[NY] TABLE D101

DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN NEW YORK STATE

STATE STATIONb HEATING
DEGREE DAYS
(yearly total)
DESIGN TEMPERATURES DEGREES NORTH
LATITUDEc
Winter Summer
971/2% Dry bulb 21/2% Wet bulb 21/2%
NY Albany 6,875 -1 88 74 42°50'
Albanyd 6,201 1 88 74 42°50'
Binghamton 7,286 1 83 72 42°10'
Buffalo 7,062 6 85 73 43°00'
NY (Central Park)d 4,871 15 89 75 40°50'
NY (Kennedy) 5,219 15 87 75 40°40'
NY(LaGuardia) 4,811 15 89 75 40°50'
Rochester 6,748 5 88 73 43°10'
Schenectadyd 6,650 1 87 74 42°50'
Syracuse 6,756 2 87 73 43°10'
  1. All data were extracted from the 1985 ASHRAE Handbook, Fundamentals Volume.
  2. Design data developed from airport temperature observations unless noted.
  3. Latitude is given to the nearest 10 minutes.
  4. Design data developed from office locations within an urban area, not from airport temperature observations.