The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 53 and 58 of the New York City Fire Code. Compressed gases shall also comply with Chapter 50 of the New York City Fire Code for general requirements.
Permits shall be required as set forth in Section 106 and as required by the New York City Fire Code.
The generation of gaseous hydrogen for immediate on-premises use in indoor fuel cells or other energy production process and incidental indoor storage of gaseous hydrogen shall be located in accordance with Section 706. Exhaust ventilation shall be required in rooms or spaces that house such generation of gaseous hydrogen in accordance with the applicable provisions of NFPA 2.
The location and installation of gaseous hydrogen systems and appliances shall be in accordance with Sections 706.2 and 706.3.
Exception: Outdoor stationary fuel cell power plants in accordance with Section 633.

Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706.
Gaseous hydrogen systems shall be located in hydrogen fuel gas rooms constructed in accordance with the New York City Building Code, the New York City Mechanical Code, the New York City Fire Code and NFPA 2.
Gaseous hydrogen systems located outdoors shall be in accordance with the New York City Fire Code.