The provisions of this chapter shall govern the construction, installation,
alteration and repair of hydronic
piping systems. This chapter shall apply to hydronic
piping systems that are part of heating,
ventilation and
air-conditioning systems. Such
piping systems shall include steam, hot water, chilled water, steam
condensate and ground source
heat pump loop systems. Potable cold and hot water distribution systems shall be installed in accordance with the
International Plumbing Code.
Piping and
piping system components for hydronic systems shall be sized for the demand of the system.
As an alternative to the provisions of Sections
1202 and
1203,
piping shall be designed, installed, inspected and tested in accordance with ASME B31.9
.
Piping material shall conform to the standards cited in this section.
Exception: Embedded piping regulated by Section 1209.
Reused
pipe, fittings, valves or other materials shall be clean and free of foreign materials and shall be
approved by the
code official for reuse.
Materials shall be rated for the operating temperature and pressure of the hydronic system. Materials shall be suitable for the type of fluid in the hydronic system.
Hydronic pipe shall conform to the standards listed in Table 1202.4. The exterior of the pipe shall be protected from corrosion and degradation.
TABLE 1202.4
HYDRONIC PIPE
MATERIAL | STANDARD (see Chapter 15) |
Acrylonitrile butadiene styrene (ABS) plastic pipe | ASTM D 1527; ASTM D 2282 |
Brass pipe | ASTM B 43 |
Brass tubing | ASTM B 135 |
Copper or copper-alloy pipe | ASTM B 42; ASTM B 302 |
Copper or copper-alloy tube (Type K, L or M) | ASTM B 75; ASTM B 88; ASTM B 251 |
Chlorinated polyvinyl chloride (CPVC) plastic pipe | ASTM D 2846; ASTM F 441; ASTM F 442 |
Cross-linked polyethylene/ aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe | ASTM F 1281; CSA CAN/CSA-B-137.10 |
(continued)
TABLE 1202.4—continued
HYDRONIC PIPE
MATERIAL | STANDARD (see Chapter 15) |
Cross-linked polyethylene (PEX) tubing | ASTM F 876; ASTM F 877 |
Ductile iron pipe | AWWA C151/A21.51; AWWA C115/A21.15 |
Lead pipe | FS WW-P-325B |
Polybutylene (PB) plastic pipe and tubing | ASTM D 3309 |
Polyethylene/aluminum/polyethylen (PE-AL-PE) pressure pipe | ASTM F 1282; CSA B137.9 |
Polyethylene (PE) pipe, tubing and fittings (for ground source heat pump loop systems) | ASTM D 2513; ASTM D 3035; ASTM D 2447; ASTM D 2683; ASTM F 1055; ASTM D 2837; ASTM D 3350; ASTM D 1693 |
Polypropylene (PP) plastic pipe | ASTM F 2389 |
Polyvinyl chloride (PVC) plastic pipe | ASTM D 1785; ASTM D 2241 |
Raised temperature polyethylene (PE-RT) | ASTM F 2623 |
Steel pipe | ASTM A 53; ASTM A 106 |
Steel tubing | ASTM A 254 |
Hydronic pipe fittings shall be approved for installation with the piping materials to be installed, and shall conform to the respective pipe standards or to the standards listed in Table 1202.5.
TABLE 1202.5
HYDRONIC PIPE FITTINGS
MATERIAL | STANDARD (see Chapter 15) |
Brass | ASTM F 1974 |
Bronze | ASME B16.24 |
Copper and copper alloys | ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29 |
Ductile iron and gray iron | ANSI/AWWA C110/A21.10 |
Ductile iron | ANSI/AWWA C153/A21.53 |
Gray iron | ASTM A 126 |
Malleable iron | ASME B16.3 |
Plastic | ASTM D 2466; ASTM D 2467; ASTM D 2468; ASTM F 438; ASTM F 439; ASTM F 877; ASTM F 2389 |
Steel | ASME B16.5; ASME B16.9; ASME B16.11; ASME B16.28; ASTM A 420 |
Valves shall be constructed of materials that are compatible with the type of
piping material and fluids in the system. Valves shall be rated for the temperatures and pressures of the systems in which the valves are installed.
Flexible connectors, expansion and vibration
control devices and fittings shall be of an
approved type.
Joints and connections shall be of an approved type. Joints and connections shall be tight for the pressure of the hydronic system.
Joints between different
piping materials shall be made with
approved adapter fittings. Joints between different metallic
piping materials shall be made with
approved dielectric fittings or brass converter fittings.
Pipe shall be cut square, reamed and chamfered, and shall be free of burrs and obstructions.
Pipe ends shall have full-bore openings and shall not be undercut.
When required by Sections
1203.4 through
1203.14, the preparation and installation of brazed, mechanical, soldered, solvent-cemented, threaded and
welded joints shall comply with Sections
1203.3.1 through
1203.3.7.
Joint surfaces shall be cleaned. An approved flux shall be applied where required. The joint shall be brazed with a filler metal conforming to AWS A5.8.
Mechanical joints shall be installed in accordance with the manufacturer’s instructions.
Joint surfaces shall be cleaned. A flux conforming to ASTM B 813 shall be applied. The joint shall be soldered with a solder conforming to ASTM B 32.
Joint surfaces shall be clean and free of moisture. An approved primer shall be applied to CPVC and PVC pipe-joint surfaces. Joints shall be made while the cement is wet. Solvent cement conforming to the following standards shall be applied to all joint surfaces:
1. ASTM D 2235 for ABS joints.
2. ASTM F 493 for CPVC joints.
3. ASTM D 2564 for PVC joints.
CPVC joints shall be made in accordance with ASTM D 2846.
Threads shall conform to ASME B1.20.1. Schedule 80 or heavier plastic
pipe shall be threaded with dies specifically designed for plastic
pipe. Thread lubricant,
pipe-joint compound or tape shall be applied on the male threads only and shall be
approved for application on the
piping material.
Joint surfaces shall be cleaned by an approved procedure. Joints shall be welded with an approved filler metal.
Grooved and shouldered
mechanical joints shall conform to the requirements of ASTM F 1476 and shall be installed in accordance with the manufacturer’s installation instructions.
Mechanically extracted
outlets shall have a height not less than three times the thickness of the branch tube wall.
Branch tubes shall not restrict the flow in the run tube. A dimple/depth stop shall be formed in the branch tube to ensure that penetration into the
outlet is of the correct depth. For inspection purposes, a second dimple shall be placed
1/
4 inch (6.4 mm) above the first dimple. Dimples shall be aligned with the tube run.
Mechanically formed tee fittings shall be brazed in accordance with
Section 1203.3.1.
Press connect joints shall be
installed in accordance with the manufacturer’s instructions.
Press-connect joints shall conform to one of the standards
listed in Table 1202.5.
Joints between ABS plastic
pipe or fittings shall be solvent-cemented or threaded joints conforming to
Section 1203.3.
Joints between brass
pipe or fittings shall be brazed, mechanical, threaded or
welded joints conforming to
Section 1203.3.
Joints between brass
tubing or fittings shall be brazed, mechanical or
soldered joints conforming to
Section 1203.3.
Joints between copper or copper-alloy
pipe or fittings shall be brazed, mechanical, soldered, threaded or
welded joints conforming to
Section 1203.3.
Joints between copper or copper-alloy tubing or fittings shall be brazed, mechanical, press connect or soldered joints conforming to Section 1203.3, flared joints conforming to Section 1203.8.1 or push-fit joints conforming to Section 1203.8.2.
Flared joints shall be made by a tool designed for that operation.
Push-fit joints shall be installed in accordance with the manufacturer’s instructions.
Joints between CPVC plastic
pipe or fittings shall be solvent-cemented or threaded joints conforming to
Section 1203.3.
Joints between polybutylene plastic
pipe and
tubing or fittings shall be
mechanical joints conforming to
Section 1203.3 or heat-fusion joints conforming to
Section 1203.10.1.
Joints shall be of the socket- fusion or butt-fusion type. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM D 3309.
Joints between cross-linked polyethylene plastic
tubing and fittings shall conform to Sections
1203.11.1 and
1203.11.2.
Mechanical joints shall conform to
Section 1203.3.
When compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Soldering on the metal portion of the system shall be performed at least 18 inches (457 mm) from a plastic-to-metal adapter in the same water line.
Joints between PVC plastic
pipe and fittings shall be solvent-cemented or threaded joints conforming to
Section 1203.3.
Joints between steel
pipe or fittings shall be
mechanical joints that are made with an
approved elastomeric seal, or shall be threaded or
welded joints conforming to
Section 1203.3.
Joints between steel
tubing or fittings shall be mechanical or
welded joints conforming to
Section 1203.3.
Joints between polyethylene plastic
pipe and
tubing or fittings for ground source
heat pump loop systems shall be heat fusion joints conforming to
Section 1203.15.1, electrofusion joints conforming to
Section 1203.15.2, or stab-type insertion joints conforming to
Section 1203.15.3.
Joints shall be of the socket-fusion, saddle-fusion or butt-fusion type, joined in accordance with ASTM D 2657. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undisturbed until cool. Fittings shall be manufactured in accordance with ASTM D 2683 or ASTM D 3261.
Joints shall be of the electrofusion type. Joint surfaces shall be clean and free of moisture, and scoured to expose virgin resin. Joint surfaces shall be heated to melt temperatures for the period of time specified by the manufacturer. The joint shall be undisturbed until cool. Fittings shall be manufactured in accordance with ASTM F 1055.
Joint surfaces shall be clean and free of moisture.
Pipe ends shall be chamfered and inserted into the fittings to full depth. Fittings shall be manufactured in accordance with ASTM F 1924.
Joints between PP plastic
pipe and fittings shall comply with Sections
1203.16.1 and
1203.16.2.
Heat-fusion joints for polypropylene (PP)
pipe and
tubing joints shall be installed with socket-type heat-fused polypropylene fittings, electro- fusion polypropylene fittings or by butt fusion. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389.
Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer’s instructions.
Joints between raised temperature polyethylene
tubing and fittings shall conform to Sections
1203.17.1 and
1203.17.2.
Mechanical joints shall conform to
Section 1203.3.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Solder joints in a metal
pipe shall not occur within 18 inches (457 mm) of a transition from such metal
pipe to PE-RT
pipe.
Joints between polyethylene/aluminum/polyethylene pressure
pipe and fittings shall conform to Sections
1203.18.1 and
1203.18.2.
Mechanical joints shall comply with
Section 1203.3.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Solder joints in a metal
pipe shall not occur within 18 inches (457 mm) of a transition from such metal
pipe to PE-AL-PE
pipe.
Joints between cross-linked polyethylene/aluminum/cross-linked polyethylene pressure
pipe and fittings shall conform to Sections
1203.19.1 and
1203.19.2.
Mechanical joints shall comply with
Section 1203.3.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Solder joints in a metal
pipe shall not occur within 18 inches (457 mm) of a transition from such metal
pipe to PEX-AL-PEX
pipe.
Pipe insulation installed in buildings shall conform to the requirements of the International Energy Conservation Code; shall be tested in accordance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231; and shall have a maximum flame spread index of 25 and a smoke-developed index not exceeding 450. Insulation installed in an air plenum shall comply with Section 602.2.1.
Exception: The maximum flame spread index and smoke- developed index shall not apply to one- and two-family dwellings.
Hydronic
piping shall be insulated to the thickness required by the
International Energy Conservation Code.
Shutoff valves shall be installed in hydronic
piping systems in the locations indicated in Sections
1205.1.1 through
1205.1.6.
Shutoff valves shall be installed on the supply and return side of a heat exchanger.
Exception: Shutoff valves shall not be required when heat exchangers are integral with a boiler; or are a component of a manufacturer’s boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves required by Section 1005.1.
Shutoff valves shall be installed on the building supply and return of a central utility system.
Shutoff valves shall be installed on the connection to any pressure vessel.
Shutoff valves shall be installed on both sides of a pressure-reducing valve.
Shutoff valves shall be installed on connections to mechanical
equipment and
appliances. This requirement does not apply to components of a hydronic system such as pumps, air separators, metering devices and similar
equipment.
Shutoff valves shall be installed at connections to nondiaphragm-type expansion tanks.
A
pressure relief valve shall be installed on the low-pressure side of a hydronic
piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with
Section 1006.
Piping, valves, fittings and connections shall be installed in accordance with the conditions of approval.
Hydronic piping systems shall be designed and installed to permit the system to be drained. Where the system drains to the plumbing drainage system, the installation shall conform to the requirements of the International Plumbing Code.
Exception: The buried portions of systems embedded underground or under floors.
The potable water system shall be protected from backflow in accordance with the
International Plumbing Code.
Openings for
pipe penetrations in walls, floors or ceilings shall be larger than the penetrating
pipe. Openings through concrete or masonry building elements shall be sleeved. The annular space surrounding
pipe penetrations shall be protected in accordance with the
International Building Code.
A
pipe in a hydronic
piping system in which the exterior temperature exceeds 250°F (121°C) shall have a minimum
clearance of 1 inch (25 mm) to
combustible materials.
A hydronic
piping system shall not be in direct contact with building materials that cause the
piping material to degrade or corrode, or that interfere with the operation of the system.
The flow velocity of the hydronic
piping system shall be controlled to reduce the possibility of water hammer. Where a quick-closing valve creates water hammer, an
approved water-hammer arrestor shall be installed. The arrestor shall be located within a range as specified by the manufacturer of the quick-closing valve.
Steam
piping shall be installed to drain to the boiler or the steam trap. Steam systems shall not have
drip pockets that reduce the capacity of the steam
piping.
Piping shall be installed so as to prevent detrimental strains and stresses in the
pipe. Provisions shall be made to protect
piping from damage resulting from expansion, contraction and structural settlement.
Piping shall be installed so as to avoid structural stresses or strains within building components.
Piping located in a flood hazard area shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the
design flood elevation.
Pipe shall be supported in accordance with
Section 305.
Provisions shall be made to prevent the formation of condensation on the exterior of
piping.
The
flash point of transfer fluid in a hydronic
piping system shall be a minimum of 50°F (28°C) above the maximum system operating temperature.
The transfer fluid shall be compatible with the makeup water supplied to the system.
Hydronic
piping systems other than ground- source
heat pump loop systems shall be tested hydrostatically at one and one half times the maximum system design pressure, but not less than 100 psi (689 kPa). The duration of each test shall be not less than 15 minutes. Ground-source
heat pump loop systems shall be tested in accordance with
Section 1208.1.1.
Before connection (header) trenches are backfilled, the assembled loop system shall be pressure tested with water at 100 psi (689 kPa) for 30 minutes with no observed leaks. Flow and pressure loss testing shall be performed and the actual flow rates and pressure drops shall be compared to the calculated design values. If actual flow rate or pressure drop values differ from calculated design values by more than 10 percent, the problem shall be identified and corrected.
Piping for heating panels shall be standard-weight steel
pipe, Type L copper
tubing, polybutylene or other
approved plastic
pipe or
tubing rated at 100 psi (689 kPa) at 180°F (82°C).
Piping to be embedded in concrete shall be pressure tested prior to pouring concrete. During pouring, the
pipe shall be maintained at the proposed operating pressure.
Joints of
pipe or
tubing that are embedded in a portion of the building, such as concrete or plaster, shall be in accordance with the requirements of Sections
1209.3.1 through
1209.3.3.
Steel
pipe shall be welded by electrical arc or oxygen/acetylene method.
Copper
tubing shall be joined by
brazing with filler metals having a melting point of not less than 1,000°F (538°C).
Polybutylene
pipe and
tubing shall be installed in continuous lengths or shall be joined by heat fusion in accordance with
Section 1203.10.1.
Joints of other
piping in cavities or running exposed shall be joined by
approved methods in accordance with manufacturer’s installation instructions and related sections of this code.
Radiant floor heating systems shall be provided with a thermal barrier in accordance with Sections 1209.5.1 through 1209.5.4.
Exception: Insulation shall not be required in engineered systems where it can be demonstrated that the insulation will decrease the efficiency or have a negative effect on the installation.
Radiant
piping utilized in slab-on-grade applications shall be provided with insulating materials installed beneath the
piping having a minimum
R-value of 5.
In suspended floor applications, insulation shall be installed in the joist bay cavity serving the heating space above and shall consist of materials having a minimum R-value of 11.
A thermal break shall be provided consisting of asphalt expansion joint materials or similar insulating materials at a point where a heated slab meets a foundation wall or other conductive slab.
Insulating materials utilized in thermal barriers shall be installed such that the manufacturer’s R-value mark is readily observable upon inspection.