This chapter shall apply to palletized, solid-piled, bin box, shelf, or back-to-back shelf storage for a broad range of combustibles.
The requirements of Chapter 12 shall apply unless modified by this chapter.
Protection for Class I through Class IV commodities in the following configurations shall be provided in accordance with this section:
- Nonencapsulated commodities that are solid-piled, palletized, or bin box storage up to 30 ft (9.1 m) in height
- Nonencapsulated commodities on shelf storage up to 15 ft (4.6 m) in height
- *Encapsulated commodities that are solid-piled, palletized, bin box, or shelf storage up to 15 ft (4.6 m) in height
- Back-to-back shelf storage up to 15 ft (4.6 m) in height
- Encapsulated storage of solid-piled and palletized Class I through IV commodities permitted in accordance with 14.2.5 for storage heights over 15 ft (4.6 m) up to and including 20 ft (6.1 m)
The protection criteria for storage up to and including 12 ft (3.7 m) shall be the same as for miscellaneous storage selected from Chapter 13.
The protection criteria in Chapter 13 shall be acceptable for storage of Class I to Class IV commodities up to and including 12 ft (3.7 m) in height (see Table 13.2.1).
Where using ordinary temperature-rated sprinklers, a single point shall be selected from the appropriate commodity curve on Figure 14.2.4.1.

FIGURE 14.2.4.1 Sprinkler System Design Curves for 20 ft (6.1 m) High Storage — Ordinary Temperature-Rated Sprinklers.
Where using high temperature-rated sprinklers, a single point shall be selected from the appropriate commodity curve on Figure 14.2.4.2.

FIGURE 14.2.4.2 Sprinkler System Design Curves for 20 ft (6.1 m) High Storage — High Temperature-Rated Sprinklers.
For storage greater than 12 ft (3.7 m), the design density shall not be less than 0.15 gpm/ft2 (6.1 mm/min), and the design area shall not be less than 2000 ft2 (186 m2) for wet systems or 2600 ft2 (242 m2) for dry systems for any commodity, class, or group.
For back-to-back shelf storage, the design density shall be taken from Figure 14.2.4.1 for storage greater than 12 ft (3.7 m) and up to 15 ft (4.6 m) with no reduction for design density referenced in Figure 14.2.4.3.
Encapsulated storage over 15 ft (4.6 m) in height up to and including 20 ft (6.1 m) in height shall be limited to solid-piled and palletized storage.
Encapsulated storage over 15 ft (4.6 m) in height up to and including 20 ft (6.1 m) in height shall be protected by sprinklers with a K-factor of 11.2 (160) or larger.
Encapsulated storage over 15 ft (4.6 m) in height up to and including 20 ft (6.1 m) in height of Class I commodity shall be protected with a density/area of at least 0.46 gpm/ft2 over 2000 ft2 (18.7 mm/min over 186 m2).
Encapsulated storage over 15 ft (4.6 m) in height up to and including 20 ft (6.1 m) in height of Class II commodity shall be protected with a density/area of at least 0.53 gpm/ft2 over 2000 ft2 (21.7 mm/min over 186 m2).
Protection of palletized and solid-piled storage of Class I through Class IV commodities shall be in accordance with Table 14.3.1.
Table 14.3.1 CMSA Sprinkler Design Criteria for Palletized and Solid-Piled Storage of Class I Through Class IV Commodities (Encapsulated and Nonencapsulated)
Configuration | Commodity Class | Maximum Storage Height | Maximum Ceiling/Roof Height | K-Factor/Orientation | Type of System | Number of Design Sprinklers | Minimum Operating Pressure | |||
---|---|---|---|---|---|---|---|---|---|---|
ft | m | ft | m | psi | bar | |||||
Palletized | Class I or II | 25 | 7.6 | 30 | 9.1 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 |
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 10 | 0.7 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
35 | 10.6 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 | ||||
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 15 | 1.0 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 | ||
Class III | 25 | 7.6 | 30 | 9.1 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 | |
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 15 | 1.0 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
35 | 10.6 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 | ||||
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 15 | 1.0 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 | ||
Class IV | 20 | 6.1 | 30 | 9.1 | 11.2 (160) Upright | Wet | 20 | 25 | 1.7 | |
15 | 50 | 3.5 | ||||||||
16.8 (240) Upright | Wet | 20 | 15 | 1.0 | ||||||
15 | 22 | 1.5 | ||||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
25 | 7.6 | 30 | 9.1 | 16.8 (240) Upright | Wet | 15 | 22 | 1.5 | ||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 | ||
Solid piled | Class I or II | 20 | 6.1 | 30 | 9.1 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 |
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 10 | 0.7 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
25 | 7.6 | 30 | 9.1 | 16.8 (240) Upright | Wet | 15 | 10 | 0.7 | ||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 | ||
Class III | 20 | 6.1 | 30 | 9.1 | 11.2 (160) Upright | Wet | 15 | 25 | 1.7 | |
Dry | 25 | 25 | 1.7 | |||||||
16.8 (240) Upright | Wet | 15 | 15 | 1.0 | ||||||
Dry | 25 | 15 | 1.0 | |||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
25 | 7.6 | 30 | 9.1 | 16.8 (240) Upright | Wet | 15 | 22 | 1.5 | ||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 | ||
Class IV | 20 | 6.1 | 30 | 9.1 | 11.2 (160) Upright | Wet | 15 | 50 | 3.5 | |
16.8 (240) Upright | Wet | 15 | 22 | 1.5 | ||||||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
25 | 7.6 | 30 | 9.1 | 16.8 (240) Upright | Wet | 15 | 22 | 1.5 | ||
19.6 (280) Pendent | Wet | 15 | 16 | 1.1 | ||||||
30 | 9.1 | 35 | 10.6 | 19.6 (280) Pendent | Wet | 15 | 25 | 1.7 | ||
35 | 10.6 | 40 | 12.1 | 19.6 (280) Pendent | Wet | 15 | 30 | 2.1 |
Hose stream allowance and water supply duration requirements shall be in accordance with Table 14.3.1.
For the purpose of using Table 14.3.1, preaction systems shall be classified as dry pipe systems.
Building steel shall not require special protection where Table 14.3.1 are applied as appropriate for the storage configuration.
Protection of palletized and solid-piled storage of Class I through Class IV commodities shall be in accordance with Table 14.4.1.
Table 14.4.1 ESFR Protection of Palletized and Solid-Piled Storage of Class I Through Class IV Commodities
Commodity | Maximum Storage Height | Maximum Ceiling/Roof Height | Nominal K-Factor | Orientation | Minimum Operating Pressure | |||
---|---|---|---|---|---|---|---|---|
ft | m | ft | m | psi | bar | |||
Class I, II, III, or IV, encapsulated and nonencapsulated (no open-top containers) | 20 | 6.1 | 25 | 7.6 | 14.0 (200) | Upright/pendent | 50 | 3.4 |
16.8 (240) | Upright/pendent | 35 | 2.4 | |||||
22.4 (320) | Pendent | 25 | 1.7 | |||||
25.2 (360) | Pendent | 15 | 1.0 | |||||
25 | 7.6 | 30 | 9.1 | 14.0 (200) | Upright/pendent | 50 | 3.4 | |
16.8 (240) | Upright/pendent | 35 | 2.4 | |||||
22.4 (320) | Pendent | 25 | 1.7 | |||||
25.2 (360) | Pendent | 15 | 1.0 | |||||
32 | 9.8 | 14.0 (200) | Upright/pendent | 60 | 4.1 | |||
16.8 (240) | Pendent | 42 | 2.9 | |||||
30 | 9.1 | 35 | 10.7 | 14.0 (200) | Upright/pendent | 75 | 5.2 | |
16.8 (240) | Upright,/pendent | 52 | 3.6 | |||||
22.4 (320) | Pendent | 35 | 2.4 | |||||
25.2 (360) | Pendent | 20 | 1.4 | |||||
35 | 10.7 | 40 | 12.2 | 16.8 (240) | Upright/pendent | 52 | 3.6 | |
22.4 (320) | Pendent | 40 | 2.8 | |||||
25.2 (360) | Pendent | 25 | 1.7 | |||||
35 | 10.7 | 45 | 13.7 | 22.4 (320) | Pendent | 40 | 2.8 | |
25.2 (360) | Pendent | 40 | 2.8 | |||||
40 | 12.2 | 45 | 13.7 | 22.4 (320) | Pendent | 40 | 2.8 | |
25.2 (360) | Pendent | 40 | 2.8 |
ESFR sprinkler systems shall be designed such that the minimum operating pressure is not less than that indicated in Table 14.4.1 for commodity, storage height, and building height involved.
The design area shall consist of the most hydraulically demanding area of 12 sprinklers, consisting of four sprinklers on each of three branch lines.
Bin box and shelf storage that is over 12 ft (3.7 m) but not in excess of the height limits of 14.2.1 and that is provided with walkways at vertical intervals of not over 12 ft (3.7 m) shall be protected with automatic sprinklers under the walkway (s).
Protection shall be as follows:
- Ceiling design density shall be based on the total height of storage within the building.
- Automatic sprinklers under walkways shall be designed to maintain a minimum discharge pressure of 15 psi (1 bar) for the most hydraulically demanding six sprinklers on each level. Walkway sprinkler demand shall not be required to be added to the ceiling sprinkler demand. Sprinklers under walkways shall not be spaced more than 8 ft (2.4 m) apart horizontally.
A reduction in ceiling density to one-half that required for Class I through Class IV commodities, idle pallets, or plastics shall be permitted without revising the design area, but the density shall be no less than 0.15 gpm/ft2 (6.1 mm/min).