Heads up: There are no amended sections in this chapter.
Level 3 alterations as described in Section 405 shall comply with the requirements of this chapter.
In addition to the provisions of this chapter, work shall comply with all of the requirements of Chapters 6 and 7. The requirements of Sections 703, 704, and 705 shall apply within all work areas whether or not they include exits and corridors shared by more than one tenant and regardless of the occupant load.

Exception:
Buildings in which the reconfiguration of space affecting exits or shared egress access is exclusively the result of compliance with the accessibility requirements of Section 605.2 shall not be required to comply with this chapter.
Any building having occupied floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall comply with the requirements of Sections 802.1.1 and 802.1.2.
When a floor is served by a recirculating air or exhaust system with a capacity greater than 15,000 cubic feet per minute (701 m 3 /s), that system shall be equipped with approved smoke and heat detection devices installed in accordance with the Mechanical Code of New York State.
Where there is an elevator or elevators for public use, at least one elevator serving the work area shall comply with this section. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.
Boiler and furnace equipment rooms adjacent to or within the following facilities shall be enclosed by 1-hour fire-resistance-rated construction: day nurseries, children's shelter facilities, residential childcare facilities, and similar facilities with children below the age of 21/2 years or that are classified as Group I-2 occupancies, shelter facilities, residences for the developmentally disabled, group homes, transitional living homes, rooming and boarding houses, hotels, and multiple dwellings.

Exceptions:
  1. Furnace and boiler equipment of low-pressure type, operating at pressures of 15 pounds per square inch gauge (psig) (103.4 KPa) or less for steam equipment or 170 psig (1171 KPa) or less for hot water equipment, when installed in accordance with manufacturer recommendations.
  2. Furnace and boiler equipment of residential R-3 type with 200,000 British thermal units (Btu) (2.11 × 108 J) per hour input rating or less is not required to be enclosed.
  3. Furnace rooms protected with automatic sprinkler protection.
Emergency controls for boilers and furnace equipment shall be provided in accordance with the Mechanical Codeof New York State in all buildings classified as day nurseries, children's shelter facilities, residential childcare facilities, and similar facilities with children below the age of 2 1 / 2 years or that are classified as Group I-2 occupancies, and in group homes, and supervised transitional living homes in accordance with the following:
  1. Emergency shutoff switches for furnaces and boilers in basements shall be located at the top of the stairs leading to the basement; and
  2. Emergency shutoff switches for furnaces and boilers in other enclosed rooms shall be located outside of such room.
Where existing nightclubs contain or are located within Level 3 alteration work areas, the building or portion thereof in which the nightclub is located shall comply with Sections 802.3.1 - 802.3.4.
Interior finishes in nightclubs and the means of egress therefrom shall be in conformance with Table 803.5 of the Building Code of New York State .
Where an automatic sprinkler system is required to be installed by Section 903 of the Building Code of New York State , an adequate water supply shall be deemed to be available where the automatic sprinkler system can be designed and installed without installation of a fire pump. Where an adequate water supply is not available, the code enforcement official may accept alternative means for protecting occupants. A written report shall be prepared and submitted by a registered design professional which provides documentation that the proposed alternative(s) meet the performance standard.
Where an automatic fire detection system is required to be installed by Section 907 of the Building Code of New York State , it shall be installed in conformance with the provisions of Section 907.2.1 of the Fire Code of New York State .
The means of egress from nightclubs shall be in conformance with Section 1029 of the Fire Code of New York State for A occupancies. Existing nightclubs required to conform with provisions of the Uniform Fire Prevention and Building Code in effect on or after January 1, 1984 shall not be required to conform with Section 1029.
Existing stairways that are part of the means of egress shall be enclosed in accordance with Section 703.2.1 between the highest work area floor and the level of exit discharge and all floors below.
Fire separation in Group R-3 occupancies shall be in accordance with Section 803.2.1.
Where the work area is in any attached dwelling unit in Group R-3 or any multiple single family dwelling (townhouse), walls separating the dwelling units that are not continuous from the foundation to the underside of the roof sheathing shall be constructed to provide a continuous fire separation using construction materials consistent with the existing wall or complying with the requirements for new structures. All work shall be performed on the side of the dwelling unit wall that is part of the work area.

Exception:
Where alterations or repairs do not result in the removal of wall or ceiling finishes exposing the structure, walls are not required to be continuous through concealed floor spaces.
Interior finish in exits serving the work area shall comply with Section 703.4 between the highest floor on which there is a work area to the floor of exit discharge.
Automatic sprinkler systems shall be provided in all work areas when required by Section 704.2 or by this section.
In high-rise buildings, work areas shall be provided with automatic sprinkler protection where the building has a sufficient municipal water supply system to the site. Where the work area exceeds 50 percent of floor area, sprinklers shall be provided in the specified areas where sufficient municipal water supply for design and installation of a fire sprinkler system is available at the site.
Rubbish and linen chutes located in the work area shall be provided with sprinklered protection where protection of the rubbish and linen chute would be required under the provisions of the Building Codeof New York State f or new construction and the building has sufficient municipal water supply available to the site.
Fire alarm and detection systems complying with Sections 704.4.1 and 704.4.3 shall be provided throughout the building in accordance with the Building Code of New York State.
Where required by the Building Code of New York State, a manual fire alarm system shall be provided throughout the work area. Alarm notification appliances shall be provided on such floors and shall be automatically activated as required by the Building Code of New York State.
Exceptions:
  1. Alarm-initiating and notification appliances shall not be required to be installed in tenant spaces outside of the work area.
  2. Visual alarm notification appliances are not required, except where an existing alarm system is upgraded or replaced or where a new fire alarm system is installed.
Where required by the Building Code of New York State for new buildings, automatic fire detection systems shall be provided throughout the work area.
The means of egress shall comply with the requirements of Section 705 except as specifically required in Sections 805.2 and 805.3.
Means of egress from the highest work area floor to the floor of exit discharge shall be provided with artificial lighting within the exit enclosure in accordance with the requirements of the Building Code of New York State.
Means of egress from the highest work area floor to the floor of exit discharge shall be provided with exit signs in accordance with the requirements of the Building Code of New York State.
A building, facility, or element that is altered shall comply with Section 605.
When more than four Group R-2 or R-3 dwelling units or sleeping units are being altered, 25 percent shall comply with Section 1107.2 of the Building Code of New York State.

Exception:
Buildings without elevator services where the lowest story containing Group R-2 or R-3 dwelling units is not the ground floor.
Where buildings are undergoing Level 3 alterations including structural alterations, the provisions of this section shall apply.
Alterations shall not reduce the structural strength or stability of the building, structure, or any individual member thereof.

Exception:
Such reduction shall be allowed provided that the structural strength and the stability of the building are not reduced to below the Building Code of New York State levels.
New structural members in alterations, including connections and anchorage, shall comply with the Building Code of New York State.
The minimum design loads on existing elements of a structure that do not support additional loads as a result of an alteration shall be the loads applicable at the time the building was constructed.
Buildings and structures undergoing Level 3 structural alterations or buildings in which the seismic base shear is increased by more than 10 percent or in which the seismic base shear capacity is decreased by more than 10 percent because of alterations shall comply with this section. Changes in base shear and base shear capacity shall be calculated relative to conditions at the time of the original construction.

Exceptions:
  1. Buildings of Group R occupancy with no more than five dwelling or sleeping units used solely for residential purposes that are altered based on the conventional light-frame construction methods of the Building Code of New York State.
  2. Where such alterations involve only the lowest story of a building and the change of occupancy provisions of Chapter 9 do not apply, only the lateral-force-resisting components in and below that story need comply with this section.
  3. If the building's seismic base shear capacity has been increased since the original construction, the percentage changes shall be permitted to be calculated relative to the increased value.
An engineering evaluation and analysis that establishes the structural adequacy of the altered structure shall be prepared by a registered design professional and submitted to the code enforcement official.
Where more than 30 percent of the total floor and roof areas of the building or structure have been or are proposed to be involved in structural alteration within a 12-month period, the evaluation and analysis shall demonstrate that the altered building or structure complies with the Building Codeof New York State for wind loading and with reduced Building Codeof New York State level seismic forces as specified in Section 506.1.1.3 for seismic loading. For seismic considerations, the analysis shall be based on one of the procedures specified in Section 506.1.1.1. The areas to be counted toward the 30 percent shall be those areas tributary to the vertical load-carrying components, such as joists, beams, columns, walls and other structural components that have been or will be removed, added or altered, as well as areas such as mezzanines, penthouses, roof structures and in-filled courts and shafts.
Where not more than 30 percent of the total floor and roof areas of the building are involved in structural alteration within a 12-month period, the evaluation and analysis shall demonstrate that the altered building or structure complies with the loads applicable at the time of the original construction or of the most recent substantial structural alteration as defined by Section 807.5.2.
Where gravity loading is increased on the roof or floor of a building or structure, all structural members affected by such increase shall meet the gravity load requirements of the Building Code of New York State.

Exceptions:
  1. Structural elements whose stress is not increased by more than 5 percent.
  2. Buildings of Group R occupancy with no more than five dwelling units or sleeping units used solely for residential purposes that are altered based on the conventional light-frame construction methods of the Building Code of New York State.
Alterations of existing structural elements and additions of new structural elements that are initiated for the purpose of increasing the lateral-force-resisting strength or stiffness of an existing structure and that are not required by other sections of this code shall not be required to be designed for forces conforming to the Building Code of New York State, provided that an engineering analysis is submitted to show that:
  1. The capacity of existing structural elements required to resist forces is not reduced;
  2. Either the lateral loading to existing structural elements is not increased beyond their capacity or the lateral loading to existing structural elements is not increased by more than 10 percent;
  3. New structural elements are detailed and connected to the existing structural elements as required by the Building Code of New York State;
  4. New or relocated nonstructural elements are detailed and connected to existing or new structural elements as required by the Building Code of New York State; and
  5. A dangerous condition as defined in this code is not created.

    Voluntary alterations to lateral-force-resisting systems conducted in accordance with Appendix A and the referenced standards of this code shall be permitted.
Energy conservation measures in existing buildings shall be in conformance with Section 101 of the Energy Conservation Construction Code of New York State.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING