Heads up:
There are no amended sections in this chapter.
The provisions of this chapter shall apply where a change of occupancy occurs, as defined in Section 202, including:
- Where the occupancy classification is not changed, or
- Where there is a change in occupancy classification or the occupancy group designation changes.
A change in occupancy, as defined in Section 202, with no change of occupancy classification shall not be made to any structure that will subject the structure to any special provisions of the applicable Codes of New York State, including the provisions of Sections 902 through 911, without the approval of the code enforcement official.
Any repair or alteration work undertaken in connection with a change of occupancy that does not involve a change of occupancy classification shall conform to the applicable requirements for the work as classified in Chapter 4 and to the requirements of Sections 902 through 911.
Exception: As modified in Section 1105 for historic buildings.
Exception: As modified in Section 1105 for historic buildings.
Where a portion of an existing building is changed to a new occupancy classification, Section 912 shall apply.
Building Code of New York State. Where the character or use of an existing building or part of an existing building is changed to one of the following special use or occupancy categories as defined in the Building Code of New York State, the building shall comply with all of the applicable requirements of the Building Code of New York State:
- Covered mall buildings.
- Atriums.
- Motor vehicle-related occupancies.
- Aircraft-related occupancies.
- Motion picture projection rooms.
- Stages and platforms.
- Special amusement buildings.
- Incidental use areas.
- Hazardous materials.
An underground building in which there is a change of use shall comply with the requirements of the Building Code of New York State applicable to underground structures.
Nightclubs shall not be located on a story of a building where such use would not be permitted by Table 503 of the Building Code of New York State , and as modified by Section 504 where applicable.
Interior finishes in nightclubs and means of egress therefrom shall be in conformance with Table 803.5 of the Building Code of New York State .
An approved, supervised automatic sprinkler system conforming with the provisions of Section 903.3 of the Fire Code of New York State shall be installed throughout all floors containing a nightclub having an occupant load of 100 or more persons, and on all floor levels between the nightclub and the level of exit discharge.
An approved, supervised automatic fire alarm system conforming with the provisions of Section 907 of the Fire Code of New York State shall be installed throughout all buildings containing a nightclub, except notification appliances shall be required only on the floor levels containing a nightclub.
The means of egress from nightclubs shall be in conformance with Section 1029 of the Fire Code of New York State for A occupancies.
Exceptions:
- Existing doors having a clear opening width of not less than 28 inches (710 mm) and a height of 78 inches (1980 mm) shall be permitted to remain in use.
- Existing stairways having a width of not less than 36 inches (915 mm) shall be permitted to remain in use.
- Existing stairways shall be permitted to remain in use if the riser height does not exceed 81/4 inches (210 mm) and the tread is not less than 9 inches (229 mm), and that variations in riser height do not exceed 1/4 inch (155 mm) in any run of stairs.
- Existing guards and handrails having a height of not less than 34 inches (865 mm) and openings not exceeding 6 inches (155 mm) shall be permitted to remain in use.
Building elements and materials in portions of buildings undergoing a change of occupancy classification shall comply with Section 912.
Fire protection requirements of Section 912 shall apply where a building or portions thereof undergo a change of occupancy classification.
Carbon monoxide alarms and detectors shall comply with the Fire Code of New York State.
Means of egress in portions of buildings undergoing a change of occupancy classification shall comply with Section 912.
Accessibility in portions of buildings undergoing a change of occupancy classification shall comply with Section 912.8.
Buildings or portions thereof subject to a change of occupancy where such change in the nature of occupancy results in higher uniform or concentrated loads based on Tables 1607.1 and 1607.6 of the Building Code of New York State shall comply with the gravity load provisions of the Building Code of New York State.
Exceptions:
- Structural elements whose stress is not increased by more than 5 percent.
- Existing elements to remain in structures less than 3,500 square feet (325 m2) per floor and less than four stories, shall be permitted with live loads identified in Table 907.1 provided:
- The floor structure does not permit direct access by heavy equipment such as forklifts, through a loading dock or doors more than 44 inches in width, and
- Incidental storage or retail shelves shall not be permitted to exceed 6 feet 8 inches (2632 mm) in height.
OCCUPANCY OR USE | UNIFORM LOAD (PSF) | CONCENTRATED LOAD (LBS) |
Corridors | Same as occupancy served | |
Dining rooms and restaurants | 75 | |
Offices | 40 | |
Stairs and exits | 75 | 300 |
Stores—Retail—First floor | 75 |
Buildings and structures subject to a change of occupancy where such change in the nature of occupancy results in higher wind or snow occupancy categories based on Table 1604.5 of the Building Code of New York State shall be analyzed and shall comply with the applicable wind or snow load provisions of the Building Code of New York State.
Exception: Where the new occupancy with a higher importance factor is less than or equal to 10 percent of the total building floor area. The cumulative effect of the area of occupancy changes shall be considered for the purposes of this exception.
Exception: Where the new occupancy with a higher importance factor is less than or equal to 10 percent of the total building floor area. The cumulative effect of the area of occupancy changes shall be considered for the purposes of this exception.
Building Code of New York State . When a building or portion thereof is subject to a change of occupancy such that a change in the nature of the occupancy results in a seismic occupancy category based on Table 1604.5 of the Building Code of New York State; or where such change of occupancy results in a reclassification of a building to a higher hazard category as shown in Table 912.4; or where a change of a Group M occupancy to a Group A, E, I-1 R-1, R-2 or R-4 occupancy with two-thirds or more of the floors involved in Level 3 alteration work, the building shall conform to the seismic requirements of the Building Code of New York State for the new occupancy category.
Exceptions:
- Group M occupancies being changed to Group A, E, I-1, R-1, R-2 or R-4 occupancies for buildings less than six stories in height and in Seismic Design Category A, B or C.
- Specific detailing provisions required for a new structure are not required to be met where it can be shown that an acceptable level of performance and seismic safety is obtained for the applicable occupancy category using reduced Building Code of New York State level seismic forces as specified in Section 506.1.1.3. The rehabilitation procedures shall be approved by the code enforcement official and shall consider the regularity, overstrength, redundancy and ductility of the lateral-load-resisting system within the context of the existing detailing of the system.
- Where the area of the new occupancy with a higher hazard category is less than or equal to 10 percent of the total building floor area and the new occupancy is not classified as Occupancy Category IV. For the purposes of this exception, where a structure is occupied for two or more occupancies not included in the same occupancy category, the structure shall be assigned the classification of the highest occupancy category corresponding to the various occupancies. Where structures have two or more portions that are structurally separated, each portion shall be separately classified. Where a structurally separated portion of a structure provides required access to, required egress from, or shares life safety components with another portion having a higher occupancy category, both portions shall be assigned the higher occupancy category. The cumulative effect of the area of occupancy changes shall be considered for the purposes of this exception.
- Unreinforced masonry bearing wall buildings in Occupancy Category III when assigned to Seismic Design Category A or B shall be allowed to be strengthened to meet the requirements of Appendix Chapter A1 of this code.
Where the change of occupancy is such that compliance with Section 907.3.1 is required and the occupancy category is a Category IV, the operational access to such Occupancy Category IV existing structure shall not be through an adjacent structure.
Exception: Where the adjacent structure conforms to the requirements for Occupancy Category IV structures.
Where operational access is less than 10 feet (3048 mm) from an interior lot line or less than 10 feet (3048 mm) from another structure, access protection from potential falling debris shall be provided by the owner of the Occupancy Category IV structure.
Exception: Where the adjacent structure conforms to the requirements for Occupancy Category IV structures.
Where operational access is less than 10 feet (3048 mm) from an interior lot line or less than 10 feet (3048 mm) from another structure, access protection from potential falling debris shall be provided by the owner of the Occupancy Category IV structure.
Where the occupancy of an existing building or part of an existing building is changed to one of the following special occupancies as described in the NFPA 70, the electrical wiring and equipment of the building or portion thereof that contains the proposed occupancy shall comply with the applicable requirements of the NFPA 70 whether or not a change of occupancy group is involved:
- Hazardous locations.
- Commercial garages, repair, and storage.
- Aircraft hangars.
- Gasoline dispensing and service stations.
- Bulk storage plants.
- Spray application, dipping, and coating processes.
- Health care facilities.
- Places of assembly.
- Theaters, audience areas of motion picture and television studios, and similar locations.
- Motion picture and television studios and similar locations.
- Motion picture projectors.
Where the occupancy of an existing building or part of an existing building is changed, all unsafe conditions shall be corrected without requiring that all parts of the electrical system be brought up to NFPA 70.
Where the occupancy of an existing building or part of an existing building is changed, electrical service shall be upgraded to meet the requirements of the NFPA 70 for the new occupancy.
Where the occupancy of an existing building or part of an existing building is changed, the number of electrical outlets shall comply with the NFPA 70 for the new occupancy.
Where the occupancy of an existing building or part of an existing building is changed such that the new occupancy is subject to different kitchen exhaust requirements or to increased mechanical ventilation requirements in accordance with the Mechanical Code of New York State, the new occupancy shall comply with the intent of the respective Mechanical Code of New York State provisions.
Where the occupancy of an existing building or part of an existing building is changed such that the new occupancy is subject to increased or different plumbing fixture requirements or to increased water supply requirements in accordance with the Plumbing Code of New York State, the new occupancy shall comply with the intent of the respective Plumbing Code of New York State provisions.
If the new occupancy is a food-handling establishment, all existing sanitary waste lines above the food or drink preparation or storage areas shall be panned or otherwise protected to prevent leaking pipes or condensation on pipes from contaminating food or drink. New drainage lines shall not be installed above such areas and shall be protected in accordance with the Plumbing Code of New York State.
If the new occupancy will produce grease or oil-laden wastes, interceptors shall be provided as required in the Plumbing Code of New York State.
If the new occupancy will produce chemical wastes, the following shall apply:
- If the existing piping is not compatible with the chemical waste, the waste shall be neutralized prior to entering the drainage system, or the piping shall be changed to a compatible material.
- No chemical waste shall discharge to a public sewer system without the approval of the sewage authority.
If the occupancy group is changed to Group I-2, the plumbing system shall comply with the applicable requirements of the Plumbing Code of New York State.
Light and ventilation shall comply with the requirements of the Building Code of New York State for the new occupancy.
Any nonconditioned space that is altered to become conditioned space shall be required to be brought into full compliance with the Energy Conservation Construction Code of New York State.
The provisions of this section shall apply to buildings or portions thereof undergoing a change of occupancy classification. This includes a change of occupancy classification within a group as well as a change of occupancy classification from one group to a different group. Such buildings shall also comply with Sections 902 through 911. The application of requirements for the change of occupancy shall be as set forth in Sections 912.1.1 through 912.1.4. A change of occupancy, as defined in Section 202, without a corresponding change of occupancy classification shall comply with Section 901.2. For the purposes of this section and Tables 912.4, 912.5 and 912.6, an R-3 occupancy and one and two family dwelling shall be considered equivalent occupancies in terms of hazard classification.
Where a portion of an existing building is changed to a new occupancy classification and that portion is not separated from the remainder of the building with fire barriers having a fire-resistance rating as required in the Building Code of New York State for the separate occupancy, the entire building shall comply with all of the requirements of Chapter 8 applied throughout the building for the most restrictive occupancy classification in the building and with the requirements of this chapter.
Where a portion of an existing building that is changed to a new occupancy classification and that portion is separated from the remainder of the building with fire barriers having a fire-resistance rating as required in the Building Code of New York State for the separate occupancy, that portion shall comply with all the requirements of Chapter 8 for the new occupancy classification and with the requirements of this chapter.
All buildings undergoing a change of occupancy classification shall comply with Section 912.8.
Where a change in occupancy classification occurs that requires an automatic fire sprinkler system to be provided based on the new occupancy in accordance with Chapter 9 of the Building Code of New York State , such system shall be provided throughout the area where the change of occupancy occurs.
Where a change in occupancy classification occurs that requires a fire alarm and detection system to be provided based on the new occupancy in accordance with Chapter 9 of the Building Code of New York State , such system shall be provided throughout the area where the change of occupancy occurs. Existing alarm notification appliances shall be automatically activated throughout the building. Where the building is not equipped with a fire alarm system, alarm notification appliances shall be provided throughout the area where the change of occupancy occurs and shall be automatically activated.
In areas of the building undergoing the change of occupancy classification, the interior finish of walls and ceilings shall comply with the requirements of the Building Code of New York State for the new occupancy classification.
Hazard categories in regard to life safety and means of egress shall be in accordance with Table 912.4.
TABLE 912.4 MEANS OF EGRESS HAZARD CATEGORIES
TABLE 912.4 MEANS OF EGRESS HAZARD CATEGORIES
RELATIVE HAZARD | OCCUPANCY CLASSIFICATIONS |
1 (Highest Hazard) | H |
2 | I-2, I-3, I-4 |
3 | A, E, I-1, M, R-1, R-2, R-4 |
4 | B, F-1, R-3, S-1 |
5 (Lowest Hazard) | F-2, S-2, U |
When a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 912.4, the means of egress shall comply with the requirements of Chapter 10 of the Building Code of New York State.
Exceptions:
- Stairways shall be enclosed in compliance with the applicable provisions of Section 803.1.
- Existing stairways including handrails and guards complying with the requirements of Chapter 7 shall be permitted for continued use subject to approval of the code enforcement official.
- Any stairway replacing an existing stairway within a space where the pitch or slope cannot be reduced because of existing construction shall not be required to comply with the maximum riser height and minimum tread depth requirements.
- Existing corridor walls constructed of wood lath and plaster in good condition or 1/2-inch-thick (12.7 mm) gypsum wallboard shall be permitted.
- Existing corridor doorways, transoms, and other corridor openings shall comply with the requirements in Sections 705.5.1, 705.5.2, and 705.5.3.
- Existing dead-end corridors shall comply with the requirements in Section 705.6.
- An existing operable window with clear opening area no less than 4 square feet (0.38 m2) and with minimum opening height and width of 18 inches (457 mm) shall be accepted as an emergency escape and rescue opening.
When a change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 912.4, existing elements of the means of egress shall comply with the requirements of Section 805 for the new occupancy classification. Newly constructed or configured means of egress shall comply with the requirements of Chapter 10 of the Building Code of New York State .
Exception: Any stairway replacing an existing stairway within a space where the pitch or slope cannot be reduced because of existing construction shall not be required to comply with the maximum riser height and minimum tread depth requirements.
Exception: Any stairway replacing an existing stairway within a space where the pitch or slope cannot be reduced because of existing construction shall not be required to comply with the maximum riser height and minimum tread depth requirements.
Egress capacity shall meet or exceed the occupant load as specified in the Building Code of New York State for the new occupancy.
Existing stairways shall comply with the handrail requirements of Section 705.9 in the area of the change of occupancy classification.
Existing guards shall comply with the requirements in Section 705.10 in the area of the change of occupancy classification.
Hazard categories in regard to height and area shall be in accordance with Table 912.5.
TABLE 912.5 HEIGHTS AND AREAS HAZARD CATEGORIES
TABLE 912.5 HEIGHTS AND AREAS HAZARD CATEGORIES
RELATIVE HAZARD | OCCUPANCY CLASSIFICATIONS |
1 (Highest Hazard) | H |
2 | A-1, A-2, A-3, A-4, I, R-1, R-2, R-4 |
3 | E, F-1, S-1, M |
4 (Lowest Hazard) | B, F-2, S-2, A-5, R-3, U |
When a change of occupancy classification is made to a higher hazard category as shown in Table 912.5, heights and areas of buildings and structures shall comply with the requirements of Chapter 5 of the Building Code of New York State for the new occupancy classification.
Exception: In other than Groups H, F-1, I and S-1, in lieu of fire walls, use of fire barriers having a fire-resistance rating of not less than that specified in Table 705.4 of the Building Code of New York State, constructed in accordance with Section 706 of the Building Code of New York State, shall be permitted to meet area limitations required for the new occupancy in buildings protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the Fire Code of New York State.
Exception: In other than Groups H, F-1, I and S-1, in lieu of fire walls, use of fire barriers having a fire-resistance rating of not less than that specified in Table 705.4 of the Building Code of New York State, constructed in accordance with Section 706 of the Building Code of New York State, shall be permitted to meet area limitations required for the new occupancy in buildings protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the Fire Code of New York State.
When a change of occupancy classification is made to an equal or lesser hazard category as shown in Table 912.5, the height and area of the existing building shall be deemed acceptable.
When a change of occupancy classification is made to a higher hazard category as shown in Table 912.5, fire barriers in separated mixed-use buildings shall comply with the fire resistance requirements of the Building Code of New York State .
Exception: Where the fire barriers are required to have a 1-hour fire-resistance rating, existing wood lath and plaster in good condition or existing 1 / 2 -inch-thick (12.7 mm) gypsum wallboard shall be permitted.
Exception: Where the fire barriers are required to have a 1-hour fire-resistance rating, existing wood lath and plaster in good condition or existing 1 / 2 -inch-thick (12.7 mm) gypsum wallboard shall be permitted.
Hazard categories in regard to fire-resistance ratings of exterior walls shall be in accordance with Table 912.6.
TABLE 912.6 EXPOSURE OF EXTERIOR WALLS HAZARD CATEGORIES
TABLE 912.6 EXPOSURE OF EXTERIOR WALLS HAZARD CATEGORIES
RELATIVE HAZARD | OCCUPANCY CLASSIFICATION |
1 (Highest Hazard) | H |
2 | F-1, M, S-1 |
3 | A, B, E, I, R |
4 (Lowest Hazard) | F-2, S-2, U |
When a change of occupancy classification is made to a higher hazard category as shown in Table 912.6, exterior walls shall have fire resistance and exterior opening protectives as required by the Building Code of New York State . This provision shall not apply to walls at right angles to the property line.
Exception: A 2-hour fire-resistance rating shall be allowed where the building does not exceed three stories in height and is classified as one of the following groups: A-2 and A-3 with an occupant load of less than 300, B, F, M, or S.
Exception: A 2-hour fire-resistance rating shall be allowed where the building does not exceed three stories in height and is classified as one of the following groups: A-2 and A-3 with an occupant load of less than 300, B, F, M, or S.
When a change of occupancy classification is made to an equal or lesser hazard category as shown in Table 912.6, existing exterior walls, including openings, shall be accepted.
Openings in exterior walls shall be protected as required by the Building Code of New York State . Where openings in the exterior walls are required to be protected because of their distance from the property line, the sum of the area of such openings shall not exceed 50 percent of the total area of the wall in each story.
Exceptions:
- Where the Building Code of New York State permits openings in excess of 50 percent.
- Protected openings shall not be required in buildings of Group R occupancy that do not exceed three stories in height and that are located not less than 3 feet (914 mm) from the property line.
- Where exterior opening protectives are required, an automatic sprinkler system throughout may be substituted for opening protection.
- Exterior opening protectives are not required when the change of occupancy group is to an equal or lower hazard classification in accordance with Table 912.6
Vertical shafts shall be designed to meet the Building Code of New York State requirements for atriums or the requirements of this section.
When a change of occupancy classificiation is made to a higher hazard category as shown in Table 912.4, interior stairways shall be enclosed as required by the Building Code of New York State.
Exceptions:
Exceptions:
- In other than Group I occupancies, an enclosure shall not be required for openings serving only one adjacent floor and that are not connected with corridors or stairways serving other floors.
- Unenclosed existing stairways need not be enclosed in a continuous vertical shaft if each story is separated from other stories by 1-hour fire-resistance-rated construction or approved wired glass set in steel frames and all exit corridors are sprinklered. The openings between the corridor and the occupant space shall have at least one sprinkler head above the openings on the tenant side. The sprinkler system shall be permitted to be supplied from the domestic water-supply systems, provided the system is of adequate pressure, capacity, and sizing for the combined domestic and sprinkler requirements.
- Existing penetrations of stairway enclosures shall be accepted if they are protected in accordance with the Building Code of New York State.
Interior vertical shafts other than stairways, including but not limited to elevator hoistways and service and utility shafts, shall be enclosed as required by the Building Code of New York State when there is a change of use to a higher hazard category as specified in Table 912.4.
Exceptions:
- Existing 1-hour interior shaft enclosures shall be accepted where a higher rating is required.
- Vertical openings, other than stairways, in buildings of other than Group I occupancy and connecting less than six stories shall not be required to be enclosed if the entire building is provided with an approved automatic sprinkler system.
All openings into existing vertical shaft enclosures shall be protected by fire assemblies having a fire-protection rating of not less than 1 hour and shall be maintained self-closing or shall be automatic closing by actuation of a smoke detector. All other openings shall be fire protected in an approved manner. Existing fusible link-type automatic door-closing devices shall be permitted in all shafts except stairways if the fusible link rating does not exceed 135°F (57°C).
Existing buildings or portions thereof that undergo a change of group or occupancy classification shall have all of the following accessible features:
- At least one accessible building entrance.
- At least one accessible route from an accessible building entrance to primary function areas.
- Signage complying with Section 1110 of the Building Code of New York State.
- Accessible parking, where parking is provided.
- At least one accessible passenger loading zone, where loading zones are provided.
- At least one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.
- At least one accessible toilet room complying with Section 1109.2.1 of the Building Code of New York State, where toilet rooms are provided.
- Where more than four Groups R-2 or R-3 dwelling units or sleeping units are being constructed, twenty-five percent shall comply with Section 1107.2 of the Building Code of New York State.
Exception: Buildings without elevator service where the lowest story containing Group R-2 or R-3 dwelling units is not the ground floor.
Where it is technically infeasible to comply with the new construction standards for any of these requirements for a change of group or occupancy, the above items shall conform to the requirements to the maximum extent technically feasible. Changes of group or occupancy that incorporate any alterations or additions shall comply with this section and Sections 605.1, 706.1 or 1005.1 as applicable.