The requirements of Chapter 12 shall apply unless modified by this chapter.
Where fireproofing is not provided, steel columns shall be protected as follows:
- Storage exceeding 15 ft through 20 ft (4.6 m through 6 m) in height — one sidewall sprinkler directed to one side of the column at a 15 ft (4.6 m) level
- Storage exceeding 20 ft (6.1 m) in height — two sidewall sprinklers, one at the top of the column and the other at a 15 ft (4.6 m) level, both directed to the side of the column
The flow from a column sprinkler(s) shall be permitted to be omitted from the sprinkler system hydraulic calculations.
The protection specified in 18.2.1 shall not be required where ESFR or CMSA sprinkler systems that are approved for rubber tire storage are installed.
Total water supplies shall be in accordance with the following options:
- A minimum of not less than 750 gpm (2835 L/min) for hose streams in addition to that required for automatic sprinklers and foam systems. Water supplies shall be capable of supplying the demand for sprinkler systems and hose streams for not less than 3 hours.
- For on-floor storage up to and including 5 ft (1.5 m) in height, hose stream requirements shall be permitted to be 250 gpm (946 L/min) with a water supply duration of not less than 2 hours.
- For ESFR and CMSA sprinkler systems approved for rubber tire storage, duration and hose allowance shall be in accordance with Table 18.4(c) and Table 18.4(d).
Sprinkler discharge and area of application shall be in accordance with one of the following:
- Table 18.4(a) or Table 18.4(b) for standard spray sprinklers
- Table 18.4(c) for CMSA sprinklers
- Table 18.4(d) for ESFR sprinklers
Table 18.4(a) Protection Criteria for Rubber Tire Storage Using Control Mode Density/Area Sprinklers
Piling Method | Pile Height (ft) | Sprinkler Discharge Density (gpm/ft2 over ft2) (see Note 1) |
Areas of Application (ft2) (see Note 1) |
|
---|---|---|---|---|
Ordinary Temperature | High Temperature (see Note 1) |
|||
(1) On-floor storage | Up to 5 | 0.19 | 2000 | 2000 |
(a) Pyramid piles, on-side | Over 5 to 12 | 0.30 | 2500 | 2500 |
(b) Other arrangements such that no horizontal channels are formed (see Note 2) | Over 12 to 18 | 0.60 | Not allowed | 2500 |
(2) On-floor storage Tires, on-tread |
Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 12 | 0.30 | 2500 | 2500 | |
(3) Palletized portable rack storage On-side or on-tread |
Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 20 | See Table 18.4(b) | — | — | |
Over 20 to 30 | 0.30 plus high-expansion foam | 3000 | 3000 | |
(4) Palletized portable rack storage, on-side | Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 20 | See Table 18.4(b) | — | — | |
Over 20 to 25 | 0.60 and | Not allowed | 5000 | |
0.90 (see Note 3) or | Not allowed | 3000 | ||
0.75 with 1-hour fire-resistive rating of roof and ceiling assembly | Not allowed | 4000 | ||
(5) Open portable rack storage, on-side or on-tread | Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 12 | 0.60 | 5000 | 3000 | |
Over 12 to 20 | 0.60 and | Not allowed | 5000 | |
0.90 (see Note 3) or | Not allowed | 3000 | ||
0.30 plus high-expansion foam | 3000 | 3000 | ||
(6) Open portable rack storage, laced | Over 12 to 20 | 0.60 and | Not allowed | 5000 |
0.90 (see notes 3 and 3) | Not allowed | 3000 | ||
(7) Single-, double-, and multiple-row fixed rack | Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 20 | See Table 18.4(b) or | 3000 | 3000 | |
0.40 plus one level in-rack sprinklers or | ||||
0.30 plus high-expansion foam | 3000 | 3000 | ||
Over 20 to 30 | 0.30 plus high-expansion foam | Not allowed | 3000 | |
(8) Single-, double-, and multiple-row fixed rack storage without pallets or shelves, on-side or on-tread | Up to 5 | 0.19 | 2000 | 2000 |
Over 5 to 12 | 0.60 | 5000 | 3000 | |
0.40 plus one level in-rack sprinklers | 3000 | 3000 | ||
Over 12 to 20 | 0.60 and | Not allowed | 5000 | |
0.90 (see Note 3) or | Not allowed | 3000 | ||
0.40 plus one level in-rack sprinklers or | 3000 | 3000 | ||
0.30 plus high-expansion foam | 3000 | 3000 | ||
Over 20 to 30 | 0.30 plus high-expansion foam | Not allowed | 3000 | |
For SI units, 1 ft = 0.3048 m; 1 ft2 = 0.0929 m2; 1 gpm/ft2 = 40.746 mm/min. | ||||
Notes: | ||||
(1) Sprinkler discharge densities and areas of application are based on a maximum clearance to ceiling of 10 ft (3.1 m) with the maximum height of storage anticipated. | ||||
(2) Laced tires on-floor, vertical stacking on-side (typical truck tires), and off-road tires. Laced tires are not stored to a significant height by this method due to the damage inflicted on the tire (i.e., bead). | ||||
(3) Water supply shall fulfill both requirements. | ||||
(4) Shelf storage of rubber tires shall be protected as solid rack shelving. | ||||
(5) This protection scheme is for use with K-16.8 (240) or larger control mode sprinklers only. Maximum clearance to ceiling can be increased to 14 ft (4.25 m) with this scheme. |
Table 18.4(b) Control Mode Density/Area Sprinklers System Density (gpm/ft2 over ft2) for Palletized Portable Rack Storage and Fixed Rack Storage of Rubber Tires with Pallets Over 5 ft to 20 ft in Height
Storage Height (ft) |
Sprinkler Temperature | |
---|---|---|
High Temperature | Ordinary Temperature | |
>5 to 10 | 0.32/2000 | 0.32/2000 |
>10 to 12 | 0.39/2000 | 0.39/2600 |
>12 to 14 | 0.45/2000 | 0.45/3200 |
>14 to 16 | 0.5/2300 | 0.5/3700 |
>16 to 18 | 0.55/2600 | 0.55/4400 |
>18 to 20 | 0.6/3000 | 0.6/5000 |
Table 18.4(c) Control Mode Specific Application (CMSA) Protection for Rubber Tires
Piling Method | Maximum Storage Height | Maximum Ceiling/Roof Height | K-Factor | Type of System | Number of Sprinklers | Operating Pressure | Hose Stream Allowance | Water Supply Duration (hours) | ||
---|---|---|---|---|---|---|---|---|---|---|
ft | m | ft | m | |||||||
Rubber tire storage, on-side or on-tread, in palletized portable racks, or open portable racks, or fixed racks without solid shelves | 25 | 7.6 | 32 | 9.8 | 11.2 (160) | Wet | 15 | 75 psi (5.2 bar) | 500 gpm (1900 L/min) | 3 |
25 | 7.6 | 32 | 9.8 | 16.8 (240) | Wet | 15 | 35 psi (2.4 bar) | 500 gpm (1900 L/min) | 3 |
Table 18.4(d) Early Suppression Fast-Response (ESFR) Sprinklers for Protection of Rubber Tires (see Note 1)
Piling Method | Pile Height | Maximum Building Height | Nominal K-factor | Orientation | Number of Sprinklers | Minimum Operating Pressure (see Note 2) |
Duration (hours) | Hose Allowance | |||
---|---|---|---|---|---|---|---|---|---|---|---|
ft | m | psi | bar | gpm | L/min | ||||||
Rubber tire storage, on-side or on-tread, in palletized portable racks, open portable racks, or fixed racks without solid shelves | Up to 25 ft (7.6 m) | 30 | 9.1 | 14.0 (200) |
Upright/pendent | 12 (see Note 2) |
50 | 3.5 | 1 | 250 | 946 |
16.8 (240) |
Upright/pendent | 12 (see Note 2) |
35 | 2.4 | 1 | 250 | 946 | ||||
22.4 (320) |
Pendent | 12 (see Note 2) |
25 | 1.7 | 1 | 250 | 946 | ||||
25.2 (360) |
Pendent | 12 (see Note 2) |
15 | 1.0 | 1 | 250 | 946 | ||||
Rubber tire storage, on-side, in palletized portable racks, open portable racks, or fixed racks without solid shelves | Up to 25 ft (7.6 m) |
35 | 10.7 | 14.0 (200) |
Upright/pendent | 12 (see Note 2) |
75 | 5.2 | 1 | 250 | 946 |
16.8 (240) |
Pendent | 12 (see Note 2) |
52 | 3.6 | 1 | 250 | 946 | ||||
22.4 (320) |
Pendent | 12 (see Note 2) |
35 | 2.4 | 1 | 250 | 946 | ||||
25.2 (360) |
Pendent | 12 (see Note 2) |
25 | 1.7 | 1 | 250 | 946 | ||||
On-tread, on-side, and laced tires in open portable steel racks or palletized portable racks | Up to 25 ft (7.6 m) |
30 | 9.1 | 14.0 (200) |
Pendent | 20 (see Notes 3 and 4) |
75 | 5.2 | 3 | 500 | 1900 |
16.8 (240) |
Pendent | 20 (see Notes 3 and 4) |
52 | 3.6 | |||||||
Rubber tire storage, on-side, in palletized portable racks | Up to 25 ft (7.6 m) |
40 | 12.2 | Pendent | 12 | 75 | 5.2 | 1 | 250 | 946 | |
16.8 (240) |
Pendent | 12 | 52 | 3.6 | |||||||
Rubber tire storage, on-tread, or laced in open portable steel racks | Up to 25 ft (7.6 m) |
40 | 12.2 | 25.2 (360) |
Pendent | 12 | 40 | 2.8 | 1 | 250 | 946 |
On-tread, on-side, and laced tires in open portable steel racks or palletized portable racks | Up to 30 ft (9.1 m) |
40 | 12.2 | 25.2 (360) |
Pendent | 12 | 75 | 5.2 | 1 | 250 | 946 |
Notes: | |||||||||||
(1) Wet systems only. | |||||||||||
(2) The shape of the design area shall be in accordance with 14.4.3 and 14.4.4. | |||||||||||
(3) Where used in this application, ESFR protection is expected to control rather than to suppress the fire. | |||||||||||
(4) The design area shall consist of the most hydraulically demanding area of 20 sprinklers, consisting of five sprinklers on each of four branch lines. The design shall include a minimum operating area of 1600 ft2 (149 m2). |
In-rack sprinklers, where provided, shall be installed in accordance with Chapter 17, except as modified by 18.5.2 through 18.5.4.
Where high-expansion foam systems are installed in accordance with NFPA 11, a reduction in sprinkler discharge density to one-half the density specified in Table 18.4(a) or 0.24 gpm/ft2 (9.78 mm/min), whichever is higher, shall be permitted.