The provisions of this chapter shall govern the minimum mechanical and electrical facilities and equipment to be provided.
The owner of the structure shall provide and maintain mechanical and electrical facilities and equipment in compliance with these requirements. A person shall not occupy as owner-occupant or permit another person to occupy any premises which does not comply with the requirements of this chapter.
Heating facilities shall be provided in structures as required by this section.
Dwellings shall be provided with heating facilities capable of maintaining a room temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms based on the winter design dry-bulb temperature for the locality indicated in the Energy Conservation Construction Code of New York State. Cooking appliances shall not be used to provide space heating to meet the requirements of this section.

Exception:
Owner-occupied one-family dwellings subject to the approval of the code enforcement official.
Every owner and operator of any building who rents, leases or lets one or more dwelling unit, rooming unit, dormitory or guestroom on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat during the period from September 15th to May 31st to maintain a temperature of not less than 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms.

Exception:
When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required, provided that the heating system is operating at its full design capacity. The winter design dry-bulb temperature for the locality shall be as indicated in the Energy Conservation Construction Code of New York State.
Indoor occupiable work spaces shall be supplied with heat during the period from September 15th to May 31st to maintain a temperature of not less than 65°F (18°C) during the period the spaces are occupied.

Exceptions:


1. Processing, storage and operation areas that require cooling or special temperature conditions.
2. Areas in which persons are primarily engaged in vigorous physical activities.
Indoor public spaces shall be supplied with heat during the period from September 15th to May 31st to maintain a temperature of not less than 68°F (20°C) in accordance with the Building Code of New York State during the period the spaces are occupied.
The required room temperatures shall be measured 3 feet (914 mm) above the floor near the center of the room and 2 feet (610 mm) inward from the center of each exterior wall.
All mechanical appliances, fireplaces, solid fuel-burning appliances, cooking appliances and water heating appliances shall be properly installed and maintained in a safe working condition, and shall be capable of performing the intended function.
All fuel-burning equipment and appliances shall be connected to an approved chimney or vent.

Exception:
Fuel-burning equipment and appliances which are labeled for unvented operation.
All required clearances to combustible materials shall be maintained.
All safety controls for fuel-burning equipment shall be maintained in effective operation.
A supply of air for complete combustion of the fuel and for ventilation of the space containing the fuel-burning equipment shall be provided for the fuel-burning equipment.
Devices intended to reduce fuel consumption by attachment to a fuel-burning appliance, to the fuel supply line thereto, or to the vent outlet or vent piping therefrom, shall not be installed unless labeled for such purpose and the installation is specifically approved.
Every occupied building shall be provided with an electrical system in compliance with the requirements of this section and Section 605.

Exception:
Owner-occupied one-family dwellings dwellings not supplied with electrical power, subject to the approval of the code enforcement official.
The size and usage of appliances and equipment shall serve as a basis for determining the need for additional facilities in accordance with Chapter 27 of the Building Code of New York State or Part VIII of the Residential Code of New York State, as applicable.
Where it is found that the electrical system in a structure constitutes a hazard to the occupants or the structure by reason of inadequate service, improper fusing, insufficient receptacle and lighting outlets, improper wiring or installation, deterioration or damage, or for similar reasons, the defects shall be corrected to eliminate the hazard.
All electrical equipment, wiring and appliances shall be properly installed and maintained in a safe and approved manner.
Every habitable space in a dwelling shall contain at least two separate and remote receptacle outlets. Every laundry area shall contain at least one grounded-type receptacle or a receptacle with a ground fault circuit interrupter. Every bathroom shall contain at least one receptacle. Any new bathroom receptacle outlet shall have ground fault circuit interrupter protection.
Every public hall, interior stairway, toilet room, kitchen, bathroom, laundry room, boiler room and furnace room shall contain at least one electric lighting fixture.
Elevators, dumbwaiters and escalators shall be maintained in compliance with ASME A17.1. The most current certificate of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter, or the certificate shall be available for public inspection in the office of the building operator. The inspection and tests shall be performed at not less than the periodical intervals listed in ASME A17.1, Appendix N, except where otherwise specified by the authority having jurisdiction.
Elevators, dumbwaiters, escalators and platform lifts shall be maintained and meet schedule of inspections in accord with Building Code of New York State, Section 3001, and Appendix N, Table-1 of ASME A17.1 and ASME A18.1.
In buildings equipped with passenger elevators, at least one elevator shall be maintained in operation at all times when the building is occupied.

Exception:
Buildings equipped with only one elevator shall be permitted to have the elevator temporarily out of service for testing or servicing.
Duct systems shall be maintained free of obstructions and shall be capable of performing the required function.
The owner or operator of each assembly space shall have the assistive listening system and all components thereof inspected annually and shall thereupon certify to the local authority having jurisdiction that each such system continues to comply with the Building Code of New York State, Appendix L, including the minimum number of required receivers/transducers.
Resources
Help us
keep law free