Heads up: There are no amended sections in this chapter.
This appendix provides the modifications to the nationally recognized standard ASHRAE 90.1-2010, governing commercial energy efficiency. Where a referenced publication has been modified for the City of New York as by the New York City Construction Codes and the New York City Energy Conservation Code, every reference to such publication shall be deemed to include all such modifications.
The standards for energy efficiency in commercial buildings, as defined in Section C202 of this code, shall be in accordance with Chapter C4 of this code or in accordance with ASHRAE 90.1-2010 as amended by chapter 3 of the 2014 Supplement and Section 28-1001.2.3 of the Administrative Code. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.
The following New York City amendments to ASHRAE 90.1-2010, as amended by Chapter 3 of the 2014 Supplement, are hereby adopted as set forth in this section.

Chapter 2 — Definitions, Abbreviations, and Acronyms

2.2 Delete Section 2.2 and replace with the following:

2.2 The provisions of this standard do not apply to:

(a) detached one-family dwellings having not more than three stories above grade plane;

(b) detached two-family dwellings having not more than three stories above grade plane;

(c) buildings that (i) consist of three or more attached townhouse units and (ii) have not more than three stories above grade plane;

(d) buildings that (i) are classified in accordance with Chapter 3 of the 2010 edition of the Building Code of New York State in Group R-2, R-3 or R-4 and (ii) have not more than three stories above grade plane;

(e) factory manufactured homes (as defined in section 372(8) of the Executive Law); and

(f) mobile homes (as defined in section 372(13) of the Executive Law).

For the purposes of this section 2.2, the term "grade plane" means a reference plane representing the average of finished ground level adjoining the building at exterior walls. Where the finished ground level slopes away from the exterior walls, the reference plane shall be established by the lowest points within the area between the building and the lot line or, where the lot line is more than 6 feet (1829 mm) from the building, between the building and a point 6 feet (1829 mm) from the building, and the term "townhouse unit" means a single-family dwelling unit constructed in a group of three or more attached units in which each unit (i) extends from the foundation to roof and (ii) has open space on at least two sides.

The provisions of this standard do apply to all buildings not included in (a), (b), (c), (d), (e) of (f) of this Section 2.2. In particular, but not by way of limitation, the provisions of this standard do apply to detached one-family dwellings having more than three stories above grade plane.

Chapter 6 — Heating, Ventilation, and Air-Conditioning

6.7.2.4 Delete Section 6.7.2.4 in its entirety and replace with a new Section 6.7.2.4 to read as follows:

6.7.2.4. Projects complying with this standard shall also comply with Section C408 of the New York City Energy Conservation Code in regards to system commissioning. When demonstrating compliance with Section C408.3.1, projects following ASHRAE 90.1-2010 must demonstrate compliance with Chapter 9 of ASHRAE 90.1-2010 as required, in lieu of Section C405 of the New York City Energy Conservation Code.

Table 6.8.1A Delete Table 6.8.1A in its entirety and replace with a new Table 6.8.1A to read as follows:

TABLE 6.8.1A ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT TYPE SIZE CATEGORY HEATING
SECTION TYPE
SUBCATEGORY OR
RATING CONDITION
MINIMUM EFFICIENCYa TEST PROCEDUREb
Before 6/1/2011 As of 6/1/2011
Air conditioners,
air cooled
< 65,000 Btu/hc All Split System 13.0 SEER 13.0 SEER AHRI
210/240
Single Package 14.0 SEER 14.0 SEER
Through-the-wall
(air cooled)
≤ 30,000 Btu/hc All Split system 13.0 SEER 13.0 SEER
Single Package 14.0 SEER 14.0 SEER
Small-duct high-velocity
(air cooled)
< 65,000 Btu/hc All Split System 10.0 SEER 11.0 SEER
Air conditioners,
air cooled
≥ 65,000 Btu/h
and
< 135,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.2 EER
11.4 IEER
11.2 EER
11.4 IEER
AHRI
340/360
All other Split System and
Single Package
11.0 EER
11.2 IEER
11.0 EER
11.2 IEER
≥ 135,000 Btu/h
and
< 240,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.0 EER
11.2 IEER
11.0 EER
11.2 IEER
All other Split System and
Single Package
10.8 EER
11.0 IEER
10.8 EER
11.0 IEER
≥ 240,000 Btu/h
and
< 760,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
10.0 EER
10.1 IEER
10.0 EER
10.1 IEER
All other Split System and
Single Package
9.8 EER
9.9 IEER
9.8 EER
9.9 IEER
≥ 760,000 Btu/h Electric Resistance
(or None)
Split System and
Single Package
9.7 EER
9.8 IEER
9.7 EER
9.8 IEER
All other Split System and
Single Package
9.5 EER
9.6 IEER
9.5 EER
9.6 IEER
Air conditioners,
water cooled
< 65,000 Btu/hb All Split System and
Single Package
12.1 EER
12.3 IEER
12.1 EER
12.3 IEER
AHRI
210/240
≥ 65,000 Btu/h
and
< 135,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.5 EER
11.7 IEER
12.1 EER
12.3 IEER
AHRI
340/360
All other Split System and
Single Package
11.3 EER
11.5 IEER
11.9 EER
12.1 IEER
≥ 135,000 Btu/h
and
< 240,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.0 EER
11.2 IEER
12.5 EER
12.5 IEER
All other Split System and
Single Package
10.8 EER
11.0 IEER
12.3 EER
12.5 IEER
≥ 240,000 Btu/h
and
< 760,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.0 EER
11.1 IEER
12.4 EER
12.6 IEER
All other Split System and
Single Package
10.8 EER
10.9 IEER
12.2 EER
12.4 IEER
≥ 760,000 Btu/h Electric Resistance
(or None)
Split System and
Single Package
11.0 EER
11.1 IEER
12.2 EER
12.4 IEER
All other Split System and
Single Package
10.8 EER
10.9 IEER
12.0 EER
12.2 IEER


(continued)

TABLE 6.8.1A ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT
TYPE
SIZE
CATEGORY
HEATING
SECTION
TYPE
SUB-CATEGORY
OR
RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDUREa
Before
6/1/2011
As of
6/1/2011
Air conditioners,
evaporatively cooled
< 65,000 Btu/hb All Split System and
Single Package
12.1 EER
12.3 IEER
12.1 EER
12.3 IEER
AHRI
210/240
≥ 65,000 Btu/h
and
< 135,000 Btu/h
Electric
Resistance
(or None)
Split System and
Single Package
11.5 EER
11.7 IEER
12.1 EER
12.3 IEER
AHRI
340/360
All other Split System and
Single Package
11.3 EER
11.5 IEER
11.9 EER
12.1 IEER
≥ 135,000 Btu/h
and
< 240,000 Btu/h
Electric
Resistance
(or None)
Split System and
Single Package
11.0 EER
11.2 IEER
12.0 EER
12.2 IEER
All other Split System and
Single Package
10.8 EER
11.0 IEER
11.8 EER
12.0 IEER
≥ 240,000 Btu/h
and
< 760,000 Btu/h
Electric
Resistance
(or None)
Split System and
Single Package
11.0 EER
11.1 EER
11.9
EER
12.1
EER
All other Split System and
Single Package
10.8 EER
10.9 EER
12.2 EER
11.9 EER
≥ 760,000 Btu/h Electric
Resistance
(or None)
Split System and
Single Package
11.0 EER
11.1 EER
11.7 EER
11.9 EER
All other Split System and
Single Package
10.8 EER
10.9 EER
11.5 EER
11.7 EER
Condensing units,
air cooled
≥ 135,000 Btu/h 10.1 EER
11.4 IEER
10.5 EER
11.8 IEER
AHRI
365
Condensing units,
water cooled
≥ 135,000 Btu/h 13.1 EER
13.6 IEER
13.5 EER
14.0 IEER
Condensing units,
evaporatively cooled
≥ 135,000 Btu/h 13.1 EER
13.6 IEER
13.5 EER
14.0 IEER

a. IPLVs and part-load rating conditions are only applicable to equipment with capacity modulation.
b. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
c. Single-phase, air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.


Table 6.8.1B Delete Table 6.8.1B in its entirety and replace with a new Table 6.8.1B to read as follows:

TABLE 6.8.1B ELECTRICALLY OPERATED UNITARY AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION
TYPE
SUBCATEGORY OR
RATING CONDITION
MINIMUM
EFFICIENCYa
TEST PROCEDUREb
Air cooled
(cooling mode)
< 65,000 Btu/hc All Split System 14.0 SEER AHRI
210/240
Single Packaged 14.0 SEER
Through-the-wall,
air cooled
≤ 30,000 Btu/hc All Split System 14.0 SEER
Single Packaged 14.0 SEER
Single-duct high-velocity
air cooled
< 65,000 Btu/hc All Split System 13.0 SEER
Air cooled
(cooling mode)
≥ 65,000 Btu/h and
< 135,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
11.0 EER
11.2 IEER
AHRI
340/360
All other Split System and
Single Package
10.8 EER
11.0 IEER
≥ 135,000 Btu/h and
< 240,000 Btu/h
Electric Resistance
(or None)
Split System and
Single Package
10.6 EER
10.7 IEER
All other Split System and
Single Package
10.4 EER
10.5 IEER
≥ 240,000 Btu/h Electric Resistance
(or None)
Split System and
Single Package
9.5 EER
9.6 IEER
All other Split System and
Single Package
9.3 EER
9.4 IEER
Water source
(cooling mode)
< 17,000 Btu/h All 86°F entering water 11.2 EER ISO 13256-1
≥ 17,000 Btu/h and
< 65,000 Btu/h
All 86°F entering water 12.0 EER
≥ 65,000 Btu/h and
< 135,000 Btu/h
All 86°F entering water 12.0 EER
Ground water source
(cooling mode)
< 135,000 Btu/h All 59°F entering water 16.2 EER
All 77°F entering water 13.4 EER
Water-source water to water
(cooling mode)
< 135,000 Btu/h All 86°F entering water 10.6 EER ISO 13256-2
59°F entering water 16.3 EER
Ground water source
Brine to water
(cooling mode)
< 135,000 Btu/h All 77°F entering fluid 12.1 EER


(continued)

TABLE 6.8.1B—continued ELECTRICALLY OPERATED UNITARY AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT TYPE SIZE
CATEGORY
HEATING SECTION
TYPE
SUBCATEGORY OR
RATING CONDITION
MINIMUM
EFFICIENCYa
TEST PROCEDUREb
Air cooled
(heating mode)
< 65,000 Btu/hc Split System 8.2 HSPF AHRI
210/240
Single Package 8.0 HSPF
Through-the-wall,
(air cooled, heating mode)
≤30,000 Btu/hc
(cooling capacity)
Split System 8.2 HSPF
Single Package 8.0 HSPF
Small-duct high velocity
(air cooled, heating mode)
< 65,000 Btu/hc Split System 7.7 HSPF
Air cooled
(heating mode)
≥ 65,000 Btu/h and
< 135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
Outdoor Air
3.3 COP AHRI
340/360
17°F db/15°F wb
Outdoor Air
2.25 COP
≥ 135,000 Btu/h
(cooling capacity)
47°F db/43°F wb
Outdoor Air
3.2 COP
17°F db/15°F wb
Outdoor Air
2.05 COP
Water source
(heating mode)
< 135,000 Btu/h
(cooling capacity)
68°F entering water 4.2 COP ISO 13256-1
Ground water source
(heating mode)
< 135,000 Btu/h
(cooling capacity)
50°F entering water 3.6 COP
Ground source
(heating mode)
< 135,000 Btu/h
(cooling capacity)
32°F entering fluid 3.1 COP
Water-source
water to water
(heating mode)
< 135,000 Btu/h
(cooling capacity)
68°F entering water 3.7 COP ISO 13256-2
50°F entering water 3.1 COP
Ground source
brine to water
(heating mode)
< 135,000 Btu/h
(cooling capacity)
32°F entering fluid 2.5 COP

a. IPLVs and part-load rating conditions are only applicable to equipment with capacity modulation.
b. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
c. Single-phase, air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.


Table 6.8.1D Delete Table 6.8.1D in its entirety and replace with a new Table 6.8.1D to read as follows:

TABLE 6.8.1D ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS AND ROOM AIR-CONDITIONER HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT TYPE SIZE CATEGORY
(INPUT)
SUBCATEGORY OR
RATING
CONDITION
MINIMUM EFFICIENCY TEST PROCEDUREa
Before 10/08/2012 As of 10/08/2012
PTAC (cooling mode)
standard size
All Capacities 95°F db outdoor air 12.5 - (0.213 ×
Cap/1000)c EER
13.8 - (0.300 ×
Cap/1000)c EER
AHRI
310/380
PTAC (cooling mode)
nonstandard sizeb
All Capacities 95°F db outdoor air 10.9 - (0.213 ×
Cap/1000)c EER
10.9 - (0.213 ×
Cap/1000)c EER
PTHP (cooling mode)
standard size
All Capacities 95°F db outdoor air 12.3 - (0.213 ×
Cap/1000)c EER
14.0 - (0.300 ×
Cap/1000)c EER
PTHP (cooling mode)
nonstandard sizeb
All Capacities 95°F db outdoor air 10.8 - (0.213 ×
Cap/1000) EER
10.8 - (0.213 ×
Cap/1000) EER
PTHP (heating mode)
standard size
All Capacities 3.2 - (0.026 ×
Cap/1000) COP
3.7 - (0.052 ×
Cap/1000) COP
PTHP (heating mode)
nonstandard sizeb
All Capacities 2.9 - (0.026 ×
Cap/1000) COP
2.9 - (0.026 ×
Cap/1000) COP
SPVAC
(cooling mode)
< 65,000 Btu/h 95°F db/ 75°F wb
outdoor air
9.0 EER 9.0 EER AHRI 390
≥ 65,000 Btu/h and
< 135,000 Btu/h
95°F db/ 75°F wb
outdoor air
8.9 EER 8.9 EER
≥ 135,000 Btu/h and
< 240,000 Btu/h
95°F db/ 75°F wb
outdoor air
8.6 EER 8.6 EER
SPVHP
(cooling mode)
< 65,000 Btu/h 95°F db/ 75°F wb
outdoor air
9.0 EER 9.0 EER
≥ 65,000 Btu/h and
< 135,000 Btu/h
95°F db/ 75°F wb
outdoor air
8.9 EER 8.9 EER
≥ 135,000 Btu/h and
< 240,000 Btu/h
95°F db/ 75°F wb
outdoor air
8.6 EER 8.6 EER
SPVHP
(heating mode)
< 65,000 Btu/h 47°F db/ 43°F wb
outdoor air
3.0 COP 3.0 COP AHRI 390
≥ 65,000 Btu/h and
< 135,000 Btu/h
47°F db/ 43°F wb
outdoor air
3.0 COP 3.0 COP
≥ 135,000 Btu/h and
< 240,000 Btu/h
47°F db/ 75°F wb
outdoor air
2.9 COP 2.9 COP


(continued)

TABLE 6.8.1D—continued ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS AND ROOM AIR-CONDITIONER HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT TYPE SIZE CATEGORY
(INPUT)
SUBCATEGORY OR
RATING
CONDITION
MINIMUM EFFICIENCY TEST PROCEDUREa
Before 10/08/2012 As of 10/08/2012
Room air conditioners,
with louvered slides
< 6,000 Btu/h 9.7 SEER 11.0 SEER ANSI/AHAM
RAC-1
≥ 6,000 Btu/h and
< 8,000 Btu/h
9.7 EER 11.0 EER
≥ 8,000 Btu/h and
< 14,000 Btu/h
9.8 EER 10.9 EER
≥ 14,000 Btu/h and
< 20,000 Btu/h
9.7 SEER 10.7 SEER
≥ 20,000 Btu/h 8.5 EER 9.4 EER
Room air conditioners,
without louvered slides
< 8,000 Btu/h 9.0 EER 10.0 EER
≥ 8,000 Btu/h and
< 20,000 Btu/h
8.5 EER 9.5 EER
≥ 20,000 Btu/h 8.5 EER 9.4 EER
Room air-conditioner
heat pumps with
louvered sides
< 20,000 Btu/h 9.0 EER 9.8 EER
≥ 20,000 Btu/h 8.5 EER 9.3 EER
Room air-conditioner
heat pumps without
louvered sides
< 14,000 Btu/h 8.5 EER 9.3 EER
≥ 14,000 Btu/h 8.0 EER 8.7 EER
Room air conditioner,
casement only
All capacities 8.7 EER 9.5 EER
Room air conditioner,
casement-slider
All capacities 9.5 EER 10.4 EER

a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY: NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 in. high or less than 42 in. wide and having a cross-sectional area less than 670 in2.
c. Cap means the rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.


Table 6.8.1E Delete Table 6.8.1E in its entirety and replace with a new Table 6.8.1E to read as follows:

TABLE 6.8.1E WARM-AIR FURNACES AND COMBINATION WARM-AIR FURNACES/AIR-CONDITIONING UNITS, WARM-AIR DUCT FURNACES AND UNIT HEATERS

EQUIPMENT
TYPE
SIZE
CATEGORY
(INPUT)
SUBCATEGORY OR
RATING CONDITION
MINIMUM
EFFICIENCY
TEST PROCEDUREa
Warm-air furnace,
gas fired
< 225,000 Btu/h Maximum capacityc 80% AFUE or
80%Etb,d
DOE 10 CFR Part 430 or Section 2.39,
Thermal Efficiency, ANSI Z21.47
≥ 225,000 Btu/h Maximum capacityc 81%Etd Section 2.39, Thermal Efficiency, ANSI
Z21.47
Warm air
furnaces,
oil fired
< 225,000 Btu/h Maximum capacityc 80% AFUE or
80%Etb,d
DOE 10 CFR Part 430
Or Section 42, Combustion, UL 727
≥ 225,000 Btu/h Maximum capacityc 82%Etd Section 42, Combustion, UL 727
Warm-air duct
furnaces,
gas fired
All capacities Maximum capacityc 80%Ece Section 2.10, Efficiency, ANSI Z83.8
Warm-air unit
heaters,
gas fired
All capacities Maximum capacityc 80%Ece,f Section 2.10, Efficiency, ANSI Z83.8
Warm-air unit
heaters,
oil fired
All capacities Maximum capacityc 80%Ece,f Section 40, Combustion, UL 731

a. Section 12 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.
b. Combination units not covered by the NAECA (3-phase power or cooling capacity greater than or equal to 19 kW) may comply with either rating.
c. Compliance of multiple firing rate units shall be at the maximum firing rate.
d. Et= thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.
e. Ec = Combustion efficiency (100% less flue losses). See test procedure for detailed discussion.
f. As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.


Table 6.8.1F Delete Table 6.8.1F in its entirety and replace with a new Table 6.8.1F to read as follows:

TABLE 6.8.1F GAS- AND OIL-FIRED BOILERS, MINIMUM EFFICIENCY REQUIREMENTS

EQUIPMENT
TYPEa
SUBCATEGORY OR
RATING
CONDITION
SIZE
CATEGORY
(INPUT)
MINIMUM
EFFICIENCYb,c
EFFICIENCY as of
3/2/2010 (Date 3yrs
after ASHRAE
Board Approval)
EFFICIEN as of
3/2/2010 (Date
3yrs after
ASHRAE Board
Approval)
TEST
PROCEDURE
Boilers, hot
water
Gas-fired < 300,000 Btu/h 82% AFUE 82% AFUE 82% AFUE 10 CFR Part 430
≥ 300,000 Btu/h
and
≤ 2,500,000 Btu/hd
83% Et 83% Et 83% Et 10CFR Part 431
> 2,500,000 Btu/ha 85% Ec 85% Ec 85% Ec
Oil-firede < 300,000 Btu/h 84% AFUE 84% AFUE 84% AFUE 10 CFR Part 430
≥ 300,000 Btu/h
and
≤ 2,500,000 Btu/hd
84% Et 84% Et 84% Et 10 CFR Part 431
> 2,500,000 Btu/ha 85% Ec 85% Ec 85% Ec
Boilers, steam Gas-fired < 300,000 Btu/h 80% AFUE 80% AFUE 80% AFUE 10 CFR Part 430
Gas-fired- all,
except natural
draft
≥ 300,000 Btu/h
and
≤ 2,500,000 Btu/hd
80% Et 80% Et 80% Et 10CFR Part 431
> 2,500,000 Btu/ha 80% Et 80% Et 80% Et
Gas-fired-
natural draft
≥ 300,000 Btu/h
and
≤ 2,500,000 Btu/hd
79% Et 79% Et 79% Et
> 2,500,000 Btu/ha 79% Et 79% Et 79% Et
Oil-firede < 300,000 Btu/h 82% AFUE 82% AFUE 82% AFUE 10 CFR Part 430
≥ 300,000 Btu/h
and
≤ 2,500,000 Btu/hd
83% Et 83% Et 83% Et 10CFR Part 431
> 2,500,000 Btu/ha 83% Et 83% Et 83% Et

For SI: 1 British thermal unit per hour = 0.2931 W.
a. These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
b. Ec = Combustion efficiency (100% less flue losses). See reference document for detailed information.
c. Et= Thermal efficiency. See reference document for detailed information.
d. Maximum capacity — minimum and maximum ratings as provided for and allowed by the unit's controls.
e. Includes oil-fired (residual).


Chapter 8 - Power

Section 8.2.1 of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

8.2.1 Power distribution systems in all projects shall comply with the requirements of Section 8.1, General; Section 8.4, Prescriptive Provisions; and Section 8.7, Submittals.

The caption of Section 8.4 of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

8.4 Prescriptive provisions

The "Exception" in Section 8.4.1 of ASHRAE 90.1-2010 shall be deemed to be deleted.

8.5 Delete Section 8.5 in its entirety and replace with a new Section 8.5 to read as follows:

8.5 Mandatory Provisions.

8.5.1 Measurement of electrical consumption of tenant spaces in covered buildings constructed on and after January 1, 2016.
The terms meter, submeter, covered building, tenant space and covered tenant space shall be as defined in Section 28-311.2 of the Administrative Code of the city of New York. Each covered tenant space in a building where plans were filed with the department on and after January 1, 2016 shall be equipped with a separate meter or sub-meter to measure the electrical consumption of such space when let or sublet. Where the covered tenant space is a floor with multiple tenancies, each tenancy that is 10,000 gross square feet (929 m2) in area or less shall (i) be equipped with a separate meter or sub-meter, (ii) share a meter or sub-meter with other tenant spaces on the floor, or (iii) share a meter or sub-meter covering the entire floor. As new covered tenant spaces are created, they shall be equipped with meters or sub-meters as provided in this section.

Exception: Covered tenant space for which the electrical consumption within such space is measured by a meter dedicated exclusively to that space.

Chapter 9 - Lighting

9.1.1 Delete Exception b and replace with a new Exception b to read as follows:

b. dwelling units within commercial buildings shall not be required to comply with this section provided that a minimum of 75 percent of the lamps in permanently installed lighting fixtures, other than low-voltage lighting, shall be high-efficacy lamps, or a minimum of 75 percent of the permanently installed lighting fixtures shall contain only high efficacy lamps.

9.4.1 Delete Section 9.4.1 in its entirety and replace with a new Section 9.4.1 to read as follows:

9.4.1 Lighting Control.
Automatic control devices shall be installed in the following spaces to automatically turn off lights within 30 minutes of all occupants leaving the space as follows:

1. Occupant sensors shall be installed in all classrooms (not including shop classrooms, laboratory classrooms, and preschool classrooms), conference/meeting rooms, employee lunch and break rooms, and offices smaller than 200 square feet (18.5 m2) in area. These shall be manual-on switches. Such sensors and controls shall not have an override switch that converts from manual-on to automatic-on functionality. The occupant sensor may have a grace period of up to 30 seconds to turn on the lighting automatically after the sensor has turned off the lighting if occupancy is detected.

2. Occupant sensors shall be installed in restrooms, storage rooms, private offices 200 square feet (18.5 m2) in area or greater, janitorial closets, and other spaces 300 square feet (28 m2) in area or less enclosed by floor-to-ceiling height partitions, except for spaces listed in Item 1. These automatic control devices shall be installed to automatically turn off lights within 30 minutes of all occupants leaving the space, and shall either be manual on or shall be controlled to automatically turn the lighting on to not more than 50 percent power.

Exception: Full automatic-on controls shall be permitted to control lighting in public corridors, stairways, restrooms, primary building entrance areas and lobbies, and areas where manual-on operation would endanger the safety or security of the room or building occupants.

9.4.1.4 Delete the section number and title of Section 9.4.1.4 and replace with the following:

9.2.2.4 Automatic Day lighting Control for Primary Side lighted Areas (Prescriptive).

Chapter 11 — Energy Cost Budget Method

Section 11.1.4 of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

11.1.4 Compliance.
Compliance with Section 11 will be achieved if:

a. all requirements of Sections 5.4, 6.4, 7.4, 9.4 and 10.4 are met. The proposed design need not meet the requirements of Section 9.2.2.4, but the budget building design and energy cost budget shall reflect meeting the requirements of 9.2.2.4;

b. the design energy cost, as calculated in Section 11.3, does not exceed the energy cost budget, as calculated by the simulation program described in Section 11.2; and

c. the energy efficiency level of components specified in the building design meet or exceed the efficiency levels used to calculate the design energy cost.

The entry in the "Budget Building Design" column of Section 6 of Table 11.3.1 ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

Lighting power in the Budget building design shall be determined using the same categorization procedure (building area or space-by-space method) and categories as the proposed design with lighting power set equal to the maximum allowed for the corresponding method and category in either Section 9.5 or 9.6. Power for the fixtures not included in the LPD calculation shall be modeled identically in the proposed building design and budget building design. Lighting controls shall be the minimum required.

Automatic Daylighting Controls for Primary Sidelighted Areas shall be modeled with the following parameters:

• Light Output and Power Fractions shall be as follows based on type of dimming control modeled:

o Stepped Dimming: Light output and power shall decrease in equivalent steps of 100 percent, 66 percent, and 33 percent; or

o Continuous Dimming: Light output and power shall both decrease continuously to 33 percent of peak output and power.

• The daylight control reference point(s) shall be located at the center of the width and at the depth of the primary sidelighted area. If the primary sidelighted area includes apertures with orientations that differ by more than 45 degrees, then the model shall include one daylight control reference point for each orientation. (Note: if the modeling tool is limited by the number of daylight control reference points allowed per zone then the number of zones modeled may need to be increased.)

• The fraction of lighting power affected by the daylight control shall be equal to the primary sidelighted area divided by the total area within a thermal block.

• Illumination setpoint(s) shall be as follows:

Space Type Illumination Setpoint
(FC)
Common Space Types
Atrium 35
Audience/Seating Area - Permanent 35
For Auditorium 35
For Performing Arts Theater 35
For Motion Picture Theater 35
Classroom/Lecture/Training 50
Conference/Meeting/Multipurpose 50
Corridor/Transition 35
Dining Area 35
For Bar Lounge/Leisure Dining 35
For Family Dining 35
Dressing/Fitting Room
For Performing Arts Theater 35
Food Preparation 50
Laboratory
For Classroom 50
For Medical Industrial Research 50
Lobby 35
For Elevator 35
For Performing Arts Theater 35
For Motion Picture Theater 35
Locker Room 35
Lounge/Recreation 50
Office
Enclosed 50
Open Plan 50
Restrooms 35
Sales Area (Retail) Exempt
Stairway 35
Storage 35
Workshop 50
Building Specific Space Types
Automotive
Service/Repair 35
Bank/Office
Banking Activity Area 50
Convention Center
Audience Seating 35
Exhibit Space 35
Courthouse/Police Sta./Penitentiary
Courtroom 50
Confinement Cells 50
Judges Chambers 50
Penitentiary Audience 35
Penitentiary Classroom 50
Penitentiary Dining 35
Dormitory
Living Quarters 35
Fire Stations
Engine Room 50
Sleeping Quarters 35
Gymnasium/Exercise Center 35
Fitness Area 35

Space Type Illumination Setpoint
(FC)
Common Space Types
Gymnasium Audience Seating 35
Playing Area 35
Hospital
Corridor/Transition 50
Emergency 50
Exam/Treatment 50
Laundry-Washing 35
Lounge/Recreation 50
Medical Supply 50
Nursery 50
Nurse Station 50
Operating Room 35
Patient Room 50
Pharmacy 50
Physical Therapy 50
Radiology 35
Recovery 50
Hotel/Highway Lodging
Hotel Dining 35
Hotel Guest Rooms 35
Hotel Lobby 35
Highway Lodging Dining 35
Highway Lodging Guest Rooms 35
Library
Card File and Cataloging 50
Reading Area 50
Stacks 50
Manufacturing
Corridor/Transition 35
Detailed Manufacturing 50
Equipment Room 50
Extra High Bay (> 50 ft Floor to Ceiling
Height)
50
High Bay (25 - 50 ft Floor to Ceiling Height) 50
Low Bay (<25 ft Floor to Ceiling Height) 50
Museum
General Exhibition 35
Restoration 50
Parking Garage
Garage Area 35
Post Office
Sorting Area 50
Religious Buildings
Audience Seating 35
Fellowship Hall 35
Worship Pulpit, Choir 50
Retail
Dressing/Fitting Room Exempt
Sales Area Exempt
Mall Concourse Exempt
Sports Arena
Audience Seating 35
Court Sports Arena-Class 4 35

Space Type Illumination Setpoint
(FC)
Building Specifics Space Types
Court Sports Arena-Class 3 35
Court Sports Arena-Class 2 35
Court Sports Arena-Class 1 35
Ring Sports Arena 35
Transportation
Air/Train/Bus - Baggage Area 35
Airport - Concourse 35
Audience Seating 35
Terminal - Ticket Counter 50
Warehouse
Fine Material Storage 50
Medium/Bulky Material Storage 35


The following item shall be deemed to be added to the "Proposed Building Design (Column A) Design Energy Cost (DEC)" column of Section 12 of Table 11.3.1 of ASHRAE 90.1-2010:

When the voltage drop in the proposed design is greater than the requirements of Section 8.4, then voltage drop shall be included when calculating the design energy cost, and the voltage drop shall be based upon that in the proposed design.

The following items shall be deemed to be added to the "Budget Building Design (Column B) Energy Cost Budget (ECB)" portion of Section 12 of Table 11.3.1 of ASHRAE 90.1-2010:

When voltage drop in the proposed design is greater than the requirements of Section 8.4, then voltage drop shall be included when calculating the energy cost budget, and the voltage drop shall be based upon requirements Section 8.4 as applied to the budget building design.

When the proposed design does not meet the requirements in 8.4.2 for Automated Receptacle Control, then the budget building design shall include Automated Receptacle Control per 8.4.2, and the energy cost budget calculations shall reflect the following reductions in the connected receptacle load for 50 percent of receptacle loads subject to 8.4.2:

Space Type Occupied Hours Unoccupied Hours
Private Offices 22% 100%
Open Office 21% 100%
Computer Classrooms 32% 100%


Exception "b" in the "Proposed Building Design (Column A) Design Energy Cost (DEC)" column of Section 13 ("Modeling Exceptions") of Table 11.3.1 of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

b. the applicable prescriptive requirements of Sections 5.5, 6.5, 7.5, 8.4, 9.2.2.4, and either 9.5 or 9.6 applying to the excluded components are met.

Appendix G — Performance Rating Method

Section G1.2 of Normative Appendix G of ASHRAE 90.1-2010 shall be deemed to be amended by the addition of a new Exception to read as follows:

Exception: The proposed design need not meet the requirements of Section 9.2.2.4, but the Budget building design and Budget building performance shall reflect meeting the requirements of 9.2.2.4.

Section G1.3 of Normative Appendix G of ASHRAE 90.1-2010 shall be deemed to be amended as follows:

Gl.3 Trade-Off Limits.
When the proposed modifications apply to less than the whole building, only parameters related to the systems to be modified shall be allowed to vary. Parameters relating to unmodified existing conditions or to future building components shall be identical for determining both the baseline building performance and the proposed building performance. Future building components shall meet the prescriptive requirements of Sections 5.5, 6.5, 7.5, 9.2, 9.5, and 9.6.

Item "e " in section G1.4 of Normative Appendix G of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

e. A list identifying those aspects of the proposed design that are less stringent than the requirements of 5.5, 6.5, 7.5, 8.4, 9.2.2.4, 9.5, and 9.6 (prescriptive provisions).

The entry in the "Baseline Building Performance" column of Section 6 of Table G3.1 in Normative Appendix G of ASHRAE 90.1-2010 shall be deemed to be amended to read as follows:

Lighting power in the baseline building design shall be determined using the same categorization procedure (building area or space-by-space method) and categories as the proposed design with lighting power set equal to the maximum allowed for the corresponding method and category in Section 9.2. Lighting shall be modeled having the automatic and manual controls required in Section 9.2.2.4 and 9.4. No additional automatic lighting controls shall be modeled in the baseline building design, as the lighting schedules used are understood to reflect the mandatory control requirements in this standard.

Automatic Daylighting Controls for Primary Sidelighted Areas shall be modeled with the following parameters:

• Light Output and Power Fractions shall be as follows based on type of dimming control modeled:

o Stepped Dimming: Light output and power shall decrease in equivalent steps of 100 percent, 66 percent, and 33 percent; or

o Continuous Dimming: Light output and power shall both decrease continuously to 33 percent of peak output and power.

• The daylight control reference point(s) shall be located at the center of the width and at the depth of the primary sidelighted area. If the primary sidelighted area includes apertures with orientations that differ by more than 45 degrees, then the model shall include one daylight control reference point for each orientation. (Note: if the modeling tool is limited by the number of daylight control reference points allowed per zone then number of zones modeled may need to be increased.)

• The fraction of lighting power affected by the daylight control shall be equal to the primary sidelighted area divided by the total area within a thermal block.

• Illumination setpoint(s) shall be as follows:

Space Type Illumination Setpoint (FC)
Common Space Types
Atrium 35
Audience/Seating Area - Permanent 35
For Auditorium 35
For Performing Arts Theater 35
For Motion Picture Theater 35
Classroom/Lecture/Training 50
Conference/Meeting/Multipurpose 50
Corridor/Transition 35
Dining Area 35
For Bar Lounge/Leisure Dining 35
For Family Dining 35
Dressing/Fitting Room
For Performing Arts Theater 35
Food Preparation 50
Laboratory
For Classroom 50
For Medical Industrial Research 50
Lobby 35
For Elevator 35
For Performing Arts Theater 35
For Motion Picture Theater 35
Locker Room 35
Lounge/Recreation 50
Office
Enclosed 50
Open Plan 50

Space Type Illumination Setpoint (FC)
Common Space Types
Restrooms 35
Sales Area (Retail) Exempt
Stairway 35
Storage 35
Workshop 50
Building Specific Space Types
Automotive
Service/Repair 35
Bank/Office
Banking Activity Area 50
Convention Center
Audience Seating 35
Exhibit Space 35
Courthouse/Police Sta./Penitentiary
Courtroom 50
Confinement Cells 50
Judges Chambers 50
Penitentiary Audience 35
Penitentiary Classroom 50
Penitentiary Dining 35
Dormitory
Living Quarters 35
Fire Stations
Engine Room 50
Sleeping Quarters 35
Gymnasium/Exercise Center 35
Fitness Area 35
Gymnasium Audience Seating 35
Playing Area 35
Hospital
Corridor/Transition 50
Emergency 50
Exam/Treatment 50
Laundry-Washing 35
Lounge/Recreation 50
Medical Supply 50
Nursery 50
Nurse Station 50
Operating Room 35
Patient Room 50
Pharmacy 50
Physical Therapy 50
Radiology 35
Recovery 50
Hotel/Highway Lodging
Hotel Dining 35
Hotel Guest Rooms 35
Hotel Lobby 35
Highway Lodging Dining 35
Highway Lodging Guest Rooms 35
Library
Card File and Cataloging 50
Reading Area 50

Space Type Illumination Setpoint (FC)
Building Specific Space Types
Stacks 50
Manufacturing
Corridor/Transition 35
Detailed Manufacturing 50
Equipment Room 50
Extra High Bay (> 50 ft Floor to Ceiling Height) 50
High Bay (25 - 50 ft Floor to Ceiling Height) 50
Low Bay (<25 ft Floor to Ceiling Height) 50
Museum
General Exhibition 35
Restoration 50
Parking Garage
Garage Area 35
Post Office
Sorting Area 50
Religious Buildings
Audience Seating 35
Fellowship Hall 35
Worship Pulpit, Choir 50
Retail
Dressing/Fitting Room Exempt
Sales Area Exempt
Mall Concourse Exempt
Sports Arena
Audience Seating 35
Court Sports Arena-Class 4 35
Court Sports Arena-Class 3 35
Court Sports Arena-Class 2 35
Court Sports Arena-Class 1 35
Ring Sports Arena 35
Transportation
Air/Train/Bus - Baggage Area 35
Airport - Concourse 35
Audience Seating 35
Terminal - Ticket Counter 50
Warehouse
Fine Material Storage 50
Medium/Bulky Material Storage 35


The following item shall be deemed to be added to the "Proposed Building Performance" column of Section 12 of Table G3.1 in Normative Appendix G of ASHRAE 90.1-2010:

If voltage drop in the proposed design is greater than the requirements of Section 8.4, then voltage drop shall be included when calculating the proposed building performance, and the voltage drop shall be based upon that in the proposed design.

The following items shall be deemed to be added to the "Baseline Building Performance" column of Section 12 of Table G3.1 in Normative Appendix G of ASHRAE 90.1-2010:

If voltage drop in the proposed design is greater than the requirements of Section 8.4, then voltage drop shall be included when calculating the baseline building performance, and the voltage drop shall be based upon requirements Section 8.4, as applied to the baseline building.

When the proposed design does not meet the requirements in 8.4.2 for Automated Receptacle Control, then the baseline building performance shall include Automated Receptacle Control per 8.4.2, and the baseline building performance calculations shall reflect the following reductions in the connected receptacle load for 50% of receptacle loads subject to 8.4.2:

Space Type Occupied Hours Unoccupied Hours
Private Offices 22% 100%
Open Office 21% 100%
Computer Classrooms 32% 100%
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING