- Number of occupants. The subject subsection (27-972(h)) of the Building Code states that a communication and alarm system, acceptable to the Commissioner of Buildings, shall be provided in buildings classified in occupancy group E, less than 100 feet in height, occupied or arranged to be occupied for an occupant load of more than one hundred persons above or below the street floor or more than a total of five hundred persons in the entire building. The provisions regarding occupant load are to be interpreted to apply where one or more of the following prevail:
- The sum of the occupants on all the floors below the street floor exceeds 100 persons; or
- The sum of the occupants on all the floors above the street floor exceeds 100 persons; or
- A total of more than 500 persons in the entire building including the street floor.
- Occupancy load. Occupant load shall be determined by the existing certificate of occupancy. In the absence of such certificate of occupancy, the occupant load shall be the greater of the actual number of occupants or on the basis of 1 person per 100 square feet net floor area. Net floor area shall be all space within the building exterior walls, excluding the following areas:
- areas enclosing stairs.
- public corridors.
- elevators and shafts.
- rest rooms.
- storage rooms.(For example, a net floor area of 10,100 square feet is capable of an occupancy of 101 persons.)The communication and alarm system, acceptable to the Commissioner of Buildings, shall have the following capabilities and components:
- Capabilities and components.
- Fire command station. A communications center, located in the lobby of the building on the entrance floor as part of the elevator control panel if such exists, or located in the immediate vicinity of the elevators if they exist, to provide:
- Individual two-way voice communication from the fire command station to a fire warden station on each floor and to the regularly assigned location of the fire safety director, to consist of a telephone handset or approved speaker microphone system or other approved voice communication system. Initiation of a call from the fire command station shall sound a loud and distinctive sound or an audible device, selectively on the entire floor which is being called or at all floors throughout the building, through the use of a general all call button. This call shall be immediately answered by the fire wardens of the floors involved.
- Manual pull station located adjacent to the fire command station to transmit a fire alarm signal to the fire department via a central station of a franchised operating company.
- Annunciation of associated fire safety systems at the fire command station is optional; however, such annunciation shall not be connected to the mini-class "E" system.
- This system shall be a "supervised" system. A "supervised" system is one that is electrically monitored so that the occurrence of a single open or single ground fault condition of its wiring which prevents the required normal operation of the system or causes the failure of its primary (main) power supply source is indicated by a distinctive trouble signal.
- Fire Warden Station. A station located on each floor within view of the passenger elevator lobby if such exists; however, when an elevator lobby does not exist, the station shall be located in the path of egress to an existing stairway. The fire warden station shall have two-way communication with the Fire Command Station and:
- Shall consist of telephone handset or a speaker microphone system or other approved equivalent voice communication system.
- The initiation of a call from a fire warden shall cause a loud and distinctive sound at the Fire Command Station and at the Fire Safety Director's Office, which call shall be immediately answered by the Fire Safety Director from the Fire Command Station.
- Fire Safety Director's Office. A station located within the building at the principal work location of the Fire Safety Director arranged the same as a warden's station. There shall be a two-way voice communication system to the Fire Command Station. A two-way voice communication system described above shall also be provided at the mechanical control center should one exist.
- General requirements.
- The components of the system shall require New York City Department of Buildings Material Equipment Acceptance ("M.E.A.") approval.
- SOURCES OF ELECTRICAL POWER Two sources of electrical power shall be provided as follows:
- The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
- The secondary source shall be an emergency power system (as per Section 27-396 of the Building Code), an emergency generator and/or battery power.
- One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the New York City Electrical Code. The primary source of power and the secondary source (if said secondary source is an emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208 volt side. The incoming supply connections shall comply with the New York City Electrical Code, and the fused cutout panel shall comply with the requirements specified herein before.
- PRIMARY POWER SOURCE The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
- SECONDARY POWER SOURCE The secondary service to the fire alarm system shall be provided as follows:
- If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
- If the building has an emergency generator supplying power to any of the loads listed in Section 27-396.4 of the Building Code, the secondary source shall be the generator.
- For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17-5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by 15 minutes of total system load.
- WIRING
- Power Conductors (Above 75 volts) shall be:
- Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
- Cable type MI, M.E.A. approved for fire alarm service.
- Low Voltage Conductors (75 volts and less) shall be:
- Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW, XHH, or XHHW minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
- Minimum wire size No. 18 AWG.
- Multi-conductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
- Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150 C; colored red.
- Red colored jacket overall; minimum thickness 25 mils.
- Cable printing as per UL 1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE" legible without removing jacket.
- Installation of Conductors and Raceway shall be in accordance with the following:
- Power conductors shall not be installed in common raceways with low voltage conductors.
- Comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
- Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
- Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment.
- All wiring within mechanical and elevator equipment rooms shall be run in raceways.
- Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
- Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT), except that multi-conductor cables may also be run in surface metal raceway. Conductors for other electrical systems shall not be installed in raceways containing REFERENCE STANDARD 17 conductors.
- Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
- Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support; Cables must be supported independently from the building structure.
- Cables must be secured by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Cables must be secured in place at intervals not exceeding 5'-0" on centers and within 12" of every associated cabinet, box or fitting.
- Installation of raceways, boxes and cabinets shall comply with the following general requirements:
- Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
- Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
- Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
- Raceways or cables shall not penetrate top of any equipment box or cabinet.
- All conduits supplying 120-volt power to the fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
- For cabinets whose 120 volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel-framed buildings, a connection to local steel structure will be acceptable.
- Splices and terminations of wires and cables shall be as follows:
- Permitted only in boxes or cabinets specifically approved for the purpose.
- Utilize mechanical connections specifically approved by UL 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
- Wiring for audible notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices inoperative, and the devices shall be so connected to the circuitry (i.e. by means of alternate circuits) as to maintain at least partial audibility throughout the entire floor.
- The name and telephone number of the central office company shall be displayed at the manual pull station.
- There shall be a Fire Safety Director on duty at all times that the premises is actually occupied by the number of persons specified in the opening paragraphs of these rules. The Director shall have a Certificate of Fitness issued by the New York City Fire Department.
- Applications shall be filed and permits obtained as required by departmental memoranda concerning fire alarm systems.
- Number of occupants. Subdivisions 27-968(a)(10)(a) and (b) of the Building Code state that an interior fire alarm and signal system shall be provided in any room, place or space occupied or arranged to be occupied by 75 or more persons and in which either any musical entertainment, singing, dancing or other form of amusement is permitted in connection with the restaurant business or the business of directly or indirectly selling to the public food or drink, or where dancing is carried on and the public may gain admission, with or without payment of a fee, and food or beverages are sold, served, or dispensed, and any new or altered catering place as of April 4, 1979 having 300 or more persons. This does not apply to eating or drinking places which provide incidental musical entertainment, without dancing, either by mechanical devices, or by not more than three persons playing piano, organ, accordion or guitar or any stringed instrument or by not more than one singer accompanied by himself or a person playing piano, organ, accordion, guitar or any stringed instrument.
- Occupant load. The occupant load of a Place of Assembly shall be calculated by dividing the net floor area of the space by the appropriate figure in the following table:
Occupancy Net Floor Area Per Occupancy (Square Feet)(1) Dance Floor 10(2) Dining Spaces 12(3) Standing Room (Audience) in all Places of Assembly 4(4) Seating Area (Audience) in all Places of Assembly (4) (i) Fixed Seats Designated Number of Seats or Occupants(4) (ii) Movable Seats 10 - Capabilities and components.
- Fire Alarm System: shall be closed circuit, "electrically supervised", individually coded and connected to an approved franchise/central office alarm company. A "supervised" system is one that is electrically monitored so that the occurrence of a single open or single ground fault condition of its wiring which prevents the required normal operation of the system or causes the failure of its primary (main) power supply source is indicated by a distinctive trouble signal.
- Manual fire alarm stations: shall be installed at each required natural path of egress from all levels from public assembly area.
- Fire alarm gongs: shall be installed to provide adequate audibility throughout the Public Assembly area and all areas occupied in conjunction with the area at all levels including dressing rooms, rest rooms, coat rooms, etc. "Audibility" shall be loud and distinct under maximum sound system operation unless 1 RCNY § 15-02(c)(2)(ii) is complied with.
- Sprinkler waterflow device: shall be installed to indicate flow of water in the sprinkler system and shall be made part of the interior Fire Alarm by interconnecting the waterflow device to the interior Fire Alarm so that actuation of the waterflow device shall sound a distinctive coded alarm via the fire alarm gongs.
- General requirements.
- The components of the system shall require New York City M.E.A. approval.
- A device may be installed to automatically turn off the sound system and psychedelic and special effects lighting when a manual fire alarm and/or sprinkler waterflow device is activated in all public assemblies that require an interior fire alarm and signal system.
-
- SOURCES OF ELECTRICAL POWER Two sources of electrical power shall be provided as follows:
- The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
- The secondary source shall be an emergency power system (as per Section 27-396 of the Building Code), an emergency generator and/or battery power.
- One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the New York City Electrical Code. The primary source of power and the secondary source (if said secondary source is an emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208 volt side. The incoming supply connections shall comply with the New York City Electrical Code, and the fused cutout panel shall comply with the requirements specified in this rule.
- PRIMARY POWER SOURCE
- The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
- Partial systems such as strobe light control panels, partial fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and an identified, locked fused cutout box located within 5 feet of the tap. Where an emergency power system (E.P.S.) is provided in accordance with Section 27-396.4 of the Building Code, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.
- SECONDARY POWER SOURCE The secondary service to the fire alarm system shall be provided as follows:
- If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
- If the building has an emergency generator supplying power to any of the loads listed in Section 27-396.4 of the Building Code, the secondary source shall be the generator.
- For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17-5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by 15 minutes of total system load.
- SOURCES OF ELECTRICAL POWER Two sources of electrical power shall be provided as follows:
- WIRING
- Power Conductors (Above 75 volts) shall be:
- Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
- Cable type MI, M.E.A. approved for fire alarm service.
- Low Voltage (75 volts and less) shall be:
- Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW, XHH, or XHHW minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
- Minimum wire size No. 18 AWG.
- Multi-conductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
- Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150 C; colored red.
- Red colored jacket overall; minimum thickness 25 mils.
- Cable printing as per UL 1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE" legible without removing jacket.
- Installation of Conductors and Raceway shall be in accordance with the following:
- Power conductors shall not be installed in common raceways with low voltage conductors.
- Comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
- Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
- Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment.
- All wiring within mechanical and elevator equipment rooms shall be run in raceways.
- Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
- Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT), except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing REFERENCE STANDARD 17 conductors.
- Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
- Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support; Cables must be supported independently from the building structure.
- Cables must be secured by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Cables must be secured in place at intervals not exceeding 5'-0" on centers and within 12" of every associated cabinet, box or fitting.
- Installation of raceways, boxes and cabinets shall comply with the following general requirements:
- Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
- Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
- Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
- Raceways or cables shall not penetrate top of any equipment box or cabinet.
- All conduits supplying 120-volt power to the fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
- For cabinets whose 120 volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel-framed buildings, a connection to local steel structure will be acceptable.
- Splices and terminations of wires and cables shall be as follows:
- Permitted only in boxes or cabinets specifically approved for the purpose.
- Utilize mechanical connections specifically approved by UL 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
- Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e. by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.
- Power Conductors (Above 75 volts) shall be:
- The equipment shall be colored RED and enclosed in suitable housing permanently fastened to the structure at the appropriate locations. A diagonal white stripe one inch wide from upper left corner to lower right corner shall be painted or applied to sending stations. The stripe shall not render any lettering illegible or obliterate the station number.
- The name and telephone number of the central office company shall be displayed at all manual pull stations and at all central office transmitters.
- There shall be a fire guard on duty at all times that the Place of Assembly is open and functioning as a cabaret. The fire guard shall have a Certificate of Fitness issued by the New York City Fire Department.
- Emergency Lighting and Sprinkler Systems shall be installed and maintained as required by law.
- A Fire Alarm System in a Place of Assembly subject to this rule in a high rise (Class E) office building shall interface with a Fire Alarm and Communication System required by Local Law No. 5/1973.
- Applications shall be filed and permits obtained as required by Departmental Memorandum.
- Fire Alarm System: shall be closed circuit, "electrically supervised", individually coded and connected to an approved franchise/central office alarm company. A "supervised" system is one that is electrically monitored so that the occurrence of a single open or single ground fault condition of its wiring which prevents the required normal operation of the system or causes the failure of its primary (main) power supply source is indicated by a distinctive trouble signal.
- Definition. Existing J-1 Residential Hotel. An existing J-1 residential hotel is defined as a single room occupancy multiple dwelling, in which at least seventy-five (75) percent or more of the total number of occupied individual dwelling units:
- have had no more than two (2) separate tenancies for at least three (3) years preceding the date on which the application for residential hotel status is made or, preceding the date of submission of an annual certification as set forth below or
- have been used by a religious not-for-profit organization as a residency for its members who maintain residency for at least one (1) year and have no more than two (2) separate tenancies for at least one (1) year preceding the date on which the application for residential hotel status is made, provided that a fire safety plan for fire drill and evacuation procedures in accordance with the requirements of the Fire Commissioner shall be submitted to the Fire Department and the approval of the Fire Commissioner shall be obtained.
- Details of exemptions. This section shall exempt owners of existing "residential hotels," as that term is defined in 1 RCNY § 15-04(a), from J-l fire safety special filing requirements of §§ 27-382(b), 27-384(b), 27-954(w), 27-989(b), 27-996.2(a)(2) of Article 26 of Subchapter 1 of Chapter 1 of Title 27 of the Administrative (Building) Code as enacted by Local Law 16 of 1984, effective March 17, 1984, as well as installation requirements set forth in the following sections:
- § 27-382(b) Power source — Exit lights.
- § 27-384(b) Power source — Exit signs.
- § 27-954(w) Required sprinklers.
- § 27-989(b) Elevator in readiness.
- § 27-996.2(a)(2) Firemen service operation in existing elevators.
- Certification.
- The certification of residential hotel status may be obtained only by the filing of an alteration application for residential hotel certification. Such application shall contain the supporting documentation required in 1 RCNY § 15-04(d) below. Certification of residential hotel status as defined in 1 RCNY § 15-03(a) above shall be issued by the borough superintendent. Certification shall be valid for a period of one (1) year from the date of initial certification. Thereafter, the owner of the residential hotel shall engage a registered architect or licensed professional engineer to certify annually through the filing of a building notice application that the residential hotel is in compliance with the requirements of 1 RCNY § 15-03(a) above.
- Owners of residential hotels shall keep a copy of their residential hotel certification on site at the hotel. Failure to timely renew a hotel's residential certification may result in the issuance of violations for the hotel's failure to comply with the requirements of Local Law 16 of 1984 and Local Law 16 of 1987 for a J-l occupancy.
- Supporting documentation. The following documentation shall be furnished by the owner in support of his or her application for certification of residential hotel status:
- Certificate of Occupancy or, if unavailable;
- Occupancy and Arrangement Card from the Department of Housing Preservation and Development and Department of Housing Preservation and Development Computer Printout;
- List all rooms occupied by tenants who have resided at the premises for six months or longer or who are in occupancy pursuant to a lease of six months or longer, together with the name of the tenant in each of the aforementioned rooms and copies of any and all existing leases for the period stated in 1 RCNY § 15-03(a) of this section; and
- For each dwelling unit in the premises subject to rent control or hotel stabilization, copies of the annual registration statement filed with the New York State Division of Housing and Community Renewal; and
- Copies of any relevant documents filed by the owner with the Hotel Stabilization Association; and
- Any other documentation deemed relevant by the borough superintendent, in his or her discretion.
- Determination of J-2 Dormitory.
- A building owner may contend that his/her building is a dormitory and therefore as a J-2 occupancy need only provide stair and elevator signs, and if a high-rise building also remove locks on elevator and hoistway doors. To qualify as a dormitory, the building's current Certificate of Occupancy must indicate use as a dormitory. Where the Certificate of Occupancy indicates both dormitory and J-l occupancy, those portions which are J-l must comply with LL 16/84 requirements for J-1 occupancies.
- When an owner seeks to amend his building's Certificate to provide for dormitory occupancy, he must submit an affidavit stating he will use the dormitory space only for sleeping accommodations of individuals on a month-to-month or longer-term basis (Administrative Code § 27-265) and that the dormitory will be owned and operated by either a not-for-profit corporation or a school. Such amended Certificates of Occupancy shall provide that the dormitory may only be owned or operated by either a not-for-profit corporation or a school.
- Number of occupants. These rules and regulations shall apply to buildings or parts thereof classified in Article 11 of Subchapter 3 of Chapter 1 to Title 27 of the Administrative Code of the City of New York as occupancy group J-l, J-2 occupied or arranged to be occupied in whole or part by a transient occupancy. For the purpose of these rules and regulations, buildings or parts thereof which contain a total of more than 30 sleeping rooms or can accommodate a total of more than 30 lodgers, or contains more than 15 sleeping rooms or can accommodate more than 15 lodgers above the first or ground story, used for living or sleeping purposes by the same person or persons for a period of ninety days or less shall be considered as being occupied by a transient occupancy. Such buildings shall include but are not limited to buildings occupied as hotels, motels, lodging houses, dormitories and single room occupancies. All such buildings occupied or arranged to be occupied in whole or part by a transient occupancy, regardless of the number of sleeping rooms or accommodations, over 75 feet in height, shall comply with these rules and regulations. The owner or other person having charge of such building shall file a Fire Safety Plan with the Fire Department indicating compliance with 1 RCNY § 15-05(b) within 30 days after the effective date of these rules and regulations. The owner or other person shall resubmit the revised Fire Safety Plan for approval within 30 days after receiving comments from the Fire Department. Upon approval, the Fire Safety Plan shall be immediately put into effect. The owner or other person having charge of such building shall comply with 1 RCNY §§ 15-05(c)(1) to 15-04(c)(5) within 30 days of the effective date of these rules and regulations.
- Details of fire safety plan.
- A fire safety plan for fire drill and evacuation procedures in accordance with the requirements of the Fire Commissioner shall be submitted to the Fire Department and the approval of the Fire Commissioner shall be obtained. The applicable parts of the fire safety plan shall be distributed to the building service employees. All employees of the building shall participate and cooperate in carrying out the provisions of the fire safety plan.
- Fire safety director and deputy fire safety director.
- One employee shall be designated as fire safety director and a sufficient number of employees shall be designated as deputy fire safety directors. Such employees shall have a knowledge of the building's fire protection systems and shall have a certificate of fitness, in accordance with the requirements of the Fire Commissioner, qualifying him to conduct fire drills, evacuations and related activities such as organizing, training and supervising a fire brigade when required. In the absence of a fire safety director, when a fire safety director is required to be on duty in the building, such deputy ffire safety director shall act as fire safety director.
- As the building is continuously occupied, there shall be a fire safety director continuously on duty in the building with the required certificate of fitness. During fire emergencies, the primary responsibility of the fire safety director shall be the manning of the fire command post and the direction and execution of the evacuation as provided in the fire safety plan and to assist the Fire Department with his knowledge of the building's fire protection systems. Such activities shall be subject to the Fire Department control.
- If sufficient personnel are available, as determined by the Fire Department, a fire brigade shall be organized.
- Fire drills shall be conducted, in accordance with the fire safety plan, at least once every three months on each shift. A written record of such drills shall be kept on the premises for a three year period and shall be readily available for inspection by the Fire Department.
- In buildings where compliance would cause practical difficulty or undue hardship, the Fire Commissioner may waive or modify the requirements of this subdivision and accept alternatives fulfilling the intent of these requirements consistent with public safety.
- Signage.
- Elevator landings. A sign shall be posted and maintained on every floor at the elevator landing. The sign shall read "IN CASE OF FIRE, USE STAIRS UNLESS OTHERWISE INSTRUCTED." The lettering shall be at least one-half inch block letters and of contrasting color from the background or as otherwise approved by the Commissioner of Buildings. Such lettering shall be properly spaced to provide good legibility. The sign shall also contain a diagram showing the location where it is posted and the location and letter identification of the stairs on the floor. The sign shall be at least eight inches by ten inches, located directly above a call button and securely attached to the wall or partition. The top of such sign shall not be above six feet from the floor level. The diagram on such sign may be omitted provided that signs containing such diagram are posted in conspicuous places on the respective floor. In such case, the sign at the elevator landing shall be at least two and one-half inches by ten inches and the diagram signs shall be at least eight inches by ten inches.
- Floor numbering. A sign shall be posted and maintained with each stair enclosure on every floor, indicating the number of the floor. The numerals and background shall be in contrasting colors. The sign shall be securely attached to the stair side of the door.
- Stairs and elevators. Each stair and each bank of elevators shall be identified by an alphabetic letter. A sign indicating the letter of identification for the elevator bank shall be posted and maintained at each elevator landing directly above or as part of the sign specified in 1 RCNY § 15-05(c)(1). The stair identification sign shall be posted and maintained on the occupancy side of the stair door. The letter on the sign shall be at least three inches high, of bold type and of contrasting color from the background. Such signs shall be securely attached.
- Sign material. Signs shall be of metal or other durable material.
- Placing, size and content of signs. A sign shall be posted and maintained on the inside of every door opening onto a public corridor giving access to a sleeping room. The sign shall contain a diagram showing the location where it is posted and the location and letter identification of the exit stairs on the floor. The diagram shall indicate the number of doors opening onto the public corridor which must be passed to reach each exit stair. The sign shall be at least eight inches by ten inches, located on the inside of the door and securely attached thereto. The top of such signs shall not be above six feet from the floor level. These signs are in addition to the signs required in 1 RCNY § 15-05(c)(1). These signs may contain such additional information as the Fire Department may require.
- Additional sign requirements. When floors or parts of floors are used as accessory to a J-l and J-2 transient occupancy, "Elevator Landings" 1 RCNY § 15-05(c)(1), "Floor Numbering" 1 RCNY § 15-05(c)(2) and "Stairs and Elevators" 1 RCNY § 15-05(c)(3) shall be required.
(Repealed City Record 11/7/2022, eff. 12/7/2022)
- Intent. The fire-retarding rules herewith set forth are approved by the Department of Buildings for old law tenements and converted dwellings where their entrance halls, stair halls and public halls are required, by § 189, subdivisions 1 and 4, § 238, subdivision 4, and § 218, subdivisions 5 and 6, Multiple Dwelling Law, and by § 27-2044, Housing Maintenance Code, to be fire-retarded in a manner approved by the Department of Buildings.
- All entrance halls, stair halls and public halls, including service halls and stairs, shall be fire-retarded to the extent required by the Multiple Dwelling Law and the Housing Maintenance Code.
- It is the intent that all wood structural members of partitions, ceilings and stair soffits shall be completely protected with fire-retarding materials where they may be exposed to fire in entrance, stair and public halls. To this extent these rules and regulations cover only general conditions and are not designed to cover specific or special cases. Where such may occur the owner is required to consult the Department of Buildings and receive instructions before work is started.
- Where existing dumbwaiter shafts are located in, or open on public halls which are required to be fire-retarded, such dumbwaiter shafts, when not constructed of fireproof or fire-retarding materials, shall be fire-retarded on the inner side, from the lowest story to the roof inclusive, in accordance with the requirements of 1 RCNY § 15-07(b)(1) or (b)(2), except in cellar where such shafts shall be enclosed with fireproof materials. All doors opening from such dumbwaiter shafts shall be self-closing, and doors and assemblies when of wood or other non-fireproof construction shall be lined on both sides with No. 26 U.S. gauge metal, except in cellar where doors and assemblies shall have a fire-resistive of at least one (1) hour.
- It is not intended that these rules and regulations in themselves require plans to be filed. However, should any work involve structural changes, then plans are required to be filed in the Department of Buildings and such changes shall be subject to all other rules and regulations applicable thereto.
- Work shall not commence until satisfactory evidence has been submitted to the Department of Buildings that compensation insurance has been obtained in accordance with the provisions of the Workmen's Compensation Law. It is the intent of § 238, subdivision 4, Multiple Dwelling Law, that every entrance hall, public hall and stair hall in every old law tenement four stories or more in height shall be fire-retarded. Every old law tenement three stories and a basement, or three stories, basement and cellar in height shall be deemed to be four stories in height when the main entrance from the grade is to the basement, and every entrance hall, public hall and stair hall in such building shall be fire-retarded. In old law tenements where the entrance halls, public halls and stair halls are required to be fire-retarded, existing wood stairs shall be fire-retarded in conformity with the requirements of these rules and regulations, whether or not such halls had been fire-retarded in accordance with plans filed with and approved by the former Tenement House Department or Department of Buildings, prior to the enactment of subdivision 4 of § 238 of the Multiple Dwelling Law.
- Partitions. All existing partitions separating apartments from entrance halls, stair halls and public halls, or otherwise forming enclosing partitions of entrance halls, stair halls and public halls, shall be fire-retarded by any one of the following methods:
- Metal lath and cement of gypsum mortar. Completely remove all existing materials to face of studs or other structural members on hall side of partitions and recover with metal lath and two coats of cement of gypsum mortar. If cement mortar is used it shall be three-quarters inch (3/4") thick, if gypsum mortar is used it shall be one inch (1") thick. The second coat of mortar shall not be applied until the first coat has thoroughly set and in no case shall the second coat be applied on the same day that the first coat of mortar is applied. In lieu of the above method, completely remove all combustible materials from plaster face of partitions on hall side and repair existing plaster. After inspection, cover existing plaster with herringbone or similar approved type metal lath with rigid rib reinforcement to provide good bond between new and existing plaster. Cover lath with two coats (scratch and brown) of cement of gypsum mortar as above. The first coat of cement mortar (scratch) shall be composed of one (1) part of Portland cement to one and one-half (1 1/2) parts of sand, with an additional volume of hydrated lime not greater than ten (10) percent of the volume of Portland cement. The second coat (brown) shall be composed of one (1) part of Portland cement to three parts (3) of sand, with an additional volume of hydrated lime not greater than ten (10) percent of the volume of Portland cement. The first coat (scratch) of gypsum mortar shall be composed of one (1) part of gypsum to one (1) part of sand. The second coat (brown) of gypsum mortar shall be composed of one (1) part of gypsum to one and one-half (1 1/2) parts of sand.
- Plaster boards and gypsum mortar or stamped metal. Completely remove all existing materials to face of studs or other structural members on hall side of partitions and recover with plaster boards or perforated rock lath three-eighths inch (3/8") thick, covered with two coats of gypsum mortar (scratch and brown) so that the aggregate thickness shall be at least one inch (1"), or in lieu thereof, recover same with plaster boards one-half inch (1/2") thick, covered with No. 26 U.S. gauge stamped metal. In lieu of the above method, completely remove all combustible material from plaster face of partitions on hall side and repair existing plaster. After inspection, plaster boards or perforated rock lath may be applied directly over the existing plaster face of partitions on hall side. Cover plaster boards or perforated rock lath with two coats of gypsum mortar as above, or plaster boards may be covered with No. 26 U.S. gauge stamped metal.
- Mineral wool. Fill solidly between partition uprights, from underside of flooring to ceiling with mineral wool blown in place by the pneumatic method, packed solidly to fill all spaces and voids.
- Brick, gypsum, etc. Fill solidly between partition uprights from underside of flooring to ceiling with brick, gypsum, or other acceptable material packed solidly to fill all spaces and voids. Where brick, gypsum, or other masonry material is intended to be used, application must be filed before installation with the Department of Buildings for approval of strength of existing members intended to support the proposed masonry fire-retarding.
- Other methods. No other method may be used unless same is acceptable to the Department of Housing and Buildings.
- Removal of windows in public hall partitions. When windows in walls or partitions are removed, both sides of the openings shall be sealed with fire-retarding materials, except that wood lath and plaster may be used on the room side of the opening when the existing surface of the room is constructed of wood lath and plaster.
- Electric meters. Where direct current (DC) electric meters of public utility companies are present or installed on partitions of public halls the fire-retarding shall continue unbroken behind the meters or the meters shall be mounted on a heavy slate back or non-magnetic fireproof equivalent, such as transite, asbestos board, etc., against which fire-retarding finished up tightly.
- Partitions in Class B converted dwellings. Where fire retarding is required in any Class B converted dwelling referred to in 1 RCNY § 15-07(a)(7), both sides of all enclosure partitions of entrance halls, stair halls and public halls throughout such building shall be fire-retarded in accordance with the method set forth in 1 RCNY §§ 15-07(b)(1) or (b)(2) or said partitions shall be fire-retarded in accordance with the provisions of 1 RCNY §§ 15-07(b)(3) or (b)(4).
- Partitions in altered old law tenements. In any old law tenement where the occupancy is increased on any story, the enclosing partitions of any entrance hall, stair hall or public hall on the story where the occupancy has been increased, shall be fire-retarded on both sides. Such requirements shall apply only to the walls of the entrance hall, stair hall or public hall adjoining the altered apartment. The enclosing partitions of such halls other than those adjoining the altered apartment and the partitions on any story where the occupancy has not been increased, shall be fire-retarded on the hall side. The method of fire-retarding shall be as set forth in 1 RCNY §§ 15-07(b)(1) or (b)(2), or said partitions shall be fire-retarded in accordance with the provisions of 1 RCNY §§ 15-07(b)(3) or (b)(4).
- Newly constructed partitions. In any entrance hall, stair hall or public hall where any partition or part thereof is newly constructed, and where the plaster has been removed from any partition or part thereof, such partition shall be fire-retarded on both sides.
- Ceilings. Any approved method for fire-retarding partitions shall be aacceptable for fire-retarding ceilings, provided that all existing materials are completely removed to face of joists. Mineral wool, brick gypsum or other masonry fill will not be accepted.
- Where any entrance hall, public hall or stair hall, or any portion thereof, in any part of any old law tenement of converted dwelling is required to be fire-retarded that portion of any ceiling directly underneath any such entrance hall, public hall or stair hall shall be fire-retarded. Where such ceiling is located in any store, apartment or other space it shall also be fire-retarded as required for partitions by 1 RCNY §§ 15-07(b)(1) or (b)(2). Where the above method is impractical due to the existing ceiling construction in any such store, apartment or other space, the Department of Buildings may permit the fire-retarding of such ceilings to be applied from above by removing the floor of any such entrance hall, public hall or stair hall and installing between the floor beams, and directly against the ceiling below, a layer of heavy building paper over which there shall be placed a basket made of reinforced ribbed expanded metal lath weighing at least 3.4 pounds per square yard. Such basket shall be lined with Portland cement or gypsum mortar not less than one inch (1") in thickness. The building paper, metal lath and cement or gypsum mortar shall be carried at least halfway up on the sides of the beams. However, this method will not be accepted for the fire-retarding of any such ceiling located in a space used for a hazardous purpose or business, nor will it be accepted for the fire-retarding of any such ceiling located in the cellar or for the fire-retarding of any ceiling located in any store, apartment or other space when such ceiling is constructed of wood or of wood and metal applied directly to the beams. In such cases the ceilings shall be fire-retarded according to the requirements of 1 RCNY § 15-07(b)(1) or (b)(2).
- Existing wood stairs. Except where stairs of incombustible material are required in Class B converted dwellings as set forth in 1 RCNY § 15-07(a)(7), all wood railings, balustrades and newel posts shall be completely removed from every existing wood stairs and such stairs shall be provided with railings, balustrades and newel posts of metal or other hard incombustible material, of such size and secured in such manner to the existing stairs as may be approved by the Department of Buildings, except handrails may be of hardwood. Soffits and stringers of existing wood stairs shall be fire-retarded in accordance with the methods set forth in 1 RCNY §§ 15-07(e) or (f).
- Stair soffits. The soffits of every stair in every entrance hall, public hall, and stair hall, including any soffit extending beyond the enclosure partitions of any such hall, shall be fire-retarded. Any approved method for fire-retarding partitions shall be acceptable for fire-retarding stair soffits provided that all existing materials are completely removed to face of structural members of stair soffits.
- Fascia — stair and well. Fascia of outside stringer on rake of stairs, and well fascia at floor level, shall be fire-retarded their full depth to form complete seals with the soffits of stairs and ceilings of halls, respectively. Type of fire-retarding shall be one of those herein approved for ceilings of halls, or in lieu thereof, cover fascia with sheet asbestos not less than three-sixteenths inch (3/16") thick with joints well pointed over which there shall be an additional single layer of No. 26 U.S. gauge stamped metal or cover fascia with a single layer of No. 14 U.S. gauge steel.
- Fire-stopping. All partitions required to be fire-retarded shall be fire-stopped with incombustible material at floors, ceilings and roofs. Fire-stopping over partitions shall extend from the ceilings to the underside of the flooring or roofing above. Fire-stopping under partitions shall extend from the underside of flooring to ceiling below. All spaces between floor joints (directly over and under partitions) shall be completely filled the full depth of the joists. Any space from top of partition to underside of roof boarding shall be completely fire-stopped. Fire-stopping shall be done with brick, cinder concrete, gypsum, metal lath and Portland cement or gypsum mortar, mineral wool, or other materials acceptable to the Department of Buildings.
- Door openings. Except as provided in 1 RCNY §§ 15-07(h)(1) and (h)(2), all door openings into any public hall, entrance hall or stair hall which is required to be fire-retarded shall be equipped with self-closing protective assemblies having a fire-resistive rating of at least one hour.
- In old law tenements where the number of apartments is not being increased, existing wood doors opening into public halls, entrance halls or stair halls may remain provided such doors are made to be self-closing ("Butterfly" spring hinges are not acceptable) and, provided further, all glazed transoms and panels in every such door are glazed with wire glass. All such transoms shall be made stationary.
- Where, in any old law tenement, the number of apartments is being increased on one or more stories, door openings into public halls, entrance halls or stair halls on each story or stories shall be equipped with self-closing protective assemblies having a fire-resistive rating of at least one hour. In such old law tenements existing wood doors opening into public halls, entrance halls or stair halls may remain on any story where there is no increase in the number of apartments, provided such doors and every transom and panel in same are made to conform to the requirements set forth in 1 RCNY § 15-07(h).
- All doors shall be properly fitted to their assemblies and there shall be no unnecessary spaces between doors and door bucks or saddles.
- Materials. All materials used in the process of fire-retarding shall be of a type and manufacture acceptable to the Department of Buildings. The following shall be considered as minimum requirements:
- Metal lath. Metal lath shall weigh at least 30 pounds per square yard, except lath used over existing plaster which lath shall weigh at least 3.4 pounds per square yard and be reinforced with rigid ribs not less than three eighths inch (3/8") deep, spaced not more than eight (8") on center running full length of sheets. Where ribs exceed 4.8 inches on center, same shall have at least one intermediate one eighth inch (1/8") inverted rib running the full length of sheets. Metal lath fastened to stubs shall be attached at least six inch (6") intervals with 4-penny nails or one inch (1") roofing nails or No. 14 steel wire gauge wire staples, and to wood joists by at least 6-penny nails, one and one-quarter inch (1 1/4") roofing nails, or one inch (1") No. 14 steel wire gauge wire staples. When metal lath is applied over existing plastered surfaces, same shall be fastened with nails or staples of the same gauge and such nails or staples shall have anchorage of at least one-half inch (1/2") in studs and three-quarters inch (3/4") in joists. Laps between the studs or joists shall be securely tied or laced. Stiffened metal lath on wood studs, or joists, shall be nailed or stapled at least at eight inch (8") intervals, and the laps between studs similarly tied or laced. Metal lath shall be galvanized or painted.
- Plaster boards or perforated rock lath. Plaster boards or perforated rock lath shall be of type and manufacture acceptable to the Department of Buildings. Each board shall bear the name of manufacturer and brand stamped thereon for inspection after erection. Plaster boards or perforated rock lath nailed directly to wood studding or joists shall be fastened with one and one-eighth inches (1 1/8") wire nails of at least No. 13 steel wire gauge, with flat three-eighth inch (3/8") heads. When such boards are applied over existing plastered surfaces, same shall be fastened with nails of the same gauge and such nails shall have anchorage of at least one-half inch (1/2") in studs and three-quarters inch (3/4") in joists. The maximum space between nails shall be four inches (4"). The joints shall be broken at every other board. The wetting of such boards before plastering is forbidden.
- Stamped metal. Stamped metal shall be No. 26 U.S. gauge (equivalent thickness .018 inches or 3/160 inches) with one inch (1") lapped seams. Size of sheets shall be not more than twenty-four inches by ninety-six inches (24" × 96"), having a selvage consisting of a half-round bead sufficient to create a one inch (1") overlap at both seams. Nailing shall be secured direct to studs or joists with 6-penny smooth box nails (two inches (2") or No. 12 1/2 gauge) with nails on end seams spaced not more than three inches (3") apart. Nailing to plaster is forbidden and in all cases nails shall have anchorage of at least one-half inch (1/2") in studs and three-quarters inch (3/4") in joists. All beads at seams shall be chisel sealed, making a tight joint. All sheets shall be marked "26 U.S. Gauge" for identification and inspection after erection.
- Mineral wool. Mineral wool shall be of a type and manufacture acceptable to the Department of Buildings. Holes shall be cut approximately three inches (3") in diameter through the wood lath and plaster near the ceiling, in the panels between each two adjacent studs. As an alternative, holes may be cut approximately three inches by six inches (3" × 6") on every second stud. Check each stud panel with weight and line to find out whether there is any obstruction. If any cross-bridging or other obstruction is encountered additional holes shall be cut until access has been gained to all open spaces within the stud panel in all specified partitions. Mineral wool shall then be blown into all spaces by the pneumatic method with air pressure sufficient to pack the insulation to a density acceptable to the Department of Buildings. Mineral wool for this work shall be in bags or containers marked with the manufacturer's name and label specifying its type.
- Other materials. No other material may be used unless same is acceptable to the Department of Buildings.
- Exceptions. Where any portion of any entrance hall, stair hall or public hall has been previously fire-retarded under the supervision of this department, the former Tenement House Department or various former Departments of Buildings, such fire-retarding will be accepted only to the extent that same has been previously approved, provided, however, that such entrance hall, stair hall or public hall is otherwise made to conform to all the requirements set forth in these rules.
- Intent. The fire-retarding rules herewith set forth are approved by the Department of Buildings for the existing multiple dwellings where the ceilings of the cellar or other lowest story is required, by § 85 and § 240, subdivision 3, Multiple Dwelling Law, and by § 27-2044, Housing Maintenance Code, to be fire-retarded in a manner approved by the Department of Buildings.
- It is the intent of the law to provide a continuous fire-retarded covering over the entire ceiling of the cellar, or other lowest story, so as to prevent fire communicating with upper stories of a multiple dwelling. Where there is a space less than four feet six inches (4'-6") in height from the ground or floor level to the underside of the first tier of beams, such space shall be considered as an "air space" and not as a cellar. However, when such space opens to a cellar where fire-retarding of the ceiling is required, then such space shall be separated from the cellar with a partition constructed of incombustible material in which there is provided self-closing door and assembly having a fire-resistive rating of at least one hour. Where the ceiling of the cellar or other lowest story is required to be fire-retarded, all openings in such ceilings for stairways not located directly under a main stair, also openings in ceiling such as pipe shafts, vent shafts, unenclosed dumbwaiter shafts, disused flues, etc., shall be properly closed. (Private stairs within duplex apartments extending into cellar or basement are not required to be enclosed.) New partitions erected to enclose existing stair referred to in the preceding paragraph shall be of incombustible materials. Existing partitions enclosing any such stair will be acceptable where same are of incombustible materials or where same are fire-retarded on both sides in accordance with the methods set forth in 1 RCNY § 15-07(b)(1) or (b)(2) and with materials conforming with the requirement of 1 RCNY § 15-07(i). Door openings in such enclosure partitions shall be equipped with self-closing protective assemblies having fire-resistive ratings of at least one hour. When existing shafts, including dumbwaiter shafts, extend below the ceiling a distance less than one-half (1/2) the height of the cellar, such shafts shall be considered as being part of the cellar ceiling and the enclosures of said shafts shall be fire-retarded in the same manner as required for cellar ceilings. All existing shafts, including dumbwaiter shafts, which extend below the ceiling a distance more than one-half (1/2) the height of the cellar shall be enclosed with incombustible materials. All shafts referred to in this paragraph shall have adequate cleanout at base consisting of fire-proof self-closing door and assembly having a fire-resistive rating of at least one hour. Where new partitions or enclosures are erected in a cellar they shall be constructed of incombustible materials.
- Wood girders, columns, posts, etc. The fire-retarding material of ceiling of cellar or other lowest story shall be carried down and around all non-fireproof ceiling projections, such as wood girders, etc., which are less than six inches by six inches (6" × 6") in dimension. The fire-retarding material also shall be turned down at least three inches (3") on all non-fire-retarding columns, posts, etc., which are less than six inches (6") in diameter.
- Non-fire-retarded cellar partitions. When non-fire-retarded partitions in cellar, or other lowest story, extend to the ceiling, the fire-retarding material of the ceiling shall be turned down at least three inches (3") on said partitions, or the partitions shall be cut off at top to permit the fire-retarding of the ceiling to be continuous. Where, in any old law tenement three (3) stories and basement in height, there is also a cellar under the basement story, the ceiling of such cellar shall be fire-retarded; and also, in any such old law tenement, where the main entrance from the grade is to the first story that portion of the basement ceiling which is directly under the first story entrance hall, public hall and stair hall shall be fire-retarded. In every old law tenement three (3) stories and basement in height with no cellar under the basement, where the main entrance from the grade is to the basement story, the ceiling of the basement story shall be fire-retarded throughout. In any such old law tenement where the main entrance from the grade is to the first story no such fire-retarding will be required.
- Heating appliances. The portion of the ceiling over any furnace, boiler or hot water heater shall be fire-retarded in accordance with the methods set forth in 1 RCNY §§ 15-07(b)(1) or (b)(2), and such fire-retarding shall extend for a distance of at least four feet (4'-0") beyond the sides and rear, and eight feet (8'-0") in front of such furnace or boiler.
- It is not intended that these rules and regulations in themselves require plans to be filed. However, should any work involve structural changes, then plans are required to be filed in the Department of Buildings and such changes shall be subject to all other Rules and Regulations applicable thereto.
- Work shall not commence until satisfactory evidence has been submitted to the Department of Buildings that compensation insurance has been obtained in accordance with the provisions of the Workmen's Compensation Law.
- Methods. Cellar ceilings shall be fire-retarded according to any of the following methods: Metal lath and cement or gypsum mortar conforming to 1 RCNY § 15-07(b)(1). Plaster boards and gypsum mortar or stamped metal conforming to 1 RCNY § 15-07(b)(2). No. 26 U.S. gauge stamped metal over existing plastered ceiling, when erected without damage to the plaster. Furring strips are not required, but if used, they shall be metal covered on both sides and on face surface. Stamped metal shall not be applied until after existing plastered ceiling has been inspected and approved by an inspector of the Department of Housing and Buildings. No other method may be used unless same are acceptable to the Department of Buildings.
- Materials. Materials used shall be in accordance with the provisions of 1 RCNY §§ 15-07(i)(1), (i)(2) or (i)(3). Mineral wool, brick, gypsum or other masonry fill will not be accepted for fire-retarding cellar ceilings. No other materials may be used unless same are acceptable to the Department of Buildings.
- Intent. The rules herewith set forth are approved by the Department of Buildings for the protection of cooking spaces under §§ 33 and 176 of the Multiple Dwelling Law. As set forth in § 33 of the Multiple Dwelling Law, nothing in these rules shall be construed as permitting fire-retarding partitions in fireproof multiple dwellings.
- Multiple Dwelling Law. Except when sprinkler heads are installed in conformity with subdivision (e) of this section, § 33 of the Multiple Dwelling Law requires fire-retarding of cooking spaces in existing and newly cconstructed class A and class B multiple dwellings.
- Ceilings and walls exclusive of doors. Walls and ceilings shall be fire-retarded according to any of the following methods: Metal lath and cement or gypsum mortar conforming to 1 RCNY § 15-07(b)(1). Plaster boards and gypsum mortar or stamped metal conforming to 1 RCNY § 15-07(b)(2). No. 26 U.S. gauge stamped metal over existing plaster when erected without damage to the plaster. Furring strips are not required, but if used, they shall be metal covered on both sides and on face surface. Stamped metal shall not be applied until after existing plaster has been inspected and approved by an inspector of the Department of Buildings. Materials used shall be in accordance with the provisions of 1 RCNY §§ 15-07(i)(1), (i)(2) or (i)(3). No other methods or materials may be used unless same are acceptable to the Department of Buildings.
- Combustible material. In every cooking space, all combustible material immediately underneath or within one foot of any apparatus used for cooking or warming of food shall be fire-retarded in conformity with the applicable provisions of these rules or covered with asbestos at least three-sixteenths inch (3/16") in thickness and twenty-six gauge metal or with fire-resistive material of equivalent rating. There shall always be at least two feet (2'-0") of clear space above such apparatus.
- Sprinkler heads installed in ceilings of cooking spaces in lieu of fire-retarding the ceilings and walls. Where sprinkler heads are installed in the ceilings of cooking spaces in lieu of fire-retarding the ceilings and walls, all of the provisions of 1 RCNY §§ 15-09(a) through (f) inclusive, shall be complied with, except that it will not be required that the fire-retarding of the walls and ceilings of cooking spaces be complied with. Before the installation of sprinkler heads is begun an application shall be filed with and approved by the Department of Buildings. Sprinkler heads shall be of a type and manufacture approved by the Department of Buildings or previously approved by the Board of Standards and Appeals or by the Underwriters Laboratories Limited, and shall have fusible struts constructed to fuse at a temperature not higher than two hundred twelve degrees (212°) Fahrenheit. Every sprinkler head shall bear the year of manufacture clearly on its surface. No sprinkler head may be installed after December 31st of the year following the year of manufacture. There shall be provided at least one (1) sprinkler head for every fifty-nine (59) square feet or fraction thereof of the floor area of the cooking space. Sprinkler heads shall be connected with the water supply of the building through a pipe of at least one-half (1/2) inch inside diameter. Where practicable, sprinkler heads shall be located in an upright position on top of the sprinkler piping. There shall be kept available on the premises at all times a sufficient supply of extra sprinkler heads and also a sprinkler wrench for use to replace promptly any fused or damaged sprinkler heads. Any head which has opened or has been damaged shall be replaced immediately with a good sprinkler head. Painting or kalsomining of sprinkler heads is prohibited.
- Cooking spaces constructed after July 1, 1949. Application and plans must be filed with and approved by the Department before any work is started in connection with the construction of any cooking space after July 1, 1949.
- (a) Intent. These rules have been approved by the Department to supplement the provisions of § 53 of the Multiple Dwelling Law in relation to Fire Escapes, fire-stairs, etc. Where fire escapes serve as a means of exit from other than multiple dwellings, such fire escapes shall comply with the laws governing such occupancy. The voluntary erection of fire escapes on private residence buildings or business and residence buildings shall be in conformity with these rules and regulations unless otherwise directed by the Borough Superintendent of the Department of Buildings. It is the intent of these rules to cover only general conditions and they are not designed to cover specific or special cases. When such may occur the owner is required to consult the Department of Buildings and receive instructions before starting of work.
- Fire escapes on multiple dwellings requiring new certificate of occupancy. Except as provided in 1 RCNY § 15-10(g)(2) re lodging houses, double-rung ladder type fire escapes will not be accepted when a new Certificate of Occupancy is required.
- Alterations for increased occupancy. Where an alteration is made increasing occupancy on any story and a fire escape is required such fire escape shall conform to the provisions of § 53 of the Multiple Dwelling Law and to the applicable provisions of these rules.
- (b) General provisions.
- Caution. No fire escapes shall be removed from any apartment without due precaution against leaving occupants without fire escape protection as required by subdivision 9 of § 53 of the Multiple Dwelling Law.
- Entrance story, etc. — second means of egress. Where the distance to safe landing, from the window sill of any apartment on any story, including the entrance story, is more than twelve feet (12'-0"), a balcony and sliding drop-ladder or other approved second means of egress shall be provided for such apartment. Safe egress to street or other safe place shall be provided from the termination of such means of egress.
- Application blanks and plans. Before the erection of new fire escapes or alteration of existing fire escapes upon any multiple dwelling, application must be filed with and approved by the Department of Buildings.
- Projections beyond the building line. Every part of fire escapes or balconies erected on the fronts of multiple dwellings shall be at least ten feet (10') above the sidewalk when such fire escapes or balconies project beyond the building line.
- (c) Illegal fire escapes shall be removed. All vertical ladder, wire, chain or cable fire escapes if required as a means of egress shall be removed and replaced with a legal means of egress.
- (d) Acceptable existing means of egress on existing multiple dwellings. Except as provided in 1 RCNY § 15-10(c), in any existing multiple dwelling any existing means of egress which was lawfully permitted prior to the time the Multiple Dwelling Law became effective may be continued as a legal means of egress as hereinafter enumerated. If located on the front or rear wall of the building and properly connected with stairs with proper openings. If located in an outer court at a point distant not more than thirty feet (30'-0") from the outer end of such court and provided such court is not less than five feet (5'-0") in width from wall to wall at any point between such fire escape and the outer end of said court. If located in an inner court whose least horizontal dimension is not less than fifteen feet (15'-0") measured from wall to wall. If a party-wall balcony on the front or rear wall of the building and there are no doors or openings in the walls between the two buildings other than windows in fireproof air shafts. If a party-balcony located in an outer court not more than fifteen feet (15'-0") in length measured from the outer end of such court to the innermost point thereof, and not less than five feet (5'-0") in width from wall to wall at any point between the fire escape and the outer end of said court, and provided also that there are no doors or openings in the walls between the two buildings other than windows in fireproof air-shafts. No fire escape, however, shall be deemed sufficient unless all the following conditions are complied with: All fire escapes, whether a required means of egress or not, shall be maintained in good order, repair and structurally safe. All parts shall be of iron or stone. Except as provided in 1 RCNY § 15-10(bb) every apartment above the ground floor in each multiple dwelling shall have direct access to a legal fire escape without passing through a public hall. Except party-wall balconies, all balconies shall be connected to each other by means of a stair or, when permitted, by double-rung ladders. All fire escapes, except party-wall balconies, shall have proper drop-ladders in guides from the lowest balcony of sufficient length to reach a safe landing place beneath. All fire escapes not on the street shall have a safe and adequate means of egress from the yard or court to the street or to the adjoining premises. Prompt and ready access shall be had to all fire escapes. Except as provided in 1 RCNY § 15-10(bb), such access shall be through a living room or private hall in each apartment or suite of rooms at each story above the ground floor and shall not include the window of a stairhall, nor shall any such egress be obstructed by sinks or other kitchen fixtures, or in any other way. No existing fire escape shall be extended or have its location changed except with the written approval of the Department of Buildings. Where an existing apartment in a tenement house erected prior to April twelfth, nineteen hundred and one, is located entirely on a court and has no rooms opening on the street or yard, fire escapes hereafter provided for such apartments may be located in courts under the same conditions as prescribed for existing fire escapes in this subdivision. When wire, chain cable or vertical ladder fire escapes are permitted to remain on Multiple Dwellings under the provisions of subdivision 9 of § 53, they shall be considered only as supplemental fire escapes. Such fire escapes shall be maintained in a safe condition of repair at all times and shall be subject to the applicable requirements of all laws and to these rules in relation to maintenance of existing fire escapes. Before a pending violation requiring the removal of such existing fire escapes is superseded or cancelled, an inspection shall be made in accordance with the specific requirements as set forth in the preceding paragraph. Each of the owners of adjoining structures, commonly served by party-wall balconies serving as a required means of egress, shall maintain in good order and repair that portion of each such balcony which is on his property, and each such owner shall maintain egress normally unobstructed and unimpeded from each such balcony to and through his structure. It shall be unlawful for the owner of a structure on which there is a party-wall balcony serving as a required means of egress from an adjoining structure, to remove such party-wall balcony or any portion thereof or to prevent, eliminate or obstruct egress from such party-wall balcony to and through his structure, unless and until such owner has had erected a legal fire escape or other approved means of egress. See also 1 RCNY § 15-10(bb).
- (e) Party-wall balconies.
- New party-wall balconies. The erection of new party-wall balconies shall be subject to the discretion and jurisdiction of the Department of Buildings, provided, however, that there shall be no doors or openings in the wall between the buildings served by such balconies other than windows in fireproof airshafts. New party-wall balconies will not be permitted on adjoining frame multiple dwellings.
- Existing party-wall balconies. Party-wall balconies existing on any multiple dwelling shall afford safe egress, be kept in good order and repair, be constructed so as to be structurally strong and shall be maintained in conformity with all other applicable laws, rules and regulations. Such fire escapes are acceptable on occupied multiple dwellings.
- (f) Party-wall fire escapes. The Department of Buildings my consent to the erection of party-wall fire escapes on adjoining multiple dwellings, to which the occupants have safe, unobstructed access in common, when such party-wall fire escapes are constructed and maintained in accordance with the law and these rules.
- Any existing party-wall fire escape (stairways) connection with and used in common by a multiple dwelling and a non-multiple dwelling is acceptable when such fire escape is maintained in good order and repair and affords safe egress.
- (g) Double-rung ladders.
- Double-rung ladders will not be permitted on new fire escapes.
- Any fire escape existing prior to the enactment of the Multiple Dwelling Law on any multiple dwelling that does not require a certificate of occupancy resulting from an alteration, if structurally sound and in good condition and provided with existing ladders inclined at an angle not exceeding eighty (80) degrees and equipped with double-rung steps and which affords safe egress, shall be deemed to be a legal fire escape. When a Certificate of Occupancy is requested or required in connection with a lodging house which is equipped with a double-rung ladder Fire Escape and such fire escape is in good repair and adequate, except as to type, and only minor violations exist the correction of which will make the premises conform to all other law requirements, the existing double-rung ladder fire escape may be accepted.
- Except as provided in 1 RCNY § 15-10(g)(2) re lodging houses, double-rung ladders are not acceptable when a new Certificate of Occupancy is to be issued.
- (h) Alteration of existing two-balcony fire escapes on existing multiple dwellings. When a building is not more than three (3) stories in height and provided with a balcony on each of the second and third stories, with connecting vertical ladders, and balconies not less than two feet five inches (2'-5") in width and of adequate length, the Department of Buildings may permit the removal of vertical ladders and replacing of the said ladders with regulation sixty (60) degree connecting stairs. Standards shall be one-half inch (1/2") round or square and height of rail at least two feet nine inches (2'-9"). The stairs shall be not less than seventeen inches (17") wide with a passageway between string and wall or string and top rail of not less than fourteen inches (14"). In lieu of such passageway, the Department of Buildings will permit a drop-ladder to be installed and placed at each end of the lowest balcony in those cases where it is impractical to provide a passageway of such minimum width. New brackets shall be provided where necessary. The gateway shall be cut in the front rail with a drop-ladder and guides from second (2nd) story to safe landing. Where fire escapes are located at rear of building a gooseneck ladder shall be provided. The gooseneck ladder may be placed at an angle from the top floor balcony to the roof. When placed at an angle a minimum space of twenty-four inches (24") shall be maintained between the strings and front top rail and a minimum space of fourteen inches (14") between the strings and the front bottom rail. There shall be a space of at least twenty-four inches (24") between the string of the gooseneck ladder and the frame of the window. Conditions may be found where this modification will not exactly apply. When such a condition is found it should be brought to the attention of the Department of Buildings for decision. When fire escapes are at the front no gooseneck ladder shall be required. When access to such existing two-balcony fire escape is solely by means of a window in a bathroom, the doors of such bathrooms shall be glazed with glass other than wire glass and all key or cylinder locks shall be removed from doors. In such bathrooms there shall be no fixture located in front of the window opening to fire escape. Such altered two-balcony fire escape shall conform to all other requirements of law and these rules and regulations.
- (i) Accessibility of fire escapes from apartments, rooms, kitchenettes and other spaces. Prompt and ready access shall be had to all fire escapes and, except as provided in 1 RCNY § 15-10(bb), such access shall be through a living room, kitchenette or private hall in each apartment or suite of rooms at each story above the ground floor. Access to fire escapes shall not include the window of a stairhall, nor shall any such egress be obstructed by sinks or other kitchen fixtures, or in any other way. A clear space of at least twenty-one inches (21") must be maintained as a passageway between any fixtures and the side of an opening leading to fire escapes. In any apartment which is occupied by a "family" as defined in § 4(5), Multiple Dwelling Law, and in which one or more living rooms are rented to boarders of lodgers, every such room shall be directly accessible to a fire escape without passing through a public hall, and for separately occupied living rooms access to fire escapes shall be direct from such rooms without passing through a public hall or any other separately occupied room, except as may be permitted in §§ 66, 67, and 248 of the Multiple Dwelling Law.
- Egress from apartments used for "Single Room Occupancy". No room in any apartment shall be so occupied for "single room occupancy" unless each room therein shall have free and unobstructed access to each required means of egress from the dwelling without passing through any sleeping room, bathroom or water-closet compartment. In apartments used for "single room occupancy" there shall be access to a second means of egress within the apartment without passing through any public stair or public hall. On and after July 1, 1957, every tenement used or occupied for single room occupancy in whole or part under the provisions of § 248, Multiple Dwelling Law, and which does not have at least two means of egress accessible to each apartment and extending from the ground story to the roof, shall be provided with at least two means of egress, or, in lieu of such egress, every stair hall or public hall, and every hall or passage within an apartment, shall be equipped on each story with one or more automatic sprinkler heads approved by the department. Elevator shafts in such tenements shall be completely enclosed with fireproof or other incombustible material and the doors to such shafts shall be fireproof or shall be covered on all sides with incombustible material. In apartments used for "single room occupancy" where access to a required means of egress is provided through a room such access to such room shall be through a clear opening at least thirty inches (30") wide extending from floor to ceiling and such opening shall not be equipped with any door frame, or with any device by means of which the opening may be closed, concealed or obstructed.
- (j) Window bars, gates, etc. No iron bars, gates or other obstructing devices will be permitted on any window giving access to fire escapes or where such window provides a secondary means of egress in case of fire on any story, including the ground floor, basement, cellar, etc. Windows on grade level at sidewalk, yard or court, or at roof level of an adjoining building, may have bars, but at least, one window in any apartment or suite of rooms shall be without bars or obstructions of any kind in order to afford a second means of egress and such window shall conform to the provisions of 1 RCNY § 15-10(k).
- (k) Windows and doors to fire escapes. The window or door giving access to fire escapes shall not be less than two feet (2') in width and the sill of the window shall not be more than three feet (3') above the floor. Window openings shall be not less than two feet six inches (2'-6") high in the clear.
- Steel casement sash. Steel casement sash opening outward onto any fire escape balcony three feet six inches (3'-6") in width will be permitted, provided such sash is equipped with approved extension hinges so that, when opened, the sash will be flat against the wall, and further provided that there will be no adjusters on the sash as part of its equipment. Passageway of fourteen inches (14") clear width is required to be maintained between the sash or hinges and any portion of the fire escape when the sash lies flat against the wall. When casement sash is set at right angle to the fire escape stairway a clear radial width of twenty inches (20") must be provided.
- Wire screens and storm windows. Wire screens are permitted on a door or window giving access to a fire escape. Such screens may be of the rolling type, casement or of a type that slides vertically or horizontally in sections, providing that there shall be a clear unobstructed space two feet (2') in width and two feet six inches (2'-6") in height when the screens are opened and further provided that no such screen shall be subdivided with muntins or other dividing or separating bars into spaces less than two feet (2') in width by two feet six inches (2'-6") in height. Storm sash and storm doors are permitted on openings giving access to fire escapes provided they are arranged so as to be easily and readily opened from the inside and do not obstruct or interfere with safe egress.
- (l) Egress from fire escape balconies not to be obstructed. Egress from fire escape balconies must not be obstructed by signs, fixed awnings or any other obstruction.
- (m) Extension roofs used as means of egress or directly under fire escape balcony.
- Hereafter erected extension roofs. Where the roof of an extension hereafter erected is to be used as a means of egress from a fire escape, or where a fire escape balcony is located directly above said roof, such roof shall be of fireproof construction.
- Existing extension roofs. Except in converted dwellings where sprinklers may be installed, in every multiple dwelling where a fire escape balcony is situated over and not more than eight feet (8') above a non-fireproof roof, or where a non-fireproof roof of an extension is to be used as egress from fire escapes, the entire ceiling of said extension must be fire-retarded with metal lath and cement or gypsum mortar in the manner prescribed in 1 RCNY § 15-07(b)(1) and (i)(1), or with one-half inch (1/2") approved plaster boards lined with No. 26 U.S. gauge stamped metal. In buildings requiring the issuance of a Certificate of Occupancy as a result of being altered structurally, the only approved method shall be with cement of gypsum mortar and metal lath weighing not less than three (3.0) pounds per square yard which shall be applied directly to the beams or other structural members. Where the roof of an existing extension is used as fire egress, a balcony shall be provided at the level of the roof and, if the distance between the said balcony and a safe landing is more than sixteen feet (16'-0"), a landing platform must be provided not more than ten feet (10'-0") from said safe landing and this landing platform and the balcony on the roof level must be connected by a regulation stairway. From the landing platform a drop-ladder in guides must be provided so as to reach the safe landing. A balcony and drop-ladder in guides as per 1 RCNY § 15-10(r)(11) shall be provided for every two fire escape stacks or fraction thereof using an extension roof for landing and fire egress.
- Skylights on extensions. Any existing skylights in said roof must be constructed of incombustible material whenever deemed necessary. Where skylights exist or are hereafter constructed on the roof of an extension used as a means of egress from a fire escape, they must not interfere with egress in any way and if in the line of said egress, they must be provided with a substantial guard-rail not less than three feet six inches (3'-6") high.
- (n) Egress to street required from fire escapes located in yards and courts not extending to the street. In an old law tenement or a converted dwelling where fire escapes are located in a yard less than thirty feet (30'-0") in depth, or in a court which does not extend to such a yard or to the street, there shall be egress to the street by means of a fire-proof passageway. In such multiple dwellings, where the yard is less than thirty feet (30'-0") in depth and where the consent of the owner of the adjoining premises is obtained, in lieu of providing such fire-proof passageway, a door or gate in a lot-line fence leading from such yard or court to the yard or court of the adjoining premises may be accepted, provided, however, that such door or gate provides adequate egress and is not locked or secured in any manner except by a readily-accessible, easy to open hook or bolt. Where fire escapes are located in the yard of a new law tenement or of a multiple dwelling erected after April 18, 1929, access shall be provided from the street to the yard either in a direct line or through a court as provided in paragraph c of subdivision 2 of § 238 and paragraph i of subdivision 2 of Section 27, Multiple Dwelling Law. Where fire escapes are located in a court of a new law tenement or of a multiple dwelling erected after April 18, 1929, and such court does not extend to the street, a fireproof passageway leading directly to the street shall be provided as required by paragraph b of subdivision 2 of § 53, Multiple Dwelling Law. All passageways required under these rules shall be not less than seven feet (7'-0") in height and not less than three feet (3'-0") in width and shall at all times be kept clear and unobstructed. Doors and gates at the end of such passageways are prohibited, except that a door or gate equipped with an approved-type knob or panic belt which shall be readily openable from the inside will be permitted at the building line. Doors and gates provided with keylocks or padlocks are prohibited.
- (o) Location for new fire escapes. No required fire-escape shall be permitted to be placed on an adjoining property without the written consent of the Department of Buildings. No fire escape shall be erected within ten feet (10') of the termination of a duct. Fire escapes for existing multiple dwellings shall be located as required by the department and arranged so as to provide legal egress for all rooms and apartments.
- Fire escapes in court (side yard). Except as provided in 1 RCNY § 15-10(bb)(6) where an apartment has a street frontage and extends also to a yard, fire escapes may be permitted to be placed in a court (side yard) if the court (side yard) is not less than seven feet (7'-0") wide. In any multiple dwelling where exterior structural conditions are such as to prevent the erection of a fire escape on the street front or yard, new fire escapes may be permitted to be erected in a lot-line court (side yard) providing the lot-line court (side yard) extends from street to rear yard and is not less than three feet (3'-0") in width for its full length. Fire escapes erected in such court may be three feet (3'-0") wide when the width of such court does not permit balconies three feet four inches (3'-4") in width. The width of stairways and passageways and other arrangement details affected by the permitted reduction in the width of balconies will be determined and furnished to contractor by the Department upon request.
- Where an existing apartment in a tenement erected prior to April 12, 1901, is located entirely on a court and has no rooms opening on the street or yard, fire escapes hereafter provided for such apartments may be located in courts under the same conditions as prescribed for existing fire escapes in 1 RCNY § 15-10(d).
- (p) Materials. All fire escapes hereafter constructed shall consist of outside open balconies and stairways of iron, stone, or other approved materials. Wherever the term wrought iron is used in these rules it shall be deemed to include all other especially approved metals. Cast iron will not be permitted to enter into the construction of fire escapes. The use of old material in the construction of new fire escapes is prohibited. Bolts used in the construction or repair of fire escapes shall be machine bolts. The use of stove bolts is prohibited. The strength and construction of stone balconies hereafter erected forming part of the fire escape shall be subject to the approval of the Department of Housing and Buildings. All structural steel used in the construction of fire escapes shall be at least one-quarter (0.25) inch in thickness.
- (q) Types of fire escapes. There shall be two types of fire escapes: "Type A" and "Type B". Except for brackets and braces as hereafter described, what is applicable to one type is equally applicable to the other whether or not it is so stated specifically.
- Definition of "Type A" and "Type B" fire escapes. A "Type A" fire escape is one which has a supporting bracket at each end of the balcony or platform. A "Type B" fire escape is one which has brackets not more than four feet (4') apart supporting the balcony or platform.
- Cantilever brackets will not be accepted for new fire escapes on existing buildings.
- Details of other types of structural supports for fire escapes must be submitted to and approved by the Department before being used in the construction of fire escapes.
- "Type A" fire escapes are not permitted on frame buildings, walls or hollow masonry constructions, on walls of solid masonry less than eight inch (8") in thickness nor on hollow walls of solid masonry unless complete construction details are submitted to and approved by the Department before the construction of fire escapes.
- (r) Balconies. All balconies, except those erected upon frame buildings and buildings having eight inch (8") brick walls, shall be not less than three feet four inches (3'-4") in width over all and may project into the public highway to a distance not greater than four feet (4') beyond the building line. Balconies erected upon frame buildings and buildings having eight inch (8") brick walls shall be thirty-six inches (36") in width. Balcony railings must be not less than two feet nine inches (2'-9") high.
- Passageway. Seventeen inches (17") in width is required between the strings of stairs and the wall, or between the strings of stairs and railings, clear of all projections to a height of six feet six inches (6'-6"). Fourteen inches (14") clear width is required between the hatchway railing and the window sill. Seventeen inches (17") in width is required between the gooseneck ladder and the hatchway on the upper balcony.
- Openings. The openings for stairways in all balconies shall be not less than twenty-one inches (21") wide, and of such length as to provide at least six feet six inches (6'-6") clear headroom on all stairways at every tread, and shall have no covers of any kind. A round, iron guard rail, three-quarters inch (3/4") in diameter shall be provided around all hatchways on all new balconies, and also, when necessary, around hatchways on existing balconies. Such guard rails shall be at least two feet six inches (2'-6") high and shall be properly braced at intervals of three feet (3'). The brace from guard rail to the front top rail shall be so arranged to allow six feet six inches (6'-6") of headroom on the stairway. Openings are not permitted in the floor of the lowest balcony of any new fire escapes. Egress must be from a gateway in the front or end rail.
- Top rails. New top rails must be one and three-quarters inches by one-half inch (1 3/4" × 1/2") wrought iron or steel. Angle iron top rails will not be accepted. Separate bolt ends must be one and one-half inches by one-half inch (1 1/2" × 1/2") at connection with top rails and secured to the same by two three-eighths inch (3/8") bolts well upset. No welded connections, other than shop welding, for top rails, will be permitted. Top rails must go through the wall. When the wall is of brick, stone or concrete they must be anchored on the inner face thereof by means of nuts and four-inch by four-inch by three-eighths inch (4" × 4" × 3/8") washers. Where a masonry wall is eight inches (8") in thickness the washers shall be continuous and shall extend vertically from four inches (4") below the bracket anchorage to four inches (4") above the top rail. Bolt ends must be at least three-quarters inch (3/4") in diameter. Top rails must be anchored in the wall at least nine inches (9") from the window or door opening. On recess fire escapes the top rails need not go through the wall, but must be hot leaded six inches (6") in brick or stone and at least twelve inches (12") from the outside face of the wall. The front and return top rail, unless in one (1) piece, must be secured at the angle in the following manner: (1) with lap joint, by one-half inch (1/2") rivet and a strap of same dimension as the top rail, with one (1) three-eighths inch (3/8") rivet or bolt in each end of the strap; (2) with butt joint, by a triangular plate four inches by six inches by three-eighths inch (4" × 6" × 3/8") secured to each member of the top rail by two (2) three-eighths inch (3/8") rivets or bolts. Top rails may be spliced with iron of the same dimensions as the rails with two (2) three-eighths inch (3/8") rivets or bolts on each side of the splice, or may be overlapped not less than eight inches (8") and secured by two (2) three-eighths inch (3/8") bolts or rivets. Where front rails are not rigid they must be braced with outside braces. Said braces must be wrought iron not less than one and three-quarters inches by one-half inch (1 3/4" × 1/2") placed on edge. The braces must be properly spaced and secured to the extended brackets and top rails by three-eighths inch (3/8") rivets or bolts. Where brackets are extended to receive outside braces the extended portion must never be less than two inches by one-half inch (2" × 1/2") and secured to the bracket by two (2) three-eighths inch (3/8") rivets or bolts. Bow braces and over head braces will not be accepted.
- Bottom rails. Bottom rails must be one and one-half inches by three-eighths inch (1 1/2" × 3/8") wrought iron and front rail of same must be secured to brackets by three-eighths inch (3/8") rivets or bolts. Return bottom rails must be leaded or cemented in the wall when the latter is of brick, or may be secured to the brackets when this is practicable. The bottom front and return rails must be connected at angles by at least one (1) three-eighths inch (3/8") rivet or bolt well burred. They may be spliced as in case of top rails.
- Standards. Standards must be not less than one-half inch (1/2") round or square set vertically, riveted to the top and bbottom rails, not more than six inches (6") apart on centers. Special designs must be submitted for any variation, and approved before work is begun.
- Floor slats. Floor slats must be of wrought iron one and one-half inches (1 1/2") in width and three-eighths inch (3/8") thick and placed not more than one and one-quarter inches (1 1/4") apart. In new balconies floor slats shall not project more than six inches (6"), and in old balconies not more than eighteen inches (18"), beyond the end bracket and shall not be supported by the bottom rail. All floors must be well secured to the brackets by three-eighths inch (3/8") "U" or damp bolts. Floor slats may be spliced with a four-inch (4") splice late three-eighths inch (3/8") thick, secured by three-eighths inch (3/8") countersunk or round-head bolts or rivets on each side of the joint. The ends of the floor slats must not project over stairs so as to overhang the top tread more than one-half inch (1/2"). The ends of such floor slats shall not be cut or burned off so as to be jagged or uneven. The floor slats shall be in true alignment.
- Battens. Battens must be one and one-half inches by three-eighths inch (1 1/2" × 3/8") not more than three feet (3') apart, riveted to the slats by five-sixteenth inch (5/16") rivets and so spaced as to secure rigidity. No welded connections, other than shop welding, for top rails will be permitted. Top rails must go through the wall. When the wall is of brick, stone or concrete they must be anchored on the inner face thereof by means of nuts and four-inch by four-inch by three-eighths inch (4" × 4" × 3/8") washers. Where a masonry wall is eight inches (8") in thickness the washers shall be continuous and shall extend vertically from four inches (4") below the bracket anchorage to four inches (4") above the top rail. Bolt ends must be at least three-quarters inch (3/4") in diameter. Top rails must be anchored in the wall at least nine inches (9") from the window or door opening. On recess fire escapes the top rails need not go through the wall, but must be hot leaded six inches (6") in brick or stone and at least twelve inches (12") from the outside face of the wall. The front and return top rail, unless in one (1) piece, must be secured at the angle in the following manner: (1) with lap joint, by one-half inch (1/2") rivet and a strap of same dimension as the top rail, with one (1) three-eighths inch (3/8") rivet or bolt in each end of the strap; (2) with butt joint, by a triangular plate four inches by six inches by three-eighths inch (4" × 6" × 3/8") secured to each member of the top rail by two (2) three-eighths inch (3/8") rivets or bolts. Top rails may be spliced with iron of the same dimensions as the rails with two (2) three-eighths inch (3/8") rivets or bolts on each side of the splice, or may be overlapped not less than eight inches (8") and secured by two (2) three-eighths inch (3/8") bolts or rivets. Where front rails are not rigid they must be braced with outside braces. Said braces must be wrought iron not less than one and three-quarters inches by one-half inch (1 3/4" × 1/2") placed on edge. The braces must be properly spaced and secured to the extended brackets and top rails by three-eighths inch (3/8") rivets or bolts. Where brackets are extended to receive outside braces the extended portion must never be less than two inches by one-half inch (2" × 1/2") and secured to the bracket by two (2) three-eighths inch (3/8") rivets or bolts. Bow braces and over head braces will not be accepted.
- Landings. Landings at the head and foot of stairs shall be at least forty inches by twenty inches (40" × 20"), except on the balcony on the top story where the gooseneck ladder is located such landing shall be not less than forty inches by thirty inches (40" × 30"). On the lowest balcony where the opening to drop-ladder is in the return rail at front of the lowest tread the landing must be at least forty inches by thirty-six inches (40" × 36").
- Egress from lowest balcony. The gateway in the rail must be of sufficient width to permit the proper installation of the drop-ladder and guide-rods. Where the opening to the drop-ladder is in the return rail and at front of the lowest step, the landing at the foot of the stairs must be at least three feet by three feet, four inches (3' × 3' × 4"). Top rails must be well braced at the gateway.
- Distance from lowest balcony to ground. The distance from the lowest balcony to the ground or safe landing shall be not more than sixteen feet (16'-0"), except that in existing multiple dwellings where due to structural conditions, such as plate glass store fronts, etc., it is not possible to erect such lowest balcony within sixteen feet (16'-0") of the ground, the Department of Buildings may permit such balcony to be erected at a height of not more than eighteen feet (18'-0") above the ground.
- Termination of fire escapes on extension roofs. Where fire escape stairs or ladders rest upon a fireproof roof, no balcony need be provided at the foot of such stairs or ladders. Where fire escapes terminate on the roof of an existing extension, a guide-rod drop-ladder shall be provided at the level of the roof of such extension. Where the distance from such roof to a safe landing is more than sixteen feet (16'-0"), an intermediate balcony not more than ten feet (10'-0") above a safe landing shall be provided, and such intermediate balcony shall be equipped with a guide-rod and drop-ladder and connected by means of a regulation stairway and balcony at the level of the extension roof. Balconies, where required, must be anchored and constructed in a manner satisfactory to the Department of Buildings. The roof of every extension used for egress, or upon which fire escapes terminate, shall be fireproof or fire-retarded according to the provisions of 1 RCNY § 15-10(m).
- (s) Brackets and braces.
- "Type A". All horizontal members of brackets and all cross beams shall be not less than four-inch (4") channels weighing not less than seven and one-quarter (7.25) pounds to the linear foot. The end bracket members shall enter the wall at a point not less than nine inches (9") from a door or window and shall be anchored on the inside face of the wall with an eight-inch by eight-inch by three-eighths inch (8" × 8" × 3/8") washer and a one-inch (1") bolt and nut. Where the wall is eight inches (8") in thickness the washer shall be continuous and shall extend across all brackets and cross beams. The bolt end shall be wrought iron not less than two inches by one-half inch (2" × 1/2") which shall be drawn out to form the necessary bolt end without welded connections. The bolt end shall be secured to the bracket with two (2) one-half inch (1/2") rivets. On eight-inch (8") walls the bolt end shall not be less than nine inches (9") long. On twelve-inch (12") walls the bolt end shall not be less than eleven inches (11") long. On sixteen-inch (16") walls the bolt end shall not be less than fifteen inches (15") long. When the wall is eight inches (8") in thickness the bracket member shall enter the wall not less than seven inches (7"). When the wall is twelve inches (12") in thickness the bracket member shall enter the wall not less than eleven inches (11"). When the wall is sixteen inches (16") in thickness the bracket member shall enter the wall not less than fifteen inches (15"). The intermediate cross beams shall enter the wall not less than eight inches (8") except where they enter the wall under a window. In such case the cross beam shall enter the wall not less than four inches (4"). The member forming the hatchway opening shall be a four-inch (4") channel iron weighing not less than seven and one-quarter (7.25) pounds per foot. It shall be secured to the intermediate cross beam with a three-inch by three-inch by one-quarter inch (3" × 3" × 1/4") lug and two (2) one-half inch (1/2") rivets or bolts. The front bottom member of the fire escape shall be of the following size and weights:
Length of Balcony Weight of Channels Size of Channels Up to 11 feet 9.0 pounds per foot 5 inches Up to 13 feet 10.5 pounds per foot 6 inches Up to 15 feet 12.25 pounds per foot 7 inches Up to 17 feet 13.75 pounds per foot 8 inches
The bracket braces shall be angle iron not less than two and one-half inches by two and one-half inches by one-quarter inch (2 1/2" × 2 1/2" × 1/4"). The braces shall drop not less than twenty-four inches (24") from the top of the bracket and shall extend out to a point not less than three-quarters (3/4) of the length of the bracket. Each member of the brace shall be secured to the bracket with two (2) one-half inch (1/2") rivets. The drop member of the brace shall be secured to the extended member with two (2) one-half inch (1/2") rivets. The heel of the brace shall be cut out one-half inch (1/2") to allow for the drainage of water. Where, owing to cornices, water-tables and porticos, it is impossible to use the standard brackets, inverted brackets may be used. When inverted brackets are used they shall be constructed with an upright wall member and a diagonal member. The wall member shall be an angle iron not less than three inches by four inches by three-eighths inch (3" × 4" × 3/8") and the diagonal member shall be an angle iron not less than three inches by three inches by three-eighths inch (3" × 4" × 3/8"). Each member shall be secured to the bracket with two (2) one-half inch (1/2") rivets. The wall members shall be secured to the wall with two (2) one-inch (1") bolts which shall pass through the wall and be anchored on the inside face of the wall with a washer four inches by three-eighths inch (4" × 3/8") which shall extend across the two (2) bolts. A one-inch (1") nut shall secure the washer to the bolt. The bolts shall be placed sixteen inches (16") apart on centers. The four-inch (4") member of the wall brace shall bear against the wall and shall extend from the bracket to and above the top return rail of the balcony. The top return rail of the balcony shall be secured to the wall member of the brace with two (2) one-inch (1") rivets or nuts and bolts. When inverted braces are used the bracket member shall enter the wall not less than four inches (4"). All other portions of "Type A" fire escapes, except roof balconies, shall be constructed and erected as specified for the construction and erection of "Type B" fire escapes. - "Type B". The horizontal members of brackets shall consist of a one-piece wrought iron bar two inches by one-half inch (2" × 1/2") set so that the two inch (2") dimension is vertical. Brackets shall be not more than four feet (4'-0") apart. Welded brackets will not be accepted. Angle iron brackets will not be accepted. The top member of the bracket must be drawn out to form the necessary bolt end without welded connection. Brackets shall be placed not less than eight inches (8") nor more than sixteen inches (16") below the window sill, except by special permission from this Department. The top member of the bracket must go through the wall, and when the wall is of brick, must be anchored as specified for brackets in new buildings. Brackets on buildings in course of erection must be built into the wall. They must be carried through the wall and turned down three inches (3"), or the top member must be drawn out so as to form a bolt end one inch (1") in diameter and provided with nuts and with washers four inches by six inches (4" × 6") and three-eighths inch (3/8") in thickness, or where brackets on existing buildings or buildings in the course of erection pass through the walls under window or door openings, such brackets shall be anchored on the inside face of the wall with a four-inch by three-eighths inch (4" × 3/8") plate extending across the opening and bearing nine inches (9") on the inner face of each pier. In such case an additional one-half inch (1/2") bolt passing through wall and anchored to plate with one-half inch (1/2") nut shall be provided. If wall is recessed said bar must be shaped so as to bear on inner face of recessed wall and the ends of said bar to bear nine inches (9") on inner face of each pier. In addition a four-inch (4") steel channel stiffener must be provided to extend across the entire recessed portion. Blocking the recessed portion will not be permitted. Where walls are eight inches (8") in thickness the four-inch by three-eighths inch (4" × 3/8") plate must extend across and take in all brackets. Special designs must be submitted for fire escape framing other than standard and for masonry openings not included in above schedule. Horizontal members of brackets must be braced with one-inch (1") square braces and shall rest on a shoulder. The braces shall be secured to the horizontal member with a rivet one-half inch (1/2") in diameter, at a point two-thirds (2/3") of the length of the horizontal member from the wall. The heel of the brace must be secured to the top member by a rivet of the same size. The brace when entering the wall must be hot leaded in brick or stone three inches (3") and have a proper bearing on the face of the wall for at least eight inches (8"). If wedges are used to obtain full bearing against the wall, they must be of iron and well secured to the brace and must fill in solidly the space between brace and wall. Anchorage in or bracing in terra cotta is not permitted. Braces must drop at least one-third (1/3) of the length of the long brackets and must drop not less than eight inches (8") for short brackets. Where a bracket is to receive additional weight on account of suspension rod for lower balconies, said bracket must be reinforced by an additional one-inch (1") square brace running from the end of the bracket parallel to the regulation brace. Where it is impossible to brace the brackets in the manner described above, angle iron and tie rod supports must be used.
- Anchorages for mullion windows, both "Type A" and "Type B".
Masonry Span Brackets Anchorage Member 5'-0" 3'-6" long 6" channel 10.5 pounds or 6" × 4" × 9/16" angle 6'-0" 3'-6" long 7" channel 9.8 pounds or 6" × 4" × 11/16" angle 7'-0" 3'-6" long 8" channel 11.5 pounds or 7" channel 12.25 pounds 8'-0" 3'-6" long 8" channel 11.5 pounds 9'-0" 3'-6" long 8" channel 13.75 pounds 5'-0" 4'-0" long 8" channel 11.5 pounds or 6" × 4" × 3/4" angle 6'-0" 4'-0" long 8" channel 11.5 pounds 7'-0" 4'-0" long 8" channel 13.75 pounds 8'-0" 4'-0" long 8" channel 16.25 pounds 9'-0" 4'-0" long 8" channel 21.25 pounds
Notes: l — Working stresses taken at 16,000 pounds per square inch.
Notes: 2 — Load taken at 100 pounds per sq. ft. and includes live and dead loads.
Notes: 3 — Loads on anchorage members due to bracket reaction placed for maximum bending moment produced in member.
Notes: 4 — Bearing plates of suitable size must be provided for brackets taking ladder load and for anchorage members.
6" × 4 9/16" angle weighs 18.1 pounds per lin. ft.
6" × 4 11/16" angle weighs 21.8 pounds per lin. ft.
6" × 4 3/4" angle weighs 23.6 pounds per lin. ft.
Angle irons to support balconies where regulation braces cannot be used shall not be less than four inches by four inches by three-eighths inch (4" × 4" × 3/8"). Tie rods shall not be less than one inch (1") in diameter and shall be anchored through the wall in the same manner as brackets. The angle iron support in such cases shall be set so that the tie rods will pull toward the heaviest part of the webs. When it becomes necessary to shift a bracket from one location to another in order to carry the stairs, a new regulation two inch by one-half inch (2" × 1/2") bracket shall be installed. No welded brackets, corroded brackets or brackets set flat with cast iron under-bracing will be accepted. Such brackets shall be replaced, wherever found, by a two-inch by one-half inch (2" × 1/2") rregulation bracket. However, when a two inch by one-half inch (2" × 1/2") bar bracket with cast iron under-bracing is found, said bracket may be permitted to remain if proper one inch (1") square under-bracing is provided.
- "Type A". All horizontal members of brackets and all cross beams shall be not less than four-inch (4") channels weighing not less than seven and one-quarter (7.25) pounds to the linear foot. The end bracket members shall enter the wall at a point not less than nine inches (9") from a door or window and shall be anchored on the inside face of the wall with an eight-inch by eight-inch by three-eighths inch (8" × 8" × 3/8") washer and a one-inch (1") bolt and nut. Where the wall is eight inches (8") in thickness the washer shall be continuous and shall extend across all brackets and cross beams. The bolt end shall be wrought iron not less than two inches by one-half inch (2" × 1/2") which shall be drawn out to form the necessary bolt end without welded connections. The bolt end shall be secured to the bracket with two (2) one-half inch (1/2") rivets. On eight-inch (8") walls the bolt end shall not be less than nine inches (9") long. On twelve-inch (12") walls the bolt end shall not be less than eleven inches (11") long. On sixteen-inch (16") walls the bolt end shall not be less than fifteen inches (15") long. When the wall is eight inches (8") in thickness the bracket member shall enter the wall not less than seven inches (7"). When the wall is twelve inches (12") in thickness the bracket member shall enter the wall not less than eleven inches (11"). When the wall is sixteen inches (16") in thickness the bracket member shall enter the wall not less than fifteen inches (15"). The intermediate cross beams shall enter the wall not less than eight inches (8") except where they enter the wall under a window. In such case the cross beam shall enter the wall not less than four inches (4"). The member forming the hatchway opening shall be a four-inch (4") channel iron weighing not less than seven and one-quarter (7.25) pounds per foot. It shall be secured to the intermediate cross beam with a three-inch by three-inch by one-quarter inch (3" × 3" × 1/4") lug and two (2) one-half inch (1/2") rivets or bolts. The front bottom member of the fire escape shall be of the following size and weights:
- (t) Stairways. All stairways shall be placed at an angle of not more than sixty (60) degrees with flat open steps not less than six inches (6") in width and twenty inches (20") in length and with a rise of not more than nine inches (9").
- Treads. Treads of such construction as may be approved by the Department from time to time will be permitted. Flat iron bars forming treads must be one and one-half inches by three-eighths inch (1 1/2" × 3/8") and spaced not more than three-quarters of an inch (3/4") apart. Bars forming treads must be secured to supporting angle irons by three-eighths inch (3/8") rivets and these angle irons must be fastened to the strings by two (2) three-eighths inch (3/8") rivets or bolts, well burred. Galvanized angle irons one and one-half inches by one and one-half inches by one-quarter inch (1 1/2" × 1 1/2" × 1/4") will be accepted but if not galvanized, said angle irons shall be one and one-half inches by one and one-half inches by three-eighths inch (1 1/2" × 1 1/2" × 3/8"). In all cases the vertical legs of the angle irons must be set tightly against the strings so that there will be no intervening spaces. All treads must be set level and must not overhang so as to interfere with foot room on the tread below.
- Patented treads. Patented treads approved by the Department of Buildings or previously approved by the Board of Standards and Appeals for new installations will be accepted by the Department of Buildings as legal for use in buildings under its jurisdiction. Five samples of approved treads to be furnished to the Department of Buildings (one delivered to each borough) as a permanent record.
- Strings. Where the strings of the stairs are adjacent to the front rails the strings must be securely fastened to the top rails. Strings must be braced by round bars three-quarters inch (3/4") in thickness, properly hot-leaded or secured by four inches by three-eighths inch (4" × 3/8") expansion bolts in brick or stone wall at height of not less than six feet six inches (6'6") in the clear above the floor of the balcony. Strings of stairways shall be four inches by three-eighths inch (4" × 3/8") wrought iron and shall rest on a bracket at the bottom and be bolted to a bracket at the top. Welded strings, other than shop welded, will not be accepted.
- Hand rails. Hand rails must be of wrought iron, three-quarters inch (3/4") round or one and one-half inches by three-eighths inch (1 1/2" × 3/8") bar, well braced with intermediate braces not more than five feet (5'-0") apart, and of the same size and material as the hand rail, and secured to the strings with two (2) three-eighths inch (3/8") rivets at each end and at each brace; or hand rails may be secured to the bottom rail of the upper balcony and top rail of the lower balcony by two (2) three-eighths inch (3/8") rivets at each end. On all fire escapes hereafter erected double hand rails must be provided for all stairways.
- (u) Drop-ladder. A drop-ladder shall be provided from the lowest balcony and be of sufficient length to reach a safe landing place beneath. The drop-ladder shall be fifteen inches (15") in width, shall be placed in guides and shall be not more than sixteen feet (16'-0") in length. Except in multiple dwellings hereafter erected or converted, where the distance from the lowest balcony to a safe landing place is more than sixteen feet (16'-0") but because of structural conditions, such as plate glass store fronts, etc., a balcony is not possible, the department may accept a drop-ladder in guides, if the distance from the floor of the lowest balcony to a safe landing place is not more than eighteen feet (18'-0"). No drop-ladder is required where the distance from the lowest balcony to a safe landing place does not exceed five feet (5'-0"). No drop-ladder will be permitted to land or terminate on a stoop or any part thereof unless the written approval of the Department of Buildings is obtained.
- Guides. All drop-ladders shall have guides provided with stops so that the ladders cannot be raised above the same. The drop-ladder must be suspended from a point directly over the opening in the rail of the balcony and arranged to slide in the guides so as to drop in position for use. All drop-ladders shall be provided with a shoe at the bottom. The guides shall be constructed of one and one-half inches by one and one-half inches by one-quarter inch (1 1/2" × 1 1/2" × 1/4") angle iron, and shall be not less than twenty-one inches (21") apart.
- Strings. Strings of drop-ladders must be one and one-half inches by three-eighths inch (1 1/2" × 3/8") bar. No welded drop-ladders will be accepted unless shop welded.
- Rungs. The rungs must be five-eighths inch (5/8") in thickness, not over twelve inches (12") apart and must be riveted to the strings.
- (v) Gooseneck ladder. The top balcony of every fire escape shall be provided with a stair or with a gooseneck ladder leading from said balcony to and above the roof, except that no such stairs or gooseneck ladders will be required in the following locations or under the following conditions:
- On multiple dwellings with peak roofs having a pitch of more than twenty (20) degrees.
- Where fire escapes are located on the fronts or in street courts of multiple dwellings facing upon the street. Where a multiple dwelling does not face upon the street, such as a multiple dwelling located at the rear of a lot upon which there is another building, every fire escape on such multiple dwelling shall be provided with a stair or gooseneck ladder as required above, except where the roof of such building has a pitch of more than twenty (20) degrees as stated in exception (1) above. Except as provided in exceptions (1) and (2) above, every fire escape on every hereafter erected or converted multiple dwelling, and every new Fire Escape hereafter provided on every existing multiple dwelling shall be provided with a regulation stairway from the top balcony to the roof when such buildings exceed four (4) stories in height. In such multiple dwellings exceeding four (4) stories in height when due to special structural conditions which would not permit the erection of a stair from the top balcony to the roof or where the height from the top balcony to the roof may be such as to make the installation of a stair impractical, the Department of Buildings may accept a gooseneck ladder in lieu of a regulation stairway. The top balcony of a fire escape on every multiple dwelling not exceeding four (4) stories in height may be equipped with a gooseneck ladder.
- Construction and location of gooseneck ladders. The gooseneck ladder shall be fifteen inches (15") wide and shall be so located that it will not obstruct egress from the apartment or apartments on the top floor. The effective opening between the side of any window and the string of gooseneck ladder shall be not less than twenty-four inches (24"). The gooseneck ladder must be fourteen inches (14") from the front rail on existing balconies and twenty-one inches (21") on balconies hereafter erected.
- Strings. The gooseneck ladder must be constructed with one piece strings of two inch by one-half inch (2" × 1/2") wrought iron. Strings must be directly secured to the brackets or secured to a two inch by one-half inch (2" × 1/2") bar bearing on two (2) brackets and well secured to strings and brackets by three-eighths inch (3/8") bolts or rivets. Strings must spread at the parapet wall or roof to give a passageway of eighteen inches (18"). Strings must be tied through the wall by braces going through the parapet immediately above the roof, or, in the absence of the parapet wall, the said braces must go through the wall immediately below the ceiling of the top floor and be secured by three-quarters inch (3/4") bolts and four inches by four inches by three-eighths inch (4" × 4" × 3/8") washers. The gooseneck ladder strings must extend thirty inches (30") above the roof level. Where there is a parapet, a gateway at the roof level shall be provided. The strings of the gooseneck ladder must be secured to and braced at the roof.
- Rungs. Rungs shall be of wrought iron five-eighths inch (5/8") thick, spaced not more than twelve inches (12") apart and shall be riveted through the strings. The top rung of all gooseneck ladders shall be level with the roof.
- (w) Painting. Section 53, Multiple Dwelling Law, required new fire escapes to have two (2) coats of paint. The Department of Buildings will require these two (2) coats to be applied on contrasting colors, the first coat at the shop before erection, and the second coat applied after erection. Existing fire escapes shall be repainted whenever deemed necessary.
- (x) Exceptions. Any deviations or exceptions from these rules other than those specifically mentioned herein shall be submitted to the Department of Buildings for approval. Consent and approval shall be in written form and bear the signature of the commissioner, deputy commissioner, superintendent or the person designated to sign such consent by the commissioner, deputy commissioner or superintendent.
- (y) Fire escapes on frame buildings. Fire escapes shall be constructed as for brick or stone buildings with the following exceptions, and except also that balconies three feet (3'-0") wide will be acceptable to the department.
- Brackets. Horizontal members of brackets must be one and three-quarters inches by one-half inch (1 3/4" × 1/2") wrought iron set on edge; one inch (1") bolt end through a four inches by three-eighths inch (4" × 3/8") iron plate, long enough to take in all brackets, secured to and bearing directly on the inside of the studs. Spaces between the studs behind such plates shall be filled in solidly with timber secured to the studs. The heel of bracket braces must rest against one and three-quarter inches by one and three-quarter inches by one-quarter high (1 3/4" × 1 3/4" × 1/4") angle iron extended across and well secured to studs.
- Top rails. Top rails shall be anchored by three-quarters inch (3/4") bolt ends, through a four inch by three-eighths inch (4" × 3/8") wrought iron plate spanning at least two (2) studs. Space behind plate and between studs shall be blocked solidly.
- Bottom rails. Bottom rails shall be secured to the siding in a substantial manner with two (2) one and one-quarter inch (1 1/4") No. 14 wood screws, or may be secured to the brackets where practicable.
- Stairways. Stair braces shall be secured to the wall of the building by two (2) No. 14 wood screws.
- (z) Outside fireproof stairs. Outside fireproof stairs shall be constructed according to approved plans and applications of the Department of Buildings. Such regulations as govern the measurements of inside stairs shall be applied to outside fireproof stairways except that in multiple dwellings not exceeding three (3) stories and basement in height, fireproof stairway leading from a front porch roof which is fireproof to the fireproof floor of an unenclosed porch will be deemed an outside fireproof stairway and such stairways may be of the same width as the ordinary fire escape stairs. Area covered by fireproof outside stairs must not encroach upon the minimum dimensions of yard or courts.
- (aa) Fire towers. Fire towers shall be constructed according to approved plans and applications filed with the Department of Buildings.
- (bb) Egress. Hotels and certain other class A and class B dwellings which are subject to the provisions of § 67, Multiple Dwelling Law.
- Exceptions. Any such multiple dwelling, altered or erected after April fifth, nineteen hundred forty-four, and which is required to conform to the provisions of articles one, two,
three, four, five, eight, nine and eleven of Multiple Dwelling Law, shall not be required to conform to the provisions of 1 RCNY § 15-10(bb)(1)(i), (2), (3) and (4).
- Except in fireproof class A multiple dwellings erected under plans filed after January first, nineteen hundred twenty-five, and which were completed before December thirty-one, nineteen hundred thirty-three, and except as otherwise provided in paragraph (4) of subdivision (bb) of this section, in every such dwelling three (3) or more stories in height there shall be from each story at least two (2) independent means of unobstructed egress located remote from each other and accessible to each room, apartment or suite.
- First means of egress. The first means of egress shall be an enclosed stair extending directly to a street, or to a yard, court or passageway affording continuous, safe and unobstructed access to a street, or by an enclosed stair leading to the entrance story, which story shall have direct access to a street. That area of the dwelling immediately above the street level and commonly known as the main floor, where the occupants are registered and the usual business of the dwelling is conducted, shall be considered a part of the entrance story; and a required stair terminating at such main floor or its mezzanine shall be deemed to terminate at the entrance story. An elevator or unenclosed escalator shall never be accepted as a required means of egress.
- Second means of egress. The second means of egress shall be by an additional enclosed stair conforming to the provisions of 1 RCNY § 15-10(bb)(2), a fire-stair, a fire-tower or an outside fire escape. In a non-fireproof dwelling when it is necessary to pass through a stair enclosure which may or may not be a required means of egress to reach a required means of egress, such stair enclosure and that part of the public hall or corridor leading thereto from a room, apartment or suite, shall be protected by one (1) or more sprinkler heads; in a fireproof dwelling only that part of the hall or corridor leading to such stair enclosure need be so protected.
- Required second means of egress — impractical. Where it is impractical in such existing dwellings to provide a second means of egress, the department may order additional alteration to the first means of egress and shafts, stairs and other vertical openings as the department may deem necessary to safeguard the occupants of the dwelling, may require the public halls providing access to the first means of egress to be equipped on each story with one (1) or more automatic sprinkler heads, and, in non-fireproof dwellings, may also require automatic sprinkler heads in the stair which serves as the only means of egress.
- Public halls and corridors providing access to fire escapes. Public halls and corridors providing access to fire escapes, existing and new, are acceptable when a direct and uninterrupted line to travel to the fire escape is provided. Public halls and corridors providing access to fire escapes shall be fire-retarded or shall be equipped with automatic sprinkler heads. The fire-retarding and sprinkler installation shall be in conformity with the rules and regulations of this department and as required by § 67(3) of the Multiple Dwelling Law. All openings which provide direct access to an existing fire escape from a public hall or corridor shall be equipped with fireproof doors and assemblies with the doors self-closing or fireproof windows glazed with clear wire glass. Access to new fire escapes from such halls or corridors shall be by means of fireproof doors and assemblies with doors self-closing. Doors providing access to fire escapes from public halls or corridors may be glazed with clear wire glass.
- Fire Escapes — existing and new. Existing fire escapes which are structurally strong and in good repair, having connecting stairways set at an angle of not more than sixty-five (65) degrees, may be accepted as a secondary means of egress. Except as otherwise required herein, new and existing fire escapes shall be provided with a safe landing and the termination shall lead directly to a street or to a passageway which provides access to a street. When it is impractical to provide a termination for fire escapes as specified in these rules, the Department may accept a termination from such fire escapes which leads to safety.
- Supplementary means of egress. A stair, fire-stair, fire-tower, or fire escape which is supplementary to the egress requirements of 1 RCNY § 15-10(bb)(2), (3) and (4), need not lead to the entrance story or to a street, or to a yard or a court which leads to a street, provided the means of egress therefrom is approved by the Department. Fire escapes which are supplementary to the required second means of egress, including fire escapes of the inclined ladder and vertical ladder types, may remain on the dwelling if maintained in good order and repair, are structurally strong and safe and are provided with safe landing and the termination thereof leads to safety in a manner satisfactory to this Department.
- Signs — supplementary means of egress. Supplementary stairs, fire-stairs, fire-towers or fire escapes which do not lead to tthe entrance story or to a street, or to a yard or court leading to a street, shall be clearly marked "NOT AN EXIT" in black letters at least four inches (4") high on a yellow background and at the termination of each such stair, fire-stair, firetower or fire escape, there shall be a directional sign indicating the nearest means of egress leading to a street. All signs shall be constructed, located and illuminated in a manner satisfactory to the department.
- Signs — general provisions. Every means of egress shall be indicated by a sign reading "EXIT" in red letters at least eight inches (8") high on a white background, or vice versa, illuminated at all time during the day and night by a red light of at least twenty-five (25) watts or equivalent illumination. Such light shall be maintained in a keyless socket. On all stories where doors, openings or passageways giving access to any means of egress are not visible from all portions of such stories, directional sign shall be maintained in conspicuous locations, indicating in red on a white background, or vice versa, the direction of travel to the nearest means of egress. At least one sign shall be visible from the doorway of each room or suite of rooms. Existing signs and illumination may be accepted if, in the opinion of the Department, such existing signs and illumination serve the intent and purpose of this subdivision.
- Stairs, fire-stairs and fire-towers. Stairs, fire-stairs and fire-towers hereafter provided shall be constructed according to plans and applications approved by the Department of Buildings
- Exceptions. Any such multiple dwelling, altered or erected after April fifth, nineteen hundred forty-four, and which is required to conform to the provisions of articles one, two,
three, four, five, eight, nine and eleven of Multiple Dwelling Law, shall not be required to conform to the provisions of 1 RCNY § 15-10(bb)(1)(i), (2), (3) and (4).
- (cc) Egress: lodging houses
- Arrangement. There shall be at least two (2) means of unobstructed egress from each lodging-house story, which shall be remote from each other. The first means of egress shall be to a street either directly or by an enclosed stair having unobstructed direct access thereto. If the story is above the entrance story, the second means of egress shall be by an outside fire escape constructed in accordance with the provisions of section fifty-three, Multiple Dwelling Law, or by an additional enclosed stair. Such second means of egress shall be accessible without passing through the first means of egress.
- Doors and windows. All doors opening upon entrance halls, stair halls, other public halls or stairs, or elevator, dumbwaiter or other shafts, and the door assemblies, shall be fireproof with the doors made self-closing by a device approved by the department, and such doors shall not be held open by any device whatever. All openings on the course of a fire escape shall be provided with such doors and assemblies or with fireproof windows and assemblies, with the windows self-closing and glazed with wire glass, such doors or windows and their assemblies to be acceptable to the department.
- Aisles. There shall be unobstructed aisles providing access to all required means of egress in all dormitories. Main aisles, approved as such by the department to provide adequate approaches to the required means of egress, shall be three feet (3'-0") or more in width, except that no aisles need be more than two feet six inches (2'-6") wide if it is intersected at intervals of not more than fifty feet (50'-0") by cross-over aisles at least three feet (3'-0") wide leading to other aisles or to an approved means of egress.
- Signs. Every required means of egress from the lodging-house part of the dwelling shall be indicated by a sign reading "EXIT" in red letters at least eight inches (8") high on a white background illuminated at all times during the day and night by a light of at least twenty-five (25) watts or equivalent illumination. Such light shall be maintained in a keyless socket. On all lodging-house stories where doors, openings, passageways or aisles are not visible from all portions of such stories, and in other parts of the dwelling which may be used in entering or leaving the lodging-house part and in which a similar need exists, signs with easily readable letters at least eight inches (8") in height, and continuously and sufficiently illuminated by artificial light at all times when the natural light is not sufficient to make them easily readable, shall be maintained in conspicuous locations, indicating the direction of travel to the nearest means of egress. At least one (1) such sign shall be easily visible from the doorway of each cubicle.
- Roof egress. Access from the public hall at the top story to the roof shall be provided by means of a bulkhead or a scuttle acceptable to the Department. Every such scuttle and the stair or ladder leading thereto shall be located within the stair enclosure.
- Persons accommodated. The number of persons accommodated on any story in a lodging house shall not be greater than the sum of the following components:
- Twenty-two (22) persons for each full multiple of twenty-two inches (22") in the smallest clear width of each means of egress approved by the Department, other than a fire escape.
- Twenty persons (20) for each lawful fire escape accessible from such story if it is above the entrance story.
- In view of the fact that § 66, Subdivision 3 (formerly § 13, subdivision m), Multiple Dwelling Law, required lodging houses to be sprinklered throughout, including the public halls, the Department will accept existing double-rung ladder type fire escapes on the condition that such fire escapes are maintained in a good state of repair.
- (dd) Ladders leading to roof scuttles. Ladders to roof scuttles as required under the provisions of §§ 187 and 233 of the Multiple Dwelling Law, shall be of incombustible material, not less than fifteen inches (15") wide, with strings not less than one and one-half inches by three-eighths inch (1 1/2" × 3/8"), with five-eighths inch (5/8") rungs not more than twelve inches (12") apart. Strings of such ladders shall be secured at top and bottom and ladder must be so arranged as to permit sufficient toe hold.