Adopts With Amendments:

NFPA 13, 2016

Heads up: There are no amended sections in this chapter.
The requirements of Chapter 12 shall apply unless modified by this chapter.
Where fireproofing is not provided, steel columns shall be protected as follows:
  1. Storage exceeding 15 ft through 20 ft (4.6 m through 6.1 m) in height — one sidewall sprinkler directed to one side of the column at a 15 ft (4.6 m) level
  2. Storage exceeding 20 ft (6.1 m) in height — two sidewall sprinklers, one at the top of the column and the other at a 15 ft (4.6 m) level, both directed to the side of the column
The flow from a column sprinkler(s) shall be permitted to be omitted from the sprinkler system hydraulic calculations.
The protection specified in 18.2.1(1) and 18.2.1(2) shall not be required where storage in fixed racks is protected by in-rack sprinklers.
The protection specified in 18.2.1 shall not be required where ESFR or CMSA sprinkler systems that are approved for rubber tire storage are installed.
The rate of water supply shall be sufficient to provide the required sprinkler discharge density over the required area of application plus provision for generation of high-expansion foam and in-rack sprinklers where used.

18.3 Water Supplies

Amendment
This section has been amended by the state, county, or city.
Total water supplies shall be capable of providing flow for automatic sprinklers, and foam systems (if provided) for the duration required in Table 12.8.6.
Sprinkler discharge and area of application shall be in accordance with one of the following:
  1. Table 18.4(a) or Table 18.4(b) for standard spray sprinklers
  2. Table 18.4(c) for CMSA sprinklers
  3. Table 18.4(d) for ESFR sprinklers
Table 18.4(a) Protection Criteria for Rubber Tire Storage Using Control Mode Density/Area Sprinklers
Piling Method Pile Height [ft (m)] Sprinkler Discharge Density
[gpm/ft2 over ft2 (mm/min over m2)]
(see Note 1)
Areas of Application [ft2 (m2)]
(see Note 1)
Ordinary Temperature High Temperature
(see Note 1)
(1) On-floor storage Up to 5(1.5) 0.19(0.72) 2000 (186) 2000 (186)
(a) Pyramid piles, on-side Over 5 (1.5) to 12 (3.7) 0.30 (1.1) 2500 (232) 2500 (232)
(b) Other arrangements such that no horizontal channels are formed (see Note 2) Over 12 (3.7) to 18 (5.5) 0.60 (2.3) Not allowed 2500 (232)
(2) On-floor storage Up to 5 (1.5) 0.19 (0.72) 2000 (186) 2000 (186)
Tires, on-tread Over 5 (1.5) to 12 (3.7) 0.30 (1.1) 2500 (232) 2500 (232)
(3) Palletized portable rack storage Up to 5 (1.5) 0.19 (0.72) 2000 (186) 2000 (186)
On-side or on-tread Over 5 (1.5) to 20 (6.1) See Table 18.4(b)
Over 20 (6.1) to 30 (9.1) 0.30 (1.1) plus high-expansion foam 3000 (280) 3000 (280)
(4) Palletized portable rack storage, on-side Up to 5 (1.5) 0.19 (0.72) 2000 (186) 2000 (186)
Over 5 (1.5) to 20 (6.1) See Table 18.4(b)
Over 20 (6.1 m) to 25 (7.6) 0.60 (2.2) and Not allowed 5000 (465)
  0.90 (3.4) (see Note 3) or Not allowed 3000 (280)
  0.75 (2.8) with 1-hour fire-resistive rating of roof and ceiling assembly Not allowed 4000 (370)
(5) Open portable rack storage, on-side or on-tread Up to 5 (1.5) 0.19 (0.72) 2000 (186) 2000 (186)
Over 5 (1.5) to 12 (3.7) 0.60 (2.2) 5000 (465) 3000 (280)
Over 12 (3.7) to 20 (6.1) 0.60 (2.2) and Not allowed 5000 (465)
  0.90 (3.4) (see Note 3) or Not allowed 3000 (280)
  0.30 (1.1) plus high-expansion foam 3000 (280) 3000 (280)
(6) Open portable rack storage, laced Over 12 (3.7) to 20 (6.1) 0.60 (2.2) and Not allowed 5000 (465)
  0.90 (3.4) (see Notes 3 and 5) Not allowed 3000 (280)
(7) Single-, double-, and multiple-row fixed rack storage on pallets, on-side, or on-tread without shelves Up to 5 (1,5) 0.19 (0.72) 2000 (186) 2000 (186)
Over 5 (1.5) to 20 (6.1) See Table 18.4(b) or 0.40 (1.5) plus one level in-rack sprinklers or 3000 (280) 3000 (280)
  0.30 (1.1) plus high-expansion foam 3000 (280) 3000 (280)
Over 20 (6.1) to 30 (9.1) 0.30 (1.1) plus high-expansion foam Not allowed 3000 (280)
(8) Single-, double-, and multiple-row fixed rack storage without pallets or shelves, on-side or on-tread Up to 5 (1.5) 0.19 (0.72) 2000 (186) 2000 (186)
Over 5 (1.5) to 12 (3.7) 0.60 (2.2) 5000 (465) 3000 (280)
0.40 (1.5) plus one level in-rack sprinklers 3000 (280) 3000 (280)
Over 12 (3.7) to 20 (6.1) 0.60 (2.2) and Not allowed 5000 (280)
  0.90 (3.4) (see Note 3) or Not allowed 3000 (280)
  0.40 (1.5) plus one level in-rack sprinklers or 3000 (280) 3000 (280)
  0.30 (1.1) plus high-expansion foam 3000 (280) 3000 (280)
Over 20 (6.1) to 30 (9.1) 0.30 (1.1) plus high-expansion foam Not allowed 3000 (280)
Notes:
(1) Sprinkler discharge densities and areas of application are based on a maximum clearance to ceiling of 10 ft (3.0 m) with the maximum height of storage anticipated.
(2) Laced tires on-floor, vertical stacking on-side (typical truck tires), and off-road tires. Laced tires are not stored to a significant height by this method due to the damage inflicted on the tire (i.e., bead).
(3) Water supply shall fulfill both requirements.
(4) Shelf storage of rubber tires shall be protected as solid rack shelving.
(5) This protection scheme is for use with K-16.8 (240) or larger control mode sprinklers only. Maximum clearance to ceiling can be increased to 14 ft (4.3 m) with this scheme.
Table 18.4(b) Control Mode Density/Area Sprinklers System Density (gpm/ft2 over ft2) for Palletized Portable Rack Storage and Fixed Rack Storage of Rubber Tires with Pallets Over 5 ft (1.5 m) to 20 ft (3.7 m) in Height
Storage Height
[ft (m)]
Sprinkler Temperature
High Temperature Ordinary Temperature
>5 to 10 (1.5 to 3.0) 0.32/2000 (1.2/186) 0.32/2000 (1.2/186)
>10 to 12 (3.0 to 3.7) 0.39/2000 (1.5/186) 0.39/2600 (1.5/241)
>12 to 14 (3.7 to 4.3) 0.45/2000 (1.7/186) 0.45/3000 (1.7/300)
>14 to 16 (4.3 to 4.9) 0.5/2300 (1.9/214) 0.5/3450 (1.9/345)
>16 to 18 (4.9 to 5.5) 0.55/2600 (2.1/241) 0.55/4100 (2.1/410)
>18 to 20 (5.5 to 6.1) 0.6/2800 (2.3/280) 0.6/5000 (2.3/465)
Table 18.4(c) Control Mode Specific Application (CMSA) Protection for Rubber Tires
Piling Method Maximum Storage Height Maximum Ceiling/Roof Height K-Factor Type of System Number of Sprinklers Operating Pressure
ft m ft m
Rubber tire storage, on-side or on-tread, in palletized portable racks, or open portable racks, or fixed racks without solid shelves 25 7.6 32 10 11.2 (160) Wet 15 75 psi (5.2 bar)
25 7.6 32 10 16.8 (240) Wet 15 35 psi (2.4 bar)
Table 18.4(d) Early Suppression Fast-Response (ESFR) Sprinklers for Protection of Rubber Tires (see Note 1)
Piling Method Pile Height Maximum Building Height Nominal K-factor Orientation Number of Sprinklers Minimum Operating Pressure (see Note 2)
ft m psi bar
Rubber tire storage, on-side or on-tread, in palletized portable racks, open portable racks, or fixed racks without solid shelves Up to 25 ft (7.6 m) 30 9.1 14.0
(200)
Upright/pendent 12 (see Note 2) 50 3.4
16.8
(240)
Upright/pendent 12 (see Note 2) 35 2.4
22.4
(320)
Pendent 12 (see Note 2) 25 1.7
25.2
(360)
Pendent 12 (see Note 2) 15 1.0
Rubber tire storage, on-side, in palletized portable racks, open portable racks, or fixed racks without solid shelves Up to 25 ft
(7.6 m)
35 11 14.0
(200)
Upright/pendent 12 (see Note 2) 75 5.2
16.8
(240)
Pendent 12 (see Note 2) 52 3.6
22.4
(320)
Pendent 12 (see Note 2) 35 2.4
25.2
(360)
Pendent 12 (see Note 2) 25 1.7
On-tread, on-side, and laced tires in open portable steel racks or palletized portable racks Up to 25 ft
(7.6 m)
30 9.1 14.0
(200)
Pendent 20 (see Notes 3 and 4) 75 5.2
16.8
(240)
Pendent 20 (see Notes 3 and 4) 52 3.6
Rubber tire storage, on-side, in palletized portable racks Up to 25 ft
(7.6 m)
40 12 16.8
(240)
Pendent 12 52 3.6
Rubber tire storage, on-tread, or laced in open portable steel racks Up to 25 ft
(7.6 m)
40 12 25.2
(360)
Pendent 12 40 2.8
On-tread, on-side, and laced tires in open portable steel racks or palletized portable racks Up to 30 ft
(9.1 m)
40 12 25.2
(360)
Pendent 12 75 5.2
Notes:
(1) Wet systems only.
(2) The shape of the design area shall be in accordance with 14.4.3.
(3) Where used in this application, ESFR protection is expected to control rather than to suppress the fire.
(4) The design area shall consist of the most hydraulically demanding area of 20 sprinklers, consisting of five sprinklers on each of four branch lines. The design shall include a minimum operating area of 1600 ft2 (149 m2).
In-rack sprinklers, where provided, shall be installed in accordance with Chapter 17, except as modified by 18.5.2 through 18.5.4.
The maximum horizontal spacing of sprinklers in racks shall be 8 ft (2.4 m).
Water demand for sprinklers installed in racks shall be based on simultaneous operation of the most hydraulically remote 12 sprinklers where only one level is installed in racks.
Sprinklers in racks shall discharge at not less than 30 psi (2.1 bar).
Where high-expansion foam systems are installed in accordance with NFPA 11, a reduction in sprinkler discharge density to one-half the density specified in Table 18.4(a) or 0.24 gpm/ft2 (9.8 mm/min), whichever is higher, shall be permitted.
Linked Resources
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Bookmarks
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More