CODES

ADOPTS WITH AMENDMENTS:

International Residential Code 2009 (IRC 2009)

Chapter 1 Scope and Administration

Chapter 2 Definitions

Chapter 3 Building Planning

Chapter 4 Foundations

Chapter 5 Floors

Chapter 6 Wall Construction

Chapter 7 Wall Covering

Chapter 8 Roof-Ceiling Construction

Chapter 9 Roof Assemblies

Chapter 10 Chimneys and Fireplaces

Chapter 11 Energy Efficiency

Chapter 12 Mechanical Administration

Chapter 12 Mechanical Administration

Chapter 13 General Mechanical System Requirements

Chapter 13 General Mechanical System Requirements

Chapter 14 Heating and Cooling Equipment

Chapter 14 Heating and Cooling Equipment

Chapter 15 Exhaust Systems

Chapter 15 Exhaust Systems

Chapter 16 Duct Systems

Chapter 16 Duct Systems

Chapter 17 Combustion Air

Chapter 17 Combustion Air

Chapter 18 Chimneys and Vents

Chapter 18 Chimneys and Vents

Chapter 19 Special Fuel-Burning Equipment

Chapter 19 Special Fuel-Burning Equipment

Chapter 20 Boilers and Water Heaters

Chapter 20 Boilers and Water Heaters

Chapter 21 Hydronic Piping

Chapter 21 Hydronic Piping

Chapter 22 Special Piping and Storage Systems

Chapter 22 Special Piping and Storage Systems

Chapter 23 Solar Systems

Chapter 23 Solar Systems

Chapter 24 Fuel Gas

Chapter 24 Fuel Gas

Chapter 25 Plumbing Administration

Chapter 25 Plumbing Administration

Chapter 26 General Plumbing Requirements

Chapter 26 General Plumbing Requirements

Chapter 27 Plumbing Fixtures

Chapter 27 Plumbing Fixtures

Chapter 28 Water Heaters

Chapter 28 Water Heaters

Chapter 29 Water Supply and Distribution

Chapter 29 Water Supply and Distribution

Chapter 30 Sanitary Drainage

Chapter 30 Sanitary Drainage

Chapter 31 Vents

Chapter 31 Vents

Chapter 32 Traps

Chapter 32 Traps

Chapter 33 Storm Drainage

Chapter 33 Storm Drainage

Chapter 34 General Requirements

Chapter 34 General Requirements

Chapter 35 Electrical Definitions

Chapter 35 Electrical Definitions

Chapter 36 Services

Chapter 36 Services

Chapter 37 Branch Circuit and Feeder Requirements

Chapter 37 Branch Circuit and Feeder Requirements

Chapter 38 Wiring Methods

Chapter 38 Wiring Methods

Chapter 39 Power and Lighting Distribution

Chapter 39 Power and Lighting Distribution

Chapter 40 Devices and Luminaires

Chapter 40 Devices and Luminaires

Chapter 41 Appliance Installation

Chapter 41 Appliance Installation

Chapter 42 Swimming Pools

Chapter 42 Swimming Pools

Chapter 43 Class 2 Remote-Control, Signaling and Power-Limited Circuits

Chapter 43 Class 2 Remote-Control, Signaling and Power-Limited Circuits

Chapter 44 Referenced Standards

Chapter 45 HIGH WIND ZONES

Chapter 46 COASTAL AND FLOOD PLAIN CONSTRUCTION STANDARDS

Appendix A Sizing and Capacities of Gas Piping

Appendix B Sizing of Venting Systems Serving Appliances Equipped With Draft Hoods, Category I Appliances, and Appliances Listed for Use With Type B Vents

Appendix C Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems

Appendix D Recommended Procedure for Safety Inspection of an Existing Appliance Installation

Appendix E Manufactured Housing Used as Dwellings

Appendix F Radon Control Methods

Appendix G Swimming Pools, Spas and Hot Tubs

Appendix H Patio Covers

Appendix I Private Sewage Disposal

Appendix J Existing Buildings and Structures

Appendix K Sound Transmission

Appendix L Permit Fees

Appendix M Home Day Care - R-3 Occupancy

Appendix M WOOD DECKS

Appendix N Venting Methods

Appendix N BASIC LOAD ESTIMATING

Appendix O Gray Water Recycling Systems

Appendix O FOAM PLASTIC DIAGRAMS

Appendix P Sizing of Water Piping System

Appendix P DWELLING UNIT FIRE SPRINKLER SYSTEMS

Appendix Q ICC International Residential Code Electrical Provisions/National Electrical Code Crossreference

Appendix Q DISCONTINUOUS FOOTING DETAIL FOR GARAGE OR PORCH WALLS FOUNDATION WALL EXTENSION DETAIL

Chapter 15 Exhaust Systems

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

The air removed by every mechanical exhaust system shall be discharged to the outdoors. Air shall not be exhausted into an attic, soffit, ridge vent or crawl space.

Exception: Whole-house ventilation-type attic fans that discharge into the attic space of dwelling units having private attics shall be permitted.

Clothes dryers shall be exhausted in accordance with the manufacturer’s instructions.

Dryer exhaust systems shall be independent of all other systems and shall convey the moisture to the outdoors.

Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers.

Exhaust ducts shall terminate on the outside of the building. Exhaust duct terminations shall be in accordance with the dryer manufacturer’s installation instructions. If the manufacturer’s instructions do not specify a termination location, the exhaust duct shall terminate not less than 3 feet (914 mm) in any direction from openings into buildings. Exhaust duct terminations shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination.
Dryer exhaust ducts shall conform to the requirements of Sections M1502.4.1 through M1502.4.6.
Exhaust ducts shall have a smooth interior finish and shall be constructed of metal a minimum 0.016-inch (0.4 mm) thick. The exhaust duct size shall be 4 inches (102 mm) nominal in diameter.
Exhaust ducts shall be supported at 4 foot (1219 mm) intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or similar fasteners that protrude into the inside of the duct.
Transition ducts used to connect the dryer to the exhaust duct system shall be a single length that is listed and labeled in accordance with UL 2158A. Transition ducts shall be a maximum of 8 feet (2438 mm) in length. Transition ducts shall not be concealed within construction.
The maximum allowable exhaust duct length shall be determined by one of the methods specified in Section M1502.4.4.1 or M1502.4.4.2.

The maximum length of the exhaust duct shall be 25 feet (7620 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance with Table M1502.4.4.1.

TABLE M1502.4.4.1
DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH

DRYER EXHAUST DUCT FITTING TYPE

EQUIVALENT LENGTH

4 inch radius mitered 45 degree elbow

2 feet 6 inches

4 inch radius mitered 90 degree elbow

5 feet

6 inch radius smooth 45 degree elbow

1 foot

6 inch radius smooth 90 degree elbow

1 foot 9 inches

8 inch radius smooth 45 degree elbow

1 foot

8 inch radius smooth 90 degree elbow

1 foot 7 inches

10 inch radius smooth 45 degree elbow

9 inches

10 inch radius smooth 90 degree elbow

1 foot 6 inches

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.

The size and maximum length of the exhaust duct shall be determined by the dryer manufacturer’s installation instructions. The code official shall be provided with a copy of the installation instructions for the make and model of the dryer at the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table M1502.4.4.1 shall be used.
Where the exhaust duct is concealed within the building construction, the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection.

Where space for a clothes dryer is provided, an exhaust duct system shall be installed. Where the clothes dryer is not installed at the time of occupancy the exhaust duct shall be capped or plugged in the space in which it originates and identified and marked “future use.”

Exception: Where a listed condensing clothes dryer is installed prior to occupancy of the structure.

Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than 11/4 inches (32 mm) between the duct and the finished face of the framing member. Protective shield plates shall be constructed of steel, shall have a minimum thickness of 0.062-inch (1.6 mm) and shall extend a minimum of 2 inches (51 mm) above sole plates and below top plates.

Range hoods shall discharge to the outdoors through a single-wall duct. The duct serving the hood shall have a smooth interior surface, shall be air tight and shall be equipped with a backdraft damper. Ducts serving range hoods shall not terminate in an attic or crawl space or areas inside the building.

Exception: Where installed in accordance with the manufacturer’s installation instructions, and where mechanical or natural ventilation is otherwise provided, listed and labeled ductless range hoods shall not be required to discharge to the outdoors.

Single-wall ducts serving range hoods shall be constructed of galvanized steel, stainless steel or copper.

Exception: Ducts for domestic kitchen cooking appliances equipped with down-draft exhaust systems shall be permitted to be constructed of schedule 40 PVC pipe and fittings provided that the installation complies with all of the following:

1. The duct is installed under a concrete slab poured on grade; and

2. The underfloor trench in which the duct is installed is completely backfilled with sand or gravel; and

3. The PVC duct extends not more than 1 inch (25 mm) above the indoor concrete floor surface; and

4. The PVC duct extends not more than 1 inch (25 mm) above gradeoutside of the building; and

5. The PVC ducts are solvent cemented.

Where domestic kitchen cooking appliancesare equipped with ducted range hoods or down-draft exhaust systems, the fans shall be sized in accordance with Section M1507.3.
Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system.
The installation of a listed and labeled cooking appliance or microwave oven over a listed and labeled cooking appliance shall conform to the terms of the upper appliance’s listing and label and the manufacturer’s installation instructions. The microwave oven shall conform to UL 923.
Domestic open-top broiler units shall have a metal exhaust hood, having a minimum thickness of 0.0157-inch (0.3950 mm) (No. 28 gage) with 1/4 inch (6.4 mm) clearance between the hood and the underside of combustible material or cabinets. A clearance of at least 24 inches (610 mm) shall be maintained between the cooking surface and the combustible material or cabinet. The hood shall be at least as wide as the broiler unit, extend over the entire unit, discharge to the outdoors and be equipped with a backdraft damper or other means to control infiltration/exfiltration when not in operation. Broiler units incorporating an integral exhaust system, and listed and labeled for use without an exhaust hood, need not have an exhaust hood.
Where exhaust duct construction is not specified in this chapter, construction shall comply with Chapter 16.
Where toilet rooms and bathrooms are mechanically ventilated, the ventilation equipment shall be installed in accordance with this section.
Exhaust air from bathrooms and toilet rooms shall not be recirculated within a residence or to another dwelling unit and shall be exhausted directly to the outdoors. Exhaust air from bathrooms and toilet rooms shall not discharge into an attic, crawl space or other areas inside the building.

Ventilation systems shall be designed to have the capacity to exhaust the minimum air flow rate determined in accordance with Table M1507.3.

TABLE M1507.3
MINIMUM REQUIRED EXHAUST RATES FOR
ONE- AND TWO-FAMILY DWELLINGS

AREA TO BE VENTILATED

VENTILATION RATES

Kitchens

100 cfm intermittent or

25 cfm continuous

Bathrooms—Toilet Rooms

Mechanical exhaust capacity of
50 cfm intermittent or 20 cfm continuous

For SI: 1 cubic foot per minute = 0.4719 L/s.

Resources
Help us
keep law free