Heads up:
There are no amended sections in this chapter.
SCOPE
Part 8 contains general requirements for new and existing equipment.
NOTE: Requirements 8.1, 8.6, 8.7, 8.9, 8.10, and 8.11 apply to both new and existing installations.
Key(s) used to access or operate elevator, escalator, moving walk, dumbwaiter, and material lift equipment shall conform to the following:
(a) Keys used to open any other lock in the building shall not access or operate the devices classified as Security Group 1, 2, 3, or 4.
(b) The same key shall be permitted to access or operate all of the devices within only one assigned group (see 8.1.2, 8.1.3, 8.1.4, or 8.1.5), and not those in any other group except as indicated in 8.1.1(c).
(c) The keys for Group 1 devices shall also be permitted to operate Group 2, 3, and 4 devices. The keys for Group 2 devices shall be permitted to operate Group 3 and 4 devices.
(d) Keys shall be kept on the premises in a location readily accessible to the personnel in the assigned group, but not where they are accessible to the general public.
(e) Elevator personnel shall have access to all assigned groups.
Group 1 covers access or operation of equipment restricted to elevator personnel, except as noted.
NOTE: See the following:
(b) Requirement 2.7.3.4.6, access openings in machinery space floor, etc.
(d) Requirement 2.7.5.1.4, equipment access panels.
(f) Requirement 2.7.6.4.3(b), access to the means to move the car from outside the hoistway.
(g) Requirement 2.7.6.4.3(d), access to removable means to move the car from outside the hoistway.
(h) Requirement 2.7.6.5.2(b), inspection and test panel enclosure.
(j) Requirement 3.19.4.5, access to pressure gauge fittings.
(k) Requirement 2.11.1.2(h), emergency access doors. (Shall also be made available to emergency personnel during an emergency.)
(l) Requirement 2.12.6.2.4, hoistway door unlocking device. (Shall also be made available to emergency personnel during an emergency.)
(m) Requirement 2.12.7.2.2, hoistway access switch.
(n) Requirement 2.12.7.3.1, hoistway access enabling switch or its locked cover.
(o) Requirement 2.26.14.3(b), in-car inspection operation transfer switch.
(p) Requirement 2.26.2.21, in-car stop switch or its locked cover.
(q) Requirement 4.2.5.2, screw machine controllers located away from hoistway, machine room, or machinery space.
(r) Requirement 4.2.5.5, screw machine access panels.
(t) Requirement 5.1.11.1.2(d), inclined elevator uphill end emergency exit.
(u) Requirement 5.7.8.3, hoistway door unlocking device.
(v) Requirement 7.1.12.4, power and hand dumbwaiters without automatic transfer devices hoistway access switch.
(w) Requirement 7.9.2.15, electric material lifts with automatic transfer devices car-mounted operating devices.
Group 2 covers access or operation of equipment by authorized and elevator personnel.
NOTE: See the following:
(c) Requirement 2.11.14, access openings for cleaning of car and hoistway enclosures.
(d) Requirement 2.14.2.6(b), access openings for cleaning of car and hoistway enclosure.
(e) Requirement 2.14.7.2.1(b), car light control switch or its locked cover.
(f) Requirement 3.19.4.1, access to manually operated shutoff valve.
(g) Requirement 5.6.1.25.2(b), rooftop elevator keyed operation switch.
(j) Requirement 6.2.6.2.1(d), moving walk starting switch.
Group 3 covers access or operation of equipment by emergency, authorized, and elevator personnel.
NOTE: See the following:
(a) Requirements 2.27.2.4.1 and 2.27.8, emergency or standby power access selector switch.
(d) Side emergency exit doors on existing equipment.
(e) Firefighters Emergency Operation Phase I and Phase II and Occupant Evacuation Operation shall be by New York City standard key 2642 and FDNY standard key 1620.
Group 4 covers access or operation of equipment not classified as Group 1, 2, or 3.
NOTE: See the following:
(a) Requirement 5.3.1.18.3, private residence elevator key-operated switch for exterior operation.
Requirement 8.2 contains certain design data, formulas, and charts for the designer. It is not intended to limit design. More detailed design and calculation methods shall be permitted to be used, provided that the stresses and deflections required by other sections of this Code are not exceeded.
The following formulas shall be used for determining the minimum rated load of passenger elevators (see also 2.16.1).
For an elevator having an inside net platform area of not more than 4.65 m (50 ft2)
(SI Units)
W = 35A2 + 325A
(Imperial Units)
W = 0.667A2 + 66.7A
For an elevator having an inside net platform area of more than 4.65 m2 (50 ft2)

(SI Units)
W = 2.45A2 + 610A — 620
(Imperial Units)
W = 0.0467A2 + 125A — 1,367
where
A | = | inside net platform area, m2 (ft2) as specified in Fig. 8.2.1.2 |
W | = | minimum rated load, kg (lb) |
Figure 8.2.1.2 gives the minimum rated loads for various inside net platform areas.
Fig. 8.2.1.2 Minimum Rated Load for Passenger Elevators


The stresses and deflections in side-post-type car frame and platform members shall be based on the data and formulas listed in 8.2.2.
All stresses and their resultant deflections, not only those based on the data and formulas listed in this Section, shall be considered when side-post-type car frames are located off the platform centerline by more than one-eighth of the distance from the front to the back of the platform.
For cars with corner-post, underslung-type, or other special car frame and platform construction, the formulas and specified methods of calculation of loads and the resulting stresses and deflections do not generally apply and shall be modified to suit the specific conditions and requirements in each case.
The maximum allowable stresses and deflections of members of all car frames and platforms shall be not more than those permitted by 2.15.10 and 2.15.11.
The symbols used in the formulas in 8.2.2 shall have the following meaning:
A | = | net area of section, m2 (in.2) |
B | = | inside clear width of car, mm (in.) |
C | = | net weight of complete elevator car, kg (lb) |
D | = | distance between guide rails, mm (in.) |
E | = | modulus of elasticity of material used, MPa (psi) |
G | = | load supported by crosshead with the maximum load for the class of loading in car at rest at top terminal landing, kg (lb) |
H | = | vertical center distance between upper and lower guide shoes (or rollers), mm (in.) |
I | = | moment of inertia of member, gross section, mm4 (in.4) |
K | = | turning moment as determined by class of loading, N•mm (lbf-in.) |
L | = | free length of uprights (distance from lowest fastening in crosshead to top fastening in plank), mm (in.) |
R | = | least radius of gyration of section, mm (in.) |
W | = | rated load, kg (lb) |
Z | = | combined section moduli of plank members, gross section, mm3 (in.3) |
Zu | = | section modulus of one upright, gross section, mm3 (in.3) |
The stresses in the car frame crosshead shall be based on the total load supported by the crosshead with the car and the maximum load for the class of loading in the car when at rest at the top terminal landing.
The stresses in the car frame plank when the stringers are supported directly on the plank members shall be based on the sum of five-eighths of the platform weight uniformly distributed plus the concentrated loads due to the tension in the compensation means and the traveling cables with car at top of its travel plus the loading specified in 8.2.2.3(a) or (b).
(a) For passenger and Class A freight loading, five-eighths of the rated load uniformly distributed.
(b) For Classes B and C freight loading, the loading as specified in 8.2.2.6.
In calculating the stress resulting from oil-buffer engagement, one-half the sum of the weight of the car and its rated load shall be considered as being concentrated at each end of the plank with the buffer force applied at the middle. The buffer force shall be considered to be that required to produce gravity retardation with rated load in the car.
The following formula shall be used to determine the stress resulting from buffer engagement:
(SI Units)

(Imperial Units)

Where more than one oil buffer is used, the formula shall be modified to suit the location of the buffers.
NOTE (see 8.2.2.4): Symbols used in the preceding formula are defined in 8.2.2.1.1.
The total stress in each car frame upright due to tension and bending, and the slenderness ratio of each upright and its moment of inertia, shall be determined in accordance with the following formulas.
(SI Units)

(Imperial Units)

Where KL/4HZu is the bending stress in each upright in the plane of the frame due to live load W on the platform for the class of loading A, B, or C for which the elevator is to be used (see 2.16.2.2); G/2A is the tensile strength in each upright, and K is determined by the following formulas [see Fig. 8.2.2.5.1]:
(a) For Class A freight loading or passenger loading
(SI Units)

(Imperial Units)

(b) For Class B freight loading
(SI Units)

whichever is greater.
(Imperial Units)

whichever is greater.
(c) For Class C freight loading
(SI Units)

(Imperial Units)

NOTE (8.2.2.5.1): Symbols used in the preceding formulas are defined in 8.2.2.1.1.
Fig. 8.2.2.5.1 Turning Moment Based on Class of Loading

GENERAL NOTE: See 8.2.2.5.1 for formulas in SI Units.
The slenderness ratio L/R for uprights subject to compressions other than those resulting from safety and buffer action shall not exceed 120. Where the upper side-brace connections on passenger elevator car frame uprights are located at a point less than two-thirds of L from the bottom, (top fastening in car frame plank) a slenderness ratio of L/R not exceeding 160 is permissible (L/R ≤ 160).
NOTE (8.2.2.5.2): Symbols used in the above formulas are defined in 8.2.2.1.1.
The moment of inertia of each upright shall be not less than determined by the following formula:
(SI Units)

(Imperial Units)

NOTE (8.2.2.5.3): Symbols used in the preceding formula are defined in 8.2.2.1.1.
The calculation for stresses in the platform members of freight elevators shall be based on the following concentrated loads assumed to occupy the position that will produce the maximum stress:
(a) for Class A Loading, 25% of the rated load
(b) for Class B Loading, 75% of the rated load or 15 400 kg (34,000 lb), whichever is less, divided into two equal parts 1 525 mm (60 in.) apart
(c) for Class C1 Loading, with a load rating of 9 000 kg (20,000 lb) or less, 80% of the rated load divided into two equal parts, 765 mm (30 in.) apart
(d) for Class C2 Loading, with a load rating of 9 000 kg (20,000 lb) or less, 80% of the rated load or of the loaded truck weight, whichever is greater, divided into two equal parts, 765 mm (30 in.) apart
(e) for Class C1 or C2 Loading, with a rated load in excess of 9 000 kg (20,000 lb), 80% of the 9 000 kg (20,000 lb) or of the maximum loaded truck weight, whichever is greater, divided into two equal parts, 765 mm (30 in.) apart
(f) for Class C3 Loading, determined on the basis of the actual loading conditions but not less than that required for Class A loading
The stresses in hoisting rope hitch plates and shapes shall be based on the total applied rope load with the car and its rated load at rest at the top terminal landing.
The following formulas give the buffer reaction and the impact on the car and counterweight oil buffer supports resulting from buffer engagement [see 2.1.2.3(a) or 3.22.1.2.1]:
(a) Buffer Reaction
(SI Units)

(Imperial Units)

(b) Impact
P = 2R
The following formulas give the buffer reaction and the impact on the supports of car and counterweight spring buffers that do not fully compress under the conditions outlined in 2.1.2.3(a):
(a) Buffer reaction
(SI Units)

(Imperial Units)

(b) Impact
P = R
where
P | = | impact, N (lbf) |
R | = | buffer reaction, N (lbf) |
S | = | buffer stroke, m (ft) |
V | = | speed at impact (for electric), m/s (ft/s); operating speed in the down direction (for hydraulic), m/s (ft/s) |
W | = | weight of car plus rated load or weight of counterweight, kg (lb) |
The following formula gives the value of the stopping distance based on gravity retardation from any initial velocity (see 2.4.6, 2.4.8, 2.4.9, and 2.22.4.1):
(SI Units)
S = 51V2
(Imperial Units)

where
S | = | free fall (gravity stopping distance), mm (in.) |
V | = | initial velocity, m/s (ft/min) |
Figure 8.2.4 shows the gravity stopping distances from various initial velocities.
Fig. 8.2.4 Gravity Stopping Distances

The following formulas shall be used to determine the maximum and minimum stopping distances for Type B car and counterweight safeties (see 2.17.3):
(SI Units)

(Imperial Units)

where
S | = | maximum stopping distance, m (ft) |
S' | = | minimum stopping distance, m (ft) |
V | = | governor tripping speed, m/s (ft/min) |
Figure 8.2.6 shows the maximum and minimum stopping distances from various governor tripping speeds.
Fig. 8.2.6 Stopping Distances for Type B Car and Counterweight Safeties



Figure 8.2.7 shows the minimum factors of safety for suspension wire ropes of power elevators for various rope speeds (see 2.20.3).

(a) Where slenderness ratio of plunger is less than 120
(SI Units)

(Imperial Units)

(b) Where slenderness ratio of plunger is greater than 120
(SI Units)

(Imperial Units)

Formulas are for steel where
A | = | net sectional area of plunger (area of metal), m2 (in.2) |
L | = | maximum free length of plunger, mm (in.). Where a plunger-follower guide conforming to 3.18.2.7 is used, L shall be taken as one-half the amount that the free length would be if no follower guide were provided. |
R | = | radius of gyration of plunger section, mm (in.) |
W | = | allowable gross weight to be sustained by plunger, N (lbf). Where a counterweight is provided, the weight of the counterweight plus the unbalanced weight of the counterweight ropes shall be permitted to be deducted in determining W. In determining W, one-half of the weight of the plunger shall be included except where a plunger-follower guide conforming to 3.18.2.7 is used, in which case, three-fourths of the plunger weight shall be included. |
W/A | = | fiber stress, kPa (psi) |
NOTE [8.2.8.1.1(a) and (b)]: Figure 8.2.8.1.1 has been calculated from the formulas given in 8.2.8.1.1 for the more usual pipe sizes and pipe schedules and indicate allowable gross loads directly.
(c) Plungers having a free length of 7.6 m (25 ft) or less shall be permitted to be accepted without further examination for strength and elastic stability, provided all of the following conditions exist:
(1) the working pressure is 2 070 kPa (300 psi) or less
(2) the plunger is 100 mm (4 in.) nominal pipe size or larger
(3) pipe not lighter than schedule 40 is used, and not more than 1.6 mm (0.063 in.) of metal has been removed from the wall thickness in machining
(d) Plungers With Varying Cross Section. For plungers with varying cross section, the stress shall be calculated for a factor of safety of at least 3 using accepted methods for elastic stability.
Fig. 8.2.8.1.1 Allowable Gross Loads

GENERAL NOTES:
- Curves are based upon the removal of not more than 1.5 mm (0.0625 in.) from the wall thickness in machining.
- Curves stop at 18 m (59 ft) for convenience only. For plunger sizes or lengths not shown on this chart, see the applicable formula in 8.2.8.1.1.
Fig. 8.2.8.1.1 Allowable Gross Loads (Cont'd)

GENERAL NOTES:
- Curves are based upon the removal of not more than 1.5 mm (0.0625 in.) from the wall thickness in machining.
- Curves stop at 18 m (59 ft) for convenience only. For plunger sizes or lengths not shown on this chart, see the applicable formula in 8.2.8.1.1.
For plungers subject to bending, the stresses due to bending as determined by the following formulas shall be subtracted from the stresses W/A as determined by the applicable formula in 8.2.8.1.1.
(SI Units)

(Imperial Units)

where
e | = | eccentricity of Wb, mm (in.) |
S | = | stress due to bending, MPa (psi) |
Wb | = | maximum eccentric load, N (lbf). Where any or all of this load is caused by moving wheel loads imposed on the edge of the platform, the total of such loads shall be doubled for impact (see 8.2.2.6). |
Z | = | section modulus of plunger section, mm3 (in.3) |
For plungers subjected to external pressure, the working pressure shall be not more than that indicated by the following formulas.
(a) Where the ratio of t/D is less than 0.023:
(SI Units)

(Imperial Units)

(b) Where the ratio of t/D is greater than 0.023:
(SI Units)

(Imperial Units)

where
D | = | external finished diameter, mm (in.) |
p | = | working pressure, kPa (psi) |
t | = | finished wall thickness, mm (in.) |
Telescoping plungers shall have each plunger section internally guided. If more than two movable sections are used, plunger follower guides shall be provided for each plunger section. In the formulas in 8.2.8.1.1(a) and 8.2.8.1.1(b), the values of A and R shall be for the smallest plunger section. When plunger follower guides are used, the value of L shall be the maximum free length of the smallest section in millimeters (inches). When plunger follower guides are not used, the value of L shall be taken as 1.4 times the maximum free length of the smallest plunger section.
Cylinders shall be designed and constructed in accordance with the following formula:

where
C | = | depth of the thread or groove, mm (in.) |
d | = | internal diameter, mm (in.) |
p | = | working pressure, kPa (psi) |
S | = | allowable stress, kPa (psi) (see 8.2.8.5.2) |
t | = | minimum thickness of wall, mm (in.) |
Heads of cylinders and heads of plungers subject to fluid pressure shall be designed and constructed in accordance with one of the following applicable formulas:
(a) Flat unreinforced heads

(b) Dished seamless hemispherical heads, concave to pressure

(c) Dished seamless ellipsoidal heads, concave to pressure (ellipsoidal heads in which one-half of the minor axis equals one-quarter the inside diameter of skirt),

where
D | = | inside diameter of skirt, mm (in.) |
d | = | diameter of head between supporting edges, mm (in.) |
p | = | working pressure, kPa (psi) |
r | = | radius to which head is dished, measured on concave side (not greater than d), mm (in.) |
S | = | allowable stress, kPa (psi) (see 8.2.8.5.2) |
t | = | minimum thickness of head, mm (in.) |
The minimum wall thickness of pipe shall be 1.65 mm plus C or as determined by the following:

or

where
C | = | 1.3 mm (0.05 in.) for threaded pipe up to 9.5 mm (3/8 in.) pipe size, the depth of the thread in millimeters for threaded pipe over 9.5 mm (3/8 in.) pipe size, the depth of groove in millimeters for grooved pipe, or 0.000 for other pipe or unreduced thickness |
D | = | the outside diameter of pipe, mm (in.) |
e | = | the joint efficiency: 1 for seamless pipe; 0.85 for electric resistance welded pipe |
p | = | the maximum working pressure, kPa (psi) |
t | = | the minimum wall thickness, mm (in.) |
S | = | the allowable stress, based on a factor of safety in accordance with 8.2.8.5.2, kPa (psi) |
Steel pipes and fittings used for gauge ports need not comply with this formula, but shall be a minimum of Schedule 80 pipe and maximum length of 75 mm (3 in.), except as permitted by 3.19.2.4.
Except as required in 3.19.3.3.1(b), the minimum factor of safety for components subject to fluid pressure shall be as follows:

where
E | = | percent elongation in 50 mm (2 in.) gauge length as per ASTM Standard E8 expressed as a whole number (e.g., 20% = 20 and 5% = 5). The minimum allowable E shall be 5. |
F | = | minimum factor of safety based on 0.2% proof stress yield point. The minimum allowable F shall be 3. |
The allowable stress to be used in 8.2.8.2 through 8.2.8.4 shall be determined as follows:

where
F | = | minimum factor of safety based on 0.2% proof stress yield point as determined in 8.2.8.5.1 |
S | = | allowable stress kPa (psi) |
Y.P. | = | yield point, based on 0.2% proof stress yield point, kPa (psi) |
The maximum pressure to be applied by the plunger gripper to avoid local buckling should be calculated as follows for steel:
(SI Units)

(Imperial Units)

where
D | = | outside diameter of plunger, mm (in.) |
Pmax | = | maximum pressure, MPa (psi) |
t | = | minimum wall thickness, mm (in.) |
The stresses and deflections in side-post-type car frame and platform members shall be based on the data and formulas listed in 8.2.9.
All stresses and their resultant deflections, not only those based on the data and formulas in this Section, shall be considered when side-post-type car frames are located off the platform center line by more than one-eighth of the distance from the front to the back of the platform.
For cars and corner-post, sub-post, or other special car frame and platform construction, the formulas and specified methods of calculation of loads and the resulting stresses and deflections do not generally apply and shall be modified to suit the specific conditions and requirements in each case.
The maximum allowable stresses and deflections of members of all car frames and platforms shall be not more than those permitted by 3.15.2.
The maximum stresses in car frame uprights that are normally subject to compression shall be such that the quantity [(fa / Fa) + (fb / Fb)] does not exceed unity
where
Fa | = | allowable axial compressive unit stress [not exceeding 117 200 — 3.344 (L/R)2 in SI units and 17,000 — 0.485 (L/R)2 in Imperial units] |
fa | = | actual axial compressive unit stress based on gross section |
Fb | = | allowable bending unit stress [113 MPa (16,500 psi), if area basis is gross section or 138 MPa (20,000 psi) if area basis is net section] |
fb | = | actual bending unit stress |
L | = | free length of uprights (distance from lowest fastening in crosshead to top fastening in plank), mm (in.) |
R | = | least radius of gyration of section, mm (in.) |
The stresses in the car frame crosshead shall be based on the total load, if any, supported by the crosshead.
The crosshead members(s) and connection between the crosshead and upright (stile) shall be designed to resist the bending moment, shear and axial forces transferred between the upright and the crosshead.
The bending stresses in the car frame planks due to the normal loading shall be based on the following loads:
(a) concentrated load(s) located at their point of application equal to the total maximum static load on all the driving members lifting the car divided by the number of lifting members [see Fig. 8.2.9.1.3, sketch (a)]
(b) five-eighths of the platform weight uniformly distributed over the length of the planks when the platform members are supported directly by the plank members [see Fig. 8.2.9.1.3, sketch (b)]
(c) the duty load distribution is as follows:
(1) for passenger and Class A freight loading, five-eighths of the rated load uniformly distributed over the length of the planks when the platform members are supported directly by the plank members [see Fig. 8.2.9.1.3, sketch (c)]
(2) for Classes B and C freight loading, the loading in conformance with 8.2.2.6
(d) the balance of loads shall be taken as acting at their respective point(s) of application [see Fig. 8.2.9.1.3, sketch (d)]
(e) where the platform members are only supported directly by the planks at or adjacent to the ends of the planks, 8.2.9.1.3(b) and 8.2.9.1.3(c)(1) do not apply, and concentrated loads equal to one-half of the total maximum static load on all the driving members shall be applied at each end of the planks [see Fig. 8.2.9.1.3, sketch (e)]
Fig. 8.2.9.1.3 Load Distribution

D | = | distance between guide rails, m (in.) |
W | = | rated load, kg (lb) (passenger or Class A freight) |
WP | = | platform weight, kg (lb) |
P1, P2, P3, Pm | = | balance of loads acting on the plank members located at their respective points of application. Such loads typically include the weights of cab and doors, carframe members and guide shoes, traveling cables, electrical devices, door devices, and the balance of load distributions of the platform weight and rated load not distributed to the plank members. |
P5 | = | total maximum static load on all the driving members, kg (lb) |
GENERAL NOTES:
- 1 mm= 1 in./25.4 (1 in.= 25.4 mm);
- 1 kg= 1 lb/0.454 (1 lb= 0.454 kg).
The stresses in each car frame upright due to compression and bending and the slenderness ratio of each upright and its moment of inertia shall be determined in accordance with the following formulas:
(a) Stresses Due to Bending

where
fb | = | the bending stress in each upright in the plane of the frame due to the live load W on the platform for the class of loading A, B, or C for which the elevator is to be used (see 2.16.2.2 and 3.16) |
K | = | turning moment in N•m (lbf-in.) as determined by the class of loading (see Fig. 8.2.2.5.1) by the following formulas |
(1) For Class A freight loading or passenger loading
(SI Units)

(Imperial Units)

(2) For Class B freight loading
(SI Units)

(Imperial Units)

whichever is greater.
(3) For Class C freight loading
(SI Units)

(Imperial Units)

NOTE [8.2.9.1.4(a)]: Symbols used in the above formulas are defined in 8.2.2.1.1.
(b) Stresses Due to Compression
fa = compressive stress in each upright
(c) Slenderness Ratio. The slenderness ratio L/R for uprights subject to compressions other than those resulting from buffer or safety action shall not exceed 120. Where the upper side-brace connections on passenger elevator car frame uprights are located at a point less than two-thirds of L from the bottom (top fastening in car frame plank), a slenderness ratio of L/R not exceeding 160 is permissible.
(d) Moment of Inertia. The moment of inertia of each upright shall be not less than determined by the following formula:
(SI Units)

(Imperial Units)

NOTE [8.2.9.1.4(d)]: Symbols used in the above formula are defined in 8.2.2.1.1.
The following formula shall be used to determine the minimum stroke of oil buffers used for inclined elevators (see 5.1.17.4):
(SI Units)

(Imperial Units)

where
Smin | = | minimum oil buffer stroke, mm (in.) |
υ | = | rated car speed, m/s (ft/min) |
θ | = | angle of inclination from horizontal (degrees) |
The following formulas shall be used to determine the maximum and minimum stopping distances for Type B car and counterweight safeties used on inclined elevators (see 5.1.14.2):
(SI Units)

(Imperial Units)

where
Smin | = | minimum stopping distance, mm (in.) |
Smax | = | maximum stopping distance, mm (in.) |
υg | = | governor tripping speed, m/s (ft/min) |
θ | = | angle of inclination from horizontal (degrees) |
The design data and formulas in 8.2 as they apply to freight elevators shall apply to material lifts with automatic transfer devices. Where vehicle loading is used, Class B loading shall apply.
Requirement 8.3 covers:
(a) type of tests and certification of
(2) hoistway door interlocks, hoistway door combination mechanical locks, electric contacts, and hoistway-door electric contacts, as required in 2.12.4 (see also 8.3.1 and 8.3.3)
(3) car door or gate electric contacts, and car door interlocks as required in 2.14.4.2 (see 8.3.1 and 8.3.3)
(4) entrance fire tests as required by 2.11 (see 8.3.4)
(b) engineering tests of
(2) test method for evaluating room, fire growth, contribution of textile wall covering, as required in 8.7.2.14 (see 8.3.7 and 8.3.8)
(4) safety nut and speed-limiting device of screw column elevators, as required in 4.2.11.2 (see 8.3.1 and 8.3.10)
(a) Type Tests (see 1.3) shall be carried out when required.
(b) Engineering Tests (see 1.3) shall be carried out when required.
(c) The tests shall be permitted to be made by laboratories other than the certifying organization or manufacturers, but the responsibility shall remain with the original certifying organization.
The application for engineering or type tests shall be made by the component manufacturer, equipment manufacturer, installer, or importer.
The application shall include
(a) the manufacturer's name and the equipment or component designation or model
(b) two sets of assembly and detail drawings showing details as specified in 8.3
A certificate shall be issued for a component or equipment that has been successfully tested. The certificate shall include
(a) the name of applicant (see 8.3.1.2.1)
(b) the name of the manufacturer
(c) the manufacturer's designation of the type or model tested
(d) the certifying organization's label/mark and the method of affixing the label/mark to each component or each piece of equipment subsequently manufactured, where required
(e) the method of testing, the test report, and a list of the instruments used (Note: this may be attached to the certificate)
(f) the conditions for use of the certificate and label/mark
(g) a statement to the effect that the component or equipment tested has met the specified test requirements
(h) any other information required in ASME A17.1/CSA B44
(i) the edition of the Code under which the component was tested and certified
The certificate shall be valid until recalled by the certifying organization or until the applicable requirements in ASME A17.1/CSA B44 are changed unless otherwise stated (see 8.3.1.4).
The drawings and other documents submitted by the applicant (see 8.3.1.2), together with the original test records, data, performance curves, and certificate shall be filed, as a permanent record for future reference.
The applicant shall be permitted to examine and copy the test records upon request.
Where any change is made in the design of the component or equipment after certification, including changes resulting from the revisions in applicable code requirements, revised drawings showing such changes shall be filed with the original or other certifying organization. The certifying organization shall issue to the applicant a revised certificate, based upon the previous test results or any new tests that are needed, depending on the nature of the changes.
Changes in the design that do not affect the performance of the component or equipment shall be permitted to be made without the approval of the certifying organization. The certifying organization shall be apprised in writing of the change.
The precision of the instruments shall allow measurements to be made, unless otherwise specified, within the following tolerances:
(a) ± 1% — masses, forces, distances, time, speeds, and hydraulic pressure
(b) ± 2% — accelerations, retardations, and flow rating
(c) ± 5% — voltages and currents
(d) ± 10% — temperatures
Tests shall be made on a buffer of each type or design to be installed. Each buffer shall conform to the documents submitted and have the following oil portings:
(a) the porting having the range of the maximum loads for which the buffer is designed
(b) the porting having the range of the minimum loads for which the buffer is designed
The testing equipment shall be of such design as to perform the tests specified herein and to determine that the buffer conforms to all the requirements of 2.22 for oil buffers and shall also conform to 8.3.2.3.1 through 8.3.2.3.3.
The required drop test load shall be accurate to within ± 1%.
The test weight shall be so guided as to ensure that when dropped onto the buffer, its travel shall be substantially vertical.
The instruments used to measure the test results shall conform to the following requirements:
(a) The instruments shall be of the recording type.
(b) The instruments shall provide data, for the plotting of the buffer performance curves showing time intervals, travel of test weight, velocity of test weight, and retardation of test weight during the buffer stroke, that shall be accurate to within the following tolerances:
(1) The timing device shall record time in increments of not more than 1/60 s during the entire buffer stroke.
(2) Time increments and total time shall be recorded with an error of less than ±0.5%.
(3) The position of the test weight at each time interval shall be recorded with an error of less than ±0.1%.
(4) Time, travel, velocity, and retardation shall be determined by means of a device that will provide the accuracy specified.
A buffer of the spring-return type shall be placed on a foundation designed to withstand without appreciable deformation the forces resulting from the buffer compression on the drop tests. The buffer shall be installed in a vertical position and located centrally with relation to the drop-test weight.
The buffer, after being installed, shall be filled with oil to a level at or between the manufacturer's gauge line or lines. The oil shall conform to 2.22.4.9 and the data specified on the buffer marking plate.
After filling with oil, the procedure outlined below shall be followed to ensure that a constant oil level has been established.
(a) The buffer shall be fully compressed at slow speed, and shall then be allowed to return to its fully extended position and remain there for at least 10 min. The oil level shall then be checked.
(b) If the oil level as previously determined has changed, due to the elimination of entrapped air or due to the retention of air under pressure within the buffer, the change in level shall be noted and the procedure repeated until a constant oil level is obtained when the buffer is in its extended position.
(c) If the oil level tends to remain above the level to which it was filled, the air vents, if provided, should be checked for obstructions.
(d) When a constant oil level has been established, the level shall be adjusted to the manufacturer's lowest gauge line, and the exact level noted and recorded before making the drop tests hereinafter specified.
Each oil buffer with oil portings as submitted shall be subjected to tests for retardation, strength, oil leakage, plunger return, and lateral plunger movement, as hereinafter specified.
The following drop tests shall be made for each buffer porting specified in 8.3.2.2, from a height such that the striking velocity of the falling weight will be equal to 115% of the rated car speed for which the buffer is designed:
(a) three drop tests with a total test weight equal to the manufacturer's rated maximum load for which the porting is designed [see 8.3.2.2(a)]
(b) one drop test with a total test weight equal to the manufacturer's rated minimum load for which the porting is designed [see 2.7.2.2]
Following each drop test, the buffer shall be held its fully compressed position for a period of 5 min, and shall then be allowed to return free to its fully extended position and stand for 30 min to permit return of the oil to the reservoir and to permit escape of any air entrained in the oil.
On each of these tests, the average retardation of the test weight, during the stroke of the buffer, shall not exceed 9.81 m/s2 (32.2 ft/s2), and any retardation peak having a duration of more than 0.04 s shall not exceed 24.5 m/s2 (80.5 ft/s2).
On completion of the drop tests, no part of the buffer shall show any permanent deformation or injury.
(a) Two drop tests shall be made as follows:
(1) One drop test shall be made with the porting as specified in 8.3.2.2(a), with a total test weight equal to 120% of the manufacturer's rated maximum load, from a height such that the maximum velocity attained by the falling weight during the buffer compression shall be equal to 125% of the rated car speed for which the buffer is rated. In this test, the retardation shall be noted and shall be permitted to exceed the values specified in 8.3.2.5.1.
Immediately following this test, the buffer shall be examined externally for visible deformation or injury. If no damage is apparent, the buffer shall then be fully compressed at low speed and then released to determine if it will return freely to its extended position.
(2) After the buffer has been examined externally and has returned freely to its extended position, a second drop test shall be made from the same height and with the same load as specified in 8.3.2.5.1(a). During this test, the retardation shall not exceed the corresponding retardation developed in the test specified in 8.3.2.5.1(a) by more than 5%.
(b) If for given stroke of buffer having more than one porting, the construction of the buffer varies for the different portings, then a strength test similar to that specified in 8.3.2.5.2(a)(1) shall also be made for the porting having the range at minimum loads for which the porting is designed as specified in 8.3.2.2(b).
Following each drop test, the buffer shall be held in its fully compressed position for a period of 5 min, and shall then be allowed to freely return to its fully extended position and stand for 30 min to permit return of the oil to the reservoir and to permit the escape of any air entrained in the oil.
Tests for oil leakage shall be made concurrently with the retardation tests specified in 8.3.2.5.1, and the drop test specified in 8.3.2.5.2(a)(2), to determine the loss of oil during these tests. The oil level shall be noted after the buffer has returned to its fully extended position following each drop test, and after the time interval specified in 8.3.2.5.1.
The drop in oil level, as indicated by these measurements, shall show no loss of oil exceeding 5 mm/m (0.06 in./ft) of buffer stroke, but in no case shall the loss be such as to lower the oil level below the bottom of the plunger or below the highest metering orifice, whichever is higher.
Where the volume of oil above the porting is small when the buffer is filled to its normal working level, the laboratory shall be permitted to make additional tests for oil leakage.
During the drop tests specified in 8.3.2.5.1 and 8.3.2.5.2, the time required for the buffer plunger to return to its fully extended position, measured from the instant the test weight is raised clear of the buffer until the plunger has returned to its fully extended position, shall be noted. This time shall be not more than 90 s.
Should the plunger fail to return to its fully extended position, or should the time required for it to return to its fully extended position exceed the time specified, the manufacturer shall either submit a duplicate buffer or install a new pressure cylinder and piston, following which the plunger-return test shall be repeated. Should the buffer again fail to meet the plunger-return test requirements, it shall be rejected.
Buffers of the spring-return type shall be tested for plunger return with a 20 kg (45 lb) test weight resting on top of the plunger during the test. The plunger shall be depressed 50 mm (2 in.) and when released, the plunger, while supporting the test weight, shall return to its fully extended position within 30 s.
The following tests shall be made for lateral movement.
(a) Spring-Return-Type Buffers. The lateral movement at the top of the fully extended plunger shall be accurately measured, the upper end of the plunger being manually moved from its extreme right to its extreme left position. One-half of the total movement measured shall be considered as being the true lateral movement at the top of the plunger and shall not exceed 5 mm/m (0.06 in./ft) of buffer stroke.
(b) Gravity-Return-Type Buffers. A similar test for lateral movement shall be made. The measurement shall be taken at the lower end of the buffer cylinder when the buffer plunger is fully extended and braced to prevent lateral movement. One-half of the total movement measured shall not exceed 5 mm/m (0.06 in./ft) of buffer stroke.
The certificate shall conform to 8.3.1.3.1 and shall include the following:
(a) the maximum impact speed
(b) the maximum total load
(c) the minimum total load
(d) specification of the fluid
When the test results are not satisfactory with the minimum and maximum total loads appearing in the application, the laboratory shall be permitted to, in agreement with the applicant, establish the acceptable limits.
This Section specifies the type test of hoistway door interlocks, car door interlocks, combination mechanical locks and electric contacts, and hoistway door and car door or gate electric contacts.
Prior to testing, the certifying organization shall examine each device submitted to ascertain that it conforms to the applicable requirements in Part 2.
During the tests specified by 8.3.3.4.1, 8.3.3.4.3, and 8.3.3.4.4, the devices shall have their electrical parts connected in a noninductive electrical circuit having a constant resistance and in which a current of twice the rated current at rated voltage is flowing. The electric circuit shall be closed, but shall not be broken at the contact within the device on each cycle of operation during the tests.
If the electric contact of a device submitted for test has already been tested as part of another device, and has successfully met the test requirements (see 8.3.3), the electrical tests of the contact need not be repeated.
Tests of retiring cams or equivalent devices used to operate interlocks shall not be required.
The testing equipment shall actuate the mechanical locking members of hoistway door (runway door) combination mechanical locks and electric contacts to unlock at each cycle of operation during the tests specified by 8.3.3.4.1, 8.3.3.4.3, and 8.3.3.4.4.
Each device submitted shall be subjected to and shall successfully pass the following tests.
The device, lubricated in accordance with the manufacturer's instructions, shall complete 960 000 cycles of operation without failure of any kind, without excessive wearing or loosening of parts, or without undue burning or pitting of the contacts (see 8.3.3.3.1). For private residence elevators the number of cycles shall be reduced to 25 000.
After completion of the test specified by 8.3.3.4.1, the device used therein shall satisfactorily complete the following additional tests, to check that the ability to break a live circuit is adequate.
The tests shall be carried out with the locking device located in accordance with the manufacturer's drawings. If several positions are indicated, the test shall be made in the position that the laboratory judges to be the most unfavorable.
The sample tested shall be provided with covers and electrical wiring in accordance with the manufacturer's drawings.
(a) AC rated locking devices shall have their electrical parts connected to an inductive circuit with a power factor of 0.7 ± 0.05 in which a current of 11 times the rated current, at 110% of rated voltage, is flowing. The AC locking devices shall open and close 50 times, at normal speed, and at intervals of 5 s to 10 s, with the contact remaining closed for at least 0.5 s.
(b) DC rated locking devices shall have their electrical parts connected to an inductive circuit in which the current reaches 95% of the steady state value of 110% of the rated current in 0.3 s maximum, at 110% of rated voltage. The DC locking devices shall open and close 20 times, at normal speed, and at intervals of 5 s to 10 s, with the contact remaining closed for at least 0.5 s.
(c) The test results are considered satisfactory if no evidence of insulation breakdown due to arcing or tracking occurs and if no deterioration occurs that could adversely affect safety.
After completion of the test specified by 8.3.3.4.2, the device used therein shall be used for this test.
The device, except self-lubricating bearings and bearings of a type not requiring frequent replenishment of lubricant, shall then be taken apart and freed of lubricant by washing in nonflammable liquids having cleansing characteristics.
After reassembling, the device shall, without other than the usual initial adjustment (i.e., without adjustment especially made to meet the conditions of the particular test) and without further attention, complete 25 000 cycles or 20 000 cycles for private residence elevator of operation without failure of any kind, without excessive wearing or loosening of parts, and without undue burning or pitting of contacts.
After completion of the test specified by 8.3.3.4.3, the device used therein shall be used for this test.
The device shall be subjected continuously, in an unventilated enclosure, to an atmosphere saturated with a range of 3.5% to 5% solution of sodium chloride for 72 consecutive hours. During this period, it shall be operated for only 10 consecutive cycles at the end of each of the first two 24 h periods and shall be allowed to stand exposed to the air for 24 h, and shall not fail in a manner that creates an unsafe condition.
The device shall again be lubricated and shall, without adjustment and without further attention, complete 15 000 cycles or 10 000 cycles for private residence elevator of operation without failure of any kind.
(a) All Types of Doors. The device shall operate effectively when the car cam or other equivalent operating device used in making the test has been displaced horizontally from its normal position (the position in which it was when the device was installed) successively as follows:
(1) in a direction perpendicular to the plane of the door opening
(a) backward 6 mm (0.25 in.)
(b) forward 6 mm (0.25 in.)
(2) in a direction parallel to the plane of the door opening
(a) to the right 6 mm (0.25 in.)
(b) to the left 6 mm (0.25 in.)
(b) Horizontally Sliding Doors. The device shall operate effectively
(1) when the bottom of the door has been displaced horizontally from its normal position in a direction perpendicular to the plane of the door opening
(a) backward 6 mm (0.25 in.)
(b) forward 6 mm (0.25 in.)
(2) when the top of the door has been displaced horizontally from its normal position in a direction perpendicular to the plane of the door opening
(a) backward 3 mm (0.125 in.)
(b) forward 3 mm (0.125 in.)
(c) Swinging Doors. The device shall operate effectively when the strike edge of the door has been displaced
(1) perpendicular to the plane of the door opening
(a) forward 3 mm (0.125 in.)
(b) backward 3 mm (0.125 in.)
(2) parallel to the plane of the door opening
(a) 3 mm (0.125 in.) to the right
(b) 3 mm (0.125 in.) to the left
(c) 3 mm (0.125 in.) up
(d) 3 mm (0.125 in.) down
(d) Vertically Sliding Doors. The device shall operate effectively when the door has been displaced
(1) perpendicular to the plane of the door opening
(a) forward 3 mm (0.125 in.)
(b) backward 3 mm (0.125 in.)
(2) parallel to the plane of the door opening:
(a) 3 mm (0.125 in.) to the right
(b) 3 mm (0.125 in.) to the left
The insulation of the electrical parts shall withstand a test with a root-mean square (effective) voltage of twice the rated voltage plus 1 000 V, 60 HZ, applied for 1 min.
When testing devices of a type that are released by retiring cam (see 2.12.2.5), measurements shall be made of the force required to release the device and of the movement of the element engaged by the cam, with the device mounted in its normal position as specified by the manufacturer, before and after the test specified by 8.3.3.4.1.
The force and movement recorded in each test shall be, respectively
(a) the maximum force, measured in a horizontal plane, that must be applied to that member of the device that is directly actuated by the cam to release the door-locking member of the device from locking engagement
(b) the distance, projected on a horizontal plane, that the member of the device directly actuated by the cam travels from its position when the lock is fully engaged to its position when the locking member is released from engagement
The force and movement markings required by 2.12.4.3(f) shall be not less than the average of these recorded values.
After completion of the endurance test in 8.3.3.4.1, a type test shall be made consisting of a static force applied over a period of 300 s with the force increasing incrementally. The force shall be applied in the opening direction of the door and at a location as near to the locking element as possible, but not to exceed 300 mm (12 in.). The force shall be 1 000 N (225 lbf) in the case of a locking device intended for use with sliding doors, and 3 000 N (675 lbf) or 670 N (150 lbf) for private residence elevator applied at right angles to the panel evenly distributed over an area 5 cm2 (0.78 in.2) in round or square section in the case of a locking device intended for use with swinging doors.
The electrical spacings shall comply with CSA B44.1/ASME A17.5, Section 16.
Verify that there is at least 7 mm (0.28 in.) engagement of the locking elements before the hoistway door interlock contact closes.
The electrical contact bridging means shall be tested to verify conformance to 2.12.2.4.1.
In jurisdictions not enforcing the NBCC, test of elevator horizontal slide-type and swing-type entrance assemblies and tests of elevator and dumbwaiter vertical slide-type entrance assemblies shall be conducted in accordance with UL 10B, or NFPA 252.
Test entrance assemblies shall be constructed in accordance with 2.11.
The application required in 8.3.1.2 shall include information regarding
(a) the component rated pressure
(b) the flow rating
(c) the fluid specification
(d) the operating temperature range of fluid
(e) the coil voltage and current
Tests shall be conducted on a representative sample in the sequence as stated in 8.3.5.3.
Test samples shall be subject to 100 000 operating cycles (100 000 up and 100 000 down) at the component rated pressure and within the fluid specifications and temperature range stipulated by the manufacturer. Each operating cycle shall be not less than 5 s nor more than 24 s.
(a) The hydraulic pressure shall be maintained at 1.5 times the component rated pressure for a period sufficient to establish the rate of leakage, but not less than 1 h nor more than 24 h. The test shall be started at the maximum stipulated fluid temperature for which the valve is designed. The fluid temperature shall be permitted to gradually decrease during the test to 20°C (68°F).
(b) The test shall be repeated using a pressure of 750 kPa (110 psi).
(c) Total leakage from output to input during either test shall not exceed the flow rate of the valve divided by one million.
The hydraulic pressure shall be maintained at twice the component rated pressure for a period of 10 min to establish the rate of leakage. The rate of leakage shall not exceed 10% of the rated flow of the valve.
For elongations greater than or equal to 10%, the pressure chambers of the valve shall be subjected to a hydraulic pressure five times the component rated pressure.
For elongations of less than 10%, the test value shall be 1.5 times the value indicated by 8.2.8.5 multiplied by the component rated pressure.
To test the strength, this hydraulic pressure shall be maintained for a period of 5 min. During the test, the valve body shall not rupture.
NOTES (8.3.5.3.4):
- In order to obtain and maintain the test pressure, it is permissible to substitute alternate sealing material; and to tighten bolts during the test.
- It is not expected that the valve will be able to perform its function during or after the valve body strength test.
Valves shall be tested to the electrical requirements of CSA C22.2 No. 139, Clause 6.
Where required by 6.1.5.3.3, escalators shall be subjected to such tests as are necessary to certify that
(b) the relationship that exists between the range of brake settings and stopping distances complies with 6.1.5.3.1
The stopping distance shall be measured by the movement of a step along its path of travel after a stop has been initiated.
The tests shall be permitted to be made in the manufacturer's plant or on an escalator installation.
Provided that design loads of the brake are not exceeded, it is permissible to simulate on the test escalator, by means of alternative loads, a number of heights and widths, for the purpose of certification of an escalator type (design), provided that those escalators for the additional widths and heights utilize the same motor and machine.
In jurisdictions not enforcing the NBCC, napped, tufted, woven, looped, and similar materials [see 2.14.2.1.2(b)] shall be subjected to the engineering tests specified in 8.3.7.1 through 8.3.7.6.
Materials shall be tested either as a section cut from a fabricated part as installed in the car or as a specimen simulating a cut section, such as a specimen cut from a flat sheet of the material or a model of the fabricated part. The specimen shall be cut from any location in a fabricated part; however, fabricated units, such as sandwich panels, shall not be separated for test. The specimen shall be no thicker than the minimum thickness to be qualified for use in the car. In the case of fabrics, both the warp and fill direction of the weave shall be tested to determine the most critical flammability conditions. The specimen shall be mounted in a metal frame so that the two long edges and the upper edge are held securely. The exposed area of the specimen shall be at least 51 mm (2 in.) wide and 305 mm (12 in.) long, unless the actual size used in the car is smaller. The edge to which the burner flame is applied must not consist of the finished or protected edge of the specimen but shall be representative of the actual cross section of the material or part installed in the car.
A minimum of three specimens shall be tested and the results averaged. For fabric, the direction of weave corresponding to the most critical flammability conditions shall be parallel to the longest dimension. Each specimen shall be supported vertically. The specimen shall be exposed to a Bunsen or Tirrill burner with a nominal 9.5 mm (0.375 in.) I.D. tube adjusted to give a flame of 38 mm (1.5 in.) in height. The minimum flame temperature measured by a calibrated thermocouple pyrometer in the center of the flame shall be 840°C (1,545°F). The lower edge of the specimen must be 19 mm (0.75 in.) above the top edge of the burner.
The flame shall be applied to the centerline of the lower edge of the specimen. The flame shall be applied for 12 s and then removed. Flame time, burn length, and flaming time of drippings, if any, shall be recorded. The burn length determined in accordance with 8.3.7.5 shall be measured to the nearest 2.5 mm (0.1 in.).
Burn length is the distance from the original edge to the farthest evidence of damage to the test specimen due to flame impingement, including areas of partial or complete consumption, charring, or embrittlement, but not including areas sooted, stained, warped, or discolored, and not areas where material has shrunk or melted away from the heat source.
(a) The average burn length shall not exceed 203 mm (8 in.).
(b) The average flame time after removal of the flame source shall not exceed 15 s.
(c) Drippings from the test specimen shall not continue to flame for more than 5 s.
Textile wall covering shall be tested and meet the acceptance criteria of the NFPA 265, Fire Test for Evaluating Room Fire Growth Contribution of Textile Wall Covering, when tested using the product mounting system, including adhesive, of actual use.
The overspeed valve test shall be based on the marking required by 3.19.4.7.2 and specifications provided by the valve manufacturer.
Tests shall be conducted on a representative sample of the overspeed valve.
The test sample shall be subjected to 1 000 closing cycles at the component rated pressure, maximum flow rate, and within the fluid specifications and temperature range stipulated by the manufacturer. Additionally, the sample shall be subjected to 100 operating cycles at the minimum flow rate and pressure, to ensure range coverage.
The hydraulic pressure shall be maintained at 1.5 times the component rated pressure for a period sufficient to establish the rate of leakage, but not less than 1 h and not more than 24 h. Total leakage of the valve from input to output during the test period shall not exceed the flow rate of the valve divided by one million.
For elongations greater than or equal to 10%, the valve shall be subjected to a hydraulic pressure 7.5 times the component rated pressure. For elongations of less than 10%, the test valve shall be 2.25 times the value indicated by 8.2.8.5 multiplied by the component rated pressure. The strength test for this hydraulic pressure shall be maintained for a period of 5 min. During the test, the valve body shall not rupture.
NOTES:
- In order to obtain and maintain the test pressure, it is permissible to substitute alternate sealing material; and tighten bolts during the test.
- It is not expected that the valve will be able to perform its function during or after the valve body strength test.
This Section specifies the engineering tests of safety nuts and speed-limiting devices that are permitted as alternate safety devices on screw-column elevators driven by alternating current squirrel cage motors and having a down speed of not more than 0.38 m/s (75 ft/min).
The test shall be made in either the manufacturer's plant, in a testing laboratory, or in the field by suspending the elevator car with rated load a distance above the safety nut of at least 13 mm (0.5 in.) and allowing it to drop (free-fall) until the entire load rests on the safety nut. The test shall be witnessed by, and the test results certified by, a testing laboratory or registered professional engineer. After the test, the screw column, screw supports, safety nut, guide rails, and car frame shall be inspected to determine that there has been no damage. A test on a given capacity elevator shall be accepted for all similarly designed elevators by that manufacturer for the same or lesser capacity (rated load).
The test shall be made either in the manufacturer's plant, in a testing laboratory, or in the field by suspending the elevator car with rated load a distance of at least 4 572 mm (15 ft) above the lower limit of normal travel and allowing it to drop (free-fall) until the descent is controlled by the speed-limiting device. The elevator car shall be allowed to continue its descent until brought to rest by the car buffer or bumper. The test shall be instrumented so that a graph of velocity versus distance can be plotted. The test shall be witnessed by, and the test results certified by, a testing laboratory or a registered professional engineer. After the test, the screw column, screw-column supports, speed-limiting device, guide rails, car buffer or bumper, and car frame shall be inspected to determine that there has been no damage. A test on a given capacity elevator shall be accepted for all similarly designed elevators by that manufacturer for the same or lesser capacity (rated load).
The test shall be made at either the manufacturer's facility or at a testing laboratory.
Escalator steps shall be mounted in an arrangement that duplicates the conditions on the escalator incline and their attachment to the step chain. Moving walk pallets shall be mounted in an arrangement that duplicates the condition of a horizontal moving walk and their attachment to the pallet chain.
The steps shall be subjected to a load varying from 450 N (100 lbf) to 3 000 N (650 lbf) at a frequency of 10 Hz ± 5 for 5 000 000 cycles. An undisturbed harmonic force flow shall be achieved.
The load shall be applied normal to the tread surface to a plate 25 mm (1 in.) thick, 200 mm (8 in.) wide, and 300 mm (12 in.) long, located at the center of the step or pallet, with the 300 mm (12 in.) dimension in the direction of step travel.
The step or pallet shall have no fractures or permanent tread surface deflection exceeding 4 mm (0.16 in.) following the completion of the test. The deflection of 4 mm (0.16 in.) does not include any set or wear in the supporting wheels.
This test is to be performed on each step or pallet width.
A test shall be required on each combination of suspension member, driving sheave design, and materials of construction. The test shall be conducted with the contact-surface geometry of the test specimens that results in the highest surface-pressure condition between the suspension member and driving sheave. A test on a given suspension member at its maximum allowable load shall be accepted for all similarly designed combinations by that manufacturer for any lesser load carried per suspension member. The suspension members and driving sheave combination shall be tested under the conditions for which they were designed.
One or more suspension member(s), loaded in tension to the maximum capacity to be qualified, shall be applied to its (their) driving sheave. The suspension member(s) shall be prevented from moving. The driving sheave shall be rotated at a speed no less than that corresponding to the maximum inspection speed of the elevator to which the suspension means is to be applied.
As a result of the test required by 8.3.12.2, no suspension member shall part before a minimum of 4 min.
One or more suspension member(s), loaded in tension to the maximum capacity to be qualified, shall be applied to its (their) driving sheave. The suspension member(s) shall be run at a speed corresponding to the maximum speed for which the suspension means is to be applied with respect to its (their) drive sheave. The drive sheave shall be subjected to three successive emergency stops, each causing the suspension members to slip traction over the driving sheave [see 8.3.12.4(g)]. The tests shall be so arranged that slippage occurs over substantially the same portion of the suspension means during successive tests. The duration of the slip shall correspond to that attained by the elevator counterweight and car with rated load initially moving at rated speed, and decelerating, on their own, to a complete stop. It shall be permitted to conduct this test on an installed elevator or in a suitable testing facility.
As a result of the test required by 8.3.12.3, suspension member(s) shall not sustain damage that would require replacement according to the criteria of ASME A17.6, Sections 1.10, 2.9, and 3.7, as applicable.
For the tests required in 8.3.12.2 and 8.3.12.3, the testing facilities, test procedure, and test results shall be documented in engineering reports. The following information shall be provided in each engineering report:
(a) date(s) of the test
(b) name and address of location where tests were conducted
(c) name, position, and organization of the person(s) conducting, supervising, or witnessing the tests
(d) description of apparatus and equipment used to perform the tests
(e) description of instrumentation used to measure or record data
(f) definition and description of the suspension member(s) and the driving sheave to which it (they) is (are) being applied, including part number, type designation, or other identification
(g) the values of the loads and speeds for which the suspension members and their sheaves are to be qualified
(h) the sheave rotation speed for Test 8.3.12.2
(i) description of the test procedure and pass/fail criteria
(j) observations noted during the test
(k) test results and test data
(l) conclusions indicating compliance with the acceptance criteria
(a) Section 8.4 applies to all electric elevators with counterweights, and direct-acting or roped-hydraulic elevators where applicable, where such elevators are installed in buildings assigned to one of the following:
(1) Seismic Design Category C with Component Importance Factor, Ip, of 1.5 as defined by IBC (see 1.3, building code)
(2) Seismic Design Category D or greater as defined by IBC (see 1.3, building code)
(3) Design Spectral Response Acceleration for a 0.2 s time period [Sa(0.2)] greater than 0.12 and building designated as post-disaster building or IEFaSa(0.2) is equal to or greater than 0.35 as defined by NBCC-2010 (see 1.3, building code)
(4) Seismic Performance Category C with Seismic Hazard Exposure Group II or higher as defined by earlier model building codes (see Note)
(5) Seismic Risk Zone 2 or greater as defined by earlier building codes (see Note)
NOTE: For example, SBC 1982; SBC 1994; etc.
(b) The appropriate Elevator Component Seismic Force Level is determined by the applicable building code (see Guide for Elevator Seismic Design Part 1 and Part 2, Sample Calculations 1a-g)
(1) where the applicable building code references Seismic Design Categories or Design Spectral Response Acceleration [Sa(0.2)], force levels as referenced by 8.4.14 shall be used (see 1.3, building code)
(2) where the applicable building code makes reference to ground motion parameters (such as Av or Zv), 8.4.13 shall be used
(3) where the applicable building code makes reference to Seismic Risk Zones, or Seismic Risk Zones and component force level equations, force levels for the appropriate zone, as listed throughout Section 8.4, or the calculated component force level shall be used, whichever is greater
(c) The elevator seismic requirements contained in 8.4 shall be in addition to the requirements in the other parts of the Code unless otherwise specified.
The following clearances shall supersede those specified in 2.5.1.2.
The clearance between the car and the counterweight assembly shall be not less than 50 mm (2 in.), except that where the counterweight is enclosed by double U-brackets or where single U-brackets are provided and are located within the space between the car and its counterweight, the clearance shall be not less than 100 mm (4 in.).
The clearance between the counterweight assembly and the hoistway enclosure or separator beams shall be not less than 50 mm (2 in.).
The running clearance between the counterweight assembly and the nearest obstruction, including counterweight screens, shall be not less than 25 mm (1 in.).
Overhead beams and supports including hitch-plate blocking beams shall be anchored to prevent overturning and displacement as a result of seismic forces acting simultaneously, as specified in 8.4.13 or 8.4.14, or equal to
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
where
Wp | = | component operating weight as defined by 8.4.15 |
Fastening devices including bolts used to secure machines, control panels, motor-generator units, machine beams, support beams, and sheaves, including compensating sheave assemblies, to the building structure shall conform to 8.4.2.3. Requirement 2.9.3.1.2 shall not apply (see Guide for Elevator Seismic Design, Part 2, Sample Calculation 2).
Connections (for guide-rail brackets, see 8.4.8.4) used to attach equipment to the supporting structure, that are not subject to impact loads, shall be designed to withstand seismic component force levels acting simultaneously, as defined in 8.4.13 or 8.4.14, or equal to either of the following:
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
Connections subject to impact loads shall be designed to withstand forces double those required for connections not subject to impact loads.
Maximum combined stresses in connections due to the specified seismic forces shall conform to the following applicable standards (see also 8.4.14.1.4):
(a) ANSI/AISC 360-05 or CAN/CSA-S16.1-09 for threaded fasteners
(b) Section 8.8 for welded connections
(c) ACI 318-08 or CSA A23.3-04 for fastening to concrete
(d) ANSI/AF&PA National Design Specification for Wood Construction (2005) or CSA Standard O86-01 Wood Design Manual
NOTE: Connections includes all the mechanical and/or structural components used to transmit shear forces, bending moments, and axial forces developed in the structure at the connection point.
For areas not utilizing seismic zones, the Nonstructural Component Anchorage, as defined by IBC/ASCE 7, shall be in conformance with the requirements of the governing building code.
Retainers for suspension members shall be provided on deflecting and secondary sheaves, driving-machine sheaves and drums, compensating sheaves, governor sheaves, governor tension sheaves, and suspension sheaves on cars and counterweights to inhibit the displacement of suspension members, except as specified in 8.4.3.1.4.
The retainer shall be continuous over not less than two-thirds of the arc of contact between the suspension members and its sheave or drum and shall be so located that not more than one-sixth of the arc of contact is exposed at each end of the retainer.
For double-wrap traction applications, the arc of contact for drums and secondary sheaves shall be that length of arc that is uninterrupted by the entry/exit of the suspension members leading to/from the car or counterweight (see Fig. 8.4.3.1.3). 
Fig. 8.4.3.1.3 Arc of Contact

Restraints for suspension members shall be permitted to be used in lieu of continuous guards, provided they conform to the following:
(a) Where the arc of contact is 30 deg or less and one suspension-member restraint, located at the midpoint of the arc of contact, is provided.
(b) Where the arc of contact exceeds 30 deg and restraints are provided at intervals not exceeding 30 deg of arc along the arc of contact and a restraint is located at each end of the arc of contact.
Snag points created by rail brackets, rail clip bolts, fishplates, vanes, and similar devices shall be provided with guards to prevent snagging of the following:
(a) the counterweight end of compensating means where located 760 mm (30 in.) or less from a counterweight rail bracket
(b) compensating chains where any portion of their loop below the mid-point of the elevator travel is located 915 mm (36 in.) or less horizontally from a snag point
(c) governor ropes where located 500 mm (20 in.) or less from a snag point
(d) suspension members where located 300 mm (12 in.) or less from a snag point
(e) traveling cables where any portion of their loop below the mid-point of the elevator travel is located 915 mm (36 in.) or less horizontally from a snag point
The requirements specified in 2.14.1.5 shall apply except that the emergency exit shall be so arranged that it can be opened from within the car by means of a keyed spring-return cylinder-type lock having not less than a five-pin or five-disk combination and opened from the top of the car without the use of a key.
The key required to open the emergency exit lock shall be kept on the premises in a location readily accessible to authorized persons, but not where it is available to the public. No other key to the building shall unlock the emergency exit lock except that where hoistway access switches conforming to 2.12.7 are provided, the key used to operate the access switches shall be permitted to also unlock the top emergency exit. This key shall be Group 1 Security (see 8.1).
The top emergency exit shall be provided with a car door electric contact conforming to 2.14.1.5.1(f) and so located as to be inaccessible from the inside of the car. The opening of the electrical contact shall limit the car speed to not more than 0.75 m/s (150 ft/min).
Upper and lower position restraints attached to the car frame shall be provided. The distance between the upper and lower position restraints shall be not less than the height of the car frame. Separate position restraints are not required where such restraints are an integral part of the guiding member.
Position restraints and their attachments to car frames shall be designed to withstand a seismic force acting horizontally on the weight of the car plus 40% of its rated capacity as defined in 8.4.13 or 8.4.14 (with Wp = car weight + 40% capacity), or equal to
(a) 1/2 Wp (zone 3 or greater)
(b) 1/4 Wp (zone 2)
When the car is centrally located between its guide rails and the platform is level, the clearance between each running face of the guide rail and the position restraint shall not exceed 5 mm (0.187 in.) and the depth of engagement with the rail shall be not less than the dimension of the side running face of the rail.
Where compensating ropes are used with a tension sheave assembly, means shall be provided to prevent the tension sheave assembly from being dislocated from its normal operating position when subjected to seismic forces acting simultaneously as specified in 8.4.13 or 8.4.14, or equal to either of the following:
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
Compensating rope sheaves shall be provided with a compensating rope sheaves switch or switches conforming to 2.26.2.3.
The counterweight frame and its weight sections shall be so designed and arranged as to limit the guide-rail force at the lower position restraint to not more than two-thirds of the total seismic force due to the weight or effective weight of the counterweight assembly when it is subjected to a component seismic force level as defined by 8.4.13 or 8.4.14, or a horizontal seismic force equal to
(a) 1/2 Wp (zone 3 or greater)
(b) 1/4 Wp (zone 2)
For counterweight assemblies with weight sections that occupy two-thirds or more of the frame height, 8.4.8.9 applies and Figs. 8.4.8.2-1 through 8.4.8.2-7 shall be permitted to be used in sizing the guide- rail system.
The clearance between the counter weight frame and the face of the counterweight guide rail measured at a point one-half the vertical distance between the upper and lower guiding members shall not exceed 13 mm (0.5 in.).
Upper and lower position restraints attached to the counterweight frame shall be provided. The distance between the upper and lower position restraints shall be not less than the height of the counterweight frame. Separate position restraints are not required where such restraints are an integral part of guiding member.
When the counterweight is centrally located between its guide rails, the clearance between each running face of the guide rail and the position restraint shall not exceed 5 mm (0.187 in.) and the depth of engagement with the rail shall be not less than the dimension of the side running face of the rail.
The load distribution to the guide rails due to the inertial effects of the car and counterweight on their respective guide rails shall be determined as follows:
(a) Conventional Standard Designs. The seismic forces shall be assumed to be distributed one-third to the top guiding members and two-thirds to the bottom guiding members of cars and counterweights.
(b) Non-Standard Designs. Where the design of the car, or counterweight, employs either special construction or location and quantity of guiding members, the formulas and methods of calculation of the load distribution, and resulting stresses and deflections, do not generally apply and shall be modified to suit the specific conditions and requirements in each case.
(a) For jurisdictions enforcing seismic zones or an equivalent ground motion parameter (see 8.4.13), Wp shall not exceed the maximums specified in Figs. 8.4.8.2-1 through 8.4.8.2-7 for the size of rail and the bracket spacing used.
(b) For jurisdictions enforcing IBC/NBCC, the permissible horizontal seismic force, Fp, based on Wp, per pair of guide rails shall not exceed the maximums specified in Figs. 8.4.8.2-1 through 8.4.8.2-7 for the size of rail and the bracket spacing used (see 8.4.12.1 and Guide for Elevator Seismic Design Part 2, Sample Calculation 3).
Fig. 8.4.8.2-1 12 kg/m (8 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-2 16.5 kg/m (11 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-3 18 kg/m (12 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-4 22.5 kg/m (15 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-5 27.5 kg/m (18.5 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-6 33.5 kg/m (22.5 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-7 44.5 kg/m (30 lb/ft) Guide-Rail Bracket Spacing

Fig. 8.4.8.2-8 Car and Counterweight Load Factor

L = distance between upper and lower counterweight position restraints, mm (in.)
ℓ = distance between guide brackets, mm (in.)
W = actual weight of counterweight, kg (lb)
Wa = adjusted weight of counterweight, kg (lb)
For ratios of L/ℓ < 0.65, the adjusted counterweight Wa = QW is to be used in determining bracket spacing and the number of intermediate tie brackets required.
EXAMPLE (Per 15 lb Guide Rail):
(SI Units)
For ratio L/ℓ = 0.15, and actual weight of counterweight = 3 630 kg
Q = 1.35
Wa = 1.35 (3,630) = 4 900 kg
From Fig. 8.4.8.2-4 zone 3 or greater
Required bracket spacing | = | 3 200 mm (no tie bracket) |
or | = | up to 4 215 mm (one tie bracket) |
or | = | up to 4 675 mm (two tie brackets) |
(Imperial Units)
For ratio L/ℓ = 0.15, and actual weight of counterweight = 8,000 lb
Q = 1.35
Wa 1= 1.35 (8,000) = 10 800 kg
From Fig. 8.4.8.2-4 zone 3 or greater
Required bracket spacing | = | 10 ft 6 in. (no tie bracket) |
or | = | up to 13 ft 10 in. (one tie bracket) |
or | = | up to 15 ft 4 in. (two tie brackets) |
Where the ratio of the distance between the upper and lower car or counterweight position restraints to the distance between adjacent brackets is 0.65 or less, an adjusted weight shall be used to determine the required rail size for the bracket spacing used. The adjusted weight shall be determined by multiplying the actual weight by a load factor Q obtained from Fig. 8.4.8.2-8 as follows:
Wa = QW
where
Q | = | load factor (see Fig. 8.4.8.2-8) |
W | = | actual weight of the counterweight or of the car plus 40% of its rated capacity, N (lb) |
Wa | = | adjusted weight, N (lb) |
Where the guide rail is reinforced or a rail of larger size is used, the bracket spacing shall be permitted to exceed the values specified in Figs. 8.4.8.2-1 through 8.4.8.2-7 for a given car weight plus 40% of its rated capacity, or counterweight, provided the variation conforms to 8.4.12.
EXAMPLES:
- SI Units. 5 543 kg counterweight, or car weight plus 40% rated capacity, at a bracket spacing of 4.88 m requires for zone 3 or greater:
- a 27.5 kg/m rail without reinforcement; or
- a 22.5 kg/m rail with reinforcement having a combined moment of inertia of 3.33 E + 06 mm4 and a combined section modulus of 5.26 E + 04 mm3 about an axis parallel to the base (axis x-x).
- Imperial Units. 12,000 lb counterweight, or car weight plus 40% rated capacity, at a bracket spacing of 16 ft requires for zone 3 or greater:
- an 18.5 lb rail without reinforcement; or
- a 15 lb rail with reinforcement having a combined moment of inertia of 8 in.4 and a combined section modulus of 3.21 in.3 about an axis parallel to the base (axis x-x).
For counterweight systems, intermediate tie brackets conforming to 8.4.8.7 and approximately equally spaced between main brackets shall be provided between guide rails as required by Figs. 8.4.8.2-1 through 8.4.8.2-7. Intermediate tie brackets are not required to be fastened to the building structure.
The total weight of the counterweight assembly shall not exceed the maximum specified in Table 2.23.4.3.1 for a given rail size.
(a) The horizontal seismic forces used to determine guide-rail stresses and deflections are
(1) For jurisdictions enforcing seismic zones
(a) 1/2 Wp (zone 3 or greater); or
(b) 1/4 Wp (zone 2)
(2) For jurisdictions enforcing IBC/NBCC
(a) Fp when calculating deflection
(b) 0.7Fp when calculating stress
(b) For installations where the guide rails bear the vertical loads imposed by machines, sheaves, or hitches, the following vertical loads will be considered acting simultaneously in addition to those above:
(1) For jurisdictions enforcing seismic zones
(a) 1/4 Wp (zone 3 or greater); or
(b) 1/8 Wp (zone 2)
(2) For jurisdictions enforcing IBC/NBCC
(a) Fυ when calculating deflection
(b) 0.7Fυ when calculating stress
NOTE: The forces above are the result of both any equipment attached to the rail and the tensions developed in the suspension ropes by the car and counterweight.
For jurisdictions enforcing seismic zones, stresses in a guide rail, or in a rail and its reinforcement, due to seismic loads specified in 8.4.8.2.6, shall not exceed 88% of the minimum yield stress of the material or materials used.
For jurisdictions enforcing IBC/NBCC, stresses in the guide rail, or in a rail and its reinforcements, due to seismic loads specified in 8.4.8.2.6, shall not exceed 60% of the minimum yield stress of the material or materials used.
Guide-rail brackets and their fastenings and supports, such as building beams and walls, shall be capable of withstanding the forces imposed by the seismic loads specified in 8.4.8.2.6, with a total deflection at the point of support not to exceed 6 mm (0.25 in.).
In jurisdictions enforcing IBC/NBCC, the Nonstructural Component Anchorage shall be in conformance with the requirements of the governing building code.
The joints of metal guide rails shall conform to the following requirements:
(a) The ends of the rails shall be accurately machined with a tongue and matching groove centrally located in the web.
(b) The backs of the rail flanges shall be accurately machined, in relation to the rail guiding surfaces, to a uniform distance front to back of the rails to form a flat surface for the fishplates.
(c) The ends of each rail shall be bolted to the fishplates with not less than four bolts.
(d) The width of the fishplate shall be not less than the width of the back of the rail.
(e) The section modulus and the moment of inertia of the fishplate shall be not less than that of the rail.
(f) The diameter of the bolts for each size of guide rails shall be not less than specified in Table 2.23.7.2.1.
(g) The diameter of bolt holes shall not exceed the diameter of the bolts by more than 2 mm (0.08 in.) for guide rails nor 3 mm (0.125 in.) for fishplates.
(h) The threaded portion of the bolts shall not occur in the shear plane of the guide-rail fishplate assembly.
Joints of different design and construction to those specified shall be permitted to be used, provided they are equivalent in strength and will adequately maintain the accuracy of the rail alignment.
Guide-rail brackets including intermediate tie brackets, where provided, shall be designed to withstand the forces imposed by the seismic loads specified in 8.4.8.2.6. The stresses and deflections shall not exceed those specified in Table 8.4.8.7.
NOTE (8.4.8.7): Since the specific designs of the rail brackets, their reinforcements where provided, and the method of attachment to the building structure will vary between designs, the maximum stresses and deflections shall be analyzed to suit the specific design.
Table 8.4.8.7 Stresses and Deflections of Guide-Rail Brackets and Supports
Guide-Rail Bracket | L | Bracket Type | Vertical Location | Typical Figure | Bracket Moment of Inertia, mm4 (in.4) | Bracket Design Load, P [Notes (1) and (2), and (3)] | Allowable [Notes (6) and (7)] | |
---|---|---|---|---|---|---|---|---|
Stress, MPa (psi) | Deflection, mm (in.) [Note (4)] | |||||||
N (lb) | ||||||||
Main (car and counterweight) | ≥ Rail span ℓ | Any | Building supports | … | … | ![]() [Notes (1) and (2)] | Guide-Rail Brackets: No permanent deformation | 6 (0.25) |
![]() [Notes (3)] | ||||||||
≥ Rail span ℓ | ![]() [Notes (1) and (2)] | Fastenings: 8.4.2.3.3. | ||||||
![]() [Notes (1) and (3)] | Supports: N/A [Note (5)] | |||||||
Intermediate tie (counter-weight) | … | Double "U" bracket | Mid-span | ![]() | ld | ![]() [Notes (1) and (2)] | … | |
1/3 span | ||||||||
Single "U" bracket | Mid-span | ![]() | 2ld | ![]() [Notes (1) and (3)] | ||||
1/3 span |
Fp | = | seismic component force, N (lb) |
ld | = | moment of inertia of single "U" intermediate, tie bracket, mm4 (in.4), in a double "U" bracket arrangement |
L | = | vertical distance between the upper and lower position restraints required by 8.4.5.1 and 8.4.7.2, mm (in.) |
ℓ | = | distance (rail span) between adjacent main guide-rail brackets, mm (in.) |
W | = | maximum weight of car with 40% rated capacity or counterweight, kg (lb) |
P | = | horizontal seismic load, N (lb) |
NOTES:
- For hydraulic elevator main bracket design load (car) add 1/4 the weight of the plunger (zone 3 or greater).
- For zone 2, multiply design load "P" by 0.5.
-
CB = 0.7 for purposes of stress calculations. CB = 1.0 for purposes of deflection calculations. - This limitation includes the combined deflections of the guide-rail bracket, fastenings, and building supports.
- The design of supports beyond deflection is the responsibility of the Structural Engineer of Record.
- The maximum combined stresses in any structural component due to all causes shall be based on sound engineering practice, and shall not exceed the allowable values specified in ANSI/AISC 360, Chapter H (Design of Members for Combined Forces and Torsion), for individual components.
- For jurisdictions enforcing seismic zones, allowable stresses may be increased by 1/3. For jurisdictions enforcing the IBC or NBCC 2005 or later editions, no 1/3 increase is allowed.
The following information regarding horizontal seismic forces imposed on the guide-rail brackets by the position restraints of the car or counterweight is required on elevator layout drawings. The forces are to be determined as specified in 8.4.8.9.1 and 8.4.8.9.2 (see Fig. 8.4.8.9). 
Fig. 8.4.8.9 Guide-Rail Axes

Force normal to the x-x axis of the guide rail:

(a) Where L ≥ ℓ (see Table 8.4.8.7):

(b) Where L < ℓ (see Table 8.4.8.7):

Where normal to the y-y axis:
(a) Where L ≥ ℓ (see Table 8.4.8.7):

(b) Where L < ℓ (see Table 8.4.8.7):

where
Fx-x, Fy-y | = | seismic force, N (lbf) |
Wp | = | total weight of car plus 40% of its rated load, or the total weight of the counterweight, N (lb) |
Fp | = | seismic component force as defined in 8.4.14 |
NOTE: For SI units — N = kg * 9.807
Where an expansion joint is located within the elevator installation, the location and maximum design displacement shall be indicated on the layout drawings.
All integral parts of driving machines together with their supports shall be capable of withstanding the inertia effect of their masses without permanent deformation when subjected to seismic forces acting separately as defined in 8.4.13 or 8.4.14, or equal to
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
Earthquake emergency operation shall be provided and conform to 8.4.10. Earthquake emergency operation is not required for risk zone 2, or Fp ≤ 0.25 Wp with z/h = 1 (for IBC/ASCE 7) or hx/hn = 1 (for NBCC) (see 8.4.14.2), provided the car and counterweight guide-rail systems, guiding members, and position restraints conform to the requirements and force levels for zone 3 or greater in 8.4.5, 8.4.7, and 8.4.8 where
Wp | = | component operating weight as defined by 8.4.15 |
(a) All traction elevators operating at a rated speed of 0.75 m/s (150 ft/min) or more and having counterweights located in the same hoistway shall be provided with the following:
(1) For seismic zone 3 or greater, or Fp > 0.25 Wp with z/h = 1 (for IBC/ASCE 7) or hx/hn = 1 (for NBCC): a minimum of one seismic switch per building
(2) For all elevators covered by Section 8.4
(b) an identified momentary reset button or switch for each elevator, located in the control panel in the elevator machine room [see 8.4.10.1.3(i)]
(b) For attendant-operated elevators and automatic elevators on designated attendant service, a signal system consisting of both visual and audible types activated by either the seismic switch or the displacement switch shall be provided to alert the attendant that the car is under earthquake emergency control and that the attendant is to return the car to the nearest available floor. The audible signal required by 2.27.3.1.6(h) shall be permitted to be used for this purpose in lieu of a separate audible signal.
Fig. 8.4.10.1.1 Earthquake Elevator Equipment Requirements Diagrammatic Representation

(a) Earthquake protective devices shall be of the failsafe type.
(b) Seismic switch shall activate upon excitation in a vertical direction of not more than 0.15 times gravity acceleration, 9.81 m/s2 (32.2 ft/s2). The frequency response of the switch shall be 1 Hz to 10 Hz.
Where the seismic switch is used exclusively to control the elevators, it shall be located in the elevator machine room and, where possible, shall be mounted adjacent to a vertical load-bearing building structural member.
(c) A displacement switch shall be activated by the derailment of the counterweight at any point in the hoistway to provide information to the control system that the counterweight has left its guides.
(d) Earthquake protective devices with exposed live electrical parts in the hoistway shall operate at not more than 24 V root mean square alternating current or 24 V direct current above or below ground potential and shall not be capable of supplying more than 0.5 A when short-circuited.
(a) Upon activation of a seismic switch, all elevators with traction machines, counterweights, and selective, collective, or group automatic operation that are in motion shall proceed to the nearest available floor, open their doors, and shut down; except that where Phase II Emergency In-Car Operation is in effect, door operation shall conform to 2.27.3.3.
(b) When the counterweight displacement switch is activated, the elevator, if in motion, shall initiate an emergency stop and then proceed away from the counterweight at a speed of not more than 0.75 m/s (150 ft/min) to the nearest available floor, open the doors, and shut down; except that where Phase II Emergency In-Car Operation is in effect, door operation shall conform to 2.27.3.3.
(c) Elevators with power-operated doors, upon reaching a landing shall cause their doors to open and remain open; except that where Phase II Emergency In-Car Operation is in effect, door operation shall conform to 2.27.3.3.
(d) Upon activation of an earthquake protective device, an elevator standing at a floor with its doors open shall remain at the floor. If its doors are closed, it shall open its doors. Where Phase II Emergency In-Car Operation is in effect, door operation shall conform to 2.27.3.3.
(e) An elevator not in operation when an earthquake protective device is activated shall remain at the landing.
(f) An elevator shall be permitted to be operated at a speed of not more than 0.75 m/s (150 ft/min), provided the counterweight displacement switch is of the continuously monitoring type and is not activated.
(g) Continuous activation of a displacement switch shall
(1) prevent operation of the car, except from the inspection station located on top of the car
(2) prevent operation of the car by means of the emergency service key described in 2.27.3.1 and 2.27.3.3, hospital emergency service key, and other similar types of operation
(h) Elevators stopped by an earthquake protective device with a volatile-type memory shall remain idle in the event of a power failure. Subsequent restoration of power shall not cancel the status of the earthquake protective devices nor the slow speed status of the elevator system if such existed prior to the loss of power.
(i) An elevator shall be permitted to be returned to normal service by means of the momentary reset button or switch [see 8.4.10.1.1(a)(2)], provided the displacement switch is not activated.
(j) Electrical protective devices required by 2.26.2 shall not be rendered inoperative nor bypassed by earthquake protective devices
Fig. 8.4.10.1.3 Earthquake Emergency Operation Diagrammatic Representation

Earthquake protective devices shall be arranged to be checked for satisfactory operation and shall be calibrated at intervals specified by the manufacturer.
Requirement 8.4.11 applies to all direct-acting hydraulic elevators and roped-hydraulic elevators.
For roped-hydraulic elevators other than those defined by Section 1.3 (Definitions), the requirements, formulas, and specified methods of calculation of loads and the resulting stresses and deflections do not generally apply and shall be modified to suit the specific conditions and requirements in each case.
Where hydraulic elevators are provided with counterweights, clearances shall conform to 8.4.1.
Overhead beams for attaching hitch plates shall be anchored to prevent overturning and displacement as a result of seismic forces acting simultaneously as specified in 8.4.13 or 8.4.14, or equal to
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
Fastening means in compliance with 8.4.2.3 shall be provided to prevent hydraulic machines, control panels, and storage tanks from being overturned or displaced.
Rope retainers provided on traveling sheaves and deflecting sheaves, in accordance with 3.18.1.2.4, shall comply with 8.4.3.1.2 through 8.4.3.1.4.
Requirement 8.4.4 does not apply to hydraulic elevators.
Guiding members and position restraints shall conform to 8.4.5 and 8.4.11.5.1.
Position restraints attached to the traveling sheave shall be provided for roped-hydraulic elevators. Separate position restraints are not required where such restraints are an integral part of the guiding means.
Position restraints and their attachments to the traveling sheave shall be designed to withstand a seismic force acting in a horizontal direction as defined in 8.4.13 or 8.4.14, or equal to
(a) Wp (zone 3 or greater)
(b) 1/4 Wp (zone 2)
on 1/2 the weight of the driving member of the hydraulic jack plus the weight of the traveling sheave and its attachments.
Requirement 8.4.6 does not apply to hydraulic elevators.
Where counterweights are provided, they shall conform to 8.4.7.
Guide rails, guide-rail supports, and their fastenings shall conform to the following, whichever is more restrictive:
(a) Where car safeties are provided, 3.17.2 shall apply.
(b) Seismic load application
(1) Requirement 8.4.8 shall apply.
(2) The load on the car side of direct-plunger hydraulic elevators shall be as determined by 8.4.8.3(a) and (b).
(3) Requirement 8.4.8.9 shall not apply.
The attachment of above ground hydraulic jacks to the building structure shall be capable of withstanding the inertia effect of their masses without permanent deformation when subjected to seismic forces as defined in 8.4.13 or 8.4.14, or separate acting forces equal to
(a) Wp horizontally and 1/2 Wp vertically (zone 3 or greater)
(b) 1/2 Wp horizontally and 1/4 Wp vertically (zone 2)
Requirement 8.4.10 does not apply to hydraulic elevators.
Where buildings are designed with expansion joints, the machine room and the hoistway shall be located on the same side of an expansion joint.
Hydraulic elevators not provided with car safeties complying with 3.17.2 shall be provided with
(a) an overspeed valve(s) conforming to 3.19.4.7, or
(1) Requirement 3.17.3.2 applies as modified. The primary actuation means shall be mechanical or hydraulic. Electrical means are permitted as a secondary actuation means.
(2) The plunger gripper shall be capable of withstanding inertia effects of the elevator masses without operational failure when subjected to seismic forces acting separately, an defined in 8.4.13 or 8.4.14, or equal to
(a) for zone 3 or greater, or Fp > 0.25Wp with z/h = 1 (or hx/hn = 1)
(1) Wplgr horizontally
(2) 1/2 (Wplgr + Wp) vertically
(b) for zone 2 or Fp ≤ 0.25 Wp with z/h = 1 or hx/hn = 1)
(1) 1/2Wplgr horizontally
(2) 1/4 (Wplgr + Wp) vertically
where Wplgr = weight of plunger
Piping supports to restrain transverse motion shall be provided near changes in direction and particularly near valves and joints and shall comply with 8.4.2.3.

Horizontal spans shall be supported at intervals not to exceed those specified in Table 8.4.11.13.
Table 8.4.11.13 Pipe Support Spacing
Nominal Pipe Size, in. | Maximum Spacing Between Supports, mm (in.) |
---|---|
1.0 | 1 525 (60) |
1.5 | 2 300 (90) |
2.0 | 2 600 (102) |
2.5 | 2 750 (108) |
3.0 | 3 000 (120) |
4.0 | 3 500 (138) |
(a) Spacing is based on a natural frequency limit of 20 Hz. The pipe is presumed to have oil in it and, for an added margin of safety, the oil is assumed to weigh 900 kg/m3 (56 lb/ft3) at 15.6°C (60°F).
(b) Maximum combined bending and shear stress is limited to 71.8 kPa (1,500 psi).
(c) Maximum sag at the center of the span is limited to 2.5 mm (0.1 in.).
(d) For pipe sizes other than shown, the maximum spacing between supports shall be determined by the following formula:
(SI Units)

(Imperial Units)

where
E | = | modulus of elasticity for steel [2 068 × 106 MPa (30 × 106 psi)] |
I | = | moment of inertia or pipe, mm4 (in.4) |
ℓ | = | maximum spacing between supports, m (ft) |
W | = | weight per foot of pipe with oil at 15.6°C (60°F), kg/m (lb/ft) |

Means shall be provided to prevent the tank from being overturned or displaced. Such means shall comply with 8.4.2.3.
The following information is required on elevator layout drawings. The horizontal seismic forces imposed on the guide-rail brackets by the position restraints of the traveling sheave and the position restraints of the car or the counterweight (where provided) shall be determined as shown in 8.4.11.15.1 and 8.4.11.15.2.
Force normal to (x-x) axis of the guide rail (see 8.4.8.9):

(a) Where L ≥ ℓ (see Table 8.4.8.7):

(b) Where L < ℓ (see Table 8.4.8.7):

Force normal to (y-y) axis of the guide rail (see 8.4.8.9):
(a) Where L ≥ ℓ (see Table 8.4.8.7):

(b) Where L < ℓ (see Table 8.4.8.7):

where
Fx-x, Fy-y | = | seismic force, N (lbf) |
Fp | = | seismic component force as defined by 8.4.14 |
Fplgr | = | seismic component force as defined by 8.4.14 substituting Wplgr for Wp |
(1) For car and counterweight lower position restraints:
Wp | = | total weight of car plus 40% of rated capacity, or the total weight of the counterweight, N (lb) |
Wplgr | = | plunger weight, N (lb) (for direct-acting hydraulic elevators), or |
= | 0 (for elevators provided with counterweights and roped-hydraulic elevators), based on the in-ground hydraulics. For other designs, the load distribution might be different. |
(2) For traveling sheave position restraints where guided on rails separate from car:
Wp | = | 1.5 × (weight of traveling sheave plus guide attachments), N (lb) |
Wplgr | = | plunger weight, N (lb) (for roped-hydraulic elevators) |
The following formulas shall be used to determine the maximum allowable weight per pair of guide rails.
(a) No intermediate tie brackets (car and counterweight rails):
(1) Traction elevators, roped-hydraulic elevators, or hydraulic elevator counterweight rails (where provided)
(SI Units)

(Imperial Units)

(2) Direct-acting hydraulic elevators (car guide rails only) or separately guided traveling sheaves
(SI Units)


(Imperial Units)

where

(b) One intermediate tie bracket located midway between main counterweighted guide-rail brackets:
(SI Units)

(Imperial Units)

(c) Two intermediate tie brackets approximately equally spaced between main counterweighted guide-rail brackets:
(SI Units)

(Imperial Units)

(a) No intermediate tie brackets (car and counterweight rails):
(1) Traction elevators, roped-hydraulic elevators, or hydraulic elevator counterweight rails (where provided):
(SI Units)

(Imperial Units)

(2) Direct-acting hydraulic elevators (car guide rails only) or separately guided traveling sheaves:
(SI Units)

(Imperial Units)

where

(b) One intermediate tie bracket located midway between main counterweighted guide-rail brackets
(SI Units)

(Imperial Units)

(c) Two intermediate tie brackets approximately equally spaced between main counterweighted guide-rail brackets
(SI Units)

(Imperial Units)

where
ℓ | = | distance between main car or counterweight guide-rail brackets, mm (in.) |
Wp | = | component operating weight as defined by 8.4.15 |
Wp' | = | maximum weight per pair of guide rails (hydraulic direct-acting elevators and separately guided traveling sheaves), N (lb) |
Wplgr | = | weight of hydraulic plunger, N (lb) |
Zx | = | elastic section modulus of rail about (x-x) axis, mm3 (in.3) |
Zy | = | elastic section modulus of rail about (y-y) axis, mm3 (in.3) |
The following formulas shall be used to determine the minimum allowable moment of inertia of guide rails.
(a) Traction elevators, roped-hydraulic elevators, or hydraulic elevator counterweight rails (where provided)

(b) Direct-acting hydraulic elevators (car guide rails only) or separately guided traveling sheaves

(a) Traction elevators, roped-hydraulic elevators, or hydraulic elevator counterweight rails (where provided)

(b) Direct-acting hydraulic elevators (car guide rails only) or separately guided traveling sheaves

Table 8.4.12.2.2 Maximum Allowable Deflection
Rail Size, kg (lb) | Δ, Max., mm (in.) |
---|---|
12.0 (8.0) | 20 (0.75) |
16.5 (11.0) | 25 (1.00) |
18.0 (12.0) | 32 (1.25) |
22.5 (15.0) | 38 (1.50) |
27.5 (18.5) | 38 (1.50) |
33.5 (22.5) | 38 (1.50) |
45.0 (30.0) | 45 (1.75) |

where
ℓ | = | distance between main car and counterweight guide-rail brackets, mm (in.) |
E | = | modulus of elasticity for steel = 2.068 × 105 MPa (30 × 106 psi) |
Ix | = | moment of inertia of rail about (x-x) axis, mm4 (in.4) |
Iy | = | moment of inertia of rail about (y-y) axis, mm4 (in.4) |
Wp | = | component operating weight as defined by 8.4.15 |
Wplgr | = | weight of hydraulic plunger, kg (lb) |
Δ | = | maximum allowable deflection at center of rail span, mm (in.), based on Table 8.4.12.2.2. |
For 8.4(b)(2), the component force level shall be the greater of that dictated by either of the following:
(a) the applicable building code's non-structural component requirements
When the applicable building code does not reference component vertical force levels, the appropriate seismic zone vertical force level shall be used when a vertical force level is specified.
In United States jurisdictions with building codes not referencing seismic zones and prior to IBC
Zone(s) | Affected Peak Velocity Acceleration, Aυ | |
---|---|---|
0 and 1 | Aυ < 0.10 | |
2 | 0.10 ≤ Aυ < 0.20 | |
3 and 4 | 0.20 ≤ Aυ |
In Canadian jurisdictions enforcing building codes prior to NBCC-2005, the following values of Zυ (velocity-related seismic zone) will determine the applicable seismic zone:
Zone(s) | Velocity-Related Seismic Zone, Zυ | |
---|---|---|
2 | 2 ≤ Zυ < 4 | |
≥ 3 | Zυ ≥ 4 |
NOTE: For Zυ values, see "Design Data for Selected Locations in Canada," in NBCC-1995, Appendix C.
The seismic force shall be computed per requirements of IBC/ASCE 7, or NBCC-2005 or later editions, in accordance with the applicable building code.
(a) For IBC/ASCE 7
Fp = Component Seismic Force Level (horizontal, Strength Design Level) =

Fp is not required to be taken as greater than
F = 1.6 SDSlpWp
and Fp shall not be taken as less than
Fp = 0.3 SDSlpWp
where
Fp | = | Component Seismic Force Level (horizontal, Strength Design Level) |
SDS | = | 5% damped design spectral response acceleration for short periods (i.e., 0.2 s) |
ap | = | component amplification factor = 1.00 |
lp | = | component importance factor = 1.00 or 1.50 |
Wp | = | component operating weight as defined in 8.4.15 |
Rp | = | component response modification factor = 2.5 |
z | = | height in structure of point of attachment of component with respect to the defined building base provided by the building structural engineer. For items at or below the base, z shall be taken as 0. The value of z/h need not exceed 1.0. (See Definitions, Section 1.3 for base, building and Guide for Elevator Seismic Design, Part 1) |
h | = | average roof height of structure with respect to the defined building base, provided by the building structural engineer |
NOTES:
- For isolated components refer to ASCE 7-10, Table 13.6-1.
- Fp shall be multiplied by a factor of 0.7 for stress calculations in order to convert from Strength Design (IBC/ASCE 7) to Allowable Stress Design (ASME A17.1). This factor is already included in the load combinations 8.4.14.1.3.
(b) For NBCC-2005 or later editions
Fp | = | Component Seismic Force Level (horizontal, Strength Design Level) = 0.3Fa Sa(0.2) IE Sp Wp |
where:
Fp | = | Component Seismic Force Level (horizontal, Strength Design Level) |
Fa | = | Acceleration-based site coefficient, defined in NBCC-2010, Table 4.1.8.4.B, based on Sa(0.2) and Site Class, A through F |
Sa(0.2) | = | 5% damped spectral response acceleration value, expressed as a ratio to gravitational acceleration, for a period of 0.2 s, defined in NBCC-2010, sentence 4.1.8.4(1) |
IE | = | Importance factor for the building, defined in NBCC-2010, Article 4.1.8.5 |
Sp | = | Cp Ar Ax/Rp (where Sp may range between 0.7 and 4.0) with |
Cp | = | component factor as listed in NBCC-2010, Table 4.1.8.18 |
Ar | = | component force amplification factor from NBCC-2010, Table 4.1.8.18 |
Ax | = | height factor (1 + 2 hx/hn) with |
hx | = | height in structure of point of attachment of component with respect to the defined building base provided by the building structural engineer. For items at or below the base, z shall be taken as 0. (See Definitions, Section 1.3 for base, building and Guide for Elevator Seismic Design, Part 1) |
hn | = | average roof height of structure with respect to the defined building base, provided by the building structural engineer. The value of hx/hn need not exceed 1.0. |
Rp | = | component response modification factor from NBCC-2010, Table 4.1.8.18 |
Wp | = | component operating weight as defined by 8.4.15 |
NOTES:
- For isolated components, refer to NBCC-2010, Table 4.1.8.18.
- Fp shall be multiplied by a factor of 0.7 for stress calculations in order to convert from Strength Design (NBCC-2010) to Allowable Stress Design (ASME A17.1). This factor is already included in the load combinations 8.4.14.1.3.
- Elevator equipment subject only to inertial accelerations of its own mass are considered rigid components when referencing NBCC-2010, Table 4.1.8.18 for variables Cp, Ar, and Rp. Elevator equipment subjected to accelerations and decelerations and subject to external forces independent of the mass of the component itself are considered machinery.
The seismic design force, Fp, shall be applied at the component's center of gravity. In addition, the component shall be designed for concurrent vertical seismic force Fυ equal to
(a) +/— 0.2 SDS Wp | (for IBC/ASCE 7) |
(b) +/— 0.2 [2/3 FaSa(0.2)]Wp | (for NBCC) |
NOTES:
- Guide rail mounted machinery would be an example of vertical loads imposed on the guide rail in addition to the horizontal inertial loads (see 8.4.8.2.6 and 8.4.14.1.1).
- Fυ shall be multiplied by a factor of 0.7 for stress calculations in order to convert from Strength Design (NBCC-2010) to Allowable Stress Design (ASME A17.1). This factor is already included in the load combinations 8.4.14.1.3.
Components and portions thereof shall resist the most critical effects resulting from the following combinations of loads:
For IBC/ASCE 7/NBCC
(a) (D + 0.7E), or
(b) (0.6D + 0.7E)
whichever is more stringent
where
D = dead load
E = earthquake load = Fp + Fυ
Increases in allowable stresses shall not be used.
The component operating weight, Wp shall be one of the following:
(a) for support or restraint of specific components, the component operating weight [N (lb)] will be used (i.e., counterweight, controller, etc.)
Where all electric elevator equipment cannot be located on one side of an expansion joint, the maximum displacement across the expansion joint as provided by the building design shall not impair the function of the elevator.
- Section 8.5 applies to all escalators and moving walks where such equipment is installed in buildings assigned to one of the following:
- Seismic Design Category C with Component Importance Factor, Ip, equal to 1.5 as defined by the New York City Building Code
- Seismic Design Category D or greater as defined by the New York City Building Code
- Design Spectral Response Acceleration for a 0.2 s time period [Sa(0.2)] greater than 0.12 and building designated as post-disaster building
- Seismic Performance Category C with Seismic Hazard Exposure Group II or higher as defined by earlier model building codes (see Note)
- Seismic Risk Zone 2 or greater as defined by earlier building codes (see Note)
- The appropriate Escalator Seismic Force Level is determined by the applicable building code.
- Where the applicable building code references Seismic Design Categories or Design Spectral Response Acceleration [Sa(0.2)], force levels as referenced by Section 8.4.14 shall be used (see the New York City Building Code).
- Where the applicable building code makes reference to ground motion parameters (such as Av or Zv), Section 8.4.13 shall be used.
- Where the applicable building code makes reference to Seismic Risk Zones or to Seismic Risk Zones and component force level equations, force levels for the appropriate zone, as listed throughout Section 8.5, or the calculated component force level, whichever is greater, shall be used.
- The escalator and moving walk safety requirements contained in Section 8.5 shall be used considering the requirements in the other parts of the code. These requirements are to be applied as well as those in Sections 6.1 and 6.2 but are not additive. Where multiple requirements are applicable to the same component, the most stringent requirement shall control.
Where the applicable building code does not make reference to seismic risk zones, the ground motion parameters shown in 8.4.13 shall be used.
The escalator and moving walk safety requirements contained in 8.5 shall be in addition to the requirements in the other parts of the Code unless otherwise specified.
Balustrades shall be designed to withstand the vertical inertial force due to the weight of the balustrade and the horizontal seismic forces as follows:
Fig. 8.5.1 Balustrade Handrail Force
GENERAL NOTE: This is a pictorial representation to be used for both escalators and moving walks.
- The component operating weight, Wp, is the sum of the balustrade dead load, decking weight if supported by the balustrade, and 70% of the machinery rated load (see Section 6.1.3.9.2) and the seismic force computed as defined in Sections 8.4.13 and 8.4.14.
- The seismic forces resulting from the machinery rated load shall be distributed along the exposed length of the handrail from entry newel tangent to exit newel tangent as depicted in Fig. 8.5.1.

Structural items not covered in Table 8.5.5 shall be capable of withstanding the inertia effect of the applicable masses without permanent deformation.
Wt = total dead load of the escalator, including all components supported by the truss.
- For jurisdictions enforcing seismic zones or an equivalent ground motion parameter (see 8.4.13), the horizontal (see Section 8.5.2.1) and vertical (see Section 8.5.2.2) seismic forces shall be applied separately (not simultaneously).
- Earthquake forces shall be applied simultaneously as defined by Section 8.4.14, except Wp = Wt + Wr where
Wt = total dead load of the escalator, including all components supported by the truss.
For jurisdictions enforcing seismic zones or an equivalent ground motion parameter, horizontal seismic forces shall be based on the total dead load of the escalator, including all components supported by the truss, plus 25% of the structural rated load in accordance with Section 6.1.3.9.1. The horizontal seismic force shall be computed as follows:
Where the applicable building code does not make reference to seismic risk zones, the ground motion parameters shown in Section 8.4.13 shall be used.
Fp = ZICp(Wt + Wr)
where
Cp | = | horizontal seismic force factor |
Fp | = | total horizontal seismic force |
I | = | importance factor |
Z | = | seismic zone factor |
= | 0.25 for seismic zone 2 | |
= | 0.5 for seismic zone 3 or greater |
Where the applicable building code does not make reference to seismic risk zones, the ground motion parameters shown in Section 8.4.13 shall be used.
The seismic zone shall be taken from the NHRP maps.
NOTE: When local building codes are more stringent, higher values may be applicable:
(a) For zone 2, Z = 0.25.
(b) For zone 3 or 4, Z = 0.5.
Where the applicable building code does not make reference to seismic risk zones, the ground motion parameters shown in 8.4.13 shall be used.
The escalator or moving walk is not considered a structural component of the building. The value of I shall be considered to be 1.0 unless the building is specified as an essential facility in which case a value of 1.25 shall be used.
For jurisdictions enforcing seismic zones or an equivalent ground motion parameter, vertical forces shall be structurally allocated among all the supports. The total vertical force shall be defined by the following table:
Zone | Total Vertical Force Ftv |
2 | (1 + 0.25) (Wt + Wr) |
3 or greater | (1 + 0.50) (Wt + Wr) |
The members in the truss shall be calculated by the Allowable Stress Method of the AISC Specification for Design, Fabrication, and Erection of Structural Steel for Buildings. The allowable stress as stipulated by the various sections is required to be used in lieu of yield stress. (See AISC example D1 for tension, E2 for compression, and F4 for shear stress. There are multiple rules for bending depending on type of section; therefore, examples are not listed.) Truss analysis, whether verified by computer or hand calculations, shall consider axial stresses of either compression or tension, combined axial compressive and bending stress, and combined axial tension and bending stress. There is no requirement for the escalator truss to be considered as a structural member of the building.
The truss end supports shall provide motion restraint in the principle horizontal directions capable of withstanding the seismic forces acting upon the escalator or moving walk. The clearance in the transverse direction between the escalator truss and the seismic restraint shall not exceed 6.5 mm (0.25 in.) on each side. Motion restraint in the longitudinal direction at either or both end supports shall accommodate the design story drift (see Section 8.5.3.2.2). Vertical restraint is required when the resultant vertical seismic force exceeds Wt + Wr (see Section 8.5.2.2). Where one end of the truss uses an unfastened restraint, forces resulting from movement of building structure members are not considered as being applied to the truss.
Truss end supports shall accommodate the design story drift (see Section 8.5.3.2.2) in the longitudinal direction such that
- clearance between the truss and the building is sufficient to prevent truss compression damage.
- seat depth (the longitudinal overlap and bearing surface between the building support and the truss support) is sufficient to prevent disengagement of the truss end with the building support.
When one end of the escalator truss is not designed to accommodate story drift, the design shall account for the forces developed by building movement in a manner that restricts transfer of these forces to the truss. The other truss end support shall be free to slide in the longitudinal direction to accommodate the design story drift. When both ends are designed to accommodate story drift
- means shall be provided to prevent any truss end from disengaging from its building support seat.
- the end supports shall be permitted to be free to slide in the longitudinal direction such that the sum of the motions accommodates the total design story drift.
At the sliding end(s), the depth of the beam seat shall be capable of accommodating the design story drift. The design story drift shall have a minimum value of 1.5 times the building story drift, as obtained from either of the following:
- the structural engineer or record.
- the maximum story drift value as per ASCE/SEI-7, Table 12.2.-1.
Intermediate support(s) for escalators and moving walks, when used, shall be of sufficient size to accommodate design story drift movement in both the longitudinal and transverse directions. Any motion restraint provided shall not reduce the story drift capacity of the support.
Earthquake protective devices shall be of the failsafe type. A minimum of one seismic detection device shall be provided in each escalator (nontandem operation or non-side-by-side arrangement) or moving walk. For escalators or moving walks in a tandem operation (see Section 6.1.6.6) or side-by-side arrangement, a minimum of one seismic detection device is required. The seismic detection device shall be mounted in the machine space or adjacent to the escalator or moving walk. Where possible, a seismic detection device shall be mounted adjacent to a vertical load-bearing building structural member when installed at an elevation above ground level, or any structural member if mounted at or below ground level, or any other location approved by the structural engineer of record.
- The seismic detection device shall conform to Sections 8.4.10.1.2(a) and (b).
- Actuation of the seismic detection device shall cause removal of power from the escalator and moving walk driving-machine motor(s) and brake(s) on all units controlled by the seismic detection device.
- Where a seismic detection device is used exclusively to control the escalator or moving walk, it shall be located in a machine room or machinery space and, where possible, shall be mounted adjacent to a vertical load-bearing member. Should no vertical load-bearing member be in close proximity, it shall be permitted to locate the seismic detection device at the nearest accessible vertical load-bearing member at approximately the same horizontal level as the upper machinery space or machine room.
The allowable stress limits to be used in the design of all escalator and moving walk components are listed in Table 8.5.5. An escalator or moving walk subjected to seismic loading shall be capable of withstanding the specified seismic forces in combination with the dynamic or static loads occurring during normal operation.
TABLE 8.5.5 Component-Based Allowable Design Stresses | |||
Component | Allowable Design Parameter | ||
Seismic Zones Criteria [Note(1)] |
Building Code | ||
IBC, ASCE/SEI-7 | NBCC 2005 or Later | ||
Structural, steel
|
0.88Fy | 0.6Fy | 0.6Fy |
Structural, other materials
|
Follow allowable limits asrecommended by designspecifications for materialof use | Follow allowable limits asrecommended by designspecifications for materialof use | Follow allowable limits asrecommended by designspecificat |