Part 1 — Scope and Application

R101.1 Title

AMENDMENT
This section has been amended at the state or city level.

R101.1 General

AMENDMENT
This section has been amended at the state or city level.

R101.1.1 Introduction

AMENDMENT
This section has been amended at the state or city level.
The New York State Energy Conservation Construction Code promulgated pursuant to Article 11 of the Energy Law (hereinafter referred to as the "Energy Code") is contained in Title 19 of the New York Codes, Rules and Regulations (NYCRR), Part 1240, and in the publications incorporated by reference in 19 NYCRR Part 1240. The publications incorporated by reference in 19 NYCRR Part 1240 include:

  • the publication entitled "2015 International Energy Conservation Code" (Second Printing: May 2015) published by International Code Council, Inc. (hereinafter referred to as the "2015 IECC");
  • the publication entitled "ANSI/ ASHRAE / IES Standard 90.1-2013, Energy Standard for Buildings Except Low-Rise Residential Buildings" (July 2014 Printing), published by American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (hereinafter referred to as "ASHRAE 90.1-2013");
  • the publication entitled "2016 Supplement to the New York State Energy Conservation Construction Code (Revised August 2016)" (Publication Date: August, 2016) published by the New York State Department of State (hereinafter referred to as the "2016 Energy Code Supplement"); and
  • the other referenced codes standards mentioned and/or referred to in 19 NYCRR Part 1240.

The 2015 IECC includes two sets of provisions: the "IECC — Commercial Provisions" and the "IECC — Residential Provisions." The "IECC — Commercial Provisions," as they appear in the 2015 IECC, are hereinafter referred to as the "2015 IECC Commercial Provisions." The "IECC — Residential Provisions," as they appear in the 2015 IECC, are hereinafter referred to as the "2015 IECC Residential Provisions."

For the purposes of applying the 2015 IECC Commercial Provisions, ASHRAE 90.1-2013, and the 2015 IECC Residential Provisions in New York State:

R101.1.2 Titles

AMENDMENT
This section has been amended at the state or city level.
2015 IECC Commercial Provisions. The 2015 IECC Commercial Provisions, as they appear in the 2015 IECC, are referred to in the 2016 Energy Code Supplement as the "2015 IECC Commercial Provisions."

2015 IECC Commercial Provisions (as amended). The 2015 IECC Commercial Provisions, as amended by Part 1 of the 2016 Energy Code Supplement, are referred to in the 2016 Energy Code Supplement as the "2015 IECC Commercial Provisions (as amended)."

ASHRAE 90.1-2013 (as amended). ASHRAE 90.1-2013, as amended by Part 2 of the 2016 Energy Code Supplement, is referred to in the 2016 Energy Code Supplement as "ASHRAE 90.1-2013 (as amended)."

2015 IECC Residential Provisions. The 2015 IECC Residential Provisions, as they appear in the 2015 IECC, are referred to in the 2016 Energy Code Supplement as the "2015 IECC Residential Provisions."

2015 IECC Residential Provisions (as amended). The 2015 IECC Residential Provisions, as amended by Part 3 of the 2016 Energy Code Supplement, are referred to in the 2016 Energy Code Supplement as the "2015 IECC Residential Provisions (as amended)."

References in the 2015 IECC Residential Provisions to "this code." Each reference in the 2015 IECC Residential Provisions to "this code" shall be deemed to be a reference to the 2015 IECC Residential Provisions (as amended).

References in the 2015 IECC Residential Provisions to Sections and Tables. Each reference in the 2015 IECC Residential Provisions to a Section or Table in the 2015 IECC Residential Provisions shall be deemed to be a reference to such Section or Table in the 2015 IECC Residential Provisions (as amended).

R101.1.3 Administration and Enforcement

AMENDMENT
This section has been amended at the state or city level.
The Energy Code shall be administered and enforced in accordance with the strictest of:

(i)    the requirements of the code enforcement program established by the governmental unit or agency responsible for administration and enforcement of the Energy Code with respect to the building in question,

(ii)   the minimum requirements established by the regulations adopted by the Department of State pursuant to section 381(1) of the New York State Executive Law, or

(iii)  the requirements set forth in this Chapter 1 [RE] and, as applicable, in Chapter 1 [CE] of the 2015 IECC Commercial Provisions (as amended).

R101.2 Scope

AMENDMENT
This section has been amended at the state or city level.
The 2015 IECC Residential Provisions (as amended) apply to residential buildings, the sites on which residential buildings are located, and building systems and equipment in residential buildings.

R101.3 Intent

AMENDMENT
This section has been amended at the state or city level.
The 2015 IECC Residential Provisions (as amended) shall regulate the design and construction of new residential buildings; additions to, alterations of, and/or renovations of existing residential buildings; and additions to, alterations of, and/or renovations of building systems in existing residential buildings for the use and conservation of energy over the life of each such residential building. The 2015 IECC Residential Provisions (as amended) are intended to provide flexibility to permit the use of innovative approaches and techniques to achieve the objectives set forth in the preceding sentence. The 2015 IECC Residential Provisions (as amended) are not intended to abridge safety, health or environmental requirements contained in other applicable statutes, laws, rules, regulations, codes or ordinances.

Nothing in this section R101.3, or in any other provision in this Chapter 1 [RE] of the 2015 IECC Residential Provisions (as amended), or in any other provision of the 2015 IECC Residential Provisions (as amended), shall be construed as permitting any code official, or any governmental unit or agency charged with the administration and enforcement of the Energy Code, to waive, vary, modify or otherwise alter any standard or requirement of the 2015 IECC Residential Provisions (as amended) or any other standard or requirement of the Energy Code. Standards or requirements of the Energy Code may be varied or modified only pursuant to Section 11-106 of the New York State Energy Law.

R101.4 Applicability

AMENDMENT
This section has been amended at the state or city level.
Where, in any specific case, different sections of the 2015 IECC Residential Provisions (as amended) specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern.

R101.4.1 Mixed Occupancy

AMENDMENT
This section has been amended at the state or city level.
Where a building includes both residential and commercial occupancies, (1) each occupancy shall be separately considered; (2) each residential occupancy shall meet the applicable provisions of the 2015 IECC Residential Provisions (as amended); and (3) each commercial occupancy shall meet the applicable provisions of the 2015 IECC Commercial Provisions (as amended), or, to the extent permitted by the 2015 IECC Commercial Provisions (as amended), the applicable provisions of ASHRAE 90.1- 2013 (as amended).

R101.5 Compliance

AMENDMENT
This section has been amended at the state or city level.
Residential buildings shall meet the 2015 IECC Residential Provisions (as amended). Commercial buildings shall meet the 2015 IECC Commercial Provisions (as amended). To the extent permitted by the 2015 IECC Commercial Provisions (as amended), commercial buildings may comply with ASHRAE 90.1-2013 (as amended) in lieu of complying with the 2015 IECC Commercial Provisions (as amended).

R101.5.1 Compliance Materials

AMENDMENT
This section has been amended at the state or city level.

R101.5.1 Compliance Software

AMENDMENT
This section has been amended at the state or city level.
Compliance with the 2015 IECC Residential Provisions (as amended) can be demonstrated through the use of:

(1) computer software that is developed by the United States Department of Energy (such as REScheck) specifically for the 2015 IECC Residential Provisions (as amended), or

(2) other software that shall have been expressly approved in writing by the New York Secretary of State as acceptable for demonstrating compliance with the 2015 IECC Residential Provisions (as amended).

Software programs used to demonstrate compliance must indicate compliance with the 2015 IECC Residential Provisions (as amended), and must reflect the actual requirements of the 2015 IECC Residential Provisions (as amended).

R101.5.1.1 Mandatory Provisions

AMENDMENT
This section has been amended at the state or city level.
The use of the software approach to demonstrate compliance does not excuse compliance with any mandatory provision of the 2015 IECC Residential Provisions (as amended). When using the software approach to demonstrate compliance with the provisions of the 2015 IECC Residential Provisions (as amended), compliance with all applicable mandatory provisions of the 2015 IECC Residential Provisions (as amended) will still be required.

R101.6 Statutory Limitations and Exemptions

AMENDMENT
This section has been amended at the state or city level.

R101.6.1

AMENDMENT
This section has been amended at the state or city level.
In the event of an addition to or alteration of an existing building or building system, the Energy Code shall not be interpreted to require any unaltered portion of such existing building or building system to comply with the Energy Code.

R101.6.2

AMENDMENT
This section has been amended at the state or city level.
The Energy Code shall not apply to any of the following, provided that the energy use of the building is not increased: (1) storm windows installed over existing fenestration; (2) glass only replacements in an existing sash and frame; (3) existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with insulation; (4) construction where the existing roof, wall or floor cavity is not exposed; (5) reroofing for roofs where neither the sheathing nor the insulation is exposed; roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be insulated either above or below the sheathing; (6) replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided, however, that an existing vestibule that separates such conditioned space from the exterior shall not be removed; (7) alterations that replace less than fifty percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power; or (8) alterations that replace only the bulb and ballast within the existing luminaires in a space provided that the alteration does not increase the installed interior lighting power.

R101.6.3

AMENDMENT
This section has been amended at the state or city level.
Historic buildings are exempt from the Energy Code.

Section R102 Alternative Materials, Design and Methods of Construction and Equipment

AMENDMENT
This section has been amended at the state or city level.

Section R102 Alternate Materials, Methods of Construction, Design or Insulating Systems

AMENDMENT
This section has been amended at the state or city level.

R102.1 General

AMENDMENT
This section has been amended at the state or city level.
The 2015 IECC Residential Provisions (as amended) are not intended to prevent the use of any material, method of construction, design or insulating system not specifically prescribed in the 2015 IECC Residential Provisions (as amended), provided that such method of construction, design or insulating system has been approved by the code official as (1) meeting the intent of the 2015 IECC Residential Provisions (as amended) and (2) achieving energy savings that is equivalent or greater than that which would be achieved by the prescribed method of construction, design or insulating system.

Nothing in this section R102.1, or in any other provision in this Chapter 1 [RE] of the 2015 IECC Residential Provisions (as amended), or in any other provision of the 2015 IECC Residential Provisions (as amended), shall be construed shall be construed as permitting any code official, or any governmental unit or agency charged with the administration and enforcement of the Energy Code, to waive, vary, modify or otherwise alter any standard or requirement of the 2015 IECC Residential Provisions (as amended) or any other standard or requirement of the Energy Code. Standards or requirements of the Energy Code may be varied or modified only pursuant to Section 11-106 of the New York State Energy Law.

R102.1.1 Above Code Programs

AMENDMENT
This section has been amended at the state or city level.

Part 2 — Administration and Enforcement

Section R103 Construction Documents

AMENDMENT
This section has been amended at the state or city level.
NOTE: Requirements relating to the construction documents that must be provided with an application for a building permit or construction permit shall be the strictest of:

(i)    the requirements of the code enforcement program established by the governmental unit or agency responsible for administration and enforcement of the Energy Code with respect to the building in question,

(ii)   the minimum requirements established by the regulations adopted by the Department of State pursuant to section 381(1) of the New York State Executive Law, or

(iii)  the requirements set forth in this Section R103 and, as applicable, the requirements set forth in Section C103 of the 2015 IECC Commercial Provisions (as amended).

R103.1 General

AMENDMENT
This section has been amended at the state or city level.
Construction documents and other supporting data shall be submitted in one or more sets with each application for a permit. The construction documents shall be prepared by a registered design professional as required by the New York State Education Law Articles 145 and 147.

Exception: Where construction documents are not required to be prepared by a registered design professional in accordance with New York State Education Law Articles 145 and 147, the code official is authorized to waive the requirements for construction documents or other supporting data if the code official determines they are not necessary to confirm compliance with this code.

R103.2 Information on Construction Documents

AMENDMENT
This section has been amended at the state or city level.
Construction documents shall be drawn to scale upon suitable material. Electronic media documents are permitted to be submitted where approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed, and shall show in sufficient detail pertinent data and features of the building, systems and equipment as herein governed. Details shall include, but are not limited to, the following as applicable:
  1. Insulation materials and their R-values.
  2. Fenestration U-factor and solar heat gain coefficient (SHGC).
  3. Area-weighted U-factor and solar heat gain coefficient (SHGC) calculations.
  4. Mechanical system design criteria.
  5. Mechanical and service water heating system and equipment types, sizes and efficiencies.
  6. Equipment and system controls.
  7. Duct sealing, duct and pipe insulation and location.
  8. Air sealing details.

R103.2.1 Building Thermal Envelope Depiction

AMENDMENT
This section has been amended at the state or city level.
The building's thermal envelope shall be represented on the construction drawings.

R103.2.2 Written Statement

AMENDMENT
This section has been amended at the state or city level.
When plans or specifications bear the seal and signature of a registered design professional, such registered design professional shall also include a written statement that to the best of his or her knowledge, belief and professional judgment, such plans or specifications are in compliance with the Energy Code.

R103.3 Examination of Documents

AMENDMENT
This section has been amended at the state or city level.
The code official shall examine or cause to be examined the accompanying construction documents and shall ascertain whether the construction indicated and described is in accordance with the requirements of the Energy Code and other pertinent laws or ordinances. The code official is authorized to utilize a registered design professional, or other approved entity not affiliated with the design or construction of the building in question, in conducting the review of the plans and specifications for compliance with the Energy Code.

R103.3.1 Approval of Construction Documents

AMENDMENT
This section has been amended at the state or city level.
When the code official issues a permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "Reviewed for Energy Code Compliance." Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.

One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, kept at the site of work and shall be open to inspection by the code official or a duly authorized representative.

R103.3.2 Previous Approvals

AMENDMENT
This section has been amended at the state or city level.
The 2015 IECC Residential Provisions (as amended) shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit was issued prior to the effective date of the rule making the 2015 IECC Residential Provisions (as amended) part of the Energy Code, provided that construction pursuant to such permit is commenced in good faith within 180 days after such effective date and is thereafter diligently pursued through completion.

R103.3.3 Phased Approval

AMENDMENT
This section has been amended at the state or city level.
The code official shall have the authority to issue a permit for the construction of part of an energy conservation system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of the Energy Code. The holders of such permit shall proceed at their own risk without assurance that the permit for the entire energy conservation system will be granted.

R103.4 Amended Construction Documents

AMENDMENT
This section has been amended at the state or city level.
Changes made during construction that are not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents.

R103.5 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level.
One set of approved construction documents shall be retained by the code official for a period of not less than seven years from the date of the demolition and removal of the building.

Section R104 Inspections

AMENDMENT
This section has been amended at the state or city level.
NOTE: Requirements relating to inspections of work shall be the strictest of:

(i)    the requirements of the code enforcement program established by the governmental unit or agency responsible for administration and enforcement of the Energy Code with respect to the building in question,

(ii)   the minimum requirements established by the regulations adopted by the Department of State pursuant to section 381(1) of the New York State Executive Law, or

(iii)  the requirements set forth in Section R104 and, as applicable, the requirements set forth in Section C104 of the 2015 IECC Commercial Provisions (as amended).

R104.1 General

AMENDMENT
This section has been amended at the state or city level.
Construction or work for which a permit is required shall be subject to inspection by the code official or an inspector who is (i) qualified to perform the inspections (such qualifications to include, where required, completion of the training required by 19 NYCRR Part 1208) and (ii) approved by the code official.

R104.1.1 Required Approvals

AMENDMENT
This section has been amended at the state or city level.
Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The permit holder or the permit holder's agent shall notify the code official when work has progressed to the point where the next required inspection described in Section R104.2 can be made. The code official (or other qualified inspector approved by the code official pursuant to Section R104.1), shall make such inspection, and the code official shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or the permit holder's agent wherein the same fails to comply with the Energy Code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official. In the case of a building that is subject to the New York City Construction Codes, such required approvals and inspections shall be subject to the provisions of Article 116 of Chapter 1 of Title 28 of the New York City Administrative Code.

R104.2 Required Inspections

AMENDMENT
This section has been amended at the state or city level.
The code official (or other qualified inspector approved by the code official pursuant to Section R104.1), upon notification, shall make the inspections set forth in Sections R104.2.1 through R104.2.5.

R104.2.1 Footing and Foundation Inspection

AMENDMENT
This section has been amended at the state or city level.
Inspections associated with footings and foundations shall verify compliance with the code as to R-value, location, thickness, depth of burial and protection of insulation as required by the 2015 IECC Residential Provisions (as amended) and approved plans and specifications.

R104.2.2 Framing and Rough-In Inspection

AMENDMENT
This section has been amended at the state or city level.
Inspections at framing and rough-in shall be made before application of interior finish and shall verify compliance with the code as to types of insulation and corresponding R-values and their correct location and proper installation; fenestration properties (U-factor and SHGC) and proper installation; and air leakage controls as required by the 2015 IECC Residential Provisions (as amended) and approved plans and specifications.

R104.2.3 Plumbing Rough-In Inspection

AMENDMENT
This section has been amended at the state or city level.
Inspections at plumbing rough-in shall verify compliance as required by the code and approved plans and specifications as to types of insulation and corresponding R-values and protection; required controls; and required heat traps.

R104.2.4 Mechanical Rough-In Inspection

AMENDMENT
This section has been amended at the state or city level.
Inspections at mechanical rough-in shall verify compliance as required by the 2015 IECC Residential Provisions (as amended) and approved plans and specifications as to installed HVAC equipment type and size, required controls, system insulation and corresponding R-value, system air leakage control, programmable thermostats, dampers, whole-house ventilation, and minimum fan efficiency.

Exception: Systems serving multiple dwelling units shall be inspected in accordance with Section C104.2.4 in the 2015 IECC Commercial Provisions (as amended).
The building shall have a final inspection and shall not be occupied until approved. The final inspection shall include verification of the installation of all required building systems, equipment and controls and their proper operation and the required number of high-efficacy lamps and fixtures.
A building shall be reinspected when determined necessary by the code official.

R104.4 Approved Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.
The code official is authorized to accept reports of third-party inspection agencies not affiliated with the design or construction of the building in question, provided such agencies are approved as to qualifications and reliability relevant to the building components and building systems they are inspecting.
It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.

R104.6 Reinspection and Testing

AMENDMENT
This section has been amended at the state or city level.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made to achieve compliance with the Energy Code. The work or installation shall then be resubmitted to the code official for inspection and testing.

R104.7 Approval

AMENDMENT
This section has been amended at the state or city level.
After the prescribed tests and inspections indicate that the work complies in all respects with the Energy Code, a notice of approval shall be issued by the code official.

R104.7.1 Revocation

AMENDMENT
This section has been amended at the state or city level.
The code official is authorized to suspend or revoke a notice of approval wherever the code official determines that the notice is issued in error or on the basis of incorrect information supplied, or where it is determined that the building or structure, or any portion thereof, or the premises, or portion thereof, is in violation of any provision of the Energy Code; any provision of the Uniform Code or New York City Construction Codes, as applicable; or any other any applicable law, statute, rule, regulation or ordinance. Any such suspension or revocation shall be in writing, signed by the code official or by his or her designated agent.

R105.1 General

AMENDMENT
This section has been amended at the state or city level.
If any portion of the 2015 IECC Residential Provisions (as amended) is held by a court of competent jurisdiction to be illegal or void, such holding shall not affect the validity of the remainder of the 2015 IECC Residential Provisions (as amended) or of any other portion of the Energy Code.

Section R106 Referenced Codes and Standard

AMENDMENT
This section has been amended at the state or city level.

R106.1 Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.

R106.1 General

AMENDMENT
This section has been amended at the state or city level.
The codes and standards referenced in the 2015 IECC Residential Provisions (as amended) shall be those listed in Chapter 6 of the 2015 IECC Residential Provisions (as amended), and such codes and standards shall be considered as part of the requirements of the 2015 IECC Residential Provisions (as amended) to the prescribed extent of each such reference and subject to the provisions and limitations set forth in Sections R106.1.1 and R106.1.2.

R106.1.1 Conflicts

AMENDMENT
This section has been amended at the state or city level.
Where conflicts occur between provisions of the 2015 IECC Residential Provisions (as amended) and referenced codes and standards listed in Chapter 6 of the 2015 IECC Residential Provisions (as amended), the provisions of the 2015 IECC Residential Provisions (as amended) shall control.

R106.1.2 Provisions in Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level.
Where the extent of the reference to a referenced code or standard listed in Chapter 6 of the 2015 IECC Residential Provisions (as amended) includes subject matter that is within the scope of the 2015 IECC Residential Provisions (as amended), the provisions of the 2015 IECC Residential Provisions (as amended), as applicable, shall take precedence over the provisions in the referenced code or standard.

R106.2 Application of References

AMENDMENT
This section has been amended at the state or city level.

R106.3 Other Laws

AMENDMENT
This section has been amended at the state or city level.

Section R107 Fees

AMENDMENT
This section has been amended at the state or city level.

Section R107 Other Laws and Regulations

AMENDMENT
This section has been amended at the state or city level.

R107.1 Fees

AMENDMENT
This section has been amended at the state or city level.

R107.1 General

AMENDMENT
This section has been amended at the state or city level.
The Energy Code shall not be deemed to nullify any federal, state or local statute, law, rule, regulation, or ordinance relating to any matter as to which the Energy Code does not provide.

R107.1.1 Other Agencies' Regulations

AMENDMENT
This section has been amended at the state or city level.
Pursuant to Section 11-103(3) of the New York State Energy Law, any other code, rule or regulation heretofore promulgated or enacted by any state agency other than the State Fire Prevention and Building Code Council, incorporating specific energy conservation requirements applicable to the construction of any building, shall be superseded by the Energy Code.

R107.1.2 More Stringent Local Energy Codes

AMENDMENT
This section has been amended at the state or city level.
Pursuant to section 11-109 of the New York State Energy Law, and subject to the provisions and requirements of that section, any municipality has the power to promulgate a local energy conservation construction code that is more stringent than the Energy Code.

R107.2 Schedule of Permit Fees

AMENDMENT
This section has been amended at the state or city level.

R107.3 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

R107.4 Related Fees

AMENDMENT
This section has been amended at the state or city level.

R107.5 Refunds

AMENDMENT
This section has been amended at the state or city level.

Section R108 Stop Work Order

AMENDMENT
This section has been amended at the state or city level.

Section R108 Interpretation of Energy Code Requirements

AMENDMENT
This section has been amended at the state or city level.
NOTE: Except as may be otherwise provided by procedures established by the Secretary of State, as currently in effect or as hereafter established or amended for time to time, the procedures for requesting and issuing written interpretations of the Energy Code shall be as set forth in this Section R108.

R108.1 Authority

AMENDMENT
This section has been amended at the state or city level.

R108.1 General

AMENDMENT
This section has been amended at the state or city level.
The Secretary of State is authorized by section 11-103(4) of the New York State Energy Law to issue written interpretations of the Energy Code upon written request of a permit applicant or the code official responsible for the administration and enforcement of the provisions of the Energy Code.

R108.2 Issuance

AMENDMENT
This section has been amended at the state or city level.

R108.2 Procedure

AMENDMENT
This section has been amended at the state or city level.
A request for an interpretation shall be signed by the building permit applicant and the code official, or by one or the other, individually, and shall include the following information in order to be considered complete:

  1. Name, address, and telephone number of the building permit applicant and the code official;
  2. A detailed description of the proposed construction, including a copy of the building permit application and plans and specifications that have been filed by the building permit applicant with the code official, as well as any other floor plans, elevations, cross-sections, details specifications, or construction documents necessary to describe adequately the proposed construction;
  3. Identification of each requirement of this code for which an interpretation is requested;
  4. A concise summary of the disagreement concerning the application of each such requirement for which an interpretation is requested; and
  5. A copy of the building permit application denial if one was issued by the code official.

R108.3 Emergencies

AMENDMENT
This section has been amended at the state or city level.

R108.3 Incomplete Information

AMENDMENT
This section has been amended at the state or city level.
If the request is incomplete or does not otherwise contain sufficient information necessary to issue an interpretation, the Secretary of State may request clarification of the information provided or additional information necessary to issue the requested interpretation.

R108.4 Failure to Comply

AMENDMENT
This section has been amended at the state or city level.

R108.4 Notification

AMENDMENT
This section has been amended at the state or city level.
Upon receipt of a complete request for an interpretation signed by only the building permit applicant or the code official, the Secretary of State shall provide written notification to the party who has not signed the request for an interpretation that such request for an interpretation has been filed with the Department of State. The party receiving such notification shall have 20 days from the date of such notification in which to provide, in writing, any comments or additional information pertaining to the request for an interpretation, provided that the Commissioner may waive this deadline when warranted by extenuating circumstances.

R108.5 Issuing Interpretation

AMENDMENT
This section has been amended at the state or city level.
The Secretary of State shall either issue the interpretation or provide notification of the intent not to issue an interpretation to the building permit applicant and the code official within 45 days of any of the following:

  1. Receipt of a complete request for an interpretation signed by both the building permit applicant and the code official,
  2. Receipt of comments when the request for an interpretation is signed by only one party, or
  3. The expiration of the 20-day comment period when the request for an interpretation is signed by only one party.

R108.6 Enforcement

AMENDMENT
This section has been amended at the state or city level.
Subsequent enforcement of the Energy Code shall be consistent with the interpretations issued by the Secretary of State pursuant to section 11-103(4) of the New York State Energy Law.

R108.7 Interpretation of More Stringent Local Energy Code Provisions

AMENDMENT
This section has been amended at the state or city level.
If a municipality has adopted a local energy code in accordance with the provisions of section 11-109 of the New York State Energy Law, and if such local energy code shall have become effective in such municipality in accordance with the provisions of section 11-109 of the New York State Energy Law, the local code official in such municipality is permitted to interpret those provisions of such local energy code that are (1) in addition to the provisions of Energy Code or (2) more stringent than the provisions of the Energy Code. However, no such interpretation shall be deemed to be an interpretation of the Energy Code by the Secretary of State pursuant to section 11-103(4) of the New York State Energy Law. In addition, if a local code official interprets a provision of a local energy code in a manner that makes such provision less stringent that the corresponding provision of the Energy Code, the corresponding provision of the Energy Code shall supersede such provision of the local energy code.

Section R109 Board of Appeals

AMENDMENT
This section has been amended at the state or city level.

Section R109 References to Chapters, Sections, Tables or Provisions

AMENDMENT
This section has been amended at the state or city level.

R109.1 General

AMENDMENT
This section has been amended at the state or city level.
Each reference in the 2015 IECC Residential Provisions (as amended) to a chapter, section or table by number only, or to a provision not specifically identified by number, without specification of the publication in which such chapter, section, table or provision is contained, shall be deemed to be a reference to such chapter, section, table or provision in the 2015 IECC Residential Provisions (as amended).

Example: Section R402.5 of the 2015 IECC Residential Provisions (as amended) includes a reference to "Section R402.1.5 or R405" and "Climate Zones 4 through 8." Such references shall be deemed to be references to Sections R402.1.5 and R405 of the 2015 IECC Residential Provisions (as amended) and to Climate Zones 4 through 8 as determined in accordance with Chapter 3 of the 2015 IECC Residential Provisions (as amended), respectively.

R109.2 Limitations on Authority

AMENDMENT
This section has been amended at the state or city level.

R109.3 Qualifications

AMENDMENT
This section has been amended at the state or city level.