Heads up: There are no amended sections in this chapter.
Level 1 alterations as described in Section 403 shall comply with the requirements of this chapter. Level 1 alterations to historic buildings shall comply with this chapter, except as modified in Chapter 11.
An existing building or portion thereof shall not be altered such that the building becomes less safe than its existing condition.

Exception:
Where the current level of safety or sanitation is proposed to be reduced, the portion altered shall conform to the requirements of the Building Code of New York State.
In flood hazard areas, alterations that constitute substantial improvement shall require that the building comply with Section 1612 of the Building Code of New York State.
All newly installed interior finishes shall comply with the flame spread requirements of the Building Code of New York State.
New carpeting used as an interior floor finish material shall comply with the radiant flux requirements of the Building Code of New York State.
All new work shall comply with materials and methods requirements in the NFPA 70, Building Code of New York State, Energy Conservation Construction Code of New York State, Mechanical Code of New York State, and Plumbing Code of New York State, as applicable, that specify material standards, detail of installation and connection, joints, penetrations, and continuity of any element, component, or system in the building.
Fuel Gas Code of New York State . The following sections of the Fuel Gas Code of New York State shall constitute the fuel gas materials and methods requirements for Level 1 alterations.[FG]
  1. All of Chapter 3, entitled "General Regulations," except Sections 303.7 and 306.
  2. All of Chapter 4, entitled "Gas Piping Installations," except Sections 401.8 and 402.3.
2.1. Sections 401.8 and 402.3 shall apply when the work being performed increases the load on the system such that the existing pipe does not meet the size required by the code. Existing systems that are modified shall not require resizing as long as the load on the system is not increased and the system length is not increased even if the altered system does not meet code minimums.
3. All of Chapter 5, entitled "Chimneys and Vents."
4. All of Chapter 6, entitled "Specific Appliances."
Alterations shall be done in a manner that maintains the level of fire protection provided.
nightclubs. Foam plastic materials that are not permitted to be used in new construction by the Building Code of New York State shall be removed in existing nightclubs.
Repairs shall be done in a manner that maintains the level of protection provided for the means of egress.
A building, facility or element that is altered shall comply with the applicable provisions in Sections 605.1.1 through 605.1.12, Chapter 11 of the Building Code of New York State and ICC/ANSI A117.1 unless it is technically infeasible. Where compliance with this section is technically infeasible, the alteration shall provide access to the maximum extent that is technically feasible.

A building, facility or element that is constructed or altered to be accessible shall be maintained accessible during occupancy.

Exceptions:
  1. The altered element or space is not required to be on an accessible route unless required by Section 605.2.
  2. Accessible means of egress required by Chapter 10 of the Building Code of New York State are not required to be provided in existing buildings and facilities.
  3. The alteration to Type A individually owned dwelling units within a Group R-2 occupancy shall meet the provisions for Type B dwelling units and shall comply with the applicable provisions in Chapter 11 of the Building Code of New York State and ICC/ANSI A117.1.
Where an alteration includes alterations to an entrance, and the building or facility has an accessible entrance on an accessible route, the altered entrance is not required to be accessible unless required by Section 605.2. Signs complying with Section 1110 of the Building Code of New York State shall be provided.
Altered elements of existing elevators shall comply with ASME A17.1 and ICC/ANSI A117.1. Such elements shall also be altered in elevators programmed to respond to the same hall call control as the altered elevator.
Platform (wheelchair) lifts complying with ICC/ANSI A117.1 and installed in accordance with ASME A18.1 shall be permitted as a component of an accessible route.
Where steeper slopes than allowed by Section 1010.2 of the Building Code of New York State are necessitated by space limitations, the slope of ramps in or providing access to existing buildings or facilities shall comply with Table 605.1.4.

TABLE 605.1.4
RAMPS

SLOPE MAXIMUM RISE
Steeper than 1:10 but not steeper than 1:8 3 inches
Steeper than 1:12 but not steeper than 1:10 6 inches


For SI: 1 inch = 25.4 mm.
An accessible route to raised or sunken dining areas or to outdoor seating areas is not required provided that the same services and decor are provided in an accessible space usable by any occupant and not restricted to use by people with a disability.
Where it is technically infeasible to alter performance areas to be on an accessible route, at least one of each type of performance area shall be made accessible.
In alterations, accessible wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where ramp or lift access poses a hazard by restricting or projecting into a required means of egress.
Where Group I-1, I-2, I-3, R-1, R-2, or R-4 dwelling or sleeping units are being altered, the requirements of Section 1107 of the Building Code of New York State for accessible or Type B units and Chapter 9 of the Building Code of New York State for accessible alarms apply only to the quantity of the spaces being altered.
Where it is technically infeasible to alter existing toilet and bathing facilities to be accessible, an accessible unisex toilet or bathing facility is permitted. The unisex facility shall be located on the same floor and in the same area as the existing facilities.
Where it is technically infeasible to provide accessible dressing, fitting, or locker rooms at the same location as similar types of rooms, one accessible room on the same level shall be provided. Where separate sex facilities are provided, accessible rooms for each sex shall be provided. Separate sex facilities are not required where only unisex rooms are provided.
The maximum height of thresholds at doorways shall be 3 / 4 inch (19.1 mm). Such thresholds shall have beveled edges on each side.
An alteration of an existing element, space, or area of a building or facility shall not impose a requirement for greater accessibility than that which would be required for new construction. Alterations shall not reduce or have the effect of reducing accessibility of a building, portion of a building, or facility.
Where an alteration affects the accessibility to a, or contains an area of, primary function, the route to the primary function area shall be accessible. The accessible route to the primary function area shall include toilet facilities or drinking fountains serving the area of primary function.

Exceptions:
  1. The costs of providing the accessible route are not required to exceed 20 percent of the costs of the alterations affecting the area of primary function.
  2. This provision does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets and signs.
  3. This provision does not apply to alterations limited solely to mechanical systems, electrical systems, installation or alteration of fire protection systems and abatement of hazardous materials.
  4. This provision does not apply to alterations undertaken for the primary purpose of increasing the accessibility of an existing building, facility or element.
Where alteration work includes replacement of equipment that is supported by the building or where a reroofing permit is required, the structural provisions of this section shall apply.
Existing structural components supporting alteration work shall comply with this section.
Where addition or replacement of roofing or replacement of equipment results in additional dead loads, structural components supporting such reroofing or equipment shall comply with the vertical load requirements of the Building Code of New York State.
Exceptions:
  1. Structural elements where the additional dead load from the roofing or equipment is not increased by more than 5 percent.
  2. Buildings constructed in accordance with the Residential Code of New York State or the conventional light-frame construction methods of the Building Code of New York State and where the dead load from the roofing or equipment is not increased by more than 5 percent.
  3. Addition of a second layer of roof covering weighing 3 pounds per square foot (0.1437 kN/m2) or less over an existing, single layer of roof covering shall be permitted.
Unreinforced masonry bearing wall buildings classified as Seismic Design Category D, E, or F shall have parapet bracing and wall anchors installed at the roof line whenever a reroofing permit is issued. Such parapet bracing and wall anchors shall be designed in accordance with the reduced Building Code of New York State level seismic forces as specified in Section 506.1.1.3 and design procedures of Section 506.1.1.1.
Where roofing materials are removed from more than 50 percent of the roof diaphragm of a building or section of a building where the roof diaphragm is a part of the main windforce-resisting system the integrity of the roof diaphragm shall be evaluated and if found deficient because of insufficient or deteriorated connections, such connections shall be provided or replaced.
Energy conservation measures in existing buildings shall be in conformance with Section 101 of the Energy Conservation Construction Code of New York State.
Materials and methods of application used for recovering or replacing an existing covering or replacing an existing roof covering shall comply with the requirements of Chapter 15 of the Building Code of New York State.

Exception
: Reroofing shall not be required to meet the minimum design slope requirement of one-quarter vertical in 12 units horizontal (2-percent slope) in section 1507 of the Building Code of New York State for roofs that provide positive drainage.
Structural roof componenets shall be capable of supporting the roof-covering system and the material and equipment loads that will be encountered during installation of the system.
New roof coverings shall not be installed without first removing all existing layers of roof coverings where any of the following conditions occur:
  1. Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing.
  2. Where the existing roof covering is wood shake, slate, clay, cement or asbestos-cement tile.
  3. Where the existing roof has two or more applications of any type of roof covering.
    Exceptions:
    1. Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings.
    2. The application of a new protective coating over an existing spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings.
Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum board, mineral fiber, glass fiber or other approved materials securely fastened in place.
Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars and metal counterflashings shall not be reinstalled where rusted, damaged or deteriorated. Aggregate surfacing materials shall not be reinstalled.
Flashings shall be reconstructed in accordance with approved manufacturer's installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING