Part 1 — General Provisions
These regulations shall be known as the
North
Carolina Fire Code
of [NAME OF JURISDICTION], hereinafter referred to as “this code.”as adopted by the North Carolina Building
Code Council on September 14, 2010 to be effective September
1, 2011. References to the International Code shall mean
the North Carolina Codes. The North Carolina amendments to
the International Code are underlined.
This code establishes regulations affecting or relating to structures, processes, premises and safeguards regarding:
1. The hazard of fire and explosion arising from the storage, handling or use of structures, materials or devices;
2. Conditions hazardous to life, property or public welfare in the occupancy of structures or premises;
3. Fire hazards in the structure or on the premises from occupancy or operation;
4. Matters related to the construction, extension, repair, alteration or removal of fire suppression or alarm systems; and
5. Conditions affecting the safety of fire fighters and emergency responders during emergency operations.
Provisions in the appendices shall not
be enforceable apply unless specifically adopted by the local governing
authority having jurisdiction and subsequently
approved for use by the Building Code Council..
The purpose of this code is to establish the minimum requirements consistent with nationally recognized good practice for providing a reasonable level of life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises and to provide safety to fire fighters and emergency responders during emergency operations.
If a section, subsection, sentence, clause or phrase of this code is, for any reason, held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this code.
In the event any part or provision of this code is held to be illegal or void, this shall not have the effect of making void or illegal any of the other parts or provisions hereof, which are determined to be legal; and it shall be presumed that this code would have been adopted without such illegal or invalid parts or provisions.
The North Carolina State
Building Codes do not include all additional requirements for
buildings and structures that may be imposed by other State agencies, occupational licensing boards and commissions. It
shall be the responsibility of a permit holder, design professional,
contractor or occupational license holder to determine
whether any additional requirements exist.
The construction and design provisions of this code shall apply to:
- Structures, facilities and conditions arising after the adoption of this code.
- Existing structures, facilities and conditions not legally in existence at the time of adoption of this code.
- Existing structures, facilities and conditions when required in Chapter 46.
When the current North Carolina Building State Codes
require safety to life requirements for existing buildings,
those requirements shall apply.
- Existing structures, facilities and conditions which, in the opinion of the fire code official, constitute a distinct hazard to life or property.
The legal occupancy of any structure existing on the date
of adoption of this code shall be permitted to continue
without change, except as is specifically covered in this
code or the International Building Code, or when there
exists a distinct hazard to life or property.
The administrative, operational and maintenance provisions of this code shall apply to:
1. Conditions and operations arising after the adoption of this code.
2. Existing conditions and operations.
No change shall be made in the use or occupancy of any structure that would place the structure in a different division of the same group or occupancy or in a different group of occupancies, unless such structure is made to comply with the requirements of this code and the International Building Code. Subject to the approval of the fire code official, the use or occupancy of an existing structure shall be allowed to be changed and the structure is allowed to be occupied for purposes in other groups without conforming to all the requirements of this code and the International Building Code for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.
The provisions of the
North Carolina Administrative Code and Policies and applicable
North Carolina General Statutes shall apply to all buildings
undergoing a change of occupancy.
The design and construction of new structures shall comply with the
International Building Code, and any
alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the
International Building Code, shall be made in accordance therewith.
Where structures are designed and constructed in accordance with the International Residential Code, the provisions of this code shall apply as follows:
1. Construction and design provisions: Provisions of this code pertaining to the exterior of the structure shall apply including, but not limited to, premises identification, fire apparatus access and water supplies. Where interior or exterior systems or devices are installed, construction permits required by Section 105.7 of this code shall also apply.
2. Administrative, operational and maintenance provisions: All such provisions of this code shall apply.
The provisions of this code relating to the construction,
alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local
jurisdiction as
historic buildings when such buildings or structures do not constitute a distinct hazard to life or property. Fire protection in designated
historic buildings and structures shall be provided in accordance with an
approved fire protection plan.
The codes and standards referenced in this code shall be those that are listed in
Chapter 45 and such codes and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply.
Where no applicable standards or requirements are set forth in this code, or are contained within other laws, codes, regulations, ordinances or bylaws adopted by the
jurisdiction, compliance with applicable standards of the National Fire Protection Association or other nationally recognized fire safety standards, as
approved, shall be deemed as prima facie evidence of compliance with the intent of this code. Nothing herein shall derogate from the authority of the
fire code official to determine compliance with codes or standards for those activities or installations within the
fire code official’s jurisdiction or responsibility.
Requirements that are essential for the public safety of an existing or proposed activity, building or structure, or for the safety of the occupants thereof, which are not specifically provided for by this code shall be determined by the
fire code official.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall be applicable. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.
References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
The provisions of this code
shall not apply to the following:
- Occupancy of one- and two-family dwellings.
- Farm buildings located outside the building rules jurisdiction
of any municipality.
Exception: All buildings used for sleeping purposes
shall conform to the provisions of the technical codes.
- The design, construction, location, installation or operation
of equipment for storing, handling, and transporting
liquefied petroleum gases for fuel purposes up to the first
stage regulator, liquefied natural gases, and anhydrous
ammonia or other liquid fertilizers.
- The design, construction, location, installation or operation
of equipment or facilities of a public utility, as
defined in General Statute 62-3, or an electric or telephone
membership corporation, including without limitation
poles, towers and other structures supporting
electric or communication lines from the distribution
network up to the meter location.
Exception: All buildings owned and operated by a
public utility or an electric or telephone membership
corporation shall meet the provisions of the code.
- The Storage and Handling of Hazardous Chemicals
Right to Know Act. North Carolina General Statute
95-173 through 95-218.
- Open burning pursuant to General Statute 113-60.21
through 113-60.31 under the jurisdiction of the North
Carolina Department of Environment and Natural
Resources.
Part 2 — Administrative Provisions
The department of fire prevention is established within the
jurisdiction under the direction of the
fire code official. The function of the department shall be the implementation, administration and enforcement of the provisions of this code.
The fire code official shall be appointed by the chief appointing authority of the jurisdiction; and the fire code official shall not be removed from office except for cause and after full opportunity to be heard on specific and relevant charges by and before the appointing authority.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
In accordance with the prescribed procedures of this jurisdiction and with the concurrence of the appointing authority, the fire code official shall have the authority to appoint a deputy fire code official, other related technical officers, inspectors and other employees.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
The fire code official, member of the board of appeals, officer or employee charged with the enforcement of this code, while acting for the jurisdiction, in good faith and without malice in the discharge of the duties required by this code or other pertinent law or ordinance, shall not thereby be rendered liable personally, and is hereby relieved from all personal liability for any damage accruing to persons or property as a result of an act or by reason of an act or omission in the discharge of official duties.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
Any suit instituted against any officer or employee because of an act performed by that officer or employee in the lawful discharge of duties and under the provisions of this code shall be defended by the legal representative of the jurisdiction until the final termination of the proceedings. The fire code official or any subordinate shall not be liable for costs in an action, suit or proceeding that is instituted in pursuance of the provisions of this code; and any officer of the department of fire prevention, acting in good faith and without malice, shall be free from liability for acts performed under any of its provisions or by reason of any act or omission in the performance of official duties in connection therewith.
See the provisions of the North
Carolina Administrative Code and Policies and applicable
North Carolina General Statutes.
The
fire code official is hereby authorized to enforce the provisions of this code and shall have the authority to render interpretations of this code, and to adopt policies, procedures, rules and regulations in order to clarify the application of its provisions. Such interpretations, policies, procedures, rules and regulations shall be in compliance with the intent and purpose of this code and shall not have the effect of waiving requirements specifically provided for in this code.
The
fire code official is authorized to receive applications, review
construction documents and issue
permits for construction regulated by this code, issue
permits for operations regulated by this code, inspect the premises for which such
permits have been issued and enforce compliance with the provisions of this code.
Whenever it is necessary to make an inspection to enforce the provisions of this code, or whenever the fire code official has reasonable cause to believe that there exists in a building or upon any premises any conditions or violations of this code which make the building or premises unsafe, dangerous or hazardous, the fire code official shall have the authority to enter the building or premises at all reasonable times to inspect or to perform the duties imposed upon the fire code official by this code. If such building or premises is occupied, the fire code official shall present credentials to the occupant and request entry. If such building or premises is unoccupied, the fire code official shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. If entry is refused, the fire code official has recourse to every remedy provided by law to secure entry.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
When the fire code official has first obtained a proper inspection warrant or other remedy provided by law to secure entry, an owner or occupant or person having charge, care or control of the building or premises shall not fail or neglect, after proper request is made as herein provided, to permit entry therein by the fire code official for the purpose of inspection and examination pursuant to this code.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
The fire code official shall carry proper identification when inspecting structures or premises in the performance of duties under this code.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
The fire code official is authorized to issue such notices or orders as are required to affect compliance with this code in accordance with Sections 109.1 and 109.2.
See the provisions of the North
Carolina Administrative Code and Policies and applicable
North Carolina General Statutes.
The fire code official shall keep official records as required by Sections 104.6.1 through 104.6.4. Such official records shall be retained for not less than five years or for as long as the structure or activity to which such records relate remains in existence, unless otherwise provided by other regulations.
See the provisions of the North
Carolina Administrative Code and Policies and applicable
North Carolina General Statutes.
A record of approvals shall be maintained by the
fire code official and shall be available for public inspection during business hours in accordance with applicable laws.
The
fire code official shall keep a record of each inspection made, including notices and orders issued, showing the findings and disposition of each.
The fire department shall keep a record of fires occurring within its
jurisdiction and of facts concerning the same, including statistics as to the extent of such fires and the damage caused thereby, together with other information as required by the
fire code official.
Application for modification, alternative methods or materials and the final decision of the
fire code official shall be in writing and shall be officially recorded in the permanent records of the
fire code official.
All materials, equipment and devices
approved by the
fire code official shall be constructed and installed in accordance with such approval.
Materials, equipment and devices shall not be reused or reinstalled unless such elements have been reconditioned, tested and placed in good and proper working condition and approved.
To determine the acceptability of technologies, processes, products,
facilities, materials and uses attending the design, operation or use of a building or premises subject to inspection by the
fire code official, the
fire code official is authorized to require the
owner or
agent to provide, without charge to the
jurisdiction, a technical opinion and report. The opinion and report shall be prepared by a qualified engineer, specialist, laboratory or fire safety specialty organization acceptable to the
fire code official and shall analyze the fire safety properties of the design, operation or use of the building or premises and the
facilities and appurtenances situated thereon, to recommend necessary changes. The
fire code official is authorized to require design submittals to be prepared by, and bear the stamp of, a
registered design professional.
Whenever there are practical difficulties involved in carrying out the provisions of this code, the fire code official shall have the authority to grant modifications for individual cases, provided the fire code official shall first find that special individual reason makes the strict letter of this code impractical and the modification is in compliance with the intent and purpose of this code and that such modification does not lessen health, life and fire safety requirements. The details of action granting modifications shall be recorded and entered in the files of the department of fire prevention.
See the provisions of the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes.
The provisions of this code are not intended to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by this code, provided that any such alternative has been approved. The fire code official is authorized to approve an alternative material or method of construction where the fire code official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety.
See the provisions
of the North Carolina Administrative Code and Policies and
applicable North Carolina General Statutes.
Supporting data, when necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
Whenever there is insufficient evidence of compliance with the provisions of this code, or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the
fire code official shall have the authority to require tests as evidence of compliance to be made at no expense to the
jurisdiction. Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the
fire code official shall approve the testing procedures. Tests shall be performed by an
approved agency. Reports of such tests shall be retained by the
fire code official for the period required for retention of public records.
The fire code official, the fire department or other responsible authority shall have the authority to investigate the cause, origin and circumstances of any fire, explosion or other hazardous condition. Information that could be related to trade secrets or processes shall not be made part of the public record except as directed by a court of law.
See the provisions of the North
Carolina Administrative Code and Policies and applicable
North Carolina General Statutes.
Police and other enforcement agencies shall have authority to render necessary assistance in the investigation of fires when requested to do so.
The
fire chief or officer of the fire department in charge at the scene of a fire or other emergency involving the protection of life or property or any part thereof, shall have the authority to direct such operation as necessary to extinguish or control any fire, perform any rescue operation, investigate the existence of suspected or reported fires, gas leaks or other hazardous conditions or situations, or take any other action necessary in the reasonable performance of duty. In the exercise of such power, the
fire chief is authorized to prohibit any person, vehicle, vessel or thing from approaching the scene and is authorized to remove, or cause to be removed or kept away from the scene, any vehicle, vessel or thing which could impede or interfere with the operations of the fire department and, in the judgment of the
fire chief, any person not actually and usefully employed in the extinguishing of such fire or in the preservation of property in the vicinity thereof.
The
fire chief or officer of the fire department in charge at the scene of an emergency is authorized to place ropes, guards, barricades or other obstructions across any street, alley, place or private property in the vicinity of such operation so as to prevent accidents or interference with the lawful efforts of the fire department to manage and control the situation and to handle fire apparatus.
No
person shall obstruct the operations of the fire department in connection with extinguishment or control of any fire, or actions relative to other emergencies, or disobey any lawful command of the
fire chief or officer of the fire department in charge of the emergency, or any part thereof, or any lawful order of a police officer assisting the fire department.
No
person shall render a system or device inoperative during an emergency unless by direction of the
fire chief or fire department official in charge of the incident.
Permits shall be in accordance with Sections
105.1.1 through
105.7.14.
Permits required by this code shall be obtained from the
fire code official.
Permit fees, if any, shall be paid prior to issuance of the
permit. Issued
permits shall be kept on the premises designated therein at all times and shall be readily available for inspection by the
fire code official.
There shall be two types of permits as follows:
1. Operational permit. An operational permit allows the applicant to conduct an operation or a business for which a permit is required by Section 105.6 for either:
1.1. A prescribed period.
1.2. Until renewed or revoked.
2. Construction permit. A construction permit allows the applicant to install or modify systems and equipment for which a permit is required by Section 105.7.
Operational permits listed as mandatory
in Section 105.6 shall be obtained from the fire code official.
For decisions on any appeals of the provisions of mandatory
permits, see the provisions of the North Carolina Administrative
Code and Policies and applicable North Carolina
General Statutes.
Operational permits listed as optional in Section 105.6
must be adopted by local ordinance to be legally issued by
the fire code official. A permit listed as optional does not
make any of the technical provisions of this code optional.
When more than one
permit is required for the same location, the
fire code official is authorized to consolidate such
permits into a single
permit provided that each provision is listed in the
permit.
Application for a
permit required by this code shall be made to the
fire code official in such form and detail as prescribed by the
fire code official. Applications for
permits shall be accompanied by such plans as prescribed by the
fire code official.
If the application for a
permit describes a use that does not conform to the requirements of this code and other pertinent laws and ordinances, the
fire code official shall not issue a
permit, but shall return the application to the applicant with the refusal to issue such
permit. Such refusal shall, when requested, be in writing and shall contain the reasons for refusal.
Before a new operational
permit is
approved, the
fire code official is authorized to inspect the receptacles, vehicles, buildings, devices, premises, storage spaces or areas to be used to determine compliance with this code or any operational constraints required.
An application for a permit for any proposed work or operation shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been diligently prosecuted or a permit shall have been issued; except that the fire code official is authorized to grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated.
See the provisions
of the North Carolina Administrative Code and Policies and
applicable North Carolina General Statutes.
The
fire code official shall examine or cause to be examined applications for
permits and amendments thereto within a reasonable time after filing. If the application or the
construction documents do not conform to the requirements of pertinent laws, the
fire code official shall reject such application in writing, stating the reasons therefor. If the
fire code official is satisfied that the proposed work or operation conforms to the requirements of this code and laws and ordinances applicable thereto, the
fire code official shall issue a
permit therefor as soon as practicable.
A
permit shall constitute permission to maintain, store or handle materials; or to conduct processes which produce conditions hazardous to life or property; or to install equipment utilized in connection with such activities; or to install or modify any
fire protection system or equipment or any other construction, equipment installation or modification in accordance with the provisions of this code where a
permit is required by
Section 105.6 or
105.7. Such permission shall not be construed as authority to violate, cancel or set aside any of the provisions of this code or other applicable regulations or laws of the
jurisdiction.
An operational permit shall remain in effect until reissued, renewed, or revoked or for such a period of time as specified in the permit. Construction permits shall automatically become invalid unless the work authorized by such permit is commenced within 180 days after its issuance, or if the work authorized by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. Before such work recommences, a new permit shall be first obtained and the fee to recommence work, if any, shall be one-half the amount required for a new permit for such work, provided no changes have been made or will be made in the original construction documents for such work, and provided further that such suspension or abandonment has not exceeded one year. Permits are not transferable and any change in occupancy, operation, tenancy or ownership shall require that a new permit be issued.
An operational permit shall remain in
effect until reissued, renewed or revoked or for such a time
as prescribed in the permit. Permits are not transferable and
any change in occupancy, operation, tenancy, or ownership
shall require a new permit to be issued.
A permittee holding an unexpired permit shall have the right to apply for an extension of the time within which the permittee will commence work under that permit when work is unable to be commenced within the time required by this section for good and satisfactory reasons. The fire code official is authorized to grant, in writing, one or more extensions of the time period of a permit for periods of not more than 180 days each. Such extensions shall be requested by the permit holder in writing and justifiable cause demonstrated.
The building or structure shall not be occupied prior to the
fire code official issuing a
permit and conducting associated inspections indicating the applicable provisions of this code have been met.
Where
permits are required and upon the request of a
permit applicant, the
fire code official is authorized to issue a conditional
permit to occupy the premises or portion thereof before the entire work or operations on the premises is completed, provided that such portion or portions will be occupied safely prior to full completion or installation of equipment and operations without endangering life or public welfare. The
fire code official shall notify the
permit applicant in writing of any limitations or restrictions necessary to keep the
permit area safe. The holder of a conditional
permit shall proceed only to the point for which approval has been given, at the
permit holder’s own risk and without assurance that approval for the occupancy or the utilization of the entire premises, equipment or operations will be granted.
Issued
permits shall be kept on the premises designated therein at all times and shall be readily available for inspection by the
fire code official.
The issuance or granting of a
permit shall not be construed to be a
permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the
jurisdiction.
Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
jurisdiction shall not be valid. The issuance of a
permit based on
construction documents and other data shall not prevent the
fire code official from requiring the correction of errors in the
construction documents and other data. Any addition to or
alteration of
approved construction documents shall be
approved in advance by the
fire code official, as evidenced by the issuance of a new or amended
permit.
The
fire code official shall issue all
permits required by this code on an
approved form furnished for that purpose. The
permit shall contain a general description of the operation or occupancy and its location and any other information required by the
fire code official. Issued
permits shall bear the signature of the
fire code official or other
approved legal authorization.
The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinances of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid. The issuance of a permit based on construction documents, operational documents and other data shall not prevent the fire code official from requiring correction of errors in the documents or other data.
See the provisions of the North
Carolina Administrative Code and Policies and applicable
North Carolina General Statutes.
Construction documents shall be in accordance with this section.
See the provisions of
the North Carolina Administrative Code and Policies and
applicable North Carolina General Statutes.
Construction documents and supporting data shall be submitted in two or more sets with each application for a permit and in such form and detail as required by the fire code official. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed.
Exception: The fire code official is authorized to waive the submission of construction documents and supporting data not required to be prepared by a registered design professional if it is found that the nature of the work applied for is such that review of construction documents is not necessary to obtain compliance with this code.
The
fire code official shall examine or cause to be examined the accompanying
construction documents and shall ascertain by such examinations whether the work indicated and described is in accordance with the requirements of this code.
Construction documents shall be drawn to scale upon suitable material. Electronic media documents are allowed to be submitted when
approved by the
fire code official.
Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations as determined by the
fire code official.
Shop drawings for the fire protections system(s) shall be submitted to indicate compliance with this code and the
construction documents and shall be
approved prior to the start of installation. Shop drawings shall contain all information as required by the referenced installation standards in
Chapter 9.
It shall be the responsibility of the applicant to ensure that the
construction documents include all of the fire protection requirements and the shop drawings are complete and in compliance with the applicable codes and standards.
Construction documents approved by the
fire code official are
approved with the intent that such
construction documents comply in all respects with this code. Review and approval by the
fire code official shall not relieve the applicant of the responsibility of compliance with this code.
The
fire code official is authorized to issue a
permit for the construction of part of a structure, system or operation before the
construction documents for the whole structure, system or operation have been submitted, provided that adequate information and detailed statements have been filed complying with pertinent requirements of this code. The holder of such
permit for parts of a structure, system or operation shall proceed at the holder’s own risk with the building operation and without assurance that a
permit for the entire structure, system or operation will be granted.
Where field conditions necessitate any substantial change from the
approved construction documents, the
fire code official shall have the authority to require the corrected
construction documents to be submitted for approval.
One set of construction documents shall be retained by the fire code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws. One set of approved construction documents shall be returned to the applicant, and said set shall be kept on the site of the building or work at all times during which the work authorized thereby is in progress.
See the
provisions of the North Carolina Administrative Code and
Policies and applicable North Carolina General Statutes.
The fire code official is authorized to revoke a permit issued under the provisions of this code when it is found by inspection or otherwise that there has been a false statement or misrepresentation as to the material facts in the application or construction documents on which the permit or approval was based including, but not limited to, any one of the following:
1. The permit is used for a location or establishment other than that for which it was issued.
2. The permit is used for a condition or activity other than that listed in the permit.
3. Conditions and limitations set forth in the permit have been violated.
4. There have been any false statements or misrepresentations as to the material fact in the application for permit or plans submitted or a condition of the permit.
5. The permit is used by a different person or firm than the name for which it was issued.
6. The permittee failed, refused or neglected to comply with orders or notices duly served in accordance with the provisions of this code within the time provided therein.
7. The permit was issued in error or in violation of an ordinance, regulation or this code.
The
fire code official is authorized to issue operational
permits for the operations set forth in Sections
105.6.1 through
105.6.46.
An operational permit is required to manufacture, store or handle an aggregate quantity of Level 2 or Level 3 aerosol products in excess of 500 pounds (227 kg) net weight.
An operational permit is required to operate a special amusement building.
An operational permit is required to use a Group H or Group S occupancy for aircraft servicing or repair and aircraft fuel-servicing vehicles. Additional permits required by other sections of this code
include, but are not limited to, hot work, hazardous materials and flammable or combustible finishes.
An operational permit is required to conduct a carnival or fair.
An operational permit is required to store, handle or use cellulose nitrate film in a Group A occupancy.
An operational permit is required to operate a grain elevator, flour starch mill, feed mill, or a plant pulverizing aluminum, coal, cocoa, magnesium, spices or sugar, or other operations producing combustible dusts as defined in Chapter 2.
An operational permit is required for the storage and handling of combustible fibers in quantities greater than 100 cubic feet (2.8 m3).
Exception: A permit is not required for agricultural storage.
An operational permit is required for the storage, use or handling at normal temperature and pressure (NTP) of compressed gases in excess of the amounts listed in Table 105.6.8.
Exception: Vehicles equipped for and using compressed gas as a fuel for propelling the vehicle.
TABLE 105.6.8
PERMIT AMOUNTS FOR COMPRESSED GASES
TYPE OF GAS | AMOUNT (cubic feet at NTP) |
Corrosive | 200 |
Flammable (except cryogenic fluids and liquefied petroleum gases) | 200 |
Highly toxic | Any Amount |
Inert and simple asphyxiant | 6,000 |
Oxidizing (including oxygen) | 504 |
Pyrophoric | Any Amount |
Toxic | Any Amount |
For SI: 1 cubic foot = 0.02832 m3.
An operational permit is required for:
1. The placement of retail fixtures and displays, concession equipment, displays of highly combustible goods and similar items in the mall.
2. The display of liquid- or gas-fired equipment in the mall.
3. The use of open-flame or flame-producing equipment in the mall.
An operational permit is required to produce, store, transport on site, use, handle or dispense cryogenic fluids in excess of the amounts listed in Table 105.6.10.
Exception: Permits are not required for vehicles equipped for and using cryogenic fluids as a fuel for propelling the vehicle or for refrigerating the lading.
TABLE 105.6.10
PERMIT AMOUNTS FOR CRYOGENIC FLUIDS
TYPE OF CRYOGENIC FLUID | INSIDE BUILDING (gallons) | OUTSIDE BUILDING (gallons) |
Flammable | More than 1 | 60 |
Inert | 60 | 500 |
Oxidizing (includes oxygen) | 10 | 50 |
Physical or health hazard not indicated above | Any Amount | Any Amount |
For SI: 1 gallon = 3.785 L.
An operational permit is required to conduct cutting or welding operations within the jurisdiction.
An operational permit is required to engage in the business of dry cleaning or to change to a more hazardous cleaning solvent used in existing dry cleaning equipment.
An operational permit is required to operate exhibits and trade shows.
An operational permit is required for the manufacture, storage, handling, sale or use of any quantity of explosives, explosive materials, fireworks or pyrotechnic special effects within the scope of Chapter 33.
Exception:Exceptions:
- Fireworks allowed by North Carolina General
Statute 14-414.
- Storage in Group R-3 occupancies of smokeless propellant, black powder and small arms primers for personal use, not for resale and in accordance with Section 3306.
An operational permit is required to use or operate fire hydrants or valves intended for fire suppression purposes which are installed on water systems and accessible to a fire apparatus access road that is open to or generally used by the public.
Exception: A permit is not required for authorized employees of the water company that supplies the system or the fire department to use or operate fire hydrants or valves.
An operational permit is required:
1. Optional permit. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the Department of Transportation (DOTn) nor does it apply to piping systems.
2. Optional permit. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following:
2.1. The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, unless such storage, in the opinion of the code official, would cause an unsafe condition.
2.2. The storage or use of paints, oils, varnishes or similar flammable mixtures when such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days.
3. Optional permit. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment.
4. Optional permit. To store, handle or use Class IIIB liquids in tanks or portable tanks for fueling motor vehicles at motor fuel-dispensing facilities or where connected to fuel-burning equipment.
Exception: Fuel oil and
used motor oil used for space heating or water heating.
5. Optional permit. To remove Class I or II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes.
6. Mandatory permit. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used.
7. Mandatory permit. To place temporarily out of service (for more than 90 days) an underground, protected above-ground or above-ground flammable or combustible liquid tank.
8. Mandatory permit. To change the type of contents stored in a flammable or combustible liquid tank to a material that poses a greater hazard than that for which the tank was designed and constructed.
9. Mandatory permit. To manufacture, process, blend or refine flammable or combustible liquids.
10. Mandatory permit. To engage in the dispensing of liquid fuels into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments.
11. Mandatory permit. To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of motor vehicles, marine craft and other special equipment at commercial, industrial, governmental or manufacturing establishments.
An operational permit is required for floor finishing or surfacing operations exceeding 350 square feet (33 m2) using Class I or Class II liquids.
An operational permit is required to operate a fruit- or crop-ripening facility or conduct a fruit-ripening process using ethylene gas.
An operational permit is required to operate a business of fumigation or thermal insecticidal fogging and to maintain a room, vault or chamber in which a toxic or flammable fumigant is used.
An operational permit is required to store, transport on site, dispense, use or handle hazardous materials in excess of the amounts listed in Table 105.6.20.
TABLE 105.6.20
PERMIT AMOUNTS FOR HAZARDOUS MATERIALS
TYPE OF MATERIAL | AMOUNT |
Combustible liquids | See Section 105.6.16 |
Corrosive materials Gases Liquids Solids | See Section 105.6.8 55 gallons 1000 pounds |
Explosive materials | See Section 105.6.14 |
Flammable materials Gases Liquids Solids | See Section 105.6.8 See Section 105.6.16 100 pounds |
Highly toxic materials Gases Liquids Solids | See Section 105.6.8 Any Amount Any Amount |
Oxidizing materials Gases Liquids Class 4 Class 3 Class 2 Class 1 Solids Class 4 Class 3 Class 2 Class 1 | See Section 105.6.8 Any Amount 1 gallona 10 gallons 55 gallons Any Amount 10 poundsb 100 pounds 500 pounds |
Organic peroxides Liquids Class I Class II Class III Class IV Class V Solids Class I Class II Class III Class IV Class V | Any Amount Any Amount 1 gallon 2 gallons No Permit Required Any Amount Any Amount 10 pounds 20 pounds No Permit Required |
Pyrophoric materials Gases Liquids Solids | Any Amount Any Amount Any Amount |
Toxic materials Gases Liquids Solids | See Section 105.6.8 10 gallons 100 pounds |
Unstable (reactive) materials Liquids Class 4 Class 3 Class 2 Class 1 Solids Class 4 Class 3 Class 2 Class 1 | Any Amount Any Amount 5 gallons 10 gallons Any Amount Any Amount 50 pounds 100 pounds |
Water-reactive materials Liquids Class 3 Class 2 Class 1 Solids Class 3 Class 2 Class 1 | Any Amount 5 gallons 55 gallons Any Amount 50 pounds 500 pounds |
For SI: 1 gallon = 3.785 L, 1 pound = 0.454 kg.
a. 20 gallons when Table 2703.1.1(1) Note k applies and hazard identification signs in accordance with Section 2703.5 are provided for quantities of 20 gallons or less.
b. 200 pounds when Table 2703.1.1(1) Note k applies and hazard identification signs in accordance with Section 2703.5 are provided for quantities of 200 pounds or less.
An operational permit is required to store, handle or use hazardous production materials.
An operational permit is required to use a building or portion thereof as a high-piled storage area exceeding 500 square feet (46 m2).
An operational permit is required for hot work
including, but not limited to:
1. Public exhibitions and demonstrations where hot work is conducted.
2. Use of portable hot work equipment inside a structure.
Exception: Work that is conducted under a construction permit.
3. Fixed-site hot work equipment such as welding booths.
4. Hot work conducted within a wildfire risk area.
5. Application of roof coverings with the use of an open-flame device.
6. When approved, the fire code official shall issue a permit to carry out a hot work program. This program allows approved personnel to regulate their facility’s hot work operations. The approved personnel shall be trained in the fire safety aspects denoted in this chapter and shall be responsible for issuing permits requiring compliance with the requirements found in Chapter 26. These permits shall be issued only to their employees or hot work operations under their supervision.
An operational permit is required for operation of industrial ovens regulated by Chapter 21.
An operational permit is required for the storage or processing of lumber exceeding 100,000 board feet (8,333 ft3) (236 m3).
An operational permit is required to display, operate or demonstrate liquid- or gas-fueled vehicles or equipment in assembly buildings.
An operational permit is required for:
1. Storage and use of LP-gas.
Exception: A permit is not required for individual containers with a 500-gallon (1893 L) water capacity or less serving occupancies in Group R-3.
2. Operation of cargo tankers that transport LP-gas.
A permit may be required and issued by
the North Carolina Department of Agriculture and Consumer
Services for LP-gas equipment used for storage, handling,
transporting, and utilizing liquefied petroleum gas for
fuel purposes.
An operational permit is required to melt, cast, heat treat or grind more than 10 pounds (4.54 kg) of magnesium.
An operational permit is required to store in any building or upon any premises in excess of 2,500 cubic feet (71 m3) gross volume of combustible empty packing cases, boxes, barrels or similar containers, rubber tires, rubber, cork or similar combustible material.
An operational permit is required for the kindling or maintaining of an open fire or a fire on any public street, alley, road, or other public or private ground. Instructions and stipulations of the permit shall be adhered to.
Exception: Recreational fires.
An operational permit is required to remove paint with a torch; or to use a torch or open-flame device in a wildfire risk area.
An operational permit is required to use open flames or candles in connection with assembly areas, dining areas of restaurants or drinking establishments.
An operational permit is required for any organic-coating manufacturing operation producing more than 1 gallon (4 L) of an organic coating in one day.
An operational permit is required to operate a place of assembly.
An operational permit is required for the removal from service, use or operation of private fire hydrants.
Exception: A permit is not required for private industry with trained maintenance personnel, private fire brigade or fire departments to maintain, test and use private hydrants.
An operational permit is required for use and handling of pyrotechnic special effects material.
An operational permit is required for storage or handling of more than 25 pounds (11 kg) of cellulose nitrate (pyroxylin) plastics and for the assembly or manufacture of articles involving pyroxylin plastics.
An operational permit is required to operate a mechanical refrigeration unit or system regulated by Chapter 6.
An operational permit is required for operation of repair garages and automotive, marine and fleet motor fuel-dispensing facilities.
An operational permit is required for the operation of a rooftop heliport.
An operational permit is required to conduct a spraying or dipping operation utilizing flammable or combustible liquids or the application of combustible powders regulated by Chapter 15.
An operational permit is required to establish, conduct or maintain storage of scrap tires and tire byproducts that exceeds 2,500 cubic feet (71 m3) of total volume of scrap tires and for indoor storage of tires and tire byproducts.
An operational permit is required to operate an air-supported temporary membrane structure or a tent having an area in excess of 400 square feet (37 m2).
Exceptions:
1. Tents used exclusively for recreational camping purposes.
2. Tents open on all sides, which comply with all of the following:
2.1. Individual tents having a maximum size of 700 square feet (65 m2).
2.2. The aggregate area of multiple tents placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m2) total.
2.3. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be provided.
3. Funeral tents and curtains or extensions attached
thereto, when used for funeral services.
An operational permit is required for the operation and maintenance of a tire-rebuilding plant.
An operational permit is required for the operation of wrecking yards, junk yards and waste material-handling facilities.
An operational permit is required to store chips, hogged material, lumber or plywood in excess of 200 cubic feet (6 m3).
The fire code official is authorized to issue construction permits for work as set forth in Sections 105.7.1 through 105.7.14.
See the North Carolina
Administrative Code and Policies and applicable North
Carolina General Statutes for general information concerning
construction permits.
A construction
permit is required for installation of or modification to an automatic fire-extinguishing system. Maintenance performed in accordance with this code is not considered a modification and does not require a
permit.
A
permit is required to install stationary storage battery systems having a liquid capacity of more than 50 gallons (189 L).
When the compressed gases in use or storage exceed the amounts listed in Table 105.6.8, a construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a compressed gas system.
Exceptions:
1. Routine maintenance.
2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
A construction
permit is required for installation of or
alteration to outdoor stationary
cryogenic fluid storage systems where the system capacity exceeds the amounts listed in
Table 105.6.10. Maintenance performed in accordance with this code is not considered an
alteration and does not require a construction
permit.
A construction
permit is required for installation of or modification to
fire alarm and detection systems and related equipment. Maintenance performed in accordance with this code is not considered a modification and does not require a
permit.
A construction
permit is required for installation of or modification to fire pumps and related fuel
tanks, jockey pumps, controllers and generators. Maintenance performed in accordance with this code is not considered a modification and does not require a
permit.
A construction permit is required:
1. To install, repair or modify a pipeline for the transportation of flammable or combustible liquids.
2. To install, construct or alter tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used.
Maintenance performed in accordance with this
code is not considered an installation, construction or
alteration and does not require a permit.
3. To install, alter, remove, abandon or otherwise dispose of a flammable or combustible liquid tank.
A construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a storage facility or other area regulated by Chapter 27 when the hazardous materials in use or storage exceed the amounts listed in Table 105.6.20.
Exceptions:
1. Routine maintenance.
2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
A construction permit is required for installation of industrial ovens covered by Chapter 21.
Exceptions:
1. Routine maintenance.
2. For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
A construction permit
is required for
the installation of or modification to an LP-gas system may be required and
approved by the North Carolina Department of Agriculture
and Consumer Services..
A construction
permit is required for the installation or modification of private fire hydrants.
A construction
permit is required to install or modify a spray room, dip
tank or booth.
A construction
permit is required for the installation, modification or removal from service of a standpipe system. Maintenance performed in accordance with this code is not considered a modification and does not require a
permit.
A construction permit is required to erect an air-supported temporary membrane structure or a tent having an area in excess of 400 square feet (37 m2).
Exceptions:
1. Tents used exclusively for recreational camping purposes.
2. Funeral tents and curtains or extensions attached thereto, when used for funeral services.
3. Tents and awnings open on all sides which comply with all of the following:
3.1. Individual tents shall have a maximum size of 700 square feet (65 m2).
3.2. The aggregate area of multiple tents placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m2) total.
3.3. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be maintained.
In order to preserve and protect public health and safety and to
satisfy the requirements of General Statute 153A-364 and General
Statute 160A-424, political subdivisions assuming inspection
duties, as set out in General Statute 153A-351 and General
Statute 160A-411, shall have a periodic inspection schedule for
the purpose of identifying activities and conditions in buildings,
structures and premises that pose dangers of fire, explosion
or related hazards. Such inspection schedule shall be
approved by the local governing body and shall be submitted to
the Office of State Fire Marshal of the Department of Insurance.
In no case shall inspections be conducted less frequently
than described in the schedule below:
Once every year |
Hazardous, institutional, high-rise assembly except those noted below, and residential except one- and twofamily dwellings and only interior common areas of dwelling units of multi-family occupancies. New and existing lodging establishments, including hotels, motels and tourist homes that provide accommodations for 7 or more continuous days (extended-stay establishments), bed and breakfast inns and bed and breakfast homes as defined in General Statute 130A-247 for the installation and maintenance of carbon monoxide alarms and detectors in accordance with General Statute 143-138(b2). |
Once every two years |
Industrial and educational (except public schools). |
Once every three years |
Assembly occupancies with an occupant load less than 100, business, mercantile, storage, churches, synagogues, and miscellaneous Group U occupancies. |
Frequency rates for inspections of occupancies as mandated
by the North Carolina General Statutes shall supersede this
schedule. Nothing in this section is intended to prevent a jurisdiction
from conducting more frequent inspections than the
schedule listed above or the schedule filed with the Office of
State Fire Marshal of the Department of Insurance.
On unattended or vacant structures, the fire code official
shall affix a letter on the premises in a conspicuous place at or
near the entrance to such premises requesting an inspection in
accordance with this section. This order of notice shall be
mailed by registered or certified mail with return receipt
requested, to the last known address of the owner, occupant or
both. If the owner, occupant or both shall fail to respond to said
notice within 10 calendar days, these actions by the fire code
official shall be deemed to constitute an inspection in accordance
with this section.
The
fire code official is authorized to enter and examine any building, structure, marine vessel, vehicle or premises in accordance with
Section 104.3 for the purpose of enforcing this code.
The
fire code official is authorized to conduct such inspections as are deemed necessary to determine the extent of compliance with the provisions of this code and to approve reports of inspection by
approved agencies or individuals. All reports of such inspections shall be prepared and submitted in writing for review and approval. Inspection reports shall be certified by a responsible officer of such
approved agency or by the responsible individual. The
fire code official is authorized to engage such expert opinion as deemed necessary to report upon unusual, detailed or complex technical issues subject to the approval of the governing body.
It shall be the duty of the holder of the
permit or their duly authorized
agent to notify the
fire code official when work is ready for inspection. It shall be the duty of the
permit holder to provide access to and means for inspections of such work that are required by this code.
Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the
fire code official. The
fire code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the
permit holder or his or her
agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the
fire code official.
It shall be the duty of the
permit applicant to cause the work to remain accessible and exposed for inspection purposes. Whenever any installation subject to inspection prior to use is covered or concealed without having first been inspected, the
fire code official shall have the authority to require that such work be exposed for inspection. Neither the
fire code official nor the
jurisdiction shall be liable for expense entailed in the removal or replacement of any material required to allow inspection.
Approval as the result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other ordinances of the
jurisdiction. Inspections presuming to give authority to violate or cancel provisions of this code or of other ordinances of the
jurisdiction shall not be valid.
Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.
Equipment requiring periodic testing or operation to ensure maintenance shall be tested or operated as specified in this code.
Required test and inspection records shall be available to the
fire code official at all times or such records as the designates shall be filed with the
fire code official.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the
fire code official for inspection and testing.
Maintenance and testing shall be under the supervision of a responsible person who shall ensure that such maintenance and testing are conducted at specified intervals in accordance with this code.
Portable or fixed fire-extinguishing systems or devices and fire-warning systems shall not be rendered inoperative or inaccessible except as necessary during emergencies, maintenance, repairs,
alterations, drills or prescribed testing.
Correction and abatement of violations of this code shall be the responsibility of the
owner. If an occupant creates, or allows to be created, hazardous conditions in violation of this code, the occupant shall be held responsible for the abatement of such hazardous conditions.
Overcrowding or admittance of any
person beyond the
approved capacity of a building or a portion thereof shall not be allowed. The
fire code official, upon finding any
overcrowding conditions or obstructions in
aisles, passageways or other
means of egress, or upon finding any condition which constitutes a life safety hazard, shall be authorized to cause the event to be stopped until such condition or obstruction is corrected.
See the provisions of the North Carolina Administrative Code and Policies and applicable North Carolina General Statutes.
In order to hear and decide appeals of orders, decisions or determinations made by the
fire code official relative to the application and interpretation of this code, there shall be and is hereby created a board of appeals. The board of appeals shall be appointed by the governing body and shall hold office at its pleasure. The
fire code official shall be an ex officio member of said board but shall have no vote on any matter before the board. The board shall adopt rules of procedure for conducting its business, and shall render all decisions and findings in writing to the appellant with a duplicate copy to the
fire code official.
An application for appeal shall be based on a claim that the intent of this code or the rules legally adopted hereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equivalent method of protection or safety is proposed. The board shall have no authority to waive requirements of this code.
The board of appeals shall consist of members who are qualified by experience and training to pass on matters pertaining to hazards of fire, explosions, hazardous conditions or
fire protection systems and are not employees of the
jurisdiction.
For violations of the North Carolina Fire Prevention Code or a
local Fire Prevention Code that has received prior approval of
the Building Code Council, either the local fire code official or
the State Commissioner of Insurance or other state official with
responsibility under General Statute 143-139 may, in addition
to other remedies, institute any appropriate action or proceedings,
including civil remedies set out in General Statute
160A-175 or General Statute 153A-143, that have been
adopted as ordinances within that jurisdiction.
It shall be unlawful for a person, firm or corporation to erect, construct, alter, repair, remove, demolish or utilize a building, occupancy, premises or system regulated by this code, or cause same to be done, in conflict with or in violation of any of the provisions of this code.
When the
fire code official finds a building, premises, vehicle, storage
facility or outdoor area that is in violation of this code, the
fire code official is authorized to prepare a written notice of violation describing the conditions deemed unsafe and, when compliance is not immediate, specifying a time for reinspection.
A notice of violation issued pursuant to this code shall be served upon the
owner, operator, occupant or other
person responsible for the condition or violation, either by personal service, mail or by delivering the same to, and leaving it with, some
person of responsibility upon the premises. For unattended or abandoned locations, a copy of such notice of violation shall be posted on the premises in a conspicuous place at or near the entrance to such premises and the notice of violation shall be mailed by certified mail with return receipt requested or a certificate of mailing, to the last known address of the
owner, occupant or both.
A notice of violation issued or served as provided by this code shall be complied with by the
owner, operator, occupant or other
person responsible for the condition or violation to which the notice of violation pertains.
If the notice of violation is not complied with promptly, the
fire code official is authorized to request the legal counsel of the
jurisdiction to institute the appropriate legal proceedings at law or in equity to restrain, correct or abate such violation or to require removal or termination of the unlawful occupancy of the structure in violation of the provisions of this code or of the order or direction made pursuant hereto.
Signs, tags or seals posted or affixed by the
fire code official shall not be mutilated, destroyed or tampered with or removed without authorization from the
fire code official.
Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the
approved construction documents or directive of the
fire code official, or of a
permit or certificate used under provisions of this code, shall be guilty of a [SPECIFY OFFENSE], punishable by a fine of not more than [AMOUNT] dollars or by imprisonment not exceeding [NUMBER OF DAYS], or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
In addition to the imposition of the penalties herein described, the
fire code official is authorized to institute appropriate action to prevent unlawful construction or to restrain, correct or abate a violation; or to prevent illegal occupancy of a structure or premises; or to stop an illegal act, conduct of business or occupancy of a structure on or about any premises.
If during the inspection of a premises, a building or structure or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the
fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section and shall refer the building to the building department for any repairs,
alterations, remodeling, removing or demolition required.
Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate
means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. A vacant structure which is not secured against unauthorized entry as required by
Section 311 shall be deemed unsafe.
When an apparent structural hazard is caused by the faulty installation, operation or malfunction of any of the items or devices governed by this code, the
fire code official shall immediately notify the building code official in accordance with
Section 110.1.
The
fire code official or the fire department official in charge of an incident shall be authorized to order the immediate evacuation of any occupied building deemed unsafe when such building has hazardous conditions that present imminent danger to building occupants.
Persons so notified shall immediately leave the structure or premises and shall not enter or re-enter until authorized to do so by the
fire code official or the fire department official in charge of the incident.
Where conditions exist that are deemed hazardous to life and property, the
fire code official or fire department official in charge of the incident is authorized to abate summarily such hazardous conditions that are in violation of this code.
The
owner, operator or occupant of a building or premises deemed unsafe by the
fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other
approved corrective action.
See the provisions of the North Carolina Administrative Code and Policies and applicable North Carolina General Statutes.
Whenever the
fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the
fire code official is authorized to issue a stop work order.
A stop work order shall be in writing and shall be given to the
owner of the property, or to the
owner’s agent, or to the
person doing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order, and the conditions under which the cited work is authorized to resume.
Where an emergency exists, the
fire code official shall not be required to give a written notice prior to stopping the work.
Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine of not less than [AMOUNT] dollars or more than [AMOUNT] dollars.
The
fire code official shall have the authority to authorize disconnection of utility service to the building, structure or system in order to safely execute emergency operations or to eliminate an immediate hazard. The
fire code official shall notify the serving utility and, whenever possible, the
owner and occupant of the building, structure or service system of the decision to disconnect prior to taking such action if not notified prior to disconnection. The
owner or occupant of the building, structure or service system shall be notified in writing as soon as practical thereafter.
A
permit shall not be issued until the fees have been paid, nor shall an amendment to a
permit be released until the additional fee, if any, has been paid.
A fee for each
permit shall be paid as required, in accordance with the schedule as established by the applicable governing authority.
Any
person who commences any work, activity or operation regulated by this code before obtaining the necessary
permits shall be subject to an additional fee established by the applicable governing authority, which shall be in addition to the required
permit fees.
The payment of the fee for the construction,
alteration, removal or demolition of work done in connection to or concurrently with the work or activity authorized by a
permit shall not relieve the applicant or holder of the
permit from the payment of other fees that are prescribed by law.
The applicable governing authority is authorized to establish a refund policy.
No person shall knowingly maintain a fire
hazard.
For local modification, see the
provisions of the North Carolina Administrative Code and Policies
and applicable North Carolina General Statutes.
A list of jurisdictions shall be maintained
by the North Carolina Department of Insurance, Office
of State Fire Marshal.