Chapter 1 Administration

Chapter 2 Definitions

Chapter 3 Use and Occupancy Classification

Chapter 4 Special Detailed Requirements Based on Use and Occupancy

Chapter 5 General Building Heights and Areas; Separation of Occupancies

Chapter 6 Types of Construction

Chapter 7 Fire-Resistance-Rated Construction

Chapter 8 Interior Finishes

Chapter 9 Fire Protection Systems

Chapter 10 Means of Egress

Chapter 11 Accessibility

Chapter 12 Interior Environment

Chapter 13 Energy Efficiency

Chapter 14 Exterior Walls

Chapter 15 Roof Assemblies and Rooftop Structures

Chapter 16 Structural Design

Chapter 17 Structural Tests and Special Inspections

Chapter 18 Soils and Foundations

Chapter 19 Concrete

Chapter 20 Aluminum

Chapter 21 Masonry

Chapter 22 Steel

Chapter 23 Wood

Chapter 24 Glass and Glazing

Chapter 25 Gypsum Board and Plaster

Chapter 26 Plastic

Chapter 27 Electrical

Chapter 28 Mechanical Systems

Chapter 29 Plumbing Systems

Chapter 30 Elevators and Conveying Systems

Chapter 31 Special Construction

Chapter 32 Encroachments Into the Public Right-Of-Way

Chapter 33 Safeguards During Construction or Demolition

Chapter 34 Reserved

Chapter 35 Referenced Standards [PDF]

Appendix A Reserved

Appendix B Reserved

Appendix C Reserved

Appendix D Fire Districts

Appendix E Supplementary Accessibility Requirements

Appendix F Rodent Proofing

Appendix G Flood-Resistant Construction

Appendix H Outdoor Signs

Appendix I Reserved

Appendix J Reserved

Appendix K Modified Industry Standards for Elevators and Conveying Systems

Appendix L Reserved

Appendix M Supplementary Requirements for One- And Two-Family Dwellings

Appendix O Reserved

Appendix N Assistive Listening Systems Performance Standards

Appendix P R-2 Occupancy Toilet and Bathing Facilities Requirements

Appendix Q Modified National Standards for Automatic Sprinkler, Standpipe, and Fire Alarm Systems

Appendix R Acoustical Tile and Lay-In Panel Ceiling Suspension Systems

This chapter shall govern the materials, design, construction and quality of masonry.
Masonry shall comply with the provisions of one of the following design methods in this chapter as well as the requirements of Sections 2101 through 2104. Masonry designed by the working stress design provisions of Section 2101.2.1, the strength design provisions of Section 2101.2.2 or the prestressed masonry provisions of Section 2101.2.3 shall comply with Section 2105 for Quality Assurance.
Masonry designed by the working stress design method shall comply with the provisions of Sections 2106 and 2107.
Masonry designed by the strength design method shall comply with the provisions of Sections 2106 and 2108.
Prestressed masonry shall be designed in accordance with Chapters 1 and 4 of ACI 530/ASCE 5/TMS 402 and Section 2106. Special inspection during construction shall be provided as set forth in Section 1704.5.
Masonry designed by the empirical design method shall comply with the provisions of Sections 2106 and 2109 or Chapter 5 of ACI 530/ASCE 5/TMS 402.
Glass masonry shall comply with the provisions of Section 2110 or with the requirements of Chapter 7 of ACI 530/ASCE 5/TMS 402.
Masonry veneer shall comply with the provisions of Chapter 14.
The construction documents shall show all of the items required by this code including the following:
  1. Specified size, grade, type and location of reinforcement, anchors and wall ties.
  2. Reinforcing bars to be welded and welding procedure.
  3. Size and location of structural elements.
  4. Provisions for dimensional changes resulting from elastic deformation, creep, shrinkage, temperature and moisture.
The construction documents shall describe in sufficient detail the location, size and construction of masonry fireplaces. The thickness and characteristics of materials and the clearances from walls, partitions and ceilings shall be clearly indicated. The masonry fireplace shall comply with the provisions of Section 2111.0.
The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.
  ANCHOR. Metal rod, wire or strap that secures masonry to its structural support.
  ARCHITECTURAL TERRA COTTA. Plain or ornamental hard-burned modified clay units, larger in size than brick, with glazed or unglazed ceramic finish.
  AREA.
  Bedded. The area of the surface of a masonry unit that is in contact with mortar in the plane of the joint.
  Gross cross-sectional. The area delineated by the out-to-out specified dimensions of masonry in the plane under consideration.
  Net cross-sectional. The area of masonry units, grout and mortar crossed by the plane under consideration based on out-to-out specified dimensions.
  BED JOINT. The horizontal layer of mortar on which a masonry unit is laid.
  BOND BEAM. A horizontal grouted element within masonry in which reinforcement is embedded.
  BOND REINFORCING. The adhesion between steel reinforcement and mortar or grout.
  BRICK.
  Calcium silicate (sand lime brick). A masonry unit made of sand and lime.
  Clay or shale. A masonry unit made of clay or shale, usually formed into a rectangular prism while in the plastic state and burned or fired in a kiln.
  Concrete. A masonry unit having the approximate shape of a rectangular prism and composed of inert aggregate particles embedded in a hardened cementitious matrix.
  BUTTRESS. A projecting part of a masonry wall built integrally therewith to provide lateral stability.
  CAST STONE. A building stone manufactured from portland cement concrete precast and used as a trim, veneer or facing on or in buildings or structures.
  CELL. A void space having a gross cross-sectional area greater than 11/2 square inches (967 mm2).
  CHIMNEY. A primarily vertical enclosure containing one or more flues used to remove hot gases from burning fuel, refuse, or from industrial processes to the outside atmosphere.
  High-heat appliance type. An approved chimney for removing the products of combustion from fuel-burning, high-heat appliances producing combustion gases in excess of 2,000°F (1093°C) measured at the appliance flue outlet (see Section 2113.11.3).
  Low-heat appliance type. An approved chimney for removing the products of combustion from fuel-burning, low-heat appliances producing combustion gases not in excess of 1,000°F (538°C) under normal operating conditions, but capable of producing combustion gases of 1,400°F (760°C) during intermittent forces firing for periods up to 1 hour. Temperatures shall be measured at the appliance flue outlet.
  Masonry type. A field-constructed chimney of solid masonry units or stones.
  Medium-heat appliance type. An approved chimney for removing the products of combustion from fuel-burning, medium-heat appliances producing combustion gases between 1000°F (538°C) and 2,000°F (1093°C) measured at the appliance flue outlet (see Section 2113.11.2).
  CLEANOUT. An opening to the bottom of a grout space of sufficient size and spacing to allow the removal of debris.
  COLLAR JOINT. Vertical longitudinal joint between wythes of masonry or between masonry and backup construction that is permitted to be filled with mortar or grout.
  COLUMN, MASONRY. An isolated vertical member whose horizontal dimension measured at right angles to its thickness does not exceed three times its thickness and whose height is at least four times its thickness.
  COMPOSITE ACTION. Transfer of stress between components of a member designed so that in resisting loads, the combined components act together as a single member.
  COMPOSITE MASONRY. Multiwythe masonry members acting with composite action.
  COMPRESSIVE STRENGTH OF MASONRY. Maximum compressive force resisted per unit of net cross-sectional area of masonry, determined by the testing of masonry prisms or a function of individual masonry units, mortar and grout.
  CONNECTOR. A mechanical device for securing two or more pieces, parts or members together, including anchors, wall ties and fasteners.
  COVER. Distance between surface of reinforcing bar and edge of member.
  DIAPHRAGM. A roof or floor system designed to transmit lateral forces to shear walls or other lateral-load-resisting elements.
  Actual. The measured dimension of a masonry unit or element.
  Nominal. A dimension equal to a specified dimension plus an allowance for the joints with which the units are to be laid. Thickness is given first, followed by height and then length.
  Specified. The dimensions specified for the manufacture or construction of masonry, masonry units, joints or any other component of a structure.
  EFFECTIVE HEIGHT. For braced members, the effective height is the clear height between lateral supports and is used for calculating the slenderness ratio. The effective height for unbraced members is calculated in accordance with engineering mechanics.
  FIREPLACE. A hearth and fire chamber or similar prepared place in which a fire may be made and which is built in conjunction with a chimney.
  FIREPLACE THROAT. The opening between the top of the firebox and the smoke chamber.
  FLUE. A passageway within a chimney or vent through which gaseous combustion products pass.
  FLUE, APPLIANCE. The passage(s) within an appliance through which combustion products pass from the combustion chamber of the appliance to the draft hood inlet opening on an appliance equipped with a draft hood or to the outlet of the appliance on an appliance not equipped with a draft hood.
  FLUE GASES. Products of combustion plus excess air in appliance flues or heat exchangers.
  FLUE LINER (LINING). A system or material used to form the inside surface of a flue in a chimney or vent, for the purpose of protecting the surrounding structure from the effects of combustion products and for conveying combustion products without leakage into the atmosphere.
  GROUT. Flowable cementitious material comprising cement mixed with fine or coarse aggregates and having a compressive strength not less than 2,000 pounds per square inch (13 790 kPa) at 28 days, and a slump of 8 inches to 11 inches (203 mm to 279 mm).
  Grouted hollow-unit masonry. That form of grouted masonry construction in which certain designated cells of hollow units are continuously filled with grout.
  Grouted multi-wythe masonry. That form of grouted masonry construction in which the space between the wythes is solidly or periodically filled with grout.
  HEAD JOINT. Vertical mortar joint placed between masonry units within the wythe at the time the masonry units are laid.
  HEADER (Bonder). A masonry unit that connects two or more adjacent wythes of masonry.
  HEIGHT, WALLS. The vertical distance from the foundation wall or other immediate support of such wall to the top of the wall.
  MASONRY. A built-up construction or combination of building units or materials of clay, shale, concrete, glass, gypsum, stone or other approved units bonded together with or without mortar or grout or other accepted method of joining.
  Ashlar masonry. Masonry composed of various sized rectangular units having sawed, dressed or squared bed surfaces, properly bonded and laid in mortar.
  Coursed ashlar. Ashlar masonry laid in courses of stone of equal height for each course, although different courses shall be permitted to be of varying height.
  Glass unit masonry. Nonload-bearing masonry composed of glass units bonded by mortar.
  Plain masonry. Masonry in which the tensile resistance of the masonry is taken into consideration and the effects of stresses in reinforcement are neglected.
  Random ashlar. Ashlar masonry laid in courses of stone set without continuous joints and laid up without drawn patterns. When composed of material cut into modular heights, discontinuous but aligned horizontal joints are discernible.
  Reinforced masonry. Masonry construction in which reinforcement acting in conjunction with the masonry is used to resist forces.
  Solid masonry. Masonry consisting of solid masonry units laid contiguously with the joints between the units filled with mortar.
  MASONRY UNIT. Brick, tile, stone, glass block or concrete block conforming to the requirements specified in Section 2103.
  Clay. A building unit larger in size than a brick, composed of burned clay, shale, fire clay or mixtures thereof.
  Concrete. A building unit or block larger in size than 12 inches by 4 inches by 4 inches (305 mm by 102 mm by 102 mm) made of cement and suitable aggregates.
  Hollow. A masonry unit whose net cross-sectional area in any plane parallel to the load-bearing surface is less than 75 percent of its gross cross-sectional area measured in the same plane.
  Solid. A masonry unit whose net cross-sectional area in every plane parallel to the load-bearing surface is 75 percent or more of its gross cross-sectional area measured in the same plane.
  MEAN DAILY TEMPERATURE. The average daily temperature of temperature extremes predicted by a local weather bureau for the next 24 hours.
  MORTAR. A plastic mixture of approved cementitious materials, fine aggregates and water used to bond masonry or other structural units.
  MORTAR, SURFACE-BONDING. A mixture to bond concrete masonry units that contains hydraulic cement, glass fiber reinforcement with or without inorganic fillers or organic modifiers and water.
  PLASTIC HINGE. The zone in a structural member in which the yield moment is anticipated to be exceeded under loading combinations that include earthquakes.
  PRESTRESSED MASONRY. Masonry in which internal stresses have been introduced to counteract potential tensile stresses in masonry resulting from applied loads.
  PRISM. An assemblage of masonry units and mortar with or without grout used as a test specimen for determining properties of the masonry.
  RUBBLE MASONRY. Masonry composed of roughly shaped stones.
  Coursed rubble. Masonry composed of roughly shaped stones fitting approximately on level beds and well bonded.
  Random rubble. Masonry composed of roughly shaped stones laid without regularity of coursing but well–bonded and fitted together to form well-divided joints.
  Rough or ordinary rubble. Masonry composed of unsquared field stones laid without regularity of coursing but well-bonded.
  RUNNING BOND. The placement of masonry units such that head joints in successive courses are horizontally offset at least one-quarter the unit length.
  Detailed plain masonry shear wall. A masonry shear wall designed to resist lateral forces neglecting stresses in reinforcement, and designed in accordance with Section 2106.1.1.
  Intermediate pre-stressed masonry shear wall. A pre-stressed masonry shear wall designed to resist lateral forces considering stresses in reinforcement, and designed in accordance with Section 2106.1.1.2.
  Intermediate reinforced masonry shear wall. A masonry shear wall designed to resist lateral forces considering stresses in reinforcement, and designed in accordance with Section 2106.1.1.
  Ordinary plain masonry shear wall. A masonry shear wall designed to resist lateral forces neglecting stresses in reinforcement, and designed in accordance with Section 2106.1.1.
  Ordinary plain pre-stressed masonry shear wall. A pre-stressed masonry shear wall designed to resist lateral forces considering stresses in reinforcement, and designed in accordance with Section 2106.1.1.1.
  Ordinary reinforced masonry shear wall. A masonry shear wall designed to resist lateral forces considering stresses in reinforcement, and designed in accordance with Section 2106.1.1.
  Special pre-stressed masonry shear wall. A pre-stressed masonry shear wall designed to resist lateral forces considering stresses in reinforcement and designed in accordance with Section 2106.1.1.3 except that only grouted, laterally restrained tendons are used.
  Special reinforced masonry shear wall. A masonry shear wall designed to resist lateral forces considering stresses in reinforcement, and designed in accordance with Section 2106.1.1.
  SHELL. The outer portion of a hollow masonry unit as placed in masonry.
  SPECIFIED. Required by construction documents.
  SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f'm. Minimum compressive strength, expressed as force per unit of net cross-sectional area, required of the masonry used in construction by the construction documents, and upon which the project design is based. Whenever the quantity f'm is under the radical sign, the square root of numerical value only is intended and the result has units of pounds per square inch (psi) (Mpa).
  STACK BOND. The placement of masonry units in a bond pattern is such that head joints in successive courses are vertically aligned. For the purpose of this code, requirements for stack bond shall apply to masonry laid in other than running bond.
  STONE MASONRY. Masonry composed of field, quarried or cast stone units bonded by mortar.
  Ashlar stone masonry. Stone masonry composed of rectangular units having sawed, dressed or squared bed surfaces and bonded by mortar.
  Rubble stone masonry. Stone masonry composed of irregular-shaped units bonded by mortar.
  STRENGTH.
  Design strength. Nominal strength multiplied by a strength reduction factor.
  Nominal strength. Strength of a member or cross section calculated in accordance with these provisions before application of any strength-reduction factors.
  Required strength. Strength of a member or cross section required to resist factored loads.
  TIE, LATERAL. Loop of reinforcing bar or wire enclosing longitudinal reinforcement.
  TIE, WALL. A connector that connects wythes of masonry walls together.
  TILE. A ceramic surface unit, usually relatively thin in relation to facial area, made from clay or a mixture of clay or other ceramic materials, called the body of the tile, having either a "glazed" or "unglazed" face and fired above red heat in the course of manufacture to a temperature sufficiently high enough to produce specific physical properties and characteristics.
  TILE, STRUCTURAL CLAY. A hollow masonry unit composed of burned clay, shale, fire clay or mixture thereof, and having parallel cells.
  WALL. A vertical element with a horizontal length-to-thickness ratio greater than three, used to enclose space.
  Cavity wall. A wall built of masonry units or of concrete, or a combination of these materials, arranged to provide an airspace within the wall, and in which the inner and outer parts of the wall are tied together with metal ties.
  Composite wall. A wall built of a combination of two or more masonry units bonded together, one forming the backup and the other forming the facing elements.
  Dry-stacked, surface-bonded walls. A wall built of concrete masonry units where the units are stacked dry, without mortar on the bed or head joints, and where both sides of the wall are coated with a surface-bonding mortar.
  Masonry-bonded hollow wall. A wall built of masonry units so arranged as to provide an airspace within the wall, and in which the facing and backing of the wall are bonded together with masonry units.
  Parapet wall. The part of any wall entirely above the roof line.
  WEB. An interior solid portion of a hollow masonry unit as placed in masonry.
  WYTHE. Each continuous, vertical section of a wall, one masonry unit in thickness.

An

=

Net cross-sectional area of masonry, square inches (mm2).

b

=

Effective width of rectangular member or width of flange for T and I sections, inches (mm).

db

=

Diameter of reinforcement, inches (mm).

fr

=

Modulus of rupture, psi (MPa).

fy

=

Specified yield stress of the reinforcement or the anchor bolt, psi (MPa).

f'm

=

Specified compressive strength of masonry at age of 28 days, psi (MPa).

K

=

The lesser of the masonry cover, clear spacing between adjacent reinforcement, or five times db, inches (mm).

Ls

=

Distance between supports, inches (mm).

Lw

=

Length of wall, inches (mm).

ld

=

Required development length of reinforcement, inches (mm).

lde

=

Embedment length of reinforcement, inches (mm).

Pw

=

Weight of wall tributary to section under consideration, pounds (N).

T

=

Specified wall thickness dimension or the least lateral dimension of a column, inches (mm).

Vn

=

Nominal shear strength, pounds (N).

Vu

=

Required shear strength due to factored loads, pounds (N).

W

=

Wind load, or related internal moments in forces.

γ

=

Reinforcement size factor.

ρn

=

Ratio of distributed shear reinforcement on plane perpendicular to plane of Amv.

ρmax

=

Maximum reinforcement ratio.

Φ

=

Strength reduction factor.
Concrete masonry units shall conform to the following standards: ASTM C 55 for concrete brick; ASTM C 90 for load-bearing concrete masonry units; ASTM C 129 for non-load bearing concrete masonry units or ASTM C 744 for prefaced concrete and calcium silicate masonry units.
Clay or shale masonry units shall conform to the following standards: ASTM C 34 for structural clay load-bearing wall tile; ASTM C 56 for structural clay nonload-bearing wall tile; ASTM C 62 for building brick (solid masonry units made from clay or shale); ASTM C 1088 for solid units of thin veneer brick; ASTM C 126 for ceramic-glazed structural clay facing tile, facing brick and solid masonry units; ASTM C 212 for structural clay facing tile; ASTM C 216 for facing brick (solid masonry units made from clay or shale); ASTM C 652 for hollow brick (hollow masonry units made from clay or shale) and ASTM C 73 for calcium silicate face brick.
  Exception: Structural clay tile for nonstructural use in fireproofing of structural members and in wall furring shall not be required to meet the compressive strength specifications. The fire-resistance rating shall be determined in accordance with ASTM E 119 and shall comply with the requirements of Table 602.
Stone masonry units shall conform to the following standards: ASTM C 503 for marble building stone (exterior): ASTM C 568 for limestone building stone; ASTM C 615 for granite building stone; ASTM C 616 for sandstone building stone or ASTM C 629 for slate building stone.
Ceramic tile shall be as defined in, and shall conform to the requirements of, ANSI A137.1.
Hollow glass units shall be partially evacuated and have a minimum average glass face thickness of 316 inch (4.8 mm). Solid glass-block units shall be provided when required. The surfaces of units intended to be in contact with mortar shall be treated with a polyvinyl butyral coating or latex-based paint. Reclaimed units shall not be used.
Second-hand masonry units shall not be reused unless they conform to the requirements of new units. The units shall be of whole, sound materials and free from cracks and other defects that will interfere with proper laying or use. Old mortar shall be cleaned from the unit before reuse.
  Exception: second-hand masonry units need not conform to the requirements for new units when their reuse is to comply with historic restoration standards or requirements of the New York City Landmarks Preservation Commission or the New York State Historic Preservation Office.
Mortar for use in masonry construction shall conform to ASTM C 270 and shall conform to the proportion specifications of Table 2103.7(1) or the property specifications of Table 2103.7(2). Type S or N mortar shall be used for glass unit masonry. The amount of water used in mortar for glass unit masonry shall be adjusted to account for the lack of absorption. Re-tempering of mortar for glass unit masonry shall not be permitted after initial set. Unused mortar shall be discarded within 21/2 hours after initial mixing except that unused mortar for glass unit masonry shall be discarded within 11/2 hours after initial mixing.

TABLE 2103.7(1)
MORTAR PROPORTIONS






MORTAR






TYPE
PROPORTIONS BY VOLUME (cementitious materials)






HYDRATED LIMEe
OR LIME PUTTY





AGGREGATE
MEASURED IN A
DAMP, LOOSE
CONDITION
Portland cementa
or blended
cementb
Masonry cementc Mortar cementd
M S N M S N
Cement-lime M
S
N
O
1
1
1
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
¼
over ¼ to ½
over ½ to 1½
over 1½ to ½






Not less than 2¼ and not more than 3 times the sum of the separate volumes of cementitious materials
Mortar cement M
M
s
s
N
O
1
-
½
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
-
-
-
-
-
-
-
1
-
-
1
-
1
-
1
1
-
-
-
-
-
-
Masonry cement M
M
s
s
N
O
1
-
½
-
-
-
-
1
-
-
-
-
-
-
-
1
-
-
1
-
1
-
1
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
  1. Portland cement conforming to the requirements of ASTM C 150.
  2. Blended cement conforming to the requirements of ASTM C 595.
  3. Masonry cement conforming to the requirements of ASTM C 91.
  4. Mortar cement conforming to the requirements of ASTM C 1329.
  5. Hydrated lime conforming to the requirements of ASTM C 207.

TABLE 2103.7(2)
MORTAR PROPERTIESa


MORTAR


TYPE
AVERAGE COMPRESSIVEb
STRENGTH AT 28 DAYS
minimum (psi)
WATER RETENTIO
Nminimum (%)
AIR CONTENT
maximum (%)
Cement-lime M
s
N
O
2,500
1,800
750
350
75
75
75
75
12
12
14c
14c
Mortar cement M
s
N
O
2,500
1,800
750
350
75
75
75
75
12
12
14c
14c
Masonry cement M
s
N
O
2,500
1.800
750
350
75
75
75
75
18
18
20d
20d
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895kPa.
  1. This aggregate ratio (measured in damp, loose condition) shall notbe less than 2¼ and notmore than 3 times the sum of the separate volumes of cementitious materials.
  2. Average of three 2-inch cubes of laboratory-prepared mortar, in accordance with ASTM C 270.
  3. When structural reinforcement is incorporated in cement-lime or mortar cement mortars, the maximum air content shall not exceed 12 percent.
  4. When structural reinforcement is incorporated in masonry cement mortar, the maximum air content shall not exceed 18 percent.
Surface-bonding mortar shall comply with ASTM C 887. Surface bonding of concrete masonry units shall comply with ASTM C 946.
Portland cement mortars for installing ceramic wall and floor tile shall comply with ANSI A108.1A and ANSI A108.1B and be of the compositions indicated in Table 2103.9.

TABLE 2103.9
CERAMIC TILE MORTAR COMPOSITIONS
LOCATION MORTAR COMPOSITION
Walls Scratchcoat 1 cement; ⅕ hydrated lime;
4 dry or 5 damp sand
Setting bed and leveling coat 1 cement; ½ hydrated lime;
5 damp sand to 1 cement 1 hydrated lime, 7 damp sand
Floors Setting bed 1 cement; 110 hydrated lime;
5 dry or 6 damp sand; or 1 cement; 5 dry or 6 damp sand
Ceilings Scratchcoat and sand bed 1 cement; ½ hydrated lime;
2½ dry sand or 3 damp sand
Premixed prepared portland cement mortars, which require only the addition of water and are used in the installation of ceramic tile, shall comply with ANSI A118.1. The shear bond strength for tile set in such mortar shall be as required in accordance with ANSI A118.1. Tile set in dry-set portland cement mortar shall be installed in accordance with ANSI A108.5.
Premixed prepared portland cement mortars, which require only the addition of water and comply with ANSI A118.2, shall be used in the installation of electrically conductive ceramic tile. Tile set in electrically conductive dry-set mortar shall be installed in accordance with ANSI A108.7.
Latex-modified portland cement thin-set mortars in which latex is added to dry-set mortar as a replacement for all or part of the gauging water that are used for the installation of ceramic tile shall comply with ANSI A118.4. Tile set in latex- modified portland cement shall be installed in accordance with ANSI A108.5.
Ceramic tile set and grouted with chemical-resistant epoxy shall comply with ANSI A118.3. Tile set and grouted with epoxy shall be installed in accordance with ANSI A108.6.
Chemical-resistant furan mortar and grout that are used to install ceramic tile shall comply with ANSI A118.5. Tile set and grouted with furan shall be installed in accordance with ANSI A108.8.
Modified epoxy-emulsion mortar and grout that are used to install ceramic tile shall comply with ANSI A118.8. Tile set and grouted with modified epoxy-emulsion mortar and grout shall be installed in accordance with ANSI A108.9.
Water-resistant organic adhesives used for the installation of ceramic tile shall comply with ANSI A136.1. The shear bond strength after water immersion shall not be less than 40 psi (275 kPa) for Type I adhesive, and not less than 20 psi (138 kPa) for Type II adhesive, when tested in accordance with ANSI A136.1. Tile set in organic adhesives shall be installed in accordance with ANSI A108.4.
Portland cement grouts used for the installation of ceramic tile shall comply with ANSI A118.6. Portland cement grouts for tile work shall be installed in accordance with ANSI A108.10.
Grout shall conform to Table 2103.10 or to ASTM C 476. When grout conforms to ASTM C 476, the grout shall be specified by proportion requirements or property requirements.

TABLE 2103.10
GROUT PROPORTIONS BY VOLUME FOR
MASONRY CONSTRUCTION




TYPE
PARTS BY VOLUME OF PORTLAND CEMENT OR BLENDED CEMENT PARTS BY VOLUME OF HYDRATED LIME OR LIME PUTTY AGGREGATE, MEASURED IN A
DAMP, LOOSE CONDITION

Fine

Coarse
Fine grout 1 0-1/10 2¼-3 times the sum of the volumes of the cementitious materials
-
Coarse grout 1 0-1/10 2¼-3 times the sum of the volumes of the cementitious materials 1-2,times,the,sum of the volumes of the cementitious materials
Metal reinforcement and accessories shall conform to Sections 2103.11.1 through 2103.11.7.
Deformed reinforcing bars shall conform to one of the following standards: ASTM A 615 for deformed and plain billet-steel bars for concrete reinforcement; ASTM A 706 for low-alloy steel deformed bars for concrete reinforcement; ASTM A 767 for zinc-coated reinforcing steel bars; ASTM A 775 for epoxy-coated reinforcing steel bars and ASTM A 996 for rail steel and axle steel deformed bars for concrete reinforcement.
Joint reinforcement shall comply with ASTM A 951. The maximum spacing of crosswires in ladder-type joint reinforcement and of point of connection of cross wires to longitudinal wires of truss-type reinforcement shall be 16 inches (406 mm).
Deformed reinforcing wire shall conform to ASTM A 496.
Wire fabric shall conform to ASTM A 185 for plain steel-welded wire fabric for concrete reinforcement or ASTM A 496 for welded deformed steel wire fabric for concrete reinforcement.
Anchors, ties and accessories shall conform to the following standards: ASTM A 36 for structural steel; ASTM A 82 for plain steel wire for concrete reinforcement; ASTM A 185 for plain steel-welded wire fabric for concrete reinforcement; ASTM A 167, Type 304, for stainless and heat-resisting chromium- nickel steel plate, sheet and strip and ASTM A 366 for cold-rolled carbon steel sheet, commercial quality.
Prestressing tendons shall conform to one of the following standards:
  1. Wire. . . . . . . . . ........... . .ASTM A 421
  2. Low-relaxation wire. . . . .ASTM A 421
  3. Strand . . . . . . . . ......... . . .ASTM A 416
  4. Low-relaxation strand. . . . ASTM A 416
  5. Bar . . . . . . . . ............... . . .ASTM A 722
  Exceptions:
  1. Wire, strands and bars not specifically listed in ASTM A 421, ASTM A 416 or ASTM A 722 are permitted, provided they conform to the minimum requirements in ASTM A 421, ASTM A 416, or ASTM A 722 and are approved by the architect/engineer.
  2. Bars and wires of less than 150 kips per square inch (ksi) (1034 MPa) tensile strength and conforming to ASTM A 82, ASTM A 510, ASTM A 615, ASTM A 616, ASTM A 996 or ASTM A 706/A 706 M are permitted to be used as pre-stressed tendons provided that:
  2.1. The stress relaxation properties have been assessed by tests according to ASTM E 328 for the maximum permissible stress in the tendon.
  2.2. Other nonstress-related requirements of ACI 530/ASCE 5/TMS 402, Chapter 4, addressing pre-stressing tendons are met.
Corrosion protection for pre-stressing tendons, pre-stressing anchorages, couplers and end block shall comply with the requirements of ACI 530.1/ASCE 6/TMS 602, Article 2.4G. Corrosion protection for carbon steel accessories used in exterior wall construction or interior walls exposed to a mean relative humidity exceeding 75 percent shall comply with either Section 2103.11.7.1 or 2103.11.7.2. Corrosion protection for carbon steel accessories used in interior walls exposed to a mean relative humidity equal to or less than 75 percent shall comply with either Section 2103.11.7.1, 2103.11.7.2 or 2103.11.7.3.
Apply a hot-dipped galvanized coating after fabrication as follows:
  1. For joint reinforcement, wall ties, anchors and inserts, apply a minimum coating of 1.5 ounces per square foot (psf) (458 g/m2) complying with the requirements of ASTM A 153, Class B.
  2. For sheet metal ties and sheet metal anchors, comply with the requirements of ASTM A 153, Class B.
  3. For steel plates and bars, comply with the requirements of either ASTM A 123 or ASTM A 153, Class B.
Carbon steel accessories shall be epoxy-coated as follows:
  1. For joint reinforcement, comply with the requirements of ASTM A 884 Class B, Type 2—18 mils (457 m).
  2. For wire ties and anchors, comply with the requirements of ASTM A 899 Class C—20mils (508 m).
  3. For sheet metal ties and anchors, provide a minimum thickness of 20 mils (508 m) or in accordance with the manufacturer's specification.
Apply a mill galvanized coating as follows:
  1. For joint reinforcement, wall ties, anchors and inserts, apply a minimum coating of 0.1 ounce psf (31g/m2) complying with the requirements of ASTM A 641.
  2. For sheet metal ties and sheet metal anchors, apply a minimum coating complying with Coating Designation G-60 according to the requirements of ASTM A 653.
  3. For anchor bolts, steel plates or bars not exposed to the earth, weather or a mean relative humidity exceeding 75 percent, a coating is not required.
Where unidentified reinforcement is approved for use, not less than three tension and three bending tests shall be made on representative specimens of the reinforcement from each shipment and grade of reinforcing steel proposed for use in the work.
Masonry construction shall comply with the requirements of Sections 2104.1.1 through 2104.5 and with ACI 530.1/ASCE 6/TMS 602.
Masonry, except masonry veneer, shall be constructed within the tolerances specified in ACI 530.1/ASCE 6/TMS 602.
Placement of mortar and units shall comply with Sections 2104.1.2.1 through 2104.1.2.5.
Unless otherwise required or indicated on the construction documents, head and bed joints shall be 38 inch (9.5 mm) thick, except that the thickness of the bed joint of the starting course placed over foundations shall not be less than 14 inch (6.4 mm) and not more than ¾ inch (19.1 mm).
Open-end units with beveled ends shall be fully grouted. Head joints of open-end units with beveled ends need not be mortared. The beveled ends shall form a grout key that permits grouts within 58 inch (15.9 mm) of the face of the unit. The units shall be tightly butted to prevent leakage of the grout.
Hollow units shall be placed such that face shells of bed joints are fully mortared. Webs shall be fully mortared in all courses of piers, columns, pilasters, in the starting course on foundations where adjacent cells or cavities are to be grouted, and where otherwise required. Head joints shall be mortared a minimum distance from each face equal to the face shell thickness of the unit.
Unless otherwise required or indicated on the construction documents, solid units shall be placed in fully mortared bed and head joints. The ends of the units shall be completely buttered. Head joints shall not be filled by slushing with mortar. Head joints shall be constructed by shoving mortar tight against the adjoining unit. Bed joints shall not be furrowed deep enough to produce voids.
Glass units shall be placed so head and bed joints are filled solidly. Mortar shall not be furrowed. Unless otherwise required, head and bed joints of glass unit masonry shall be 14 inch (6.4 mm) thick, except that vertical joint thickness of radial panels shall not be less than 18 inch (3.2 mm). The bed joint thickness tolerance shall be minus 116 inch (1.6 mm) and plus 18 inch (3.2 mm). The head joint thickness tolerance shall be plus or minus 18 inch (3.2 mm).
Units shall be placed while the mortar is soft and plastic. Any unit disturbed to the extent that the initial bond is broken after initial positioning shall be removed and relaid in fresh mortar.
The ends of wall ties shall be embedded in mortar joints. Wall tie ends shall engage outer face shells of hollow units by at least 12 inch (12.7 mm). Wire wall ties shall be embedded at least 112 inches (38 mm) into the mortar bed of solid masonry units or solid-grouted hollow units. Wall ties shall not be bent after being embedded in grout or mortar.
Chases and recesses shall be constructed as masonry units are laid. Masonry directly above chases or recesses wider than 12 inches (305 mm) shall be supported on lintels.
The design of masonry lintels shall be in accordance with the masonry design provisions of either Section 2107 or 2108. Minimum length of end support shall be 4 inches (102 mm).
Masonry shall not be supported on wood girders or other forms of wood construction except as permitted in Section 2304.12.
The top of unfinished masonry work shall be covered to protect the masonry from the weather.
Weep holes shall be provided in the exterior wythe of masonry walls and shall be at a maximum spacing of 33 inches (838 mm) on center (o.c.). Weep holes shall not be less than 316 inch (4.8 mm) in diameter.
The maximum corbeled projection beyond the face of the wall shall not be more than one-half of the wall thickness nor one-half the wythe thickness for hollow walls. The maximum projection of one unit shall neither exceed one-half the height of the unit nor one-third the thickness at right angles to the wall.
Unless structural support and anchorage are provided to resist the overturning moment, the center of gravity of projecting masonry or molded cornices shall lie within the middle one-third of the supporting wall. Terra cotta and metal cornices shall be provided with a structural frame of approved noncombustible material anchored in a manner approved by the commissioner.
The cold weather construction provisions of ACI 530.1/ASCE 6/TMS 602, Article 1.8 C, or the following procedures shall be implemented when either the ambient temperature falls below 40°F (4°C) or the temperature of masonry units is below 40°F (4°C).
  1. Temperatures of masonry units shall not be less than 20°F (-7°C) when laid in the masonry. Masonry units containing frozen moisture, visible ice or snow on their surface shall not be laid.
  2. Visible ice and snow shall be removed from the top surface of existing foundations and masonry to receive new construction. These surfaces shall be heated to above freezing, using methods that do not result in damage.
  3. No salt or other chemicals for the purpose of lowering the freezing temperature of water shall be permitted in the mortar mix.
The following requirements shall apply to work in progress and shall be based on ambient temperature.
The following construction requirements shall be met when the ambient temperature is between 40°F (4°C) and 32°F (0°C):
  1. Glass unit masonry shall not be laid.
  2. Water and aggregates used in mortar and grout shall not be heated above 140°F (60°C).
  3. Mortar sand or mixing water shall be heated to produce mortar temperatures between 40°F (4°C) and 120°F (49°C) at the time of mixing. When water and aggregates for grout are below 32°F (0°C), they shall be heated.
The requirements of Section 2104.3.2.1 and the following construction requirements shall be met when the ambient temperature is between 32°F (0°C) and 25°F (–4°C):
  1. The mortar temperature shall be maintained above freezing until used in masonry.
  2. Aggregates and mixing water for grout shall be heated to produce grout temperatures between 70°F (21°C) and 120°F (49°C) at the time of mixing. Grout temperature shall be maintained above 70°F (21°C) at the time of grout placement.
The requirements of Sections 2104.3.2.1 and 2104.3.2.2 and the following construction requirements shall be met when the ambient temperature is between 25°F (–4°C) and 20°F (–7°C):
  1. Masonry surfaces under construction shall be heated to 40°F (4°C).
  2. Wind breaks or enclosures shall be provided when the wind velocity exceeds 15 miles per hour (mph) (24 km/h).
  3. Prior to grouting, masonry shall be heated to a minimum of 40°F (4°C).
The requirements of Sections 2104.3.2.1, 2104.3.2.2 and 2104.3.2.3 and the following construction requirement shall be met when the ambient temperature is below 20°F (–7°C): Enclosures and auxiliary heat shall be provided to maintain air temperature within the enclosure to above 32°F (0°C).
The requirements of this section and Sections 2104.3.3.1 through 2104.3.3.4 apply after the masonry is placed and shall be based on anticipated minimum daily temperature for grouted masonry and anticipated mean daily temperature for ungrouted masonry.
The temperature of glass unit masonry shall be maintained above 40°F (4°C) for 48 hours after construction.
When the temperature is between 40°F (4°C) and 25°F (–4°C), newly constructed masonry shall be covered with a weather-resistive membrane for 24 hours after being completed.
When the temperature is between 25°F (–4°C) and 20°F (–7°C), newly constructed masonry shall be completely covered with weather-resistive insulating blankets, or equal protection, for 24 hours after being completed. The time period shall be extended to 48 hours for grouted masonry, unless the only cement in the grout is Type III portland cement.
When the temperature is below 20°F (–7°C), newly constructed masonry shall be maintained at a temperature above 32°F (0°C) for at least 24 hours after being completed by using heated enclosures, electric heating blankets, infrared lamps or other acceptable methods. The time period shall be extended to 48 hours for grouted masonry, unless the only cement in the grout is Type III portland cement.
The hot weather construction provisions of ACI 530.1/ASCE 6/TMS 602, Article 1.8 D, or the following procedures shall be implemented when the temperature or the temperature and wind-velocity limits of this section are exceeded.
The following requirements shall be met prior to conducting masonry work.
When the ambient temperature exceeds 100°F (38°C), or exceeds 90°F (32°C) with a wind velocity greater than 8 mph (13 km/h):
  1. Necessary conditions and equipment shall be provided to produce mortar having a temperature below 120°F (49°C).
  2. Sand piles shall be maintained in a damp, loose condition.
When the ambient temperature exceeds 115°F (46°C), or 105°F (40°C) with a wind velocity greater than 8 mph (13 km/h), the requirements of Section 2104.4.1.1 shall be implemented, and materials and mixing equipment shall be shaded from direct sunlight.
The following requirements shall be met while masonry work is in progress.
When the ambient temperature exceeds 100°F (38°C), or exceeds 90°F (32°C) with a wind velocity greater than 8 mph (13 km/h):
  1. The temperature of mortar and grout shall be maintained below 120°F (49°C).
  2. Mixers, mortar transport containers and mortar boards shall be flushed with cool water before they come into contact with mortar ingredients or mortar.
  3. Mortar consistency shall be maintained by retempering with cool water.
  4. Mortar shall be used within 2 hours of initial mixing.
When the ambient temperature exceeds 115°F (46°C), or exceeds 105°F (40°C) with a wind velocity greater than 8 mph (13 km/h), the requirements of Section 2104.4.2.1 shall be implemented and cool mixing water shall be used for mortar and grout. The use of ice shall be permitted in the mixing water prior to use. Ice shall not be permitted in the mixing water when added to the other mortar or grout materials.
When the mean daily temperature exceeds 100°F (38°C), or exceeds 90°F (32°C) with a wind velocity greater than 8 mph (13 km/h), newly constructed masonry shall be fog sprayed until damp at least three times a day until the masonry is three days old.
Brick (clay or shale) at the time of laying shall require wetting if the unit's initial rate of water absorption exceeds 21.42 grams per 30 square inches (19355 mm2) per minute or 0.025 ounce psi (1 g/645 mm2), as determined by ASTM C 67.
A quality assurance program shall be used to ensure that the constructed masonry is in compliance with the construction documents. The quality assurance program shall comply with the inspection and testing requirements of Chapter 17.
Compressive strength of masonry shall be considered satisfactory if the compressive strength of each masonry wythe and grouted collar joint equals or exceeds the value of  f'm.
The compressive strength for each wythe shall be determined by the unit strength method or by the prism test method as specified herein.
The compressive strength of masonry shall be determined based on the strength of the units and the type of mortar specified using Table 2105.2.2.1.1, provided:
  1. Units conform to ASTM C 62, ASTM C 216 or ASTM C 652 and are sampled and tested in accordance with ASTM C 67.
  2. Thickness of bed joints does not exceed 5/8 inch (15.9 mm).
  3. For grouted masonry, the grout meets one of the following requirements:
  3.1. Grout conforms to ASTM C 476.
  3.2. Minimum grout compressive strength equals f'm but not less than 2,000 psi (13.79 MPa). The compressive strength of grout shall be determined in accordance with ASTM C 1019.

TABLE 2105.2.2.1.1
COMPRESSIVE STRENGTH OF CLAY MASONRY
NET AREA COMPRESSIVE STRENGTH OF
CLAY MASONRY UNITS (psi)
NET AREA
COMPRESSIVE
STRENGTH OF
MASONRY (psi)
Type M or S mortar Type N mortar
1,700 2,100 1,000
3,350 4,150 1,500
4,950 6,200 2,000
6,600 8,250 2,500
8,250 10,300 3,000
9,900 - 3,500
13,200 - 4,000
For SI: 1 pound per square inch = 0.00689 mPa.
The compressive strength of masonry shall be determined based on the strength of the unit and type of mortar specified using Table 2105.2.2.1.2, provided:
  1. Units conform to ASTM C 55 or ASTM C 90 and are sampled and tested in accordance with ASTM C 140.
  2. Thickness of bed joints does not exceed 5/8 inch (15.9 mm).
  3. For grouted masonry, the grout meets one of the following
requirements:
  3.1. Grout conforms to ASTM C 476.
  3.2. Minimum grout compressive strength equals f'm but not less than 2,000 psi (13.79 MPa). The compressive strength of grout shall be determined in accordance with ASTM C 1019.

TABLE 2105.2.2.1.2
COMPRESSIVE STRENGTH OF CONCRETE MASONRY
NET AREA COMPRESSIVE STRENGTH OF
CLAY MASONRY UNITS (psi)
NET AREA
COMPRESSIVE
STRENGTH OF
MASONRY (psi)a
Type M or S mortar Type N mortar
1,250 1,300 1,000
1,900 2,150 1,500
2,800 3,050 2,500
3,750 4,050 2,500
4,800 5,250 3,000
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689mPa.
  1. For units less than 4 inches in height, 85 percent of the values listed.
The compressive strength of masonry shall be determined by the prism test method:
  1. Where specified in the construction documents.
  2. Where masonry does not meet the requirements for application of the unit strength method in Section 2105.2.2.1.
A prism test shall consist of three prisms constructed and tested in accordance with ASTM C 1314.
When approved by the commissioner acceptance of masonry that does not meet the requirements of Section 2105.2.2.1 or 2105.2.2.2 shall be permitted to be based on tests of prisms cut from the masonry construction in accordance with Sections 2105.3.1, 2105.3.2 and 2105.3.3.
A set of three masonry prisms that are at least 28 days old shall be saw cut from the masonry for each 5,000 square feet (465 m2) of the wall area that is in question but not less than one set of three masonry prisms for the project. The length, width and height dimensions of the prisms shall comply with the requirements of ASTM C 1314. Transporting, preparation and testing of prisms shall be in accordance with ASTM C 1314.
The compressive strength of prisms shall be the value calculated in accordance ASTM C 1314, except that the net cross-sectional area of the prism shall be based on the net mortar bedded area.
Compliance with the requirement for the specified compressive strength of masonry, f' m , shall be considered satisfied provided the modified compressive strength equals or exceeds the specified f' m . Additional testing of specimens cut from locations in question shall be permitted.
Masonry structures and components shall comply with the requirements in Section 1.13.2.2 of ACI 530/ASCE 5/TMS 402 and Section 1.13.3, 1.13.4, 1.13.5, 1.13.6 or 1.13.7 of ACI 530/ASCE 5/TMS 402 depending on the structure's seismic design category as determined in Section 1616.3. All masonry walls, unless isolated on three edges from in-plane motion of the basic structural systems, shall be considered to be part of the seismic-force-resisting system. In addition, the following requirements shall be met.
Buildings relying on masonry shear walls as part of the basic seismic-force-resisting system shall comply with Section 1.13.2.2 of ACI 530/ASCE 5/TMS 402 or with Section 2106.1.1.1, 2106.1.1.2 or 2106.1.1.3.
Ordinary plain prestressed masonry shear walls shall comply with the requirements of Chapter 4 of ACI 530/ASCE 5/TMS 402.
Intermediate prestressed masonry shear walls shall comply with the requirements of Section 1.13.2.2.4 of ACI 530/ASCE 5/TMS 402 and shall be designed by Chapter 4, Section 4.5.3.3, of ACI 530/ASCE 5/TMS 402 for flexural strength and by Section 3.2.4.1.2 of ACI 530/ASCE 5/TMS 402 for shear strength. Sections 1.13.2.2.5(a), 3.2.3.5 and 3.2.4.3.2(c) of ACI 530/ASCE 5/TMS 402 shall be applicable for reinforcement. Flexural elements subjected to load reversals shall be symmetrically reinforced. The nominal moment strength at any section along a member shall not be less than one-fourth the maximum moment strength. The cross-sectional area of bonded tendons shall be considered to contribute to the minimum reinforcement in Section 1.13.2.2.4 of ACI 530/ASCE 5/TMS 402. Tendons shall be located in cells that are grouted the full height of the wall.
Special prestressed masonry shear walls shall comply with the requirements of Section 1.13.2.2.5 of ACI 530/ASCE 5/TMS 402 and shall be designed by Chapter 4, Section 4.5.3.3, of ACI 530/ASCE 5/TMS 402 for flexural strength and by Section 3.2.4.1.2 of ACI 530/ASCE 5/TMS 402 for shear strength. Sections 1.13.2.2.5(a), 3.2.3.5 and 3.2.4.3.2(c) of ACI 530/ASCE 5/TMS 402 shall be applicable for reinforcement. Flexural elements subjected to load reversals shall be symmetrically reinforced. The nominal moment strength at any section along a member shall not be less than one-fourth the maximum moment strength. The cross-sectional area of bonded tendons shall be considered to contribute to the minimum reinforcement in Section 1.13.2.2.5 of ACI 530/ASCE 5/TMS 402. Special prestressed masonry shear walls shall also comply with the requirements of Section 3.2.3.5 of ACI 530/ASCE 5/TMS 402.
Prestressing tendons shall consist of bars conforming to ASTM A 722.
All cells of the masonry wall shall be grouted.
Masonry walls shall be anchored to the roof and floors that provide lateral support for the wall in accordance with Section 1604.8.2.
Structures assigned to Seismic Design Category B shall conform to the requirements of Section 1.13.4 of ACI 530/ASCE 5/TMS 402.
Masonry partition walls, masonry screen walls and other masonry elements that are not designed to resist vertical or lateral loads, other than those induced by their own mass, shall be isolated from the structure so that the vertical and lateral forces are not imparted to these elements. Isolation joints and connectors between these elements and the structure shall be designed to accommodate the design story drift.
Structures assigned to Seismic Design Category C shall conform to the requirements of Section 1.13.5 of ACI 530/ASCE 5/TMS 402 and the additional requirements of this section.
Columns and pilasters that are part of the lateral-force-resisting system and that support reactions from discontinuous stiff members such as walls shall be provided with transverse reinforcement spaced at no more than one-fourth of the least nominal dimension of the column or pilaster. The minimum transverse reinforcement ratio shall be 0.0015. Beams supporting reactions from discontinuous walls or frames shall be provided with transverse reinforcement spaced at no more than one-half of the nominal depth of the beam. The minimum transverse reinforcement ratio shall be 0.0015.
Masonry partition walls, masonry screen walls and other masonry elements that are not designed to resist vertical or lateral loads, other than those loads induced by their own mass, shall be isolated from the structure so that the vertical and lateral forces are not imparted to these elements. Isolation joints and connectors between these elements and the structure shall be designed to accommodate the design story drift.
Structures assigned to Seismic Design Category D shall conform to the requirements of Section 2106.4, Section 1.13.6 of ACI 530/ASCE 5/TMS 402 and the additional requirements of this section.
When calculating in-plane shear or diagonal tension stresses by the working stress design method, shear walls that resist seismic forces shall be designed to resist 1.5 times the seismic forces required by Chapter 16. The 1.5 multiplier need not be applied to the overturning moment.
For a shear wall whose nominal shear strength exceeds the shear corresponding to development of its nominal flexural strength, two shear regions exist.

  For all cross sections within a region defined by the base of the shear wall and a plane at a distance Lw above the base of the shear wall, the nominal shear strength shall be determined by Equation 21-1.

Vn = An ρn fy (Equation 21-1)


  The required shear strength for this region shall be calculated at a distance Lw/2 above the base of the shear wall, but not to exceed one-half story height. For the other region, the nominal shear strength of the shear wall shall be determined from Section 2108.
The design of masonry structures using working stress design shall comply with Section 2106 and the requirements of Chapters 1 and 2, except Section 2.1.2.1 and 2.1.3.3 of ACI 530/ASCE 5/TMS 402. The text of ACI 530/ASCE 5/TMS 402 shall be modified as follows.
Special inspection during construction shall be provided as set forth in Section 1704.5.
Masonry columns used only to support light-frame roofs of carports, porches, sheds or similar structures with a maximum area of 450 square feet (41.8 m2) assigned to Seismic Design Category B or C are permitted to be designed and constructed as follows:
  1. Concrete masonry materials shall be in accordance with Section 2103.1. Clay or shale masonry units shall be in accordance with Section 2103.2.
  2. The nominal cross-sectional dimension of columns shall not be less than 8 inches (203 mm).
  3. Columns shall be reinforced with not less than one No. 4 bar centered in each cell of the column.
  4. Columns shall be grouted solid.
  5. Columns shall not exceed 12 feet (3658 mm) in height.
  6. Roofs shall be anchored to the columns. Such anchorage shall be capable of resisting the design loads specified in Chapter 16.
  7. Where such columns are required to resist uplift loads, the columns shall be anchored to their footings with two No. 4 bars extending a minimum of 24 inches (610 mm) into the columns and bent horizontally a minimum of 15 inches (381 mm) in opposite directions into the footings. One of these bars is permitted to be the reinforcing bar specified in Item 3 above. The total weight of a column and its footing shall not be less than 1.5 times the design uplift load.
The minimum length of lap splices for reinforcing bars in tension or compression, lld, shall be calculated by Equation 21-2, but shall not be less than 15 inches (381 mm).

(Equation 21-2)

For SI: lld = 1.95d2bfyλ / K√f‘m
where:
db = Diameter of reinforcement, inches (mm).
ƒy = Specified yield stress of the reinforcement or the anchor bolt, psi (mPa).
ƒ′m = Specified compressive strength of masonry at age of 28 days, psi (mPa).
lld = Minimum lap splice length, inches (mm).
Κ = The lesser of the masonry cover, clear spacing between adjacent reinforcement or five times db, inches (mm).
γ = 1.0 for No. 3 through No. 5 reinforcing bars. 1.4 for No.6 and No.7 reinforcing bars. 1.5 for No.8 through No. 9 reinforcing bars.
The bar diameter shall not exceed one-eighth of the nominal wall thickness and shall not exceed one-quarter of the least dimension of the cell, course or collar joint in which it is placed.
Reinforcing bars larger than No. 9 in size shall be spliced using mechanical connectors in accordance with ACI 530/ASCE 5/TMS 402, Section 2.1.10.6.3.
Special reinforced masonry shear walls having a shear span ratio, M/Vd, equal to or greater than 1.0 and having an axial load, P greater than 0.05 f'mAn which are subjected to in-plane forces, shall have a maximum reinforcement ratio, rmax, not greater than that computed as follows:
The design of masonry structures using strength design shall comply with Section 2106 and the requirements of Chapters 1 and 3 of ACI 530/ASCE 5/TMS 402. The minimum nominal thickness for hollow clay masonry in accordance with Section 3.2.5.5 of ACI 530/ASCE 5/TMS 402 shall be 4 inches (102 mm). The text of ACI 530/ASCE 5/TMS 402 shall be modified as follows;
Modify Section 3.2.2(g) as follows:
  3.2.2(g). The relationship between masonry compressive stress and masonry strain shall be assumed to be defined by the following:
  Masonry stress of 0.80 f'm shall be assumed uniformly distributed over an equivalent compression zone bounded by edges of the cross section and a straight line located parallel to the neutral axis at a distance, a = 0.80 c, from the fiber of maximum compressive strain. The distance, c, from the fiber of maximum strain to the neutral axis shall be measured perpendicular to that axis. For out-of-plane bending, the width of the equivalent stress block shall not be taken greater than six times the nominal thickness of the masonry wall or the spacing between reinforcement, whichever is less. For in-plane bending of flanged walls, the effective flange width shall not exceed six times the thickness of the flange.
Modify Section 3.2.3.4 (b) and (c) as follows:
  3.2.3.4 (b). A welded splice shall have the bars butted and welded to develop at least 125 percent of the yield strength, fy, of the bar in tension or compression, as required. Welded splices shall be of ASTM A 706 steel reinforcement. Welded splices shall not be permitted in plastic hinge zones of intermediate or special reinforced walls or special moment frames of masonry.
  3.2.3.4 (c). Mechanical splices shall be classified as Type 1 or 2 according to Section 21.2.6.1 of ACI 318. Type 1 mechanical splices shall not be used within a plastic hinge zone or within a beam-column joint of intermediate or special reinforced masonry shear walls or special moment frames. Type 2 mechanical splices are permitted in any location within a member.
Add the following text to Section 3.2.3.5.1:
  For special prestressed masonry shear walls, strain in all prestressing steel shall be computed to be compatible with a strain in the extreme tension reinforcement equal to five times the strain associated with the reinforcement yield stress, fy. The calculation of the maximum reinforcement shall consider forces in the prestressing steel that correspond to these calculated strains.
Empirically designed masonry shall conform to this chapter or Chapter 5 of ACI 530/ASCE 5/TMS 402.
Empirical masonry design shall not be utilized for any of the following conditions:
  1. The design or construction of masonry in buildings assigned to Seismic Design Category D as specified in Section 1616, and the design of the seismic-force-resisting system for buildings assigned to Seismic Design Category B or C.
  2. Buildings more than 35 feet (10 668 mm) in height which have masonry wall lateral-force-resisting systems.
  In buildings that exceed one or more of the above limitations, masonry shall be designed in accordance with the engineered design provisions of Section 2107 or 2108.
Where the structure depends upon masonry walls for lateral stability, shear walls shall be provided parallel to the direction of the lateral forces resisted.
Minimum nominal thickness of masonry shear walls shall be 8 inches (203 mm).
  Exception: Shear walls of one-story buildings are permitted to be a minimum nominal thickness of 6 inches (152 mm).
In each direction in which shear walls are required for lateral stability, shear walls shall be positioned in two separate planes. The minimum cumulative length of shear walls provided shall be 0.4 times the long dimension of the building. Cumulative length of shear walls shall not include openings or any element whose length is less than one-half its height.
Masonry shear walls shall be spaced so that the length-to-width ratio of each diaphragm transferring lateral forces to the shear walls does not exceed the values given in Table 2109.2.1.3.

TABLE 2109.2.1.3
DIAPHRAGM LENGTH-TO-WIDTH RATIOS
FLOOR OR ROOF DIAPHRAGM CONSTRUCTION MAXIMUM LENGTH-TO-WIDTH RATIO OF DIAPHRAGM PANEL
Cast-in-place concrete 5:1
Precast concrete 4:1
Metal deck with concrete fill 3:1
Metal deck with no fill 2:1
Wood 2:1
The roof construction shall be designed so as not to impart out-of-plane lateral thrust to the walls under roof gravity load.
Dry-stacked, surface-bonded concrete masonry walls shall comply with the requirements of this code for masonry wall construction, except where otherwise noted in this section.
Dry-stacked, surface-bonded concrete masonry walls shall be of adequate strength and proportions to support all superimposed loads without exceeding the allowable stresses listed in Table 2109.2.3.1. Allowable stresses not specified in Table 2109.2.3.1 shall comply with the requirements of ACI 530/ASCE 5/TMS 402.

TABLE 2109.2.3.1
ALLOWABLE STRESS GROSS CROSS-SECTIONAL
AREA FOR DRY-STACKED, SURFACE-BONDED
CONCRETE MASONRY WALLS

DESCRIPTION
MAXIMUM ALLOWABLE STRESS
(psi)
Compression standard block 45
Shear 10
Flexural tension
Vertical span
Horizontal span

18
30
For SI: 1 pound per square inch = 0.006895 mPa.
Construction of dry-stacked, surface-bonded masonry walls, including stacking and leveling of units, mixing and application of mortar and curing and protection shall comply with ASTM C 946.
Compressive stresses in masonry due to vertical dead plus live loads, excluding wind or seismic loads, shall be determined in accordance with Section 2109.3.2.1. Dead and live loads shall be in accordance with Chapter 16, with live load reductions as permitted in Section 1607.9.
The compressive stresses in masonry shall not exceed the values given in Table 2109.3.2. Stress shall be calculated based on specified rather than nominal dimensions.

TABLE 2109.3.2
ALLOWABLE COMPRESSIVE STRESSES FOR EMPIRICAL DESIGN OF MASONRY
CONSTRUCTION; COMPRESSIVE
STRENGTH OF UNIT
GROSS AREA (psi)
ALLOWABLE COMPRESSIVE
STRESSESa GROSS CROSS-SECTIONAL AREA (psi)
Type M or S mortar Type N mortar
Solid masonry of brick and other solid units of clay or shale; sand-lime or concrete brick:
8,000 or greater
4,500
2,500
1,500


350
225
160
115


300
200
140
100
Grouted masonry, of clay or shale; sand-lime or concrete:
4,500 or greater
2,500
1,500


225
160
115


200
140
100
Solid masonry of solid concrete masonry units:
3,000 or greater
2,000
1,200


225
160
115


200
140
100
Masonry of hollow load-bearing units:
2,000 or greater
1,500
1,000
700

140
115
75
60

120
100
70
55
Hollow walls (noncomposite masonry bonded)b Solid units:
     2,500 or greater
1,500
Hollow units


160
115
75


140
100
70
Stone ashlar masonry:
Granite
Limestone or marble
Sandstone or cast stone

720
450
360

640
400
320
Rubble stone masonry
Coursed, rough or random

120

100
For SI: 1 pound per square inch = 0.006895 MPa.
  1. Linear interpolation for determining allowable stresses for masonry units having compressive strengths which are intermediate between those given in the table is permitted.
  2. Where floor and roof loads are carried upon one wythe, the gross cross-sectional area is that of the wythe under load; if both wythes are loaded, the gross cross-sectional area is that of the wall minus the area of the cavity between the wythes. Walls bonded with metal ties shall be considered as noncomposite walls unless collar joints are filled with mortar or grout.
Calculated compressive stresses for single wythe walls and for multi-wythe composite masonry walls shall be determined by dividing the design load by the gross cross-sectional area of the member. The area of openings, chases or recesses in walls shall not be included in the gross cross-sectional area of the wall.
The allowable stress shall be as given in Table 2109.3.2 for the weakest combination of the units used in each wythe.
Masonry walls shall be laterally supported in either the horizontal or vertical direction at intervals not exceeding those given in Table 2109.4.1.

TABLE 2109.4.1
WALL LATERAL SUPPORT REQUIREMENTS
CONSTRUCTION MAXIMUM WALL LENGTH TO
THICKNESS OR WALL HEIGHT
TO THICKNESS
Bearing walls
Solid units or fully grouted
All others

20
18
Nonbearing walls
Exterior
Interior

18
36
Except for cavity walls and cantilever walls, the thickness of a wall shall be its nominal thickness measured perpendicular to the face of the wall. For cavity walls, the thickness shall be determined as the sum of the nominal thicknesses of the individual wythes. For cantilever walls, except for parapets, the ratio of height-to-nominal thickness shall not exceed six for solid masonry or four for hollow masonry. For parapets, see Section 2109.5.5.
Lateral support shall be provided by cross-walls, pilasters, buttresses or structural frame members when the limiting distance is taken horizontally, or by floors, roofs acting as diaphragms or structural frame members when the limiting distance is taken vertically.
Minimum thickness requirements shall be based on nominal dimensions of masonry.
The thickness of masonry walls shall conform to the requirements of Section 2109.5.
The minimum thickness of masonry bearing walls more than one story high shall be 8 inches (203 mm) where the height floor to floor does not exceed 12 feet (3658 mm), the floor live load does not exceed 60 pounds per square feet (psf) (0.156 kg/m2), and the roof is designed so that the dead load imparts no lateral thrust to the wall. Bearing walls of one-story buildings shall not be less than 6 inches (152 mm) thick. However, the overall thickness of cavity or masonry-bonded hollow walls shall not be less than 8 inches (203 mm), including cavity.
Masonry walls above roof level, 12 feet (3658 mm) or less in height, enclosing stairways, machinery rooms, shafts, or penthouses, may be up to 8 inches (203 mm) thick and shall be considered as neither increasing the height nor requiring any increase in the thickness of the wall below.
The minimum thickness of rough or random or coursed rubble stone walls shall be 16 inches (406 mm).
Where walls of masonry of hollow units or masonry bonded hollow walls are decreased in thickness, a course or courses of solid masonry shall be interposed between the wall below and the thinner wall above, or special units or construction shall be used to transmit the loads from face shells or wythes above to those below.
Unreinforced parapet walls shall be at least 8 inches (203 mm) thick, and their height shall not exceed three times their thickness.
All cells in the hollow masonry units and all joints in solid, cavity, or masonry-bonded hollow wall construction shall be filled solid with mortar. All corners of masonry parapet walls shall be reinforced with joint reinforcement or its equivalent at vertical intervals not greater than 12 inches (305 mm). Such reinforcement shall extend around the corner for at least 4 feet (1219 mm) in both directions and splices shall be lapped at least 6 inches (152 mm).
Parapets of buildings taller than 35 feet (10 668 mm) shall be reinforced vertically and shall be anchored to the roof and floors that provide lateral support for the wall in accordance with section 1604.8.2.
Additional provisions for parapet walls are contained in Sections 1503.2 and 1503.3.
Foundation walls shall comply with the requirements of Sections 2109.5.6.1 and 2109.5.6.2.
Minimum thickness for foundation walls shall comply with the requirements of Table 2109.5.6.1. The provisions of Table 2109.5.6.1 are only applicable where the following conditions are met:
  1. The foundation wall does not exceed 8 feet (2438 mm) in height between lateral supports,
  2. The terrain surrounding foundation walls is graded to drain surface water away from foundation walls,
  3. Backfill is drained to remove ground water away from foundation walls,
  4. Lateral support is provided at the top of foundation walls prior to back-filling,
  5. The length of foundation walls between perpendicular masonry walls or pilasters is a maximum of three times the basement wall height,
  6. The backfill is granular and soil conditions in the area are non-expansive, and
  7. Masonry is laid in running bond using Type M or S mortar.

TABLE 2109.5.6.1
FOUNDATION WALL CONSTRUCTION

WALL
CONSTRUCTION
NOMINAL WALL
THICKNESS
(inches)
MAXIMUM DEPTH OF
UNBALANCED BACKFILL
(feet)
Hollow unit masonry 8
10
12
5
6
7
Solid unit masonry 8
10
12
5
7
7
Fully grouted masonry 8
10
12
7
8
8
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Where the requirements of Section 2109.5.6.1 are not met, foundation walls shall be designed in accordance with Section 1805.5.
The minimum thickness for partitions shall be as follows:

TABLE 2109.5.7
MINIMUM THICKNESS OF MASONRY PARTITIONS
HEIGHT OF WALLS THICKNESS
8 ft. and under 2 in.
Over 8 ft. to 12 ft 3 in.
Over 12 ft. to 16 ft 4 in.
Over 16 ft. to 20 ft 6 in.
Over 20 ft. to 24 ft. 8 in.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
The facing and backing of multi-wythe masonry walls shall be bonded in accordance with Section 2109.6.2, 2109.6.3 or 2109.6.4.
Where the facing and backing (adjacent wythes) of solid masonry construction are bonded by means of masonry headers, no less than 4 percent of the wall surface of each face shall be composed of headers extending not less than 3 inches (76 mm) into the backing. The distance between adjacent full-length headers shall not exceed 24 inches (610 mm) either vertically or horizontally. In walls in which a single header does not extend through the wall, headers from the opposite sides shall overlap at least 3 inches (76 mm), or headers from opposite sides shall be covered with another header course overlapping the header below at least 3 inches (76 mm).
Where two or more hollow units are used to make up the thickness of a wall, the stretcher courses shall be bonded at vertical intervals not exceeding 34 inches (864 mm) by lapping at least 3 inches (76 mm) over the unit below, or by lapping at vertical intervals not exceeding 17 inches (432 mm) with units that are at least 50 percent greater in thickness than the units below.
In masonry bonded hollow walls, the facing and backing shall be bonded so that not less than 4 percent of the wall surface of each face is composed of masonry bonded units extending not less than 3 inches (76 mm) into the backing. The distance between adjacent bonders shall not exceed 24 inches (610 mm) either vertically or horizontally.
Except as required by Section 2109.6.3.1.1, where the facing and backing (adjacent wythes) of masonry walls are bonded with wire size W2.8 (MW 18) wall ties or metal wire of equivalent stiffness embedded in the horizontal mortar joints, there shall be at least one metal tie for each 412 square feet (0.42 m2) of wall area. The maximum vertical distance between ties shall not exceed 24 inches (610 mm), and the maximum horizontal distance shall not exceed 36 inches (914 mm). Rods or ties bent to rectangular shape shall be used with hollow masonry units laid with the cells vertical. In other walls, the ends of ties shall be bent to 90-degree (1.57 rad) angles to provide hooks no less than 2 inches (51 mm) long. Wall ties shall be without drips. Additional bonding ties shall be provided at all openings, spaced not more than 36 inches (914 mm) apart around the perimeter and within 12 inches (305 mm) of the opening.
Where the facing and backing (adjacent wythes) of masonry are bonded with adjustable wall ties, there shall be at least one tie for each 1.77 square feet (0.16 m2) of wall area. Neither the vertical nor horizontal spacing of the adjustable wall ties shall exceed 16 inches (406 mm). The maximum vertical offset of bed joints from one wythe to the other shall be 114 inches (32 mm). The maximum clearance between connecting parts of the ties shall be 116 inch (1.6 mm). When pintle legs are used, ties shall have at least two wire size W2.8 (MW 18) legs.
Where the facing and backing (adjacent wythes) of masonry are bonded with prefabricated joint reinforcement, there shall be at least one cross wire serving as a tie for each 223 square feet (0.25 m2) of wall area. The vertical spacing of the joint reinforcing shall not exceed 24 inches (610 mm). Cross wires on prefabricated joint reinforcement shall not be less than W1.7 (MW 11) and shall be without drips. The longitudinal wires shall be embedded in the mortar.
In ashlar masonry, bonder units, uniformly distributed, shall be provided to the extent of not less than 10 percent of the wall area. Such bonder units shall extend not less than 4 inches (102 mm) into the backing wall.
Rubble stone masonry 24 inches (610 mm) or less in thickness shall have bonder units with a maximum spacing of 36 inches (914 mm) vertically and 36 inches (914 mm) horizontally, and if the masonry is of greater thickness than 24 inches (610 mm), shall have one bonder unit for each 6 square feet (0.56 m 2 ) of wall surface on both sides.
Each wythe of masonry shall be laid in running bond, head joints in successive courses shall be offset by not less than one-fourth the unit length or the masonry walls shall be reinforced longitudinally as required in Section 2109.6.5.2.
Where unit masonry is laid with less head joint offset than in Section 2109.6.5.1, the minimum area of horizontal reinforcement placed in mortar bed joints or in bond beams spaced not more than 48 inches (1219 mm) apart, shall be 0.0003 times the vertical cross-sectional area of the wall.
Masonry elements shall be anchored in accordance with Sections 2109.7.2 through 2109.7.4.
Masonry walls depending upon one another for lateral support shall be anchored or bonded at locations where they meet or intersect by one of the methods indicated in Sections 2109.7.2.1 through 2109.7.2.5.
Fifty percent of the units at the intersection shall be laid in an overlapping masonry bonding pattern, with alternate units having a bearing of not less than 3 inches (76 mm) on the unit below.
Walls shall be anchored by steel connectors having a minimum section of 14 inch (6.4 mm) by 112 inches (38 mm), with ends bent up at least 2 inches (51 mm) or with cross pins to form anchorage. Such anchors shall be at least 24 inches (610 mm) long and the maximum spacing shall be 48 inches (1219 mm).
Walls shall be anchored by joint reinforcement spaced at a maximum distance of 8 inches (203 mm). Longitudinal wires of such reinforcement shall be at least wire size W1.7 (MW 11) and shall extend at least 30 inches (762 mm) in each direction at the intersection.
Interior nonload-bearing walls shall be anchored at their intersection, at vertical intervals of not more than 16 inches (406 mm) with joint reinforcement or 14 -inch (6.4 mm) mesh galvanized hardware cloth.
Other metal ties, joint reinforcement or anchors, if used, shall be spaced to provide equivalent area of anchorage to that required by this section and be approved by the commissioner.
Floor and roof diaphragms providing lateral support to masonry shall comply with the live loads in Section 1607.3 and shall be connected to the masonry in accordance with Sections 2109.7.3.1 through 2109.7.3.3.
Wood floor joists bearing on masonry walls shall be anchored to the wall at intervals not to exceed 72 inches (1829 mm) by metal strap anchors. Joists parallel to the wall shall be anchored with metal straps spaced not more than 72 inches (1829 mm) o.c. extending over or under and secured to at least three joists. Blocking shall be provided between joists at each strap anchor.
Concentrated loads shall be supported upon construction of solid masonry, concrete, or masonry of hollow units with cells filled with mortar, grout, or concrete and of sufficient height to distribute safely the loads to the wall or column, or other adequate provisions shall be made to distribute the loads.
Solid construction for support under joists shall be at least 214 inches (57 mm) in height, and joists supported on such construction shall extend into the masonry at least 3 inches (76 mm).
Solid construction for support under beams, girders, or other concentrated loads shall be at least 4 inches (102 mm) in height, and the bearing of beams shall extend into the masonry at least 4 inches (102 mm)
Isolated masonry piers shall be bonded as required for solid walls of the same thickness and shall be provided with adequate means for distributing the load at the top of the pier.
Steel floor joists bearing on masonry walls shall be anchored to the wall with 38 -inch (9.5 mm) round bars, or their equivalent, spaced not more than 72 inches (1829 mm) o.c. Where joists are parallel to the wall, anchors shall be located at joist bridging.
Roof diaphragms shall be anchored to masonry walls with 12 -inch-diameter (12.7 mm) bolts, 72 inches (1829 mm) o.c. or their equivalent. Bolts shall extend and be embedded at least 15 inches (381 mm) into the masonry, or be hooked or welded to not less than 0.20 square inch (0.02 m2) of bond beam reinforcement placed not less than 6 inches (152 mm) from the top of the wall.
Where walls are dependent upon the structural frame for lateral support, they shall be anchored to the structural members with metal anchors or otherwise keyed to the structural members. Metal anchors shall consist of 12-inch (12.7 mm) bolts spaced at 48 inches (1219 mm) o.c. embedded 4 inches (102 mm) into the masonry, or their equivalent area.
An existing masonry wall may be used in the alteration or extension of a building provided that it meets the requirements of this standard.
Existing walls of masonry units that are structurally sound, but that are of insufficient thickness when increased in height, may be strengthened by an addition of similar masonry units laid in type M or S mortar. The foundations and lateral support shall be equivalent to those required for newly constructed walls under similar conditions. All such linings shall be thoroughly bonded into existing masonry by toothings to assure combined action of wall and lining. Toothings shall be distributed uniformly throughout the wall, and shall aggregate in vertical cross-sectional area at least 15 percent of the total surface area of the lining. Stresses in the masonry under the new conditions shall not exceed the allowable stresses.
Temporary bracing shall be used wherever necessary to resist loads to which the walls may be subjected during erection. Such bracing shall remain in place as long as may be required for safety.
All concrete framed buildings to be constructed over 35 feet (10 668 mm) in height (as measured from adjoining grade to the main roof level), whose exterior wythe are of cavity wall construction with steel lintels, shall have horizontal joints in the exterior wythe to prevent masonry distress induced by vertical shortening of the structural frame.
Unless substantiated as indicated by 2109.7.4.4.2, horizontal joints shall be 14 inch (6.4 mm) minimum thickness, with neoprene, polyethylene, or urethane gasket or equivalent joint filler filling the entire joint, except for a recess from the toe of the lintel angle to the exterior of the facing brick, to provide space for caulking. These joints shall be placed at each floor.
The applicant of record shall submit an engineering analysis establishing that proposed building horizontal joints spaced further apart than in 2109.7.4.4.1 are sufficient to provide for the effects of vertical shortening of the structural frame.
This section covers the empirical requirements for non-load-bearing glass unit masonry elements in exterior or interior walls.
Solid or hollow approved glass block shall not be used in firewalls, party walls, fire barriers or fire partitions, or for load-bearing construction. Such blocks shall be erected with mortar and reinforcement in metal channel-type frames, structural frames, masonry or concrete recesses, embedded panel anchors as provided for both exterior and interior walls or other approved joint materials. Wood strip framing shall not be used in walls required to have a fire-resistance rating by other provisions of this code.

Exception: Glass-block assemblies having a fire protection rating of not less than 34 hour shall be permitted as opening protectives in accordance with Section 715 in fire barriers and fire partitions that have a required fire-resistance rating of 1 hour and do not enclose exit stairways or exit passageways.
Hollow or solid glass-block units shall be standard or thin units.
The specified thickness of standard units shall be 378 inches (98 mm).
The specified thickness of thin units shall be 318 inches (79 mm) for hollow units or 3 inches (76 mm) for solid units.
The maximum area of each individual exterior standard-unit panel shall be 144 square feet (13.4 m2) when the design wind pressure is 20 psf (958 N/m2). The maximum panel dimension between structural supports shall be 25 feet (7620 mm) in width or 20 feet (6096 mm) in height. The panel areas are permitted to be adjusted in accordance with Figure 2110.3.1 for other wind pressures.
The maximum area of each individual exterior thin-unit panel shall be 85 square feet (7.9 m2). The maximum dimension between structural supports shall be 15 feet (4572 mm) in width or 10 feet (3048 mm) in height. Thin units shall not be used in applications where the design wind pressure exceeds 20 psf (958 N/m2).
The maximum area of each individual standard-unit panel shall be 250 square feet (23.2 m2). The maximum area of each thin-unit panel shall be 150 square feet (13.9 m2). The maximum dimension between structural supports shall be 25 feet (7620 mm) in width or 20 feet (6096 mm) in height.
The maximum area of solid glass-block wall panels in both exterior and interior walls shall not be more than 100 square feet (9.3 m2).
The width of curved panels shall conform to the requirements of Sections 2110.3.1, 2110.3.2 and 2110.3.3, except additional structural supports shall be provided at locations where a curved section joins a straight section, and at inflection points in multi-curved walls.
Glass unit masonry panels shall be isolated so that in-plane loads are not imparted to the panel.
Maximum total deflection of structural members supporting glass unit masonry shall not exceed 1600.
Glass unit masonry panels more than one unit wide or one unit high shall be laterally supported along their tops and sides. Lateral support shall be provided by panel anchors along the top and sides spaced not more than 16 inches (406 mm) o.c. or by channel-type restraints. Glass unit masonry panels shall be recessed at least 1 inch (25 mm) within channels and chases. Channel-type restraints shall be oversized to accommodate expansion material in the opening and packing and sealant between the framing restraints and the glass unit masonry perimeter units. Lateral supports for glass unit masonry panels shall be designed to resist applied loads, or a minimum of 200 pounds per lineal feet (plf) (2919 N/m) of panel, whichever is greater.
  Exceptions:
  1. Lateral support at the top of glass unit masonry panels that are no more than one unit wide shall not be required.
  2. Lateral support at the sides of glass unit masonry panels that are no more than one unit high shall not be required.
Single unit glass unit masonry panels shall conform to the requirements of Section 2110.4.3, except lateral support shall not be provided by panel anchors.
Glass unit masonry panels shall be provided with expansion joints along the top and sides at all structural supports. Expansion joints shall have sufficient thickness to accommodate displacements of the supporting structure, but shall not be less than 3 / 8 inch (9.5 mm) in thickness. Expansion joints shall be entirely free of mortar or other debris and shall be filled with resilient material. The sills of glass-block panels shall be coated with approved water-based asphaltic emulsion, or other elastic waterproofing material, prior to laying the first mortar course.
Glass unit masonry panels shall have horizontal joint reinforcement spaced not more than 16 inches (406 mm) on center, located in the mortar bed joint, and extending the entire length of the panel but not across expansion joints. Longitudinal wires shall be lapped a minimum of 6 inches (152 mm) at splices. Joint reinforcement shall be placed in the bed joint immediately below and above openings in the panel. The reinforcement shall have not less than two parallel longitudinal wires of size W1.7 (MW 11), and have welded cross wires of size W1.7 (MW 11).
A masonry fireplace is a fireplace constructed of concrete or masonry. Masonry fireplaces shall be constructed in accordance with this section, Table 2111.1 and Figure 2111.1.

TABLE 2111.1
SUMMARY OF REQUIREMENTS FOR MASONRY FIREPLACES AND CHIMNEYSa
ITEM LETTER REQUIREMENTS SECTION
Hearth and hearth extension thickness A 4-inch minimum thickness for hearth, 2-inch minimum thickness for hearth extension. 2111.9
Hearth extension (each side of opening) B 8 inches for fireplace opening less than 6 square feet. 12 inches for fireplace opening greater than or equal to 6 square feet. 2111.10
Hearth extension (front of opening) C 16 inches for fireplace opening less than 6 square feet. 20 inches for fireplace opening greater than or equal to 6 square feet.
2111.10
Firebox dimensions - 20-inch minimum firebox depth. 12-inch minimum firebox depth for Rumford fireplaces. 2111.6
Hearth and hearth extension reinforcing D Reinforced to carry its own weight and all imposed loads. 2111.9
Thickness of wall of firebox E 10 inches solid masonry or 8 inches where firebrick lining is used. 2111.5
Distance from top of opening to throat
F
8 inches minimum. 2111.7
2111.7.1
Smoke chamber wall thickness dimensions G 6 inches lined; 8 inches unlined. Not taller than opening width; walls not inclined more than 45 degrees from vertical for prefabricated smoke chamber linings or 30 degrees from vertical for corbeled masonry.
2111.8
Chimney vertical reinforcing H Four,No.,4,full-length bars for chimney up to 40 inches wide. Add two No. 4 bars for each additional 40 inches or fraction of width, or for each additional flue. 2111.3.1, 2113.3.1
Chimney horizontal reinforcing J ¼-inch ties at each 18 inches, and two ties at each bend in vertical steel. 2111.3.2, 2113.3.2
Fireplace lintel L Noncombustible material with 4-inch bearing length of each side of opening. 2111.7
Chimney walls with flue lining M 4-inch-thick solid masonry with 58-inch fireclay liner or equivalent.½-inch grout or airspace between fireclay liner and wall.
2113.11.1
Effective flue area (based on area of fireplace opening and chimney) P See Section 2113.16. 2113.6
Clearances
From chimney
From fireplace
From combustible trim or materials
Above roof


R

2 inches interior, 1 inch exterior or 12 inches from lining.
2 inches back or sides or 12 inches from lining.
6 inches from opening
3 feet above roof penetration, 2 feet above part of structure within 10 feet.


2113.19
2111.11
2111.12
2113.9
Anchorage strap
Number required
Embedment into chimney
Fasten to
Number of bolts

S
316 inch by 1 inch
Two
12 inches hooked around outer bar with 6-inch extension.
4 joists
Two ½-inch diameter.

2111.4

2113.4.1
Footing
Thickness
Width

T

12-inch minimum.
6 inches each side of fireplace wall.


2111.2
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929m2, 1 degree = 0.017 rad.
  1. This table provides a summary of major requirements for the construction of masonry chimneys and fireplaces. Letter references are to Figure 2111.1, which shows examples of typical construction. This table does not cover all requirements, nor does it cover all aspects of the indicated requirements. For the actual mandatory requirements of the code, see the indicated section of text.




For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE 2111.1
FIREPLACE AND CHIMNEY DETAILS
Footings for masonry fireplaces and their chimneys shall be constructed of reinforced concrete or solid masonry at least 12 inches (305 mm) thick and shall extend at least 6 inches (152 mm) beyond the face of the fireplace or foundation wall on all sides. Footings shall be founded on natural undisturbed earth or engineered fill below frost depth. In areas not subjected to freezing, footings shall be at least 12 inches (305 mm) below finished grade. Foundations and footings shall be designed to support the fireplace loading and shall have a minimum fire resistance rating of three hours.
Clean-out openings, located within foundation walls below fireboxes, when provided, shall be equipped with ferrous metal or masonry doors and frames constructed to remain tightly closed, except when in use. Clean outs shall be accessible and located so that ash removal will not create a hazard to combustible materials.
Masonry or concrete fireplaces shall be constructed, anchored, supported and reinforced as required in this chapter. In Seismic Design Category D, masonry and concrete fireplaces shall be reinforced and anchored as detailed in Sections 2111.3.1, 2111.3.2, 2111.4 and 2111.4.1 for chimneys serving fireplaces. In Seismic Design Category B or C, reinforcement and seismic anchorage is not required.
For fireplaces with chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars, anchored in the foundation, shall be placed in the concrete, between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section 2103.10. For fireplaces with chimneys greater than 40 inches (1016 mm) wide, two additional No. 4 vertical bars shall be provided for each additional 40 inches (1016 mm) in width or fraction thereof.
Vertical reinforcement shall be placed enclosed within 14 -inch (6.4 mm) ties or other reinforcing of equivalent net cross-sectional area, spaced not to exceed 18 inches (457 mm) on center in concrete; or placed in the bed joints of unit masonry at a minimum of every 18 inches (457 mm) of vertical height. Two such ties shall be provided at each bend in the vertical bars.
Masonry and concrete chimneys in Seismic Design Category D shall be anchored at each floor, ceiling or roof line more than 6 feet (1829 mm) above grade, except where constructed completely within the exterior walls. Anchorage shall conform to the following requirements.
Two 316 -inch by 1-inch (4.8 mm by 25 mm) straps shall be embedded a minimum of 12 inches (305 mm) into the chimney. Straps shall be hooked around the outer bars and extend 6 inches (152 mm) beyond the bend. Each strap shall be fastened to a minimum of four floor joists with two 12 -inch (12.7 mm) bolts.
Masonry fireboxes shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. When a lining of firebrick at least 2 inches (51 mm) in thickness or other approved lining is provided, the minimum thickness of back and side-walls shall each be 8 inches (203 mm) of solid masonry, including the lining. The approved lining shall be able to withstand a temperature of 2000°F (1093°C) without cracking. The width of joints between firebricks shall not be greater than 14 inch (6.4 mm). When no lining is provided, the total minimum thickness of back and side-walls shall be 12 inches (305 mm) of solid masonry. Firebrick shall conform to ASTM C 27 or ASTM C 1261 and shall be laid with medium-duty refractory mortar conforming to ASTM C 199.
Steel fireplace units are permitted to be installed with solid masonry to form a masonry fireplace provided they are installed according to either the requirements of their listing or the requirements of this section. Steel fireplace units incorporating a steel firebox lining shall be constructed with steel not less than 14 inch (6.4 mm) in thickness, and an air-circulating chamber which is ducted to the interior of the building. The firebox lining shall be encased with solid masonry to provide a total thickness at the back and sides of not less than 8 inches (203 mm), of which not less than 4 inches (102 mm) shall be of solid masonry or concrete. Circulating air ducts employed with steel fireplace units shall be constructed of metal or masonry.
The firebox of a concrete or masonry fireplace shall have a minimum depth of 20 inches (508 mm). The throat shall not be less than 8 inches (203 mm) above the fireplace opening. The throat opening shall not be less than 4 inches (102 mm) in depth. The cross-sectional area of the passageway above the firebox, including the throat, damper and smoke chamber, shall not be less than the cross-sectional area of the flue.
  Exception: Rumford fireplaces shall be permitted provided that the depth of the fireplace is at least 12 inches (305 mm) and at least one-third of the width of the fireplace opening, and the throat is at least 12 inches (305 mm) above the lintel, and at least 1/20 the cross-sectional area of the fireplace opening.
Masonry over a fireplace opening shall be supported by a lintel of noncombustible material. The minimum required bearing length on each end of the fireplace opening shall be 4 inches (102 mm). The fireplace throat or damper shall be located a minimum of 8 inches (203 mm) above the top of the fireplace opening.
Masonry fireplaces shall be equipped with a ferrous metal damper located at least 8 inches (203 mm) above the top of the fireplace opening. Dampers shall be installed in the fireplace or at the top of the flue venting the fireplace, and shall be operable from the room containing the fireplace. Damper controls shall be permitted to be located in the fireplace. The damper shall be able to withstand distortion from binding, cracking or corrosion when exposed to the fireplace operating temperature.
Smoke chamber walls shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. Corbeling of masonry units shall not leave unit cores exposed to the inside of the smoke chamber. The inside surface of corbeled masonry shall be parged smooth. Where no lining is provided, the total minimum thickness of front, back and side walls shall be 8 inches (203 mm) of solid masonry. When a lining of firebrick at least 2 inches (51 mm) thick, or a lining of vitrified clay at least 58 inch (15.9 mm) thick, is provided, the total minimum thickness of front, back and side walls shall be 6 inches (152 mm) of solid masonry, including the lining. Firebrick shall conform to ASTM C 27 or ASTM C 1261 and shall be laid with refractory mortar conforming to ASTM C 199.
The inside height of the smoke chamber from the fireplace throat to the beginning of the flue shall not be greater than the inside width of the fireplace opening. The inside surface of the smoke chamber shall not be inclined more than 45 degrees (0.76 rad) from vertical when prefabricated smoke chamber linings are used or when the smoke chamber walls are rolled or sloped rather than corbeled. When the inside surface of the smoke chamber is formed by corbeled masonry, the walls shall not be corbeled more than 30 degrees (0.52 rad) from vertical.
Masonry fireplace hearths and hearth extensions shall be constructed of concrete, ceramic tile, masonry or equivalent, supported by noncombustible materials, and reinforced to carry their own weight and all imposed loads. No combustible material shall remain against the underside of hearths or hearth extensions after construction.
The minimum thickness of fireplace hearths shall be 4 inches (102 mm).
The minimum thickness of hearth extensions shall be 2 inches (51 mm).
  Exception: When the bottom of the firebox opening is raised at least 8 inches (203 mm) above the top of the hearth extension, a hearth extension of not less than 3/8-inch-thick (9.5 mm) brick, concrete, stone, tile or other approved noncombustible material is permitted.
Hearth extensions shall extend at least 16 inches (406 mm) in front of, and at least 8 inches (203 mm) beyond, each side of the fireplace opening. Where the fireplace opening is 6 square feet (0.56 m2 ) or larger, the hearth extension shall extend at least 20 inches (508 mm) in front of, and at least 12 inches (305 mm) beyond, each side of the fireplace opening.
Where a fireplace is elevated or overhangs a floor, the hearth extension shall also extend over the area under the fireplace.
Any portion of a masonry fireplace located in the interior of a building or within the exterior wall of a building shall have a clearance to combustibles of not less than 2 inches (51 mm) from the front faces and sides of masonry fireplaces and not less than 4 inches (102 mm) from the back faces of masonry fireplaces. The airspace shall not be filled, except to provide fireblocking in accordance with Section 2111.13.
  Exceptions:
  1. Masonry fireplaces listed and labeled for use in contact with combustibles in accordance with UL 127, and installed in accordance with the manufacturer's installation instructions, are permitted to have combustible material in contact with their exterior surfaces.
  2. When masonry fireplaces are constructed as part of masonry or concrete walls, combustible materials shall not be in contact with the masonry or concrete walls less than 12 inches (306 mm) from the inside surface of the nearest firebox lining.
  3. Exposed combustible trim and the edges of sheathing materials, such as wood siding, flooring and drywall, are permitted to abut the masonry fireplace sidewalls and hearth extension, in accordance with Figure 2111.11, provided such combustible trim or sheathing is a minimum of 12 inches (306 mm) from the inside surface of the nearest firebox lining.
  4. Exposed combustible mantels or trim is permitted to be placed directly on the masonry fireplace front surrounding the fireplace opening provided such combustible materials shall not be placed within 6 inches (153 mm) of a fireplace opening. Combustible material within 12 inches (306 mm) of the fireplace opening shall not project more than 1/8 inch (3.2 mm) for each 1-inch (25 mm) distance from such opening.
Woodwork or other combustible materials shall not be placed within 6 inches (152 mm) of a fireplace opening. Combustible material within 12 inches (305 mm) of the fireplace opening shall not project more than 18 inch (3.2 mm) for each 1-inch (25mm) distance from such opening.
All spaces between fireplaces and floors and ceilings through which fireplaces pass shall be fire-blocked with approved noncombustible material securely fastened in place. The fire-blocking of spaces between wood joists, beams or headers shall be to a depth of 1 inch (25 mm) and shall only be placed on strips of metal or metal lath laid across the spaces between combustible material and the chimney.
Factory-built or masonry fireplaces covered in this section shall be equipped with an exterior air supply to ensure proper fuel combustion unless the room is mechanically ventilated and controlled so that the indoor pressure is neutral or positive.
Exterior combustion air ducts for factory-built fireplaces shall be listed components of the fireplace, and installed according to the fireplace manufacturer's instructions.
Listed combustion air ducts for masonry fireplaces shall be installed according to the terms of their listing and manufacturer's instructions.
The exterior air intake shall be capable of providing all combustion air from the exterior of the dwelling. The exterior air intake shall not be located within the garage, attic, basement or crawl space of the dwelling nor shall the air intake be located at an elevation higher than the firebox. The exterior air intake shall be covered with a corrosion-resistant screen of 14 -inch (6.4 mm) mesh.
Unlisted combustion air ducts shall be installed with a minimum 1-inch (25 mm) clearance to combustibles for all parts of the duct within 5 feet (1524 mm) of the duct outlet.
The combustion air passageway shall be a minimum of 6 square inches (3870 mm2) and not more than 55 square inches (0.035 m2), except that combustion air systems for listed fireplaces or for fireplaces tested for emissions shall be constructed according to the fireplace manufacturer's instructions.
The exterior air outlet is permitted to be located in the back or sides of the firebox chamber or within 24 inches (610 mm) of the firebox opening on or near the floor. The outlet shall be closable and designed to prevent burning material from dropping into concealed combustible spaces.
A masonry heater is a heating appliance constructed of concrete or solid masonry, hereinafter referred to as "masonry," having a mass of at least 1,760 pounds (800 kg), excluding the chimney and foundation, which is designed to absorb and store heat from a solid fuel fire built in the firebox by routing the exhaust gases through internal heat exchange channels in which the flow path downstream of the firebox includes at least one 180-degree (3.14 rad) change in flow direction before entering the chimney, and that delivers heat by radiation from the masonry surface of the heater that shall not exceed 230°F (110°C) except within 8 inches (203 mm) surrounding the fuel loading door(s).
Masonry heaters may be installed only when their use is permitted by the New York City Air Pollution Control Code. When such use is permitted, masonry heaters shall be installed in accordance with ASTM E 1602. If permitted, such appliances shall be operated in compliance with the New York City Air Pollution Control Code.
Seismic reinforcing shall not be required within the body of a masonry heater whose height is equal to or less than 2.5 times its body width and where the masonry chimney serving the heater is not supported by the body of the heater. Where the masonry chimney shares a common wall with the facing of the masonry heater, the chimney portion of the structure shall be reinforced in accordance with Sections 2113.3 and 2113.4.
Wood or other combustible framing shall not be placed within 4 inches (102 mm) of the outside surface of a masonry heater, provided the wall thickness of the firebox is not less than 8 inches (203 mm) and the wall thickness of the heat exchange channels is not less than 5 inches (127 mm). A clearance of at least 8 inches (203 mm) shall be provided between the gas-tight capping slab of the heater and a combustible ceiling. The required space between the heater and combustible material shall be fully vented to permit the free flow of air around all heater surfaces.
A masonry chimney is a chimney constructed of concrete or masonry, hereinafter referred to as "masonry." Masonry chimneys shall be constructed, anchored, supported and reinforced as required in this chapter.
  Chimneys shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to them to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71°C). Condensation shall not be allowed to develop to an extent that can cause deterioration of the chimney or vent.
  In any case, the outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas-fired appliances shall be vented in accordance with this code and NFPA 54.
  Chimneys shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads.
Chimneys shall be of adequate structural strength, and resistant to the temperatures to which they may be subjected and to the corrosive action of gases.
Termination caps shall not be permitted and a 3 inch (76 mm) minimum drain shall be installed to receive collected water. A positive means shall be provided to prevent water from entering the appliance.
  Exception: Termination caps shall be permitted on listed factory-built chimneys,
Decorative shrouds shall not be installed at the termination of factory-built chimneys except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with the manufacturers' installation instructions.
The lining in chimneys shall not be considered as taking either compression or tension stresses.
Expansion and contraction in chimney walls due to temperature variations shall be accommodated solely by the use of steel reinforcing rings.
Reinforcing rings shall be provided at all changes in wall thickness, at the top of the chimney, and above and below all flue openings.
Adjoining chimneys and vents shall be in accordance with Sections 2113.1.6.1 to 2113.1.6.8.
Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any previously constructed chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required, shall be exempt from this requirement. Such alterations shall be accomplished by one of the following means or a combination thereof:
  1. Carry up the previously constructed chimneys or vents to the height required in this chapter.
  2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter.
  3. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Protection.
After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment.
The owner of the new or altered building shall notify the owner of the building affected in writing at least 45 days before starting the work required and request written consent to do such work. Such notice shall be accompanied by plans indicating the manner in which the proposed alterations are to be made.
The plans and method of alteration shall be subject to the approval of the commissioner.
If consent is not granted by the owner of the previously constructed building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having submitted plans that conform to the requirements of this section, shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the new or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within forty-five days from the date of written request or fail to signify his or her refusal, he or she shall then assume all responsibilities as prescribed above.
It shall be the obligation of the owner of the new or altered building to:
  1. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; and
  2. Provide such essential services as are normally supplied by the equipment while it is out of service; and
  3. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; and
  4. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; and
  5. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the affected owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this Item, the commissioner may permit an equally safe alternative.
Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building.
The commissioner may grant a variance in accordance with the provisions of this code.
Foundations for masonry chimneys shall be constructed of concrete or solid masonry at least 12 inches (305 mm) thick and shall extend at least 6 inches (152 mm) beyond the face of the foundation or support wall on all sides. Footings shall be founded on natural undisturbed earth or engineered fill below frost depth. In areas not subjected to freezing, footings shall be at least 12 inches (305 mm) below finished grade.
Masonry or concrete chimneys shall be constructed, anchored, supported and reinforced as required in this chapter. In Seismic Design Category D, masonry and concrete chimneys shall be reinforced and anchored as detailed in Sections 2113.3.1, 2113.3.2, and 2113.4. In Seismic Design Category B or C, reinforcement and seismic anchorage is not required.
For chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars anchored in the foundation shall be placed in the concrete, between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section 2103.10. Grout shall be prevented from bonding with the flue liner so that the flue liner is free to move with thermal expansion. For chimneys greater than 40 inches (1016 mm) wide, two additional No. 4 vertical bars shall be provided for each additional 40 inches (1016 mm) in width or fraction thereof.
Vertical reinforcement shall be placed enclosed within 14 -inch (6.4 mm) ties, or other reinforcing of equivalent net cross-sectional area, spaced not to exceed 18 inches (457 mm) o.c. in concrete, or placed in the bed joints of unit masonry, at a minimum of every 18 inches (457 mm) of vertical height. Two such ties shall be provided at each bend in the vertical bars.
Masonry and concrete chimneys and foundations in Seismic Design Category D shall be anchored at each floor, ceiling or roof line more than 6 feet (1829 mm) above grade, except where constructed completely within the exterior walls. Anchorage shall conform to the following requirements.
Two 316 -inch by 1-inch (4.8 mm by 25 mm) straps shall be embedded a minimum of 12 inches (305 mm) into the chimney. Straps shall be hooked around the outer bars and extend 6 inches (152 mm) beyond the bend. Each strap shall be fastened to a minimum of four floor joists with two 12 -inch (12.7 mm) bolts.
Masonry chimneys shall not be corbeled more than half of the chimney's wall thickness from a wall or foundation, nor shall a chimney be corbeled from a wall or foundation that is less than 12 inches (305 mm) in thickness unless it projects equally on each side of the wall, except that on the second story of a two-story dwelling, corbeling of chimneys on the exterior of the enclosing walls is permitted to equal the wall thickness. The projection of a single course shall not exceed one-half the unit height or one-third of the unit bed depth, whichever is less. No masonry shall be corbeled from hollow or cavity wall masonry units.
The chimney wall or chimney flue lining shall not change in size or shape within 6 inches (152 mm) above or below where the chimney passes through floor components, ceiling components or roof components.
Where a masonry chimney is constructed with a fireclay flue liner surrounded by one wythe of masonry, the maximum offset shall be such that the centerline of the flue above the offset does not extend beyond the center of the chimney wall below the offset. Where the chimney offset is supported by masonry below the offset in an approved manner, the maximum offset limitations shall not apply. Each individual corbeled masonry course of the offset shall not exceed the projection limitations specified in Section 2113.5.
Chimneys shall not support loads other than their own weight unless they are designed and constructed to support the additional load. Masonry chimneys are permitted to be constructed as part of the masonry walls or concrete walls of the building.
Chimneys serving appliances that operate at less than 600°F (316°C) shall extend at least 3 feet (914 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimney located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined from Equation 21-5 and Table 2113.9, shall be at least as high as the construction.
  Chimneys serving appliances that operate at between 600°F (316°C) and 1000°F (538°C) shall extend at least 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such construction does not include other chimneys, vents or open structural framing. Any chimney located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 21-5 and Table 2113.9, shall be at least as high as the construction.

D = F × √A (Equation 21-5)

where:
D = Distance, in feet, measured from the center of the chimney outlet to the nearest edge of the construction.
F = Value determined from Table 2113.9.
A = Free area, in square inches, of chimney flue space.


TABLE 2113.9
“F” FACTOR FOR DETERMINING CHIMNEY DISTANCES
“F” FACTOR FOR DETERMINING CHIMNEY DISTANCES
Type of Fuel “F” Factor
600°F (316°C) and less 600°F (316°C) to 1000°F (538°C) Greater than 1000°F (538°C)
Gas 2 2 3
No. 2 fuel oil 2.5 2.5 3
No. 4, No. 6 fuel oils, solid fuels and incinerators 3 3 3
Where a spark arrestor is installed on a masonry chimney, the spark arrestor shall meet all of the following requirements:
  1. The net free area of the arrestor shall not be less than four times the net free area of the outlet of the chimney flue it serves.
  2. The arrestor screen shall have heat and corrosion resistance equivalent to 19-gage galvanized steel or 24-gage stainless steel.
  3. Openings shall not permit the passage of spheres having a diameter greater than 1/2 inch (12.7 mm) nor block the passage of spheres having a diameter less than 3/8 inch (9.5 mm).
  4. The spark arrestor shall be accessible for cleaning and the screen or chimney cap shall be removable to allow for cleaning of the chimney flue.
Masonry chimney walls shall be constructed of concrete, solid masonry units or hollow masonry units grouted solid with not less than 4 inches (102 mm) nominal thickness, or 8 inches (203 mm) nominal thickness for chimney walls extending more than 3 feet (914 mm) above the highest lateral support point.