Chapter 1 Material and Equipment Application Procedures

Chapter 2 Boiler Inspections

Chapter 3 Vacant and Unguarded Buildings

Chapter 4 Certificates of Occupancy, Live Loads and Occupancy Loads

Chapter 5 Concrete

Chapter 6 Cranes

Chapter 8 Demolition

Chapter 9 Rigging Operations

Chapter 10 Drums for Derrick Load and Boom Hoists

Chapter 11 Elevators, Escalators, Personnel Hoists and Moving Walks

Chapter 12 Emergency Power Systems

Chapter 13 Adjudications

Chapter 14 Fees [Repealed]

Chapter 15 Fire Protection

Chapter 16 Inspection of Existing Structures During Construction Operations

Chapter 17 Testing Laboratories and Testing Services

Chapter 18 Resistance to Progressive Collapse Under Extreme Local Loads

Chapter 19 Master Plumbers and Licensed Fire Suppression Piping Contractors

Chapter 20 Piping Systems

Chapter 21 Plans

Chapter 22 Pressure Tanks

Chapter 23 Noncommercial Greenhouses

Chapter 24 Refuse Chutes and Refuse Rooms

Chapter 25 Climber and Tower Crane Riggers

Chapter 27 Signs

Chapter 28 Smoke Detecting Devices and Systems and Carbon Monoxide Detecting Devices and Systems

Chapter 29 Sprinkler Systems

Chapter 30 Storage of Certain Waste Materials

Chapter 31 Suspension, Revocation or Limitation of Registration [Repealed]

Chapter 32 Walls [Repealed]

Chapter 33 Exemptions From Civil Penalties

Chapter 34 Electrical Code Rules

Chapter 35 Electrical Inspection

Chapter 36 Electrical Contractors

Chapter 37 Reference Standards

Chapter 38 Ventilation

Chapter 39 Cooling Towers and Evaporative Condensers

Chapter 40 Installation and Maintenance of Gas-Fueled Water and Space Heaters in All Portions of Dwellings Used or Occupied for Living Purposes

Chapter 41 Venting of Gas Water Heaters and Other Gas Appliances in Multiple Dwellings

Chapter 42 Entrance Doors, Locks and Intercommunication Systems

Chapter 43 Installation of Security Items in Multiple Dwellings

Chapter 44 Exemptions From Filing Requirements [Repealed]

Chapter 45 Building Permit Application Procedures

Chapter 46 Authorized Representatives

Chapter 48 Construction Superintendents [Repealed]

Chapter 49 Outdoor Signs

Chapter 50 Distributed Energy Resource Standards

Chapter 51 Dormitories

Chapter 52 Notification to the Department of Commencement of Work Pursuant to an Earthwork Permit

Chapter 100 [Administration; Enforcement; Maintenance of Buildings; Licensing; Miscellaneous Provisions]

Chapter 300 Use and Occupancy Classification

Chapter 400 Special Detailed Requirements Based on Use and Occupancy

Chapter 900 Fire Protection Systems

Chapter 1000 Means of Egress

Chapter 1100 Accessibility

Chapter 3000 Elevators and Conveying Systems

Chapter 3300 Safeguards During Construction and Demolition

Chapter 3500 Referenced Standards

Chapter 3600 Appendices

Chapter 4000 Electrical Code

Chapter 5000 New York City Energy Conservation Code

Chapter 6000 Fuel Gas Code

Chapter 7000 Mechanical Code

Chapter 8000 New York City Plumbing Code

Chapter 9000 Zoning

   (a)   Scope. This rule sets forth the criteria for the approval of building water conservation plans in accordance with Section PC C102.1 of Appendix C of the New York City Plumbing Code ("Plumbing Code"), which permits the use of waterless urinals only as part of an approved building water conservation plan.
   (b)   Compliance. Waterless urinals shall comply with national reference standard ANSI/ASME A112.19.19-2006.
   (c)   Definitions. For the purposes of this section, the following terms shall have the following meanings:
      (1)   Baseline water use. Water use calculated from the minimum number of plumbing fixtures required by the Plumbing Code and all additional fixtures as added by the design and/or as existing in the building, using the maximum flow rates permitted by Section PC 604 of the Plumbing Code and excluding the water-conserving strategies proposed in the building water conservation plan.
         (i)   The calculation for new buildings shall be in accordance with LEED NC Version 2.2, WE Credit 3, using Tables 2 and 5; Table 1 shall be replaced by PC Table 604.4; Tables 3 and 4 are not applicable.
         (ii)   The calculation for existing buildings shall be in accordance with LEED EB Version 2.0, WE Prerequisite 1, using Tables 3 and 4; Table 1 shall be replaced by PC Table 604.4; where existing fixtures are water-conserving, Table 2 shall be replaced by the flow rate listed on the fixture or published by the manufacturer.
      (2)   Design water use. Baseline water use, except that flow rates shall be the lesser of the manufacturer's published flow rates or the maximum flow rates permitted by Section PC 604 of the Plumbing Code, including all water-conserving strategies proposed in the building water conservation plan.
         (i)   The calculation for new buildings shall be in accordance with LEED NC Version 2.2, WE Credit 3, using Tables 2 and 4; Table 1 shall be replaced by PC Table 604.4; Table 3 shall be replaced by the lesser of the manufacturers' published flow rates or the maximum flow rates permitted by PC Table 604.4; Table 5 shall not apply.
         (ii)   The calculation for existing buildings shall be in accordance with LEED EB Version 2.0, WE Prerequisite 1, Table 3, and WE Credit 3, Table 4. Tables 1 in each of the prerequisite and the credit shall be replaced by PC Table 604.4. Flow rates for water-conserving flush and flow fixtures shall be taken from the manufacturers' published flow rates. Other tables in WE Prerequisite 1 and WE Credit 3 shall not apply.
      (3)   Leadership in Energy and Environmental Design ("LEED"). A set of building standards for sustainability, published by the United States Green Building Council.
      (4)   LEED NC Version 2.2. LEED for New Construction and Major Renovation ("NC"), Version 2.2, dated October 2007.
      (5)   LEED EB Version 2.0. LEED for Existing Buildings ("EB"), Version 2.0, dated October 2006.
      (6)   Waterless urinals. Urinals that discharge into a sanitary drainage system, but are not fed by the potable water supply system.
   (d)   Building water conservation plan. Any application for new building or alteration work that includes the installation of one or more waterless urinals shall include a building water conservation plan sealed and signed by a registered design professional, and signed by the building owner. Such building water conservation plan may be submitted by either the building owner or a tenant and shall include:
      (1)   A building water conservation analysis, demonstrating the means by which the building or tenant space will achieve the water reduction targets set forth below.
         (i)   New buildings. Potable water consumption, as projected by the design water use, shall be reduced by twenty (20) percent from the baseline water use calculated for the entire building, excluding irrigation supplied from the building.
         (ii)   Existing buildings. For alterations in buildings erected pursuant to plans approved under the 1968 building code or prior codes, potable water consumption, as projected by the design water use, shall be reduced by twenty (20) percent from the baseline water use calculated for the area of work of the alteration. For alterations in buildings erected pursuant to plans approved under the 2008 New York City Construction Codes, potable water consumption, as projected by the design water use, shall be reduced by twenty (20) percent from the baseline water use calculated for the entire building, excluding irrigation supplied from the building.
         (iii)   Water conservation measures. Water conservation measures utilized to achieve the efficiencies set forth in subparagraphs (i) and (ii) of this paragraph may include but are not limited to low-flow fixtures, waterless urinals, fixture sensors, metering controls and water recycling systems in compliance with Section PC C101 of Appendix C of the Plumbing Code.
      (2)   Manufacturer's specifications, installation recommendations and recommended maintenance procedures for the waterless urinals; and
      (3)   The building owner's or tenant's maintenance plan for the waterless urinals.
   (e)   Changes during design or construction. Any changes made to fixture specifications, occupant usage or other elements of the building water conservation plan or report during either design or construction shall require that a revised plan or report be submitted to the department for approval.
Resources