Chapter 1 Material and Equipment Application Procedures

Chapter 2 Boiler Inspections

Chapter 3 Vacant and Unguarded Buildings

Chapter 4 Certificates of Occupancy, Live Loads and Occupancy Loads

Chapter 5 Concrete

Chapter 6 Cranes

Chapter 8 Demolition

Chapter 9 Rigging Operations

Chapter 10 Drums for Derrick Load and Boom Hoists

Chapter 11 Elevators, Escalators, Personnel Hoists and Moving Walks

Chapter 12 Emergency Power Systems

Chapter 13 Adjudications

Chapter 14 Fees [Repealed]

Chapter 15 Fire Protection

Chapter 16 Inspection of Existing Structures During Construction Operations

Chapter 17 Testing Laboratories and Testing Services

Chapter 18 Resistance to Progressive Collapse Under Extreme Local Loads

Chapter 19 Master Plumbers and Licensed Fire Suppression Piping Contractors

Chapter 20 Piping Systems

Chapter 21 Plans

Chapter 22 Pressure Tanks

Chapter 23 Noncommercial Greenhouses

Chapter 24 Refuse Chutes and Refuse Rooms

Chapter 25 Climber and Tower Crane Riggers

Chapter 27 Signs

Chapter 28 Smoke Detecting Devices and Systems and Carbon Monoxide Detecting Devices and Systems

Chapter 29 Sprinkler Systems

Chapter 30 Storage of Certain Waste Materials

Chapter 31 Suspension, Revocation or Limitation of Registration [Repealed]

Chapter 32 Walls [Repealed]

Chapter 33 Exemptions From Civil Penalties

Chapter 34 Electrical Code Rules

Chapter 35 Electrical Inspection

Chapter 36 Electrical Contractors

Chapter 37 Reference Standards

Chapter 38 Ventilation

Chapter 39 Cooling Towers and Evaporative Condensers

Chapter 40 Installation and Maintenance of Gas-Fueled Water and Space Heaters in All Portions of Dwellings Used or Occupied for Living Purposes

Chapter 41 Venting of Gas Water Heaters and Other Gas Appliances in Multiple Dwellings

Chapter 42 Entrance Doors, Locks and Intercommunication Systems

Chapter 43 Installation of Security Items in Multiple Dwellings

Chapter 44 Exemptions From Filing Requirements [Repealed]

Chapter 45 Building Permit Application Procedures

Chapter 46 Authorized Representatives

Chapter 48 Construction Superintendents [Repealed]

Chapter 49 Outdoor Signs

Chapter 50 Distributed Energy Resource Standards

Chapter 51 Dormitories

Chapter 52 Notification to the Department of Commencement of Work Pursuant to an Earthwork Permit

Chapter 100 [Administration; Enforcement; Maintenance of Buildings; Licensing; Miscellaneous Provisions]

Chapter 300 Use and Occupancy Classification

Chapter 400 Special Detailed Requirements Based on Use and Occupancy

Chapter 900 Fire Protection Systems

Chapter 1000 Means of Egress

Chapter 1100 Accessibility

Chapter 3000 Elevators and Conveying Systems

Chapter 3300 Safeguards During Construction and Demolition

Chapter 3500 Referenced Standards

Chapter 3600 Appendices

Subchapter G Flood-resistant Construction
Subchapter K Modified Industry Standards For Elevators and Conveying Systems
Subchapter Q Modified National Standards For Automatic Sprinkler, Standpipe, and Fire Alarm Systems

Chapter 4000 Electrical Code

Chapter 5000 New York City Energy Conservation Code

Chapter 6000 Fuel Gas Code

Chapter 7000 Mechanical Code

Chapter 8000 New York City Plumbing Code

Chapter 9000 Zoning

Subchapter G Flood-resistant Construction

   (a)   Scope. This rule provides application submission requirements for alterations to structures located in areas of special flood hazard, provides the method for determining the market value of a structure, and provides the method for determining whether repairs, reconstructions, rehabilitations, additions or improvements constitute a substantial improvement.
   (b)   References. See Section BC G201.2 (definitions of market value of structure, substantial damage, and substantial improvement) and §28-104.7.11.
   (c)   Applicant's statement. Applicants shall include in every alteration application the statement: "Work proposed in this application (is/is not) included in a substantial improvement as defined by Section BC G201.2 and 1 RCNY §3606-01."
   (d)   Calculation of market value. To determine the market value of a structure, the applicant shall use either of the two calculation methods below:
      (1)   Assessment roll option. Applicants shall utilize dollar amounts provided by the Department of Finance's most recent "Final Assessment Roll" by multiplying the total market value by the ratio (market value of structure to total market value):
 
 
Market Value of Structure
=
Estimated Market Value (Total)
×
Actual AV (Total) - Actual AV (Land)
Actual AV (Total)
(See Example 1)
or
Market Value of Structure
=
Estimated Market Value (Total)
×
6-20% Limitation (Total) - 6-20% Limitation (Land)
6-20% Limitation (Total)
(See Example 2)
or
Market Value of Structure
=
Estimated Market Value (Total)
×
8-30% Limitation (Total) - 8-30% Limitation (Land)
8-30% Limitation (Total)
(See Example 3)
 
or, at the option of the owner, or where the assessment roll method would not reflect the market value of structure because more than one building occupies a single tax lot,
      (2)   Appraisal option. Applicants shall utilize dollar amounts obtained from an appraisal performed by a New York State licensed Real Estate Appraiser and performed within one year of the filing of the alteration application:
 
 
Market Value of Structure
=
Appraised Market Value (Land and Structure)
=
Appraised Market Value (Land)
 
   (e)   Calculation of cost. To determine the cost of repairs, reconstructions, rehabilitations, additions or improvements of a building or structure, the applicant shall add together:
      (1)   The costs for the given application, regardless of the time it takes to complete the work, plus
      (2)   The cost of all other work to be performed during the same period, including work filed under separate application(s) and including any minor alterations and ordinary repairs.
   (f)   Determination of substantial improvement. Work shall be deemed a substantial improvement if the cost as calculated in paragraph (e) equals or exceeds 50% of the market value of structure as calculated in paragraph (d). A substantial improvement shall also include work performed to a structure that has sustained substantial damage, as such term is defined in Section BC G201.2. In determining whether a structure has sustained substantial damage, the market value shall be calculated in accordance with paragraph (d) of this rule.
   (g)   Application for construction document approval. For an alteration that is not a substantial improvement with a cost exceeding the greater of (1) $40,000 or (2) 25% of the market value of the structure as calculated in subdivision (d) of this section, the applicant shall include calculations of the market value of the structure and costs as outlined in this rule, and shall include any relevant backup documentation including either the online printout of the Department of Finance Final Assessment Roll or a copy of the real estate appraisal.
   (h)   Examples of calculation of market value. The Assessment Information for the following examples is based on information from the Final Assessment Roll as provided by the Department of Finance.
      (1)   Example 1; Actual A/V. For the purposes of this example, the assessed values for both the land and the total for the property are indicated as follows:
 
 
DESCRIPTIONLAND TOTAL
ESTIMATED MARKET VALUE
814,000
ACTUAL AV
135,000
366,300
ACTUAL EX AV
0
136,080
TRANS AV
135,000
363,150
TRANS EX AV
0
136,080
 
The example property assessment roll indicates that the ESTIMATED MARKET VALUE is $814,000 for both the land and the structure. Using the values in the prescribed formula, the market value of only the structure is calculated as follows:
 
 
Market Value of Structure
=
Estimated Market Value (Total)
×
Actual AV (Total) - Actual AV (Land)
Actual AV (Total)
Market Value of Structure
=
$814,000
×
366,300 - 135,000
366,300
=
$814,000
×
63.15%
=
$514,041
 
      (2)   Example 2; 6-20% Limitation. For the purposes of this example, the assessed values for both the land and the total for the property are indicated as follows:
 
 
DESCRIPTIONLAND TOTAL
ESTIMATED MARKET VALUE
144,000
6-20% LIMITATION
2,040
5,702
ACTUAL EX AV
1,570
1,570
 
The example property assessment roll indicates that the ESTIMATED MARKET VALUE is $144,000 for both the land and the structure. Using the values in the prescribed formula, the market value of only the structure is calculated as follows:
 
 
Market Value of Structure
=
Estimated Market Value (Total)
×
6-20% Limitation (Total) - 6-20% Limitation (Land)
6-20% Limitation (Total)
Market Value of Structure
=
$144,000
×
5,702 - 2,040
5,702
=
$144,000
×
64.22%
=
$92,481
 
      (3)   Example 3; 8-30% Limitation. For the purposes of this example, the assessed values for both the land and the total for the property are indicated as follows:
 
 
DESCRIPTIONLAND TOTAL
ESTIMATED MARKET VALUE
391,000
8-30% LIMITATION
13,050
30,427
ACTUAL EX AV
0
0
 
The example property assessment roll indicates that the ESTIMATED MARKET VALUE is $391,000 for both the land and the structure. Using the values in the prescribed formula, the market value of only the structure is calculated as follows:
 
 
Market Value of Structure
=
Estimated Market Value (Total)
×
8-30% Limitation (Total) - 8-30% Limitation (Land)
8-30% Limitation (Total)
Market Value of Structure
=
$391,000
×
30,427 - 13,050 30,427
=
$391,000
×
57.11%
=
$223,302
 
(Am. eff. 7/30/2015)
   (a)   Scope. This section establishes procedures for processing letters of map change, including Letters of Map Amendment and Letters of Map Revision based on Fill.
   (b)   References. See §§ BC G102.3, G106.5, and G201.2 (definitions of letter of map amendment (LOMA) and letter of map revision based on fill (LOMR-F)) and §28-104.7.11.
   (c)   Letters of Map Amendment (LOMAs). Where the FEMA FIRMs 360497 indicate that a tax lot or structure is located within an area of special flood hazard, but the owner has obtained an approved LOMA from FEMA removing such tax lot or structure from areas of special flood hazard, the applicant shall nonetheless indicate on the application for construction document approval that the work is located within an area of special flood hazard. However, the work need not conform to the requirements of Appendix G of the Building Code provided (i) the applicant submits the approved LOMA with the application for construction document approval and (ii) the proposed work does not alter the grades on the site to be lower than those elevations specified in the LOMA. The examiner shall waive any required items relating to flood zones. Certificates of occupancy shall comply with Section BC G106.5.
   (d)   Letters of Map Revisions based on Fill (LOMR-Fs). The following procedures shall be followed where the owner requests that the Department sign a FEMA "Community Acknowledgment Form" in support of an application to FEMA for a LOMR-F (see 44 C.F.R. § 65.5). In no case shall fill be placed so as to raise the level of grade higher than curb level within a required yard or rear yard equivalent (see Zoning Resolution §§23-42, 33-22, and 43-22). The applicant shall undertake the following steps in the following order:
      (1)   Submit application for construction document approval. Work to re-grade a site in an A-Zone in order to remove land from an area of special flood hazard shall be performed pursuant to a work permit issued by the Department. Such work shall be allowed as either a separate earthwork application or as part of a new building or alteration application. The application for construction document approval shall include (i) through (v) below:
         (i)   The check-off in the box on the application that the work is located in an area of special flood hazard;
         (ii)   An "Initial Survey" of existing conditions showing 1'-0" contour lines;
         (iii)   No fewer than three sections traversing the entire parcel showing the base flood elevation, any proposed structures (including elevation of lowest floor), required yards and rear yard equivalents, levels of existing natural grade, levels of grade to be removed, final levels of compacted fill, and final levels of uncompacted topsoil. Additional sections shall be required when necessary to adequately depict that the work proposed complies with the code. All levels shall be indicated in NGVD with borough datum in parentheses;
         (iv)   An "Initial LOMR-F Flood Zone Certification" by the registered design professional who is the applicant, stating:
            "In accordance with FEMA's Technical Bulletin 10-01 and in accordance with accepted professional practice, I, ________, certify that the design for the aforementioned development is reasonably safe from flooding and that the design of the development will not increase the risk of flooding to surrounding areas. Additionally, I certify that the design complies with the requirements of Appendix G of the Building Code, and that the level of compacted fill adjacent to all structures in the development, exclusive of uncompacted topsoil, is proposed to be at or above the base flood elevation. Further, I certify that no fill is proposed to be placed in the regulatory floodway or in an area designated as a V-Zone. Further I certify that all applicable Federal, State, and local laws shall be complied with, and all Federal, State, and local permits required for the proposed work have been obtained and submitted into the folder for this job" and
         (v)   Identification of special inspection for fill placement and of evaluation of in-place density in accordance with Sections BC 1704.7.2 and 1704.7.3 (to be certified prior to sign-off). Compaction standards shall be as referenced in FEMA Technical Bulletin 10-01.
      (2)   Obtain approval of construction documents.
      (3)   Submit application to FEMA for Conditional LOMR-F (CLOMR-F) (optional). While the CLOMR-F is an optional step, it provides preconstruction assurance that FEMA will approve the Final LOMR-F if constructed in accordance with the approved plans. At any time after construction document approval, the applicant may present to the Borough Commissioner for the Borough Commissioner's review and signature a FEMA "Community Acknowledgement Form" (which shall indicate "Conditional LOMR-F" in the "Community Comments" section), along with the approved construction documents. The owner may submit this signed Community Acknowledgement Form to FEMA. If the owner elects not to undertake the actions specified in this paragraph three, the owner must nonetheless follow the procedures and take the actions specified in paragraphs four through eight of this subdivision, however, in such case, there will be no preconstruction assurance that FEMA will ultimately approve the Final LOMR-F.
      (4)   Obtain work permit.
      (5)   Complete all grading, fill, and foundation work.
      (6)   Present Community Acknowledgement Form to Borough Commissioner. After the completion of all grading, fill and foundation work, the applicant shall present to the Borough Commissioner for review and signature a FEMA Community Acknowledgement Form, along with the approved plans and following list of additional required items:
         (i)   A "Final Survey" of completed conditions showing 1'-0" contour lines;
         (ii)   Certification of completion for the special inspections for fill placement and of evaluation of in-place density. Compaction standards shall be as referenced in FEMA Technical Bulletin 10-01; and
         (iii)   A "Final LOMR-F Flood Zone Certification" by the registered architect or professional engineer who is the applicant on the PW-1, stating:
"In accordance with FEMA's Technical Bulletin 10-01 and in accordance with accepted professional practice, I, __________________________ , certify that all grading, fill and foundation work is complete, that the design for and construction of the aforementioned development is reasonably safe from flooding and that the design for and construction of the development will not increase the risk of flooding to surrounding areas. I have thoroughly reviewed the annexed "Initial Survey", "Final Survey" and the special inspection reports for fill placement and evaluation of in-place density. Further, I certify that all the work complies with the requirements of Appendix G of the Building Code, and that the level of compacted fill adjacent to all structures in the development, exclusive of uncompacted topsoil, is at or above the base flood elevation. Additionally, I certify that no fill has been placed in the regulatory floodway or in a designated V-Zone. Further, I certify that all applicable Federal, State, and local laws have been complied with, and all Federal, State, and local permits required for the work have been obtained and submitted into the folder for this job".
      (7)   Apply to FEMA for Final LOMR-F. After the Borough Commissioner signs the Community Acknowledgement Form, the owner shall submit such signed form to FEMA.
      (8)   Submit to the Department the approved LOMR-F and either a signed elevation certificate or dry floodproofing certificate as required pursuant to Section BC G 105.3. No certificate of occupancy or other final signoff shall be issued by the Department unless and until the applicant submits to the Department the Final LOMR-F approved by FEMA and either a signed elevation certificate or dry floodproofing certificate, and until all documents and submissions required by this rule are microfilmed into the permanent records of the Department. Certificates of occupancy shall comply with Section BC G 106.5.
Pursuant to §28-103.19 of the Administrative Code, the reference standard FEMA FIRMs 360497, as identified in Section BC G402 of the Building Code, is modified for New York City to read as follows:
 
FEMA
FIRMs 360497
Flood Insurance Rate Map, Community Number 360497, Panel Numbers 1 through 0457, Revised September 5, 2007;
Federal Emergency Management Agency, with the following Letter of Map Revision:
Letter of Map Revision effective September 29, 2008, FEMA case #08-02-0948P, revising FIRM panel 0111.

G102.2, G102.3, G102.3.1, G102.3.2, G103.3, G201.2
 

Subchapter K Modified Industry Standards For Elevators and Conveying Systems

(Repealed eff. 8/24/2015)
(Repealed eff. 8/24/2015)
Pursuant to Section 28-103.19 of the New York City Administrative Code and Section BC 3008 of the New York City Building Code, Section 2.27 of American Society of Mechanical Engineers A17.1-2000, with supplements A17.1 a-2002 and A17.1 b-2003, as modified by Chapter K1 of Appendix K of the New York City Building Code, is hereby amended to read as follows:
SECTION 2.27
EMERGENCY OPERATION AND SIGNALING DEVICES
2.27.5 Firefighters' emergency operation: automatic elevators with designated-attendant operation
Delete and revise Section 2.27.5.1 to read as follows:
   2.27.5.1 When designated-attendant operation is not in effect, elevators shall conform to 2.27.3 and when Occupant Evacuation Operation is provided shall also conform to 2.27.11.6.
Delete and revise Section 2.27.5.2 to read as follows:
   2.27.5.2 When operated by a designated attendant in the car.
   (a)   elevators parked at the recall level shall conform to 2.27.3 and when Occupant Evacuation Operation is provided shall also conform to 2 27.11.6 without delay: elevators parked at a floor other than the recall level shall conform to 2.27.3.1.6(h). At the completion of a time delay of not less than 10 seconds and not more than 30 seconds, elevators parked at a floor away from the recall level shall conform to 2.27.3 and when Occupant Evacuation Operation is provided shall also conform to 2.27.11.6.
   (b)   a moving car shall conform to 2.27.3 and when Occupant Evacuation Operation is provided shall also conform to 2.27.11.6.
   Exception. The provisions of Section 2.27.5.2 do not apply to hospital service.
Delete and revise Section 2.27.5.3 to read as follows:
   2.27.5.3 When an elevator that is provided with Firefighters' Emergency Operation or Occupant Evacuation Operation is on hospital service, a visual signal as shown in Fig. 2.27.3.1.6(h) shall illuminate and a continuous audible signal, audible within the car, shall sound when a "FIRE RECALL" switch (see 2.27.3.1 and 2.27.11.1.2) is in the "FIREMEN SERVICE" position, or when a fire alarm initiating device (see 2.27.3.2) is activated to alert the operator of an emergency. There may be a means located in the car for manually silencing the audible signal, after the signal has been active for at least 5 seconds.
      The signal shall be automatically reactivated when the doors open.
   The car shall remain under control of the operator until removed from hospital service. An elevator on Firefighters' Emergency Operation or Occupant Evacuation Operation shall not be placed on hospital service.
Delete and revise Section 2.27.6 to read as follows:
2.27.6 Firefighters' emergency operation, occupant evacuation operation: inspection operation
   When an elevator that is provided with Firefighters' Emergency Operation or Occupant Evacuation Operation is on inspection operation (see 2.26.1.4 and 2.26.1.5) or when a hoistway access switch has been enabled (see 2.12.7.3.3(a)), a continuous audible signal, audible at the location where the inspection operation is activated, shall sound when a "FIRE RECALL" switch (see 2.27.3.1 and 2.27.11.1.2) is in the "ON" position or when the fire alarm initiating device (see 2.27.3.2 and 2.27.11.5) is activated to alert the operator of an emergency. The car shall remain under the control of the operator until removed from inspection operation or hoistway access operation. Inspection operation or hoistway access operation shall take precedence over Phase I Emergency Recall Operation, Phase II Emergency In-Car Operation, and Occupant Evacuation Operation.
Add new Section 2.27.11 to read as follows:
2.27.11 Occupant evacuation operation
   Where elevators are provided for occupant evacuation, Occupant Evacuation Operation (OEO) shall be provided to function prior to Firefighter's Emergency Operation and shall conform to 2.27.11.1 through 2.27.11.6.
Note: See also Nonmandatory Appendix V for additional information.
   2.27.11.1 The requirements of 2.27.3.1 are modified as follows.
      2.27.11.1.1 The two-position switch in the lobby (2.27.3.1.1) and two-position switch in the fire command center (2.27.3.1.2) shall be labeled "BANK FIRE RECALL" and indicate the elevator bank that they control.
      2.27.11.1.2 An additional two-position key operated individual "CAR FIRE RECALL" switch per elevator, that will not change position without a deliberate action by the user, shall be located in the lobby at the designated level adjacent to the elevator it controls. Each switch shall be labeled "CAR FIRE RECALL" (with the car identification, as specified in 2.29.1, inserted), and its positions marked "NORMAL" and "FIREMEN SERVICE" (in that order) in letters a minimum of 5 mm (0.25 in.) high. Text shall be black on a yellow background. Each switch shall control the associated elevator in conformance with 2.27.3.1.6, but shall not control the other elevators controlled by the "BANK FIRE RECALL" switch (see 2.27.11.1.1).
      2.27.11.1.3 Each individual "CAR FIRE RECALL" switch shall terminate Occupant Evacuation Operation for the elevator it controls when placed in the "FIREMEN SERVICE" position. Each "BANK FIRE RECALL" switch shall terminate Occupant Evacuation Operation for the elevators it controls when placed in the "FIREMEN SERVICE" position.
      2.27.11.1.4 Each individual "CAR FIRE RECALL" switch shall be provided with an illuminated visual signal to indicate when Phase I Emergency Recall Operation is in effect for that car (see 2.27.3.1.5).
      2.27.11.1.5 To remove an individual elevator from Phase I Emergency Recall Operation, the individual "CAR FIRE RECALL" switch shall be rotated to the "NORMAL" position, provided that
      (a)   the "BANK FIRE RECALL SWITCH" and the additional two-position "BANK FIRE RECALL" switch, where provided, are in the "NORMAL" position; and
      (b)   no fire alarm initiating device is activated (see 2.27.3.2).
      2.27.11.1.6 A car with its individual "CAR FIRE RECALL" switch in the "FIREMEN SERVICE" position shall not be removed from Phase I Emergency Recall Operation when the "BANK FIRE RECALL" switch is rotated to the "NORMAL" position.
      2.27.11.1.7 At the elevator designated level, only the door(s) serving the lobby where the "BANK FIRE RECALL" switch is located shall open.
   2.27.11.2 The sign required by 2.27.9 shall not be installed. A variable message sign, as defined in ANSI/ICC A117.1, shall be installed for each elevator bank on each landing served It shall be located not less than 2 130 mm (84 in.) and not more than 3 000 mm (120 in.) above the floor and in a central visible location within the elevator lobby. Message text shall be a minimum of 50 mm (2 in.) high and conform to ANSI/ICC A117.1. The variable message signs shall be powered by the same power supply as the elevator, including emergency or standby power.
      When the elevators are not on Occupant Evacuation Operation or Firefighters' Emergency Operation, the variable message signs shall not display other elevator system status messages.
   2.27.11.3 Where hoistway pressurization is provided, a car on Phase I Emergency Recall, after completing the requirements of 2.27.3.1.6,, shall conform to the following:
   (a)   A car shall close its doors after 15 seconds.
   (b)   Door reopening devices, door force limiting devices, kinetic energy limiting devices, and the door open button shall remain active.
   (c)   At least one operating device normally used to call a car to the landing (e.g., hall call button, keypad) shall be located in the elevator lobby at the elevator designated level. Actuating this device shall cause all recalled cars to open their doors for 30 seconds to 45 seconds, then reclose.
   2.27.11.4 A position indicator shall be provided at the elevator designated level above or adjacent to the entrance for each car. The position indicator shall be powered by the same power supply as the elevator, including emergency or standby power.
   2.27.11.5 Fire alarm system interface.
      2.27.11.5.1 Upon activation of an automatic fire alarm initiating device in the building in any area that does not initiate Phase I recall in this bank, the fire alarm system shall provide signals to the elevator system in conformance with NFPA 72, as modified by Appendix Q of the New York City Building Code and any applicable rules, indicating the floors to be evacuated. The floors to be evacuated shall be a contiguous block of floors, consisting of at least the floor with an active alarm, one floor above and one floor below. The elevator system shall initiate Occupant Evacuation Operation in accordance with 2.27.11.6 for the indicated floors. If activation of an automatic fire alarm initiating device which does not initiate Phase I recall in this bank occurs on any additional floor at any time while Occupant Evacuation Operation in accordance with 2.27.11.6 is in effect, the evacuation zone shall be expanded to include all floors with an active alarm, all floors between the highest and lowest floor with an active alarm plus one floor above the highest floor with an active alarm and one floor below the lowest floor with an active alarm. If the active alarm is on the elevator designated level, automatic initiation of Occupant Evacuation Operation in accordance with 2.27.11.6 shall not be permitted. Initiation by authorized or emergency personnel shall be provided through manual operation of the fire alarm system.
      For the purposes of this section, an active alarm refers to the condition caused by the activation of an automatic fire alarm initiating device.
      2.27.11.5.2 A means to initiate total building evacuation, labeled "ELEVATOR TOTAL BUILDING EVACUATION," shall be provided at the fire command center location and installed in accordance with NFPA 72, as modified by Appendix Q of the New York City Building Code and any applicable rules. When this means is actuated, the fire alarm system shall provide a signal to the elevator system indicating that all floors are to be evacuated. The means to initiate total building evacuation shall be keyed as New York City standard #2642 and FDNY standard key.
   2.27.11.6 When any of the signals provided in 2.27.11.5 actuate, the elevators shall conform to 2.27.11.6.1 through 2.27.11.6.10 in order to move occupants from the floors affected by the fire to the elevator designated level.
      2.27.11.6.1 The variable message signs required by 2.27.11.2 shall indicate one of the following messages:
      (a)   On all floors being evacuated, they shall indicate that the elevators are available for evacuation and the estimated time duration in minutes for the next elevator to arrive.
      Text shall read: "Elevators and stairs available for evacuation. Next car in about "X" minutes."
      (b)   On all floors not being evacuated, they shall indicate that elevator service is not available.
      Text shall read: "Elevators temporarily dedicated to other floors"
      (c)   On the elevator designated level, they shall indicate that the cars are in evacuation mode and that passengers should not use elevators.
      Text shall read: "Elevators dedicated to evacuation. Do not enter elevator."
      (d)   If no elevators are available for Occupant Evacuation Operation (fire service, inspection, shut off, etc.), they shall indicate that elevator service is not available.
      On all floors being evacuated they shall also indicate that occupants should use the stairs.
      Text for floors being evacuated: "Elevators out of service. Use stairs to evacuate." Text for other floors: "Elevators out of service."
      2.27.11.6.2 Automatic visual signal or variable message sign, and voice notification in each car shall indicate that the car is being used to evacuate the building.
      In the event that the car stops to pick up passengers at a floor other than the elevator designated level, the signals shall instruct the passengers to remain in the car.
      Upon or prior to arrival at the elevator designated level, passengers shall be notified that they have arrived at the exit floor and to exit quickly. Message text shall be a minimum of 25 mm (1 in.) high and conform to ANSI/ICC A117.1. Voice notification shall be at least 10 dBA above ambient but not more than 80 dBA measured 1 525 mm (60 in.) above the floor, at the center of the car.
      2.27.11.6.3 All landing calls outside of the contiguous block of floors being evacuated shall be canceled and disabled. Building security systems that limit service to these floors shall be overridden. Any landing call within the contiguous block of floors shall call an elevator or elevators to that landing. Landing calls entered at the floor with an active alarm shall be given higher priority than the calls at the floors above and below it. If a subsequent active alarm is received from a different floor, the evacuation priority shall be assigned in the sequence received. Once passengers have entered an elevator, it shall proceed only towards the elevator designated level. When total building evacuation is in effect and no calls are entered at an affected floor, priority shall be based on distance from the elevator designated level, with the furthest floor served getting highest priority.
      2.27.11.6.4 Car calls for all floors, except for the elevator designated level, shall be canceled and disabled.
      A car call for the elevator designated level shall be automatically entered when any landing call is answered.
      2.27.11.6.5 Cars that are unoccupied when Occupant Evacuation Operation is actuated shall move without delay to a floor that is being evacuated, and park with their doors closed until a landing call is registered. If the car is in motion away from the floors being evacuated, it shall stop at or before the next available floor, without opening the doors, reverse direction, and move to a floor that is being evacuated.
      2.27.11.6.6 Cars that are occupied when Occupant Evacuation Operation is actuated shall proceed without delay to the elevator designated level. Any reversal of travel direction that is needed shall be done at or before the next available floor without opening the doors. After opening and closing the doors at the elevator designated level, the cars shall proceed without delay to a floor that is being evacuated and park with their doors closed until a landing call is registered.
      2.27.11.6.7 When a car answers a landing call at a floor being evacuated, a car call for the elevator discharge level shall be automatically registered. The system shall accept a new landing call as soon as the doors have opened to permit loading at that floor, or sooner. If a new landing call is registered at this floor, it shall be assigned to another car, and not canceled until that car arrives. Actuation of the landing call device shall not prevent a loaded car from closing its doors and leaving the floor.
      2.27.11.6.8 While passengers are entering the car at a floor being evacuated, when the load reaches no greater than 80% of car capacity, the door reopening device(s) shall be disabled and the doors shall initiate closing at reduced kinetic energy in accordance with 2.13.4.2.1(c). If the doors stall while closing, they shall reopen fully, then close. An audible signal shall sound until the doors are closed. If the load exceeds 100% of capacity, the doors shall reopen and remain open and a voice notification and visual signal shall indicate that the car is overloaded.
      2.27.11.6.9 Once the block of floors being evacuated has been evacuated, as indicated by a 60 second period in which no landing calls are registered, one car shall park with its doors closed at the lowest floor of the block of floors ready to answer subsequent landing calls within the block of floors: the rest shall park with doors closed at the elevator designated level. A car parked at the elevator designated level shall replace the car at the lowest floor of the block that has answered a landing call.
      2.27.11.6.10 Occupant Evacuation Operation shall be terminated when the fire alarm system is reset or the signals provided in 2.27.3.2 are actuated (see 2.27.11.1.3).
Add new Section 2.27.12 to read as follows:
2.27.12 Inspections and tests
   2.27.12.1 Annual inspections and tests. All elevators provided with Occupant Evacuation Operation shall be subjected, by authorized personnel, to a check of the operation in conjunction with the fire alarm system testing in accordance with the requirements of NFPA 72. as modified by Appendix Q of the New York City Building Code and any applicable rules. Deficiencies shall be corrected. A record of findings shall be available to elevator personnel and the authority having jurisdiction. These tests and inspections are not part of the Category 1 or Category 5 tests or inspections.
   2.27.12.2 Acceptance tests. Acceptance tests shall be performed jointly by the fire alarm installer and the elevator system installer in conjunction with NFPA 72, as modified by Appendix Q of the New York City Building Code and any applicable rules. Acceptance tests shall also verify conformance with 2.27.11.
(Eff. 8/24/2015)
Pursuant to Section 28-103.19 of the New York City Administrative Code and Section BC 3001.2 of the New York City Building Code, Section 2.27.3.5 of American Society of Mechanical Engineers A17.1-2000, with supplements A17.1a-2002 and A17.1b - 2003, as modified by Chapter K1 of Appendix K of the New York City Building Code, is hereby amended to read as follows:
SECTION 2.27
EMERGENCY OPERATION AND SIGNALING DEVICES
Delete and revise Section 2,27,3.5 to read as follows:
   2.27.3.5 Multicompartment Elevators. Multicompartment elevators shall also conform to 2.27.3.5.1 through 2.27.3.5.10 and shall be designed to have a usable hoistway entrance for the lower compartment when the upper compartment is at the designated or alternate level. When the upper compartment has been recalled to the designated or alternate level and Phase I Emergency Recall Operation is in effect, the car and hoistway doors for both compartments shall open.
Delete and revise Section 2.27.3.5.1 to read as follows:
   2.27.3.5.1 The "FIRE RECALL" switch (2.27.3.1) shall be located at the designated level served by the upper compartment. Where a sky lobby exists, a "FIRE RECALL" switch shall also be located at the floor served by the upper compartment that is immediately above the sky lobby level. This level above the sky lobby level shall be the sky lobby designated level.
Delete and revise Section 2.27.3.5.2 to read as follows:
   2.27.3.5.2 The Phase II Emergency In-Car Operation switch (see 2.27.3.3) shall be located in the upper compartment.
Add new Sections 2.27.3.5.3 through 2.27.3.5.10 to read as follows:
   2.27.3.5.3 A visual and audible signal (see 2.27.3.1.6(h)) shall be provided in the main car operating panel of both the upper and lower compartments.
   2.27.3.5.4 A minimum 3" diagonal video display shall be installed in the car operating panel of the upper compartment so that the entire floor area in the lower compartment is visible. The display shall show the lower compartment when the upper deck is on Phase I Emergency Recall Operation and is at the designated level with the car doors open and shall remain on during Phase II Emergency In-Car Operation.
   2.27.3.5.5 Moving the Phase II Emergency In-Car Operation key switch to the "FIREMAN SERVICE" position shall result in locking out the lower compartment.
   (a)   When placed in the "FIREMAN SERVICE" position, the control system shall:
      (1)   disable all door reopening devices in the lower compartment; and
      (2)   initiate closing of the lower compartment doors in accordance with 2.13.4.2.1(c).
   (b)   When the upper compartment is stopped at the designated level, the Phase II Emergency In-Car Operation key switch is in the "NORMAL" position and Phase I Emergency Recall Operation is in effect, the lower compartment doors shall be opened.
   2.27.3.5.6 Two-way hands-free voice communication shall be established between the upper and lower compartments when the elevator is on Phase I Emergency Recall Operation, the upper compartment is at the designated or alternate level, and the car and hoistway doors are open. Voice communication between the two compartments shall be maintained until such time as the elevator is returned to normal service.
   2.27.3.5.7 A switch labeled "LOWER COMPARTMENT RECOVERY" with two positions marked "OFF" and "ON" shall be located adjacent to the elevator at the designated level. The key shall only be removable when the switch is in the "OFF" position.
   (a)   When the switch is in the "ON" position, the doors of the upper and lower compartments shall close in accordance with 2.13.4.2.1(c), and the lower compartment shall move to the designated level.
   (b)   When the lower compartment arrives at the designated level, the doors of the lower compartment shall open and remain open until the switch is turned to the "OFF" position. The doors of the upper compartment shall remain closed.
   (c)   When the switch is turned to the "OFF" position, the doors of the lower compartment shall close and the upper compartment shall arrive at the designated level and open the doors.
      (1)   The doors of the upper compartment shall remain open until:
         (i)   the elevator is placed on Phase II Emergency In-Car Operation; or
         (ii)   the elevator is returned to normal operation.
      (2)   The doors of the lower compartment shall remain closed until such time as:
         (i)   the elevator is returned to normal operation:
         (ii)   the "LOWER COMPARTMENT RECOVERY" switch is operated and the lower compartment has returned to the designated level; or
         (iii)   the elevator is on "FIREMAN SERVICE" Phase I Emergency Recall Operation.
   2.27.3.5.8 Activation of a fire alarm initiating device at either the designated level or the level below the designated level shall cause the elevator(s) to travel to the alternate level.
   2.27.3.5.9 Activation of a fire alarm initiating device at the sky lobby or the level above the sky lobby (which is the sky lobby designated level) shall cause the elevator(s) to travel to the sky lobby alternate level.
   2.27.3.5.10 Alternate levels shall be located in accordance with the following provisions:
   (a)   Where no blind hoistway exists, the alternate level shall be three (3) levels above the designated level.
   (b)   Where blind hoistways exist, the alternate level shall be the second level above the blind hoistway.
   (c)   The sky lobby alternate level shall be three (3) levels above the sky lobby designated level.
(Eff. 10/26/2015)

Subchapter Q Modified National Standards For Automatic Sprinkler, Standpipe, and Fire Alarm Systems

Pursuant to Section 28-103.19 of the New York City Administrative Code, NFPA 72 (2010 edition) is hereby amended as follows:
Chapter 1 – Administration No changes.
Chapter 2 – Referenced Publications
2.1 Add at end the following: Where a referenced publication has been modified for the City of New York by the New York City Building Code or the rules of the Department of Buildings, every reference to such publication shall be deemed to include all such modifications.
2.2 Revise references to NFPA 13, 70 and 720, to read as follows:  NFPA 13, Standard for the Installation of Sprinkler Systems, as referenced in and modified by Appendix Q of the New York City Building Code.  NFPA 70, National Electrical Code, as referenced in and modified by the New York City Electrical Code.  NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, as referenced in and modified by 1 RCNY 908-01.
2.3.1 Revise references to ANSI/ASME A17.1a/CSA B44a, to read as follows:  ANSI/ASME A17.1a/CSA B44a, Safety Code for Elevators and Escalators, as referenced in and modified by Appendix K of the New York City Building Code.
2.4 Delete reference to NFPA 5000, and revise reference to NFPA 70, to read as follows:  NFPA 70, National Electrical Code, as referenced in and modified by the New York City Electrical Code.
Chapter 3 – Definitions No changes.
Chapter 4 – Reserved No changes.
Chapter 5 – Reserved No changes.
Chapter 6 – Reserved No changes.
Chapter 7 – Reserved No changes.
Chapter 8 – Reserved No changes.
Chapter 9 – Reserved No changes.
Chapter 10 – Fundamentals
10.4.1.1 Delete and replace with the following: Fire alarm system and emergency communication system plans and specifications shall be developed in accordance with the New York City Building Code by persons licensed and registered to practice the profession of engineering under the Education Law of the State of New York, who are also experienced in the proper design, application, installation, and testing of the system.
10.4.1.2 Delete.
10.4.2.1 Add at beginning the following: Fire alarm installations shall be performed by a New York City licensed electrical contractor.
10.4.3.1 Add at beginning the following: Fire alarm inspection, testing and maintenance shall be performed by a New York City licensed electrical contractor holding a New York State registration for "Business of Installing, Servicing or Maintaining Security or Fire Alarm Systems" or those fire alarm companies holding a New York State registration for "Business of Installing, Servicing or Maintaining Security or Fire Alarm Systems," and in accordance with rules and regulations promulgated by the Fire Commissioner.
10.5.3.1 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.3.2 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.3.3 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.3.4 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.4.1 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.4.2 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.4.3 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.5.1 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.5.2 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.5.3 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.5.4 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.6.1 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.6.2 Delete and replace with the following: Refer to the New York City Electrical Code for requirements.
10.5.6.3.1 Delete and replace with the following: The secondary power supply for fire alarm systems and supervising station facilities shall have sufficient capacity to operate the system in accordance with the New York City Electrical Code. The secondary power supply for other systems shall have sufficient capacity to operate the system under quiescent load (system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for 5 minutes, unless otherwise permitted or required by the following:
      (1)   Reserved.
      (2)   Reserved.
      (3)   Reserved.
      (4)   The secondary power supply for high-power speaker arrays used for wide-area mass notification systems shall be in accordance with 24.4.3.4.2.2.
      (5)   The secondary power supply for textual visible appliances shall be in accordance with 24.4.3.4.7.1.
      (6)   The secondary power supply capacity for central control stations of a wide-area mass notification systems shall be capable of supporting operations for a minimum of 24 hours.
      (7)   The secondary power supply for in-building mass notification systems shall be capable of operating the system under quiescent load for a minimum of 24 hours and then shall be capable of operating the system during emergency condition for a period of 15 minutes at maximum connected load.
Chapter 11 – Reserved No changes.
Chapter 12 – Circuits and Pathways No changes.
Chapter 13 – Reserved No changes.
Chapter 14 – Inspection, Testing and Maintenance
14.1.1 Delete and replace with the following: The inspection, testing and maintenance of systems, their initiating devices, and notification appliances shall comply with the requirements of this chapter and the New York City Fire Code.
14.1.2 Delete and replace with the following: The inspection, testing and maintenance of single- and multiple-station smoke and heat alarms and household fire alarm systems shall comply with the requirements of this chapter and the New York City Fire Code.
14.6.3 Delete and replace with the following: Supervising Station Records. For supervising station alarm systems, records pertaining to signals received at the supervising station that result from maintenance, inspection, and testing shall be maintained in accordance with the New York City Fire Code.
14.6.3.1 Delete.
14.6.3.2 Delete.
14.6.4 Delete.
Chapter 15 – Reserved No changes.
Chapter 16 – Reserved No changes.
Chapter 17 – Initiating Devices No changes.
Chapter 18 – Notification Appliances No changes.
Chapter 19 – Reserved No changes.
Chapter 20 – Reserved No changes.
Chapter 21 – Emergency Control Functions and Interfaces
21.3.3 Delete and replace with the following: Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and elevator machine room smoke detectors, sprinkler waterflow alarm-initiating devices, or other automatic fire detection as permitted by 21.3.7, and initiating devices used to initiate shutdown of elevator power in accordance with 21.4 shall be used to recall elevators for fire fighters' service.
21.3.12 Delete and replace with the following: Separate outputs from the fire alarm systems to the elevator controller(s) shall be provided to implement elevator Phase 1 Emergency Recall Operation in accordance with ANSI/ASME A17.1a/CSA B44a, Safety Code for Elevators and Escalators.
21.3.12.1 Delete and replace with the following: See ANSI/ASME A17.1a/CSA B44a, Safety Code for Elevators and Escalators, for designated and alternate levels of elevator recall.
21.3.12.2 Delete and replace with the following: See ANSI/ASME A17.1a/CSA B44a, Safety Code for Elevators and Escalators, for designated and alternate levels of elevator recall.
21.3.12.3 Delete and replace with the following: See ANSI/ASME A17.1a/CSA B44a, Safety Code for Elevators and Escalators, for designated and alternate levels of elevator recall.
21.4.2 Delete and replace with the following: If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 24 in. (610 mm) of each sprinkler head and be installed in accordance with the requirements of Chapter 17. Upon activation of the heat detector used for elevator power shutdown, there shall be permitted to be a delay in the activation of the power shunt trip. This delay should be the time that it takes the elevator cab to travel from the top of the hoist way to the lowest recall level. Alternatively, engineering methods, such as those specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of the growth rate scenarios.
21.4.3 Delete and replace with the following: Pressure or water flow switches shall not be used to shut down elevator power.
21.6 Delete and replace with the following:
21.6 Occupant Evacuation Elevators.
21.6.1 Elevator Status. Any elevator specifically designated and marked for use by occupants for evacuation during fires shall comply with all of the provisions of Sections 21.5 and 21.6.
21.6.2 Elevator Occupant Evacuation Operation (OEO). Outputs from the fire alarm system to the elevator controller(s) shall be provided to implement elevator occupant evacuation operation in accordance with Section 2.27 of ASME A17.1/CSA B44 as modified by Chapter K1 of Appendix K of the New York City Building Code, as required in 21 6.2.1 and 21.6.2.2.
21.6.2.1 Partial Evacuation. Where an elevator or group of elevators is designated for use by occupants for evacuation, the provisions of 21.6.2.1.1 through 21.6.2.1.4 shall apply for partial evacuation.
21.6.2.1.1 Initiation. Output signal(s) shall be provided to initiate elevator occupant evacuation operation upon automatic or manual detection of a fire on a specific floor or floors as a result of either or both of the following:
   (1)   Activation of any automatic fire alarm initiating device in the building, other than an initiating device used for elevator Phase l Emergency Recall Operation in accordance with Chapter K1 of Appendix K of the New York City Building Code.
   (2)*   Activation of manual means at the fire command center by authorized or emergency personnel.
21.6.2.1.2* Floor Identification.
   (A)   The output signal(s) shall identify each floor to be evacuated.
   (B)   The identified floors shall be a contiguous block of floors including the following:
      (1)   The floor with the first activated automatic initiating device.
      (2)   Floors with any subsequently activated automatic initiating devicefs).
      (3)   Floors identified by manual means from the fire command center.
      (4)   One floor above the highest floor identified by 21.6.2.1.2(B)(1) through 21.6.2.1.2(B)(3).
      (5)   One floor below the lowest floor identified by 21.6.2.1.2(B)(1) through 21.6.2.1.2(B)(3).
   (C)   The identified floors shall be displayed on a standard emergency services interface along with the other elevator status information required by 21.6.1.
21.6.2.1.3 Manual Floor Selection.
   (A)   A means shall be provided at the fire command center to allow the manual selection of floors.
   (B)   The floors shall be selected on the basis of information from authorized or emergency personnel.
21.6.2.1.4* Occupant Notification.
   The in-building fire emergency voice/alarm communications system shall transmit coordinated messages throughout the building.
   (A)   Live voice evacuation messages shall be transmitted to the floors identified in 21.6.2.1.2 to indicate the need to evacuate and that elevator service is available.
   (B)   Live voice messages shall be transmitted to the floors not being evacuated to inform occupants of evacuation status and shall include an indication that elevator service is not available.
   (C)*   Live voice messages shall be transmitted to the floors identified in 21.6.2.1.2 to indicate that elevator service is not available when all elevators have been recalled on Phase I Emergency Recall Operation.
   (D)   All live voice messages shall be coordinated with the text displays provided separately by the elevator management system.
21.6.2.2 Total Evacuation. Where an elevator or group of elevators is designated for use by occupants for evacuation, the provisions of 21.6.2.2.1 through 21.6.2.2.3 shall apply for total evacuation.
21.6.2.2.1 Output(s) to signal elevator occupant evacuation operation for total evacuation shall be manually activated from the fire command center bv a means labeled "ELEVATOR TOTAL BUILDING EVACUATION."
21.6.2.2.2 The output(s) shall identify that all floors are to be evacuated.
21.6.2.2.3 A live voice evacuation message shall be transmitted from the in-building fire emergency voice/alarm communication system throughout the entire building to indicate the need to evacuate.
21.7.3* Delete and replace with the following: Fan Shutdown and Restart.
21.7.3* Delete and replace with the following: Fan Shutdown and Restart.
Add 21.7.3.1 Connections between fire alarm systems and the HVAC systems for the purpose of monitoring and control shall be arranged such that primary control (the control that all other controls are secondary or subservient to) capability rests with the fire alarm control unit(s) under all circumstances and in addition shall operate and be monitored in accordance with the New York City Building Code.  Exception – Primary control of HVAC systems may rest with approved smoke control systems.
Add 21.7.3.2 HVAC fans or fan systems which have been automatically shut down by the activation of any fire alarm control unit or device shall be arranged and equipped not to automatically restart when the fire alarm control unit or device is resent. At least two manual means of restarting the fans or fan systems shall be required, such as manually resetting the fire alarm control unit or device and subsequently manually resetting the fan or fan system controls.
Add 21.7.3.3 Fans or fan systems that were automatically shut down by the fire alarm control unit or device in high rise fire alarm systems shall be manually enabled to start by means of overriding the fan shut down through the use of city wide standard key (#2642) located at the Fire Command Center and/or Fire Fighters' Smoke Control Station. The actual start of the fans shall be accomplished manually through HVAC controls at the Fire Command Center, Fire Fighters' Smoke Control Station and locally at the fan rooms.
Add 21.7.3.4 Smoke Exhaust control means shall be enabled through the use of city wide standard key (#2642) located at the Fire Command Center, Fire Fighters' Smoke Control Station, fire alarm control unit or, in the entrance lobby of the building adjacent to the fire alarm remote annunciator, when provided.
21.9.1 Delete and replace with the following: Where permitted by the New York City Building Code, any device or system intended to electrically lock a required means of egress door in the direction of egress shall be connected to the fire alarm system serving the protected premises.
21.9.3 Delete and replace with the following: Where permission is obtained from the Commissioner, for all means of egress doors connected in accordance with 21.9.1, and where batteries are used in accordance with 10.5.6.1.1(1) as the secondary power supply, the batteries shall not be utilized to maintain these doors in the locked condition, unless the fire alarm control unit is arranged with circuitry and sufficient secondary power to ensure the exits will unlock within 10 minutes of loss of primary power.
Chapter 22 – Reserved No changes.
Chapter 23 – Protected Premises Fire Alarm Systems
23.3.2 Delete and replace with the following: Nonrequired Systems. The features for a nonrequired system shall be established by the system designer on the basis of the goals and objectives intended by the system owner and subject to approval of the Building Department and Fire Department.
23.8.1.2.2(3) Delete and replace with the following: (3) Subsequent system operation shall be subject to approval of the Fire Department.
Add Section 23.8.1.2.3 Group A Occupancies. Presignal systems in Group A Occupancies required by Section 907.2.1.1 of the New York City Building Code shall operate in the "Event/Non-Event Mode," as follows:
      (1)   For the purposes of this section, Event Mode is defined as an assembly space occupied by public members. The Event Mode and Non-Event Mode shall be selectable positions in a two position key switch operated by city wide standard key (#2642) with visual indication of mode status at the fire alarm control panel. A log record shall be maintained for all mode operations identifying the operator, time and date of each such operation of mode and the selected duration of time for Event Mode.
      (2)   In the Event Mode no automatic alarm audible or visual notification signals shall be transmitted to the public or occupants of the place of assembly and support areas - manual live voice announcements shall be made by the designated Fire Guard(s) supervising the fire alarm panel during all publicly attended place of assembly for direction and implementation of emergency procedures including evacuation.
      (3)   The Event Mode shall be adjustable up to a maximum time period duration of twelve hours, and shall automatically revert to Non-Event Mode at the expiration of the time period unless manually switched to Non-Event Mode prior to such expiration time. A supervisory signal in addition to the foregoing is not prohibited.
      (4)   In the Non-Event Mode all speakers, horns and visual appliances shall emit alarm notification signals for public notification purposes - the audible signal shall be a temporal code three signal pattern.
      (5)   In the Event Mode an unacknowledged alarm actuation shall, after the expiration of 180 seconds (3 minutes), automatically revert to Non-Event Mode and cause all alarm appliances to emit notification signals throughout the entire premises without exception, including publicly occupied assembly and support areas. Prerecorded or synthesized voice messages are prohibited.
      (6)   The fire alarm system shall be accessible within or adjacent to the assembly space to permit the assigned Fire Guard(s) to assess conditions and effectively direct evacuation of the admitted public.
      (7)   The Fire Alarm Panel with voice communication shall be manned by a Fire Guard(s), with a Certificate of Fitness issued by the Fire Department, during all times that the fire alarm system is in Event Mode.
      (8)   A central station connection for manual, automatic and waterflow valve alarm and trouble shall be provided for the fire alarm system, activated automatically in either Event or Non-event Mode.
23.8.5.1.2 Delete Exception.
23.10.1 Delete and replace with the following: The requirements of Section 23.10 shall apply to both audible (tone and prerecorded voice) and visible notification appliance circuits when permitted with the approval of the New York City Department of Buildings in concurrence with the Fire Department.
Chapter 24 – Emergency Communications Systems (ECS)
24.3.5.4.1 Add the following exception: Exception – Pathway survivability Level 1 is permitted when pathway is designated as Class A or Class X with redundant pathways separated by a minimum of 15 feet.
Add 24.4.1.10 One-Way Emergency Voice Communications System.
Add 24.4.1.10.1 Scope. One-way emergency voice communications equipment shall be installed in accordance with section 24.4.1.10.
Add 24.4.1.10.2 Fire Department Use. One-way emergency voice communications service, where provided, shall be for use only by the Fire Department or by building personnel authorized to use such service who have obtained a Certificate of Fitness from the Fire Department.
Add 24.4.1.10.2.1 Activation. The voice communication panel at the annunciator panel shall be operated only by the Fire Department with activation of city wide standard key (#2642).
Add 24.4.1.10.2.2 Building Personnel Use. If requested by a building owner, building personnel who have obtained a FDNY Certificate of Fitness shall be permitted to utilize the system from a panel at the concierge or security desk.
Add 24.4.1.10.2.3 Permitted Variation. Any variation of equipment and system operation, if permitted by the Fire Commissioner, provided in order to facilitate additional uses of any one-way emergency voice communications service shall not adversely affect performance when used by those authorized pursuant to section 24.4.1.10.2 of this chapter.
Add 24.4.1.10.2.4 Speaker Stations. Speaker stations shall be installed in each dwelling unit and on at least every other story in every required vertical exit enclosure.
Add 24.4.1.10.2.5 System Zones. One-way emergency voice communication systems shall, at a minimum, have the capability for an all-call function to all speaker stations, and shall have the capability of permitting simultaneous operation of any and all of the following selectable zones:
      (1)   All speaker stations within the dwelling units on any given floor; and
      (2)   All speaker stations within a given required vertical exit enclosure.
Add 24.4.1.10.2.6 Dwelling Unit Intercoms. One-way emergency voice communication systems may share wiring, speaker stations and other components with an intercommunication system required by section 1008.4.4 of the New York City Building Code provided the entire system otherwise complies with the provisions of this chapter.
24.5.1.11 Delete and replace with the following: In buildings provided with a two-way telephone communications system, at least one telephone station shall be provided where required by the New York City Building Code.
24.5.1.15 Delete and replace with the following: Telephone jacks are prohibited in new buildings and new fire alarm systems in existing buildings.
24.5.2* Two-way Radio Communications Enhancement Systems (In-Building Auxiliary Radio Communication System (ARCS)).
Add 24.5.2.1.3 Definitions. The following definitions are applicable to this section only.
Delivered Audio Quality (DAQ). A measure of audio quality over a transmission medium as defined in standards published in TIA/TSB-88C. The following table shows the DAQ descriptions as published in the document:
 
Delivered Audio Quality (DAQ) Faded Subjective Performance Description
1
Unusable, speech present but unreadable.
2
Understandable with considerable effort. Frequent repetition due to noise/distortion.
3
Speech understandable with slight effort. Occasional repetition required due to noise/distortion.
3.4
Speech understandable with repetition only rarely required. Some noise/distortion.
4
Speech easily understood. Occasional noise/distortion.
4.5
Speech easily understood. Infrequent noise/distortion.
5
Speech easily understood.
 
Dedicated Radio Console (DRC). A fixed location console that contains at least the following components:
      (1)   A handset or headset to broadcast and/or receive voice communications from/to ARCS.
      (2)   A visual display to identify all signals transmitted from the Firefighter handheld units and supervisory signals.
      (3)   Fire Department city wide standard key (#2642) to enable/disable radio transmission.
In-Building Auxiliary Radio Communication System (ARCS). Wireless two-way radio communication enhancement system installed in buildings to propagate Fire Department wireless frequencies for the use of the Fire Department in case of an emergency.
Repeater Channel System. A repeater system utilizing channels with paired receive and transmit frequencies. When a user within the building transmits on a repeater channel, the repeater system rebroadcasts the users' signal to the DRC and all users within the building on that channel. This transmission increases the distance from which users can directly talk with each other. A user at the DRC must enable repeater channel for users to communicate.
Simplex Channel System. A simplex system utilizing channels with the same frequencies for transmit and receive. Users communicate on simplex channels radio-to-radio without going through infrastructure. However, their radios need to be within a certain distance to be picked up by one another. A simplex system allows a user at the DRC to communicate with a user on a simplex channel anywhere in the building, even though the distance between the DRC and the user would typically be prohibitive. A simplex system only extends the transmission's reach for the DRC. It does not improve coverage between individual user radios.
24.5.2.2.1 Delete and replace with the following: Critical Areas. Critical areas, such as the fire/emergency command center(s), the fire pump room(s), exit stairs, exit passageways, elevator lobbies, standpipe cabinets, sprinkler sectional valve locations, and other areas deemed critical by the authority having jurisdiction at the time of plan examination, shall be provided with 100 percent floor area radio coverage.
24.5.2.2.2 Delete and replace with the following: General Building Areas. General building areas shall be provided with 95 percent floor area radio coverage in accordance with rules promulgated by the Fire Department.
24.5.2.2.3 Delete and replace with the following:
System Types. Buildings and structures that cannot support the required level of radio coverage shall be equipped with either a repeater channel system or a simplex channel system.
24.5.2.3.1 Delete and replace with the following: Inbound. A minimum inbound signal strength of -95 dBm, or other signal strength as required by the authority having jurisdiction, shall be provided throughout the coverage area and provide a minimum intelligible DAQ of 3.4.
24.5.2.3.2 Delete and replace with the following: Outbound. A minimum outbound signal strength of -95 dBm at the donor site, or other signal strength as required by the authority having jurisdiction, shall be provided from the coverage area and provide a minimum intelligible DAQ of 3.4.
24.5.2.4* Delete and replace with the following:
System Radio Frequencies. The ARCS shall be capable of transmitting all public safety radio frequencies assigned by the Fire Department and be capable of using any modulation technology.
24.5.2.4.1 Delete and replace with the following: List of Assigned Frequencies. The Fire Department shall maintain a list of all inbound/outbound frequency pairs for distribution to system designers and installers.
24.5.2.4.2* Delete and replace with the following: Frequency Changes. Systems shall be capable of upgrade, to allow for instances where the Fire Department changes or adds system frequencies, in order to maintain radio system coverage as originally designed.
Add 24.5.2.4.3 Perimeter Coverage. The design of the ARCS shall minimize RF radiation beyond the intended building's limits so as to avoid interference, in compliance with FCC regulations.
24.5.2.5.1 Delete and replace with the following: Component Approval. Components utilized in the installation of the public safety radio enhancement system, such as repeaters, transmitters, receivers, signal boosters, cabling, and fiber-distributed antenna systems, shall be FCC compliant, listed by a Nationally Recognized Testing Laboratory (NRTL) and shall be compatible with the Fire Department radio system.
24.5.2.5.2 Delete and replace with the following: Component Enclosures. All active components including but not limited to repeater, transmitter, receiver, and signal booster components remotely located from the Fire Command Center shall be contained in a NEMA 4- or 4X- type enclosure(s).
Add 24.5.2.5.2.1 The enclosure shall be painted Fire Department Red.
Add 24.5.2.5.2.2 The enclosure shall have a locking mechanism that utilizes Fire Department city wide standard key (#2642).
Add 24.5.2.5.2.3 A tamper switch shall monitor all active components in non-secure locations located remotely from the Fire Command Center such as amplifiers and repeaters. The notification for the tamper switch shall be monitored at the DRC.
24.5.2.5.3 Delete and replace with the following: Power Supply. Power supply to the ARCS shall be in accordance with section 760.41 of the New York City Electrical Code.  Exception – Where power supply for the building fire alarm system has adequate capacity to support the ARCS power requirements, connection to the fire alarm system power supply via dedicated branch circuits with appropriate overcurrent protection is permitted.
Add 24.5.2.5.4.1 External filters. Permanent external filters and attachments shall not be permitted.
Add 24.5.2.5.5 Labeling.
Add 24.5.2.5.5.1 Cables.
Add 24.5.2.5.5.1.1 Cables utilized in the ARCS shall be labeled as "FDNY Communications Use".
Add 24.5.2.5.5.1.2 Where continuously accessible, the cable shall be marked every 8 feet.
Add 24.5.2.5.5.1.3 Wherever the cable is intermittently accessible, each accessible point shall be labeled.
Add 24.5.2.5.5.1.4 Field labeling of the cables shall be acceptable.
Add 24.5.2.5.5.2 Dedicated Radio Console Enclosure. The DRC shall be enclosed and the outside of the enclosure shall be labeled the following in white lettering contrasted against a Fire Department Red background:
 
AUXILIARY RADIO COMMUNICATIONS
Add 24.5.2.5.5.3 Cable Rating. All ARCS cables shall be protected such that the circuit shall maintain its electrical function during fire conditions for at least a 2-hour period and the protection shall not interfere with the normal operation of the system as a whole.  Exception-Radiating ARCS cables running horizontally that are not part of the main trunk connecting to a vertical riser shall have a plenum rating with a minimum temperature of 125C.
24.5.2.6.1 Delete and replace with the following: Supervisory signals shall be provided in the form of visual indications (e.g., LED, alpha-numeric display) at the DRC with at minimum for the following system functions:
   (1)   The integrity of the circuit monitoring signal booster(s) and power supply(ies) shall comply with 10.17.1.
   (2)   Base Station Failure.
      (a)   Low transmit power
      (b)   Over temperature
      (c)   High Voltage Standing Wave Ratios (VSWR)
   (3)   Supervisory Signals.
      (a)   Loss of alternating-current power source
      (b)   Overall base-station failure
      (c)   Low battery capacity, alarming at 70 percent of battery capacity
      (d)   Antenna malfunction, where applicable
      (e)   Signal amplification failure, where applicable
      (f)   Tamper switch as required
24.5.2.7 Delete and replace with the following: Technical Criteria. The Fire Department shall maintain a document of technical information specific to its requirements. This document shall contain, at a minimum, the following:
   (1)   Frequencies required
   (2)   Maximum time domain interference
   (3)   Unit ID and emergency alert signaling
   (4)   DRC specifications
   (5)   Installation specifications
   (6)   Test equipment specifications
   (7)   Other supporting technical information necessary to direct system design
24.5.2.8 Delete and replace with the following: Inspection and Testing. Inspection and testing shall be performed in accordance with testing frequencies and methods set forth in the rules of the Fire Department.
Chapter 25 – Reserved No changes.
Chapter 26 – Supervising Station Alarm Systems
26.3.8.2 Delete and replace with the following: Testing and maintenance records shall be retained as required by the New York City Fire Code.
26.3.9 Delete and replace with the following: Testing and maintenance for central station service shall be performed in accordance with the New York City Fire Code.
26.4.1 Delete and replace with the following: Application. Where permitted by the Fire Department, supervising facilities of proprietary alarm systems shall comply with the operating procedures of Section 26.4. The facilities, equipment, personnel, operation, testing, and maintenance of the proprietary supervising station shall also comply with 26.4.
26.6.5 Delete and replace with the following: Testing and maintenance of communications methods shall be in accordance with the requirements of the New York City Fire Code.
Chapter 27 – Public Emergency Alarm Reporting Systems No changes.
Chapter 28 – Reserved No changes.
Chapter 29 – Single- and Multiple-Station Alarms and Household Fire Alarm Systems
29.1.4 Delete and replace with the following: The requirements of this chapter shall not apply to one- and two-family manufactured homes.
29.5 Delete, including subsections, and replace with the following: Smoke alarm detection and notification requirements shall be in accordance with Section 907 of the New York City Building Code.
29.6.3(2) Delete and replace with the following: (2) All electrical systems shall be installed by a New York City licensed electrical contractor.
(Am. eff. 10/8/2015)
(Repealed eff. 10/8/2015)
*Subchapter Q added City Record May 11, 2009 § 1, eff. June 10, 2009.
**Note that an asterisk (**) found withing the foregoing rule, following the number or letter designating a paragraph, indicates that explanatory material on the paragraph can be found in Annex A of NFPA 13.
Resources