Heads up:
There are no amended sections in this chapter.
The provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials.
The provisions of Section 803 shall limit the allowable fire performance and smoke development of interior wall and ceiling finish materials based on occupancy classification.
The provisions of Section 804 shall limit the allowable fire performance of interior floor finish materials based on occupancy classification.
Decorative materials and trim shall be restricted by combustibility, fire performance or flame propagation performance criteria, in accordance with Section 806.
For buildings in flood hazard areas as established in Appendix G, interior finishes, trim and decorative materials below the design flood elevation shall be flood-damage-resistant materials.
Combustible materials complying with the requirements of this chapter shall be permitted to be used as finish for walls, ceilings, floors and other interior surfaces of buildings.
Show windows in the exterior walls of the first story above grade plane shall be
permitted to be of wood or of unprotected metal framing.
Foam plastics shall not be used as interior finish except as provided in Section 803.4. Foam plastics shall not be used as interior trim except as provided in Section 806.5 or 2604.2. This section shall apply both to exposed foam plastics and to foam plastics used in conjunction with a textile or vinyl facing or cover.
The following terms are defined in Chapter 2:
Interior wall and ceiling finish materials shall be accepted as compliant for fire performance and smoke development in accordance with Section 803.1.1 or Section 803.1.2, and installed in accordance with the criteria therein.
Interior wall and ceiling finish materials shall be tested and classified in accordance with ASTM E 84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed indexes.
Class A | = | Flame spread index 0-25; smoke developed index 0-450. |
Class B | = | Flame spread index 26-75; smoke developed index 0-450. |
Class C | = | Flame spread index 76-200; smoke developed index 0-450. |
Exception: Materials tested in accordance with Section 803.1.2 need not be classified in accordance with Section 803.1.1.
The interior finish shall comply with the
following:
- During the 40 kW exposure, flames shall not spread to the ceiling.
- The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
- Flashover, as defined in NFPA 286, shall not occur.
- The peak heat release rate throughout the test shall not exceed 800 kW.
- The total smoke released throughout the test shall not exceed 10,764 square feet (1000 m2 ).
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section
803.1.3.1 of this code when tested in the manner intended for use in accordance with the Method
B protocol of NFPA 265 using the product-mounting system, including adhesive.
The interior finish shall comply with the
following:
- During the 40 kW exposure, flames shall not spread to the ceiling.
- The flame shall not spread to the outer extremities of the samples on the 8-foot by 12-foot (2438.4 mm by 3657.6 mm) walls.
- Flashover, as defined in NFPA 265, shall not occur.
- The total smoke released throughout the test shall not exceed 10,764 square feet (1000 m2 ).
Specimens shall be tested and indexed per ASTM E 84 or UL 723, and classified for flame spread
per Section 803.1.4.1 of this code.
Textile wall and ceiling coverings and expanded vinyl wall
and ceiling coverings shall have a Class A flame spread index per Section 803.1.1 of this code;
shall meet the smoke developed index requirements of Section 803.1.1; and shall be protected
by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2
of this code. Test specimen preparation and mounting shall be in accordance with ASTM E
2404.
Materials having a thickness less than 0.036 inch (0.9 mm) applied
directly to the surface of walls or ceilings shall not be required to be tested.
Exposed portions of building elements
complying with the requirements for buildings of Type IV construction in Section 602.4 shall not be
subject to interior finish requirements.
Foam plastics shall not be used as interior finish except as provided in Section
2603.9. This section shall apply both to exposed foam plastics and to foam plastics used in
conjunction with a textile or vinyl facing or cover.
Where used as interior wall finish materials, textile wall coverings,
including materials having woven or nonwoven, napped, tufted, looped or similar surface and carpet
and similar textile materials, shall be tested in the manner intended for use, using the product
mounting system, including adhesive, and shall comply with the requirements of Section 803.1.2,
803.1.3 or 803.1.4.1.
Where used as interior ceiling finish materials, textile ceiling
coverings, including materials having woven or nonwoven, napped, tufted, looped or similar surface
and carpet and similar textile materials, shall be tested in the manner intended for use, using the
product mounting system, including adhesive, and shall comply with the requirements of Section
803.1.2 or 803.1.4.1.
Where used as interior ceiling finish materials,
expanded vinyl ceiling coverings shall be tested in the manner intended for use, using the product
mounting system, including adhesive, and shall comply with the requirements of Section 803.1.2 or
803.1.4.1.
Where high-density
polyethylene or polypropylene is used as an interior finish it shall comply with Section 803.1.2.
Where used as interior wall or interior ceiling finish
materials, site-fabricated stretch systems containing all three components described in the definition
in Chapter 2 of this code shall be tested in the manner intended for use, and shall comply with the
requirements of Section 803.1.1 or 803.1.2 of this code. If the materials are tested in accordance with
ASTM E 84 or UL 723, specimen preparation and mounting shall be in accordance with ASTM E
2573
Interior wall and ceiling finish shall have a flame spread index and smoke-developed index not greater than that specified in Table 803.11 of this code for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 of this code, shall be permitted to be used where a Class A classification, in accordance with ASTM E 84 or UL 723, is required.
GROUP | SPRINKLEREDl | NONSPRINKLERED | ||||
Interior exit stairways, interior exit ramps and exit passagewaysa,b | Corridors and enclosure for exit access stairways and exit access ramps | Rooms and enclosed spacesc | Interior exit stairways, interior exit ramps and exit passagewaysa,b | Corridors and enclosure for exit access stairways and exit access ramps | Rooms and enclosed spacesc | |
A-1 & A-2 | B | B | C | A | Ad | Be |
A-3f, A-4, A-5 | B | B | C | A | Ad | C |
B, E, M, R-1 | B | B | B | A | A | B |
F | B | C | C | A | B | B |
H | B | B | Cg | A | A | B |
I-1 | B | C | C | A | B | B |
I-2 | B | B | Bh, i | A | A | B |
I-3 | A | Aj | C | A | A | B |
I-4 | B | B | Bh, i | A | A | B |
R-2 | B | B | C | A | A | C |
R-3 | C | C | C | C | C | C |
S | B | C | C | A | B | C |
U | No restrictions | No restrictions |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2
- Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 1,000 square feet (92 m2 ) of applied surface area in the grade lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.13.1.
- In other than Group I-3 occupancies in buildings less than three stories above grade plane, Class B interior finish for nonsprinklered buildings and Class C interior finish for sprinklered buildings shall be permitted in interior exit stairways and ramps.
- Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions. Where a fire-resistance rating is required for structural elements, the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered enclosing spaces and the rooms or spaces on both sides shall be considered one. In determining the applicable requirements for rooms and enclosed spaces, the specific occupancy thereof shall be the governing factor regardless of the group classification of the building or structure.
- Lobby areas in Group A-1, A-2 and A-3 occupancies shall not be less than Class B materials.
- Class C interior finish materials shall be permitted in places of assembly with an occupant load of 300 persons or less.
- For places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be permitted.
- Class B material is required where the building exceeds two stories.
- Class C interior finish materials shall be permitted in administrative spaces.
- Class C interior finish materials shall be permitted in rooms with a capacity of four persons or less.
- Class B materials shall be permitted as wainscotting extending not more than 48 inches above the finished floor in corridors and exit access stairways and ramps.
- Finish materials as provided for in other sections of this code.
- Applies when protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Interior finish materials regulated by this chapter shall be applied or
otherwise fastened in such a manner that such materials will not readily become detached where
subjected to room temperatures of 200°F (93.3°C) for not less than 30 minutes.
Where interior finish materials are applied on walls, ceilings or
structural elements required to have a fire-resistance rating or to be of noncombustible construction,
these finish materials shall comply with the provisions of this section.
Where walls and ceilings are
required by any provision in this code to be of fire-resistance-rated or noncombustible
construction, the interior finish material shall be applied directly against such construction or to
furring strips not exceeding 1
3/4 inches (44.5 mm), applied directly against such surfaces.
If the interior finish material is applied to furring strips, the
intervening spaces between such furring strips shall comply with one of the following:
- Be filled with material that is inorganic or noncombustible;
- Be filled with material that meets the requirements of a Class A material in accordance with Section 803.1.1 or 803.1.2; or
- Be fireblocked at a maximum of 8 feet (2438.4 mm) in every direction in accordance with Section 718.
Where walls and ceilings are required to be of fire-resistance-rated or noncombustible construction and walls are set out or ceilings are dropped distances greater than specified in Section 803.13.1, Class A finish materials, in accordance with Section 803.1.1 or 803.1.2, shall be used .
Exceptions:
- Where interior finish materials are protected on both sides by an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
- Where interior finish materials are attached to noncombustible backing or furring strips installed as specified in Section 803.13.1.1.
The hangers and assembly members of such
dropped ceilings that are below the horizontal-fire-resistance-rated floor or
roof assemblies shall be of noncombustible materials. The construction of each set out wall and horizontal fire-resistance-rated floor or roof assembly shall be of fire-resistance-rated construction as required elsewhere in this code.
Exception:
In Type III and V construction, fire-retardant-treated wood shall be permitted
for use as hangers and assembly members of dropped ceilings.
Wall and ceiling finishes
of all classes as permitted in this chapter that are installed directly against the wood decking or
planking of Type IV construction or to wood furring strips applied directly to the wood decking
or planking shall be fireblocked as specified in Section 803.13.1.1.
An interior wall or ceiling finish material that is not more than 1/4 inch (6.4 mm) thick shall be applied directly onto the wall, ceiling or building element without the use of furring strips and shall not be suspended away from the building element to which that finish material is applied.
Exceptions:
- Noncombustible interior finish materials.
- Materials that meet the requirements of Class A materials in accordance with Section 803.1.1 or 803.1.2 where the qualifying tests were made with the material furred out from the noncombustible backing.
- Materials that meet the requirements of Class A materials in accordance with Section 803.1.1 or 803.1.2 where the qualifying tests were made with the material suspended away from the noncombustible backing shall be permitted to be used suspended away from the building element.
Interior floor finish and floor covering materials shall comply with this section.
Interior floor finish and floor covering materials required by Section 804.4.1 of this code to be of Class I or II materials shall be classified in accordance with NFPA 253 or ASTM E 648. The classification referred to herein corresponds to the classifications determined by NFPA 253 or ASTM E 648 as follows: Class I, 0.45 watts/cm2 or greater; Class II, 0.22 watts/cm2 or greater.
Interior floor finish and floor covering materials shall be tested by an approved agency in accordance with NFPA 253 or ASTM E 648 and identified by a hang tag or other suitable method so as to identify the manufacturer or supplier and style, and shall indicate the interior floor finish or floor covering classification in accordance with Section 804.2 of this code. Carpet-type floor coverings shall be tested as proposed for use, including underlayment. Test reports confirming the information provided in the manufacturer's product identification shall be furnished to the department upon request.
In buildings and spaces classified in Occupancy Group H and in all exits and exit passageways of any occupancy group, floor finishes shall be of noncombustible materials.
Exception: Interior floor finish may be of combustible materials in the following spaces. Carpet-type materials must be able to withstand a minimum critical radiant flux as specified in Section 804.4.1.
Exception: Interior floor finish may be of combustible materials in the following spaces. Carpet-type materials must be able to withstand a minimum critical radiant flux as specified in Section 804.4.1.
- Buildings of Type VB Construction.
- Interior stairs in buildings of Type III, IV and V construction in Occupancy Group B, F, M or S-2, when the buildings are two stories in height or less.
- Interior stairs in buildings of Type III, IV and V construction in Occupancy Groups R-2 and R-3 when the buildings are three stories in height or less.
- Interior stairs in buildings of Type III, IV and V construction in Occupancy Group R-2 when occupied by three families or less.
Interior floor finishes shall not be less than Class I in Occupancy Groups I-2 and I-3 and not less than Class II in Occupancy Groups A, B, E, H, I-4, M, R-1, R-2 and S. In all other occupancy groups, the interior floor finish shall comply with the DOC FF-1 "pill test" (CPSC 16 CFR, Part 1630).
Carpet and carpet cushion as defined in Section 17-1401 of the Administrative Code shall comply with the limits on volatile organic compound emissions set forth in Chapter 14 of Title 17 of such code.
Combustible materials installed on or embedded in floors of buildings of Type I or II construction shall comply with Sections 805.1.1 through 805.1.4.
Exceptions:
- Stages and platforms constructed in accordance with Sections 410.3 and 410.4, respectively.
- Bleachers, grandstands and folding and telescopic seating within assembly spaces constructed in accordance with Section 1029.1.1.
Floor sleepers, bucks and nailing blocks shall not be constructed of combustible materials, unless the space between the fire-resistance-rated floor assembly and the flooring is either solidly filled with noncombustible materials or fireblocked in accordance with Section 718, and provided that such open spaces shall not extend under or through permanent partitions or walls.
Wood finish flooring is permitted to be attached directly to the embedded or fireblocked wood sleepers and shall be permitted where cemented directly to the top surface of approved fire-resistance-rated floor assemblies or directly to a wood subfloor attached to sleepers as provided for in Section 805.1.1.
Combustible insulating boards not more than 1/2-inch (12.7 mm) thick and covered with finish flooring are permitted, where attached directly to a noncombustible floor assembly or to wood subflooring attached to sleepers as provided for in Section 805.1.1.
Carpet-type floor coverings are permitted where cemented directly to the top surface of approved fire-resistance-rated construction or directly to a wood subfloor attached to sleepers as provided for in Section 805.1.1.
All decorations shall comply with the requirements of the New York City Fire Code.
Foam plastic used as trim shall comply with Section 2604.2 and shall
not be permitted in occupancies other than Group R-3, within individual dwelling units
of Group R-1 and R-2 occupancies, or unless approved in accordance with Section 2603.9.
Material, other than foam plastic used as interior trim, shall have a minimum Class C flame spread index and maximum smoke-developed index when tested in accordance with ASTM E 84 or UL 723 as described in Section 803.1.1. Combustible trim, excluding handrails and guardrails, shall not exceed 10 percent of the specific wall or ceiling area in which it is attached.
Interior floor-wall base that is 6 inches (152.4 mm) or
less in height shall be tested in accordance with Section 804.2 and shall be not less than Class II.
Where a Class I floor finish is required, the floor-wall base shall be Class I.
Thermal and acoustical insulation shall comply with Section 720.
Acoustical materials complying with the interior finish requirements of Section 803 shall be installed in accordance with the manufacturer's recommendations and applicable provisions for applying interior finish.
Acoustical ceilings that are to be suspended below floor or roof construction by means of a framing system shall consist of supporting hangers of minimum 1/4-inch diameter (6.4 mm) steel rods, carrying channels of minimum 11/2-inch deep (38.1 mm) cold-rolled steel weighing 0.440 pounds per linear foot (0.681 kg/m), and a supporting grid complying with Appendix R. Use of wire hangers shall not be permitted. Direct hung suspension systems shall not be permitted.
Exception: Acoustical ceiling systems in Groups R-2 and R-3 occupancies shall be permitted to be installed in accordance with ASTM C 635 and ASTM C 636 without modifications.
Exception: Acoustical ceiling systems in Groups R-2 and R-3 occupancies shall be permitted to be installed in accordance with ASTM C 635 and ASTM C 636 without modifications.
Acoustical ceiling systems that are part of fire-resistance-rated construction shall be installed in the same manner used in the assembly tested and shall comply with the provisions of Chapter 7.