This chapter shall govern the storage, handling, use and transportation of hazardous materials. Hazardous material storage, handling and use shall additionally comply with the requirements of the New York State Department of Environmental Conservation regulations, as set forth in 6 NYCRR Parts 596 through 613.
Exceptions:
- The storage, handling and use in retail or wholesale mercantile occupancies of alcoholic beverages, medicines, foodstuffs, cosmetics, and consumer products containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, when packaged in individual containers not exceeding 1.3 gallons (5 L) in volume.
- Storage, handling and use of hazardous materials for agricultural purposes as a pesticide, fertilizer or similar application, when approved for such use by the regulatory agency having jurisdiction and when such storage, handling and use is in accordance with the manufacturer's instructions.
- Reserved.
- Reserved.
- Refrigerating systems when designed, installed, operated and maintained in accordance with the Mechanical Code and FC606.
- Stationary energy storage systems when designed, installed, operated and maintained in accordance with FC608 and the rules.
- The storage, handling and use, including storage for sale, of fireworks, in accordance with FC Chapter 56.
- The storage, handling and use of corrosives in Group M occupancies, including storage for sale, of personal and household products, when in the manufacturer's original consumer packaging.
- The storage of wines in wooden barrels and casks.
- The manufacturing, storage, handling and use of distilled spirits in distilleries in accordance with FC Chapter 40.
- The use of dispensers containing alcohol-based hand rubs classified as Class I or Class II liquids, when stored, handled and used in accordance with FC5705.5.
This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, except that when specific requirements inconsistent with the provisions of this chapter are set forth elsewhere in this code, those specific requirements shall apply to the extent that they are inconsistent. Where a material is in multiple hazard categories, compliance with each hazard category shall be required. Where a material is both a physical hazard and a health hazard, compliance with the requirements for each hazard category shall be required.
Hazardous materials shall be classified by physical hazard, health hazard and/or other hazards associated with the properties of the material, or if the hazardous material is a mixture, with the hazards associated with the mixture as a whole. The commissioner may determine the appropriate hazard classification of a hazardous material, or may accept the classification set forth in nationally recognized standards, safety data sheets, or other approved standard or method.
Hazardous materials shall be classified according to hazard categories. The categories include materials regulated by this chapter and materials regulated elsewhere in this code.
The material categories listed in this section are classified primarily as physical hazards.
- Explosives and blasting agents.
- Combustible liquids.
- Flammable solids, liquid and gases.
- Organic peroxide solids or liquids.
- Oxidizing solids or liquids.
- Oxidizing gases.
- Pyrophoric solids or liquids.
- Unstable (reactive) solids, liquids or gases.
- Water-reactive solids and liquids.
- Cryogenic fluids.
The material categories listed in this section are classified primarily as health hazards.
- Highly toxic and toxic materials.
- Corrosive materials.
For retail and wholesale storage and display of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in Group M occupancies and storage in Group S occupancies, see FC5003.11.
The commissioner may require an application for a permit to include a Hazardous Materials Management Plan (HMMP). Such plan shall be drawn approximately to scale. The HMMP shall contain the following:
- Access to each area where hazardous materials are stored, handled or used.
- Location of emergency equipment.
- Location where liaison required by FC5003.9.1.1 will meet emergency responders.
- Facility evacuation meeting point locations.
- The predominant use and/or occupancy of areas within the building where hazardous materials are not stored or used.
- Location of all aboveground and underground hazardous material storage tanks and their appurtenances including, but not limited to, sumps, vaults, below-grade treatment systems and piping.
- The hazard classes of hazardous materials stored or used in each area.
- Locations of all control areas and Group H occupancies.
- Locations of exits.
- Such other information and documentation as the commissioner may prescribe.
The storage of hazardous materials shall be reported as required by the New York State General Municipal Law Section 209-u. The commissioner may require an application for a permit pursuant to this code to include a copy of the current filing pursuant to such New York State General Municipal Law for the facility or premises for which a permit is sought. The commissioner may also require an application for a permit to include a Hazardous Materials Inventory Statement (HMIS), such as a statement prepared for purposes of the Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report, or other approved statement. The HMIS shall include the following information:
- Product name.
- Chemical composition.
- Chemical Abstract Service (CAS) number.
- Location where stored or used.
- Container size.
- Hazard classification.
- Quantity in storage.
- Quantity in use-closed systems.
- Quantity in use-open systems.
Facilities shall be placed permanently out of service in
accordance with FC 5001.6.2 and 5001.6.3 and, as applicable, with the New
York State Department of Environmental Conservation regulations as set forth in 6 NYCRR
Sections 598.10 and 613.
Facilities that are not operated for
a period of more than 1 year or for which a permit has lapsed for more than 1 year shall be
deemed to be permanently out of service and shall be closed in an approved manner.
The commissioner may require permittees to apply
for approval to permanently close a facility that manufactures, stores, handles or uses
hazardous materials. Such application shall be submitted at least 30 calendar days prior to the
planned closure of the facility. Such plan and/or such other requirements as the commissioner may prescribe shall demonstrate that hazardous materials that are manufactured, stored,
handled or used in the facility will be lawfully disposed of in a manner that eliminates the need
for further maintenance and any threat to public health and safety.
The following terms shall, for the purposes of this chapter, FC Chapters 51 through 67, and as used elsewhere in this code, have the meanings set forth in FC202.
BOILING POINT.
CARGO TANK.
CEILING LIMIT.
CHEMICAL.
CHEMICAL NAME.
CLOSED CONTAINER.
CONTAINER.
CONTROL AREA.
DEFLAGRATION.
DESIGN PRESSURE.
DETACHED BUILDING.
DISPENSING.
EXCESS FLOW CONTROL.
EXHAUSTED ENCLOSURE.
EXPLOSION.
FLAMMABLE VAPORS OR FUMES.
GAS CABINET.
GAS ROOM.
HANDLING.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH).
INCOMPATIBLE MATERIALS.
LABORATORY CHEMICAL.
LABORATORY UNIT.
LIQUID.
LOWER EXPLOSIVE LIMIT (LEL).
LOWER FLAMMABLE LIMIT (LFL).
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA.
NON-PRODUCTION LABORATORY.
NORMAL TEMPERATURE AND PRESSURE (NTP).
OUTDOOR CONTROL AREA.
PERMISSIBLE EXPOSURE LIMIT (PEL).
PESTICIDE.
PRESSURE VESSEL.
SAFETY CAN.
SAFETY DATA SHEET (SDS).
SECONDARY CONTAINMENT.
SOLID.
STANDARD CUBIC FEET (SCF).
SYSTEM.
TANK, ATMOSPHERIC.
TANK, PORTABLE.
TANK, STATIONARY.
VAPOR PRESSURE.
BOILING POINT.
CARGO TANK.
CEILING LIMIT.
CHEMICAL.
CHEMICAL NAME.
CLOSED CONTAINER.
CONTAINER.
CONTROL AREA.
DEFLAGRATION.
DESIGN PRESSURE.
DETACHED BUILDING.
DISPENSING.
EXCESS FLOW CONTROL.
EXHAUSTED ENCLOSURE.
EXPLOSION.
FLAMMABLE VAPORS OR FUMES.
GAS CABINET.
GAS ROOM.
HANDLING.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH).
INCOMPATIBLE MATERIALS.
LABORATORY CHEMICAL.
LABORATORY UNIT.
LIQUID.
LOWER EXPLOSIVE LIMIT (LEL).
LOWER FLAMMABLE LIMIT (LFL).
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA.
NON-PRODUCTION LABORATORY.
NORMAL TEMPERATURE AND PRESSURE (NTP).
OUTDOOR CONTROL AREA.
PERMISSIBLE EXPOSURE LIMIT (PEL).
PESTICIDE.
PRESSURE VESSEL.
SAFETY CAN.
SAFETY DATA SHEET (SDS).
SECONDARY CONTAINMENT.
SOLID.
STANDARD CUBIC FEET (SCF).
SYSTEM.
TANK, ATMOSPHERIC.
TANK, PORTABLE.
TANK, STATIONARY.
VAPOR PRESSURE.
Hazardous materials shall be manufactured, stored, handled, used and
transported in accordance with this chapter.
The maximum allowable quantity per control area shall be as specified in FC Tables 5003.1.1(1) through 5003.1.1(4), and for retail and wholesale storage and display in Group M occupancies, and Group S storage, as specified in FC5003.11.
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
For SI: 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 pound per square inch absolute = 6.895 kPa, °C = (°F-32)/1.8.
Exceptions: The maximum allowable quantity per control area requirements set forth in FC Tables 5003.1.1(1) through 5003.1.1(4) shall not apply to:
- A construction site in an unoccupied building prior to issuance of a certificate of occupancy or temporary certificate of occupancy for such building. Maximum allowable quantity per control area requirements shall apply to a construction site in an occupied or partially occupied building, except as may be otherwise authorized by the department in writing.
- Liquid or gaseous fuel in fuel tanks on motor vehicles.
- Gaseous fuels in piping systems and fixed appliances regulated by the Fuel Gas Code.
- Liquid fuels in piping systems and fixed appliances regulated by the Mechanical Code.
Material
|
Class
|
GROUP WHEN THE MAXIMUM ALLOWABLE QUANTITY IS EXCEEDEDt
|
STORAGEb
|
USE-CLOSED SYSTEMSb
|
USE-OPEN SYSTEMSb
|
|||||
Solid pounds (cubic feet)
|
Liquid gallons (pounds)
|
Gas
SCF |
Solid pounds (cubic feet)
|
Liquid gallons (pounds)
|
Gas
SCF |
Solid pounds (cubic feet)
|
Liquid gallons (pounds)
|
|||
Combustible dust |
Not Applicable
|
H-2
|
See Note q
|
Not Applicable
|
Not Applicable
|
See Note q
|
Not Applicable
|
Not Applicable
|
See Note q
|
Not Applicable
|
Combustible fiberq |
Loose Baledo
|
H-3
|
(100) (1,000)
|
Not Applicable
|
Not Applicable
|
(100) (1,000)
|
Not Applicable
|
Not Applicable
|
(20) (200)
|
Not Applicable
|
Combustible liquidc, i, r |
II
IIIA
IIIB
|
H-2 or H-3
H-2 or H-3
Not Applicable
|
Not Applicable
|
120d, e
330d, e
13,200e, f
|
Not Applicable
|
Not Applicable
|
120d
330d
13,200f
|
Not Applicable
|
Not Applicable
|
30d
80d
3,300f
|
Cryogenics flammable |
Not Applicable
|
H-2
|
Not Applicable
|
45d
|
Not Applicable
|
Not Applicable
|
45d
|
Not Applicable
|
Not Applicable
|
10d
|
Cryogenics inert |
Not Applicable
|
Not Applicable
|
Not Applicable
|
Not Applicable
|
Not Limited
|
Not Applicable
|
Not Applicable
|
Not Limited
|
Not Applicable
|
Not Applicable
|
Cryogenics oxidizing |
Not Applicable
|
H-3
|
Not Applicable
|
45d
|
Not Applicable
|
Not Applicable
|
45d
|
Not Applicable
|
Not Applicable
|
10d
|
Explosives |
Division 1.1
Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 |
H-1
H-1
H-1 or H-2
H-3
H-3
H-1
H-1
|
0
1e, g
5e, g 50e, g 125e, l 1e, g 1e, g |
0
(1)e, g
(5)e, g
(50)e, g
Not Applicable
(1)e, g
Not Applicable
|
Not Applicable
|
0
0.25g
1g
50g
Not Applicable
0.25g
Not Applicable
|
0
(0.25)g
(1)g
(50)g
Not Applicable
(0.25)g
Not Applicable
|
Not Applicable
|
0
0.25g
1g
Not Applicable
Not Applicable
0.25g
Not Applicable
|
0
(0.25)g
(1)g
Not Applicable
Not Applicable
(0.25)g
Not Applicable
|
Flammable gas |
Gaseous Liquefied
|
H-2
|
Not Applicable
|
Not Applicable
(150)d, e
|
1,000d, e
Not Applicable
|
Not Applicable
|
Not Applicable
(150)d, e
|
1,000d, e
Not Applicable
|
Not Applicable
|
Not Applicable
|
Flammable liquidsc, r |
IAs
IB and IC
|
H-2
or
H-3
|
Not Applicable
|
30d, e
120d, e
|
Not Applicable
|
Not Applicable
|
30d
120d
|
Not Applicable
|
Not Applicable
|
10d
30d
|
Flammable liquid, combination (IAs , IB, IC) |
Not Applicable
|
H-2
or
H-3
|
Not Applicable
|
120d, e, h
|
Not Applicable
|
Not Applicable
|
120d, h
|
Not Applicable
|
Not Applicable
|
30d, h
|
Flammable solid |
Not Applicable
|
H-3
|
125d, e
|
Not Applicable
|
Not Applicable
|
125d
|
Not Applicable
|
Not Applicable
|
25d
|
Not Applicable
|
Inert gas |
Gaseous Liquefied
|
Not Applicable
Not Applicable
|
Not Applicable
Not Applicable
|
Not Applicable
Not Applicable
|
Not Limited
Not Limited
|
Not Applicable
Not Applicable
|
Not Applicable
Not Applicable
|
Not Limited
Not Limited
|
Not Applicable
Not Applicable
|
Not Applicable
Not Applicable
|
Organic peroxidep |
I
II
III
IV
V
|
H-1
H-2
H-3
H-3
Not Applicable
Not Applicable |
1e, g
5d, e
50d, e
125d, e
Not Limited
Not Limited
|
(1)e, g
(5)d, e
(50)d, e
(125)d, e
Not Limited
Not Limited
|
Not Applicable
|
0.25g
1d
50d
125d
Not Limited
Not Limited
|
(0.25) g
(1)d
(50)d
(125)d
Not Limited
Not Limited
|
Not Applicable
|
0.25g
1d
10d
25d
Not Limited
Not Limited
|
(0.25)g
(1)d
(10)d
(25)d
Not Limited
Not Limited
|
Oxidizer |
4
3k
2
1
|
H-1
H-2
H-3
H-3
|
1g
10d, e
250d, e
4,000e, f
|
(1)e, g
(10)d, e
(250)d, e
(4,000)e, f
|
Not Applicable
|
0.25g
2d
250d
4,000f
|
(0.25)g
(2)d
(250)d
(4,000)f
|
Not Applicable
|
0.25g
2d
50d
1,000f
|
(0.25)g
(2)d
(50)d
(1,000)f
|
Oxidizing gasu |
Gaseous Liquefied
|
H-3
|
Not Applicable
|
Not Applicable
(150)d, e
|
1,500d, e
Not Applicable
|
Not Applicable
|
Not Applicable
(150)d, e
|
(1,500)d, e
Not Applicable
|
Not Applicable
|
Not Applicable
|
Pyrophoric materialp detonable |
Not Applicable
|
H-1
|
1e, g
|
(1)e, g
|
10e, g
|
0.25g
|
(0.25)g
|
2e, g
|
0
|
0
|
Pyrophoric material nondetonable |
Not Applicable
|
H-2
|
4e, g
|
(4)e, g
|
50e, g
|
1g
|
(1)g
|
10e, g
|
0
|
0
|
Unstable (reactive)p detonable |
4
3
|
H-1
H-1
|
1e, g
1e, g
|
(1)e, g
(1)e, g
|
10e, g
10e, g
|
0.25g
0.25g
|
(0.25)g
(0.25)g
|
2e, g
2e, g
|
0.25g
0.25g
|
(0.25)g
(0.25)g
|
Unstable (reactive) nondetonable |
4
3
2
1
|
H-1
H-1 or H-2
H-3
Not Applicable
|
1e, g
5d, e
50d, e
Not Limited
|
(1)e, g
(5)d, e
(50)d, e
Not Limited
|
10e, g
50d, e
250d, e
750d, e
|
0.25g
1d
50d
Not Limited
|
(0.25) g
(1)d
(50)d
Not Limited
|
2e, g
10d, e
250d, e
750d, e
|
0.25g
1d
10d
Not Limited
|
(0.25)g
(1)d
(10)d
Not Limited
|
Water-reactive detonablep |
3
2
|
H-1
H-1
|
1e, g
1e, g
|
(1)e, g
(1)e, g
|
Not Applicable
|
0.25g
0.25g
|
(0.25)g
(0.25)g
|
Not Applicable
|
0.25g
0.25g
|
(0.25)g
(0.25)g
|
Water-reactive nondetonable |
3
2
1
|
H-2
H-3
Not Applicable
|
5d, e
50d, e
Not Limited
|
(5)d, e
(50)d, e
Not Limited
|
Not Applicable
|
5d
50d
Not Limited
|
(5)d
(50)d
Not Limited
|
Not Applicable
|
1d
10d
Not Limited
|
(1)d
(10)d
Not Limited
|
- For use of control areas, see FC5003.8.3.
- The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
- The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
- Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, may be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e applies, the quantities may be increased as set forth in both notes.
- Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, may be increased 100 percent when stored in approved storage cabinets, gas cabinets, gas rooms, exhausted enclosures or listed safety cans. Listed safety cans shall be in accordance with FC5003.9.10. Where Note d applies, the quantities may be increased as set forth in both notes.
- Quantities shall not be limited in a building protected throughout by a sprinkler system.
- Allowed only in buildings protected throughout by a sprinkler system.
- Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids.
- Stationary fuel oil storage tanks shall comply with the requirements of the construction codes, including the Mechanical Code.
- Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
- A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance and operation of equipment when the storage containers and the manner of storage are approved.
- Reserved.
- For gallons of liquids, divide the amount in pounds by 10 in accordance with FC5003.1.2.
- For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the requirements of FC5003.11, see FC Table 5003.11.1.
- Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
- Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
- Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with FC104.7.2.
- For storage of flammable and combustible liquids in Group M occupancy, see FC Chapter 57. For storage of flammable and combustible liquids in distilleries, see FC Chapter 40. The maximum allowable quantities shall not apply to alcohol-based hand rubs classified as Class I or II liquids in dispensers that are installed or placed for use on a premises in accordance with FC 5705.5.1 and 5705.5.2.
- For purposes of this table, gasoline and other flammable liquid motor fuels are classified as a Class IA flammable liquid.
- The maximum allowable quantities shall be limited by FC5006 for non-production laboratories classified as Occupancy Group B.
- Medical gas storage in hospitals and other medical facilities classified as Occupancy Group B and I shall be subject to the requirements as set forth in FC5306.
Material
|
STORAGEb
|
USE-CLOSED SYSTEMSb
|
USE-OPEN SYSTEMSb
|
|||||
Solid poundsd, e
|
Liquid gallons (pounds)d, e
|
Gas
SCF (pounds)d |
Solid poundsd
|
Liquid gallons (pounds)d
|
Gas
SCF (pounds)d |
Solid poundsd
|
Liquid gallons (pounds)d
|
|
Corrosive
|
5,000
|
500
|
Gaseous 810e
Liquefied (150) |
5,000
|
500
|
Gaseous 810e
Liquefied (150) |
1,000
|
100
|
Highly toxic
|
10
|
(10)
|
Gaseous 20g
Liquefied (4)g |
10
|
(10)
|
Gaseous 20g
Liquefied (4)g |
3
|
(3)
|
Toxic
|
50
|
(500)
|
Gaseous 810e
Liquefied (150)e |
50
|
(500)
|
Gaseous 810e
Liquefied (150)e |
125
|
(125)
|
- For use of control areas, see FC5003.8.3.
- The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
- In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
- Maximum allowable quantities may be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e applies, the quantities increased shall be as set forth in both notes.
- Maximum allowable quantities may be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures. Where Note d applies, the quantities increased shall be as set forth in both notes.
- For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the requirements of FC5003.11, see FC Table 5003.11.1.
- Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures.
- Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
- For gallons of liquids, divide the amount in pounds by 10 in accordance with FC5003.1.2.
- The maximum allowable quantities shall be limited by FC5006 for non-production laboratories classified as Occupancy Group B.
Material
|
Class
|
STORAGEb
|
USE-CLOSED SYSTEMSb
|
USE-OPEN SYSTEMSb
|
|||||
Solid pounds
|
Liquid gallons (pounds)
|
Gas
SCF |
Solid pounds
|
Liquid gallons (pounds)
|
Gas
SCF |
Solid pounds
|
Liquid gallons (pounds)
|
||
Gaseous Liquefied
|
Not Applicable
|
Not Applicable (150)
|
1000
Not Applicable |
Not Applicable
|
Not Applicable (150)
|
1000
Not Applicable |
Not Applicable
|
Not Applicable
|
|
Not Applicable
|
125
|
Not Applicable
|
Not Applicable
|
25
|
Not Applicable
|
Not Applicable
|
25
|
Not Applicable
|
|
Cryogenic inert
|
Gaseous Liquefied
Not Applicable |
Not Applicable
Not Applicable Not Applicable |
Not Applicable
Not Applicable Not Applicable |
Not Limited
Not Limited Not Limited |
Not Applicable
Not Applicable Not Applicable |
Not Applicable
Not Applicable Not Applicable |
Not Limited
Not Limited Not Limited |
Not Applicable
Not Applicable Not Applicable |
Not Applicable
Not Applicable Not Applicable |
1
|
(1)
|
Not Applicable
|
0.25
|
(0.25)
|
Not Applicable
|
0.25
|
(0.25)
|
||
I
II III IV V |
5
50 125 500 Not Limited |
(5)
(50) (125) (500) Not Limited |
Not Applicable
|
1
50 125 500 Not Limited |
(1)
(50) (125) (500) Not Limited |
Not Applicable
|
1
10 25 100 Not Limited |
(1)
(10) (25) (100) Not Limited |
|
4
3 2 1 |
1
10 250 4,000 |
(1)
(10) (250) (4,000) |
Not Applicable
|
0.25
2 250 4,000 |
(0.25)
(2) (250) (4,000) |
Not Applicable
|
0.25
2 50 1,000 |
(0.25)
(2) (50) (1,000) |
|
Gaseous Liquefied
|
Not Applicable
|
Not Applicable
15 |
1,500
Not Applicable |
Not Applicable
|
Not Applicable
15 |
1,500
Not Applicable |
Not Applicable
|
Not Applicable
|
|
Pyrophoric materiale detonable
|
Not Applicable
|
1
|
(1)
|
10
|
0.25
|
(0.25)
|
2
|
0
|
0
|
Pyrophoric material nondetonable
|
Not Applicable
|
4
|
(4)
|
50
|
1
|
(1)
|
10
|
0
|
0
|
Unstable (reactive)e detonable
|
4
3 |
1
1 |
(1)
(1) |
10
10 |
0.25
0.25 |
(0.25)
(0.25) |
2
2 |
0.25
0.25 |
(0.25)
(0.25) |
Unstable (reactive) nondetonable
|
4
3 2 1 |
1
5 50 Not Limited |
(1)
(5) (50) Not Limited |
10
50 250 750 |
0.25
1 50 Not Limited |
(0.25)
(1) (50) Not Limited |
2
10 250 750 |
0.25
1 10 Not Limited |
(0.25)
(1) (10) Not Limited |
Water-reactivee detonable
|
3
2 |
1
1 |
(1)
(1) |
Not Applicable
|
0.25
0.25 |
(0.25)
(0.25) |
Not Applicable
|
0.25
0.25 |
(0.25)
(0.25) |
Water-reactive nondetonable
|
3
2 1 |
5
50 Not Limited |
(5)
(50) Not Limited |
Not Applicable
|
5
50 Not Limited |
(5)
(50) Not Limited |
Not Applicable
|
1
10 Not Limited |
(1)
(10) Not Limited |
- For gallons of liquids, divide the amount in pounds by 10 in accordance with FC5003.1.2.
- The aggregate quantities in storage and use shall not exceed the quantity listed for storage.
- The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area when such storage is in accordance with FC5003.11.
- Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
- Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage (see FC Chapter 56).
- In addition to these requirements, the outdoor storage and use of hazardous materials shall comply with applicable requirements of the Zoning Resolution.
Material
|
STORAGEb
|
USE-CLOSED SYSTEMSb
|
USE-OPEN SYSTEMSb
|
|||||
Solid pounds
|
Liquid gallons (pounds)
|
Gas
SCF (pounds) |
Solid pounds
|
Liquid gallons (pounds)
|
Gas
SCF (pounds) |
Solid pounds
|
Liquid gallons (pounds)
|
|
Corrosives
|
5,000
|
500
|
Gaseous 810
Liquefied (150) |
5,000
|
500
|
Gaseous 810
Liquefied (150) |
1,000
|
100
|
Highly toxics
|
10
|
(10)
|
Gaseous 20d
Liquefied (4)d |
10
|
(10)
|
Gaseous 20d
Liquefied (4)d |
3
|
(3)
|
Toxics
|
50
|
(500)
|
Gaseous 810
Liquefied (150) |
50
|
50e
|
Gaseous 810
Liquefied (150) |
25
|
(25)e
|
- For gallons of liquids, divide the amount in pounds by 10 in accordance with FC5003.1.2.
- The aggregate quantities in storage and use shall not exceed the quantity listed for storage.
- The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage on a single property under the same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area when such storage is in accordance with FC5003.11.
- Allowed only when used in approved exhausted gas cabinets, exhausted enclosures or under fume hoods.
- The maximum allowable quantity per control area for toxic liquids with vapor pressures in excess of 1 psia at 77°F shall be the maximum allowable quantity per control area listed for highly toxic liquids.
- Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
- In addition to these requirements, the outdoor storage and use of hazardous materials shall comply with the applicable requirements of the Zoning Resolution.
A conversion factor of 10 pounds per gallon (1.2 kg/L) shall
be used to ascertain the weight per gallon of liquid when such weight is not provided or
otherwise available to the commissioner.
The storage, handling and use of hazardous materials in quantities not exceeding the
maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1)
through 5003.1.1(4) shall be in accordance with FC 5001 and
5003.
The storage, handling and use of hazardous materials in quantities exceeding the
maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1)
through 5003.1.1(4) shall be in accordance with this chapter and, in a high-
hazard occupancy, the requirements of the Building Code.
The storage, handling and use of
hazardous materials shall additionally comply with the specific requirements of FC Chapters
51 through 67, as applicable.
Devices, equipment, systems and processes utilized for storage, handling and use of hazardous materials shall be in accordance with FC 5003.2.1 through 5003.2.8 and the regulations of the New York State Department of Environmental Conservation as set forth in 6 NYCRR Parts 596, 598, 599, 613.
Containers and tanks
shall be designed and constructed in accordance with approved standards. Containers, tanks
and other means used for containment of hazardous materials shall be of an approved type.
Piping, tubing, valves and fittings
conveying hazardous materials, except piping for inlet connections to prevent backflow or
piping for pressure relief devices, shall be designed and installed in accordance with approved
standards and FC 5003.2.2.1 and 5003.2.2.2.
Piping, tubing, valves, fittings and ancillary equipment used for hazardous materials shall be in accordance with the following:
- Piping, tubing, valves, fittings and ancillary equipment shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subjected.
- Piping and tubing shall be identified in accordance with ASME A13.1 to indicate the material conveyed.
- Readily accessible manual valves, or automatic remotely-activated fail-safe emergency shutoff valves, shall be installed on supply piping and tubing at the point of use and at the tank, container or other source of supply.
- Emergency shutoff valves shall be clearly visible and readily accessible. A durable sign shall be conspicuously posted immediately adjacent to such valves that identifies their location.
- Backflow prevention or check valves shall be provided when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials.
- Where gases or liquids having a hazard ranking of health hazard Class 3 or 4, flammability Class 4, or instability Class 3 or 4 in accordance with NFPA 704 are conveyed in pressurized piping above 15 pounds per square inch gauge (psig) (103 kPa), an approved means of leak detection and emergency shutoff or excess flow control shall be provided. Where the piping originates from within a hazardous material storage room or area, the excess flow control shall be located within the storage room or area. Where the piping originates from any other source of supply, the excess flow control shall be located as close to the source of supply as practical.
Exceptions:
- Piping for inlet connections designed to prevent backflow.
- Piping for pressure relief devices.
Supply piping and tubing for gases and liquids having a health-hazard ranking of 3 or 4 in accordance with NFPA704 shall be in accordance with ASME B31.3 and the following:
- Piping and tubing utilized for the transmission of highly toxic, toxic or highly volatile corrosive liquids and gases shall have welded, threaded or flanged connections throughout, except where connections are located within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid.
- Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H occupancies.
Exception: Piping and tubing within the space defined by the walls of corridors and the floor or roof above or in concealed spaces above other occupancies when installed in accordance with Section 415 of the Building Code for Group H-5 occupancies.
Devices, equipment and systems,
including required detection and alarm systems, installed or used in conjunction with the
storage, handling and use of hazardous materials shall be listed or approved.
Installation of tanks shall be in accordance with FC
5003.2.4.1 through 5003.2.4.3 and with the regulations of the New
York State Department of Environmental Conservation as set forth in 6 NYCRR Sections
599 and 613.
Underground tanks used for the storage of
liquid hazardous materials shall be provided with secondary containment.
Aboveground stationary tanks used for the
storage of liquid hazardous materials shall be located and protected in compliance with the
requirements for outdoor storage of the particular material involved.
Aboveground stationary tanks shall be marked
as required by FC5003.5.
Hazardous materials storage tanks located in areas
of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of the Building Code) shall
comply with Section G307.5 of Appendix G of the Building Code.
Empty containers and tanks previously
used for the storage of hazardous materials shall be free from residual material and vapor in
compliance with the requirements of DOTn, the Resource Conservation and Recovery Act
(RCRA) or other governmental agencies having jurisdiction, or shall be stored, handled and
used in compliance with the requirements of this code.
In addition to the requirements of
FC5003.2.3, all devices, equipment and systems used in conjunction with hazardous materials,
including tanks, and detection and alarm systems, shall be maintained in good working order.
Defective devices, equipment and systems shall be removed from service and repaired or
replaced, or disposed of lawfully.
Stationary tanks not used for a
period of 30 calendar days or more shall be properly safeguarded or removed in an
approved manner. Such tanks shall have the fill line, gauge opening and pump connection
secured against tampering. Vent lines shall be properly maintained. Stationary tanks
containing flammable and combustible liquid out of service for a period of 30 calendar
days or more shall additionally comply with the requirements of FC5704.2.13.
Atmospheric tanks that contain hazardous
material liquids shall be equipped with a liquid-level limit control or other approved means to
prevent overfilling of the tank.
Exception:
Tanks with a capacity not exceeding 500 gallons (1893 L) that are filled from
a source other than a cargo tank or tank car.
Machinery and equipment utilizing hazardous
materials shall be braced and anchored in accordance with the seismic design requirements of
the Building Code for the seismic design category in which the machinery or equipment is
classified.
The following devices, equipment and systems shall be tested at the time of installation and not less than annually thereafter, provided that testing shall be conducted at least as often as is recommended by the manufacturer of such device, equipment or system:
- Gas detection systems, alarms and automatic emergency shutoff valves required by FC6004.2.2.10 for highly toxic and toxic gases.
- Limit control systems for liquid level, temperature and pressure required by FC 5003.2.7, 5004.8 and 5005.1.4.
- Emergency alarm systems required by FC 5004.9 and 5005.4.4.
- Monitoring and supervisory systems required by FC 5004.10 and 5005.1.6.
- Manually activated shutdown controls required by FC6403.1.1.1 for compressed gas systems conveying pyrophoric gases.
It shall be unlawful to release or dispose of any amount of hazardous material, including pesticides and fertilizers used for domestic, agricultural or horticultural purposes, into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere, except when allowed by federal, state or local regulations or permits, including the regulations of the New York State Department of Environmental Conservation, as set forth in 6 NYCRR Parts 597 and 611.
When hazardous materials are released in
quantities reportable under federal, state or local regulations, the commissioner shall be
notified and the following procedures required in accordance with FC 5003.3.1.1
through 5003.3.1.4.
Accurate records shall be kept of the discharge of
hazardous materials.
Provisions shall be made for controlling and
mitigating accidental discharges.
The owner of a facility or other
person responsible for an accidental discharge shall undertake all actions necessary to
remediate such discharge. When deemed necessary by the commissioner, cleanup may be
initiated by the department or other city agency. Costs associated with such cleanup shall
be borne by the owner or other person responsible for the discharge. The department shall
give such owner or other person written notice of such costs and an opportunity to be heard.
Payment of such costs shall be recoverable in any manner authorized by law, rule or
regulation. Failure to pay such costs shall cause a lien to be placed upon the premises
pursuant to the provisions of FC117.4, as applicable, or against vehicles or other personal
property in accordance with the provisions applicable thereto. Nothing in this section shall
be construed to preclude the implementation of response measures, or the recovery of the
costs of such measures, by any other city agency, either prior or subsequent to any response
measure implemented pursuant to this section.
A safety data sheet (SDS) for each hazardous material stored, handled or used on a premises shall be maintained on
such premises at a location where the SDS is readily available for reference by persons
handling or using such hazardous materials or supervising such storage, handling or use, and by
any department representative.
Unless otherwise exempted by the commissioner,
hazard identification signs as set forth in NFPA 704 for the specific material contained shall be
conspicuously affixed on stationary containers and aboveground tanks and at entrances to locations
where hazardous materials are stored, handled or used, including dispensing, in quantities
requiring a permit, including locations where such materials are dispensed, and at such other
locations as may be designated by the commissioner.
Individual containers, cartons or packages shall be
conspicuously marked or labeled in an approved manner. Signs reading "COMPRESSED
GAS" shall be conspicuously posted at the entrance to rooms or on cabinets containing
compressed gases.
Signs and markings required by FC 5003.5 and 5003.5.1 shall not be obscured or removed, shall be in English as a primary language or in symbols allowed by this code, shall be durable, and the size, color and lettering shall be acceptable to the commissioner.
Sources of ignition shall comply with the requirements of FC 5003.7.1 through 5003.7.3.
It shall be unlawful to smoke in the following locations, and "No Smoking" signs in compliance with the requirements of FC310 shall be conspicuously posted:
- In rooms or areas where hazardous materials are stored or used in open systems in amounts requiring a permit.
- Within 25 feet (7620 mm) of outdoor hazardous material storage, handling and use areas, including dispensing areas.
- In rooms or areas where flammable or combustible hazardous materials are stored, handled or used.
Open flames and devices that generate or operate at a high
temperature shall be kept a safe distance from hazardous material in storage or use.
Powered industrial trucks used in areas designated as
hazardous (classified) locations in accordance with the Electrical Code shall be listed and
labeled in accordance with NFPA 505.
Buildings, structures, control areas, enclosures and
cabinets for hazardous materials shall be designed and constructed in accordance with FC
5003.8.1 through 5003.8.7.
Buildings, structures, or portions thereof, in which hazardous
materials are stored, handled or used shall be constructed in accordance with the construction
codes, including the Building Code.
Group H occupancies containing quantities of hazardous materials in excess of those set forth in FC Table 5003.8.2 shall be in detached buildings.
For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.02832 m3, 1 ton = 2,000 pounds = 907.2 kg.
DETACHED STORAGE IS REQUIRED WHEN THE QUANTITY OF MATERIAL EXCEEDS THAT LISTED HEREIN
|
|||
Material
|
Class
|
Gases (SCF)a, b
|
|
Explosivesa |
Division 1.1
Division 1.2
Division 1.3
Division 1.4c
Division 1.5
Division 1.6
|
Maximum Allowable Quantity
Maximum Allowable Quantity
Maximum Allowable Quantity
Maximum Allowable Quantity
1
Maximum Allowable Quantity
Maximum Allowable Quantity
|
Not Applicable
|
Oxidizers |
Class 4
|
Maximum Allowable Quantity
|
Maximum Allowable Quantity
|
Unstable (reactives) detonable |
Class 3 or 4
|
Maximum Allowable Quantity
|
Maximum Allowable Quantity
|
Water-reactives detonable |
Class 2 or 3
|
Maximum Allowable Quantity
|
Not Applicable
|
Oxidizer, liquids and solids |
Class 3
Class 2
|
1,200
2,000
|
Not Applicable
|
Organic peroxides |
Class I
Class II
Class III
|
Maximum Allowable Quantity
Maximum Allowable Quantity
25
50
|
Not Applicable
|
Unstable (reactives) nondetonable |
Class 4
Class 3
Class 2
|
Maximum Allowable Quantity
1
25
|
Maximum Allowable Quantity
2,000
10,000
|
Water-reactives nondetonable |
Class 3
Class 2
|
1
25
|
Not Applicable
|
Pyrophoric material detonable |
Not Applicable
|
Maximum Allowable Quantity
|
Maximum Allowable Quantity
|
Pyrophoric gases nondetonable |
Not Applicable
|
Not Applicable
|
2,000
|
- For materials that are detonable, the distance to other buildings or lot lines shall be as specified in the Building Code. For materials classified as explosives, the required separation distances shall be as specified in FC Chapter 56. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
- "Maximum Allowable Quantity" means the maximum allowable quantity per control area set forth in FC Table 5003.1.1(1).
- Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing the net explosive weight of individual articles does not exceed 1 pound.
Control areas shall be separated
from each other by fire barriers constructed in accordance with Chapter 7 of the Building Code or horizontal assemblies constructed in accordance with Chapter 7 of the Building
Code, or both.
The percentage
of maximum allowable quantities of hazardous materials per control area allowed at each
floor level within a building shall be in accordance with FC Table 5003.8.3.3.
The maximum number of control areas per floor within a building or structure shall be in accordance with FC Table 5003.8.3.3.
FLOOR LEVEL
|
PERCENTAGE OF THE MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREAa
|
NUMBER OF CONTROL AREAS PER FLOOR
|
||
Above grade plane
|
Higher than 9
7-9
6
5
4
3
2
1
|
5
5
12.5
12.5
12.5
50
75
100
|
1
2
2
2
2
2
3
4
|
2
2
2
2
2
1
1
1
|
Below grade plane
|
1
2
Lower than 2
|
75
50
Not Allowed
|
3
2
Not Allowed
|
1
1
Not Allowed
|
- Percentages shall be of the maximum allowable quantity per control area shown in FC Tables 5003.1.1(1) and 5003.1.1(2), with all increases allowed in the footnotes to those tables.
- Fire barriers shall include walls and floors as necessary to provide separation from other portions of the building.
The required fire-resistance rating for fire barriers shall be in accordance with FC Table 5003.8.3.3. The floor assembly of the control area and the construction supporting the floor of the control area shall have a minimum 2-hour fire-resistance rating.
Exception: The floor assembly of the control area and the construction supporting the floor of the control area may be 1-hour fire-resistance rated in a building of Type IIA, IIIA and VA construction that is three stories or less in height and protected throughout by a sprinkler system.
The aggregate quantity of nonflammable solid and
nonflammable or noncombustible liquid hazardous materials allowed within a single
control area of a Group M display and storage area or a Group S storage area is allowed to
exceed the maximum allowable quantities specified in FC Tables 5003.1.1(1)
and 5003.1.1(2) without classifying the building or use as a Group H
occupancy, provided that the materials are displayed and stored in accordance with
FC5003.11.
Where a gas room is provided to comply with the
requirements of FC Chapter 60, the gas room shall be in accordance with FC
5003.8.4.1 and 5003.8.4.2.
Gas rooms shall be protected throughout by a
sprinkler system. Gas rooms shall be separated from the remainder of the building in
accordance with the construction codes, including the Building Code, based on the
occupancy group into which the building has been classified.
The ventilation system for gas rooms shall be
designed to operate at a negative pressure relative to the surrounding area. Highly toxic
and toxic gases shall additionally comply with the requirements of FC6004.2.2.6. The ventilation system shall be installed in accordance with the construction
codes, including the Mechanical Code.
Where an exhausted enclosure is used to increase
maximum allowable quantity per control area or when the location of hazardous materials in
exhausted enclosures is provided to comply with the requirements of FC Chapter 60, the
exhausted enclosure shall be in accordance with FC 5003.8.5.1 through
5003.8.5.3.
Exhausted enclosures shall be of noncombustible
construction.
The ventilation system for exhausted enclosures shall
be designed to operate at a negative pressure relative to the surrounding area. Ventilation
systems used for highly toxic and toxic gases shall additionally comply with the
requirements of FC6004.1.3. The ventilation system shall be installed in
accordance with the construction codes, including the Mechanical Code.
Exhausted enclosures where
flammable materials are used shall be protected by a fire extinguishing system in
accordance with FC Chapter 9 and the construction codes, including the Building Code.
Where a gas cabinet is used to increase the maximum
allowable quantity per control area or when the location of compressed gases in gas cabinets
is provided to comply with the requirements of FC Chapter 60, the gas cabinet shall be in
accordance with FC 5003.8.6.1 through 5003.8.6.3.
Gas cabinets shall be constructed of not less than
0.097-inch (2.5-mm) (No. 12 gauge) steel; provided with self-closing limited access ports
or noncombustible windows to give access to equipment controls; and have all interior
surfaces treated, coated or constructed of materials that are compatible with the hazardous
materials stored.
The ventilation system for gas cabinets shall be
designed to operate at a negative pressure relative to the surrounding area. Ventilation
systems used for highly toxic and toxic gases shall additionally comply with the
requirements of FC6004.1.2. The ventilation system shall be installed in
accordance with the construction codes, including the Mechanical Code.
The number
of containers stored in a single gas cabinet shall not exceed three.
Where storage cabinets are used
to increase maximum allowable quantity per control area or to comply with the requirements
of this chapter, such cabinets shall be in accordance with FC 5003.8.7.1 and
5003.8.7.2.
All interior surfaces of such cabinets shall be treated, coated or constructed of materials that are nonreactive with the hazardous material stored. Cabinets shall either be listed in accordance with UL 1275 as suitable for the intended storage or constructed in accordance with the following:
- Cabinets shall be of steel having a thickness of not less than 0.0478 inch (1.2 mm) (No. 18 gauge). The cabinet, including the door, shall be double walled with a 11/2-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. Doors shall be well fitted, self-closing and equipped with a self-latching device.
- The bottoms of cabinets utilized for the storage of liquids shall be liquid-tight to a minimum height of 2 inches (51 mm).
Electrical equipment and devices
within cabinets used for the storage of hazardous gases or liquids shall be in accordance
with the Electrical Code.
General precautions for the safe storage, handling
and use of hazardous materials shall be in accordance with FC 5003.9.1 through
5003.9.10.
Persons responsible for the
operation of areas in which hazardous materials are stored, handled or used, including
dispensing, shall be familiar with the chemical nature of the materials and the appropriate
mitigating actions necessary in the event of fire, leak or spill. A certificate of fitness shall be
required when specified by this code or the rules or as a condition of a permit.
One or more responsible persons shall be designated to serve as a liaison to the department in connection with any emergency response to the premises, for purposes of providing access to the location where hazardous materials are stored on the premises, providing access to safety data sheets, and otherwise assisting in the development and implementation of emergency procedures. The names and telephone numbers of such responsible persons shall be included on the annual inventory required by New York State General Municipal Law Section 209-u and on a hazardous materials management plan when such plan is required. Telephone numbers shall include a 24-hour contact number for such responsible persons.
Storage, handling and use areas, including dispensing areas,
shall be secured against unauthorized entry and safeguarded in a manner approved by the
commissioner.
Posts or other approved means shall be
provided to protect storage tanks and connected piping, valves and fittings; use areas; and
dispensing areas subject to vehicular damage in accordance with FC312.
Electrical wiring and equipment shall
be installed and maintained in accordance with the Electrical Code.
When conditions exist that could cause a flammable
mixture to be ignited by static electricity, equipment shall be grounded and all other necessary
and appropriate actions taken to prevent the accumulation of a static charge.
Materials that are sensitive to light shall be stored in
containers designed to protect them from such exposure.
Materials that are sensitive to shock shall be padded, suspended
or otherwise protected against jarring, seismic activity or other movement.
Incompatible materials shall be separated while in storage or use except for stored materials in containers having a capacity of not more than 5 pounds (2 kg) or 1/2 gallon (2 L). Separation shall be accomplished by:
- Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm).
- Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material.
- Storing liquid and solid materials in hazardous material storage cabinets. Materials that are incompatible shall not be stored in the same cabinet.
- Storing compressed gases in gas cabinets or exhausted enclosures in accordance with FC 5003.8.5 and 5003.8.6. Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure.
Shelving shall be of substantial construction, and shall be braced and anchored in accordance with the seismic design requirements of the construction codes, including the Building Code, for the seismic zone in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard when used for the storage of individual containers.
Exceptions:
Shelf storage of hazardous materials shall be maintained in an orderly manner- Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use.
- Storage of hazardous materials in amounts not requiring a permit in accordance with FC105.6.
Safety cans shall be listed in accordance with UL 30 when used to
increase the maximum allowable quantities per control area of flammable or combustible
liquids in accordance with FC Table 5003.1.1(1). Safety cans listed in accordance with UL
1313 are allowed for flammable and combustible liquids when not used to increase the
maximum allowable quantities per control area and for other hazardous material liquids in
accordance with the listing.
In addition to the requirements of FC5003.2, the handling of hazardous
materials in corridors or exit enclosures shall be in accordance with FC 5003.10.1 through
5003.10.3.6.
Hazardous material gas containers and tanks moved during
handling shall have their protective caps in place. Containers and tanks of highly toxic or toxic
compressed gases shall have their valve outlets capped or plugged with an approved closure
device in accordance with FC Chapter 53.
Containers of hazardous materials having a hazard ranking of 3 or 4 pursuant to NFPA 704, and liquids in containers exceeding 5 gallons (19 L), shall be moved during handling on a cart or hand truck meeting the requirements of FC5003.10.3, when moved through any corridor or exit enclosure.
Exceptions:
- Two hazardous material liquid containers, which are hand carried in approved safety carriers.
- Not more than four drums not exceeding 55 gallons (208 L) each, which are moved by suitable drum trucks.
- Containers of compressed gases, which are moved by approved carts or hand trucks, and containers not exceeding 25 pounds (11 kg), which are hand carried.
- Solid hazardous materials not exceeding 100 pounds (45 kg), which are moved by approved hand trucks, and a single container not exceeding 50 pounds (23 kg), which is hand carried.
Carts and hand trucks required by FC5003.10.2 to be used
to move hazardous materials shall be designed and constructed in accordance with FC
5003.10.3.1 through 5003.10.3.6.
Carts and hand trucks used to move hazardous materials shall be
designed to provide a stable base for such movement during handling and shall have a
means of restraining containers to prevent accidental dislodgement. Compressed gas
containers placed on carts and hand trucks shall be individually restrained.
Carts and hand trucks shall be provided with a device that will enable the operator to safely control movement by providing stops or speed-reduction devices.
The cart or hand truck shall be sturdily constructed of materials
compatible with the material being moved.
Carts and hand trucks used to move materials shall not obstruct
or be left unattended in any corridor, exit enclosure, or other means of egress.
Incompatible materials shall not be kept on the same
cart or hand truck.
The aggregate quantity of
nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and
displayed within a single control area of a Group M occupancy, or an outdoor control area, or
stored in a single control area of a Group S occupancy, may exceed the maximum allowable
quantity per control area indicated in FC5003.1 when stored and displayed in accordance with FC
5003.11.1 through 5003.11.3.10.
The aggregate amount of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single control area of a Group M occupancy or stored in a single control area of a Group S occupancy shall not exceed the amounts set forth in FC Table 5003.11.1.
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m3.
CONDITION
|
|||
Materiala
|
Class
|
Solids pounds
|
Liquids gallons
|
HEALTH-HAZARD MATERIALS—NONFLAMMABLE AND NONCOMBUSTIBLE SOLIDS AND LIQUIDS | |||
Corrosivesb,c |
Not Applicable
|
9,750
|
975
|
Highly toxics |
Not Applicable
|
20b, c
|
2b, c
|
Toxicsb, c |
Not Applicable
|
1,000
|
100
|
PHYSICAL-HAZARD MATERIALS —NONFLAMMABLE AND NONCOMBUSTIBLE SOLIDS AND LIQUIDS | |||
Oxidizersb, c |
4
|
Not Allowed
|
Not Allowed
|
3
|
1,150g
|
115
|
|
2
|
2,250h
|
225
|
|
1
|
18,000i, j
|
1,800i, j
|
|
Nondetonable unstable (reactives)b, c |
4
|
Not Allowed
|
Not Allowed
|
3
|
550
|
55
|
|
2
|
1,150
|
115
|
|
1
|
Not Limited
|
Not Limited
|
|
Nondetonable water-reactives |
3b, c
|
550
|
55
|
2b, c
|
1,150
|
115
|
|
1
|
Not Limited
|
Not Limited
|
- Hazard categories are as specified in FC5001.2.2.
- Maximum allowable quantities shall be increased 100 percent in buildings protected throughout by a sprinkler system. When Note c applies, amounts increased shall be as set forth in both notes.
- Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets in accordance with FC5003.8. When Note b applies, amounts increased shall be as set forth in both notes.
- See FC Table 5003.8.3.3 for design and number of control areas.
- Maximum allowable quantities for other hazardous material categories shall be in accordance with FC5003.1.
- Maximum allowable quantities shall be increased 100 percent in outdoor control areas.
- Maximum allowable quantities may be increased to 2,250 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.
- Maximum allowable quantities may be increased to 4,500 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.
- Quantities are unlimited where protected by a sprinkler system.
- Quantities are unlimited in an outdoor control area.
The aggregate amount of nonflammable solid and nonflammable or
noncombustible liquid hazardous materials stored and displayed within a single outdoor
control area of a Group M occupancy shall not exceed the amounts set forth in FC Table
5003.11.1.
Storage and display shall be in accordance with FC
5003.11.3.1 through 5003.11.3.10.
Display height shall not exceed 6 feet (1829 mm)
above the finished floor in display areas of Group M occupancies. Storage height shall not
exceed 8 feet (2438 mm) above the finished floor in storage areas of Group M and Group
S occupancies.
Individual containers less than 5 gallons (19 L) or less
than 25 pounds (11 kg) shall be stored or displayed on pallets, racks or shelves.
Racks and shelves used for storage or display shall be in
accordance with FC5003.9.9.
Containers shall be approved for the intended use and
identified as to their content.
Individual containers shall not exceed 100 pounds (45 kg) for
solids or 10 gallons (38 L) for liquids in storage and display areas.
Incompatible materials shall be separated in
accordance with FC5003.9.8.
Floors shall be in accordance with FC5004.12.
Aisles 4 feet (1219 mm) in width shall be maintained on three sides of
the storage or display area.
Hazard identification signs shall be provided in accordance with
FC5003.5.
Outdoor control areas for hazardous materials in amounts not exceeding the maximum allowable quantity per outdoor control area shall be in compliance with the following requirements:
- Outdoor control area shall be kept free from vegetation, rubbish and other combustible waste, and combustible materials not necessary to the storage. The area surrounding an outdoor control area shall be kept clear of such materials for a minimum of 15 feet (4572 mm).
- Outdoor control areas shall be located at least 5 feet (1524 mm) from a building opening and at least 15 feet (4572 mm) from Group A occupancies. Outdoor control areas shall be located at least 20 feet (6096 mm) from a lot line, public street or private road. Exception: A 2-hour fire-resistance-rated wall without openings extending not less than 30 inches (762 mm) above and to the sides of the storage area is allowed in lieu of such distances required from a building opening, lot line, public street or private road.
- Where a property exceeds 10,000 square feet (929 m2), there may be two outdoor control areas separated by a minimum distance of 50 feet (15 240 mm), when approved.
- Where a property exceeds 35,000 square feet (3252 m2), there may be multiple outdoor control areas, separated a minimum distance of 50 feet (15 240 mm), when approved.
Hazardous materials in amounts exceeding the maximum allowable quantity per
control area as set forth in FC5003.1 shall be stored in accordance with FC 5001, 5003 and 5004.
Hazardous materials in amounts not exceeding the maximum allowable quantity per control area
as set forth in FC5003.1 shall be stored in accordance with FC 5001 and 5003. Nonflammable
solid and nonflammable and noncombustible liquid hazardous materials in Group M retail
occupancies and Group S wholesale storage shall be stored and displayed in accordance with
FC5003.11.
Buildings, structures, rooms or areas used for the storage of liquid or solid hazardous materials shall be provided with spill control and secondary containment in accordance with FC 5004.2.1 through 5004.2.3.
Exception: Outdoor storage of containers on approved containment pallets in accordance with FC5004.2.3.
Buildings, structures, rooms or areas used for the storage of hazardous material liquids in individual vessels having a capacity of more than 55 gallons (208 L), or in which the aggregate capacity of multiple vessels exceeds 1,000 gallons (3785 L), shall be provided with spill control to prevent the flow of liquids to adjoining areas. Floors in indoor locations, and similar surfaces in outdoor locations, shall be designed to contain a spill from the largest single vessel by one of the following methods:
Except for surfacing, the floors, sills,
dikes, sumps and collection systems shall be constructed of noncombustible material, and
the liquid-tight seal shall be compatible with the material stored. When liquid-tight sills or
dikes are provided, they are not required at perimeter openings having an open-grate trench
across the opening that connects to an approved collection system.
Where required by FC Table 5004.2.2, buildings, structures, rooms or areas used for the storage of hazardous materials liquids or solids shall be provided with secondary containment in accordance with this section when the capacity of an individual vessel or the aggregate capacity of multiple vessels exceeds the following quantities:
- Liquids: Capacity of an individual vessel exceeds 55 gallons (208 L) or the aggregate capacity of multiple vessels exceeds 1,000 gallons (3785 L).
- Solids: Capacity of an individual vessel exceeds 550 pounds (250 kg) or the aggregate capacity of multiple vessels exceeds 10,000 pounds (4540 kg).
MATERIAL
|
INDOOR STORAGE
|
OUTDOOR STORAGE
|
|||
Physical-hazard materials | |||||
Combustible liquids |
Class II
|
Not
Applicable
|
See FC Chapter 57
|
Not
Applicable
|
See FC Chapter 57
|
Class IIIA
|
See FC Chapter 57
|
See FC Chapter 57
|
|||
Class IIIB
|
See FC Chapter 57
|
See FC Chapter 57
|
|||
Cryogenic fluids |
See FC Chapter 55
|
See FC Chapter 55
|
|||
Explosivesa |
See FC Chapter 56
|
See FC Chapter 56
|
|||
Flammable liquids | Class IA |
Not
Applicable
|
See FC Chapter 57
|
Not
Applicable
|
See FC Chapter 57
|
Class IB |
See FC Chapter 57
|
See FC Chapter 57
|
|||
Class IC |
See FC Chapter 57
|
See FC Chapter 57
|
|||
Flammable solids |
Not Required
|
Not Applicable
|
Not Required
|
Not Applicable
|
|
Organic peroxides, nondetonable |
Class I
|
Required
|
Required
|
Not Required
|
Required
|
Class II
|
Required
|
Required
|
Not Required
|
Not Required
|
|
Class III
|
|||||
Class IV
|
|||||
Class V
|
Not Required
|
Not Required
|
Not Required
|
Not Required
|
|
Oxidizers |
Class 4
|
Required
|
Required
|
Not Required
|
Required
|
Class 3
|
Not Required
|
||||
Class 2
|
Not Required
|
||||
Class 1
|
Not Required
|
Not Required
|
Not Required
|
Not Required
|
|
Pyrophorics, nondetonable |
Not Required
|
Required
|
Not Required
|
Required
|
|
Unstable (reactives), nondetonable |
Class 4
|
Required
|
Required
|
Required
|
Required
|
Class 3
|
|||||
Class 2
|
|||||
Class 1
|
Not Required
|
Not Required
|
Not Required
|
Not Required
|
|
Water-reactives, nondetonable |
Class 3
|
Required
|
Required
|
Required
|
Required
|
Class 2
|
|||||
Class 1
|
Not Required
|
Not Required
|
Not Required
|
Not Required
|
|
Health-hazard materials | |||||
Corrosives |
Not Required
|
Required
|
Not Required
|
Required
|
|
Highly toxics |
Required
|
Required
|
Required
|
Required
|
|
Toxics |
- Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
The building, structure, room or area shall contain or drain the hazardous materials and fire protection water through the use of one of the following methods:
- Liquid-tight sloped or recessed floors in indoor locations or similar protection in outdoor locations.
- Liquid-tight floors and raised or recessed sills or dikes in indoor locations or similar protection in outdoor locations.
- Sumps and collection systems.
- Drainage systems leading to an approved location.
- Other approved engineered systems.
Incompatible materials used in open systems shall be
separated from each other in the secondary containment system.
Secondary containment for indoor storage areas shall be
designed to contain a spill from the largest vessel plus the design flow volume of fire
protection water calculated to discharge from the fire extinguishing system over the
minimum required system design area or area of the room or area in which the storage is
located, whichever is smaller. The containment capacity shall be designed to contain the
flow for a minimum period of 20 minutes.
Secondary containment for outdoor storage areas shall be
designed to contain a spill from the largest individual vessel. If the area is open to rainfall,
secondary containment shall be designed to include the volume of a 24-hour rainfall as
determined by a 25-year storm but in no case less than 110 percent of the largest individual
vessel and provisions shall be made to drain accumulations of ground water and rainwater.
Monitoring shall be provided to detect hazardous materials in the
secondary containment system. The method of monitoring may be visual inspection of the
primary or secondary containment, or other approved means. Where secondary
containment is subject to the intrusion of water, a monitoring method for detecting water shall be provided. Where monitoring devices are provided, they shall be connected to
approved audible or visible alarms.
Drainage systems shall be in accordance with the Plumbing Code and the following requirements:
- The slope of floors to drains in indoor locations, or similar protection in outdoor locations, shall not be less than 1 percent.
- Drains from indoor storage areas shall be sized to carry the volume of the fire protection water as determined by the design density discharged from the fire extinguishing system over the minimum required system design area or area of the room or area in which the storage is located, whichever is smaller.
- Drains from outdoor storage areas shall be sized to carry the volume of the fire flow and the volume of a 24-hour rainfall as determined by a 25-year storm.
- Materials of construction for drainage systems shall be compatible with the materials stored.
- Incompatible materials used in open systems shall be separated from each other in the drainage system.
- Drains shall terminate in an approved location away from buildings, structures, valves, means of egress, fire access roadways, adjoining property and storm drains.
When used as an alternative to spill control and secondary containment for outdoor storage in accordance with the exception set forth in FC5004.2, containment pallets shall be in compliance with the following requirements:
- A liquid-tight sump accessible for visual inspection shall be provided.
- The sump shall be designed to contain not less than 66 gallons (250 L).
- Exposed surfaces shall be compatible with material stored.
- The containment pallet shall be protected to prevent collection of rainwater within the sump.
Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored.
Exhaust ventilation systems shall comply with the following requirements:
- Installation shall be in accordance with the Mechanical Code.
- Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot (0.00508 m3/s/m2) of floor area over the storage area.
- Systems shall operate continuously unless alternative designs are approved.
- A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in an approved location. The switch shall be a break-glass or other approved type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.
- Exhaust ventilation shall be designed based on the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor. For fumes or vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (305 mm) of the highest point of the room.
- The design and location of exhaust and inlet air openings shall serve to provide air movement across all portions of the floor and room to prevent the accumulation of vapors.
Incompatible materials shall be
separated in accordance with FC5003.9.8.
Indoor storage areas and storage buildings shall be protected throughout by a sprinkler system. The design of the sprinkler system shall not be less than that required for Ordinary Hazard Group 2 with a minimum design area of 3,000 square feet (279 m2). Where the materials or storage arrangement are required by other regulations to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.
Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency power system in accordance with the Electrical Code, and the construction codes, including the Building Code, and FC604.
Exceptions:
- Mechanical ventilation for storage of Class IB and Class IC flammable liquids and combustible liquids in closed containers not exceeding 61/2 gallons (25 L) capacity.
- Storage areas for Class 1 and 2 oxidizers.
- Storage areas for Class III, IV and V organic peroxides.
- Storage areas for highly toxic or toxic materials, in accordance with FC 6004.2.2.8 and 6004.3.2.6.
- Storage areas for which an approved fail-safe engineered system has been installed for mechanical ventilation, treatment systems or temperature control systems.
Limit controls shall be provided in accordance with FC 5004.8.1 and
5004.8.2.
Materials that must be kept at temperatures other than normal
ambient temperatures shall be provided with an approved means to maintain the temperature
within a safe range. Redundant temperature control equipment that will operate on failure of
the primary temperature control system, or other approved means to maintain the required
temperature range, shall be provided.
Stationary tanks and equipment containing hazardous material
liquids that can generate pressures exceeding design limits because of exposure fires or internal
reaction, shall have some form of construction or other approved means that will relieve
excessive internal pressure. The means of pressure relief shall vent to an approved location
outdoors or to an exhaust scrubber or treatment system in accordance with FC Chapter 60.
An approved manual emergency alarm system shall be provided in
buildings, rooms or areas used for storage of hazardous materials. Emergency alarm-initiating
devices shall be installed outside of each interior exit or exit access door of storage buildings,
rooms or areas. Activation of an emergency alarm-initiating device shall sound a local alarm to
alert occupants of an emergency situation involving hazardous materials.
Emergency alarm, detection and fire extinguishing systems required by
FC5004 shall be supervised by an approved central, proprietary or remote station service or shall
initiate an audible and visual signal at a constantly attended on-site location.
The area surrounding an outdoor storage area or tank
shall be kept clear of vegetation, rubbish and other combustible waste, and storage of combustible
materials, for a minimum distance of 25 feet (7620 mm).
Except for surfacing, floors of storage areas shall be of
noncombustible construction.
Outdoor hazardous material storage areas sheltered by overhead noncombustible construction shall not be considered indoor storage when the area is constructed in accordance with the requirements for weather protection as required by the construction codes, including the Building Code.
Hazardous materials in amounts exceeding the maximum allowable quantity per
control area set forth in FC5003.1 shall be handled and used, including dispensed, in accordance
with FC 5001, 5003 and 5005. Hazardous materials in amounts not exceeding the maximum
allowable quantity per control area set forth in FC5003.1 shall be handled and used, including
dispensed, in accordance with FC 5001 and 5003.
Separation of incompatible materials shall
be in accordance with FC5003.9.8.
Except for floor finishing operations, floors of areas where
liquid or solid hazardous materials are used in open systems shall be of noncombustible, liquidtight construction.
Where
required by other provisions of FC5005, spill control and secondary containment shall be
provided for hazardous material liquids in accordance with FC5004.2.
Limit controls shall be provided in accordance with FC 5005.1.4.1
through 5005.1.4.4.
Open tanks in which liquid hazardous materials are
used shall be equipped with a liquid-level limit control or other means to prevent overfilling
of the tank.
Temperature control shall be provided in accordance
with FC5004.8.1.
Pressure control shall be provided in accordance with
FC5004.8.2.
Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency power system in accordance with the Electrical Code, the construction codes, including the Building Code, and FC604.
Exception: Systems for highly toxic or toxic gases provided with emergency power in accordance with FC 6004.2.2.8 and 6004.3.2.6.
Alarm, detection and fire extinguishing systems required by other
provisions of FC5005 shall be supervised by an approved central station or shall initiate an
audible and visible signal at a continuously attended on-site location.
Adequate lighting by natural or artificial means shall be provided.
Indoor rooms or areas in which hazardous materials are handled or used shall be protected by a fire extinguishing system in accordance with FC Chapter 9 and the construction codes, including the Building Code. The design of any sprinkler system shall not be less than that required for Ordinary Hazard, Group 2, with a minimum design area of 3,000 square feet (279 m2). Where the materials or storage arrangement are required by other regulations to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.
Indoor use areas, including dispensing areas, shall be provided with exhaust ventilation in accordance with Section 502.8 of the Mechanical Code.
Exception: Ventilation is not required for flammable solids, unless they are in the form of finely divided particles or generate finely divided particles during use.
Liquids having a hazard ranking of 3 or 4 pursuant to NFPA 704 shall be transferred by one of the following methods:
- From safety cans complying with the requirements of UL 30.
- Through an approved closed piping system.
- From containers or tanks by an approved pump taking suction through an opening in the top of the container or tank.
- From containers or tanks by gravity through an approved self-closing or automatic-closing valve when the container or tank and dispensing operations are provided with spill control and secondary containment in accordance with FC5004.2. Highly toxic liquids shall not be dispensed by gravity from tanks.
- Approved engineered liquid transfer systems.
Exceptions:
- Liquids having a hazard ranking of 4 when dispensed from approved containers not exceeding 1.3 gallons (5 L).
- Liquids having a hazard ranking of 3 when dispensed from approved containers not exceeding 5.3 gallons (20 L).
Indoor use, including dispensing, of hazardous materials shall be in buildings
complying with the requirements of the construction codes, including the Building Code, and in
accordance with FC5005.1 and FC 5005.2.1 through 5005.2.2.5.
Use of hazardous materials in open containers or systems shall be in
accordance with FC 5005.2.1.1 through 5005.2.1.4.
Explosion control shall be provided in accordance with
FC5004.6 when an explosive environment can occur because of the characteristics or
nature of the hazardous materials or the manner in which they are used.
Buildings, rooms or areas where
hazardous material liquids are dispensed into vessels exceeding a 1.3-gallon (5 L) capacity
or used in open systems exceeding a 5.3-gallon (20 L) capacity shall be provided with spill
control in accordance with FC5004.2.1.
Where required by FC Table 5005.2.1.4, buildings, structures, rooms or areas where hazardous material liquids are used in open systems shall be provided with secondary containment in accordance with FC5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
- Individual vessel or system: greater than 1.3 gallons (5 L).
- Multiple vessels or systems: greater than 5.3 gallons (20 L).
MATERIAL
|
INDOOR USE
|
OUTDOOR USE
|
|||
Physical-hazard materials | |||||
Combustible liquids |
Class II
|
Not
Applicable
|
See FC Chapter 57
|
Not
Applicable
|
See FC Chapter 57
|
Class IIIA
|
See FC Chapter 57
|
See FC Chapter 57
|
|||
Class IIIB
|
See FC Chapter 57
|
See FC Chapter 57
|
|||
Cryogenic fluids |
Not Applicable
|
See FC Chapter 55
|
Not Applicable
|
See FC Chapter 55
|
|
Explosivesa |
See FC Chapter 56
|
See FC Chapter 56
|
|||
Flammable liquids | Class IA |
Not
Applicable
|
See FC Chapter 57
|
Not
Applicable
|
See FC Chapter 57
|
Class IB |
See FC Chapter 57
|
See FC Chapter 57
|
|||
Class IC |
See FC Chapter 57
|
See FC Chapter 57
|
|||
Flammable solids |
Not Required
|
Not Applicable
|
Not Required
|
Not Applicable
|
|
Organic peroxides nondetonable |
Class I
|
Not Required
|
Required
|
Not Required
|
Required
|
Class II
|
|||||
Class III
|
|||||
Class IV
|
|||||
Class V
|
Not Required
|
Not Required
|
Not Required
|
||
Oxidizers |
Class 4
|
Required
|
Not Required
|
Required
|
|
Class 3
|
|||||
Class 2
|
|||||
Class 1
|
|||||
Pyrophorics nondetonable |
Not Required
|
Required
|
Not Required
|
Required
|
|
Unstable (reactives) nondetonable |
Class 4
|
Not Required
|
Required
|
Required
|
Required
|
Class 3
|
|||||
Class 2
|
|||||
Class 1
|
Not Required
|
Not Required
|
Required
|
Required
|
|
Water-reactives, nondetonable |
Class 3
|
Not Required
|
Required
|
Required
|
Required
|
Class 2
|
|||||
Class 1
|
Not Required
|
Not Required
|
Required
|
Required
|
|
Health-hazard materials | |||||
Corrosives |
Not Required
|
Required
|
Not Required
|
Required
|
|
Highly toxics |
Required
|
||||
Toxics |
Not Required
|
- Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
Use of hazardous materials in closed containers or systems shall be in accordance with FC 5005.2.2.1 through 5005.2.2.5.
Systems shall be suitable for the use intended and shall be designed by
a qualified person. Controls shall be designed to prevent materials from entering or leaving
the process or reaction systems at other than the intended time, rate or path. Where
automatic controls are provided, they shall be designed to be fail safe.
Where closed systems are designed to be opened as part of normal
operations, ventilation shall be provided in accordance with FC5005.2.1.1.
Explosion control shall be provided in accordance with FC5004.6 where an explosive environment exists because of the hazardous materials or the manner in which they are used.
Buildings, rooms or areas where
hazardous material liquids are used in individual vessels exceeding a 55-gallon (208 L)
capacity shall be provided with spill control in accordance with FC5004.2.1.
Where required by FC Table 5005.2.1.4, buildings, rooms or areas where hazardous material liquids are used in vessels or systems shall be provided with secondary containment in accordance with FC5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
Outdoor use, including dispensing, of hazardous materials shall be in
accordance with FC 5005.3.1 through 5005.3.9.
Outdoor
use of hazardous materials, in either closed or open containers or systems, in amounts
exceeding the maximum allowable quantity per control area indicated in FC Tables
5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5005.1 and 5005.3.
Outdoor use of hazardous materials, in either closed or open containers or systems, in amounts
not exceeding the maximum allowable quantity per control area indicated in FC Tables
5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001 and 5003.
Outdoor use areas for hazardous materials shall be located as required for
outdoor storage in accordance with FC5004.
Outdoor areas where
hazardous material liquids are dispensed in vessels exceeding a 1.3-gallon (5 L) capacity or
used in open systems exceeding a 5.3-gallon (20 L) capacity shall be provided with spill control
in accordance with FC5004.2.1.
Where required by FC Table 5005.2.1.4, outdoor areas where hazardous material liquids are used in open systems shall be provided with secondary containment in accordance with FC5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
Outdoor areas
where hazardous material liquids are used in closed systems exceeding 55 gallons (208 L) shall
be provided with spill control in accordance with FC5004.2.1.
Where required by FC Table 5005.2.1.4, outdoor areas where hazardous material liquids are used in closed systems shall be provided with secondary containment in accordance with FC5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
The area surrounding an outdoor use area, including
an area used for dispensing, shall be kept clear of vegetation, rubbish and other combustible
waste, and combustible materials, for a minimum distance of 30 feet (9144 mm).
Outdoor hazardous material use areas sheltered by overhead noncombustible construction shall not be considered indoor use when the area is constructed in accordance with the requirements for weather protection as required in the construction codes, including the Building Code.
Handling of hazardous materials in indoor and outdoor locations in amounts exceeding the
maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1) through
5003.1.1(4) shall be in accordance with FC 5001, 5003, 5005.1 and 5005.4.
Handling of hazardous materials in indoor locations in amounts not exceeding the maximum
allowable quantity per control area indicated in FC Tables 5003.1.1(1) and 5003.1.1(2) shall
be in accordance with FC 5001 and 5003. Handling of hazardous materials in outdoor locations
in amounts not exceeding the maximum allowable quantity per control area indicated in FC
Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001 and 5003.
Outdoor handling areas for hazardous materials shall be located as required
for outdoor storage in accordance with FC5004.
Where hazardous materials in quantities exceeding the maximum
allowable quantity per control area having a hazard ranking of 3 or 4 pursuant to NFPA 704
are moved through corridors or exit enclosures, there shall be an emergency telephone system,
a local manual alarm station or an approved alarm-initiating device at not more than 150-foot
(45 720-mm) intervals throughout the handling route, and at each exit doorway throughout the
handling route. The signal shall be relayed to an approved central station or remote supervising
station or a constantly attended on-site location and shall also initiate a local audible alarm.
This section shall govern the storage, handling and use of laboratory chemicals in
a non-production laboratory and accessory storage of laboratory chemicals in a storage room. The
design and construction of non-production laboratories and accessory storage rooms for laboratory
chemicals shall comply with the requirements of the construction codes, including the Building
Code and the Mechanical Code.
Laboratory chemicals within a laboratory unit, including an educational or
instructional laboratory unit, shall be stored, handled and used in accordance with this section and,
except as otherwise provided in this section, NFPA 45, as modified by FC Appendix B with respect
to laboratory unit fire hazard class D requirements. The ceiling, floor and walls of a laboratory unit
shall be separated from all adjoining areas by a minimum 1-hour fire-rated construction.
Non-production laboratory operations requiring a permit shall be under the
personal supervision of a certificate of fitness holder. At least one certificate of fitness holder shall
be present on each floor of the laboratory unit on which laboratory operations are being conducted
while the laboratory is in operation. Additional certificate of fitness holders shall be provided as
the commissioner may require as a condition of the permit. Accessory laboratory chemical storage
rooms shall be under the general supervision of a certificate of fitness holder.
It shall be unlawful in any non-production laboratory or any accessory storage of laboratory chemicals in a storage room to:
- Store, handle or use any explosive.
- Store, handle or use any unclassified detonable organic peroxide, detonable pyrophoric material, detonable unstable (reactive) material or detonable water-reactive material.
- Store, handle or use any Class 4 unstable (reactive) material.
- Store, handle or use any Class 4 oxidizing material.
- Store, handle or use below grade any flammable gas.
- Use an open flame for heating or distilling any flammable solid, flammable liquid or flammable gas.
- Store flammable liquids in basements, cellars or other areas below grade.
- Store combustible liquids in basements, cellars or other areas below grade in a manner contrary to FC5704.3.5.1.
- Store, handle or use LPG in Group E and I occupancies in a manner contrary to FC6103.2.1.4.
- Store, handle or use in an educational laboratory gases classified as a Class 3 or 4 health hazard.
The quantities of laboratory chemicals stored, handled or used
within a laboratory unit, excluding storage rooms, shall be in accordance with FC 5006.6.1 through
5006.6.10. Unless designated as a control area, FC5003.8.3 shall not apply to a laboratory unit.
The density and total quantity of flammable and combustible liquids allowed within a laboratory unit, excluding storage rooms, shall be in accordance with Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class D.
Exceptions: For laboratory units other than educational or instructional laboratories pursuant to NFPA 45, as modified by FC Appendix B:
- The density of flammable and combustible liquids allowed within a Class D laboratory unit may be increased to those set forth in Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 25 gallons (95 L).
- The density of flammable and combustible liquids allowed within a Class D laboratory unit may be increased to those set forth in Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 30 gallons (114 L) and the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction.
- The quantity of flammable and combustible liquids allowed within a Class D laboratory unit, excluding quantities in storage cabinets or safety cans, may be increased from 75 gallons (284 L) to 100 gallons (379 L), provided the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction. Total quantities of flammable and combustible liquids, including quantities in storage cabinets and safety cans, may be increased from 150 gallons (568 L) to 200 gallons (757 L), provided the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction.
The storage, handling and use of flammable solids within a laboratory unit shall be in accordance with FC Chapters 50 and 59. The total quantity of flammable solids stored, handled and used, excluding any quantities in a storage room, shall not exceed 10 pounds (4.54 kg).
Exception: The total quantity of flammable solids allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 15 pounds (6.81 kg).
The storage, handling and use of solid and liquid oxidizers and organic peroxides within a laboratory unit shall be in accordance with FC Chapters 50, 62 and 63 and the total quantity of all such material, excluding any quantities in a storage room, shall not exceed 40 pounds (18.14 kg), provided that not more than 2 pounds (0.907 kg) of such oxidizers are Class 3 oxidizers and not more than 1 pound (0.454 kg) of such peroxides are Class I organic peroxides.
Exception: The total aggregate quantity of solid and liquid oxidizers and organic peroxides allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 50 pounds (22.7 kg), provided that not more than 2 pounds (0.907 kg) of such oxidizers are Class 3 oxidizers and not more than 1 pound (0.454 kg) of such peroxides are Class I organic peroxides.
The storage, handling and use of unstable (reactive) material within a laboratory unit shall be in accordance with FC Chapters 50 and 66 and the total quantity, excluding any quantities in a storage room, shall not exceed 6 pounds (2.722 kg), provided not more than 1 pound (0.454 kg) of such reactive material is Class 3 unstable (reactive).
Exception: The total quantity of unstable (reactive) material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 12 pounds (5.44 kg), provided not more than 1 pound (0.454 kg) of such reactive material is Class 3 unstable (reactive).
The storage, handling and use of water-reactive material within a laboratory unit shall be in accordance with FC Chapters 50 and 67 and the total quantity, excluding any quantities in a storage room, shall not exceed 21/2 pounds (1.134 kg).
Exception: The total quantity of water-reactive material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 5 pounds (2.27 kg).
The storage, handling and use of solid or liquid pyrophoric material within a laboratory unit shall be in accordance with FC Chapters 50 and 64 and the total quantity, excluding any quantities in a storage room, shall not exceed 1/2 pound (0.227 kg).
Exception: The total quantity of solid or liquid pyrophoric material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 1 pound (0.454 kg).
The storage, handling and use of solid or liquid toxic material within
a laboratory unit shall be in accordance with FC Chapters 50 and 60 and the total quantity,
excluding any quantities in a storage room, shall not exceed 250 pounds (113.4 kg).
The storage, handling and use of hazardous gases within a
laboratory unit shall be in accordance with this section, FC Chapters 50, 53 through 55, 58, 60,
63, 64 and 66, as applicable, and NFPA 45, as modified by FC Appendix B. The total quantity
of hazardous gases, excluding any quantity stored in a storage room, shall be in accordance
with NFPA 45, as modified by FC Appendix B.
It shall be unlawful to store, handle
or use in any instructional laboratory unit any combination of highly toxic, toxic, and
corrosive gases in quantities that exceed 20 SCF (0.566 m3).
When the quantity of cryogenic inert gases or refrigerated
carbon dioxide stored, handled or used within a laboratory unit exceeds 60 gallons (227 L),
an oxygen sensor shall be installed and maintained at one or more locations within the
laboratory unit in accordance with FC5505.4.1.1.1, provided that at least one oxygen sensor
is installed in the laboratory unit.
Storage rooms for laboratory chemicals accessory to a
laboratory unit shall be classified as set forth in the Building Code.
In addition to the quantities that may be stored, handled and used in a laboratory unit pursuant to FC5006.6, chemicals for use in a laboratory unit may be stored in a dedicated storage room complying with Chapter 4 of the Building Code and the following requirements:
- Storage room capacity shall not exceed a maximum of 300 gallons (1136 L) of chemicals, not to exceed 5 gallons per square foot (204 L/m2) of floor area.
- Flammable gas storage rooms shall not contain more than 2,500 SCF (70.8 m3) of flammable gas.
- Chemicals that are incompatible with each other shall not be stored in the same storage room, unless in compliance with the requirements of this chapter.
- Chemicals shall not be used within the storage room.
Where more than 5 gallons (19 L) of corrosive liquid or flammable liquid
are stored, handled or used, suitable facilities with fixed overhead or flexible hand-held showers
shall be provided. Such shower shall be within 25 feet (7620 mm) of the laboratory unit and storage
room door and shall be maintained in good working order, and readily accessible at all times.
Where more than 5 gallons (19 L) of corrosive liquids
are stored, handled or used, a sufficient quantity of suitable neutralizing or absorbing agents shall
be provided.
Curtains and drapes installed in a laboratory unit shall comply with
the flame resistance requirements of FC Chapter 8.
This section shall govern the transportation of hazardous materials, as defined in
the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 173.
Transportation of hazardous materials shall be in accordance with the regulations
of the United States Department of Transportation and this section.
It shall be unlawful to:
- Transport hazardous materials in or through the city where such transport is prohibited or restricted by federal or state law, rule or regulation, including restrictions on transportation of hazardous materials over bridges and through tunnels.
- Transport in or through the city hazardous materials of such type, in such quantities, or in such manner as is prohibited by this code or the rules, except where such transport is in accordance with approved routes and times or other approved procedures or safety measures.
- Transport hazardous materials in quantities requiring a permit pursuant to this code or the rules without such permit.
- Deliver hazardous materials in quantities requiring a permit pursuant to this code or the rules to any location unless the owner or other person taking delivery thereof is in possession of a permit for the storage, handling and/or use of such hazardous material at such location.
- Transport LPG containers that are or have ever been filled with LPG in the trunk of a passenger motor vehicle, or other area of such vehicle not readily visible to emergency responders.
Transportation of hazardous materials by vehicle shall be in accordance with this section, the rules, and the requirements contained in the regulations of the United States Department of Transportation, as set forth in 49 CFR, Parts 171, 172, 173, 177, 178, 180, 383, 387, 390, 392, 393, 396 and 397 and their appendices, and any amendments thereto, with respect to:
- The design, construction, maintenance and equipment of cargo tanks and other vehicles.
- The marking and placarding of vehicles.
- The preparation, execution and use of shipping documents.
- The handling, loading and unloading of hazardous materials.
- The qualifications and commercial driver's license requirements of vehicle operators.
- Insurance and other financial requirements.
Transportation of explosives by vehicle for
storage, handling and use in the city shall additionally comply with the requirements of FC
5007.6.1 through 5007.6.6.
Except as otherwise authorized by the department, it shall be
unlawful to transport, including delivering, any blasting materials or Division 1.1 or 1.5
explosives for storage, handling or use in the city, except in a vehicle designed and constructed
in accordance with the rules, and for which a permit has been issued.
It shall be unlawful to transport any nitroglycerine-containing material, except nitroglycerine in the form of tablets, pills or granules, in quantities not exceeding ten thousand, containing not more than 1/50 of a grain each, or to transport frozen nitroglycerine.
Other than as prescribed or approved by the commissioner,
it shall be unlawful to sell or deliver for use any explosive except in original and unopened
packages, packed in accordance with FC 5007.6.3.1 through 5007.6.3.3.
Dynamite and other explosives containing a
liquid which may exude a liquid shall be transported in DOTn approved cases, lined with
a liquidproof plastic lining sufficient to prevent the exudation of the liquid. Such cases shall
contain not more than 50 pounds (22.7 kg) of net explosive weight.
Other blasting materials (except black powder, blasting
powder and smokeless propellant) that do not contain a substance subject to deterioration
or instability by exposure to moisture shall be transported in DOTn approved cases each
containing not more than 50 pounds (22.7 kg) of net explosive weight.
All explosives in the form of sticks or cartridges shall be
packed so as to lie on their sides; and, when the boxes are loaded in or upon a motor vehicle,
marine vessel or watercraft they shall be so arranged that the sticks or cartridges rest on
their sides.
Transportation of blasting caps and other detonators shall additionally
comply with the requirements of FC 5007.6.4.1 and 5007.6.4.2.
It shall be unlawful to bring into, transport, or deliver within the
city any blasting caps and other detonators, unless packaged in original, unopened boxes.
It shall be unlawful to transport any detonators in quantities
exceeding five thousand, or to transport or cause to be transported, detonators together with
any other explosives, except in an approved container in accordance with the regulations
of the United States Department of Transportation, as set forth in 49 CFR Part 177.
Black powder, blasting
powder or smokeless propellant shall be transported in containers of not more than 25 pounds
(11.34 kg).
Vehicles transporting explosives shall comply with the following requirements:
- Explosives shall be delivered only during daylight hours.
- No unnecessary stops shall be made in transit.
- Vehicles shall be escorted in accordance with FC5007.12, as applicable.
- If explosives are being transported in more than one vehicle, the vehicles shall maintain a safe distance from each other of not less than 250 feet (76 200 mm).
- It shall be unlawful to transport or deliver any explosives in a subway or other underground tunnel or conveyance, except as approved for blasting operations.
Transportation of explosives by marine
vessel and watercraft shall be in accordance with the regulations of the United States Department
of Transportation, as set forth in CFR Part 176, and any amendments thereto, and shall additionally
comply with the requirements of FC 5007.7.1 through 5007.7.5.
It shall be unlawful to store for more than 48
hours on board of any marine vessel or watercraft lying to at a wharf, pier, bulkhead or other
structure over or contiguous to navigable waters within the city, any explosives in excess of
the amount required for the vessel's own use for signaling or lifesaving purposes.
Any powder-boat or other marine vessel or watercraft used to transport
explosives upon the navigable waters within the city for delivery at a wharf, pier, bulkhead or
other structure over or contiguous to navigable waters, or to a marine vessel or watercraft lying
thereto, shall, while transporting explosives, have on board at all times two persons, each
holding a certificate of fitness for explosives handling. Only such certificate holders, the permit
holder and the marine vessel or watercraft's crew shall be allowed in or upon such vessel or
watercraft. Whenever practicable, all explosives shall be stowed on deck under a waterproof
cover or otherwise kept dry.
Except for marine vessels and watercraft engaged in export trade, it shall
be unlawful to carry in or upon a marine vessel or watercraft transporting explosives within
the city, detonators together with any other explosives, except in approved containers in accordance with the regulations of the United States Department of Transportation, as set forth
in 49 CFR Part 176.
It shall be unlawful to unload explosives onto a wharf, pier, bulkhead or
other structure over or contiguous to navigable waters. Explosives intended for storage,
handling or use within the city shall be transferred from the marine vessel or watercraft making
the delivery directly to a vehicle at a wharf, pier, bulkhead or other structure over or contiguous
to navigable waters approved by the commissioner. Explosives intended for shipment to points
outside the city may be transferred from a marine vessel or watercraft directly to another
marine vessel or watercraft lying at a wharf, pier, bulkhead or other structure within the city
over or contiguous to navigable waters approved by the commissioner, provided the amount
so transferred does not exceed 2,500 pounds (1134 kg). All such shipments in quantities
exceeding 2,500 pounds (1134 kg) but not more than 5,000 pounds (2268 kg), may be
transferred from marine vessel or watercraft to a marine vessel or watercraft at a distance of
not less than 1,000 feet (304 800 mm) from any pier line.
It shall be unlawful to smoke or maintain any
flame while in or upon any marine vessel or watercraft carrying explosives, or allow in or upon
such vessel or watercraft, any intoxicated person.
Transportation of fireworks by vehicle for
firework displays in the city shall additionally comply with the requirements of FC 5007.8.1 and
5007.8.2.
It shall be unlawful to transport fireworks through the city
unless such fireworks are being transported to or from a display site for which a permit has
been issued and such vehicle is escorted by department firefighting apparatus in accordance
with FC5007.12.
Transportation of
flammable and combustible liquids by vehicle shall additionally comply with the requirements of
FC 5007.9.1 through 5007.9.6.
Cargo tanks shall not be used unless they are in good
working order and free from accumulation of grease, oil or other flammable or combustible
waste.
The operator of a cargo tank shall not
remain in the vehicle during loading or unloading of the cargo and shall personally
supervise such operation from a location at which the operator may observe the vehicle,
the delivery and vapor recovery hoses, the fill connection and any overfilling of the tank.
The cargo tank motor shall be shut down during the making
and breaking of hose connections. If loading or unloading is performed without the use of
a power pump, the cargo tank motor shall be shut down throughout such operations.
All appropriate actions shall be taken to prevent
vehicle movement during the loading and unloading of the cargo, including setting the
parking brake and chocking of tires.
A cargo tank or compartment thereof shall not be loaded to absolute
capacity. The vacant space in a cargo tank or compartment thereof shall not be less than 1
percent to prevent leakage from or distortion of such tank or compartment by expansion of
the contents caused by a rise in temperature.
The operator of a cargo tank shall, before making delivery
to a tank, determine the unfilled capacity of the tank by use of a suitable gauging device,
and shall not deliver cargo in excess of that amount.
During the loading of cargo tanks with openable domes, the
domes shall be secured on all but the receiving compartment, except that during loading of
gasoline, all domes shall be secured.
Flammable and combustible liquids shall not be loaded
into or transported in a cargo tank or delivered at a temperature above the material's
ignition temperature.
An external bond-wire connection or bondwire integral to the delivery hose shall be provided when transferring flammable liquids
into underground tanks.
It shall be unlawful for the operator of a cargo tank to smoke in and
within 25 feet (7620 mm) of the vehicle while transporting, loading or unloading cargo or
to allow others to do so.
Flammable and combustible liquids shall be transferred to
tanks by means of approved liquid- and vapor-tight connections between the delivery hose
and fill tank connection. Where underground tanks are equipped with a vapor recovery
system, all connections required for the safe and proper functioning of the vapor recovery
system shall be made and maintained liquid- and vapor-tight throughout the unloading
process. Vapors shall not be discharged at grade level during delivery.
In making any delivery of flammable or combustible liquid
the operator of the cargo tank shall ensure, prior to unloading, that all hoses utilized for
liquid delivery and vapor recovery are protected from physical damage, including damage
by motor vehicles. Such protection shall be provided by positioning the cargo tank to
prevent motor vehicles from passing through the area or areas occupied by hoses, or by
other approved equivalent means.
Gasoline that is transferred to underground tanks shall
be discharged by gravity only.
Parking of cargo tanks shall be in accordance with FC
5007.9.2.1 and 5007.9.2.2, except that in the event of an accident, mechanical breakdown or
other emergency, a cargo tank may be parked and left unattended at any safe location while
the operator is obtaining assistance.
It shall be unlawful to:
- Leave a cargo tank unattended at any time on a public street, or any off-street location within 250 feet (76 200 mm) of an occupied building, or any other restricted location designated by the commissioner by rule or as a condition of a permit.
- Park cargo tanks indoors.
Cargo tanks temporarily parked during working hours
shall be parked at an approved off-street location not less than 250 feet (76 200 mm) from
an occupied building. Cargo tanks shall be parked during nonworking hours on the grounds
of a bulk plant or terminal, not less than 25 feet (7620 mm) from the nearest lot line; or at
other approved location, not less than 50 feet (15 240 mm) from any building.
Cargo tanks shall be equipped with a portable fire
extinguisher complying with the requirements of FC906 and having a minimum rating of 2-
A:20-B:C. During unloading of the cargo tank, the portable fire extinguisher shall be outside
of the motor vehicle and shall be readily available, but at a distance of at least 15 feet (4572
mm) from the unloading valves.
Except as otherwise provided in FC5706.2.8,
cargo tanks shall deliver flammable or combustible liquids only to approved stationary storage
systems. Flammable liquids being transported by a motor vehicle other than a cargo tank shall
not be dispensed from a container prior to removal of the container from the vehicle.
Department representatives may authorize
a transfer from one cargo tank directly into a permitted or other approved cargo tank in the
interest of public safety, such as when a cargo tank has been involved in a vehicular accident
or has otherwise been damaged.
The maximum capacity of each compartment of a cargo
tank shall be marked, in gallons, on the driver and passenger sides of the cargo tank in 3-inch
(76-mm) white letters.
Transportation of compressed
gases by cargo tank shall additionally comply with the requirements of FC5007.10.1.
It shall be unlawful to transport the following compressed gases in a cargo tank:
- Acetylene.
- Liquefied carbon monoxide.
- Liquefied chlorine.
- Cyanogen.
- Cyclopropane.
- Diborane.
- Di-, mono-, and tri-methylamines.
- Dimethyl ether.
- Ethylene.
- Fluorine.
- Liquefied hydrogen.
- Hydrogen cyanide.
- Hydrogen sulfide.
- Liquefied petroleum gases (LPG).
- Liquefied natural gas (LNG).
- Methylacetylene propadiene mixture-stabilized, including propyns, mapp gas or apache gas.
- Methyl chloride.
- Methyl mercaptan.
- Phosgene.
- Phosphine.
- Vinyl chloride.
- Vinyl fluoride.
- Vinyl methyl ether.
- Any gas mixtures of the foregoing.
- Any gas that contains:
- Bromacetone.
- Cyanogen chloride containing less than 0.9 percent water.
- Diphosgene.
- Ethyldichlorarsine.
- Methyldichlorarsine.
- Nitrogen peroxide (tetroxide).
- Nitrogen tetroxide-nitric oxide mixtures containing up to 33.2 percent weight nitric oxide.
Vehicles transporting hazardous materials shall comply
with such route and time requirements as the commissioner may promulgate by rule, to the
maximum extent possible, to minimize their travel on local, non-arterial roads.
Vehicles
transporting explosives and fireworks shall additionally comply with the requirements of FC
5007.12.1 and 5007.12.2.
Vehicles transporting in or through the city
Division 1.1, 1.2, 1.3 or 1.5 explosives requiring the vehicle to be placarded pursuant to DOTn
regulations, including vehicles in continuous transit or transporting such explosives on
approved routes at approved times, shall be escorted by department firefighting apparatus
unless such explosives are transported in a vehicle for which a transportation permit has been
issued.
Vehicles transporting fireworks in amounts
requiring the vehicle to be placarded pursuant to DOTn regulations, whether in continuous
transit through the city or to or from a fireworks display in the city or surrounding waters, shall
be escorted by department firefighting apparatus, in accordance with approved routes and
times.