Part I — Administration

Part II — Definitions

Part III — Building Planning and Construction

Part IV — Energy Conservation

Part V — Mechanical

Part VI — Fuel Gas

Part VII — Plumbing

Part VIII — Electrical

Part IX — Referenced Standards

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings.
Roof and ceiling construction shall be capable of accommodating all loads imposed according to Section R301 and of transmitting the resulting loads to the supporting structural elements.
In areas where expansive or collapsible soils are known to exist, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface at least 5 feet (1524 mm) from foundation walls or to an approved drainage system.
Refer to Figure R301.2(5) for ground snow loads and Figure R301.2(4) for wind loads.
Load-bearing dimension lumber for rafters, trusses and ceiling joists shall be identified by a grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted.
Exception: Dimension lumber which is neither identified by a grade mark nor issued a certificate of inspection by a lumber grading or inspection agency may be used for load bearing purposes under the following conditions when authorized by the authority having jurisdiction:
  1. The producing mill shall sell or provide the lumber directly to the ultimate consumer or the consumer's contract builder for use in an approved structure.
  2. The producing mill shall certify in writing to the consumer or contract builder on a form to be provided by the authority having jurisdiction that the quality and safe working stresses of such lumber are equal to or exceed No. 2 grade of the species in accordance with the conditions set forth in American Softwood Lumber Standard (PS 20-99) published by the United States Department of Commerce. Such certification shall be filed as part of the building permit application.
Blocking shall be a minimum of utility grade lumber.
Approved end-jointed lumber identified by a grade mark conforming to Section R802.1 may be used interchangeably with solid-sawn members of the same species and grade.
Fire-retardanttreated wood (FRTW) is any wood product which, when impregnated with chemicals by a pressure process or other means during manufacture, shall have, when tested in accordance with ASTM E 84, a listed flame spread index of 25 or less and shows no evidence of significant progressive combustion when the test is continued for an additional 20-minute period. In addition, the flame front shall not progress more than 10.5 feet (3200 mm) beyond the center line of the burners at any time during the test.
Fire-retardant-treated lumber and wood structural panels shall be labeled. The label shall contain:
  1. The identification mark of an approved agency in accordance with Section 1703.5 of the Building Code of New York State.
  2. Identification of the treating manufacturer.
  3. The name of the fire-retardant treatment.
  4. The species of wood treated.
  5. Flame spread and smoke-developed rating.
  6. Method of drying after treatment.
  7. Conformance to appropriate standards in accordance with Sections R802.1.3.2 through R802.1.3.5.
  8. For FRTW exposed to weather, or a damp or wet location, the words "No increase in the listed classification when subjected to the Standard Rain Test" (ASTM D 2898).
Design values for untreated lumber and wood structural panels as specified in Section R802.1 shall be adjusted for fire-retardant-treated wood. Adjustments to design values shall be based upon an approved method of investigation which takes into consideration the effects of the anticipated temperature and humidity to which the fire-retardant-treated wood will be subjected, the type of treatment and redrying procedures.
The effect of treatment and the method of redrying after treatment, and exposure to high temperatures and high humidities on the flexure properties of fire-retardant-treated softwood plywood shall be determined in accordance with ASTM D 5516. The test data developed by ASTM D 5516 shall be used to develop adjustment factors, maximum loads and spans, or both for untreated plywood design values in accordance with ASTM D 6305. Each manufacturer shall publish the allowable maximum loads and spans for service as floor and roof sheathing for their treatment.
For each species of wood treated, the effect of the treatment and the method of redrying after treatment and exposure to high temperatures and high humidities on the allowable design properties of fire-retardant-treated lumber shall be determined in accordance with ASTM D 5664. The test data developed by ASTM D 5664 shall be used to develop modification factors for use at or near room temperature and at elevated temperatures and humidity in accordance with ASTM D 6841. Each manufacturer shall publish the modification factors for service at temperatures of not less than 80°F (27°C) and for roof framing. The roof framing modification factors shall take into consideration the climatological location.
Where fire-retardant-treated wood is exposed to weather or damp or wet locations, it shall be identified as "Exterior" to indicate there is no increase in the listed flame spread index as defined in Section R802.1.3 when subjected to ASTM D 2898.
Interior fire-retardant-treated wood shall have a moisture content of not over 28 percent when tested in accordance with ASTM D 3201 procedures at 92 percent relative humidity. Interior fire-retardant-treated wood shall be tested in accordance with Section R802.1.3.2.1 or R802.1.3.2.2. Interior fire-retardant-treated wood designated as Type A shall be tested in accordance with the provisions of this section.
Fire-retardant-treated wood shall be dried to a moisture content of 19 percent or less for lumber and 15 percent or less for wood structural panels before use. For wood kiln dried after treatment (KDAT) the kiln temperatures shall not exceed those used in kiln drying the lumber and plywood submitted for the tests described in Section R802.1.3.2.1 for plywood and R802.1.3.2.2 for lumber.
Glued laminated timbers shall be manufactured and identified as required in AITC A190.1 and ASTM D 3737.
Stress grading of structural log members of nonrectangular shape, as typically used in log buildings, shall be in accordance with ASTM D 3957. Such structural log members shall be identified by the grade mark of an approved lumber grading or inspection agency. In lieu of a grade mark on the material, a certificate of inspection as to species and grade issued by a lumber-grading or inspection agency meeting the requirements of this section shall be permitted to be accepted.
The framing details required in Section R802 apply to roofs having a minimum slope of three units vertical in 12 units horizontal (25-percent slope) or greater. Roof-ceilings shall be designed and constructed in accordance with the provisions of this chapter and Figures R606.11(1), R606.11(2) and R606.11(3) or in accordance with AFPA/NDS and ASCE 7. Components of roof-ceilings shall be fastened in accordance with Table R602.3(1).
Rafters shall be framed to ridge board or to each other with a gusset plate as a tie. Ridge board shall be at least 1-inch (25 mm) nominal thickness and not less in depth than the cut end of the rafter. At all valleys and hips there shall be a valley or hip rafter not less than 2-inch (51 mm) nominal thickness and not less in depth than the cut end of the rafter. Hip and valley rafters shall be supported at the ridge by a brace to a bearing partition or be designed to carry and distribute the specific load at that point. Where the roof pitch is less than three units vertical in 12 units horizontal (25-percent slope), structural members that support rafters and ceiling joists, such as ridge beams, hips and valleys, shall be designed as beams.
Ceiling joists and rafters shall be nailed to each other in accordance with Table R802.5.1(9), and the rafter shall be nailed to the top wall plate in accordance with Table R602.3(1). Ceiling joists shall be continuous or securely joined in accordance with Table R802.5.1(9) where they meet over interior partitions and are nailed to adjacent rafters to provide a continuous tie across the building when such joists are parallel to the rafters.

Where ceiling joists are not connected to the rafters at the top wall plate, joists connected higher in the attic shall be installed as rafter ties, or rafter ties shall be installed to provide a continuous tie. Where ceiling joists are not parallel to rafters, rafter ties shall be installed. Rafter ties shall be a minimum of 2-inch by 4-inch (51 mm by 102 mm) (nominal), installed in accordance with the connection requirements in Table R802.5.1(9), or connections of equivalent capacities shall be provided. Where ceiling joists or rafter ties are not provided, the ridge formed by these rafters shall be supported by a wall or girder designed in accordance with accepted engineering practice.

Collar ties or ridge straps to resist wind uplift shall be connected in the upper third of the attic space in accordance with Table R602.3(1).

Collar ties shall be a minimum of 1-inch by 4-inch (25 mm by 102 mm) (nominal), spaced not more than 4 feet (1219 mm) on center.
Ends of ceiling joists shall be lapped a minimum of 3 inches (76 mm) or butted over bearing partitions or beams and toenailed to the bearing member. When ceiling joists are used to provide resistance to rafter thrust, lapped joists shall be nailed together in accordance with Table R602.3(1) and butted joists shall be tied together in a manner to resist such thrust.
Spans for ceiling joists shall be in accordance with Tables R802.4(1) and R802.4(2). For other grades and species and for other loading conditions, refer to the AF&PA; Span Tables for Joists and Rafters.

TABLE R802.4(1)
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics without storage, live load = 10 psf, L/Δ = 240
CEILING JOIST
SPACING

(inches)
SPECIES AND GRADE DEAD LOAD = 5 psf
2 × 4 2 × 6  2 × 8 2 × 10
Maximum ceiling joist spans
(feet - inches) (feet - inches) (feet - inches) (feet - inches)
  Douglas fir-larch SS 13-2 20-8 Note a Note a
  Douglas fir-larch #1 12-8 19-11 Note a Note a
  Douglas fir-larch #2 12-5 19-6 25-8 Note a
  Douglas fir-larch #3 10-10 15-10 20-1 24-6
  Hem-fir SS 12-5 19-6 25-8 Note a
  Hem-fir #1 12-2 19-1 25-2 Note a
  Hem-fir #2 11-7 18-2 24-0 Note a
  Hem-fir #3 10-10 15-10 20-1 24-6
12 Southern pine SS 12-11 20-3 Note a Note a
  Southern pine #1 12-8 19-11 Note a Note a
  Southern pine #2 12-5 19-6 25-8 Note a
  Southern pine #3 11-6 17-0 21-8 25-7
  Spruce-pine-firb SS 12-2 19-1 25-2 Note a
  Spruce-pine-firb #1 11-10 18-8 24-7 Note a
  Spruce-pine-firb #2 11-10 18-8 24-7 Note a
  Spruce-pine-firb #3 10-10 15-10 20-1 24-6
  Douglas fir-larch SS 11-11 18-9 24-8 Note a
  Douglas fir-larch #1 11-6 18-1 23-10 Note a
  Douglas fir-larch #2 11-3 17-8 23-0 Note a
  Douglas fir-larch #3 9-5 13-9 17-5 21-3
  Hem-fir SS 11-3 17-8 23-4 Note a
  Hem-fir #1 11-0 17-4 22-10 Note a
  Hem-fir #2 10-6 16-6 21-9 Note a
  Hem-fir #3 9-5 13-9 17-5 21-3
16 Southern pine SS 11-9 18-5 24-3 Note a
  Southern pine #1 11-6 18-1 23-1 Note a
  Southern pine #2 11-3 17-8 23-4 Note a
  Southern pine #3 10-0 14-9 18-9 22-2
  Spruce-pine-firb SS 11-0 17-4 22-10 Note a
  Spruce-pine-firb #1 10-9 16-11 22-4 Note a
  Spruce-pine-firb #2 10-9 16-11 22-4 Note a
  Spruce-pine-firb #3 9-5 13-9 17-5 21-3
  Douglas fir-larch SS 11-3 17-8 23-3 Note a
  Douglas fir-larch #1 10-10 17-0 22-5 Note a
  Douglas fir-larch #2 10-7 16-7 21-0 25-8
  Douglas fir-larch #3 8-7 12-6 15-10 19-5
  Hem-fir SS 10-7 16-8 21-11 Note a
  Hem-fir #1 10-4 16-4 21-6 Note a
  Hem-fir #2 9-11 15-7 20-6 25-3
  Hem-fir #3 8-7 12-6 15-10 19-5
19.2 Southern -pine SS 11-0 17-4 22-10 Note a
  Southern pine #1 10-10 17-0 22-5 Note a
  Southern pine #2 10-7 16-8 21-11 Note a
  Southern pine #3 9-1 13-6 17-2 20-3
  Spruce-pine-firb SS 10-4 16-4 21-6 Note a
  Spruce-pine-firb #1 10-2 15-11 21-0 25-8
  Spruce-pine-firb #2 10-2 15-11 21-0 25-8
  Spruce-pine-firb #3 8-7 12-6 15-10 19-5
  Douglas fir-larch SS 10-5 16-4 21-7 Note a
  Douglas fir-larch #1 10-0 15-9 20-1 24-6
  Douglas fir-larch #2 9-10 14-10 18-9 22-11
  Douglas fir-larch #3 7-8 11-2 14-2 17-4
  Hem-fir SS 9-10 15-6 20-5 Note a
  Hem-fir #1 9-8 15-2 19-7 23-11
  Hem-fir #2 9-2 14-5 18-6 22-7
  Hem-fir #3 7-8 11-2 14-2 17-4
24 Southern pine SS 10-3 16-1 21-2 Note a
  Southern pine #1 10-0 15-9 20-10 Note a
  Southern pine #2 9-10 15-6 20-1 23-11
  Southern pine #3 8-2 12-0 15-4 18-1
  Spruce-pine-firb SS 9-8 15-2 19-11 25-5
  Spruce-pine-firb #1 9-5 14-9 18-9 22-11
  Spruce-pine-firb #2 9-5 14-9 18-9 22-11
  Spruce-pine-firb #3 7-8 11-2 14-2 17-4
Check sources for availability of lumber in lengths greater than 20 feet.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. Span exceeds 26 feet in length.
  2. North American Spruce-Pine-Fir species only
TABLE R802.4(2)
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics with limited storage, live load = 20 psf, L/Δ = 240)
CEILING JOIST
SPACING

(inches)
SPECIES AND GRADE
DEAD LOAD = 10 psf
2 × 4  2 × 6 2 × 8 2 × 10
Maximum Ceiling Joist Spans
(feet - inches) (feet - inches) (feet - inches) (feet - inches)
  Douglas fir-larch SS 10-5 16-4 21-7 Note a
  Douglas fir-larch #1 10-0 15-9 20-1 24-6
  Douglas fir-larch #2 9-10 14-10 18-9 22-11
  Douglas fir-larch #3 7-8 11-2 14-2 17-4
  Hem-fir SS 9-10 15-6 20-5 Note a
  Hem-fir #1 9-8 15-2 19-7 23-11
  Hem-fir #2 9-2 14-5 18-6 22-7
  Hem-fir #3 7-8 11-2 14-2 17-4
12 Southern pine SS 10-3 16-1 21-2 Note a
  Southern pine #1 10-0 15-9 20-10 Note a
  Southern pine #2 9-10 15-6 20-1 23-11
  Southern pine #3 8-2 12-0 15-4 18-1
  Spruce-pine-firb SS 9-8 15-2 19-11 25-5
  Spruce-pine-firb #1 9-5 14-9 18-9 22-1
  Spruce-pine-firb #2 9-5 14-9 18-9 22-1
  Spruce-pine-firb #3 7-8 11-2 14-2 17-4
  Douglas fir-larch SS 9-6 14-11 19-7 25-0
  Douglas fir-larch #1 9-1 13-9 17-5 21-3
  Douglas fir-larch #2 8-9 12-10 16-3 19-10
  Douglas fir-larch #3 6-8 9-8 12-4 15-0
  Hem-fir SS 8-11 14-1 18-6 23-8
  Hem-fir #1 8-9 13-5 16-10 20-8
  Hem-fir #2 8-4 12-8 16-0 19-7
  Hem-fir #3 6-8 9-8 12-4 15-0
16 Southern pine SS 9-4 14-7 19-3 24-7
  Southern pine #1 9-1 14-4 18-11 23-1
  Southern pine #2 8-11 13-6 17-5 20-9
  Southern pine #3 7-1 10-5 13-3 15-8
  Spruce-pine-firb SS 8-9 13-9 18-1 23-1
  Spruce-pine-firb #1 8-7 12-10 16-3 19-10
  Spruce-pine-firb #2 8-7 12-10 16-3 19-10
  Spruce-pine-firb #3 6-8 9-8 12-4 15-0
  Douglas fir-larch SS 8-11 14-0 18-5 23-4
  Douglas fir-larch  #1 8-7 12-6 15-10 19-5
  Douglas fir-larch #2 8-0 11-9 14-10 18-2
  Douglas fir-larch #3 6-1 8-10 11-3 13-8
  Hem-fir SS 8-5 13-3 17-5 22-3
  Hem-fir #1 8-3 12-3 15-6 18-11
  Hem-fir #2 7-10 11-7 14-8 17-10
  Hem-fir #3 6-1 8-10 11-3 13-8
19.2 Southern pine SS 8-9 13-9 18-1 23-1
  Southern pine #1 8-7 13-6 17-9 21-1
  Southern pine #2 8-5 12-3 15-10 18-11
  Southern pine #3 6-5 9-6 12-1 14-4
  Spruce-pine-firb SS 8-3 12-11 17-1 21-8
  Spruce-pine-firb #1 8-0 11-9 14-10 18-2
  Spruce-pine-firb #2 8-0 11-9 14-10 18-2
  Spruce-pine-firb #3 6-1 8-10 11-3 13-8
  Douglas fir-larch SS 8-3 13-0 17-1 20-11
  Douglas fir-larch #1 7-8 11-2 14-2 17-4
  Douglas fir-larch #2 7-2 10-6 13-3 16-3
  Douglas fir-larch #3 5-5 7-11 10-0 12-3
  Hem-fir SS 7-10 12-3 16-2 20-6
  Hem-fir #1 7-6 10-11 13-10 16-11
  Hem-fir #2 7-1 10-4 13-1 16-0
  Hem-fir #3 5-5 7-11 10-0 12-3
24 Southern pine SS 8-1 12-9 16-10 21-6
  Southern pine #1 8-0 12-6 15-10 18-10
  Southern pine #2 7-8 11-0 14-2 16-11
  Southern pine #3 5-9 8-6 10-10 12-10
  Spruce-pine-firb SS 7-8 12-0 15-10 19-5
  Spruce-pine-firb #1 7-2 10-6 13-3 16-3
  Spruce-pine-firb #2 7-2 10-6 13-3 16-3
  Spruce-pine-firb
#3
5-5 7-11 10-0 12-3
Check sources for availability of lumber in lengths greater than 20 feet.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. Span exceeds 26 feet in length.
  2. North American Spruce-Pine-Fir species only
In conventional rafter construction, the unsupported span of ceiling joists shall not exceed the values set forth in Table R802.4(1) in attics which do not have a clear height of 42 inches (1067 mm) or more between joist and rafter, provided the design live load does not exceed 10 psf (479 Pa) and the design dead load does not exceed 5 psf (239Pa).
In conventional rafter construction, the unsupported span of ceiling joists shall not exceed the values set forth in Table R802.4(2) in attics which are not served by a fixed stair, have a clear height of 42 inches (1067 mm) or more between joist and rafter, and have a design live load not exceeding 20 psf (958 Pa) and a design dead load not exceeding 10 psf (479 Pa). The maximum allowable span of joists that support attic spaces that are accessed by means of a fixed stair shall be determined in accordance with Table R502.3.1(1) for residential sleeping areas.
Spans for rafters shall be in accordance with Tables R802.5.1(1) through R802.5.1(8). For other grades and species and for other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters and applicable provisions of ASCE 7. The span of each rafter shall be measured along the horizontal projection of the rafter.
Installation of purlins to reduce the span of rafters is permitted as shown in Figure R802.5.1. Purlins shall be sized no less than the required size of the rafters that they support. Purlins shall be continuous and shall be supported by 2-inch by 4-inch (51 mm by 102 mm) braces installed to bearing walls at a slope not less than 45 degrees from the horizontal. The braces shall be spaced not more than 4 feet (1219 mm) on center and the unbraced length of braces shall not exceed 8 feet (2438 mm).
TABLE R802.5.1 (1)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling not attached to rafters, L/Δ = 180)
RAFTER SPACING
(inches)
SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6  2 × 8 2 × 10 2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 11-6 18-0 23-9 Note b Note b 11-6 18-0 23-5 Note b Note b
  Douglas fir-larch #1 1-1 17-4 22-5 Note b Note b 10-6 15-4 19-5 23-9 Note b
  Douglas fir-larch #2 1-10 16-7 21-0 25-8 Note b 9-10 14-4 18-2 22-3 25-9
  Douglas fir-larch #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Hem-fir SS 10-10 17-0 22-5 Note b Note b 10-10 17-0 22-5 Note b Note b
  Hem-fir #1 10 -7 16-8 21-10 Note b Note b 10-3 14-11 18-11 23-2 Note b
  Hem-fir #2 10-1 15-11 20-8 25-3 Note b 9-8 14-2 17-11 21-11 25-5
  Hem-fir #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
12 Southern pine SS 11-3 17-8 23-4 Note b Note b 11-3 17-8 23-4 Note b Note b
  Southern pine #1 11-1 17-4 22-11 Note b Note b 11-1 17-3 21-9 25-10 Note b
  Southern pine #2 10-10 17-0 22-5 Note b Note b 10-6 15-1 19-5 23-2 Note b
  Southern pine #3 9-1 13-6 17-2 20-3 24-1 7-11 11-8 14-10 17-6 20-11
  Spruce-pine-firc SS 10-7 16-8 21-11 Note b Note b 10-7 16-8 21-9 Note b Note b
  Spruce-pine-firc #1 10-4 16-3 21-0 25-8 Note b 9-10 14-4 18-2 22-3 25-9
  Spruce-pine-firc #2 10-4 16-3 21-0 25-8 Note b 9-10 14-4 18-2 22-3 25-9
  Spruce-pine-firc #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Douglas fir-larch SS 10-5 16-4 21-7 Note b Note b 10-5 16-0 20-3 24-9 Note b
  Douglas fir-larch #1 10-0 15-4 19-5 23-9 Note b 9-1 13-3 16-10 20-7 23-10
  Douglas fir-larch #2 9-10 14-4 18-2 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Douglas fir-larch #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
  Hem-fir SS 9-10 15-6 20-5 Note b Note b 9-10 15-6 19-11 24-4 Note b
  Hem-fir #1 9-8 14-11 18-11 23-2 Note b 8-10 12-11 16-5 20-0 23-3
  Hem-fir #2 9-2 14-2 17-11 21-11 25-5 8-5 12-3 15-6 18-11 22-0
  Hem-fir #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
16 Southern pine SS 10-3 16-1 21-2 Note b Note b 10-3 16-1 21-2 Note b Note b
  Southern pine #1 10-0 15-9 20-10 25-10 Note b 10-0 15-0 18-10 22-4 Note b
  Southern pine #2 9-10 15-1 19-5 23-2 Note b 9-1 13-0 16-10 20-1 23-7
  Southern pine #3 7-11 11-8 14-10 17-6 20-11 6-10 10-1 12-10 15-2 18-1
  Spruce-pine-firc SS 9-8 15-2 19-11 25-5 Note b 9-8 14-10 18-10 23-0 Note b
  Spruce-pine-firc #1 9-5 14-4 18-2 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Spruce-pine-firc #2 9-5 14-4 18-2 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Spruce-pine-firc #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
  Douglas fir-larch SS 9-10 15-5 20-4 25-11 Note b 9-10 14-7 18-6 22-7 Note b
  Douglas fir-larch #1 9-5 14-0 17-9 21-8 25-2 8-4 12-2 15-4 18-9 21-9
  Douglas fir-larch #2 8-11 13-1 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Douglas fir-larch #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
  Hem-fir SS 9-3 14-7 19-2 24-6 Note b 9-3 14-4 18-2 22-3 25-9
  Hem-fir #1 9-1 13-8 17-4 21-1 24-6 8-1 11-10 15-0 18-4 21-3
  Hem-fir #2 8-8 12-11 16-4 20-0 23-2 7-8 11-2 14-2 17-4 20-1
  Hem-fir #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
19.2 Southern pine SS 9-8 15-2 19-11 25-5 Note b 9-8 15-2 19-11 25-5 Note b
  Southern pine #1 9-5 14-10 19-7 23-7 Note b 9-3 13-8 17-2 20-5 24-4
  Southern pine #2 9-3 13-9 17-9 21-2 24-10 8-4 11-11 15-4 18-4 21-6
  Southern pine #3 7-3 10-8 13-7 16-0 19-1 6-3 9-3 11-9 13-10 16-6
  Spruce-pine-firc SS 9-1 14-3 18-9 23-11 Note b 9-1 13-7 17-2 21-0 24-4
  Spruce-pine-firc #1 8-10 13-1 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Spruce-pine-firc #2 8-10 13-1 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Spruce-pine-firc #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
  Douglas fir-larch SS 9-1 14-4 18-10 23-4 Note b 8-11 13-1 16-7 20-3 23-5
  Douglas fir-larch #1 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Douglas fir-larch #2 8-0 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Douglas fir-larch #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
  Hem-fir SS 8-7 13-6 17-10 22-9 Note b 8-7 12-10 16-3 19-10 23-0
  Hem-fir #1 8-4 12-3 15-6 18-11 21-11 7-3 10-7 13-5 16-4 19-0
  Hem-fir #2 7-11 11-7 14-8 17-10 20-9 6-10 10-0 12-8 15-6 17-11
  Hem-fir #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
24 Southern pine SS 8-11 14-1 18-6 23-8 Note b 8-11 14-1 18-6 22-11 Note b
  Southern pine #1 8-9 13-9 17-9 21-1 25-2 8-3 12-3 15-4 18-3 21-9
  Southern pine #2 8-7 12-3 15-10 18-11 22-2 7-5 10-8 13-9 16-5 19-3
  Southern pine #3 6-5 9-6 12-1 14-4 17-1 5-7 8-3 10-6 12-5 14-9
  Spruce-pine-firc SS 8-5 13-3 17-5 21-8 25-2 8-4 12-2 15-4 18-9 21-9
  Spruce-pine-firc #1 8-0 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Spruce-pine-firc #2 8-0 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Spruce-pine-firc #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:
    HC = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. Span exceeds 26 feet in length.
  3. North American Spruce-Pine-Fir species only.
TABLE R802.5.1(2)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling attached to rafters, L/Δ = 240)
RAFTER SPACING(inches) SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6 2 × 8 2 × 10 2 × 12 2 × 4   2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet -inches) (feet -inches) (feet -inches) (feet - inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 10-5 16-4 21-7 Note b Note b 10-5 16-4 21-7 Note b Note b
  Douglas fir-larch  #1 10-0 15-9 20-10 Note b Note b 10-0 15-4 19-5 23-9 Note b
  Douglas fir-larch #2 9-10 15-6 20-5 25-8 Note b 9-10 14-4 18-2 22-3 25-9
  Douglas fir-larch #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Hem-fir SS 9-10 15-6 20-5 Note b Note b 9-10 15-6 20-5 Note b Note b
  Hem-fir #1 9-8 15-2 19-11 25-5 Note b 9-8 14-11 18-11 23-2 Note b
  Hem-fir #2 9-2 14-5 19-0 24-3 Note b 9-2 14-2 17-11 21-11 25-5
  Hem-fir #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
12 Southern pine SS 10-3 16-1 21-2 Note b Note b 10-3 16-1 21-2 Note b Note b
  Southern pine #1 10-0 15-9 20-10 Note b Note b 10-0 15-9 20-10 25-10 Note b
  Southern pine #2 9-10 15-6 20-5 Note b Note b 9-10 15-1 19-5 23-2 Note b
  Southern pine #3 9-1 13-6 17-2 20-3 24-1 7-11 11-8 14-10 17-6 20-11
  Spruce-pine-firc SS 9-8 15-2 19-11 25-5 Note b 9-8 15-2 19-11 25-5 Note b
  Spruce-pine-firc #1 9-5 14-9 19-6 24-10 Note b 9-5 14-4 18-2 22-3 25-9
  Spruce-pine-firc #2 9-5 14-9 19-6 24-10 Note b 9-5 14-4 18-2 22-3 25-9
  Spruce-pine-firc #3 8-7 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Douglas fir-larch SS 9-6 14-11 19-7 25-0 Note b 9-6 14-11 19-7 24-9 Note b
  Douglas fir-larch #1 9-1 14-4 18-11 23-9 Note b 9-1 13-3 16-10 20-7 23-10
  Douglas fir-larch #2 8-11 14-1 18-2 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Douglas fir-larch #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
  Hem-fir SS 8-11 14-1 18-6 23-8 Note b 8-11 14-1 18-6 23-8 Note b
  Hem-fir #1 8-9 13-9 18-1 23-1 Note b 8-9 12-11 16-5 20-0 23-3
  Hem-fir #2 8-4 13-1 17-3 21-11 25-5 8-4 12-3 15-6 18-11 22-0
  Hem-fir #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
16 Southern pine SS 9-4 14-7 19-3 24-7 Note b 9-4 14-7 19-3 24-7 Note b
  Southern pine #1 9-1 14-4 18-11 24-1 Note b 9-1 14-4 18-10 22-4 Note b
  Southern pine #2 8-11 14-1 18-6 23-2 Note b 8-11 13-0 16-10 20-1 23-7
  Southern pine #3 7-11 11-8 14-10 17-6 20-11 6-10 10-1 12-10 15-2 18-1
  Spruce-pine-firc SS 8-9 13-9 18-1 23-1 Note b 8-9 13-9 18-1 23-0 Note b
  Spruce-pine-firc #1 8-7 13-5 17-9 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Spruce-pine-firc #2 8-7 13-5 17-9 22-3 25-9 8-6 12-5 15-9 19-3 22-4
  Spruce-pine-firc #3 7-5 10-10 13-9 16-9 19-6 6-5 9-5 11-11 14-6 16-10
  Douglas fir-larch SS 8-11 14-0 18-5 23-7 Note b 8-11 14-0 18-5 22-7 Note b
  Douglas fir-larch #1 8-7 13-6 17-9 21-8 25-2 8-4 12-2 15-4 18-9 21-9
  Douglas fir-larch #2 8-5 13-1 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Douglas fir-larch #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
  Hem-fir SS 8-5 13-3 17-5 22-3 Note b 8-5 13-3 17-5 22-3 25-9
  Hem-fir #1 8-3 12-11 17-1 21-1 24-6 8-1 11-10 15-0 18-4 21-3
  Hem-fir #2 7-10 12-4 16-3 20-0 23-2 7-8 11-2 14-2 17-4 20-1
  Hem-fir #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
19.2 Southern pine SS 8-9 13-9 18-1 23-1 Note b 8-9 13-9 18-1 23-1 Note b
  Southern pine #1 8-7 13-6 17-9 22-8 Note b 8-7 13-6 17-2 20-5 24-4
  Southern pine #2 8-5 13-3 17-5 21-2 24-10 8-4 11-11 15-4 18-4 21-6
  Southern pine #3 7-3 10-8 13-7 16-0 19-1 6-3 9-3 11-9 13-10 16-6
  Spruce-pine-firc SS 8-3 12-11 17-1 21-9 Note b 8-3 12-11 17-1 21-0 24-4
  Spruce-pine-firc #1 8-1 12-8 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Spruce-pine-firc #2 8-1 12-8 16-7 20-3 23-6 7-9 11-4 14-4 17-7 20-4
  Spruce-pine-firc #3 6-9 9-11 12-7 15-4 17-9 5-10 8-7 10-10 13-3 15-5
  Douglas fir-larch SS 8-3 13-0 17-2 21-10 Note b 8-3 13-0 16-7 20-3 23-5
  Douglas fir-larch #1 8-0 12-6 15-10 19-5 22-6 7-5 10-10 13-9 16-9 19-6
  Douglas fir-larch #2 7-10 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Douglas fir-larch #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
  Hem-fir SS 7-10 12-3 16-2 20-8 25-1 7-10 12-3 16-2 19-10 23-0
  Hem-fir  #1 7-8 12-0 15-6 18-11 21-11 7-3 10-7 13-5 16-4 19-0
  Hem-fir #2 7-3 11-5 14-8 17-10 20-9 6-10 10-0 12-8 15-6 17-11
  Hem-fir #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
24 Southern pine SS 8-1 12-9 16-10 21-6 Note b 8-1 12-9 16-10 21-6 Note b
  Southern pine #1 8-0 12-6 16-6 21-1 25-2 8-0 12-3 15-4 18-3 21-9
  Southern pine  #2 7-10 12-3 15-10 18-11 22-2 7-5 10-8 13-9 16-5 19-3
  Southern pine  #3 6-5 9-6 12-1 14-4 17-1 5-7 8-3 10-6 12-5 14-9
  Spruce-pine-firc SS 7-8 12-0 15-10 20-2 24-7 7-8 12-0 15-4 18-9 21-9
  Spruce-pine-firc #1 7-6 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Spruce-pine-firc #2 7-6 11-9 14-10 18-2 21-0 6-11 10-2 12-10 15-8 18-3
  Spruce-pine-firc #3 6-1 8-10 11-3 13-8 15-11 5-3 7-8 9-9 11-10 13-9
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00

    where:
    HC
    = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR
    = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. Span exceeds 26 feet in length.
  3. North American Spruce-Pine-Fir species only.

TABLE R802.5.1(3)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=30 psf, ceiling not attached to rafters, L/Δ = 180)
RAFTER SPACING(inches) SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6 2 × 8 2 × 10  2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 10-0 15-9 20-9 Note b Note b 10-0 15-9 20-1 24-6 Note b
  Douglas fir-larch #1 9-8 14-9 18-8 22-9 Note b 9-0 13-2 16-8 20-4 23-7
  Douglas fir-larch #2 9-5 13-9 17-5 21-4 24-8 8-5 12-4 15-7 19-1 22-1
  Douglas fir-larch #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Hem-fir SS 9-6 14-10 19-7 25-0 Note b 9-6 14-10 19-7 24-1 Note b
  Hem-fir #1 9-3 14-4 18-2 22-2 25-9 8-9 12-10 16-3 19-10 23-0
  Hem-fir #2 8-10 13-7 17-2 21-0 24-4 8-4 12-2 15-4 18-9 21-9
  Hem-fir #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
12 Southern pine SS 9-10 15-6 20-5 Note b Note b 9-10 15-6 20-5 Note b Note b
  Southern pine #1 9-8 15-2 20-0 24-9 Note b 9-8 14-10 18-8 22-2 Note b
  Southern pine #2 9-6 14-5 18-8 22-3 Note b 9-0 12-11 16-8 19-11 23-4
  Southern pine #3 7-7 11-2 14-3 16-10 20-0 6-9 10-0 12-9 15-1 17-11
  Spruce-pine-firc SS 9-3 14-7 19-2 24-6 Note b 9-3 14-7 18-8 22-9 Note b
  Spruce-pine-firc #1 9-1 13-9 17-5 21-4 24-8 8-5 12-4 15-7 19-1 22-1
  Spruce-pine-firc #2 9-1 13-9 17-5 21-4 24-8 8-5 12-4 15-7 19-1 22-1
  Spruce-pine-firc #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Douglas fir-larch SS 9-1 14-4 18-10 23-9 Note b 9-1 13-9 17-5 21-3 24-8
  Douglas fir-larch #1 8-9 12-9 16-2 19-9 22-10 7-10 11-5 14-5 17-8 20-5
  Douglas fir-larch #2 8-2 11-11 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Douglas fir-larch #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
  Hem-fir SS 8-7 13-6 17-10 22-9 Note b 8-7 13-6 17-1 20-10 24-2
  Hem-fir #1 8-5 12-5 15-9 19-3 22-3 7-7 11-1 14-1 17-2 19-11
  Hem-fir #2 8-0 11-9 14-11 18-2 21-1 7-2 10-6 13-4 16-3 18-10
  Hem-fir #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
16 Southern pine SS 8-11 14-1 18-6 23-8 Note b 8-11 14-1 18-6 23-8 Note b
  Southern pine #1 8-9 13-9 18-1 21-5 25-7 8-8 12-10 16-2 19-2 22-10
  Southern pine #2 8-7 12-6 16-2 19-3 22-7 7-10 11-2 14-5 17-3 20-2
  Southern pine #3 6-7 9-8 12-4 14-7 17-4 5-10 8-8 11-0 13-0 15-6
  Spruce-pine-firc SS 8-5 13-3 17-5 22-1 25-7 8-5 12-9 16-2 19-9 22-10
  Spruce-pine-firc #1 8-2 11-11 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Spruce-pine-firc #2 8-2 11-11 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Spruce-pine-firc #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
  Douglas fir-larch SS 8-7 13-6 17-9 21-8 25-2 8-7 12-6 15-10 19-5 22-6
  Douglas fir-larch #1 7-11 11-8 14-9 18-0 20-11 7-1 10-5 13-2 16-1 18-8
  Douglas fir-larch #2 7-5 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
  Douglas fir-larch #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
  Hem-fir SS 8-1 12-9 16-9 21-4 24-8 8-1 12-4 15-7 19-1 22-1
  Hem-fir #1 7-9 11-4 14-4 17-7 20-4 6-11 10-2 12-10 15-8 18-2
  Hem-fir #2 7-4 10-9 13-7 16-7 19-3 6-7 9-7 12-2 14-10 17-3
  Hem-fir #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
19.2 Southern pine SS 8-5 13-3 17-5 22-3 Note b 8-5 13-3 17-5 22-0 25-9
  Southern pine #1 8-3 13-0 16-6 19-7 23-4 7-11 11-9 14-9 17-6 20-11
  Southern pine #2 7-11 11-5 14-9 17-7 20-7 7-1 10-2 13-2 15-9 18-5
  Southern pine #3 6-0 8-10 11-3 13-4 15-10 5-4 7-11 10-1 11-11 14-2
  Spruce-pine-firc SS 7-11 12-5 16-5 20-2 23-4 7-11 11-8 14-9 18-0 20-11
  Spruce-pine-firc #1 7-5 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
  Spruce-pine-firc #2 7-5 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
 
Spruce-pine-firc #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
  Douglas fir-larch SS 7-11 12-6 15-10 19-5 22-6 7-8 11-3 14-2 17-4 20-1
  Douglas fir-larch #1 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Douglas fir-larch #2 6-8 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
  Hem-fir SS 7-6 11-10 15-7 19-1 22-1 7-6 11-0 13-11 17-0 19-9
  Hem-fir #1 6-11 10-2 12-10 15-8 18-2 6-2 9-1 11-6 14-0 16-3
  Hem-fir #2 6-7 9-7 12-2 14-10 17-3 5-10 8-7 10-10 13-3 15-5
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
24 Southern pine SS 7-10 12-3 16-2 20-8 25-1 7-10 12-3 16-2 19-8 23-0
  Southern pine #1 7-8 11-9 14-9 17-6 20-11 7-1 10-6 13-2 15-8 18-8
  Southern pine #2 7-1 10-2 13-2 15-9 18-5 6-4 9-2 11-9 14-1 16-6
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 4-9 7-1 9-0 10-8 12-8
  Spruce-pine-firc SS 7-4 11-7 14-9 18-0 20-11 7-1 10-5 13-2 16-1 18-8
  Spruce-pine-firc #1 6-8 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Spruce-pine-firc #2 6-8 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Spruce-pine-firc #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00


    where:
    HC
    = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.

    HR
    = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. Span exceeds 26 feet in length.
  3. North American Spruce-Pine-Fir species only.
TABLE R802.5.1(4)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=50 psf or less, ceiling not attached to rafters, L/Δ = 180)
RAFTER SPACING
(inches)
SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4   2 × 6 2 × 8 2 × 10 2 × 12 2 × 4  2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 8-5 13-3 17-6 22-4 26-0 8-5 13-3 17-0 20-9 24-0
  Douglas fir-larch #1 8-2 12-0 15-3 18-7 21-7 7-7 11-2 14-1 17-3 20-0
  Douglas fir-larch #2 7-8 11-3 14-3 17-5 20-2 7-1 10-5 13-2 16-1 18-8
  Douglas fir-larch #3 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
  Hem-fir SS 8-0 12-6 16-6 21-1 25-6 8-0 12-6 16-6 20-4 23-7
  Hem-fir #1 7-10 11-9 14-10 18-1 21-0 7-5 10-10 13-9 16-9 19-5
  Hem-fir #2 7-5 11-1 14-0 17-2 19-11 7-0 10-3 13-0 15-10 18-5
  Hem-fir #3 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
12 Southern pine SS 8-4 13-0 17-2 21-11 Note b 8-4 13-0 17-2 21-11 Note b
  Southern pine #1 8-2 12-10 16-10 20-3 24-1 8-2 12-6 15-9 18-9 22-4
  Southern pine #2 8-0 11-9 15-3 18-2 21-3 7-7 10-11 14-1 16-10 19-9
  Southern pine #3 6-2 9-2 11-8 13-9 16-4 5-9 8-5 10-9 12-9 15-2
  Spruce-pine-firc SS 7-10 12-3 16-2 20-8 24-1 7-10 12-3 15-9 19-3 22-4
  Spruce-pine-firc #1 7-8 11-3 14-3 17-5 20-2 7-1 10-5 13-2 16-1 18-8
  Spruce-pine-firc #2 7-8 11-3 14-3 17-5 20-2 7-1 10-5 13-2 16-1 18-8
  Spruce-pine-firc #3 5-10 8-6 10-9 13-2 15-2 5-5 7-10 10-0 12-2 14-1
  Douglas fir-larch SS 7-8 12-1 15-10 19-5 22-6 7-8 11-7 14-8 17-11 20-10
  Douglas fir-larch #1 7-1 10-5 13-2 16-1 18-8 6-7 9-8 12-2 14-11 17-3
  Douglas fir-larch #2 6-8 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
  Hem-fir SS 7-3 11-5 15-0 19-1 22-1 7-3 11-5 14-5 17-8 20-5
  Hem-fir #1 6-11 10-2 12-10 15-8 18-2 6-5 9-5 11-11 14-6 16-10
  Hem-fir #2 6-7 9-7 12-2 14-10 17-3 6-1 8-11 11-3 13-9 15-11
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
16 Southern pine SS 7-6 11-10 15-7 19-11 24-3 7-6 11-10 15-7 19-11 23-10
  Southern pine #1 7-5 11-7 14-9 17-6 20-11 7-4 10-10 13-8 16-2 19-4
  Southern pine #2 7-1 10-2 13-2 15-9 18-5 6-7 9-5 12-2 14-7 17-1
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 4-11 7-4 9-4 11-0 13-1
  Spruce-pine-firc SS 7-1 11-2 14-8 18-0 20-11 7-1 10-9 13-8 15-11 19-4
  Spruce-pine-firc #1 6-8 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Spruce-pine-firc #2 6-8 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Spruce-pine-firc #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
  Douglas fir-larch SS 7-3 11-4 14-6 17-8 20-6 7-3 10-7 13-5 16-5 19-0
  Douglas fir-larch #1 6-6 9-6 12-0 14-8 17-1 6-0 8-10 11-2 13-7 15-9
  Douglas fir-larch #2 6-1 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Douglas fir-larch #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
  Hem-fir SS 6-10 10-9 14-2 17-5 20-2 6-10 10-5 13-2 16-1 18-8
  Hem-fir #1 6-4 9-3 11-9 14-4 16-7 5-10 8-7 10-10 13-3 15-5
  Hem-fir #2 6-0 8-9 11-1 13-7 15-9 5-7 8-1 10-3 12-7 14-7
  Hem-fir #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
19.2 Southern pine SS 7-1 11-2 14-8 18-9 22-10 7-1 11-2 14-8 18 7 21-9
  Southern pine #1 7-0 10-8 13-5 16-0 19-1 6-8 9-11 12-5 14-10 17-8
  Southern pine #2 6-6 9-4 12-0 14-4 16-10 6-0 8-8 11-2 13-4 15-7
  Southern pine #3 4-11 7-3 9-2 10-10 12-11 4-6 6-8 8-6 10-1 12-0
  Spruce-pine-firc SS 6-8 10-6 13-5 16-5 19-1 6-8 9-10 12-5 15-3 17-8
  Spruce-pine-firc #1 6-1 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Spruce-pine-firc #2 6-1 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Spruce-pine-firc #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
  Douglas fir-larch SS 6-8 10- 13-0 15-10 18-4 6-6 9-6 12-0 14-8 17-0
  Douglas fir-larch #1 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
  Douglas fir-larch #2 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Douglas fir-larch #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
  Hem-fir SS 6-4 9-11 12-9 15-7 18-0 6-4 9-4 11-9 14-5 16-8
  Hem-fir #1 5-8 8-3 10-6 12-10 14-10 5-3 7-8 9-9 11-10 13-9
  Hem-fir #2 5-4 7-10 9-11 12-1 14-1 4-11 7-3 9-2 11-3 13-0
  Hem-fir #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
24 Southern pine SS 6-7 10-4 13-8 17-5 21-0 6-7 10-4 13-8 16-7 19-5
  Southern pine #1 6-5 9-7 12-0 14-4 17-1 6-0 8-10 11-2 13-3 15-9
  Southern pine #2 5-10 8-4 10-9 12-10 15-1 5-5 7-9 10-0 11-11 13-11
  Southern pine #3 4-4 6-5 8-3 9-9 11-7 4-1 6-0 7-7 9-0 10-8
  Spruce-pine-firc SS 6-2 9-6 12-0 14-8 17-1 6-0 8-10 11-2 13-7 15-9
  Spruce-pine-firc #1 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Spruce-pine-firc #2 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Spruce-pine-firc #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:
    HC
    = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR
    = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. Span exceeds 26 feet in length.
  3. North American Spruce-Pine-Fir species only.
TABLE R802.5.1(5)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=30 psf, ceiling attached to rafters, L/Δ = 240)
RAFTER SPACING
(inches)
SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6 2 × 8  2 × 10 2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 9-1 14-4 18-10 24-1 Note b 9-1 14-4 18-10 24-1 Note b
  Douglas fir-larch #1 8-9 13-9 18-2 22-9 Note b 8-9 13-2 16-8 20-4 23-7
  Douglas fir-larch #2 8-7 13-6 17-5 21-4 24-8 8-5 12-4 15-7 19-1 22-1
  Douglas fir-larch #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Hem-fir SS 8-7 13-6 17-10 22-9 Note b 8-7 13-6 17-10 22-9 Note b
  Hem-fir #1 8-5 13-3 17-5 22-2 25-9 8-5 12-10 16-3 19-10 23-0
  Hem-fir #2 8-0 12-7 16-7 21-0 24-4 8-0 12-2 15-4 18-9 21-9
  Hem-fir #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
12 Southern pine SS 8-11 14-1 18-6 23-8 Note b 8-11 14-1 18-6 23-8 Note b
  Southern pine #1 8-9 13-9 18-2 23-2 Note b 8-9 13-9 18-2 22-2 Note b
  Southern pine #2 8-7 13-6 17-10 22-3 Note b 8-7 12-11 16-8 19-11 23-4
  Southern pine #3 7-7 11-2 14-3 16-10 20-0 6-9 10-0 12-9 15-1 17-11
  Spruce-pine-firc SS 8-5 13-3 17-5 22-3 Note b 8-5 13-3 17-5 22-3 Note b
  Spruce-pine-firc #1 8-3 12-11 17-0 21-4 24-8 8-3 12-4 15-7 19-1 22-1
  Spruce-pine-firc #2 8-3 12-11 17-0 21-4 24-8 8-3 12-4 15-7 19-1 22-1
  Spruce-pine-firc #3 7-1 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Douglas fir-larch SS 8-3 13-0 17-2 21-10 Note b 8-3 13-0 17-2 21-3 24-8
  Douglas fir-larch #1 8-0 12-6 16-2 19-9 22-10 7-10 11-5 14-5 17-8 20-5
  Douglas fir-larch #2 7-10 11-11 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Douglas fir-larch #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
  Hem-fir SS 7-10 12-3 16-2 20-8 25-1 7-10 12-3 16-2 20-8 24-2
  Hem-fir #1 7-8 12-0 15-9 19-3 22-3 7-7 11-1 14-1 17-2 19-11
  Hem-fir #2 7-3 11-5 14-11 18-2 21-1 7-2 10-6 13-4 16-3 18-10
  Hem-fir #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
16 Southern pine SS 8-1 12-9 16-10 21-6 Note b 8-1 12-9 16-10 21-6 Note b
  Southern pine #1 8-0 12-6 16-6 21-1 25-7 8-0 12-6 16-2 19-2 22-10
  Southern pine #2 7-10 12-3 16-2 19-3 22-7 7-10 11-2 14-5 17-3 20-2
  Southern pine #3 6-7 9-8 12-4 14-7 17-4 5-10 8-8 11-0 13-0 15-6
  Spruce-pine-firc SS 7-8 12-0 15-10 20-2 24-7 7-8 12-0 15-10 19-9 22-10
  Spruce-pine-firc #1 7-6 11-9 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Spruce-pine-firc #2 7-6 11-9 15-1 18-5 21-5 7-3 10-8 13-6 16-6 19-2
  Spruce-pine-firc #3 6-2 9-0 11-5 13-11 16-2 5-6 8-1 10-3 12-6 14-6
  Douglas fir-larch SS 7-9 12-3 16-1 20-7 25-0 7-9 12-3 15-10 19-5 22-6
  Douglas fir-larch #1 7-6 11-8 14-9 18-0 20-11 7-1 10-5 13-2 16-1 18-8
  Douglas fir-larch #2 7-4 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
  Douglas fir-larch #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
  Hem-fir SS 7-4 11-7 15-3 19-5 23-7 7-4 11-7 15-3 19-1 22-1
  Hem-fir #1 7-2 11-4 14-4 17-7 20-4 6-11 10-2 12-10 15-8 18-2
  Hem-fir #2 6-10 10-9 13-7 16-7 19-3 6-7 9-7 12-2 14-10 17-3
  Hem-fir #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
19.2 Southern pine SS 7-8 12-0 15-10 20-2 24-7 7-8 12-0 15-10 20-2 24-7
  Southern pine #1 7-6 11-9 15-6 19-7 23-4 7-6 11-9 14-9 17-6 20-11
  Southern pine #2 7-4 11-5 14-9 17-7 20-7 7-1 10-2 13-2 15-9 18-5
  Southern pine #3 6-0 8-10 11-3 13-4 15-10 5-4 7-11 10-1 11-11 14-2
  Spruce-pine-firc SS 7-2 11-4 14-11 19-0 23-1 7-2 11-4 14-9 18-0 20-11
  Spruce-pine-firc #1 7-0 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
  Spruce-pine-firc #2 7-0 10-11 13-9 16-10 19-6 6-8 9-9 12-4 15-1 17-6
  Spruce-pine-firc #3 5-7 8-3 10-5 12-9 14-9 5-0 7-4 9-4 11-5 13-2
  Douglas fir-larch SS 7-3 11-4 15-0 19-1 22-6 7-3 11-3 14-2 17-4 20-1
  Douglas fir-larch #1 7-0 10-5 13-2 16-1 18-8 6-4 9-4 11-9 14-5 16-8
  Douglas fir-larch #2 6-8 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
  Hem-fir SS 6-10 10-9 14-2 18-0 21-11 6-10 10-9 13-11 17-0 19-9
  Hem-fir #1 6-8 10-2 12-10 15-8 18-2 6-2 9-1 11-6 14-0 16-3
  Hem-fir #2 6-4 9-7 12-2 14-10 17-3 5-10 8-7 10-10 13-3 15-5
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
24 Southern pine SS 7-1 11-2 14-8 18-9 22-10 7-1 11-2 14-8 18-9 22-10
  Southern pine #1 7-0 10-11 14-5 17-6 20-11 7-0 10-6 13-2 15-8 18-8
  Southern pine #2 6-10 10-2 13-2 15-9 18-5 6-4 9-2 11-9 14-1 16-6
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 4-9 7-1 9-0 10-8 12-8
  Spruce-pine-firc SS 6-8 10-6 13-10 17-8 20-11 6-8 10-5 13-2 16-1 18-8
  Spruce-pine-firc #1 6-6 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Spruce-pine-firc #2 6-6 9-9 12-4 15-1 17-6 5-11 8-8 11-0 13-6 15-7
  Spruce-pine-firc #3 5-0 7-4 9-4 11-5 13-2 4-6 6-7 8-4 10-2 11-10
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter pans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:
    HC = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR= Height of roof ridge measured vertically above the top of the rafter support walls.
  2. Span exceeds 26 feet in length
  3. North American Spruce-Pine-Fir species only.
TABLE R802.5.1(6)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=50 psf or less, ceiling attached to rafters, L/Δ = 240)
RAFTER SPACING
(inches)
SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4  2 × 6 2 × 8 2 × 10 2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet-inches) (feet-inches) (feet-inches) (feet-inches)
(feet- inches)
(feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches)
  Douglas fir-larch SS 7-8 12-1 15-11 20-3 24-8 7-8 12-1 15-11 20-3 24-0
  Douglas fir-larch #1 7-5 11-7 15-3 18-7 21-7 7-5 11-2 14-1 17-3 20-0
  Douglas fir-larch  #2 7-3 11-3 14-3 17-5 20-2 7-1 10-5 13-2 16-1 18-8
  Douglas fir-larch  #3 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
  Hem-fir SS 7-3 11-5 15-0 19-2 23-4 7-3 11-5 15-0 19-2 23-4
  Hem-fir #1 7-1 11-2 14-8 18-1 21-0 7-1 10-10 13-9 16-9 19-5
  Hem-fir #2 6-9 10-8 14-0 17-2 19-11 6-9 10-3 13-0 15-10 18-5
  Hem-fir #3 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
12 Southern pine SS 7-6 11-10 15-7 19-11 24-3 7-6 11-10 15-7 19-11 24-3
  Southern pine #1 7-5 11-7 15-4 19-7 23-9 7-5 11-7 15-4 18-9 22-4
  Southern pine #2 7-3 11-5 15-0 18-2 21-3 7-3 10-11 14-1 16-10 19-9
  Southern pine #3 6-2 9-2 11-8 13-9 16-4 5-9 8-5 10-9 12-9 15-2
  Spruce-pine-firb SS 7-1 11-2 14-8 18-9 22-10 7-1 11-2 14-8 18-9 22-4
  Spruce-pine-firb #1 6-11 10-11 14-3 17-5 20-2 6-11 10-5 13-2 16-1 18-8
  Spruce-pine-firb #2 6-11 10-11 14-3 17-5 20-2 6-11 10-5 13-2 16-1 18-8
  Spruce-pine-firb #3 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
  Douglas fir-larch SS 7-0 11-0 14-5 18-5 22-5 7-0 11-0 14-5 17-11 20-10
  Douglas fir-larch #1 6-9 10-5 13-2 16-1 18-8 6-7 9-8 12-2 14-11 17-3
  Douglas fir-larch #2 6-7 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
  Hem-fir SS 6-7 10-4 13-8 17-5 21-2 6-7 10-4 13-8 17-5 20-5
  Hem-fir #1 6-5 10-2 12-10 15-8 18-2 6-5 9-5 11-11 14-6 16-10
  Hem-fir #2 6-2 9-7 12-2 14-10 17-3 6-1 8-11 11-3 13-9 15-11
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
16 Southern pine SS 6-10 10-9 14-2 18-1 22-0 6-10 10-9 14-2 18-1 22-0
  Southern pine #1 6-9 10-7 13-11 17-6 20-11 6-9 10-7 13-8 16-2 19-4
  Southern pine #2 6-7 10-2 13-2 15-9 18-5 6-7 9-5 12-2 14-7 17-1
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 4-11 7-4 9-4 11-0 13-1
  Spruce-pine-firb SS 6-5 10-2 13-4 17-0 20-9 6-5 10-2 13-4 16-8 19-4
  Spruce-pine-firb #1 6-4 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Spruce-pine-firb #2 6-4 9-9 12-4 15-1 17-6 6-2 9-0 11-5 13-11 16-2
  Spruce-pine-firb #3 5-0 7-4 9-4 11-5 13-2 4-8 6-10 8-8 10-6 12-3
  Douglas fir-larch SS 6-7 10-4 13-7 17-4 20-6 6-7 10-4 13-5 16-5 19-0
  Douglas fir-larch #1 6-4 9-6 12-0 14-8 17-1 6-0 8-10 11-2 13-7 15-9
  Douglas fir-larch #2 6-1 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Douglas fir-larch #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
  Hem-fir SS 6-2 9-9 12-10 16-5 19-11 6-2 9-9 12-10 16-1 18-8
  Hem-fir #1 6-1 9-3 11-9 14-4 16-7 5-10 8-7 10-10 13-3 15-5
  Hem-fir #2 5-9 8-9 11-1 13-7 15-9 5-7 8-1 10-3 12-7 14-7
  Hem-fir #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
19.2 Southern pine SS 6-5 10-2 13-4 17-0 20-9 6-5 10-2 13-4 17-0 20-9
  Southern pine #1 6-4 9-11 13-1 16-0 19-1 6-4 9-11 12-5 14-10 17-8
  Southern pine #2 6-2 9-4 12-0 14-4 16-10 6-0 8-8 11-2 13-4 15-7
  Southern pine #3 4-11 7-3 9-2 10-10 12-11 4-6 6-8 8-6 10-1 12-0
  Spruce-pine-firb SS 6-1 9-6 12-7 16-0 19-1 6-1 9-6 12-5 15-3 17-8
  Spruce-pine-firb #1 5-11 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Spruce-pine-firb #2 5-11 8-11 11-3 13-9 15-11 5-7 8-3 10-5 12-9 14-9
  Spruce-pine-firb #3 4-7 6-9 8-6 10-5 12-1 4-3 6-3 7-11 9-7 11-2
  Douglas fir-larch SS 6-1 9-7 12-7 15-10 18-4 6-1 9-6 12-0 14-8 17-0
  Douglas fir-larch #1 5-10 8-6 10-9 13-2 15-3 5-5 7-10 10-0 12-2 14-1
  Douglas fir-larch #2 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Douglas fir-larch #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
  Hem-fir SS 5-9 9-1 11-11 15-2 18-0 5-9 9-1 11-9 14-5 15-11
  Hem-fir #1 5-8 8-3 10-6 12-10 14-10 5-3 7-8 9-9 11-10 13-9
  Hem-fir #2 5-4 7-10 9-11 12-1 14-1 4-11 7-3 9-2 11-3 13-0
  Hem-fir #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
24 Southern pine SS 6-0 9-5 12-5 15-10 19-3 6-0 9-5 12-5 15-10 19-3
  Southern pine #1 5-10 9-3 12-0 14-4 17-1 5-10 8-10 11-2 13-3 15-9
  Southern pine #2 5-9 8-4 10-9 12-10 15-1 5-5 7-9 10-0 11-11 13-11
  Southern pine #3 4-4 6-5 8-3 9-9 11-7 4-1 6-0 7-7 9-0 10-8
  Spruce-pine-firb SS 5-8 8-10 11-8 14-8 17-1 5-8 8-10 11-2 13-7 15-9
  Spruce-pine-firb #1 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Spruce-pine-firb #2 5-5 7-11 10-1 12-4 14-3 5-0 7-4 9-4 11-5 13-2
  Spruce-pine-firb #3 4-1 6-0 7-7 9-4 10-9 3-10 5-7 7-1 8-7 10-0
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:
    HC
    = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR
    = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. North American Spruce-Pine-Fir species only.
TABLE R802.5.1 (7)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=70 psf or less, ceiling not attached to rafters, L/Δ = 180)
RAFTER SPACING(inches) SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6 2 × 8 2 × 10 2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum Rafter Spansa
(feet- inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches) (feet-inches)
  Douglas fir-larch SS 7-7 11-10 15-8 19-5 22-6 7-7 11-10 15-0 18-3 21-2
  Douglas fir-larch #1 7-1 10-5 13-2 16-1 18-8 6-8 9-10 12-5 15-2 17-7
  Douglas fir-larch #2 6-8 9-9 12-4 15-1 17-6 6-3 9-2 11-8 14-2 16-6
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Hem-fir SS 7-2 11-3 14-9 18-10 22-1 7-2 11-3 14-8 18-0 20-10
  Hem-fir #1 6-11 10-2 12-10 15-8 18-2 6-6 9-7 12-1 14-10 17-2
  Hem-fir #2 6-7 9-7 12-2 14-10 17-3 6-2 9-1 11-5 14-0 16-3
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
12 Southern pine SS 7-5 11-8 15-4 19-7 23-10 7-5 11-8 15-4 19-7 23-10
  Southern pine #1 7-3 11-5 14-9 17-6 20-11 7-3 11-1 13-11 16-6 19-8
  Southern pine #2 7-1 10-2 13-2 15-9 18-5 6-8 9-7 12-5 14-10 17-5
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 5-1 7-5 9-6 11-3 13-4
  Spruce-pine-firb SS 7-0 11-0 14-6 18-0 20-11 7-0 11-0 13-11 17-0 19-8
  Spruce-pine-firb #1 6-8 9-9 12-4 15-1 17-6 6-3 9-2 11-8 14-2 16-6
  Spruce-pine-firb #2 6-8 9-9 12-4 15-1 17-6 6-3 9-2 11-8 14-2 16-6
  Spruce-pine-firb #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Douglas fir-larch SS 6-10 10-9 13-9 16-10 19-6 6-10 10-3 13-0 15-10 18-4
  Douglas fir-larch #1 6-2 9-0 11-5 13-11 16-2 5-10 8-6 10-9 13-2 15-3
  Douglas fir-larch #2 5-9 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Douglas fir-larch #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
  Hem-fir SS 6-6 10-2 13-5 16-6 19-2 6-6 10-1 12-9 15-7 18-0
  Hem-fir #1 6-0 8-9 11-2 13-7 15-9 5-8 8-3 10-6 12-10 14-10
  Hem-fir #2 5-8 8-4 10-6 12-10 14-11 5-4 7-10 9-11 12-1 14-1
  Hem-fir #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
16 Southern pine SS 6-9 10-7 14-0 17-10 21-8 6-9 10-7 14-0 17-10 21-0
  Southern pine #1 6-7 10-2 12-9 15-2 18-1 6-5 9-7 12-0 14-4 17-1
  Southern pine #2 6-2 8-10 11-5 13-7 16-0 5-10 8-4 10-9 12-10 15-1
  Southern pine #3 4-8 6-10 8-9 10-4 12-3 4-4 6-5 8-3 9-9 11-7
  Spruce-pine-firb SS 6-4 10-0 12-9 15-7 18-1 6-4 9-6 12-0 14-8 17-1
  Spruce-pine-firb #1 5-9 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Spruce-pine-firb #2 5-9 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Spruce-pine-firb #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
  Douglas fir-larch SS 6-5 9-11 12-7 15-4 17-9 6-5 9-4 11-10 14-5 16-9
  Douglas fir-larch #1 5-7 8-3 10-5 12-9 14-9 5-4 7-9 9-10 12-0 13-11
  Douglas fir-larch #2 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Douglas fir-larch #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
  Hem-fir SS 6-1 9-7 12-4 15-1 17-4 6-1 9-2 11-8 14-2 15-5
  Hem-fir #1 5-6 8-0 10-2 12-5 14-5 5-2 7-7 9-7 11-8 13-7
  Hem-fir #2 5-2 7-7 9-7 11-9 13-7 4-11 7-2 9-1 11-1 12-10
  Hem-fir #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
19.2 Southern pine SS 6-4 10-0 13-2 16-9 20-4 6-4 10-0 13-2 16-5 19-2
  Southern pine #1 6-3 9-3 11-8 13-10 16-6 5-11 8-9 11-0 13-1 15-7
  Southern pine #2 5-7 8-1 10-5 12-5 14-7 5-4 7-7 9-10 11-9 13-9
  Southern pine #3 4-3 6-3 8-0 9-5 11-2 4-0 5-11 7-6 8-10 10-7
  Spruce-pine-firb SS 6-0 9-2 11-8 14-3 16-6 5-11 8-8 11-0 13-5 15-7
  Spruce-pine-firb #1 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Spruce-pine-firb #2 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Spruce-pine-firb #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
  Douglas fir-larch SS 6-0 8-10 11-3 13-9 15-11 5-9 8-4 10-7 12-11 15-0
  Douglas fir-larch #1 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Douglas fir-larch #2 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Douglas fir-larch #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
  Hem-fir SS 5-8 8-8 11-0 13-6 13-11 5-7 8-3 10-5 12-4 12-4
  Hem-fir #1 4-11 7-2 9-1 11-1 12-10 4-7 6-9 8-7 10-6 12-2
  Hem-fir #2 4-8 6-9 8-7 10-6 12-2 4-4 6-5 8-1 9-11 11-6
  Hem-fir #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
24 Southern pine SS 5-11 9-3 12-2 15-7 18-2 5-11 9-3 12-2 14-8 17-2
  Southern pine #1 5-7 8-3 10-5 12-5 14-9 5-3 7-10 9-10 11-8 13-11
  Southern pine #2 5-0 7-3 9-4 11-1 13-0 4-9 6-10 8-9 10-6 12-4
  Southern pine #3 3-9 5-7 7-1 8-5 10-0 3-7 5-3 6-9 7-11 9-5
  Spruce-pine-firb SS 5-6 8-3 10-5 12-9 14-9 5-4 7-9 9-10 12-0 12-11
  Spruce-pine-firb #1 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Spruce-pine-firb #2 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Spruce-pine-firb #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:

    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:
    1. HC = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    2. HR = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. North American Spruce-Pine-Fir species only.
TABLE R802.5.1 (8)
RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=70 psf or less, ceiling attached to rafters, L/Δ = 240)
RAFTER SPACING
(inches)
SPECIES AND GRADE DEAD LOAD = 10 psf DEAD LOAD = 20 psf
2 × 4 2 × 6 2 × 8 2 × 10 2 × 12 2 × 4 2 × 6 2 × 8 2 × 10 2 × 12
Maximum rafter spansa
(feet - inches) (feet - inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches) (feet -inches)
  Douglas fir-larch SS 6-10 10-9 14-3 18-2 22-1 6-10 10-9 14-3 18-2 21-2
  Douglas fir-larch #1 6-7 10-5 13-2 16-1 18-8 6-7 9-10 12-5 15-2 17-7
  Douglas fir-larch #2 6-6 9-9 12-4 15-1 17-6 6-3 9-2 11-8 14-2 16-6
  Douglas fir-larch #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Hem-fir SS 6-6 10-2 13-5 17-2 20-10 6-6 10-2 13-5 17-2 20-10
  Hem-fir #1 6-4 10-0 12-10 15-8 18-2 6-4 9-7 12-1 14-10 17-2
  Hem-fir #2 6-1 9-6 12-2 14-10 17-3 6-1 9-1 11-5 14-0 16-3
  Hem-fir #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
12 Southern pine SS 6-9 10-7 14-0 17-10 21-8 6-9 10-7 14-0 17-10 21-8
  Southern pine #1 6-7 10-5 13-8 17-6 20-11 6-7 10-5 13-8 16-6 19-8
  Southern pine #2 6-6 10-2 13-2 15-9 18-5 6-6 9-7 12-5 14-10 17-5
  Southern pine #3 5-4 7-11 10-1 11-11 14-2 5-1 7-5 9-6 11-3 13-4
  Spruce-pine-firb SS 6-4 10-0 13-2 16-9 20-5 6-4 10-0 13-2 16-9 19-8
  Spruce-pine-firb #1 6-2 9-9 12-4 15-1 17-6 6-2 9-2 11-8 14-2 16-6
  Spruce-pine-firb #2 6-2 9-9 12-4 15-1 17-6 6-2 9-2 11-8 14-2 16-6
  Spruce-pine-firb #3 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Douglas fir-larch SS 6-3 9-10 12-11 16-6 19-6 6-3 9-10 12-11 15-10 18-4
  Douglas fir-larch #1 6-0 9-0 11-5 13-11 16-2 5-10 8-6 10-9 13-2 15-3
  Douglas fir-larch #2 5-9 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Douglas fir-larch #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
  Hem-fir SS 5-11 9-3 12-2 15-7 18-11 5-11 9-3 12-2 15-7 18-0
  Hem-fir #1 5-9 8-9 11-2 13-7 15-9 5-8 8-3 10-6 12-10 14-10
  Hem-fir #2 5-6 8-4 10-6 12-10 14-11 5-4 7-10 9-11 12-1 14-1
  Hem-fir #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
16 Southern pine SS 6-1 9-7 12-8 16-2 19-8 6-1 9-7 12-8 16-2 19-8
  Southern pine #1 6-0 9-5 12-5 15-2 18-1 6-0 9-5 12-0 14-4 17-1
  Southern pine #2 5-11 8-10 11-5 13-7 16-0 5-10 8-4 10-9 12-10 15-1
  Southern pine #3 4-8 6-10 8-9 10-4 12-3 4-4 6-5 8-3 9-9 11-7
  Spruce-pine-firb SS 5-9 9-1 11-11 15-3 18-1 5-9 9-1 11-11 14-8 17-1
  Spruce-pine-firb #1 5-8 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Spruce-pine-firb #2 5-8 8-5 10-8 13-1 15-2 5-5 7-11 10-1 12-4 14-3
  Spruce-pine-firb #3 4-4 6-4 8-1 9-10 11-5 4-1 6-0 7-7 9-4 10-9
  Douglas fir-larch SS 5-10 9-3 12-2 15-4 17-9 5-10 9-3 11-10 14-5 16-9
  Douglas fir-larch #1 5-7 8-3 10-5 12-9 14-9 5-4 7-9 9-10 12-0 13-11
  Douglas fir-larch #2 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Douglas fir-larch #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
  Hem-fir SS 5-6 8-8 11-6 14-8 17-4 5-6 8-8 11-6 14-2 15-5
  Hem-fir #1 5-5 8-0 10-2 12-5 14-5 5-2 7-7 9-7 11-8 13-7
  Hem-fir #2 5-2 7-7 9-7 11-9 13-7 4-11 7-2 9-1 11-1 12-10
  Hem-fir #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
19.2 Southern pine SS 5-9 9-1 11-11 15-3 18-6 5-9 9-1 11-11 15-3 18-6
  Southern pine #1 5-8 8-11 11-8 13-10 16-6 5-8 8-9 11-0 13-1 15-7
  Southern pine #2 5-6 8-1 10-5 12-5 14-7 5-4 7-7 9-10 11-9 13-9
  Southern pine #3 4-3 6-3 8-0 9-5 11-2 4-0 5-11 7-6 8-10 10-7
  Spruce-pine-firb SS 5-5 8-6 11-3 14-3 16-6 5-5 8-6 11-0 13-5 15-7
  Spruce-pine-firb #1 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Spruce-pine-firb #2 5-3 7-8 9-9 11-11 13-10 5-0 7-3 9-2 11-3 13-0
  Spruce-pine-firb #3 4-0 5-10 7-4 9-0 10-5 3-9 5-6 6-11 8-6 9-10
  Douglas fir-larch SS 5-5 8-7 11-3 13-9 15-11 5-5 8-4 10-7 12-11 15-0
  Douglas fir-larch #1 5-0 7-4 9-4 11-5 13-2 4-9 6-11 8-9 10-9 12-5
  Douglas fir-larch #2 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Douglas fir-larch #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
  Hem-fir SS 5-2 8-1 10-8 13-6 13-11 5-2 8-1 10-5 12-4 12-4
  Hem-fir #1 4-11 7-2 9-1 11-1 12-10 4-7 6-9 8-7 10-6 12-2
  Hem-fir #2 4-8 6-9 8-7 10-6 12-2 4-4 6-5 8-1 9-11 11-6
  Hem-fir #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
24 Southern pine SS 5-4 8-5 11-1 14-2 17-2 5-4 8-5 11-1 14-2 17-2
  Southern pine #1 5-3 8-3 10-5 12-5 14-9 5-3 7-10 9-10 11-8 13-11
  Southern pine #2 5-0 7-3 9-4 11-1 13-0 4-9 6-10 8-9 10-6 12-4
  Southern pine #3 3-9 5-7 7-1 8-5 10-0 3-7 5-3 6-9 7-11 9-5
  Spruce-pine-firb SS 5-0 7-11 10-5 12-9 14-9 5-0 7-9 9-10 12-0 12-11
  Spruce-pine-firb #1 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Spruce-pine-firb #2 4-8 6-11 8-9 10-8 12-4 4-5 6-6 8-3 10-0 11-8
  Spruce-pine-firb #3 3-7 5-2 6-7 8-1 9-4 3-4 4-11 6-3 7-7 8-10
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below:
    HC/HR Rafter Span Adjustment Factor
    1/3 0.67
    1/4 0.76
    1/5 0.83
    1/6 0.90
    1/7.5 or less 1.00
    where:

    HC
    = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
    HR
    = Height of roof ridge measured vertically above the top of the rafter support walls.
  2. North American Spruce-Pine-Fir species only.
TABLE R802.5.1(9)
RAFTER/CEILING JOIST HEEL JOINT CONNECTIONSa, b, c, d, e, f, g
RAFTER SLOPE RAFTER SPACING (inches) GROUND SNOW LOAD (psf)
30 50  70
Roof span (feet)
12 20 28 36 12 20 28 36 12 20 28 36
Required number of 16d common nailsa,b per heel joint splicesc,d,e,f
  12 4 6 8 11 5 8 12 15 6 11 15 20
3:12 16 5 8 11 14 6 11 15 20 8 14 20 26
  24 7 11 16 21 9 16 23 30 12 21 30 39
  12 3 5 6 8 4 6 9 11 5 8 12 15
4:12 16 4 6 8 11 5 8 12 15 6 11 15 20
  24 5 9 12 16 7 12 17 22 9 16 23 29
  12 3 4 5 7 3 5 7 9 4 7 9 12
5:12 16 3 5 7 9 4 7 9 12 5 9 12 16
  24 4 7 10 13 6 10 14 18 7 13 18 23
  12 3 3 4 5 3 4 5 7 3 5 7 9
7:12 16 3 4 5 6 3 5 7 9 4 6 9 11
  24 3 5 7 9 4 7 10 13 5 9 13 17
  12 3 3 3 4 3 3 4 5 3 4 5 7
9:12 16 3 3 4 5 3 4 5 7 3 5 7 9
  24 3 4 6 7 3 6 8 10 4 7 10 13
  12 3 3 3 3 3 3 3 4 3 3 4 5
12:12 16 3 3 3 4 3 3 4 5 3 4 5 7
  24 3 3 4 6 3 4 6 8 3 6 8 10

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa.
  1. 40d box nails shall be permitted to be substituted for 16d common nails.
  2. Nailing requirements shall be permitted to be reduced 25 percent if nails are clinched.
  3. Heel joint connections are not required when the ridge is supported by a load-bearing wall, header or ridge beam.
  4. When intermediate support of the rafter is provided by vertical struts or purlins to a loadbearing wall, the tabulated heel joint connection requirements shall be permitted to be reduced proportionally to the reduction in span.
  5. Equivalent nailing patterns are required for ceiling joist to ceiling joist lap splices.
  6. When rafter ties are substituted for ceiling joists, the heel joint connection requirement shall be taken as the tabulated heel joint connection requirement for two-thirds of the actual rafter-slope.
  7. Tabulated heel joint connection requirements assume that ceiling joists or rafter ties are located at the bottom of the attic space. When ceiling joists or rafter ties are located higher in the attic, heel joint connection requirements shall be increased by the following factors:


HC/HR Rafter Span Adjustment Factor
1/3 0.67
1/4 0.76
1/5 0.83
1/6 0.90
1/7.5 or less 1.00
where:
HC
= Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls.
HR
= Height of roof ridge measured vertically above the top of the rafter support walls.



FIGURE R802.5.1
BRACED RAFTER CONSTRUCTION
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.018 rad.
NOTE: Where ceiling joints run perpendicular to the rafters, rafter ties shall be nailed to the rafter near the plate line and spaced not more than 4 feet on center.=
The ends of each rafter or ceiling joist shall have not less than 11/2 inches (38 mm) of bearing on wood or metal and not less than 3 inches (76 mm) on masonry or concrete.
If the finished ceiling material is installed on the ceiling prior to the attachment of the ceiling to the walls, such as in construction at a factory, a compression strip of the same thickness as the finish ceiling material shall be installed directly above the top plate of bearing walls if the compressive strength of the finish ceiling material is less than the loads it will be required to withstand. The compression strip shall cover the entire length of such top plate and shall be at least one- half the width of the top plate. It shall be of material capable of transmitting the loads transferred through it.
Structural roof members shall not be cut, bored or notched in excess of the limitations specified in this section.
Notches in solid lumber joists, rafters and beams shall not exceed one-sixth of the depth of the member, shall not be longer than one-third of the depth of the member and shall not be located in the middle one-third of the span. Notches at the ends of the member shall not exceed one-fourth the depth of the member. The tension side of members 4 inches (102 mm) or greater in nominal thickness shall not be notched except at the ends of the members. The diameter of the holes bored or cut into members shall not exceed one-third the depth of the member. Holes shall not be closer than 2 inches (51 mm) to the top or bottom of the member, or to any other hole located in the member. Where the member is also notched, the hole shall not be closer than 2 inches (51 mm) to the notch.
Exception: Notches on cantilevered portions of rafters are permitted provided the dimension of the remaining portion of the rafter is not less than 4-inch nominal (102 mm) and the length of the cantilever does not exceed 24 inches (610 mm).
Cuts, notches and holes bored in trusses, structural composite lumber, structural glue-laminated members or I-joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional.
Rafters and ceiling joists having a depth-to-thickness ratio exceeding 5 to 1 based on nominal dimensions shall be provided with lateral support at points of bearing to prevent rotation.
Rafters and ceiling joists having a depth-to-thickness ratio exceeding 6 to 1 based on nominal dimensions shall be supported laterally by solid blocking, diagonal bridging (wood or metal) or a continuous 1-inch by 3-inch (25 mm by 76 mm) wood strip nailed across the rafters or ceiling joists at intervals not exceeding 8 feet (2438 mm).
Openings in roof and ceiling framing shall be framed with header and trimmer joists. When the header joist span does not exceed 4 feet (1219 mm), the header joist may be a single member the sa