Heads up: There are no amended sections in this chapter.
This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in accordance with the type of occupancy, and shall provide for the minimum number of fixtures for various types of occupancies.
Water closets having a concealed trap seal or an unventilated space or having walls that are not thoroughly washed at each discharge in accordance with ASME A112.19.2M shall be prohibited. Any water closet that permits siphonage of the contents of the bowl back into the tank shall be prohibited. Trough urinals shall be prohibited.
The maximum water flow rates and flush volume for plumbing fixtures and fixture fittings shall comply with Section 604.4.
Plumbing fixtures shall be constructed of approved materials, with smooth, impervious surfaces, free from defects and concealed fouling surfaces, and shall conform to standards cited in this code. All porcelain enameled surfaces on plumbing fixtures shall be acid resistant.
Materials for specialty fixtures not otherwise covered in this code shall be of stainless steel, soapstone, chemical stoneware or plastic, or shall be lined with lead, copper-base alloy, nickel-copper alloy, corrosion-resistant steel or other material especially suited to the application for which the fixture is intended.
Sheet copper for general applications shall conform to ASTM B 152 and shall not weigh less than 12 ounces per square foot (3.7 kg/m2).
Sheet lead for pans shall not weigh less than 4 pounds per square foot (19.5 kg/m2) coated with an asphalt paint or other approved coating.
Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the Building Code of New York State. Occupancy classification shall be determined in accordance with the Building Code of New York State

TABLE 403.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.2 and 403.3)
NO. CLASSIFICATION OCCUPANCY DESCRIPTION WATER CLOSETS
(URINALS SEE SECTION 419.2)
LAVATORIES BATHTUBS/
SHOWERS
DRINKING FOUNTAIN
(SEE SECTION 410.1)
OTHERf
MALE FEMALE MALE FEMALE
1 Assembly (see Sections 403.2, 403.4 and 403.4.1)


A-1d Theaters and other buildings for the performing arts and motion pictures 1 per 125 1 per 65 1 per 200 1 per 200 1 per 500 1 service sink
A-2d Nightclubs, bars, taverns, dance halls and buildings for similar purposes 1 per 40 1 per 40 1 per 75 1 per 75 1 per 500 1 service sink
Restaurants, banquet halls and food courts 1 per 75 1 per 75 1 per 200 1 per 200  — 1 per 500 1 service sink
A-3d Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiums 1 per 125 1 per 65 1 per 200 1 per 200 1 per 500 1 service sink
Passenger terminals and transportation facilities 1 per 500 1 per 500 1 per 750 1 per 750  — 1 per 1,000 1 service sink
Places of worship and other religious
servicese.
1 per 150 1 per 75 1 per 200 1 per 200 1 per 1,000 1 service sink
A-4 Coliseums, arenas, skating rinks, pools
and tennis courts for indoor sporting events and activities
1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500 1 per 40 for the first 1,500 and 1 per 60 for the remainder exceeding 1,500 1 per 200 1 per 150 1 per 1,000 1 service sink
A-5 Stadiums, amusement parks, bleachers and grandstands for
outdoor sporting events and activities
1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500 1 per 40 for the first 1,500 and 1 per 60 for the remainder exceeding 1,500 1 per 200 1 per 150 1 per 1,000 1 service sink
2 Business (see Sections 403.2, 403.4 and 403.4.1) B Buildings for the transaction of
business, professionalservices, other services
involving merchandise, office buildings, banks, light industrial and similar uses
1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50 1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50 1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80 1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80 1 per 100 1 service sink
3 Educational E Educational facilities 1 per 50 1 per 50 1 per 50 1 per 50 1 per 100 1 service sink
4 Factory and industrial F-1 and F-2 Structures in which occupants are engaged in work fabricating, assembling or processing of products or materials 1 per 100 1 per 100 1 per 100 1 per 100 (see Section 411) 1 per 400 1 service sink
5 Institutional I-1 Residential care 1 per 10 1 per 10 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
I-2 Hospitals, ambulatory nursing home patientsb 1 per roomc 1 per roomc 1 per roomc 1 per roomc 1 per 15 1 per 100 1 service sink per floor
Employees, other than residential careb 1 per 25 1 per 25 1 per 35 1 per 35 1 per 100
Visitors, other than residential care 1 per 75 1 per 75 1 per 100 1 per 100 1 per 500
I-3 Prisonsb 1 per cell 1 per cell 1 per cell 1 per cell 1 per 15 1 per 100 1 service sink
I-3 Reformitories, detention centers, and correctional centersb 1 per 15 1 per 15 1 per 15 1 per 15 1 per 15 1 per 100 1 service sink
I-4 Adult day care and child care 1 per 15 1 per 15 1 per 15 1 per 15 1 per 100 1 service sink
6 Mercantile (see
Sections 403.2,
403.4, 403.4.1 and 403.4.2)
M Retail stores,
service stations,
shops, salesrooms,
markets and
shopping centers
1 per 500 1 per 500 1 per 750 1 per 750 1 per 1,000 1 service sink
7 Residential R-1 Hotels, motels, boarding houses (transient) 1 per sleeping
unit
1 per
sleeping
unit
1 per sleeping unit 1 per sleeping unit 1 per sleeping unit 1 service sink
R-2 Dormitories, fraternities, sororities and boarding houses (not transient) 1 per 10 1 per 10 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
R-2 Apartment house 1 per dwelling
unit
1 per
dwelling
unit
1 per dwelling unit 1 per dwelling unit 1 per dwelling unit 1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units
R-3 One- and two-family dwellings 1 per dwelling
unit
1 per
dwelling
unit
1 per dwelling unit 1 per dwelling unit 1 per dwelling unit 1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per dwelling unit
R-4 Residential care/
assisted living
facilities
1 per 10 1 per 10 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
8 Storage (see Sections 403.2, 403.4 and 403.4.1) S-1
S-2
Structures for the storage of goods, warehouses, storehouses and
freight depots. Low
and Moderate Hazard.
1 per 100 1 per 100 1 per 100 1 per 100 See Section 411 1 per 1,000 1 service sink
  1. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by the Building Code of New York State.
  2. Toilet facilities for employees shall be separate from facilities for inmates or patients.
  3. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted where such room is provided with direct access from each patient room and with provisions for privacy.
  4. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.
  5. Fixtures located in adjacent buildings under the ownership or control of the church or other place of worship shall be made available during periods the church or other place of worship is occupied.
  6. See Section 428.
Fixtures located within unisex toilet and bathing rooms complying with Section 404 are permitted to be included in determining the minimum required number of fixtures for assembly and mercantile occupancies
Where plumbing fixtures are required, separate facilities shall be provided for each sex.
Exception:
  1. Separate facilities shall not be required for dwelling units and sleeping units.
  2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or less.
  3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 50 or less.
The occupant load shall be composed of 50 percent of each sex.
Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
In occupancies other than covered malls, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).
Exception: The location and maximum travel distances to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum travel distance are approved.
In covered mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 440 mm). In covered mall buildings, the required facilities shall be based on total square footage, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum travel distance to central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space. In covered mall buildings, where employees' toilet facilities are not provided in the individual store, the maximum travel distance shall be measured from the employee's work area of the store or tenant space.
Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.
Required public facilities shall be designated by a legible sign for each sex. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with ICC/ANSI A117.1.
Accessible plumbing facilities and fixtures shall be provided in accordance with the Chapter 11 of the Building Code of New York State.
The supply lines and fittings for every plumbing fixture shall be installed so as to prevent backflow.
Plumbing fixtures shall be installed so as to afford easy access for cleaning both the fixture and the area around the fixture.
Fixtures shall be set level and in proper alignment with reference to adjacent walls.
A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches (381 mm) from its center to any side wall, partition (measured from the inside), vanity or other obstruction, or closer than 30 inches (762 mm) center-to-center between adjacent fixtures. There shall be at least a 21-inch (533 mm) clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches (762 mm) wide and 60 inches (1524 mm) deep (see Figure 405.3.1).




FIGURE 405.3.1 MINIMUM FIXTURE CLEARANCES
In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet.
Connections between the drain and floor outlet plumbing fixtures shall be made with a floor flange. The flange shall be attached to the drain and anchored to the structure. Connections between the drain and wall-hung water closets shall be made with an approved extension nipple or horn adaptor. The water closet shall be bolted to the hanger with corrosion-resistant bolts or screws. Joints shall be sealed with an approved elastomeric gasket, flange-to-fixture connection complying with ASME A112.4.3 or an approved setting compound.
Floor flanges for water closets or similar fixtures shall not be less than 0.125 inch (3.2 mm) thick for brass, 0.25 inch (6.4 mm) thick for plastic, and 0.25 inch (6.4 mm) thick and not less than a 2-inch (51 mm) caulking depth for cast-iron or galvanized malleable iron.

Floor flanges of hard lead shall weigh not less than 1 pound, 9 ounces (0.7 kg) and shall be composed of lead alloy with not less than 7.75-percent antimony by weight. Closet screws and bolts shall be of brass. Flanges shall be secured to the building structure with corrosion-resistant screws or bolts.
Floor outlet fixtures shall be secured to the floor or floor flanges by screws or bolts of corrosion-resistant material.
Wall-hung water closet bowls shall be supported by a concealed metal carrier that is attached to the building structural members so that strain is not transmitted to the closet connector or any other part of the plumbing system. The carrier shall conform to ASME A112.6.1M or ASME A112.6.2.
Joints formed where fixtures come in contact with walls or floors shall be sealed.
In mental health centers, pipes or traps shall not be exposed, and fixtures shall be bolted through walls.
Where any fixture is provided with an overflow, the waste shall be designed and installed so that standing water in the fixture will not rise in the overflow when the stopper is closed, and no water will remain in the overflow when the fixture is empty.
The overflow from any fixture shall discharge into the drainage system on the inlet or fixture side of the trap.
Exception: The overflow from a flush tank serving a water closet or urinal shall discharge into the fixture served.
Slip joints shall be made with an approved elastomeric gasket and shall only be installed on the trap outlet, trap inlet and within the trap seal. Fixtures with concealed slip-joint connections shall be provided with an access panel or utility space at least 12 inches (305 mm) in its smallest dimension or other approved arrangement so as to provide access to the slip joint connections for inspection and repair.
Integral fixture fitting mounting surfaces on manufactured plumbing fixtures or plumbing fixtures constructed on site, shall meet the design requirements of ASME A112.19.2M or ASME A112.19.3M.
Domestic automatic clothes washers shall conform to ASSE 1007.
The water supply to an automatic clothes washer shall be protected against backflow by an air gap installed integrally within the machine conforming to ASSE 1007 or with the installation of a backflow preventer in accordance with Section 608.
The waste from an automatic clothes washer shall discharge through an air break into a standpipe in accordance with Section 802.4 or into a laundry sink. The trap and fixture drain for an automatic clothes washer standpipe shall be a minimum of 2 inches (51 mm) in diameter. The automatic clothes washer fixture drain shall connect to a branch drain or drainage stack a minimum of 3 inches (76 mm) in diameter. Automatic clothes washers that discharge by gravity shall be permitted to drain to a waste receptor or an approved trench drain.
Bathtubs shall conform to ANSI Z124.1, ASME A112.19.1M, ASME A112.19.4M, ASME A112.19.9M, CSA B45.2, CSA B45.3 or CSA B45.5.
Bathtubs shall have waste outlets a minimum of 1.5 inches (38 mm) in diameter. The waste outlet shall be equipped with an approved stopper.
Windows and doors within a bathtub enclosure shall conform to the safety glazing requirements of the Building Code of New York State.
Doors within a bathtub enclosure shall conform to ASME A112.19.15.
Bidets shall conform to ASME A112.19.2M, ASME A112.19.9M or CSA B45.1.
The water supply to a bidet shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.13.1, 608.13.2, 608.13.3, 608.13.5, 608.13.6 or 608.13.8.
The discharge water temperature from a bidet fitting shall be limited to a maximum temperature of 110°F (43°C) by a water temperature limiting device conforming to ASSE 1070.
Domestic dishwashing machines shall conform to ASSE 1006. Commercial dishwashing machines shall conform to ASSE 1004 and NSF 3.
The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.
The waste connection of a dishwashing machine shall comply with Section 802.1.6 or 802.1.7, as applicable.
Drinking fountains shall conform to ASME A112.19.1M, ASME A112.19.2M or ASME A112.19.9M, and water coolers shall conform to ARI 1010. Drinking fountains and water coolers shall conform to NSF 61, Section 9. Where water is served in restaurants, drinking fountains shall not be required. In other occupancies, where drinking fountains are required, bottled water dispensers shall be permitted to be substituted for not more than 50 percent of the required drinking fountains. There shall be one drinking fountain available for each tenant. Where public and employee toilet facilities are located in the central core there shall be one per floor, readily available to the public. The code enforcement official may approve bottled water or a sink faucet in lieu of a drinking fountain when there are less than 10 occupants or when the taste of the water is unacceptable.
Drinking fountains shall not be installed in public restrooms.
Where required, emergency showers and eyewash stations shall conform to ISEA Z358.1.
Floor drains shall conform to ASME A112.6.3, ASME A112.3.1 or CSA B79. Trench drains shall comply with ASME A112.6.3.
Floor drains shall have removeable strainers. The floor drain shall be constructed so that the drain is capable of being cleaned. Access shall be provided to the drain inlet.
Floor drains shall have a minimum 2-inch-diameter (51 mm) drain outlet.
Floor drains shall be installed in commercial kitchens, public restrooms and in boiler rooms. In public coin-operated laundries and in the central washing facilities of multiple-family dwellings, the rooms containing automatic clothes washers shall be provided with floor drains located to readily drain the entire floor area. Floor drains shall have a minimum outlet of not less than 3 inches (76 mm) in diameter when installed above a slab and 4 inches when installed under a slab or otherwise not accessible for cleanout.
Exception: Floor drains are not required in public restrooms designed for use by a single occupant.
Domestic food waste grinders shall conform to ASSE 1008. Commercial food waste grinders shall conform to ASSE 1009. Food waste grinders shall not increase the drainage fixture unit load on the sanitary drainage system.
Domestic food waste grinders shall be connected to a drain of not less than 1.5 inches (38 mm) in diameter.
Commercial food waste grinders shall be connected to a drain a minimum of 2 inches (51 mm) in diameter. Commercial food waste grinders shall be connected and trapped separately from any other fixtures or sink compartments.
All food waste grinders shall be provided with a supply of cold water.
The water supply to a garbage can washer shall be protected against backflow by an air gap or a backflow preventer in accordance with Section 608.13.1, 608.13.2, 608.13.3, 608.13.5, 608.13.6 or 608.13.8.
Garbage can washers shall be trapped separately. The receptacle receiving the waste from the washer shall have a removable basket or strainer to prevent the discharge of large particles into the drainage system.
Laundry trays shall conform to ANSI Z124.6, ASME A112.19.1M, ASME A112.19.3M, ASME A112.19.9M, CSA B45.2 or CSA B45.4.
Each compartment of a laundry tray shall be provided with a waste outlet a minimum of 1.5 inches (38 mm) in diameter and a strainer or crossbar to restrict the clear opening of the waste outlet.
Lavatories shall conform to ANSI Z124.3, ASME A112.19.1M, ASME A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3 or CSA B45.4. Group wash-up equipment shall be permitted only for employee specific facilities and school locker rooms, only for the lavatories which are not required to be accessible, and shall conform to the requirements of Section 402. Every 20 inches (508 mm) of rim space shall be considered as one lavatory.
Cultured marble vanity tops with an integral lavatory shall conform to ANSI Z124.3 or CSA B45.5.
Lavatories shall have waste outlets not less than 1.25 inches (32 mm) in diameter. A strainer, pop-up stopper, crossbar or other device shall be provided to restrict the clear opening of the waste outlet.
Moveable lavatory systems shall comply with ASME A112.19.12.
Tempered water shall be delivered from public hand-washing facilities through an approved water temperature limiting device that conforms to ASSE 1070.
Prefabricated showers and shower compartments shall conform to ANSI Z124.2, ASME A112.19.9M or CSA B45.5. Shower valves for individual showers shall conform to the requirements of Section 424.3.
Every water supply riser from the shower valve to the shower head outlet, whether exposed or not, shall be attached to the structure in an approved manner.
Waste outlets serving showers shall be at least 11/2 inches (38 mm) in diameter and, for other than waste outlets in bathtubs, shall have removable strainers not less than 3 inches (76 mm) in diameter with strainer openings not less than 0.25 inch (6.4 mm) in minimum dimension. Where each shower space is not provided with an individual waste outlet, the waste outlet shall be located and the floor pitched so that waste from one shower does not flow over the floor area serving another shower. Waste outlets shall be fastened to the waste pipe in an approved manner.
All shower compartments shall have a minimum of 900 square inches (0.58 m2) of interior cross-sectional area. Shower compartments shall not be less than 30 inches (762 mm) in minimum dimension measured from the finished interior dimension of the compartment, exclusive of fixture valves, showerheads, soap dishes, and safety grab bars or rails. Except as required in Section 404, the minimum required area and dimension shall be measured from the finished interior dimension at a height equal to the top of the threshold and at a point tangent to its centerline and shall be continued to a height not less than 70 inches (1778 mm) above the shower drain outlet.
Exception: Shower compartments having not less than 25 inches (635 mm) in minimum dimension measured from the finished interior dimension of the compartment, provided that the shower compartment has a minimum of 1,300 square inches (.838 m2) of cross-sectional area.
The wall area above built-in tubs with installed shower heads and in shower compartments shall be constructed of smooth, noncorrosive and nonabsorbent waterproof materials to a height not less than 6 feet (1829 mm) above the room floor level, and not less than 70 inches (1778 mm) where measured from the compartment floor at the drain. Such walls shall form a water-tight joint with each other and with either the tub, receptor or shower floor.
The shower compartment access and egress opening shall have a minimum clear and unobstructed finished width of 22 inches (559 mm). Shower compartments required to be designed in conformance to accessibility provisions shall comply with Section 404.1.
Floor surfaces shall be constructed of impervious, noncorrosive, nonabsorbent and waterproof materials.
Floors or receptors under shower compartments shall be laid on, and supported by, a smooth and structurally sound base.
Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made water tight utilizing material complying with Sections 417.5.2.1 through 417.5.2.4. Such liners shall turn up on all sides at least 2 inches (51 mm) above the finished threshold level. Liners shall be recessed and fastened to an approved backing so as not to occupy the space required for wall covering, and shall not be nailed or perforated at any point less than 1 inch (25 mm) above the finished threshold. Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope) and shall be sloped toward the fixture drains and be securely fastened to the waste outlet at the seepage entrance, making a water-tight joint between the liner and the outlet.
Exception: Floor surfaces under shower heads provided for rinsing laid directly on the ground are not required to comply with this section.
Plasticized polyvinyl chloride (PVC) sheets shall be a minimum of 0.040 inch (1.02 mm) thick, and shall meet the requirements of ASTM D 4551. Sheets shall be joined by solvent welding in accordance with the manufacturer's installation instructions.
Nonplasticized chlorinated polyethylene sheet shall be a minimum 0.040 inch (1.02 mm) thick, and shall meet the requirements of ASTM D 4068. The liner shall be joined in accordance with the manufacturer's installation instructions.
Sheet lead shall not weigh less than 4 pounds per square foot (19.5 kg/m 2 ) coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or its equivalent. Sheet lead shall be joined by burning.
Sheet copper shall conform to ASTM B 152 and shall not weigh less than 12 ounces per square foot (3.7 kg/m 2 ). The copper sheet shall be insulated from conducting substances other than the connecting drain by 15-pound (6.80 kg) asphalt felt or its equivalent. Sheet copper shall be joined by brazing or soldering.
Windows and doors within a shower enclosure shall conform to the safety glazing requirements of the Building Code of New York State .
Sinks shall conform to ANSI Z124.6, ASME A112.19.1M, ASME A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3 or CSA B45.4.
Sinks shall be provided with waste outlets a minimum of 1.5 inches (38 mm) in diameter. A strainer or crossbar shall be provided to restrict the clear opening of the waste outlet.
Moveable sink systems shall comply with ASME A112.19.12.
Urinals shall conform to ANSI Z124.9, ASME A112.19.2M, CSA B45.1 or CSA B45.5. Urinals shall conform to the water consumption requirements of Section 604.4. Water supplied urinals shall conform to the hydraulic performance requirements of ASME A112.19.6, CSA B45.1 or CSA B45.5. Urinals shall conform to the requirements of Section 404.1.1.
In each bathroom or toilet room, urinals shall not be substituted for more than 67 percent of the required water closets in assembly and educational occupancies. Urinals shall not be substituted for more than 50 percent of the required water closets in all other occupancies, and shall conform to the requirements of Section 404.1.1.
Wall and floor space to a point 2 feet (610 mm) in front of a urinal lip and 4 feet (1219 mm) above the floor and at least 2 feet (610 mm) to each side of the urinal shall be waterproofed with a smooth, readily cleanable, nonabsorbent material.
Water closets shall conform to the water consumption requirements of Section 604.4 and shall conform to ANSI Z124.4, ASME A112.19.2M, CSA B45.1, CSA B45.4 or CSA B45.5. Water closets shall conform to the hydraulic performance requirements of ASME A112.19.6. Water closet tanks shall conform to ANSI Z124.4, ASME A112.19.2, ASME A112.19.9M, CSA B45.1, CSA B45.4 or CSA B45.5. Electro-hydraulic water closets shall comply with ASME A112.19.13.
Water closet bowls for public or employee toilet facilities shall be of the elongated type.
Water closets shall be equipped with seats of smooth, nonabsorbent material. All seats of water closets provided for public or employee toilet facilities shall be of the hinged open-front type. Integral water closet seats shall be of the same material as the fixture. Water closet seats shall be sized for the water closet bowl type.
A 4-inch by 3-inch (102 mm by 76 mm) closet bend shall be acceptable. Where a 3-inch (76 mm) bend is utilized on water closets, a 4-inch by 3-inch (102 mm by 76 mm) flange shall be installed to receive the fixture horn.
Whirlpool bathtubs shall comply with ASME A112.19.7M or with CSA B45.5 and CSA B45 (Supplement 1).
Whirlpool bathtubs shall be installed and tested in accordance with the manufacturer's installation instructions. The pump shall be located above the weir of the fixture trap.
The pump drain and circulation piping shall be sloped to drain the water in the volute and the circulation piping when the whirlpool bathtub is empty.
Suction fittings for whirlpool bathtubs shall comply with APSP 7.
Access shall be provided to circulation pumps in accordance with the fixture or pump manufacturer's installation instructions. Where the manufacturer's instructions do not specify the location and minimum size of field-fabricated access openings, a 12-inch by 12-inch (305 mm by 305 mm) minimum sized opening shall be installed to provide access to the circulation pump. Where pumps are located more than 2 feet (609 mm) from the access opening, an 18-inch by 18-inch (457 mm by 457 mm) minimum sized opening shall be installed. A door or panel shall be permitted to close the opening. In all cases, the access opening shall be unobstructed and of the size necessary to permit the removal and replacement of the circulation pump.
Doors within a whirlpool enclosure shall conform to ASME A112.19.15.
This section shall govern those aspects of health care plumbing systems that differ from plumbing systems in other structures. Health care plumbing systems shall conform to the requirements of this section in addition to the other requirements of this code. The provisions of this section shall apply to the special devices and equipment installed and maintained in the following occupancies: nursing homes, homes for the aged, orphanages, infirmaries, first aid stations, psychiatric facilities, clinics, professional offices of dentists and doctors, mortuaries, educational facilities, surgery, dentistry, research and testing laboratories, establishments manufacturing pharmaceutical drugs and medicines, and other structures with similar apparatus and equipment classified as plumbing.
All special plumbing fixtures, equipment, devices and apparatus shall be of an approved type.
All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to either the water supply or drainage system, shall be provided with protection against backflow, flooding, fouling, contamination of the water supply system and stoppage of the drain.
Fixtures designed for therapy, special cleansing or disposal of waste materials, combinations of such purposes, or any other special purpose, shall be of smooth, impervious, corrosion-resistant materials and, where subjected to temperatures in excess of 180°F (82°C), shall be capable of withstanding, without damage, higher temperatures.
Access shall be provided to concealed piping in connection with special fixtures where such piping contains steam traps, valves, relief valves, check valves, vacuum breakers or other similar items that require periodic inspection, servicing, maintenance or repair. Access shall be provided to concealed piping that requires periodic inspection, maintenance or repair.
A clinical sink shall have an integral trap in which the upper portion of a visible trap seal provides a water surface. The fixture shall be designed so as to permit complete removal of the contents by siphonic or blowout action and to reseal the trap. A flushing rim shall provide water to cleanse the interior surface. The fixture shall have the flushing and cleansing characteristics of a water closet.
A clinical sink serving a soiled utility room shall not be considered as a substitute for, or be utilized as, a service sink. A service sink shall not be utilized for the disposal of urine, fecal matter or other human waste.
Machines for manufacturing ice, or any device for the handling or storage of ice, shall not be located in a soiled utility room.
The approval and installation of all sterilizers shall conform to the requirements of the Mechanical Code of New York State.
Access for the purposes of inspection and maintenance shall be provided to all sterilizer piping and devices necessary for the operation of sterilizers.
Steam supplies to sterilizers, including those connected by pipes from overhead mains or branches, shall be drained to prevent any moisture from reaching the sterilizer. The condensate drainage from the steam supply shall be discharged by gravity.
Steam condensate returns from sterilizers shall be a gravity return system.
Pressure sterilizers shall be equipped with a means of condensing and cooling the exhaust steam vapors. Nonpressure sterilizers shall be equipped with a device that will automatically control the vapor, confining the vapors within the vessel.
Control valves, vacuum outlets and devices protruding from a wall of an operating, emergency, recovery, examining or delivery room, or in a corridor or other location where patients are transported on a wheeled stretcher, shall be located at an elevation that prevents bumping the patient or stretcher against the device.
Baptisteries, ornamental and lily pools, aquariums, ornamental fountain basins, swimming pools, and similar constructions, where provided with water supplies, shall be protected against backflow in accordance with Section 608.
Specialties requiring water and waste connections shall be submitted for approval.
Faucets and fixture fittings shall conform to ASME A112.18.1 or CSA B125. Faucets and fixture fittings that supply drinking water for human ingestion shall conform to the requirements of NSF 61, Section 9. Flexible water connectors exposed to continuous pressure shall conform to the requirements of Section 605.6.
Faucets and supply fittings shall conform to the water consumption requirements of Section 604.4.
Waste fittings shall conform to ASME A112.18.2, ASTM F 409, CSA B125 or to one of the standards listed in Tables 702.1 and 702.4 for above-ground drainage and vent pipe and fittings.
Hand-held showers shall conform to ASME A112.18.1 or CSA B125.1. Hand-held showers shall provide backflow protection in accordance with ASME A112.18.1 or CSA B125.1 or shall be protected against backflow by a device complying with ASME A112.18.3.
Individual shower and tub-shower combination valves shall be balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valves that conform to the requirements of ASSE 1016 or CSA B125 and shall be installed at the point of use. Shower and tub-shower combination valves required by this section shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturer's instructions. In-line thermostatic valves shall not be utilized for compliance with this section.
Multiple (gang) showers supplied with a single-tempered water supply pipe shall have the water supply for such showers controlled by an approved automatic temperature control mixing valve that conforms to ASSE 1069 or CSA B125, or each shower head shall be individually controlled by a balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valve that conforms to ASSE 1016 or CSA B125 and is installed at the point of use. Such valves shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturer's instructions.
The hot water supplied to bathtubs and whirlpool bathtubs shall be limited to a maximum temperature of 120°F (49°C) by a water temperature limiting device that conforms to ASSE 1070, except where such protection is otherwise provided by a combination tub/shower valve in accordance with Section 424.3.
Faucets and fixture fittings with hose-connected outlets shall conform to ASME A112.18.3M or CSA B125.
Temperature-actuated, flow reduction devices, where installed for individual fixture fittings, shall conform to ASSE 1062. Such valves shall not be used alone as a substitute for the balanced pressure, thermostatic or combination shower valves required in Section 424.3.
Deck-mounted bath/shower transfer valves containing an integral atmospheric vacuum breaker shall conform to the requirements of ASME A112.18.7.
Each water closet, urinal, clinical sink and any plumbing fixture that depends on trap siphonage to discharge the fixture contents to the drainage system shall be provided with a flushometer valve, flushometer tank or a flush tank designed and installed to supply water in quantity and rate of flow to flush the contents of the fixture, cleanse the fixture and refill the fixture trap.
A flushing device shall not serve more than one fixture.
Flushometer valves and tanks shall comply with ASSE 1037. Vacuum breakers on flushometer valves shall conform to the performance requirements of ASSE 1001 or CSA B64.1.1. Access shall be provided to vacuum breakers. Flushometer valves shall be of the water-conservation type and shall not be utilized where the water pressure is lower than the minimum required for normal operation. When operated, the valve shall automatically complete the cycle of operation, opening fully and closing positively under the water supply pressure. Each flushometer valve shall be provided with a means for regulating the flow through the valve. The trap seal to the fixture shall be automatically refilled after each valve flushing cycle.
Flush tanks equipped for manual flushing shall be controlled by a device designed to refill the tank after each discharge and to shut off completely the water flow to the tank when the tank is filled to operational capacity. The trap seal to the fixture shall be automatically refilled after each flushing. The water supply to flush tanks equipped for automatic flushing shall be controlled with a timing device or sensor control devices.
All flush tanks shall be equipped with an antisiphon fill valve conforming to ASSE 1002 or CSA B125. The fill valve backflow preventer shall be located at least 1 inch (25 mm) above the full opening of the overflow pipe.
Flush tanks shall be provided with overflows discharging to the water closet or urinal connected thereto and shall be sized to prevent flooding the tank at the maximum rate at which the tanks are supplied with water according to the manufacturer's design conditions. The opening of the overflow pipe shall be located above the flood level rim of the water closet or urinal or above a secondary overflow in the flush tank.
Sheet copper utilized for flush tank linings shall conform to ASTM B 152 and shall not weigh less than 10 ounces per square foot (0.03 kg/m 2 ).
All parts in a flush tank shall be accessible for repair and replacement.
Flush pipes and fittings shall be of nonferrous material and shall conform to ASME A112.19.5 or CSA B125.
Manual food and beverage dispensing equipment shall conform to the requirements of NSF 18.
Sanitary floor sinks shall conform to the requirements of ASME A112.6.7.
Service sinks shall be a wall mounted or floor mounted mop sink with a minimum 3-inch (76 mm) outlet. Laundry trays and laundry sinks are prohibited for use as a service sink. There shall be one service sink available for each tenant. Where public and employee toilet facilities are located in the central core there shall be one service sink per floor. The service sink shall not be located within the toilet facility and may be in a locked janitor closet.
Exception: In tenant spaces without access to a centrally located service sink and having limited areas of hard surface floors, the required service sink may be omitted subject to the approval of the Code Enforcement Official if at least one toilet room within the space is equipped with hose bib outlets for hot and cold water and a floor drain.
Analyzing code differences
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING