NA NA 25d NA
Inert gas Gaseous
Liquefied
NA
NA
NA
NA
NA
NA
NL
NL
NA
NA
NA
NA
NL
NL
NA
NA
NA
NA
Organic peroxide UD
I
II
III
IV
V
H-1
H-2
H-3
H-3
NA
NA
1e, g
5d, e
50d, e
125d, e
NL
NL
(1)e, g
(5)d, e
(50)d, e
(125)d, e
NL
NL
NA 0.25g
1d
50d
125d
NL
NL
(0.25)g
(1)d
(50)d
(125)d
NL
NL
NA 0.25g
1d
10d
25d
NL
NL
(0.25)g
(1)d
(10)d
(25)d
NL
NL
Oxidizer 4
3k
2
1
H-1
H-2 or H-3
H-3
NA
1g
10d, e
250d, e
4,000e, f
(1)e, g
(10)d, e
(250)d, e
(4,000)e, f
NA 0.25g
2d
250d
4,000f
(0.25)g
(2)d
(250)d
(4,000)f
NA 0.25g
2d
50d
1,000f
(0.25)g
(2)d
(50)d
(1,000)f
Oxidizing gas Gaseous
Liquefied
H-3 NA NA
(150)d, e
1,500d, e
NA
NA NA
(150)d, e
1,500d, e
NA
NA NA
Pyrophoric NA H-2 4e, g (4)e, g 50e, g 1g (1)g 10e, g 0 0
Unstable (reactive) 4
3
2
1
H-1
H-1 or H-2
H-3
NA
1e, g
5d, e
50d, e
NL
(1)e, g
(5)d, e
(50)d, e
NL
10e, g
50d, e
750d, e
NL
0.25g
1d
50d
NL
(0.25)g
(1)d
(50)d
NL
2e, g
10d, e
750d, e
NL
0.25g
1d
10d
NL
(0.25)g
(1)d
(10)d
NL
Water reactive 3
2
1
H-2
H-3
NA
5d, e
50d, e
NL
(5)d, e
(50)d, e
NL
NA 5d
50d
NL
(5)d
(50)d
NL
NA 1d
10d
NL
(1)d
(10)d
NL


For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
NL = Not Limited; NA = Not Applicable; UD = Unclassified Detonable.
  1. For use of control areas, see Section 414.2.
  2. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
  3. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
  4. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  5. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, gas rooms or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10 of the fire code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
  6. Quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  7. Allowed only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  8. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids.
  9. The maximum allowable quantity shall not apply to fuel oil or diesel oil storage complying with Chapter 13 or Section 915 of the mechanical code.
  10. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
  11. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage containers and the manner of storage are approved.
  12. Deleted.
  13. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the fire code.
  14. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
  15. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
  16. The following shall not be included in determining the maximum allowable quantities:
    1. Liquid or gaseous fuel in fuel tanks on vehicles.
    2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with the fire code.
    3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code.
    4. Liquid fuels in piping systems and fixed appliances regulated by the mechanical code.
    5. Alcohol-based hand rubs classified as Class I or II liquids in dispensers that are installed in accordance with Sections 5705.5 and 5705.5.1 of the fire code. The location of the alcohol-based hand rub (ABHR) dispensers shall be provided in the construction documents.
  17. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.

TABLE 307.1(2)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARDa, c, f, h, i
MATERIAL STORAGEb USE-CLOSED SYSTEMSb USE-OPEN SYSTEMSb
Solid
poundsd, e
Liquid gallons
(pounds)d, e
Gas cubic feet at NTP
(pounds)d
Solid
poundsd
Liquid gallons
(pounds)d
Gas cubic feet at NTP
(pounds)d
Solid
poundsd
Liquid gallons
(pounds)d
Corrosives 5,000 500 Gaseous 810e
Liquefied (150)
5,000 500 Gaseous 810e
Liquefied (150)
1,000 100
Highly
Toxic
10 (10) Gaseous 20g
Liquefied (4)g
10 (10) Gaseous 20g
Liquefied (4)g
3 (3)
Toxic 500 (500) Gaseous 810e
Liquefied (150)e
500 (500) Gaseous 810e
Liquefied (150)e
125 (125)

For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
  1. For use of control areas, see Section 414.2.
  2. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
  3. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
  4. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  5. Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the fire code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
  6. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
  7. Allowed only where stored in approved exhausted gas cabinets or exhausted enclosures as specified in the fire code.
  8. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
  9. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the fire code.

[F] 307.1.1 Uses Other Than Group H

AMENDMENT
This section has been amended at the state or city level.
An occupancy that stores, uses or handles hazardous materials as described in one or more of the following items shall not be classified as Group H, but shall be classified as the occupancy that it most nearly resembles.
  1. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the fire code.
  2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the fire code.
  3. Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery, building service equipment, or process equipment.
  4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both.
  5. Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
  6. Liquor stores and distributors without bulk storage.
  7. Refrigeration systems.
  8. The storage or utilization of materials for agricultural purposes on the premises.
  9. Stationary batteries utilized for facility emergency power, uninterruptable power supply or telecommunication facilities, provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the mechanical code.
  10. Corrosive personal or household products in their original packaging used in retail display.
  11. Commonly used corrosive building materials.
  12. Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the fire code.
  13. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
  14. The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the fire code.

[F] 307.1.2 Hazardous Materials

AMENDMENT
This section has been amended at the state or city level.
Hazardous materials in any quantity shall conform to the requirements of this code, including Section 414, and the fire code.
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:

Detonable pyrophoric materials

Explosives:

Division 1.1

Division 1.2

Division 1.3

Division 1.4

Division 1.5

Division 1.6

Organic peroxides, unclassified detonable

Oxidizers, Class 4

Unstable (reactive) materials, Class 3 detonable and Class 4
The following occupancies containing explosive materials shall be classified as follows:
  1. Division 1.3 explosive materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
  2. Articles, including articles packaged for shipment, that are not regulated as a Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.
Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:

Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:

Buildings and structures containing materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:

Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and constructed in accordance with Section 415.11.
Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified.

308.1 Institutional Group I

AMENDMENT
This section has been amended at the state or city level.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which care (personal, custodial, or medical) or supervision is provided to persons who are or are not capable of self-preservation without physical assistance or in which persons are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.

Exception: Ambulatory care facilities and outpatient clinics shall be classified as Group B.

308.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
The following terms are defined in Chapter 2:

CARE FACILITY.

CUSTODIAL CARE.

DETOXIFICATION FACILITIES.

FOSTER CARE FACILITIES.

HOSPITALS AND PSYCHIATRIC HOSPITALS.

INCAPABLE OF SELF-PRESERVATION.

MEDICAL CARE.

NURSING HOMES.

PERSONAL CARE SERVICE.

308.3 Institutional Group I-1

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Sections 308.3.2 and 308.3.3, Institutional Group I-1 occupancy shall include buildings, structures or portions thereof for more than 16 persons, excluding staff, who reside in a supervised environment, receive care and are capable of self-preservation. This group shall include, but not be limited to, the following:

Alcohol and drug centers

Assisted living facilities

Congregate care facilities

Group homes

Halfway houses

Residential board and care facilities

Social rehabilitation facilities

308.3.1 Occupancy Conditions

AMENDMENT
This section has been amended at the state or city level.
Buildings of Group I-1 shall be classified as one of the occupancy conditions specified in Section 308.3.1.1 or 308.3.1.2.

308.3.1 308.3.1.1 Condition 1

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which all persons receiving custodial care who, without any assistance, are capable of responding to an emergency situation to complete building evacuation.

308.3.2 308.3.1.2 Condition 2

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which there are any persons receiving care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.

308.3.3 308.3.2 Six to 16 Persons Receiving Custodial Care

AMENDMENT
This section has been amended at the state or city level.
A care facility housing not fewer than six and not more than 16 persons receiving care shall be classified as Group R-4.

308.3.4 308.3.3 Five or Fewer Persons Receiving Custodial Care

AMENDMENT
This section has been amended at the state or city level.
A care facility with five or fewer persons receiving care shall be classified as Group R as provided in Section 310.

308.4 Institutional Group I-2

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Section 308.4.2, Institutional Group I-2 occupancy shall include buildings and structures used for care for more than five persons who are incapable of self-preservation for more than 24 hours. This group shall include, but not be limited to, the following:

Foster care facilities

Detoxification facilities

Hospitals

Nursing homes

Psychiatric hospitals
Buildings of Group I-2 shall be classified as one of the occupancy conditions specified in Section 308.4.1.1 or 308.4.1.2.

308.4.1.1 Condition 1

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include facilities that provide care but do not provide emergency care, surgery, obstetrics or in-patient stabilization units for psychiatric or detoxification, including but not limited to nursing homes and foster care facilities.

308.4.1.2 Condition 2

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include facilities that provide care and could provide emergency care, surgery, obstetrics or in-patient stabilization units for psychiatric or detoxification, including but not limited to hospitals.

308.4.2 Five or Fewer Persons Receiving Medical Care

AMENDMENT
This section has been amended at the state or city level.
A care facility with five or fewer persons incapable of self-preservation receiving care shall be classified as Group R as provided in Section 310.

308.5 Institutional Group I-3

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Section 308.5.2, Institutional Group I-3 occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. A Group I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control. This group shall include, but not be limited to, the following:

Correctional centers

Detention centers

Jails

Prerelease centers

Prisons

Reformatories

308.5.1 Occupancy Conditions

AMENDMENT
This section has been amended at the state or city level.
Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.5.1.1 through 308.5.1.5 (see Section 408.1).

308.5.1 308.5.1.1 Condition 1

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R.

308.5.2 308.5.1.2 Condition 2

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits.

308.5.3 308.5.1.3 Condition 3

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote-controlled release of means of egress from such a smoke compartment to another smoke compartment.

308.5.4 308.5.1.4 Condition 4

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.

308.5.5 308.5.1.5 Condition 5

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.

308.5.2 Five or Fewer Persons Secured or Restrained

AMENDMENT
This section has been amended at the state or city level.
Buildings containing five or fewer persons who are being secured or restrained shall be classified as part of the primary occupancy.

308.6 Institutional Group I-4 , Day Care Facilities

AMENDMENT
This section has been amended at the state or city level.
Except for Type A or Type B Family Day cares facilities and except as provided in Sections 308.6.1 through 308.6.4, Institutional Group I-4 occupancy shall include buildings and structures occupied by more than five persons of any age who are capable of selfpreservation with limited physical assistance or incapable of self-preservation, who receive care for fewer than 24 hours per day by persons other than parents or guardians, relatives by blood, marriage or adoption and in a place other than the home of the person cared for. This group shall include, but not be limited to, the following:

Adult day care

Child day care

308.6.1 Classification as Group E

AMENDMENT
This section has been amended at the state or city level.
A day care facility that provides care for more than five but no more than 100 children 21/ 2 years or less of age and the day care facilities are at the level of exit discharge, and where every room where care is provided has no fewer than one exterior exit door for which the exit access and exit discharge do not require the traversing of stairs, shall be classified as Group E.
Rooms and spaces within places of religious worship providing such care during religious functions shall be classified as part of the primary occupancy.

308.6.3 Five or Fewer Persons Receiving Care

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Section 308.6.4, a care facility having five or fewer persons receiving care shall be classified as part of the primary occupancy.

308.6.4 Five or Fewer Persons Receiving Care in a Dwelling Unit

AMENDMENT
This section has been amended at the state or city level.
Except for Type B Family Daycare facilities, a care facility within a dwelling unit and having five or fewer persons receiving care shall be classified as Group R as provided in Section 310.
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:

Department stores

Drug stores

Markets

Motor fuel-dispensing facilities

Retail or wholesale stores

Sales rooms
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).

310.1 Residential Group R

AMENDMENT
This section has been amended at the state or city level.
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I or when not within the scope of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings."

310.1.1 Detached One-, Two-, or Three-Family Dwellings

AMENDMENT
This section has been amended at the state or city level.
The "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings" shall apply to structures comprised exclusively of one-, two-, or three-family dwellings (having independent exits) and their accessory structures. If no residential department is certified in a jurisdiction, construction documents for structures comprised exclusively of one-, two-, or three-family dwellings are not required to be submitted for approval.

310.1.1.1 Five or Fewer Persons Receiving Care in a Single-Family Dwelling

AMENDMENT
This section has been amended at the state or city level.
A single-family dwelling with five or fewer persons, excluding staff, who reside in a supervised environment, receive care, and are capable of self-preservation with or without limited verbal or physical assistance is not classified as Group R and is within the scope of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings."

310.1.2 Group R With Both Shared Exits and Independent Exits

AMENDMENT
This section has been amended at the state or city level.
A building with both shared exits and independent exits shall be classified Group R-2, unless the shared exit is not a required exit, in which case, the building shall be classified Group R-3.

310.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
The following terms are defined in Chapter 2:

BOARDING HOUSE.

CARE FACILITY.

CONGREGATE LIVING FACILITIES.

CUSTODIAL CARE.

DORMITORY.

GROUP HOME.

GUEST ROOM.

LODGING HOUSE.

PERSONAL CARE SERVICE.

TRANSIENT.

310.3 Residential Group R-1

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Section 310.3.3, Residential Group R-1 occupancies containing sleeping units where the occupants are primarily transient in nature, including:

Boarding houses (transient) with more than 10 occupants

Congregate living facilities (transient) with more than 10 occupants

Hotels (transient)

Motels (transient)
SRO (Single room occupancy) facility (transient)
Transient lodging structures

310.3.1 Units Not Used Primarily as Permanent Residences

AMENDMENT
This section has been amended at the state or city level.
Group R-1 occupancies typically will include sleeping units but may also include dwelling units when those units are not used primarily as permanent residences.

310.3.2 Transient Lodging Structures

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Sections 310.3.2.1 or 310.3.2.2, a Group R-1 structure composed exclusively of a single dwelling unit with no more than twenty transient occupants may comply with the construction requirements of the "Residential Code of Ohio for One-, Two-, and Three- Family Dwellings" in lieu of the requirements of this code under the following conditions:
  1. The structure is located to maintain a minimum fire separation distance of thirty feet; and
  2. There are no more than two stories above grade plane, not including mezzanines/lofts that meet the area limitations of Section 505 of this code; and
  3. The maximum travel distance to an exit directly to the exterior at the level of exit discharge is 75 feet; and
  4. Egress from all habitable levels is by stair, ramp or an exit directly to the exterior in compliance with the Residential Code of Ohio; and
  5. For a structure with eleven to twenty occupants, at least two exits are provided from all habitable levels; and
  6. Portable fire extinguishers are installed in accordance with Section 906 of this code; and
  7. Artificial light is provided that is adequate to provide an average illumination of 1 foot-candle over the area of the room at a height of thirty inches above the floor level; and
  8. Accessibility requirements of Chapter 11 of this code shall apply.
Exception: If the owner provides documentation that the structure is not a place of public accommodation as defined in 28 C.F.R. 36.104;

Hotel licensure requirements of Chapter 3731 of the Revised Code may apply to the occupancy of a transient lodging structure but are outside the scope of this code.

310.3.2.1 Semi-Primitive Transient Lodging Structures No Greater Than 400 Sq. Ft. In Area

AMENDMENT
This section has been amended at the state or city level.
A Group R-1 structure that provides permanent provisions for sleeping only or sleeping with either sanitation or kitchen facilities, but not both, may comply with the applicable construction requirements of the "Residential Code of Ohio for One-, Two-, and Three- Family Dwellings" in lieu of the requirements of this code under the following conditions:
  1. The structure is located to maintain a minimum fire separation distance of thirty feet; and
  2. There is no more than one story, no basement, and no habitable loft; and
  3. There is no more than 400 sq. ft. in area in total; and
  4. There are no more than five occupants; and
  5. There is at least one means of egress complying with Section 311 of the Residential Code of Ohio; and
  6. Portable fire extinguishers are installed in accordance with Section 906 of this code; and
  7. Accessibility requirements of Chapter 11 of this code shall apply.
    Exception: If the owner provides documentation that the structure is not a place of public accommodation as defined in 28 C.F.R. 36.104;
Exceptions: Semi-primitive transient lodging structures shall not be required to comply with the following provisions of the Residential Code of Ohio:
  1. Chapter 11 if the semi-primitive structure does not contain conditioned space or has a peak design rate of energy usage of less than 3.4 BTU/h•ft2 or 1.0 watt/ft2 as described in the International Energy Conservation Code.
  2. Section 303.6 for exterior stairway illumination if no commercial power is available

310.3.2.2 Primitive or Semi-Primitive Transient Lodging Structures Greater Than 400 Sq. Ft. In Area

AMENDMENT
This section has been amended at the state or city level.
A Group R-1 structure, for not more than twenty transient occupants, that is greater than 400 sq. ft. in area, provides permanent provisions for sleeping only or sleeping with either sanitation or kitchen facilities, but not both, may comply with the applicable construction requirements of the "Residential Code of Ohio for One-, Two- , and Three-Family Dwellings" in lieu of the requirements of this code under the following conditions:
  1. The structure is located to maintain a minimum fire separation distance of thirty feet; and
  2. There are no more than two stories above grade plane, not including mezzanines/lofts that meet the area limitations of Section 505 of this code; and
  3. The maximum travel distance to an exit directly to the exterior at the level of exit discharge is 75 feet; and
  4. Egress from all habitable levels is by stair, ramp or an exit directly to the exterior in compliance with the Residential Code of Ohio; and
  5. For a structure with eleven to twenty occupants, at least two exits are provided from all habitable levels; and
  6. Portable fire extinguishers are installed in accordance with Section 906 of this code; and
  7. Accessibility requirements of Chapter 11 of this code shall apply.
    Exception: If the owner provides documentation that the structure is not a place of public accommodation as defined in 28 C.F.R. 36.104;
Exceptions: Primitive or semi-primitive transient lodging structures greater than 400 sq. ft. in area shall not be required to comply with the following provisions of the Residential Code of Ohio:
  1. Chapter 11 if the semi-primitive structure does not contain conditioned space or has a peak design rate of energy usage of less than 3.4 BTU/h•ft2 or 1.0 watt/ft2 as described in the International Energy Conservation Code.
  2. Section 303.6 for exterior stairway illumination if no commercial power is available and the structure is a single story with no basement or habitable loft.

310.3.3 Ten or Fewer Persons in a Boarding House or Congregate Living

AMENDMENT
This section has been amended at the state or city level.
A boarding house or congregate living building intended for transient occupancy for ten or fewer persons, shall be classified as Group R-2 or Group R-3 occupancies depending on exiting arrangements.

310.4 Residential Group R-2

AMENDMENT
This section has been amended at the state or city level.
Except as provided in Sections 310.4.1 through 310.4.4, Residential Group R-2 occupancies containing sleeping units or more than three dwelling units where the occupants are primarily permanent in nature and where the units share an exit, including:

Apartment houses

Boarding houses (nontransient) where occupants share an exit

Congregate living facilities (nontransient) where occupants share an exit

Convents

Dormitories

Fraternities and sororities

Hotels (nontransient)

Live/work units

Monasteries

Motels (nontransient)

SRO (Single room occupancy) facility (transient)

Vacation timeshare properties

310.4.1 Five or Fewer Persons Receiving Care

AMENDMENT
This section has been amended at the state or city level.
A care facility with shared exit for five or fewer persons receiving care shall be classified as Group R-2.

310.4.2 Dwelling Units in Mixed Occupancy Buildings

AMENDMENT
This section has been amended at the state or city level.
This group includes residential occupancies in buildings or structures of mixed use containing one or more dwelling units where the occupants are primarily permanent in nature in structures with shared exits.

310.4.3 Dwelling Units With a Shared Exit

AMENDMENT
This section has been amended at the state or city level.
This group includes buildings or structures containing two or three dwelling units where the occupants are primarily permanent in nature and where the dwelling units share an exit.

310.4.4 Sixteen or Fewer Persons in a Boarding House or Congregate Living

AMENDMENT
This section has been amended at the state or city level.
A boarding house or congregate living in a dwelling unit with an independent exit for sixteen or fewer persons shall be classified as Group R-3.

310.5 Residential Group R-3

AMENDMENT
This section has been amended at the state or city level.
Except as provided herein, Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, and where each dwelling unit has an independent exit including:

Boarding houses (nontransient) with 16 or fewer occupants per dwelling unit

Care facilities that provide accommodations for five or fewer persons receiving care

Congregate living facilities (nontransient) with 16 or fewer occupants per dwelling unit

Lodging houses with five or fewer guest rooms

Vacation timeshare properties

310.5.1 Care Facilities Within a Dwelling

AMENDMENT
This section has been amended at the state or city level.

310.5.1 Five or Fewer Persons Receiving Care Not in a Dwelling

AMENDMENT
This section has been amended at the state or city level.
A care facility with an independent exit for five or fewer persons receiving care shall be classified as Group R-3.

310.5.2 Lodging Houses

AMENDMENT
This section has been amended at the state or city level.

310.5.2 Five or Fewer Persons Receiving Care Within a Dwelling

AMENDMENT
This section has been amended at the state or city level.
A Group R-3 two- or three-family dwelling used exclusively as care facilities for an aggregate of five or fewer persons receiving care but are capable of self-preservation shall be permitted to comply with the construction requirements of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings. "

   A Group R-3 one-, two- or three-family dwelling used exclusively as care facilities for an aggregate of five or fewer persons receiving care and are incapable of self preservation shall be permitted to comply with the construction requirements of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings" provided an automatic sprinkler system is installed in all of the dwelling units in accordance with Sections 903.3.1.1, 903.3.1.2, 903.3.1.3 or Section 2904 of the "Residential Code of Ohio for One-, Two-, or Three-Family Dwellings."

310.5.3 Dwelling Units in Mixed Occupancy Buildings

AMENDMENT
This section has been amended at the state or city level.
This group includes residential occupancies in buildings or structures of mixed use containing one or more dwelling units where the occupants are primarily permanent in nature and where each dwelling unit has an independent exit.

310.5.4 Lodging Houses

AMENDMENT
This section has been amended at the state or city level.
A Group R-3 owner-occupied lodging house with five or fewer guest rooms may comply with the construction requirements of the "Residential Code of Ohio for One-, Two-, or Three- Family Dwellings."

310.5.5 Multi-Family Alternative Compliance

AMENDMENT
This section has been amended at the state or city level.
A Group R-3 building may use Chapters 2 to 10 and 44 of the "Residential Code of Ohio for One-, Two-, and Three-Family Dwellings" (RCO) in place of the requirements of this code for Group R-3 occupancies under the following conditions:
  1. The building is comprised exclusively of dwelling units; and
  2. The building is not used as a care facility; and
  3. The building is three stories or less in height; and
  4. Each dwelling unit in the building has an independent exit; and
  5. No more than one dwelling unit is allowed to be located above another dwelling unit; and
  6. Fire separation between units within a grouping of two units, including a unit located partially or totally above another unit, shall be in accordance with the RCO section 302.2. Fire separation between any grouping of two units and other adjacent units shall be in accordance with RCO sections 302.2 through 302.6; and
  7. Chapter 1 of the OBC shall be applicable for code administration purposes; and
  8. The edition of NFPA 70 listed in Chapter 35 of the OBC shall be applicable for electrical components, equipment, and system requirements; and
  9. The mechanical code shall apply for mechanical appliances, equipment, and system requirements, including fuel gas requirements; and
  10. The plumbing code shall apply for plumbing fixtures, equipment, water supply, and sanitary systems; and
  11. Chapter 13 of this code shall apply for energy conservation; and
  12. Except for Items 7 through 11 above, the edition of standards listed in Chapter 35 of this code shall be used when the same standard is referenced in Chapter 44 of the "Residential Code of Ohio for One-, Two-, and Three-Family Dwellings."

310.5.6 More Than Sixteen Occupants in a Boarding House or Congregate Living

AMENDMENT
This section has been amended at the state or city level.
A boarding house or congregate living building for more than sixteen persons shall be classified as Group R-2.

310.6 Residential Group R-4

AMENDMENT
This section has been amended at the state or city level.
Residential Group R-4 occupancy shall include buildings, structures or portions thereof for more than five but not more than 16 persons, excluding staff, who reside in a supervised residential environment and receive care. The persons receiving care are capable of self-preservation. This group shall include, but not be limited to, the following:

Alcohol and drug centers

Assisted living facilities

Congregate care facilities

Group homes

Halfway houses

Residential board and care facilities

Social rehabilitation facilities

Where Group R-4 design criteria is not provided in this code, the construction shall meet the requirements for Group R-3.

310.6.1 Occupancy Conditions

AMENDMENT
This section has been amended at the state or city level.
Buildings of Group R-4 shall be classified as one of the occupancy conditions specified in Section 310.6.1.1 or 310.6.1.2.

310.6.1 310.6.1.1 Condition 1

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which all persons receiving care, without any assistance, are capable of responding to an emergency situation to complete building evacuation.

310.6.2 310.6.1.2 Condition 2

AMENDMENT
This section has been amended at the state or city level.
This occupancy condition shall include buildings in which there are any persons receiving care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.
Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy.
A room or space used for storage purposes that is less than 100 square feet (9.3 m2) in area and accessory to another occupancy shall be classified as part of that occupancy. The aggregate area of such rooms or spaces shall not exceed the allowable area limits of Section 508.2.
Storage Group S-1 occupancies are buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following:

  • Aerosols, Levels 2 and 3
  • Aircraft hangar (storage and repair)
  • Bags: cloth, burlap and paper
  • Bamboos and rattan
  • Baskets
  • Belting: canvas and leather
  • Books and paper in rolls or packs
  • Boots and shoes
  • Buttons, including cloth covered, pearl or bone
  • Cardboard and cardboard boxes
  • Clothing, woolen wearing apparel
  • Cordage
  • Dry boat storage (indoor)
  • Furniture
  • Furs
  • Glues, mucilage, pastes and size
  • Grains
  • Horns and combs, other than celluloid
  • Leather

    Linoleum

    Lumber
  • Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 307.1(1) (see Section 406.8)
  • Photo engravings
  • Resilient flooring
  • Silks
  • Soaps
  • Sugar
  • Tires, bulk storage of
  • Tobacco, cigars, cigarettes and snuff
  • Upholstery and mattresses
  • Wax candles
Storage Group S-2 occupancies include, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:

  • Asbestos
  • Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
  • Cement in bags
  • Chalk and crayons
  • Dairy products in nonwaxed coated paper containers
  • Dry cell batteries
  • Electrical coils
  • Electrical motors
  • Empty cans
  • Food products
  • Foods in noncombustible containers
  • Fresh fruits and vegetables in nonplastic trays or containers
  • Frozen foods
  • Glass
  • Glass bottles, empty or filled with noncombustible liquids
  • Gypsum board
  • Inert pigments
  • Ivory
  • Meats
  • Metal cabinets
  • Metal desks with plastic tops and trim
  • Metal parts
  • Metals
  • Mirrors
  • Oil-filled and other types of distribution transformers
  • Parking garages, open or enclosed
  • Porcelain and pottery
  • Stoves
  • Talc and soapstones
  • Washers and dryers

312.1 General

AMENDMENT
This section has been amended at the state or city level.
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:

Agricultural buildings*

Barns*

Carports

Fences more than 6 feet (1829 mm) in height

Grain silos*

Greenhouses*

Livestock shelters*

Private garages

Retaining walls (see exceptions in Section 101.2)

Sheds*

Stables*

Tanks associated with building services equipment

Towers (see exceptions in Section 101.2)

* Not used for agricultural purposes as defined in Section 3781.06 of the Revised Code.