Chapter 27 Plumbing Fixtures

AMENDMENT
This section has been amended at the state or city level.
The text of this chapter is extracted from the 2018 edition of the North Carolina Plumbing Code and has been modified where necessary to conform to the scope of application of the North Carolina Residential Code for One- and Two-Family Dwellings. The section numbers appearing in parentheses after each section number are the section numbers of the corresponding text in the North Carolina Plumbing Code.

P2701.1 (402.1) Quality of Fixtures

AMENDMENT
This section has been amended at the state or city level.
Plumbing fixtures, faucets and fixture fittings shall have smooth impervious surfaces, shall be free from defects, shall not have concealed fouling surfaces, and shall conform to the standards indicated in Table P2701.1 and elsewhere in this code. All porcelain enameled surfaces on plumbing fixtures shall be acid resistant.

TABLE P2701.1
PLUMBING FIXTURES, FAUCETS AND FIXTURE FITTINGS
MATERIAL STANDARD
Air gap fittings for use with plumbing fixtures, appliances and appurtenances ASME A 112.1.3
Bathtub/whirlpool pressure-sealed doors ASME A 112.19.15
Diverters for faucets with hose spray, anti-syphon type, residential application ASTM A 112.18.1/CSA B125.1
Enameled cast-iron plumbing fixtures ASME A 112.19.1M/CSA B45.2
Floor drains ASME A 112.6.3
Floor-affixed supports for off-the-floor plumbing fixtures for public use ASME A 112.6.1M
Framing-affixed supports for off-the-floor water closets with concealed tanks ASME A 112.6.2
Hose connection vacuum breaker ASSE 1052
Hot water dispensers, household storage type, electrical ASSE 1023
Household disposers ASSE 1008
Hydraulic performance for water closets and urinals ASME A 112.19.2/CSA B45.1
Individual automatic compensating valves for individual fixture fittings ASME A 112.18.1/CSA B125.1
Individual shower control valves anti-scald ASSE 1016/ASME A 112.1016/CSA B125.16
Macerating toilet systems and related components ASME A 112.3.4/CSA B45.9
Nonvitreous ceramic plumbing fixtures ASME A 112.19.2/CSA B45.1
Plastic bathtub units CSA B45.5/IAPMO Z124, ASME A112.19.2/CSA B45.1
Plastic lavatories CSA B45.5/IAPMO Z124
Plastic shower receptors and shower stall CSA B45.5/IAPMO Z124
Plastic sinks CSA B45.5/IAPMO Z124
Plastic water closet bowls and tanks CSA B45.5/IAPMO Z124
Plumbing fixture fittings ASME A 112.18.1/CSA B125.1
Plumbing fixture waste fittings ASME A 112.18.2/CSA B125.2, ASTM F 409
Porcelain-enameled formed steel plumbing fixtures ASME A 112.19.1/CSA B45.2
Pressurized flushing devices for plumbing fixtures ASSE 1037, CSA B125.3
Specification for copper sheet and strip for building construction ASTM B 370
Stainless steel plumbing fixtures ASME A 112.19.3/CSA B45.4
Suction fittings for use in whirlpool bathtub appliances ASME A 112.19.7 /CSA B45.10
Temperature-actuated, flow reduction valves to individual fixture fittings ASSE 1062
Thermoplastic accessible and replaceable plastic tube and tubular fittings ASTM F 409
Trench drains ASME A 112.6.3
Trim for water closet bowls, tanks and urinals ASME A 112.19.5/CSA B45.15
Vacuum breaker wall hydrant-frost-resistant, automatic-draining type ASSE 1019
Vitreous china plumbing fixtures ASME A 112.19.2/CSA B45.1
Wall-mounted and pedestal-mounted, adjustable and pivoting lavatory and sink
carrier systems
ASME A 112.19.12
Water closet flush tank fill valves ASSE 1002, CSA B125.3
Whirlpool bathtub appliances ASME A 112.19.7 /CSA B45.10

P2702.1 (802.3.3) Plumbing Fixtures

AMENDMENT
This section has been amended at the state or city level.
Plumbing fixtures, other than water closets, shall be provided with approved strainers.
Waste fittings shall conform to ASME A112.18.2/CSA B125.2, ASTM F 409 or shall be made from pipe and pipe fittings complying with any of the standards indicated in Tables P3002.1(1) and P3002.3.
Plastic tubular fittings shall conform to ASTM F 409 as indicated in Table P2701.1.

P2702.4 (405.4.3) Carriers for Wall-Hung Water Closets

AMENDMENT
This section has been amended at the state or city level.
Wall-hung water closet bowls shall be supported by a concealed metal carrier that is attached to the building structural members so that strain is not transmitted to the closet connector or any other part of the plumbing system. Carriers for wall-hung water closets shall conform to ASME A112.6.1 or ASME A112.6.2.
Fixture tail pieces shall be not less than 11/2 inches (38 mm) in diameter for sinks, dishwashers, laundry tubs, bathtubs and similar fixtures, and not less than 11/4 inches (32 mm) in diameter for bidets, lavatories and similar fixtures.

P2704.1 (405.8) General

AMENDMENT
This section has been amended at the state or city level.
Slip joints shall be made with an approved elastomeric gasket and shall be installed only on the trap outlet, trap inlet and within the trap seal. Fixtures with concealed slip-joint connections shall be provided with an access panel or utility space not less than 12 inches (305 mm) in its smallest dimension or other approved arrangement so as to provide access to the slip connections for inspection and repair. Where such access cannot be provided, access doors shall not be required, provided that all joints are soldered, solvent cemented or screwed to form a solid connection.

P2705.1 General

AMENDMENT
This section has been amended at the state or city level.
The installation of fixtures shall conform to the following:
  1. Floor-outlet or floor-mounted fixtures shall be secured to the drainage connection and to the floor, where so designed, by screws, bolts, washers, nuts and similar fasteners of copper, copper alloy or other corrosion-resistant material.
  2. Wall-hung fixtures shall be rigidly supported so that strain is not transmitted to the plumbing system.
  3. Where fixtures come in contact with walls and floors, the contact area shall be water tight.
  4. Plumbing fixtures shall be usable.
  5. See Figure R307.1 for minimum fixture clearances.
  6. The location of piping, fixtures or equipment shall not interfere with the operation of windows or doors.
  7. In flood hazard areas as established by Table R301.2(1), plumbing fixtures shall be located or installed in accordance with Section R322.1.6.
  8. Integral fixture-fitting mounting surfaces on manufactured plumbing fixtures or plumbing fixtures constructed on site, shall meet the design requirements of ASME A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4.
  9. Floor flanges for water closets or similar fixtures shall be not less than 0.125 inch (3.2 mm) thick for brass, 0.25 inch (6.4 mm) thick for plastic and 0.25 inch (6.4 mm) thick and not less than a 2-inch (51 mm) caulking depth for cast iron or galvanized malleable iron. Floor flanges of hard lead shall weigh not less than 1 pound, 9 ounces (0.7 kg) and shall be composed of lead alloy with not less than 7.75-percent antimony by weight. Flanges shall be secured to the building structure with corrosion-resistant screws or bolts.
  10. Where any fixture is provided with an overflow, the waste shall be designed and installed so that standing water in the fixture will not rise in the overflow when the stopper is closed, and no water will remain in the overflow when the fixture is empty. The overflow from any fixture shall discharge into the drainage system on the inlet or fixture side of the trap.

    Exception: The overflow from a flush tank serving a water closet or urinal shall discharge into the fixture served.
  11. Fixtures shall be set level and in proper alignment with reference to adjacent walls.

P2706.1 General

AMENDMENT
This section has been amended at the state or city level.
Every waste receptor shall be of an approved type. A removable strainer or basket shall cover the waste outlet of waste receptors. Waste receptors shall be installed in ventilated spaces. Waste receptors shall not be installed in plenums, attics, crawl spaces or interstitial spaces above ceilings and below floors. Waste receptors shall be readily accessible.

Exception: Hub drains.

P2706.1.1 Hub Drains

AMENDMENT
This section has been amended at the state or city level.
Hub drains shall be in the form of a hub or a pipe that extends not less than 1 inch (25 mm) above a water-impervious floor and shall not be required to have a strainer.

P2706.1.2 Standpipes

AMENDMENT
This section has been amended at the state or city level.
Standpipes shall be individually trapped. Access shall be provided to standpipes and drains for rodding. Standpipes shall be 2 inches (51 mm) in diameter and not less than 18 inches (762 mm) or more than 48 inches (1219 mm) in height as measured from the crown weir. The standpipe shall extend 34 inches (864 mm) minimum above the base of the clothes washer unless recommended otherwise by the manufacturer. The connection of a laundry tray waste line may be made into a standpipe for the automatic clothes-washer drain. The standpipe shall extend above the flood level rim of the laundry tray. The outlet of the laundry tray shall be a maximum horizontal distance of 30 inches (762 mm) from the standpipe trap.

P2706.1.2.1 Laundry Tray Connection to Standpipe

AMENDMENT
This section has been amended at the state or city level.
Plumbing fixtures that are used for washing or bathing shall not be used to receive the discharge of indirect waste piping.

Exceptions:
  1. A kitchen sink trap is acceptable for use as a receptor for a dishwasher.
  2. A laundry tray is acceptable for use as a receptor for a clothes washing machine.

Section P2707 Directional Fittings

AMENDMENT
This section has been amended at the state or city level.

P2707.1 Directional Fitting Required

AMENDMENT
This section has been amended at the state or city level.

P2708.1 General

AMENDMENT
This section has been amended at the state or city level.
Shower compartments shall have not less than 900 square inches (0.6 m2) of interior cross-sectional area. Shower compartments shall be not less than 30 inches (762 mm) in minimum dimension measured from the finished interior dimension of the shower compartment, exclusive of fixture valves, shower heads, soap dishes, and safety grab bars or rails. The minimum required area and dimension shall be measured from the finished interior dimension at a height equal to the top of the threshold and at a point tangent to its centerline and shall be continued to a height of not less than 70 inches (1778 mm) above the shower drain outlet. Hinged shower doors shall open outward. The wall area above built-in tubs having installed shower heads and in shower compartments shall be constructed in accordance with Section R702.4. Such walls shall form a water-tight joint with each other and with either the tub, receptor or shower floor.

Exceptions:
  1. Fold-down seats shall be permitted in the shower, provided the required 900-square-inch (0.6 m2) dimension is maintained when the seat is in the folded-up position.
  2. Shower compartments having not less than 25 inches (635 mm) in minimum dimension measured from the finished interior dimension of the compartment provided that the shower compartment has a cross-sectional area of not less than 1,300 square inches (0.838 m2).
  3. Shower compartments with prefabricated receptors conforming to the standards listed in Table P2708.1 (417.4).
  4. Where load-bearing, bonded, waterproof membranes meeting ANSI A118.10 are used, integrated bonding flange drains shall be approved. Clamping devices and weep holes are not required where shower drains include an integrated bonding flange. Manufacturer's installation instructions shall be followed to achieve a watertight seal between the bonded waterproof membrane and the integrated bonding flange drain. Integrated bonding flange drains shall conform to ASME A112.6.3, ASME A112.18.2/CSA B125.2, or CSA B79.
TABLE P2708.1 (417.4)
PREFABRICATED SHOWER RECEPTOR STANDARDS MATERIALS STANDARDS
Plastic shower receptors and
shower stalls
ANSI Z124
Shower pans, nonmetallic ASTM D4551
The shower compartment access and egress opening shall have a clear and unobstructed finished width of not less than 22 inches (559 mm).

P2708.2 (417.3) Shower Drain

AMENDMENT
This section has been amended at the state or city level.
Shower drains shall have an outlet size of not less than 2 inches [51 mm] in diameter, and for other than waste outlets in bathtubs, shall have removable strainers not less than 3 inches (76 mm) in diameter with strainer openings not less than 1/4 inch (6.4 mm) in least dimension. Where each shower space is not provided with an individual waste outlet, the waste outlet shall be located and the floor pitched so that waste from one shower does not flow over the floor area serving another shower. Waste outlets shall be fastened to the waste pipe in an approved manner.

Exception: Retaining pre-existing 11/2 inch (38 mm) in diameter waste outlets shall be permitted when removing an existing bathtub and installing a shower in its place.

P2708.3 (417.2) Water Supply Riser

AMENDMENT
This section has been amended at the state or city level.
Water supply risers from the shower valve to the shower head outlet, whether exposed or concealed, shall be attached to the structure using support devices designed for use with the specific piping material or fittings anchored with corrosion-resistant screws of a minimum nominal length of 3/4 inch (19 mm).

P2708.4 (424.3) Shower Control Valves

AMENDMENT
This section has been amended at the state or city level.
Individual shower and tub/shower combination valves shall be equipped with control valves of the pressure-balance, thermostatic-mixing or combination pressure-balance/thermostatic-mixing valve types with a high limit stop in accordance with ASSE 1016/ASME A112.1016/CSA B125.16. The high limit stop shall be set to limit the water temperature to not greater than 120°F (49°C), which shall be field adjusted in accordance with the manufacturer's instructions. In-line thermostatic valves shall not be used for compliance with this section. Scald preventative valves are not required in dwelling units with individual water heaters set at 120°F (49°C).
Hand-held showers shall conform to ASME A112.18.1/CSA B125.1. Hand-held showers shall provide backflow protection in accordance with ASME A112.18.1/CSA B125.1 or shall be protected against backflow by a device complying with ASME A112.18.3.
Where a shower receptor has a finished curb threshold, it shall be not less than 1 inch (25 mm) below the sides and back of the receptor. The curb shall be not less than 2 inches (51 mm) and not more than 9 inches (229 mm) deep when measured from the top of the curb to the top of the drain. The finished floor shall slope uniformly toward the drain not less than 1/4 unit vertical in 12 units horizontal (2-percent slope) nor more than 1/2 unit vertical per 12 units horizontal (4-percent slope) and floor drains shall be flanged to provide a water-tight joint in the floor.

P2709.2 (417.5.2) Lining Required

AMENDMENT
This section has been amended at the state or city level.
The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with one of the following materials:
  1. Sheet lead. Sheet lead shall weigh not less than 4 pounds per square foot (19.5 kg/m2) and shall be coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet lead shall be joined by burning.
  2. Sheet copper. Sheet copper shall conform to ASTM B152 and shall weigh not less than 12 ounces per square foot (3.7 kg/m2). The copper sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or an equivalent. Sheet copper shall be joined by brazing or soldering.
  3. Plastic liner material shall be a minimum of 0.040 inch (1.02 mm) thick and shall comply with ASTM D4068 or ASTM D4551.
  4. Hot mopping in accordance with Section P2709.2.3.
  5. Sheet-applied load-bearing, bonded waterproof membranes that comply with ANSI A118.10.
     The lining material shall extend not less than 2 inches (51 mm) beyond or around the rough jambs and not less than 2 inches (51 mm) above finished thresholds. Sheet-applied load bearing, bonded waterproof membranes shall be applied in accordance with the manufacturer's instructions.

P2709.2.1 (417.5.2.1) PVC Sheets

AMENDMENT
This section has been amended at the state or city level.
Plasticized polyvinyl chloride (PVC) sheet shall be a minimum of 0.040 inch (1.02 mm) thick and shall meet the requirements of ASTM D4551. Sheets shall be joined by solvent welding in accordance with the manufacturer's instructions.

P2709.2.2 (417.5.2.2) Chlorinated Polyethylene (CPE) Sheets

AMENDMENT
This section has been amended at the state or city level.
Nonplasticized chlorinated polyethylene sheet shall be a minimum of 0.040 inch (1.02 mm) thick and shall meet the requirements of ASTM D4068. The liner shall be joined in accordance with the manufacturer's instructions.
Shower receptors lined by hot mopping shall be built-up with not less than three layers of standard grade Type 15 asphalt-impregnated roofing felt. The bottom layer shall be fitted to the formed subbase and each succeeding layer thoroughly hot-mopped to that below. Corners shall be carefully fitted and shall be made strong and water tight by folding or lapping, and each corner shall be reinforced with suitable webbing hot-mopped in place. Folds, laps and reinforcing webbing shall extend not less than 4 inches (102 mm) in all directions from the corner and webbing shall be of approved type and mesh, producing a tensile strength of not less than 50 pounds per inch (893 kg/m) in either direction.
Liquid-type, trowel-applied, load-bearing, bonded waterproof materials shall meet the requirements of ANSI A118.10 and shall be applied in accordance with the manufacturer's instructions.

P2709.3 Installation

AMENDMENT
This section has been amended at the state or city level.
Lining materials shall be sloped a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) to weep holes in the subdrain by means of a smooth, solidly formed subbase, shall be properly recessed and fastened to approved backing so as not to occupy the space required for the wall covering, and shall not be nailed or perforated at any point less than 1 inch (25.4 mm) above the finished threshold.

P2709.3.1 Materials

AMENDMENT
This section has been amended at the state or city level.
Lead and copper linings shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or its equivalent. Sheet lead liners shall weigh not less than 4 pounds per square foot (19.5 kg/m2) and shall be coated with an asphalt paint or other approved coating. Sheet copper liners shall weigh not less than 12 ounces per square foot (3.7 kg/m2). Joints in lead and copper pans or liners shall be burned or silver brazed, respectively. Joints in plastic liner materials shall be joined in accordance with the manufacturer's instructions.
An approved flanged drain shall be installed with shower subpans or linings. The flange shall be placed flush with the subbase and be equipped with a clamping ring or other device to make a water-tight connection between the lining and the drain. The flange shall have weep holes into the drain.
Walls in shower compartments and walls above bathtubs that have a wall-mounted showerhead shall be finished in accordance with Section R307.2.
Lavatories shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
Cultured marble vanity tops with an integral lavatory shall conform to CSA B45.5/IAPMO Z124.
Lavatories shall have waste outlets not less than 11/4 inch (32 mm) in diameter. A strainer, pop-up stopper, crossbar or other device shall be provided to restrict the clear opening of the waste outlet.
Movable lavatory systems shall comply with ASME A112.19.12.
Water closets shall conform to the water consumption requirements of Section P2903.2 and shall conform to ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124. Water closets shall conform to the hydraulic performance requirements of ASME A112.19.2/CSA B45.1. Water closet tanks shall conform to ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124. Water closets that have an invisible seal and unventilated space or walls that are not thoroughly washed at each discharge shall be prohibited. Water closets that allow backflow of the contents of the bowl into the flush tank shall be prohibited. Water closets equipped with a dual flushing device shall comply with ASME A112.19.14.
Water closets shall be provided with a flush tank, flushometer tank or flushometer valve designed and installed to supply water in sufficient quantity and flow to flush the contents of the fixture, to cleanse the fixture and refill the fixture trap in accordance with ASME A112.19.2/CSA B45.1.
An adequate quantity of water shall be provided to flush and clean the fixture served. The water supply to flushing devices equipped for manual flushing shall be controlled by a float valve or other automatic device designed to refill the tank after each discharge and to completely shut off the water flow to the tank when the tank is filled to operational capacity. Provision shall be made to automatically supply water to the fixture so as to refill the trap after each flushing.
Flush valve seats in tanks for flushing water closets shall be not less than 1 inch (25 mm) above the flood-level rim of the bowl connected thereto, except an approved water closet and flush tank combination designed so that when the tank is flushed and the fixture is clogged or partially clogged, the flush valve will close tightly so that water will not spill continuously over the rim of the bowl or backflow from the bowl to the tank.
Flush tanks shall be provided with overflows discharging to the water closet connected thereto and such overflow shall be of sufficient size to prevent flooding the tank at the maximum rate at which the tanks are supplied with water according to the manufacturer's design conditions.
Parts in a flush tank shall be accessible for repair and replacement.
Water closets shall be equipped with seats of smooth, nonabsorbent material and shall be properly sized for the water closet bowl type.
Sheet copper used for flush tank linings shall have a weight of not less than 10 ounces per square foot (3 kg/m2).
Electro-hydraulic water closets shall conform to ASME A112.19.2/CSA B45.1.

P2712.10 (420.4) Water Closet Connections

AMENDMENT
This section has been amended at the state or city level.
A 4-inch by 3-inch (102 mm by 76 mm) closet bend shall be acceptable. Where a 3-inch (76 mm) bend is utilized on water closets, a 4-inch by 3-inch (102 mm by 76 mm) flange shall be installed to receive the fixture horn.
Bathtubs shall be equipped with a waste outlet and an overflow outlet. The outlets shall be connected to waste tubing or piping not less than 11/2 inches (38 mm) in diameter. The waste outlet shall be equipped with a water-tight stopper.
Doors within a bathtub enclosure shall conform to ASME A112.19.15.
Hot water supplied to bathtubs and whirlpool bathtubs shall be limited to a temperature of not greater than 120°F (49°C) by a water-temperature limiting device that conforms to ASSE 1070 or CSA B125.3, except where such protection is otherwise provided by a combination tub/shower valve in accordance with Section P2708.4.

P2713.4 (407.1) Approval

AMENDMENT
This section has been amended at the state or city level.
Bathtubs shall conform to ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/ CSA B45.4 or CSA B45.5/IAPMO Z124.
Sinks shall be provided with waste outlets not less than 11/2 inches (38 mm) in diameter. A strainer, crossbar or other device shall be provided to restrict the clear opening of the waste outlet.
Movable sink systems shall comply with ASME A112.19.12.
Each compartment of a laundry tub shall be provided with a waste outlet not less than 11/2 inches (38 mm) in diameter. A strainer or crossbar shall restrict the clear opening of the waste outlet.
Food-waste disposers shall be connected to a drain of not less than 11/2 inches (38 mm) in diameter.
A sink equipped with a food-waste disposer shall be provided with a faucet.
The water supply to a dishwasher shall be protected against backflow by an air gap complying with ASME A112.1.3 or A112.1.2 that is installed integrally within the machine or a backflow preventer in accordance with Section P2902.

P2717.2 Sink and Dishwasher

AMENDMENT
This section has been amended at the state or city level.
The combined discharge from a dishwasher and a one- or two-compartment sink, with or without a food-waste disposer, shall be served by a trap of not less than 11/2 inches (38 mm) in outside diameter. The dishwasher discharge pipe or tubing shall rise to the underside of the counter and shall be securely fastened to the underside of the sink rim or counter before connecting to the head of the food-waste disposer or to a wye fitting in the sink tailpiece.

P2718.1 (406.2) Waste Connection

AMENDMENT
This section has been amended at the state or city level.
The waste from an automatic clothes washer shall connect to a vertical drain of not less than 2 inches (51 mm) in diameter, or a horizontal drain of not less than 3 inches (76 mm) in diameter. The 2-inch (51 mm) trap in the waste connection may be used as a cleanout for both the 2-inch (51 mm) and the 3-inch (76 mm) drains. In retrofit or remodel work automatic domestic clothes washers shall be permitted to drain to a laundry sink. Automatic clothes washers that discharge by gravity shall be permitted to drain to a waste receptor or an approved trench drain.

P2718.2 (406.1) Water Connection

AMENDMENT
This section has been amended at the state or city level.
The water supply to an automatic clothes washer shall be protected against backflow by an air gap that is integral with the machine or a backflow preventer shall be installed in accordance with Section 608. Air gaps shall comply with ASME A112.1.2 or A112.1.3.
Floor drains shall have waste outlets not less than 2 inches (51 mm) in diameter and a removable strainer. Floor drains shall be constructed so that the drain can be cleaned. Access shall be provided to the drain inlet. Floor drains shall not be located under or have their access restricted by permanently installed appliances.

P2719.2 (412.5) Location

AMENDMENT
This section has been amended at the state or city level.
Floor drains shall be located to drain the entire floor area.

P2720.1 Access to Pump

AMENDMENT
This section has been amended at the state or city level.
Access shall be provided to circulation pumps in accordance with the fixture or pump manufacturer's installation instructions. Where the manufacturer's instructions do not specify the location and minimum size of field-fabricated access openings, an opening of not less than 12-inches by 12-inches (305 mm by 305 mm) shall be installed for access to the circulation pump. Where pumps are located more than 2 feet (610 mm) from the access opening, an opening of not less than 18 inches by 18 inches (457 mm by 457 mm) shall be installed. A door or panel shall be permitted to close the opening. The access opening shall be unobstructed and be of the size necessary to permit the removal and replacement of the circulation pump. A minimum clearance of 21 inches (533 mm) is required in front of the access door. Removal of a toilet cannot be used to obtain the required clearance.

P2720.2 Piping Drainage

AMENDMENT
This section has been amended at the state or city level.
The circulation pump shall be accessibly located above the crown weir of the trap. The pump drain and circulation piping shall be sloped to drain the water in the volute and the circulation piping when the whirlpool bathtub is empty.
Leak testing and pump operation shall be performed in accordance with the manufacturer's instructions.
The product shall be installed in accordance with the manufacturer's instructions.

P2720.5 (421.4) Suction Fittings

AMENDMENT
This section has been amended at the state or city level.
Suction fittings for whirlpool bathtubs shall comply with ASME A112.19.7/CSA B45.10.
The bidet shall be equipped with either an air-gap-type or vacuum-breaker-type fixture supply fitting.
The discharge water temperature from a bidet fitting shall be limited to not greater than 110°F (43°C) by a water-temperature-limiting device conforming to ASSE 1070 or CSA B125.3.

P2721.3 (408.1) Approval

AMENDMENT
This section has been amended at the state or city level.
Bidets shall conform to ASME A112.19.2/ CSA B45.1.

P2722.1 (424.1) General

AMENDMENT
This section has been amended at the state or city level.
Fixture supply valves and faucets shall comply with ASME A112.18.1/CSA B125.1 as indicated in Table P2701.1. Faucets and fixture fittings that supply drinking water for human ingestion shall conform to the requirements of NSF 61, Section 9. Flexible water connectors shall conform to the requirements of Section P2906.7.

P2722.2 (607.5) Hot Water

AMENDMENT
This section has been amended at the state or city level.
Fixture fittings supplied with both hot and cold water shall be installed and adjusted so that the left-hand side of the water temperature control represents the flow of hot water when facing the outlet.

Exception: Shower and tub/shower mixing valves conforming to ASSE 1016/ASME A112.1016/CSA B125.16, where the water temperature control corresponds to the markings on the device.

P2722.3 (424.6) Hose-Connected Outlets

AMENDMENT
This section has been amended at the state or city level.
Faucets and fixture fittings with hose-connected outlets shall conform to ASME A112.18.3 or ASME A112.18.1/CSA B125.1.

P2722.4 (604.11) Individual Pressure-Balancing In-Line Valves for Individual Fixture Fittings

AMENDMENT
This section has been amended at the state or city level.
Individual pressure-balancing in-line valves for individual fixture fittings shall comply with ASSE 1066. Such valves shall be installed in an accessible location and shall not be used as a substitute for the balanced pressure, thermostatic or combination shower valves required in Section P2708.4.

P2722.5 (424.9) Water Closet Personal Hygiene Devices

AMENDMENT
This section has been amended at the state or city level.
Personal hygiene devices integral to water closets or water closet seats shall conform to ASME A112.4.2.

P2723.1 General

AMENDMENT
This section has been amended at the state or city level.
Macerating toilet systems shall comply with ASME A112.3.4/CSA B45.9 and shall be installed in accordance with manufacturer's instructions.
The size of the drain from the macerating toilet system shall be not less than 3/4 inch (19 mm) in diameter.
Temperature-actuated mixing valves, which are installed to reduce water temperatures to defined limits, shall comply with ASSE 1017. Such valves shall be installed at the hot water source.
Temperature-actuated, flow-reduction devices, where installed for individual fixture fittings, shall conform to ASSE 1062. Such valves shall not be used as a substitute for the balanced pressure, thermostatic or combination shower valves required for showers in Section P2708.4.
Materials, design, construction and performance of nonliquid saturated treatment systems shall comply with NSF 41.