ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.

Part 1 — Scope and Application

[A] 101.1 Title

AMENDMENT
This section has been amended at the state or city level.
These regulations shall be known as the North Carolina Building Code as adopted by the North Carolina Building Code Council on June 13, 2017 to be effective January 1, 2019. References to the International Code shall mean the North Carolina Codes. The North Carolina amendments to the International Code are underlined.

[A] 101.2 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code shall apply to the construction, alteration, relocation, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.
Exceptions: If any of the following apply the building or structure is exempt from the provisions of this code:
  1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories above grade plane in height with a separate means of egress, and their accessory structures not more than three stories above grade plane in height, shall comply with the International Residential Code.
  2. Farm buildings not used for:
    1. Sleeping purposes; or
    2. Storage of hazardous materials in excess of those listed in Tables 307.1(1) and 307.1(2) within the building rules jurisdiction of any municipality.
  3. The design construction, location, installation or operation of equipment for storing, handling and transporting liquefied petroleum gases for fuel purposes up to the outlet of the first stage pressure regulator, anhydrous ammonia or other liquid fertilizer.
  4. The design construction, location, installation or operation of equipment or facilities of a public utility, as defined in N.C.G.S. 62-3, or electric or telephone membership corporation, including without limitation poles, towers and other structures supporting electric or communication lines from the distribution network up to the meter location.

    Note: All buildings owned and operated by a public utility or an electric or telephone membership corporation shall meet the provisions of this code.
  5. The storage and handling of substances governed by the Hazardous Chemicals Right to Know Act in N.C.G.S. Chapter 95, Article 18.

[A] 101.2.1 Appendices

AMENDMENT
This section has been amended at the state or city level.
Provisions in the appendices shall not apply unless specifically adopted or referenced in this code.
The purpose of this code is to establish the minimum requirements to provide a reasonable level of safety, public health and general welfare through structural strength, means of egress facilities, stability, sanitation, adequate light and ventilation, energy conservation, and safety to life and property from fire and other hazards attributed to the built environment and to provide a reasonable level of safety to fire fighters and emergency responders during emergency operations.
The other codes listed in Sections 101.4.1 through 101.4.7 and referenced elsewhere in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference.
The provisions of the International Fuel Gas Code shall apply to the installation of gas piping from the point of delivery, gas appliances and related accessories as covered in this code. These requirements apply to gas piping systems extending from the point of delivery to the inlet connections of appliances and the installation and operation of residential and commercial gas appliances and related accessories.
The provisions of the International Mechanical Code shall apply to the installation, alterations, repairs and replacement of mechanical systems, including equipment, appliances, fixtures, fittings and/or appurtenances, including ventilating, heating, cooling, air-conditioning and refrigeration systems, incinerators and other energy-related systems.
The provisions of the International Plumbing Code shall apply to the installation, alteration, repair and replacement of plumbing systems, including equipment, appliances, fixtures, fittings and appurtenances, and where connected to a water or sewage system and all aspects of a medical gas system. The provisions of the International Private Sewage Disposal Code shall apply to private sewage disposal systems.

[A] 101.4.4 Property Maintenance

AMENDMENT
This section has been amended at the state or city level.
The provisions of the International Fire Code shall apply to matters affecting or relating to structures, processes and premises from the hazard of fire and explosion arising from the storage, handling or use of structures, materials or devices; from conditions hazardous to life, property or public welfare in the occupancy of structures or premises; and from the construction, extension, repair, alteration or removal of fire suppression, automatic sprinkler systems and alarm systems or fire hazards in the structure or on the premises from occupancy or operation.
The provisions of the International Energy Conservation Code shall apply to all matters governing the design and construction of buildings for energy efficiency.
The provisions of the International Existing Building Code shall apply to matters governing the repair, alteration, change of occupancy, addition to and relocation of existing buildings.

101.5 Requirements of Other State Agencies, Occupational Licensing Boards or Commissions

AMENDMENT
This section has been amended at the state or city level.
The North Carolina State Building Codes do not include all additional requirements for buildings and structures that may be imposed by other State agencies, occupational licensing boards and commissions. It shall be the responsibility of a permit holder, registered design professional, contractor or occupational licensing holder to determine whether any additional requirements exist.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall be applicable. Where, in any specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.
References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
The codes and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.4.1 and 102.4.2.
Where conflicts occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code or the International Codes listed in Section 101.4, the provisions of this code or the International Codes listed in Section 101.4, as applicable, shall take precedence over the provisions in the referenced code or standard.
In the event that any part or provision of this code is held to be illegal or void, this shall not have the effect of making void or illegal any of the other parts or provisions.

[A] 102.6 Existing Structures

AMENDMENT
This section has been amended at the state or city level.
The legal occupancy of any structure existing on the date of adoption of this code shall be permitted to continue without change, except as otherwise specifically provided in this code, the International Existing Building Code, or the International Fire Code.
A building or portion of a building that has not been previously occupied or used for its intended purpose in accordance with the laws in existence at the time of its completion shall comply with the provisions of the International Building Code or International Residential Code, as applicable, for new construction or with any current permit for such occupancy.

[A] 102.6.2 Buildings Previously Occupied

AMENDMENT
This section has been amended at the state or city level.
The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as otherwise specifically provided in this code, the International Fire Code, or as is deemed necessary by the building official for the general safety and welfare of the occupants and the public.

Part 2 — Administration and Enforcement

Section 103 Department of Building Safety

AMENDMENT
This section has been amended at the state or city level.

[A] 103.1 Creation of Enforcement Agency

AMENDMENT
This section has been amended at the state or city level.

[A] 103.2 Appointment

AMENDMENT
This section has been amended at the state or city level.

[A] 103.3 Deputies

AMENDMENT
This section has been amended at the state or city level.

Section 104 Duties and Powers of Building Official

AMENDMENT
This section has been amended at the state or city level.

[A] 104.1 General

AMENDMENT
This section has been amended at the state or city level.

[A] 104.2 Applications and Permits

AMENDMENT
This section has been amended at the state or city level.

[A] 104.3 Notices and Orders

AMENDMENT
This section has been amended at the state or city level.

[A] 104.4 Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 104.5 Identification

AMENDMENT
This section has been amended at the state or city level.

[A] 104.6 Right of Entry

AMENDMENT
This section has been amended at the state or city level.

[A] 104.7 Department Records

AMENDMENT
This section has been amended at the state or city level.

[A] 104.8 Liability

AMENDMENT
This section has been amended at the state or city level.

[A] 104.8.1 Legal Defense

AMENDMENT
This section has been amended at the state or city level.

[A] 104.9 Approved Materials and Equipment

AMENDMENT
This section has been amended at the state or city level.

[A] 104.9.1 Used Materials and Equipment

AMENDMENT
This section has been amended at the state or city level.

[A] 104.10 Modifications

AMENDMENT
This section has been amended at the state or city level.

[A] 104.10.1 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.

[A] 104.11 Alternative Materials, Design and Methods of Construction and Equipment

AMENDMENT
This section has been amended at the state or city level.

[A] 104.11.1 Research Reports

AMENDMENT
This section has been amended at the state or city level.

[A] 104.11.2 Tests

AMENDMENT
This section has been amended at the state or city level.

Section 105 Permits

AMENDMENT
This section has been amended at the state or city level.

[A] 105.1 Required

AMENDMENT
This section has been amended at the state or city level.

[A] 105.1.1 Annual Permit

AMENDMENT
This section has been amended at the state or city level.

[A] 105.1.2 Annual Permit Records

AMENDMENT
This section has been amended at the state or city level.

[A] 105.2 Work Exempt From Permit

AMENDMENT
This section has been amended at the state or city level.

[A] 105.2.1 Emergency Repairs

AMENDMENT
This section has been amended at the state or city level.

[A] 105.2.2 Repairs

AMENDMENT
This section has been amended at the state or city level.

[A] 105.2.3 Public Service Agencies

AMENDMENT
This section has been amended at the state or city level.

[A] 105.3 Application for Permit

AMENDMENT
This section has been amended at the state or city level.

[A] 105.3.1 Action on Application

AMENDMENT
This section has been amended at the state or city level.

[A] 105.3.2 Time Limitation of Application

AMENDMENT
This section has been amended at the state or city level.

[A] 105.4 Validity of Permit

AMENDMENT
This section has been amended at the state or city level.

[A] 105.5 Expiration

AMENDMENT
This section has been amended at the state or city level.

[A] 105.6 Suspension or Revocation

AMENDMENT
This section has been amended at the state or city level.

[A] 105.7 Placement of Permit

AMENDMENT
This section has been amended at the state or city level.

Section 106 Floor and Roof Design Loads

AMENDMENT
This section has been amended at the state or city level.

[A] 106.1 Live Loads Posted

AMENDMENT
This section has been amended at the state or city level.

[A] 106.2 Issuance of Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.

[A] 106.3 Restrictions on Loading

AMENDMENT
This section has been amended at the state or city level.

Section 107 Submittal Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.1 General

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2 Construction Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.1 Information on Construction Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.2 Fire Protection System Shop Drawings

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.3 Means of Egress

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.4 Exterior Wall Envelope

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5 Site Plan

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.5.1 Design Flood Elevations

AMENDMENT
This section has been amended at the state or city level.

[A] 107.2.6 Structural Information

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3 Examination of Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3.1 Approval of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3.2 Previous Approvals

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3.3 Phased Approval

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3.4 Design Professional in Responsible Charge

AMENDMENT
This section has been amended at the state or city level.

[A] 107.3.4.1 Deferred Submittals

AMENDMENT
This section has been amended at the state or city level.

[A] 107.4 Amended Construction Documents

AMENDMENT
This section has been amended at the state or city level.

[A] 107.5 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

Section 108 Temporary Structures and Uses

AMENDMENT
This section has been amended at the state or city level.

[A] 108.1 General

AMENDMENT
This section has been amended at the state or city level.

108.2 Conformance

AMENDMENT
This section has been amended at the state or city level.

[A] 108.3 Temporary Power

AMENDMENT
This section has been amended at the state or city level.

[A] 108.4 Termination of Approval

AMENDMENT
This section has been amended at the state or city level.

Section 109 Fees

AMENDMENT
This section has been amended at the state or city level.

[A] 109.1 Payment of Fees

AMENDMENT
This section has been amended at the state or city level.

109.2 Schedule of Permit Fees

AMENDMENT
This section has been amended at the state or city level.

[A] 109.3 Building Permit Valuations

AMENDMENT
This section has been amended at the state or city level.

[A] 109.4 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

[A] 109.5 Related Fees

AMENDMENT
This section has been amended at the state or city level.

[A] 109.6 Refunds

AMENDMENT
This section has been amended at the state or city level.

Section 110 Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 110.1 General

AMENDMENT
This section has been amended at the state or city level.

[A] 110.2 Preliminary Inspection

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3 Required Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.1 Footing and Foundation Inspection

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.2 Concrete Slab and Under-Floor Inspection

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.3 Lowest Floor Elevation

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.4 Frame Inspection

AMENDMENT
This section has been amended at the state or city level.

110.3.5 Lath, Gypsum Board and Gypsum Panel Product Inspection

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.6 Fire- And Smoke-Resistant Penetrations

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.7 Energy Efficiency Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.8 Other Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.9 Special Inspections

AMENDMENT
This section has been amended at the state or city level.

[A] 110.3.10 Final Inspection

AMENDMENT
This section has been amended at the state or city level.

110.3.10.1 Flood Hazard Documentation

AMENDMENT
This section has been amended at the state or city level.

110.4 Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.

110.5 Inspection Requests

AMENDMENT
This section has been amended at the state or city level.

110.6 Approval Required

AMENDMENT
This section has been amended at the state or city level.

Section 111 Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.

111.1 Use and Occupancy

AMENDMENT
This section has been amended at the state or city level.

111.2 Certificate Issued

AMENDMENT
This section has been amended at the state or city level.

111.3 Temporary Occupancy

AMENDMENT
This section has been amended at the state or city level.

111.4 Revocation

AMENDMENT
This section has been amended at the state or city level.

Section 112 Service Utilities

AMENDMENT
This section has been amended at the state or city level.

112.1 Connection of Service Utilities

AMENDMENT
This section has been amended at the state or city level.

112.2 Temporary Connection

AMENDMENT
This section has been amended at the state or city level.

112.3 Authority to Disconnect Service Utilities

AMENDMENT
This section has been amended at the state or city level.

Section 113 Board of Appeals

AMENDMENT
This section has been amended at the state or city level.

113.1 General

AMENDMENT
This section has been amended at the state or city level.

113.2 Limitations on Authority

AMENDMENT
This section has been amended at the state or city level.

113.3 Qualifications

AMENDMENT
This section has been amended at the state or city level.

Section 114 Violations

AMENDMENT
This section has been amended at the state or city level.

114.1 Unlawful Acts

AMENDMENT
This section has been amended at the state or city level.

114.2 Notice of Violation

AMENDMENT
This section has been amended at the state or city level.

114.3 Prosecution of Violation

AMENDMENT
This section has been amended at the state or city level.

114.4 Violation Penalties

AMENDMENT
This section has been amended at the state or city level.

Section 115 Stop Work Order

AMENDMENT
This section has been amended at the state or city level.

115.1 Authority

AMENDMENT
This section has been amended at the state or city level.

115.2 Issuance

AMENDMENT
This section has been amended at the state or city level.

115.3 Unlawful Continuance

AMENDMENT
This section has been amended at the state or city level.

Section 116 Unsafe Structures and Equipment

AMENDMENT
This section has been amended at the state or city level.

116.1 Conditions

AMENDMENT
This section has been amended at the state or city level.

116.2 Record

AMENDMENT
This section has been amended at the state or city level.

116.3 Notice

AMENDMENT
This section has been amended at the state or city level.

116.4 Method of Service

AMENDMENT
This section has been amended at the state or city level.

116.5 Restoration

AMENDMENT
This section has been amended at the state or city level.