ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.

1001.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter shall apply where a change of occupancy occurs, as defined in Section 202, including:
  1. Where the occupancy use is changed; or
  2. Where there is a change in occupancy classification or the occupancy group designation changes.
     Any repair or alteration work undertaken in connection with a change of occupancy shall conform to the other applicable chapters of this code.

1001.2 Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.

1001.2 Change in Occupancy With No Change of Occupancy Classification

AMENDMENT
This section has been amended at the state or city level.
A change in occupancy, as defined in Section 202, with no change of occupancy classification shall not be made to any structure that will subject the structure to any special provisions of the applicable International Codes, including the provisions of Sections 1002 through 1011, without the approval of the code official. A certificate of occupancy shall be issued where it has been determined that the requirements for the change in occupancy have been met.

1001.2.1 Change of Use

AMENDMENT
This section has been amended at the state or city level.

1001.2.1 Additional Requirements for Group A-2 Nightclubs

AMENDMENT
This section has been amended at the state or city level.
When a Group A-2 occupancy changes the use to a nightclub, fire protection shall be provided in accordance with Section 1012.2 in addition to the requirements of Section 1001.2.

1001.2.2 Repair and Alteration With No Change of Occupancy Classification

AMENDMENT
This section has been amended at the state or city level.
Any repair or alteration work undertaken in connection with a change of occupancy that does not involve a change of occupancy classification shall conform to the applicable requirements for the work as classified in Chapter 5 and to the requirements of Sections 1002 through 1011.

Exception: As modified in Section 1205 for historic buildings.

1001.2.2 1001.2.3 Change or Partial Change of Occupancy Classification or Group

AMENDMENT
This section has been amended at the state or city level.
Where the occupancy classification changes, the provisions of Sections 1002 through 1012 shall apply. This includes a change of occupancy classification within a group as well as a change of occupancy classification from one group to a different group.

1001.2.2.1 Partial Change of Occupancy

AMENDMENT
This section has been amended at the state or city level.

1001.3 Certificate of Occupancy Required

AMENDMENT
This section has been amended at the state or city level.
A new certificate of occupancy shall be required where a change of occupancy occurs that results in a different occupancy classification as determined by Chapter 3 of the International Building Code.
Where the character or use of an existing building or part of an existing building is changed to one of the following special use or occupancy categories as defined in the International Building Code, the building shall comply with all of the applicable requirements of the International Building Code:
  1. Covered and open mall buildings.
  2. Atriums.
  3. Motor vehicle-related occupancies.
  4. Aircraft-related occupancies.
  5. Motion picture projection rooms.
  6. Stages and platforms.
  7. Special amusement buildings.
  8. Incidental use areas.
  9. Hazardous materials.
  10. Ambulatory care facilities.
  11. Group I-2 occupancies.
An underground building in which there is a change of use shall comply with the requirements of the International Building Code applicable to underground structures.
Building elements and materials in portions of buildings undergoing a change of occupancy classification shall comply with Section 1012.

1004.1 General

AMENDMENT
This section has been amended at the state or city level.
Fire protection requirements of Section 1012 shall apply where a building or portions thereof undergo a change of occupancy classification.
Means of egress in portions of buildings undergoing a change of occupancy classification shall comply with Section 1012.

1006.1 General

AMENDMENT
This section has been amended at the state or city level.
Accessibility in portions of buildings undergoing a change of occupancy classification shall comply with Section 1012.9.

1007.1 Gravity Loads

AMENDMENT
This section has been amended at the state or city level.
Buildings or portions thereof subject to a change of occupancy where such change in the nature of occupancy results in higher uniform or concentrated loads based on Table 1607.1 of the International Building Code shall comply with the gravity load provisions of the International Building Code.

Exceptions:
  1. Structural elements whose stress is not increased by more than 10 percent.
  2. A change of occupancy from Group R-3 to Group B or E occupancy is permitted when the gravity live load is increased by 10 pounds per square foot (0.48 kN/m2) or less.
Buildings and structures subject to a change of occupancy where such change in the nature of occupancy results in higher wind or snow risk categories based on Table 1604.5 of the International Building Code shall be analyzed and shall comply with the applicable wind or snow load provisions of the International Building Code.

Exception: Where the new occupancy with a higher risk category is less than or equal to 10 percent of the total building floor area. The cumulative effect of the area of occupancy changes shall be considered for the purposes of this exception.
Existing buildings with a change of occupancy shall comply with the seismic provisions of Sections 1007.3.1 and 1007.3.2.
Where a building or portion thereof is subject to a change of occupancy that results in the building being assigned to a higher risk category based on Table 1604.5 of the International Building Code, the building shall comply with the requirements for International Building Code-level seismic forces as specified in Section 301.1.4.1 for the new risk category.

Exceptions:
  1. Where approved by the code official, specific detailing provisions required for a new structure are not required to be met where it can be shown that an equivalent level of performance and seismic safety is obtained for the applicable risk category based on the provision for reduced International Building Code-level seismic forces as specified in Section 301.1.4.2.
  2. Where the area of the new occupancy with a higher hazard category is less than or equal to 10 percent of the total building floor area and the new occupancy is not classified as Risk Category IV. For the purposes of this exception, buildings occupied by two or more occupancies not included in the same risk category, shall be subject to the provisions of Section 1604.5.1 of the International Building Code. The cumulative effect of the area of occupancy changes shall be considered for the purposes of this exception.
  3. Unreinforced masonry bearing wall buildings in Risk Category III when assigned to Seismic Design Category A or B shall be allowed to be strengthened to meet the requirements of Appendix Chapter A1 of this code [Guidelines for the Seismic Retrofit of Existing Buildings (GSREB)].
Where a change of occupancy is such that compliance with Section 1007.3.1 is required and the building is assigned to Risk Category IV, the operational access to the building shall not be through an adjacent structure, unless that structure conforms to the requirements for Risk Category IV structures. Where operational access is less than 10 feet (3048 mm) from either an interior lot line or from another structure, access protection from potential falling debris shall be provided by the owner of the Risk Category IV structure.
Where the occupancy of an existing building or part of an existing building is changed to one of the following special occupancies as described in NFPA 70, the electrical wiring and equipment of the building or portion thereof that contains the proposed occupancy shall comply with the applicable requirements of NFPA 70 whether or not a change of occupancy group is involved:
  1. Hazardous locations.
  2. Commercial garages, repair, and storage.
  3. Aircraft hangars.
  4. Gasoline dispensing and service stations.
  5. Bulk storage plants.
  6. Spray application, dipping, and coating processes.
  7. Health care facilities.
  8. Places of assembly.
  9. Theaters, audience areas of motion picture and television studios, and similar locations.
  10. Motion picture and television studios and similar locations.
  11. Motion picture projectors.
  12. Agricultural buildings.
Where the occupancy of an existing building or part of an existing building is changed, all unsafe conditions shall be corrected without requiring that all parts of the electrical system comply with NFPA 70.

1008.3 Service Upgrade

AMENDMENT
This section has been amended at the state or city level.
Where the occupancy of an existing building or part of an existing building is changed such that the new load requires an increase in service, the electrical service shall be upgraded to meet the requirements of NFPA 70 for the new occupancy.
Where the occupancy of an existing building or part of an existing building is changed, the number of electrical outlets shall comply with NFPA 70 for the new occupancy.
Where the occupancy of an existing building or part of an existing building is changed such that the new occupancy is subject to different kitchen exhaust requirements or to increased mechanical ventilation requirements in accordance with the International Mechanical Code, the new occupancy shall comply with the respective International Mechanical Code provisions.
Where the occupancy of an existing building or part of an existing building is changed such that the new occupancy is subject to increased or different plumbing fixture requirements or to increased water supply requirements in accordance with the International Plumbing Code, the new occupancy shall comply with the intent of the respective International Plumbing Code provisions.
If the new occupancy is a food-handling establishment, all existing sanitary waste lines above the food or drink preparation or storage areas shall be panned or otherwise protected to prevent leaking pipes or condensation on pipes from contaminating food or drink. New drainage lines shall not be installed above such areas and shall be protected in accordance with the International Plumbing Code.
If the new occupancy will produce grease or oil-laden wastes, interceptors shall be provided as required in the International Plumbing Code.
If the new occupancy will produce chemical wastes, the following shall apply:
  1. If the existing piping is not compatible with the chemical waste, the waste shall be neutralized prior to entering the drainage system, or the piping shall be changed to a compatible material.
  2. No chemical waste shall discharge to a public sewer system without the approval of the sewage authority.
If the occupancy group is changed to Group I-2, the plumbing system shall comply with the applicable requirements of the International Plumbing Code.

1011.1 Light and Ventilation

AMENDMENT
This section has been amended at the state or city level.
Natural Light and natural ventilation shall comply with the requirements of the International Building Code or North Carolina Residential Code for the new occupancy.

1012.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall apply to buildings or portions thereof undergoing a change of occupancy classification. This includes a change of occupancy classification within a group as well as a change of occupancy classification from one group to a different group or where there is a change of occupancy within a space where there is a different fire protection system threshold requirement in Chapter 9 of the International Building Code. Such buildings shall also comply with Sections 1002 through 1011. The application of requirements for the change of occupancy shall be as set forth in Sections 1012.1.1 through 1012.1.4. A change of occupancy, as defined in Section 202, without a corresponding change of occupancy classification shall comply with Section 1001.2. For the purposes of this section, Group R-3 shall also include detached one- and two-family dwellings and townhouses.

1012.1.1 Compliance With Chapter 9

AMENDMENT
This section has been amended at the state or city level.
Where alteration work is required by the change of occupancy classification, the requirements of Chapter 9 shall be applicable throughout the building for the most restrictive occupancy classification.

Exception: Where a portion of an existing building that is changed to a new occupancy classification and that portion is separated from the remainder of the building with fire barriers having a fire-resistance rating as required in the International Building Code for the separate occupancy, that portion shall comply with all of the requirements of Chapter 9 of this code for the most restrictive occupancy in the fire area and with the requirements of this chapter.

1012.1.1.1 Change of Occupancy Classification Without Separation

AMENDMENT
This section has been amended at the state or city level.

1012.1.1.2 Change of Occupancy Classification With Separation

AMENDMENT
This section has been amended at the state or city level.
The provisions of Sections 1012.2 and 1012.3 for fire protection and interior finish, respectively, shall apply to all buildings undergoing a change of occupancy classification.
The relative degree of hazard between different occupancy classifications shall be determined in accordance with the categories specified in Tables 1012.4, 1012.5 and 1012.6. Such a determination shall be the basis for the application of Sections 1012.4 through 1012.7.

1012.1.4 Accessibility

AMENDMENT
This section has been amended at the state or city level.
All buildings undergoing a change of occupancy classification shall comply with Section 1012.9.
Fire protection systems shall be provided in accordance with Sections 1012.2.1 and 1012.2.2.

1012.2.1 Fire Sprinkler System

AMENDMENT
This section has been amended at the state or city level.
Hazard categories in regard to fire sprinkler requirements shall be in accordance with Table 1012.2.1.

TABLE 1012.2.1
SPRINKLER HAZARD CATEGORIES
RELATIVE HAZARD OCCUPANCY USE CLASSIFCATIONS
1 (Highest Hazard) H, I, Nightclub
2 A-2, R-1, R-2
3 A-1, A-3
4 F-1, M, S-1
5 A-4, E
6 (Lowest Hazard) B, F-2, R-3, R-4, S-2, U

1012.2.1.1 Change to Higher Hazard Category

AMENDMENT
This section has been amended at the state or city level.
When a change of use is made to a higher hazard category as shown in Table 1012.2.1, the building shall be provided with an automatic fire suppression system as required by Section 903 of the North Carolina Building Code.

Exception: When an area of a building is changed to a higher hazard category and the proposed use is separated from the existing use(s) by assemblies that meet the applicable fire rating in Table 508.4 of the North Carolina Building Code, an automatic fire suppression system as required above shall be installed only in the area changed.

1012.2.1.2 Change to Equal or Lesser Hazard Category

AMENDMENT
This section has been amended at the state or city level.
When a change of use is made to an equal or lesser hazard category as shown in Table 1012.2.1, there is no requirement to install an automatic fire suppression system.

Exceptions:
  1. In areas where work being performed in connection with the change of use triggers a requirement for suppression.
  2. In windowless stories an automatic fire suppression system shall be installed as required by Section 903 of the North Carolina Building Code.

1012.2.1.3 Change in NFPA 13 Hazard Level

AMENDMENT
This section has been amended at the state or city level.
Notwithstanding the relative hazard as determined by Table 1012.2.1, when a change in the character of the use is made to a higher degree of hazard as defined by NFPA 13 (Light Hazard, Ordinary Hazard Group 1, Ordinary Hazard Group 2, Extra Hazard Group 1, Extra Hazard Group 2 and Special Occupancy Hazards), the sprinkler system shall be evaluated and, where required by NFPA 13, altered to conform to the required density and maximum sprinkler protection area per head for the proposed occupancy.

1012.2.2 Fire Alarm and Detection System and Carbon Monoxide Alarm System

AMENDMENT
This section has been amended at the state or city level.
Where a change in occupancy classification occurs or where there is a change of occupancy within a space where there is a different fire protection system threshold requirement in Chapter 9 of the International Building Code that requires a fire alarm and detection system or carbon monoxide alarm system to be provided based on the new occupancy in accordance with Chapter 9 of the International Building Code, such system shall be provided throughout the area where the change of occupancy occurs. Existing alarm notification appliances shall be automatically activated throughout the building. Where the building is not equipped with a fire alarm system, alarm notification appliances shall be provided throughout the area where the change of occupancy occurs in accordance with Section 907 of the International Building Code as required for new construction.
In areas of the building undergoing the change of occupancy classification, the interior finish of walls and ceilings shall comply with the requirements of the International Building Code for the new occupancy classification.

1012.4 Means of Egress, General

AMENDMENT
This section has been amended at the state or city level.
Hazard categories in regard to life safety and means of egress shall be in accordance with Table 1012.4.

TABLE 1012.4 MEANS OF EGRESS HAZARD CATEGORIES

RELATIVE HAZARD OCCUPANCY CLASSIFICATIONS
1 (Highest Hazard) H
2 I-2, I-3, I-4
3 A, E, I-1, M, R-1, R-2, R-4
4 B, F-1, R-3a, S-1
5 (Lowest Hazard) F-2, S-2, U
  1. Detached one- and two-family dwellings and townhouses are relative hazard 5.

1012.4.1 Means of Egress for Change to Higher Hazard Category

AMENDMENT
This section has been amended at the state or city level.
When a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1012.4, the means of egress shall comply with the requirements of Chapter 10 of the International Building Code.
Exceptions:
  1. Stairways shall be enclosed in compliance with the applicable provisions of Section 903.1.
  2. Existing stairways including handrails and guards complying with the requirements of Chapter 9 shall be permitted for continued use subject to approval of the code official.
  3. Any stairway replacing an existing stairway within a space where the pitch or slope cannot be reduced because of existing construction shall not be required to comply with the maximum riser height and minimum tread depth requirements.
  4. Existing corridor walls constructed on both sides of wood lath and plaster in good condition or 1/2 inch-thick (12.7 mm) gypsum wallboard shall be permitted where 1-hour rated separation is required. Such walls shall either terminate at the underside of a ceiling of equivalent construction or extend to the underside of the floor or roof next above.
  5. Existing corridor doorways, transoms and other corridor openings shall comply with the requirements in Sections 805.5.1, 805.5.2 and 805.5.3.
  6. Existing dead-end corridors shall comply with the requirements in Section 805.6.
  7. An existing operable window with clear opening area no less than 4 square feet (0.38 m2) and minimum opening height and width of 22 inches (559 mm) and 20 inches (508 mm), respectively, shall be accepted as an emergency escape and rescue opening.
When a change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 1012.4, existing elements of the means of egress shall comply with the requirements of Section 905 for the new occupancy classification. Newly constructed or configured means of egress shall comply with the requirements of Chapter 10 of the International Building Code.
Exception: Any stairway replacing an existing stairway within a space where the pitch or slope cannot be reduced because of existing construction shall not be required to comply with the maximum riser height and minimum tread depth requirements.

1012.4.3 Egress Capacity

AMENDMENT
This section has been amended at the state or city level.
Egress capacity shall meet or exceed the occupant load as specified in the International Building Code for the new occupancy.

Exception: The occupant load of the space may be restricted to comply with Section 1006 of the North Carolina Building Code. Signage indicating the allowed quantity of occupants shall be permanently mounted in the building at a location approved by the local fire marshal.
Existing stairways shall comply with the handrail requirements of Section 805.9 in the area of the change of occupancy classification.
Existing guards shall comply with the requirements in Section 805.11 in the area of the change of occupancy classification.

1012.5 Heights and Areas

AMENDMENT
This section has been amended at the state or city level.
Hazard categories in regard to height and area shall be in accordance with Table 1012.5.

TABLE 1012.5 HEIGHTS AND AREAS HAZARD CATEGORIES

RELATIVE HAZARD OCCUPANCY CLASSIFICATIONS
1 (Highest Hazard) Ha
2 A-1, A-2, A-3, A-4, Ia
3 E, F-1, R-1, R-2, R-4, S-1, M
4 (Lowest Hazard) B, F-2, S-2, A-5, R-3, U
  1. H-1 and I-2 are not permitted in Type VB construction.
When a change of occupancy classification is made to a higher hazard category as shown in Table 1012.5, heights and areas of buildings and structures shall comply with the requirements of Chapter 5 of the International Building Code for the new occupancy classification.
Exception: For high-rise buildings constructed in compliance with a previously issued permit, the type of construction reduction specified in Section 403.2.1 of the International Building Code is permitted. This shall include the reduction for columns. The high-rise building is required to be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Building Code.
In other than Groups H, F-1 and S-1, fire barriers and horizontal assemblies constructed in accordance with Sections 707 and 711, respectively, of the International Building Code shall be permitted to be used in lieu of fire walls to subdivide the building into separate buildings for the purpose of complying with the area limitations required for the new occupancy where all of the following conditions are met:
  1. The buildings are protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Fire Code.
  2. The maximum allowable area between fire barriers, horizontal assemblies, or any combination thereof shall not exceed the maximum allowable area determined in accordance with Chapter 5 of the International Building Code without an increase allowed for an automatic sprinkler system in accordance with Section 506 of the International Building Code.
  3. The fire-resistance rating of the fire barriers and horizontal assemblies shall be not less than that specified for fire walls in Table 706.4 of the International Building Code.
Exception: Where horizontal assemblies are used to limit the maximum allowable area, the required fire-resistance rating of the horizontal assemblies shall be permitted to be reduced by 1 hour provided the height and number of stories increases allowed for an automatic sprinkler system by Section 504 of the International Building Code are not used for the buildings.
When a change of occupancy classification is made to an equal or lesser hazard category as shown in Table 1012.5, the height and area of the existing building shall be deemed acceptable.
When a change of occupancy classification is made to a higher hazard category as shown in Table 1012.5, fire barriers in separated mixed use buildings shall comply with the fire-resistance requirements of the International Building Code.
Exception: Where the fire barriers are required to have a 1-hour fire-resistance rating, existing wood lath and plaster in good condition or existing 1/2-inch-thick (12.7 mm) gypsum wallboard shall be permitted.

1012.6 Exterior Wall Fire-Resistance Ratings

AMENDMENT
This section has been amended at the state or city level.
Hazard categories in regard to fire-resistance ratings of exterior walls shall be in accordance with Table 1012.6.

TABLE 1012.6 EXPOSURE OF EXTERIOR WALLS HAZARD CATEGORIES

RELATIVE HAZARD OCCUPANCY CLASSIFICATION
1 (Highest Hazard) H
2 F-1, Ma, S-1
3 A, B, E, I, R
4 (Lowest Hazard) F-2, S-2, U
  1. Group M occupancy of 12,000 square feet (1114 m2) or less shall be relative hazard category 3.
When a change of occupancy classification is made to a higher hazard category as shown in Table 1012.6, exterior walls shall have fire resistance and exterior opening protectives as required by the International Building Code.
Exception: A 2-hour fire-resistance rating shall be allowed where the building does not exceed three stories in height and is classified as one of the following groups: A-2 and A-3 with an occupant load of less than 300, B, F, M or S.
When a change of occupancy classification is made to an equal or lesser hazard category as shown in Table 1012.6, existing exterior walls, including openings, shall be accepted.
Openings in exterior walls shall be protected as required by the International Building Code. Where openings in the exterior walls are required to be protected because of their distance from the lot line, the sum of the area of such openings shall not exceed 50 percent of the total area of the wall in each story.
Exception:
  1. Where the International Building Code permits openings in excess of 50 percent.
  2. Protected openings shall not be required in buildings of Group R occupancy that do not exceed three stories in height and that are located not less than 3 feet (914 mm) from the lot line.
  3. Where exterior opening protectives are required, an automatic sprinkler system throughout may be substituted for opening protection.
  4. Exterior opening protectives are not required when the change of occupancy group is to an equal or lower hazard classification in accordance with Table 1012.6.
Enclosure of vertical shafts shall be in accordance with Sections 1012.7.1 through 1012.7.4.

1012.7.1 Minimum Requirements

AMENDMENT
This section has been amended at the state or city level.
Vertical shafts shall be designed to meet the International Building Code requirements for atriums or the requirements of this section.

Exception: Shafts for Group M occupancies in buildings that are less than 3,000 square feet (278 m2) or less per floor and three stories or less are not required to be enclosed.
When a change of occupancy classification is made to a higher hazard category as shown in Table 1012.4, interior stairways shall be enclosed as required by the International Building Code.
Exceptions:
  1. In other than Group I occupancies, an enclosure shall not be required for openings serving only one adjacent floor and that are not connected with corridors or stairways serving other floors.
  2. Unenclosed existing stairways need not be enclosed in a continuous vertical shaft if each story is separated from other stories by 1-hour fire-resistance-rated construction or approved wired glass set in steel frames and all exit corridors are sprinklered. The openings between the corridor and the occupant space shall have at least one sprinkler head above the openings on the tenant side. The sprinkler system shall be permitted to be supplied from the domestic watersupply systems, provided the system is of adequate pressure, capacity, and sizing for the combined domestic and sprinkler requirements.
  3. Existing penetrations of stairway enclosures shall be accepted if they are protected in accordance with the International Building Code.
Interior vertical shafts other than stairways, including but not limited to elevator hoistways and service and utility shafts, shall be enclosed as required by the International Building Code when there is a change of use to a higher hazard category as specified in Table 1012.4.
Exceptions:
  1. Existing 1-hour interior shaft enclosures shall be accepted where a higher rating is required.
  2. Vertical openings, other than stairways, in buildings of other than Group I occupancy and connecting less than six stories shall not be required to be enclosed if the entire building is provided with an approved automatic sprinkler system.

1012.7.4 Openings

AMENDMENT
This section has been amended at the state or city level.
All openings into existing fire-resistance-rated vertical shaft enclosures shall be protected by fire assemblies having a fire protection rating of not less than 1 hour and shall be maintained self-closing or shall be automatic-closing by actuation of a smoke detector. All other openings shall be fire protected in an approved manner. Existing fusible link-type automatic door-closing devices shall be permitted in all shafts except stairways if the fusible link rating does not exceed 135°F (57°C).

1012.8 Dwelling Unit Separation

AMENDMENT
This section has been amended at the state or city level.

1012.8.1 Townhouses

AMENDMENT
This section has been amended at the state or city level.
Existing buildings that establish new townhouse dwelling units shall comply with the separation requirements of Section R302.2 of the North Carolina Residential Code and related subsections.

1012.8.2 Two-Family Dwellings

AMENDMENT
This section has been amended at the state or city level.
Existing buildings that establish new detached two-family dwelling units shall comply with separation requirements of Section R302.3 of the North Carolina Residential Code and related subsections.

1012.8.3 Group I-1, R-1, R-2 or R3

AMENDMENT
This section has been amended at the state or city level.
Existing buildings that establish new Group I-1, R-1, R-2 or R-3 dwelling or sleeping units shall comply with separation requirements of Section 420 of the North Carolina Building Code.

1012.8 1012.9 Accessibility

AMENDMENT
This section has been amended at the state or city level.
Existing buildings that undergo a change of group or occupancy classification shall comply with this section.

Exception: Type B dwelling or sleeping units required by Section 1107 of the International Building Code are not required to be provided in existing buildings and facilities undergoing a change of occupancy in conjunction with less than a Level 3 alteration.

1012.8.1 1012.9.1 Partial Change in Occupancy

AMENDMENT
This section has been amended at the state or city level.
Where a portion of the building is changed to a new occupancy classification, any alteration shall comply with Sections 806 and 906, as applicable.

1012.8.2 1012.9.2 Complete Change of Occupancy

AMENDMENT
This section has been amended at the state or city level.
Where an entire building undergoes a change of occupancy, it shall comply with Section 1012.9.1 and shall have all of the following accessible features:
  1. At least one accessible building entrance.
  2. At least one accessible route from an accessible building entrance to primary function areas.
  3. Signage complying with Section 1111 of the International Building Code.
  4. Accessible parking, where parking is provided.
  5. At least one accessible passenger loading zone, where loading zones are provided.
  6. At least one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.
Where it is technically infeasible to comply with the new construction standards for any of these requirements for a change of group or occupancy, the above items shall conform to the requirements to the maximum extent technically feasible.

Exception: The accessible features listed in Items 1 through 6 are not required for an accessible route to Type B units.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING