ADOPTS WITH AMENDMENTS:

International Residential Code 2015 (IRC 2015)

Part I — Administrative

Part II — Definitions

Part III — Building Planning and Construction

Part IV — Energy Conservation

Part V — Mechanical

Part VI — Fuel Gas

Part VII — Plumbing

Part VIII — Electrical

Part IX — Referenced Standards

Heads up: There are no amended sections in this chapter.
User note: Code change proposals to this chapter will be considered by the IRC — Plumbing and Mechanical Code Development Committee during the 2015 (Group A) Code Development Cycle.

Section P2901 General

AMENDMENT
This section has been amended at the state or city level.

P2901.1 Potable Water Required

AMENDMENT
This section has been amended at the state or city level.
Potable water shall be supplied to plumbing fixtures and plumbing appliances except where treated rainwater, treated gray water or municipal reclaimed water is supplied to water closets, urinals and trap primers. The requirements of this section shall not be construed to require signage for water closets and urinals.

P2901.2 Identification of Nonpotable Water Systems

AMENDMENT
This section has been amended at the state or city level.
Where nonpotable water systems are installed, the piping conveying the nonpotable water shall be identified either by color marking, metal tags or tape in accordance with Sections P2901.2.1 through P2901.2.2.3.

P2901.2.1 Signage Required

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water outlets such as hose connections, open-ended pipes and faucets shall be identified with signage that reads as follows: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER. DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant water-proof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure P2901.2.1 shall appear on the required signage.


FIGURE P2901.2.1
PICTOGRAPH—DO NOT DRINK

P2901.2.2 Distribution Pipe Labeling and Marking

AMENDMENT
This section has been amended at the state or city level.
Nonpotable distribution piping shall be purple in color and shall be embossed or integrally stamped or marked with the words: "CAUTION: NONPOTABLE WATER— DO NOT DRINK" or the piping shall be installed with a purple identification tape or wrap. Pipe identification shall include the contents of the piping system and an arrow indicating the direction of flow. Hazardous piping systems shall contain information addressing the nature of the hazard. Pipe identification shall be repeated at intervals not exceeding 25 feet (7620 mm) and at each point where the piping passes through a wall, floor or roof. Lettering shall be readily observable within the room or space where the piping is located.

P2901.2.2.1 Color

AMENDMENT
This section has been amended at the state or city level.
The color of the pipe identification shall be discernable and consistent throughout the building. The color purple shall be used to identify reclaimed, rain and gray water distribution systems.

P2901.2.2.2 Lettering Size

AMENDMENT
This section has been amended at the state or city level.
The size of the background color field and lettering shall comply with Table P2901.2.2.2.

TABLE P2901.2.2.2
SIZE OF PIPE IDENTIFICATION
PIPE DIAMETER
(inches)
LENGTH OF BACKGROUND COLOR FIELD
(inches)
SIZE OF LETTERS
(inches)
3/4 to 11/4 8 0.5
11/2 to 2 8 0.75
21/2 to 6 12 1.25
8 to 10 2 2.5
over 10 32 3.5

For SI: 1 inch = 25.4 mm.

P2901.2.2.3 Identification Tape

AMENDMENT
This section has been amended at the state or city level.
Where used, identification tape shall be not less than 3 inches (76 mm) wide and have white or black lettering on a purple field stating "CAUTION: NONPOTABLE WATER—DO NOT DRINK." Identification tape shall be installed on top of nonpotable rainwater distribution pipes and fastened not greater than every 10 feet (3048 mm) to each pipe length, and run continuously the entire length of the pipe.

Section P2902 Protection of Potable Water Supply

AMENDMENT
This section has been amended at the state or city level.

P2902.1 General

AMENDMENT
This section has been amended at the state or city level.
A potable water supply system shall be designed and installed as to prevent contamination from nonpotable liquids, solids or gases being introduced into the potable water supply. Connections shall not be made to a potable water supply in a manner that could contaminate the water supply or provide a cross-connection between the supply and a source of contamination except where approved backflow prevention assemblies, backflow prevention devices or other means or methods are installed to protect the potable water supply. Cross-connections between an individual water supply and a potable public water supply shall be prohibited.

P2902.2 Plumbing Fixtures

AMENDMENT
This section has been amended at the state or city level.
The supply lines and fittings for every plumbing fixture shall be installed so as to prevent backflow. Plumbing fixture fittings shall provide backflow protection in accordance with ASME A112.18.1/CSA B125.1.

P2902.3 Backflow Protection

AMENDMENT
This section has been amended at the state or city level.
A means of protection against backflow shall be provided in accordance with Sections P2902.3.1 through P2902.3.6. Backflow prevention applications shall conform to Table P2902.3, except as specifically stated in Sections P2902.4 through P2902.5.5.

TABLE P2902.3
APPLICATION FOR BACKFLOW PREVENTERS
DEVICE DEGREE OF HAZARDa APPLICATIONb APPLICABLE
STANDARDS
Backflow Prevention Assemblies
Double check backflow prevention assembly and
double check fire protection backflow prevention
assembly
Low hazard Backpressure or backsiphonage
Sizes 3/8" — 16"
ASSE 1015, AWWA C510,
CSA B64.5, CSA B64.5.1
Double check detector fire protection backflow
prevention assemblies
Low hazard Backpressure or backsiphonage
Sizes 2" — 16"
ASSE 1048
Pressure vacuum breaker assembly High or low hazard Backsiphonage only Sizes 1/2" — 2" ASSE 1020, CSA B64.1.2
Reduced pressure principle backflow prevention
assembly and reduced pressure principle fire protection
backflow prevention assembly
High or low hazard Backpressure or backsiphonage
Sizes 3/8" — 16"
ASSE 1013, AWWA C511,
CSA B64.4, CSA B64.4.1
Reduced pressure detector fire protection backflow
prevention assemblies
High or low hazard Backsiphonage or backpressure
(Fire sprinkler systems)
ASSE 1047
Spill-resistant vacuum breaker High or low hazard Backsiphonage only Sizes 1/4" —
2"
ASSE 1056, CSA B64.1.3
Backflow Preventer Plumbing Devices
Antisiphon-type fill valves for gravity water closet
flush tanks
High hazard Backsiphonage only ASSE 1002, CSA B125.3
Backflow preventer with intermediate
atmospheric vents
Low hazard Backpressure or backsiphonage
Sizes 1/4" — 3/8"
ASSE 1012, CSA B64.3
Dual-check-valve-type backflow preventers Low hazard Backpressure or backsiphonage
Sizes 1/4" — 1"
ASSE 1024, CSA B64.6
Hose-connection backflow preventer High or low hazard Low head backpressure, rated
working pressure backpressure or
backsiphonage Sizes 1/2" — 1"
ASSE 1052, CSA B64.2.1.1
Hose-connection vacuum breaker High or low hazard Low head backpressure or
backsiphonage Sizes 1/2", 3/4", 1"
ASSE 1011, CSA B64.2, B64.2.1
Laboratory faucet backflow preventer High or low hazard Low head backpressure and
backsiphonage
ASSE 1035, CSA B64.7
Pipe-applied atmospheric-type vacuum breaker High or low hazard Backsiphonage only Sizes 1/4" — 4" ASSE 1001, CSA B64.1.1
Vacuum breaker wall hydrants, frost-resistant,
automatic-draining type
High or low hazard Low head backpressure or
backsiphonage Sizes 3/4" — 1"
ASSE 1019, CSA B64.2.2
Other Means Or Methods
Air gap High or low hazard Backsiphonage only ASME A112.1.2
Air gap fittings for use with plumbing fixtures,
appliances and appurtenances
High or low hazard Backsiphonage or backpressure ASME A112.1.3

For SI: 1 inch = 25.4 mm.
  1. Low hazard—See Pollution (Section R202). High hazard—See Contamination (Section R202).
  2. See Backpressure (Section R202). See Backpressure, Low Head (Section R202). See Backsiphonage (Section R202).

P2902.3.1 Air Gaps

AMENDMENT
This section has been amended at the state or city level.
Air gaps shall comply with ASME A112.1.2 and air gap fittings shall comply with ASME A112.1.3. An air gap shall be measured vertically from the lowest end of a water outlet to the flood level rim of the fixture or receptor into which the water outlets discharges to the floor. The required air gap shall be not less than twice the diameter of the effective opening of the outlet and not less than the values specified in Table P2902.3.1.

TABLE P2902.3.1
MINIMUM AIR GAPS
FIXTURE MINIMUM AIR GAP
Away from a walla
(inches)
Close to a wall
(inches)
Effective openings greater than 1 inch Two times the diameter of the
effective opening
Three times the diameter of the
effective opening
Lavatories and other fixtures with effective opening not
greater than 1/2 inch in diameter
1 1.5
Over-rim bath fillers and other fixtures with effective
openings not greater than 1 inch in diameter
2 3
Sink, laundry trays, gooseneck back faucets and other fixtures
with effective openings not greater than 3/4 inch in diameter
1.5 2.5

For SI: 1 inch = 25.4 mm.
  1. Applicable where walls or obstructions are spaced from the nearest inside edge of the spout opening a distance greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.

P2902.3.2 Atmospheric-Type Vacuum Breakers

AMENDMENT
This section has been amended at the state or city level.
Atmospheric-type vacuum breakers shall conform to ASSE 1001 or CSA B64.1.1. Hose-connection vacuum breakers shall conform to ASSE 1011, ASSE 1019, ASSE 1035, ASSE 1052, CSA B64.2, CSA B64.2.1, CSA B64.2.1.1, CSA B64.2.2 or CSA B64.7. Both types of vacuum breakers shall be installed with the outlet continuously open to the atmosphere. The critical level of the atmospheric vacuum breaker shall be set at not less than 6 inches (152 mm) above the highest elevation of downstream piping and the flood level rim of the fixture or device.

P2902.3.3 Backflow Preventer With Intermediate Atmospheric Vent

AMENDMENT
This section has been amended at the state or city level.
Backflow preventers with intermediate atmospheric vents shall conform to ASSE 1012 or CSA B64.3. These devices shall be permitted to be installed where subject to continuous pressure conditions. These devices shall be prohibited as a means of protection where any hazardous chemical additives are introduced downstream of the device. The relief opening shall discharge by air gap and shall be prevented from being submerged.

P2902.3.4 Pressure Vacuum Breaker Assemblies

AMENDMENT
This section has been amended at the state or city level.
Pressure vacuum breaker assemblies shall conform to ASSE 1020 or CSA B64.1.2. Spill-resistant vacuum breaker assemblies shall comply with ASSE 1056. These assemblies are designed for installation under continuous pressure conditions where the critical level is installed at the required height. The critical level of a pressure vacuum breaker and a spill-resistant vacuum breaker assembly shall be set at not less than 12 inches (304 mm) above the highest elevation of downstream piping and the flood level rim of the fixture or device. Pressure vacuum breaker assemblies shall not be installed in locations where spillage could cause damage to the structure.

P2902.3.5 Reduced Pressure Principle Backflow Prevention Assemblies

AMENDMENT
This section has been amended at the state or city level.
Reduced pressure principle backflow prevention assemblies and reduced pressure principle fire protection backflow prevention assemblies shall conform to ASSE 1013, AWWA C511, CSA B64.4 or CSA B64.4.1. Reduced pressure detector fire protection backflow prevention assemblies shall conform to ASSE 1047. These devices shall be permitted to be installed where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented from being submerged.

P2902.3.6 Double Check Backflow Prevention Assemblies

AMENDMENT
This section has been amended at the state or city level.
Double check backflow prevention assemblies shall conform to ASSE 1015, CSA B64.5, CSA B64.5.1 or AWWA C510. Double check detector fire protection backflow prevention assemblies shall conform to ASSE 1048. These assemblies shall be capable of operating under continuous pressure conditions.

P2902.3.7 Dual Check Backflow Preventer

AMENDMENT
This section has been amended at the state or city level.
Dual check backflow preventers shall conform with ASSE 1024 or CSA B64.6.

P2902.4 Protection of Potable Water Outlets

AMENDMENT
This section has been amended at the state or city level.
Potable water openings and outlets shall be protected by an air gap, a reduced pressure principle backflow prevention assembly, an atmospheric vent, an atmospheric-type vacuum breaker, a pressure-type vacuum breaker assembly or a hose connection backflow preventer.

P2902.4.1 Fill Valves

AMENDMENT
This section has been amended at the state or city level.
Flush tanks shall be equipped with an antisiphon fill valve conforming to ASSE 1002 or CSA B125.3. The critical level of the fill valve shall be located not less than 1 inch (25 mm) above the top of the flush tank overflow pipe.

P2902.4.2 Deck-Mounted and Integral Vacuum Breakers

AMENDMENT
This section has been amended at the state or city level.
Approved deck-mounted or equipment-mounted vacuum breakers and faucets with integral atmospheric vacuum breakers or spill—resistant vacuum breaker assemblies shall be installed in accordance with the manufacturer's instructions and the requirements for labeling. The critical level of the breakers and assemblies shall be located at not less than 1 inch (25 mm) above the flood level rim.

P2902.4.3 Hose Connection

AMENDMENT
This section has been amended at the state or city level.
Sillcocks, hose bibbs, wall hydrants and other openings with a hose connection shall be protected by an atmospheric-type or pressure-type vacuum breaker, a pressure vacuum breaker assembly or a permanently attached hose connection vacuum breaker.

Exceptions:
  1. This section shall not apply to water heater and boiler drain valves that are provided with hose connection threads and that are intended only for tank or vessel draining.
  2. This section shall not apply to water supply valves intended for connection of clothes washing machines where backflow prevention is otherwise provided or is integral with the machine.

P2902.5 Protection of Potable Water Connections

AMENDMENT
This section has been amended at the state or city level.
Connections to the potable water shall conform to Sections P2902.5.1 through P2902.5.5.

P2902.5.1 Connections to Boilers

AMENDMENT
This section has been amended at the state or city level.
Where chemicals will not be introduced into a boiler, the potable water supply to the boiler shall be protected from the boiler by a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CSA B64.3. Where chemicals will be introduced into a boiler, the potable water supply to the boiler shall be protected from the boiler by an air gap or a reduced pressure principle backflow prevention assembly complying with ASSE 1013, CSA B64.4 or AWWA C511.

P2902.5.2 Heat Exchangers

AMENDMENT
This section has been amended at the state or city level.
Heat exchangers using an essentially toxic transfer fluid shall be separated from the potable water by double-wall construction. An air gap open to the atmosphere shall be provided between the two walls. Single-wall construction heat exchangers shall be used only where an essentially nontoxic transfer fluid is utilized.

P2902.5.3 Lawn Irrigation Systems

AMENDMENT
This section has been amended at the state or city level.
The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric vacuum breaker, a pressure vacuum breaker assembly or a reduced pressure principle backflow prevention assembly. Valves shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow prevention assembly.

P2902.5.4 Connections to Automatic Fire Sprinkler Systems

AMENDMENT
This section has been amended at the state or city level.
The potable water supply to automatic fire sprinkler systems shall be protected against backflow by a double check backflow prevention assembly, a double check fire protection backflow prevention assembly, a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly.
Exception: Where systems are installed as a portion of the water distribution system in accordance with the requirements of this code and are not provided with a fire department connection, backflow protection for the water supply system shall not be required.

P2902.5.4.1 Additives or Nonpotable Source

AMENDMENT
This section has been amended at the state or city level.
Where systems contain chemical additives or antifreeze, or where systems are connected to a nonpotable secondary water supply, the potable water supply shall be protected against backflow by a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly. Where chemical additives or antifreeze is added to only a portion of an automatic fire sprinkler or standpipe system, the reduced pressure principle fire protection backflow preventer shall be permitted to be located so as to isolate that portion of the system.

P2902.5.5 Solar Thermal Systems

AMENDMENT
This section has been amended at the state or city level.
Where a solar thermal system heats potable water to supply a potable hot water distribution or any other type of heating system, the solar thermal system shall be in accordance with Section P2902.5.5.1, P2902.5.5.2 or P2902.5.5.3 as applicable.

P2902.5.5.1 Indirect Systems

AMENDMENT
This section has been amended at the state or city level.
Water supplies of any type shall not be connected to the solar heating loop of an indirect solar thermal hot water heating system. This requirement shall not prohibit the presence of inlets or outlets on the solar heating loop for the purposes of servicing the fluid in the solar heating loop.

P2902.5.5.2 Direct Systems for Potable Water Distribution Systems

AMENDMENT
This section has been amended at the state or city level.
Where a solar thermal system directly heats potable water for a potable water distribution system, the pipe, fittings, valves and other components that are in contact with the potable water in the system shall comply with the requirements of Chapter 29.

P2902.5.5.3 Direct Systems for Other Than Potable Water Distribution Systems

AMENDMENT
This section has been amended at the state or city level.
Where a solar thermal system directly heats water for a system other than a potable water distribution system, a potable water supply connected to such system shall be protected by a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012. Where a solar thermal system directly heats chemically treated water for a system other than a potable water distribution system, a potable water supply connected to such system shall be protected by a reduced pressure principle backflow prevention assembly complying with ASSE 1013.

P2902.6 Location of Backflow Preventers

AMENDMENT
This section has been amended at the state or city level.
Access shall be provided to backflow preventers as specified by the manufacturer's installation instructions.

P2902.6.1 Outdoor Enclosures for Backflow Prevention Devices

AMENDMENT
This section has been amended at the state or city level.
Outdoor enclosures for backflow prevention devices shall comply with ASSE 1060.

P2902.6.2 Protection of Backflow Preventers

AMENDMENT
This section has been amended at the state or city level.
Backflow preventers shall not be located in areas subject to freezing except where they can be removed by means of unions, or are protected by heat, insulation or both.

P2902.6.3 Relief Port Piping

AMENDMENT
This section has been amended at the state or city level.
The termination of the piping from the relief port or air gap fitting of the backflow preventer shall discharge to an approved indirect waste receptor or to the outdoors where it will not cause damage or create a nuisance.

Section P2903 Water Supply System

AMENDMENT
This section has been amended at the state or city level.

P2903.1 Water Supply System Design Criteria

AMENDMENT
This section has been amended at the state or city level.
The water service and water distribution systems shall be designed and pipe sizes shall be selected such that under conditions of peak demand, the capacities at the point of outlet discharge shall not be less than shown in Table P2903.1.

TABLE P2903.1
REQUIRED CAPACITIES AT POINT OF OUTLET DISCHARGE
FIXTURE SUPPLY
OUTLET SERVING
FLOW RATE (gpm) FLOW PRESSURE (psi)
Bathtub, balanced-pressure, thermostatic or combination balanced-
pressure/thermostatic mixing valve
4 20
Bidet, thermostatic mixing valve 2 20
Dishwasher 2.75 8
Laundry tray 4 8
Lavatory 0.8 8
Shower, balanced-pressure, thermostatic or combination balanced-
pressure/thermostatic mixing valve
2.5a 20
Sillcock, hose bibb 5 8
Sink 1.75 8
Water closet, flushometer tank 1.6 20
Water closet, tank, close coupled 3 20
Water closet, tank, one-piece 6 20

For SI: 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m.
  1. Where the shower mixing valve manufacturer indicates a lower flow rating for the mixing valve, the lower value shall be applied.

P2903.2 Maximum Flow and Water Consumption

AMENDMENT
This section has been amended at the state or city level.
The maximum water consumption flow rates and quantities for plumbing fixtures and fixture fittings shall be in accordance with Table P2903.2.

TABLE P2903.2
MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FIXTURE FITTINGSb
PLUMBING FIXTURE
OR FIXTURE FITTING
MAXIMUM FLOW RATE
OR QUANTITY
Lavatory faucet 2.2 gpm at 60 psi
Shower heada 2.5 gpm at 80 psi
Sink faucet 2.2 gpm at 60 psi
Water closet 1.6 gallons per flushing cycle
For SI: 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.
  1. A handheld shower spray shall be considered a shower head.
  2. Consumption tolerances shall be determined from referenced standards.

P2903.3 Minimum Pressure

AMENDMENT
This section has been amended at the state or city level.
Where the water pressure supplied by the public water main or an individual water supply system is insufficient to provide for the minimum pressures and quantities for the plumbing fixtures in the building, the pressure shall be increased by means of an elevated water tank, a hydropnuematic pressure booster system or a water pressure booster pump.

P2903.3.1 Maximum Pressure

AMENDMENT
This section has been amended at the state or city level.
The static water pressure shall be not greater than 80 psi (551 kPa). Where the main pressure exceeds 80 psi (551 kPa), an approved pressure-reducing valve conforming to ASSE 1003 or CSA B356 shall be installed on the domestic water branch main or riser at the connection to the water service pipe.

P2903.4 Thermal Expansion Control

AMENDMENT
This section has been amended at the state or city level.
A means for controlling increased pressure caused by thermal expansion shall be installed where required in accordance with Sections P2903.4.1 and P2903.4.2.

P2903.4.1 Pressure-Reducing Valve

AMENDMENT
This section has been amended at the state or city level.
For water service system sizes up to and including 2 inches (51 mm), a device for controlling pressure shall be installed where, because of thermal expansion, the pressure on the downstream side of a pressure-reducing valve exceeds the pressure-reducing valve setting.

P2903.4.2 Backflow Prevention Device or Check Valve

AMENDMENT
This section has been amended at the state or city level.
Where a backflow prevention device, check valve or other device is installed on a water supply system using storage water heating equipment such that thermal expansion causes an increase in pressure, a device for controlling pressure shall be installed.

P2903.5 Water Hammer

AMENDMENT
This section has been amended at the state or city level.
The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. Water-hammer arrestors shall be installed in accordance with the manufacturer's instructions. Water-hammer arrestors shall conform to ASSE 1010.

P2903.6 Determining Water Supply Fixture Units

AMENDMENT
This section has been amended at the state or city level.
Supply loads in the building water distribution system shall be determined by total load on the pipe being sized, in terms of water supply fixture units (w.s.f.u.), as shown in Table P2903.6, and gallon per minute (gpm) flow rates [see Table P2903.6(1)]. For fixtures not listed, choose a w.s.f.u. value of a fixture with similar flow characteristics.

TABLE P2903.6
WATER-SUPPLY FIXTURE-UNIT VALUES FOR VARIOUS PLUMBING FIXTURES AND FIXTURE GROUPS
TYPE OF FIXTURES OR GROUP OF FIXTURES WATER-SUPPLY FIXTURE-UNIT VALUE (w.s.f.u.)
Hot Cold Combined
Bathtub (with/without overhead shower head) 1.0 1.0 1.4
Clothes washer 1.0 1.0 1.4
Dishwasher 1.4 1.4
Full-bath group with bathtub (with/without shower head) or shower stall 1.5 2.7 3.6
Half-bath group (water closet and lavatory) 0.5 2.5 2.6
Hose bibb (sillcock)a 2.5 2.5
Kitchen group (dishwasher and sink with or without food-waste disposer) 1.9 1.0 2.5
Kitchen sink 1.0 1.0 1.4
Laundry group (clothes washer standpipe and laundry tub) 1.8 1.8 2.5
Laundry tub 1.0 1.0 1.4
Lavatory 0.5 0.5 0.7
Shower stall 1.0 1.0 1.4
Water closet (tank type) 2.2 2.2

For SI: 1 gallon per minute = 3.785 L/m.
  1. The fixture unit value 2.5 assumes a flow demand of 2.5 gpm, such as for an individual lawn sprinkler device. If a hose bibb or sill cock will be required to furnish a greater flow, the equivalent fixture-unit value may be obtained from this table or Table P2903.6(1).


TABLE P2903.6(1)
CONVERSIONS FROM WATER SUPPLY FIXTURE UNIT TO GALLON PER MINUTE FLOW RATES
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSHOMETER VALVES
Load Demand Load Demand
(Water supply fixture units) (Gallons per minute) (Cubic feet per
minute)
(Water supply fixture
units)
(Gallons per minute) (Cubic feet per minute)
1 3.0 0.04104
2 5.0 0.0684
3 6.5 0.86892
4 8.0 1.06944
5 9.4 1.256592 5 15.0 2.0052
6 10.7 1.430376 6 17.4 2.326032
7 11.8 1.577424 7 19.8 2.646364
8 12.8 1.711104 8 22.2 2.967696
9 13.7 1.831416 9 24.6 3.288528
10 14.6 1.951728 10 27.0 3.60936
11 15.4 2.058672 11 27.8 3.716304
12 16.0 2.13888 12 28.6 3.823248
13 16.5 2.20572 13 29.4 3.930192
14 17.0 2.27256 14 30.2 4.037136
15 17.5 2.3394 15 31.0 4.14408
16 18.0 2.90624 16 31.8 4.241024
17 18.4 2.459712 17 32.6 4.357968
18 18.8 2.513184 18 33.4 4.464912
19 19.2 2.566656 19 34.2 4.571856
20 19.6 2.620128 20 35.0 4.6788
25 21.5 2.87412 25 38.0 5.07984
30 23.3 3.114744 30 42.0 5.61356
35 24.9 3.328632 35 44.0 5.88192
40 26.3 3.515784 40 46.0 6.14928
45 27.7 3.702936 45 48.0 6.41664
50 29.1 3.890088 50 50.0 6.684

For SI: 1 gallon per minute = 3.785 L/m, 1 cubic foot per minute = 0.4719 L/s.

P2903.7 Size of Water-Service Mains, Branch Mains and Risers

AMENDMENT
This section has been amended at the state or city level.
The size of the water service pipe shall be not less than 3/4 inch (19 mm) diameter. The size of water service mains, branch mains and risers shall be determined from the water supply demand [gpm (L/m)], available water pressure [psi (kPa)] and friction loss caused by the water meter and developed length of pipe [feet (m)], including equivalent length of fittings. The size of each water distribution system shall be determined according to design methods conforming to acceptable engineering practice, such as those methods in Appendix P and shall be approved by the code official.

P2903.8 Gridded and Parallel Water Distribution Systems

AMENDMENT
This section has been amended at the state or city level.
Hot water and cold water manifolds installed with parallel-connected individual distribution lines and cold water manifolds installed with gridded distribution lines to each fixture or fixture fitting shall be designed in accordance with Sections P2903.8.1 through P2903.8.5. Gridded systems for hot water distribution systems shall be prohibited.

P2903.8.1 Sizing of Manifolds

AMENDMENT
This section has been amended at the state or city level.
Manifolds shall be sized in accordance with Table P2903.8.1. Total gallons per minute is the demand for all outlets.

TABLE P2903.8.1
MANIFOLD SIZING
PLASTIC METALLIC
Nominal Size ID
(inches)
Maximuma
gpm
Nominal Size ID
(inches)
Maximuma
gpm
3/4 17 3/4 11
1 29 1 20
11/4 46 11/4 31
11/2 66 11/2 44

For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 foot per second = 0.3048 m/s.

Note: See Table P2903.6(1) for w.s.f.u and Table 2903.6(1) for gallon-per-minute (gpm) flow rates.
  1. Based on velocity limitation: plastic-12 fps; metal-8 fps.

P2903.8.2 Minimum Size

AMENDMENT
This section has been amended at the state or city level.
Where the developed length of the distribution line is 60 feet (18 288 mm) or less, and the available pressure at the meter is not less than 40 pounds per square inch (276 kPa), the size of individual distribution lines shall be not less than 3/8 inch (10 mm) diameter. Certain fixtures such as one-piece water closets and whirlpool bathtubs shall require a larger size where specified by the manufacturer. If a water heater is fed from the end of a cold water manifold, the manifold shall be one size larger than the water heater feed.

P2903.8.3 Support and Protection

AMENDMENT
This section has been amended at the state or city level.
Plastic piping bundles shall be secured in accordance with the manufacturer's instructions and supported in accordance with Section P2605. Bundles that have a change in direction equal to or greater than 45 degrees (0.79 rad) shall be protected from chafing at the point of contact with framing members by sleeving or wrapping.

P2903.8.4 Valving

AMENDMENT
This section has been amended at the state or city level.
Fixture valves, when installed, shall be located either at the fixture or at the manifold. Valves installed at the manifold shall be labeled indicating the fixture served.

P2903.8.5 Hose Bibb Bleed

AMENDMENT
This section has been amended at the state or city level.
A readily accessible air bleed shall be installed in hose bibb supplies at the manifold or at the hose bibb exit point.

P2903.9 Valves

AMENDMENT
This section has been amended at the state or city level.
Valves shall be installed in accordance with Sections P2903.9.1 through P2903.9.5.

P2903.9.1 Service Valve

AMENDMENT
This section has been amended at the state or city level.
Each dwelling unit shall be provided with an accessible main shutoff valve near the entrance of the water service. The valve shall be of a full-open type having nominal restriction to flow, with provision for drainage such as a bleed orifice or installation of a separate drain valve. Additionally, the water service shall be valved at the curb or lot line in accordance with local requirements.

P2903.9.2 Water Heater Valve

AMENDMENT
This section has been amended at the state or city level.
A readily accessible full-open valve shall be installed in the cold-water supply pipe to each water heater at or near the water heater.

P2903.9.3 Fixture Valves and Access

AMENDMENT
This section has been amended at the state or city level.
Shutoff valves shall be required on each fixture supply pipe to each plumbing appliance and to each plumbing fixture other than bathtubs and showers. Valves serving individual plumbing fixtures, plumbing appliances, risers and branches shall be accessible.

P2903.9.4 Valve Requirements

AMENDMENT
This section has been amended at the state or city level.
Valves shall be compatible with the type of piping material installed in the system. Valves shall conform to one of the standards listed in Table P2903.9.4 or shall be approved. Valves intended to supply drinking water shall meet the requirements of NSF 61.

TABLE P2903.9.4
VALVES
MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) plastic ASME A112.4.14, ASME A112.18.1/CSA B125.1,
ASTM F 1970, CSA B125.3
Copper or copper alloy ASME A112.4.14, ASME A112.18.1/CSA B125.1,
ASME B16.34, CSA B125.3, MSS SP-67, MSS SP-80, MSS SP-110
Gray and ductile iron ASTM A126, AWWA C500, AWWA C504, AWWA C507,
MSS SP-42, MSS SP-67, MSS SP-70, MSS SP-71, MSS SP-72,
MSS SP-78
Cross-linked polyethylene (PEX) plastic ASME A112.4.14, ASME A112.18.1/CSA B125.1, CSA B125.3,
NSF 359
Polypropylene (PP) plastic ASME A112.4.14, ASTM F 2389
Polyvinyl chloride (PVC) plastic ASME A112.4.14, ASTM F 1970

P2903.9.5 Valves and Outlets Prohibited Below Grade

AMENDMENT
This section has been amended at the state or city level.
Potable water outlets and combination stop-and-waste valves shall not be installed underground or below grade. Freezeproof yard hydrants that drain the riser into the ground are considered to be stop-and-waste valves.

Exception: Installation of freezeproof yard hydrants that drain the riser into the ground shall be permitted if the potable water supply to such hydrants is protected upstream of the hydrants in accordance with Section P2902 and the hydrants are permanently identified as nonpotable outlets by approved signage that reads as follows: "Caution, Nonpotable Water. Do Not Drink."

P2903.10 Hose Bibb

AMENDMENT
This section has been amended at the state or city level.
Hose bibbs subject to freezing, including the "frostproof" type, shall be equipped with an accessible stop-and-waste-type valve inside the building so that they can be controlled and drained during cold periods.
Exception: Frostproof hose bibbs installed such that the stem extends through the building insulation into an open heated or semiconditioned space need not be separately valved (see Figure P2903.10).



FIGURE P2903.10
TYPICAL FROSTPROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE

P2903.11 Drain Water Heat Recovery Units

AMENDMENT
This section has been amended at the state or city level.
Drain water heat recovery units shall be in accordance with Section N1103.5.4.

P2904.1 General

AMENDMENT
This section has been amended at the state or city level.
The design and installation of residential fire sprinkler systems shall be in accordance with NFPA 13D or Section P2904, which shall be considered equivalent to NFPA 13D. Partial residential sprinkler systems shall be permitted to be installed only in buildings not required to be equipped with a residential sprinkler system. Section P2904 shall apply to stand-alone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire sprinkler system shall provide domestic water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system shall be separate and independent from the water distribution system. A backflow flow preventer shall not be required to separate a stand-alone sprinkler system from the water distribution system in accordance with the plumbing subcode (N.J.A.C. 5:23-3.15).
Sprinklers shall be installed to protect all areas of a dwelling unit.

Exceptions:
  1. Attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space.
  2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.
  3. Bathrooms not more than 55 square feet (5.1 m2) in area.
  4. Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.
Sprinklers shall be new listed residential sprinklers and shall be installed in accordance with the sprinkler manufacturer's instructions.
Except as provided for in Section P2904.2.2, sprinklers shall have a temperature rating of not less than 135°F (57°C) and not more than 170°F (77°C). Sprinklers shall be separated from heat sources as required by the sprinkler manufacturer's installation instructions.
Sprinklers shall have an intermediate temperature rating not less than 175°F (79°C) and not more than 225°F (107°C) where installed in the following locations:
  1. Directly under skylights, where the sprinkler is exposed to direct sunlight.
  2. In attics.
  3. In concealed spaces located directly beneath a roof.
  4. Within the distance to a heat source as specified in Table P2904.2.2.
TABLE P2904.2.2
LOCATIONS WHERE INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIRED
HEAT SOURCE RANGE OF DISTANCE FROM HEAT SOURCE WITHIN WHICH
INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIREDa, b (inches)
Fireplace, side of open or recessed fireplace 12 to 36
Fireplace, front of recessed fireplace 36 to 60
Coal and wood burning stove 12 to 42
Kitchen range top 9 to 18
Oven 9 to 18
Vent connector or chimney connector 9 to 18
Heating duct, not insulated 9 to 18
Hot water pipe, not insulated 6 to 12
Side of ceiling or wall warm air register 12 to 24
Front of wall mounted warm air register 18 to 36
Water heater, furnace or boiler 3 to 6
Luminaire up to 250 watts 3 to 6
Luminaire 250 watts up to 499 watts 6 to 12

For SI: 1 inch = 25.4 mm.
  1. Sprinklers shall not be located at distances less than the minimum table distance unless the sprinkler listing allows a lesser distance.
  2. Distances shall be measured in a straight line from the nearest edge of the heat source to the nearest edge of the sprinkler.
Piping shall be protected from freezing as required by Section P2603.5. Where sprinklers are required in areas that are subject to freezing, dry-sidewall or dry-pendent sprinklers extending from a nonfreezing area into a freezing area shall be installed.
Sprinkler coverage requirements and sprinkler obstruction requirements shall be in accordance with Sections P2904.2.4.1 and P2904.2.4.2.
The area of coverage of a single sprinkler shall not exceed 400 square feet (37 m2) and shall be based on the sprinkler listing and the sprinkler manufacturer's installation instructions.
Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional sprinklers shall not be required where the sprinkler separation from obstructions complies with either the minimum distance indicated in Figure P2904.2.4.2 or the minimum distances specified in the sprinkler manufacturer's instructions where the manufacturer's instructions permit a lesser distance.


For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE P2904.2.4.2
MINIMUM ALLOWABLE DISTANCE BETWEEN SPRINKLER AND OBSTRUCTION
Pendent sprinklers within 3 feet (915 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
Sidewall sprinklers within 5 feet (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
The solvent cementing of threaded adapter fittings shall be completed and threaded adapters for sprinklers shall be verified as being clear of excess cement prior to the installation of sprinklers on systems assembled with solvent cement.
Painting, caulking or modifying of sprinklers shall be prohibited. Sprinklers that have been painted, caulked, modified or damaged shall be replaced with new sprinklers.
Sprinkler piping shall be supported in accordance with requirements for cold water distribution piping. Sprinkler piping shall comply with the requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold water distribution piping system.

Exception: For plastic piping, it shall be permissible to follow the manufacturer's installation instructions.
Nonmetallic pipe and tubing, such as CPVC, PEX, and PE-RT shall be listed for use in residential fire sprinkler systems.
Nonmetallic pipe and tubing systems shall be protected from exposure to the living space by a layer of not less than 3/8-inch-thick (9.5 mm) gypsum wallboard, 1/2-inch-thick (13 mm) plywood, or other material having a 15-minute fire rating.

Exceptions:
  1. Pipe protection shall not be required in areas that do not require protection with sprinklers as specified in Section P2904.1.1.
  2. Pipe protection shall not be required where exposed piping is permitted by the pipe listing.
With the exception of shutoff valves for the entire water distribution system, valves shall not be installed in any location where the valve would isolate piping serving one or more sprinklers.
Piping beyond the service valve located at the beginning of the water distribution system shall not serve more than one dwelling.
A means to drain the sprinkler system shall be provided on the system side of the water distribution shutoff valve.
The flow for sizing the sprinkler piping system shall be based on the flow rating of each sprinkler in accordance with Section P2904.4.1 and the calculation in accordance with Section P2904.4.2.
The minimum required flow for each sprinkler shall be determined using the sprinkler manufacturer's published data for the specific sprinkler model based on all of the following:
  1. The area of coverage.
  2. The ceiling configuration.
  3. The temperature rating.
  4. Any additional conditions specified by the sprinkler manufacturer.
The design flow rate for the system shall be based on the following:
  1. The design flow rate for a room having only one sprinkler shall be the flow rate required for that sprinkler, as determined by Section P2904.4.1.
  2. The design flow rate for a room having two or more sprinklers a shall be determined by identifying the sprinkler in that room with the highest required flow rate, based on Section P2904.4.1, and multiplying that flow rate by 2.
  3. Where the sprinkler manufacturer specifies different criteria for ceiling configurations that are not smooth, flat and horizontal, the required flow rate for that room shall comply with the sprinkler manufacturer's instructions.
  4. The design flow rate for the sprinkler system shall be the flow required by the room with the largest flow rate, based on Items 1, 2 and 3.
  5. For the purpose of this section, it shall be permissible to reduce the design flow rate for a room by subdividing the space into two or more rooms, where each room is evaluated separately with respect to the required design flow rate. Each room shall be bounded by walls and a ceiling. Openings in walls shall have a lintel not less than 8 inches (203 mm) in depth and each lintel shall form a solid barrier between the ceiling and the top of the opening.
The water supply shall provide not less than the required design flow rate for sprinklers in accordance with Section P2904.4.2 at a pressure not less than that used to comply with Section P2904.6.
Where a dwelling unit water supply is from a tank system, a private well system or a combination of these, the available water supply shall be based on the minimum pressure control setting for the pump.
The water supply shall have the capacity to provide the required design flow rate for sprinklers for a period of time as follows:
  1. Seven minutes for dwelling units one story in height and less than 2,000 square feet (186 m2) in area.
  2. Ten minutes for dwelling units two or more stories in height or equal to or greater than 2,000 square feet (186 m2) in area.
Where a well system, a water supply tank system or a combination thereof is used, any combination of well capacity and tank storage shall be permitted to meet the capacity requirement.
The piping to sprinklers shall be sized for the flow required by Section P2904.4.2. The flow required to supply the plumbing fixtures shall not be required to be added to the sprinkler design flow.
Piping supplying sprinklers shall be sized using the prescriptive method in Section P2904.6.2 or by hydraulic calculation in accordance with NFPA 13D. The minimum pipe size from the water supply source to any sprinkler shall be 3/4 inch (19 mm) nominal. Threaded adapter fittings at the point where sprinklers are attached to the piping shall be not less than 1/2 inch (13 mm) nominal.
Pipe shall be sized by determining the available pressure to offset friction loss in piping and identifying a piping material, diameter and length using the equation in Section P2904.6.2.1 and the procedure in Section P2904.6.2.2.

TABLE P2904.6.2(1)
WATER SERVICE PRESSURE LOSS (PLsvc)a, b
FLOW RATEc
(gpm)
3/4-INCH WATER SERVICE PRESSURE LOSS
(psi)
1-INCH WATER SERVICE PRESSURE LOSS
(psi)
11/4 -INCH WATER SERVICE PRESSURE
LOSS (psi)
Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet)
40 or
less
41 to 75 76 to 100 101 to 150 40 or less 41 to 75 76 to 100 101 to 150 40 or
less
41 to 75 76 to 100 101 to 150
8 5.1 8.7 11.8 17.4 1.5 2.5 3.4 5.1 0.6 1.0 1.3 1.9
10 7.7 13.1 17.8 26.3 2.3 3.8 5.2 7.7 0.8 1.4 2.0 2.9
12 10.8 18.4 24.9 NP 3.2 5.4 7.3 10.7 1.2 2.0 2.7 4.0
14 14.4 24.5 NP NP 4.2 7.1 9.6 14.3 1.6 2.7 3.6 5.4
16 18.4 NP NP NP 5.4 9.1 12.4 18.3 2.0 3.4 4.7 6.9
18 22.9 NP NP NP 6.7 11.4 15.4 22.7 2.5 4.3 5.8 8.6
20 27.8 NP NP NP 8.1 13.8 18.7 27.6 3.1 5.2 7.0 10.4
22 NP NP NP NP 9.7 16.5 22.3 NP 3.7 6.2 8.4 12.4
24 NP NP NP NP 11.4 19.3 26.2 NP 4.3 7.3 9.9 14.6
26 NP NP NP NP 13.2 22.4 NP NP 5.0 8.5 11.4 16.9
28 NP NP NP NP 15.1 25.7 NP NP 5.7 9.7 13.1 19.4
30 NP NP NP NP 17.2 NP NP NP 6.5 11.0 14.9 22.0
32 NP NP NP NP 19.4 NP NP NP 7.3 12.4 16.8 24.8
34 NP NP NP NP 21.7 NP NP NP 8.2 13.9 18.8 NP
36 NP NP NP NP 24.1 NP NP NP 9.1 15.4 20.9 NP

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.

NP = Not permitted. Pressure loss exceeds reasonable limits.
  1. Values are applicable for underground piping materials listed in Table P2905.4 and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
  2. Values include the following length allowances for fittings: 25% length increase for actual lengths up to 100 feet and 15% length increase for actual lengths over 100 feet.
  3. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section P2904.4.2 where the water-service pipe supplies more than one dwelling.


TABLE P2904.6.2(2)
MINIMUM WATER METER PRESSURE LOSS (PLm)a
FLOW RATE
(gallons per minute, gpm)b
5/8-INCH METER PRESSURE LOSS
(pounds per square inch, psi)
3/4-INCH METER PRESSURE
LESS (pounds per square inch, psi)
1-INCH METER PRESSURE LOSS
(pounds per square inch, psi)
8 2 1 1
10 3 1 1
12 4 1 1
14 5 2 1
16 7 3 1
18 9 4 1
20 11 4 2
22 NP 5 2
24 NP 5 2
26 NP 6 2
28 NP 6 2
30 NP 7 2
32 NP 7 3
34 NP 8 3
36 NP 8 3

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.063 L/s.

NPNot permitted unless the actual water meter pressure loss is known.
  1. Table P2904.6.2(2) establishes conservative values for water meter pressure loss or installations where the water meter loss is unknown. Where the actual water meter pressure loss is known, Pm shall be the actual loss.
  2. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section P2904.4.2 where the water-service pipe supplies more than one dwelling.
TABLE P2904.6.2(3)
ELEVATION LOSS (PLe)
ELEVATION (feet) PRESSURE LOSS (psi)
5 2.2
10 4.4
15 6.5
20 8.7
25 10.9
30 13
35 15.2
40 17.4

For SI: 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.


TABLE P2904.6.2(4)
ALLOWABLE PIPE LENGTH FOR 3/4-INCH TYPE M COPPER WATER TUBING
SPRINKLER
FLOW RATEa

(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 3/4 217 289 361 434 506 578 650 723 795 867
9 3/4 174 232 291 349 407 465 523 581 639 697
10 3/4 143 191 239 287 335 383 430 478 526 574
11 3/4 120 160 200 241 281 321 361 401 441 481
12 3/4 102 137 171 205 239 273 307 341 375 410
13 3/4 88 118 147 177 206 235 265 294 324 353
14 3/4 77 103 128 154 180 205 231 257 282 308
15 3/4 68 90 113 136 158 181 203 226 248 271
16 3/4 60 80 100 120 140 160 180 200 220 241
17 3/4 54 72 90 108 125 143 161 179 197 215
18 3/4 48 64 81 97 113 129 145 161 177 193
19 3/4 44 58 73 88 102 117 131 146 160 175
20 3/4 40 53 66 80 93 106 119 133 146 159
21 3/4 36 48 61 73 85 97 109 121 133 145
22 3/4 33 44 56 67 78 89 100 111 122 133
23 3/4 31 41 51 61 72 82 92 102 113 123
24 3/4 28 38 47 57 66 76 85 95 104 114
25 3/4 26 35 44 53 61 70 79 88 97 105
26 3/4 24 33 41 49 57 65 73 82 90 98
27 3/4 23 30 38 46 53 61 69 76 84 91
28 3/4 21 28 36 43 50 57 64 71 78 85
29 3/4 20 27 33 40 47 53 60 67 73 80
30 3/4 19 25 31 38 44 50 56 63 69 75
31 3/4 18 24 29 35 41 47 53 59 65 71
32 3/4 17 22 28 33 39 44 50 56 61 67
33 3/4 16 21 26 32 37 42 47 53 58 63
34 3/4 NP 20 25 30 35 40 45 50 55 60
35 3/4 NP 19 24 28 33 38 42 47 52 57
36 3/4 NP 18 22 27 31 36 40 45 49 54
37 3/4 NP 17 21 26 30 34 38 43 47 51
38 3/4 NP 16 20 24 28 32 36 40 45 49
39 3/4 NP 15 19 23 27 31 35 39 42 46
40 3/4 NP NP 18 22 26 29 33 37 40 44

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

NPNot permitted.
  1. Flow rate from Section P2904.4.2.


TABLE P2904.6.2(5)
ALLOWABLE PIPE LENGTH FOR 1-INCH TYPE M COPPER WATER TUBING
SPRINKLER
FLOW RATEa

(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 806 1075 1343 1612 1881 2149 2418 2687 2955 3224
9 1 648 864 1080 1296 1512 1728 1945 2161 2377 2593
10 1 533 711 889 1067 1245 1422 1600 1778 1956 2134
11 1 447 586 745 894 1043 1192 1341 1491 1640 1789
12 1 381 508 634 761 888 1015 1142 1269 1396 1523
13 1 328 438 547 657 766 875 985 1094 1204 1313
14 1 286 382 477 572 668 763 859 954 1049 1145
15 1 252 336 420 504 588 672 756 840 924 1008
16 1 224 298 373 447 522 596 671 745 820 894
17 1 200 266 333 400 466 533 600 666 733 799
18 1 180 240 300 360 420 479 539 599 659 719
19 1 163 217 271 325 380 434 488 542 597 651
20 1 148 197 247 296 345 395 444 493 543 592
21 1 135 180 225 270 315 360 406 451 496 541
22 1 124 165 207 248 289 331 372 413 455 496
23 1 114 152 190 228 267 305 343 381 419 457
24 1 106 141 176 211 246 282 317 352 387 422
25 1 98 131 163 196 228 261 294 326 359 392
26 1 91 121 152 182 212 243 273 304 334 364
27 1 85 113 142 170 198 226 255 283 311 340
28 1 79 106 132 159 185 212 238 265 291 318
29 1 74 99 124 149 174 198 223 248 273 298
30 1 70 93 116 140 163 186 210 233 256 280
31 1 66 88 110 132 153 175 197 219 241 263
32 1 62 83 103 124 145 165 186 207 227 248
33 1 59 78 98 117 137 156 176 195 215 234
34 1 55 74 92 111 129 148 166 185 203 222
35 1 53 70 88 105 123 140 158 175 193 210
36 1 50 66 83 100 116 133 150 166 183 199
37 1 47 63 79 95 111 126 142 158 174 190
38 1 45 60 75 90 105 120 135 150 165 181
39 1 43 57 72 86 100 115 129 143 158 172
40 1 41 55 68 82 96 109 123 137 150 164

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.
  1. Flow rate from Section P2904.4.2.
TABLE P2904.6.2(6)
ALLOWABLE PIPE LENGTH FOR 3/4-INCH CPVC PIPE
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 3/4 348 465 581 697 813 929 1045 1161 1278 1394
9 3/4 280 374 467 560 654 747 841 934 1027 1121
10 3/4 231 307 384 461 538 615 692 769 845 922
11 3/4 193 258 322 387 451 515 580 644 709 773
12 3/4 165 219 274 329 384 439 494 549 603 658
13 3/4 142 189 237 284 331 378 426 473 520 568
14 3/4 124 165 206 247 289 330 371 412 454 495
15 3/4 109 145 182 218 254 290 327 363 399 436
16 3/4 97 129 161 193 226 258 290 322 354 387
17 3/4 86 115 144 173 202 230 259 288 317 346
18 3/4 78 104 130 155 181 207 233 259 285 311
19 3/4 70 94 117 141 164 188 211 234 258 281
20 3/4 64 85 107 128 149 171 192 213 235 256
21 3/4 58 78 97 117 136 156 175 195 214 234
22 3/4 54 71 89 107 125 143 161 179 197 214
23 3/4 49 66 82 99 115 132 148 165 181 198
24 3/4 46 61 76 91 107 122 137 152 167 183
25 3/4 42 56 71 85 99 113 127 141 155 169
26 3/4 39 52 66 79 92 105 118 131 144 157
27 3/4 37 49 61 73 86 98 110 122 135 147
28 3/4 34 46 57 69 80 92 103 114 126 137
29 3/4 32 43 54 64 75 86 96 107 118 129
30 3/4 30 40 50 60 70 81 91 101 111 121
31 3/4 28 38 47 57 66 76 85 95 104 114
32 3/4 27 36 45 54 63 71 80 89 98 107
33 3/4 25 34 42 51 59 68 76 84 93 101
34 3/4 24 32 40 48 56 64 72 80 88 96
35 3/4 23 30 38 45 53 61 68 76 83 91
36 3/4 22 29 36 43 50 57 65 72 79 86
37 3/4 20 27 34 41 48 55 61 68 75 82
38 3/4 20 26 33 39 46 52 59 65 72 78
39 3/4 19 25 31 37 43 50 56 62 68 74
40 3/4 18 24 30 35 41 47 53 59 65 71

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.
  1. Flow rate from Section P2904.4.2.
TABLE P2904.6.2(7)
ALLOWABLE PIPE LENGTH FOR 1-INCH CPVC PIPE
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 1049 1398 1748 2098 2447 2797 3146 3496 3845 4195
9 1 843 1125 1406 1687 1968 2249 2530 2811 3093 3374
10 1 694 925 1157 1388 1619 1851 2082 2314 2545 2776
11 1 582 776 970 1164 1358 1552 1746 1940 2133 2327
12 1 495 660 826 991 1156 1321 1486 1651 1816 1981
13 1 427 570 712 854 997 1139 1281 1424 1566 1709
14 1 372 497 621 745 869 993 1117 1241 1366 1490
15 1 328 437 546 656 765 874 983 1093 1202 1311
16 1 291 388 485 582 679 776 873 970 1067 1164
17 1 260 347 433 520 607 693 780 867 954 1040
18 1 234 312 390 468 546 624 702 780 858 936
19 1 212 282 353 423 494 565 635 706 776 847
20 1 193 257 321 385 449 513 578 642 706 770
21 1 176 235 293 352 410 469 528 586 645 704
22 1 161 215 269 323 377 430 484 538 592 646
23 1 149 198 248 297 347 396 446 496 545 595
24 1 137 183 229 275 321 366 412 458 504 550
25 1 127 170 212 255 297 340 382 425 467 510
26 1 118 158 197 237 276 316 355 395 434 474
27 1 111 147 184 221 258 295 332 368 405 442
28 1 103 138 172 207 241 275 310 344 379 413
29 1 97 129 161 194 226 258 290 323 355 387
30 1 91 121 152 182 212 242 273 303 333 364
31 1 86 114 143 171 200 228 257 285 314 342
32 1 81 108 134 161 188 215 242 269 296 323
33 1 76 102 127 152 178 203 229 254 280 305
34 1 72 96 120 144 168 192 216 240 265 289
35 1 68 91 114 137 160 182 205 228 251 273
36 1 65 87 108 130 151 173 195 216 238 260
37 1 62 82 103 123 144 165 185 206 226 247
38 1 59 78 98 117 137 157 176 196 215 235
39 1 56 75 93 112 131 149 168 187 205 224
40 1 53 71 89 107 125 142 160 178 196 214

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.
  1. Flow rate from Section P2904.4.2.
TABLE P2904.6.2(8)
ALLOWABLE PIPE LENGTH FOR 3/4-INCH PEX AND PE-RT TUBING
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 3/4 93 123 154 185 216 247 278 309 339 370
9 3/4 74 99 124 149 174 199 223 248 273 298
10 3/4 61 82 102 123 143 163 184 204 225 245
11 3/4 51 68 86 103 120 137 154 171 188 205
12 3/4 44 58 73 87 102 117 131 146 160 175
13 3/4 38 50 63 75 88 101 113 126 138 151
14 3/4 33 44 55 66 77 88 99 110 121 132
15 3/4 29 39 48 58 68 77 87 96 106 116
16 3/4 26 34 43 51 60 68 77 86 94 103
17 3/4 23 31 38 46 54 61 69 77 84 92
18 3/4 21 28 34 41 48 55 62 69 76 83
19 3/4 19 25 31 37 44 50 56 62 69 75
20 3/4 17 23 28 34 40 45 51 57 62 68
21 3/4 16 21 26 31 36 41 47 52 57 62
22 3/4 NP 19 24 28 33 38 43 47 52 57
23 3/4 NP 17 22 26 31 35 39 44 48 52
24 3/4 NP 16 20 24 28 32 36 40 44 49
25 3/4 NP NP 19 22 26 30 34 37 41 45
26 3/4 NP NP 17 21 24 28 31 35 38 42
27 3/4 NP NP 16 20 23 26 29 33 36 39
28 3/4 NP NP 15 18 21 24 27 30 33 36
29 3/4 NP NP NP 17 20 23 26 28 31 34
30 3/4 NP NP NP 16 19 21 24 27 29 32
31 3/4 NP NP NP 15 18 20 23 25 28 30
32 3/4 NP NP NP NP 17 19 21 24 26 28
33 3/4 NP NP NP NP 16 18 20 22 25 27
34 3/4 NP NP NP NP NP 17 19 21 23 25
35 3/4 NP NP NP NP NP 16 18 20 22 24
36 3/4 NP NP NP NP NP 15 17 19 21 23
37 3/4 NP NP NP NP NP NP 16 18 20 22
38 3/4 NP NP NP NP NP NP 16 17 19 21
39 3/4 NP NP NP NP NP NP NP 16 18 20
40 3/4 NP NP NP NP NP NP NP 16 17 19

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.

NP Not permitted.
  1. Flow rate from Section P2904.4.2.
TABLE P2904.6.2(9)
ALLOWABLE PIPE LENGTH FOR 1-INCH PEX AND PE-RT TUBING
SPRINKLER
FLOW RATEa

(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—Pt (psi)
15 20 25 30 35 40 45 50 55 60
Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 314 418 523 628 732 837 941 1046 1151 1255
9 1 252 336 421 505 589 673 757 841 925 1009
10 1 208 277 346 415 485 554 623 692 761 831
11 1 174 232 290 348 406 464 522 580 638 696
12 1 148 198 247 296 346 395 445 494 543 593
13 1 128 170 213 256 298 341 383 426 469 511
14 1 111 149 186 223 260 297 334 371 409 446
15 1 98 131 163 196 229 262 294 327 360 392
16 1 87 116 145 174 203 232 261 290 319 348
17 1 78 104 130 156 182 208 233 259 285 311
18 1 70 93 117 140 163 187 210 233 257 280
19 1 63 84 106 127 148 169 190 211 232 253
20 1 58 77 96 115 134 154 173 192 211 230
21 1 53 70 88 105 123 140 158 175 193 211
22 1 48 64 80 97 113 129 145 161 177 193
23 1 44 59 74 89 104 119 133 148 163 178
24 1 41 55 69 82 96 110 123 137 151 164
25 1 38 51 64 76 89 102 114 127 140 152
26 1 35 47 59 71 83 95 106 118 130 142
27 1 33 44 55 66 77 88 99 110 121 132
28 1 31 41 52 62 72 82 93 103 113 124
29 1 29 39 48 58 68 77 87 97 106 116
30 1 27 36 45 54 63 73 82 91 100 109
31 1 26 34 43 51 60 68 77 85 94 102
32 1 24 32 40 48 56 64 72 80 89 97
33 1 23 30 38 46 53 61 68 76 84 91
34 1 22 29 36 43 50 58 65 72 79 86
35 1 20 27 34 41 48 55 61 68 75 82
36 1 19 26 32 39 45 52 58 65 71 78
37 1 18 25 31 37 43 49 55 62 68 74
38 1 18 23 29 35 41 47 53 59 64 70
39 1 17 22 28 33 39 45 50 56 61 67
40 1 16 21 27 32 37 43 48 53 59 64

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s.
  1. Flow rate from Section P2904.4.2.
The pressure available to offset friction loss in the interior piping system (Pt) shall be determined in accordance with the Equation 29-1.



where:

Pt = Pressure used in applying Tables P2904.6.2(4) through P2904.6.2(9).
Psup = Pressure available from the water supply source.
PLsvc = Pressure loss in the water-service pipe.
PLm = Pressure loss in the water meter.
PLd = Pressure loss from devices other than the water meter.
PLe = Pressure loss associated with changes in elevation.
Psp = Maximum pressure required by a sprinkler.
Determination of the required size for water distribution piping shall be in accordance with the following procedure:

Step 1—Determine Psup

Obtain the static supply pressure that will be available from the water main from the water purveyor, or for an individual source, the available supply pressure shall be in accordance with Section P2904.5.1.

Step 2—Determine PLsvc

Use Table P2904.6.2(1) to determine the pressure loss in the water service pipe based on the selected size of the water service.

Step 3—Determine PLm

Use Table P2904.6.2(2) to determine the pressure loss from the water meter, based on the selected water meter size.

Step 4—Determine PLd

Determine the pressure loss from devices other than the water meter installed in the piping system supplying sprinklers, such as pressure-reducing valves, backflow preventers, water softeners or water filters. Device pressure losses shall be based on the device manufacturer's specifications. The flow rate used to determine pressure loss shall be the rate from Section P2904.4.2, except that 5 gpm (0.3 L/s) shall be added where the device is installed in a water-service pipe that supplies more than one dwelling. As an alternative to deducting pressure loss for a device, an automatic bypass valve shall be installed to divert flow around the device when a sprinkler activates.

Step 5—Determine PLe

Use Table P2904.6.2(3) to determine the pressure loss associated with changes in elevation. The elevation used in applying the table shall be the difference between the elevation where the water source pressure was measured and the elevation of the highest sprinkler.

Step 6—Determine Psp

Determine the maximum pressure required by any individual sprinkler based on the flow rate from Section P2904.4.1. The required pressure is provided in the sprinkler manufacturer's published data for the specific sprinkler model based on the selected flow rate.

Step 7—Calculate Pt

Using Equation 29-1, calculate the pressure available to offset friction loss in water-distribution piping between the service valve and the sprinklers.

Step 8—Determine the maximum allowable pipe length

Use Tables P2904.6.2(4) through P2904.6.2(9) to select a material and size for water distribution piping. The piping material and size shall be acceptable if the developed length of pipe between the service valve and the most remote sprinkler does not exceed the maximum allowable length specified by the applicable table. Interpolation of Pt between the tabular values shall be permitted.

The maximum allowable length of piping in Tables P2904.6.2(4) through P2904.6.2(9) incorporates an adjustment for pipe fittings. Additional consideration of friction losses associated with pipe fittings shall not be required.
An owner's manual for the fire sprinkler system shall be provided to the owner. A sign or valve tag shall be installed at the main shutoff valve to the water distribution system stating the following: "Warning, the water system for this home supplies fire sprinklers that require certain flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut off the water to the fire sprinkler system, such as water softeners, filtration systems and automatic shutoff valves, shall not be added to this system without a review of the fire sprinkler system by a fire protection specialist. Do not remove this sign."
The water distribution system shall be inspected in accordance with Sections P2904.8.1 and P2904.8.2.

P2904.8.1 Preconcealment Inspection

AMENDMENT
This section has been amended at the state or city level.
The following items shall be verified prior to the concealment of any sprinkler system piping:
  1. Sprinklers are installed in all areas as required by Section P2904.1.1.
  2. Where sprinkler water spray patterns are obstructed by construction features, luminaires or ceiling fans, additional sprinklers are installed as required by Section P2904.2.4.2.
  3. Sprinklers are the correct temperature rating and are installed at or beyond the required separation distances from heat sources as required by Sections P2904.2.1 and P2904.2.2.
  4. The pipe size equals or exceeds the size used in applying Tables P2904.6.2(4) through P2904.6.2(9) or, if the piping system was hydraulically calculated in accordance with Section P2904.6.1, the size used in the hydraulic calculation.
  5. The pipe length does not exceed the length permitted by Tables P2904.6.2(4) through P2904.6.2(9) or, if the piping system was hydraulically calculated in accordance with Section P2904.6.1, pipe lengths and fittings do not exceed those used in the hydraulic calculation.
  6. Nonmetallic piping that conveys water to sprinklers is listed for use with fire sprinklers.
  7. Piping is supported in accordance with the pipe manufacturer's and sprinkler manufacturer's installation instructions.
  8. The piping system is tested in accordance with Section P2503.7the plumbing subcode (N.J.A.C. 5:23-3.15).
The following items shall be verified upon completion of the system:
  1. Sprinkler are not painted, damaged or otherwise hindered from operation.
  2. Where a pump is required to provide water to the system, the pump starts automatically upon system water demand.
  3. Pressure-reducing valves, water softeners, water filters or other impairments to water flow that were not part of the original design have not been installed.
  4. The sign or valve tag required by Section P2904.7 is installed and the owner's manual for the system is present.

Section P2905 Heated Water Distribution Systems

AMENDMENT
This section has been amended at the state or city level.

P2905.1 Heated Water Circulation Systems and Heat Trace Systems

AMENDMENT
This section has been amended at the state or city level.
Circulation systems and heat trace systems that are installed to bring heated water in close proximity to one or more fixtures shall meet the requirements of Section N1103.5.1.

P2905.2 Demand Recirculation Systems

AMENDMENT
This section has been amended at the state or city level.
Demand recirculation water systems shall be in accordance with Section N1103.5.2.

Section P2906 Materials, Joints and Connections

AMENDMENT
This section has been amended at the state or city level.

P2906.1 Soil and Groundwater

AMENDMENT
This section has been amended at the state or city level.
The installation of water service pipe, water distribution pipe, fittings, valves, appurtenances and gaskets shall be prohibited in soil and groundwater that is contaminated with solvents, fuels, organic compounds or other detrimental materials that cause permeation, corrosion, degradation or structural failure of the water service or water distribution piping material.

P2906.1.1 Investigation Required

AMENDMENT
This section has been amended at the state or city level.
Where detrimental conditions are suspected by or brought to the attention of the building official, a chemical analysis of the soil and groundwater conditions shall be required to ascertain the acceptability of the water service material for the specific installation.

P2906.1.2 Detrimental Condition

AMENDMENT
This section has been amended at the state or city level.
Where a detrimental condition exists, approved alternate materials or alternate routing shall be required.

P2906.2 Lead Content

AMENDMENT
This section has been amended at the state or city level.
The lead content in pipe and fittings used in the water supply system shall be not greater than 8 percent.

P2906.2.1 Lead Content of Drinking Water Pipe and Fittings

AMENDMENT
This section has been amended at the state or city level.
Pipe, pipe fittings, joints, valves, faucets and fixture fittings utilized to supply water for drinking or cooking purposes shall comply with NSF 372 and shall have a weighted average lead content of 0.25 percent lead or less.

P2906.3 Polyethylene Plastic Piping Installation

AMENDMENT
This section has been amended at the state or city level.
Polyethylene pipe shall be cut square using a cutter designed for plastic pipe. Except where joined by heat fusion, pipe ends shall be chamfered to remove sharp edges. Pipe that has been kinked shall not be installed. For bends, the installed radius of pipe curvature shall be greater than 30 pipe diameters or the coil radius where bending with the coil. Coiled pipe shall not be bent beyond straight. Bends within 10 pipe diameters of any fitting or valve shall be prohibited. Joints between polyethylene plastic pipe and fittings shall comply with Section P2906.3.1 or P2906.3.2.

P2906.3.1 Heat-Fusion Joints

AMENDMENT
This section has been amended at the state or city level.
Joint surfaces shall be clean and free from moisture. Joint surfaces shall be heated to melting temperature and joined. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM D 2657.

P2906.3.2 Mechanical Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical joints shall be installed in accordance with the manufacturer's instructions.

P2906.4 Water Service Pipe

AMENDMENT
This section has been amended at the state or city level.
Water service pipe shall conform to NSF 61 and shall conform to one of the standards indicated in Table P2906.4. Water service pipe or tubing, installed underground and outside of the structure, shall have a working pressure rating of not less than 160 pounds per square inch at 73°F (1103 kPa at 23°C). Where the water pressure exceeds 160 pounds per square inch (1103 kPa), piping material shall have a rated working pressure equal to or greater than the highest available pressure. Water service piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at the entrance to the structure. Ductile iron water service piping shall be cement mortar lined in accordance with AWWA C104/A21.4.

TABLE P2906.4
WATER SERVICE PIPE
MATERIAL STANDARD
Acrylonitrile butadiene styrene (ABS) plastic pipe ASTM D 1527; ASTM D 2282
Chlorinated polyvinyl chloride (CPVC) plastic pipe ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6
Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride
(CPVC/AL/CPVC) plastic pipe
ASTM F 2855
Copper or copper-alloy pipe ASTM B 42; ASTM B 43; ASTM B 302
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447
Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe
ASTM F 1281; ASTM F 2262; CSA B137.10
Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-HDPE) pipe
ASTM F 1986
Cross-linked polyethylene (PEX) plastic pipe and tubing ASTM F 876; ASTM F 877; AWWA C904; CSA B137.5
Ductile iron water pipe AWWA C115/A21.15; AWWA C151/A21.51
Galvanized steel pipe ASTM A 53
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe ASTM F 1282; CSA B137.9
Polyethylene (PE) plastic pipe ASTM D 2104; ASTM D 2239; AWWA C901; CSA B137.1
Polyethylene (PE) plastic tubing ASTM D 2737; AWWA C901; CSA B137.1
Polyethylene of raised temperature (PE-RT) plastic tubing ASTM F 2769
Polypropylene (PP) plastic tubing ASTM F 2389; CSA B137.11
Polyvinyl chloride (PVC) plastic pipe ASTM D 1785; ASTM D 2241; ASTM D 2672; CSA B137.3
Stainless steel (Type 304/304L) pipe ASTM A 312; ASTM A 778
Stainless steel (Type 316/316L) pipe ASTM A 312; ASTM A 778

P2906.4.1 Separation of Water Service and Building Sewer

AMENDMENT
This section has been amended at the state or city level.
Trenching, pipe installation and backfilling shall be in accordance with Section P2604. Where water service piping is located in the same trench with the building sewer, such sewer shall be constructed of materials listed in Table P3002.1(2). Where the building sewer piping is not constructed of materials indicated in Table P3002.1(2), the water service pipe and the building sewer shall be horizontally separated by not less than 5 feet (1524 mm) of undisturbed or compacted earth. The required separation distance shall not apply where a water service pipe crosses a sewer pipe, provided the water service is sleeved to a point not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing. The sleeve shall be of pipe materials indicated in Table P2906.4, P3002.1(2) or P3002.2. The required separation distance shall not apply where the bottom of the water service pipe that is located within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the highest point of the top of the building sewer.

P2906.5 Water-Distribution Pipe

AMENDMENT
This section has been amended at the state or city level.
Water-distribution piping within dwelling units shall conform to NSF 61 and shall conform to one of the standards indicated in Table P2906.5. Hot-water-distribution pipe and tubing shall have a pressure rating of not less than 100 psi at 180°F (689 kPa at 82°C).

TABLE P2906.5
WATER DISTRIBUTION PIPE
MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) plastic pipe and tubing ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6
Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) plastic pipe ASTM F 2855
Copper or copper-alloy pipe ASTM B 42; ASTM B 43; ASTM B 302
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447
Cross-linked polyethylene (PEX) plastic tubing ASTM F 876; ASTM F 877; CSA B137.5
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe ASTM F 1281; ASTM F 2262; CSA B137.10
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) pipe ASTM F 1986
Galvanized steel pipe ASTM A 53
Polyethylene/aluminum/polyethylene (PE-AL-PE) composite pipe ASTM F 1282
Polyethylene of raised temperature (PE-RT) plastic tubing ASTM F 2769
Polypropylene (PP) plastic pipe or tubing ASTM F 2389; CSA B137.11
Stainless steel (Type 304/304L) pipe ASTM A 312; ASTM A 778

P2906.6 Fittings

AMENDMENT
This section has been amended at the state or city level.
Pipe fittings shall be approved for installation with the piping material installed and shall comply with the applicable standards indicated in Table P2906.6. Pipe fittings used in water supply systems shall comply with NSF 61.

TABLE P2906.6
PIPE FITTINGS
MATERIAL STANDARD
Acrylonitrile butadiene styrene (ABS) plastic ASTM D 2468
Cast-iron ASME B16.4
Chlorinated polyvinyl chloride (CPVC) plastic ASSE 1061; ASTM D 2846; ASTM F 437; ASTM F 438;
ASTM F 439; CSA B137.6
Copper or copper alloy ASSE 1061; ASME B16.15; ASME B16.18; ASME B16.22;
ASME B16.26; ASME B16.51
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-
AL-HDPE)
ASTM F 1986
Fittings for cross-linked polyethylene (PEX) plastic tubing ASSE 1061; ASTM F 877; ASTM F 1807; ASTM F 1960;
ASTM F 2080; ASTM F 2098; ASTM F 2159; ASTM F 2434;
ASTM F 2735; CSA B137.5
Gray iron and ductile iron AWWA C110/A21.10; AWWA C153/A21.53
Malleable iron ASME B16.3
Insert fittings for
Polyethylene/aluminum/polyethylene (PE-AL-PE) and cross-linked
polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX)
ASTM F 1974; ASTM F 1281; ASTM F 1282; CSA B137.9;
CSA B137.10
Polyethylene (PE) plastic ASTM D 2609; CSA B137.1
Fittings for polyethylene of raised temperature (PE-RT) plastic tubing ASTM F 1807; ASTM F2098; ASTM F 2159; ASTM F 2735;
ASTM F 2769
Polypropylene (PP) plastic pipe or tubing ASTM F 2389; CSA B137.11
Polyvinyl chloride (PVC) plastic ASTM D 2464; ASTM D 2466; ASTM D 2467; CSA B137.2;
CSA B137.3
Stainless steel (Type 304/304L) pipe ASTM A 312; ASTM A 778
Stainless steel (Type 316/316L) pipe ASTM A 312; ASTM A 778
Steel ASME B16.9; ASME B16.11; ASME B16.28

P2906.7 Flexible Water Connectors

AMENDMENT
This section has been amended at the state or city level.
Flexible water connectors, exposed to continuous pressure, shall conform to ASME A112.18.6/CSA B125.6. Access shall be provided to flexible water connectors.

P2906.8 Joint and Connection Tightness

AMENDMENT
This section has been amended at the state or city level.
Joints and connections in the plumbing system shall be gas tight and water tight for the intended use or required test pressure.

P2906.9 Plastic Pipe Joints

AMENDMENT
This section has been amended at the state or city level.
Joints in plastic piping shall be made with approved fittings by solvent cementing, heat fusion, corrosion-resistant metal clamps with insert fittings or compression connections. Flared joints for polyethylene pipe shall be permitted in accordance with Section P2906.3.

P2906.9.1 Solvent Cementing

AMENDMENT
This section has been amended at the state or city level.
Solvent-cemented joints shall comply with Sections P2906.9.1.1 through P2906.9.1.4.

P2906.9.1.1 ABS Plastic Pipe

AMENDMENT
This section has been amended at the state or city level.
Solvent cement for ABS plastic pipe conforming to ASTM D 2235 shall be applied to all joint surfaces.

P2906.9.1.2 CPVC Plastic Pipe

AMENDMENT
This section has been amended at the state or city level.
Joint surfaces shall be clean and free from moisture. Joints shall be made in accordance with the pipe, fitting or solvent cement manufacturer's installation instructions. Where such instructions require a primer to be used, an approved primer shall be applied, and a solvent cement, orange in color and conforming to ASTM F 493, shall be applied to joint surfaces. Where such instructions allow for a one-step solvent cement, yellow or red in color and conforming to ASTM F 493, to be used, the joint surfaces shall not require application of a primer before the solvent cement is applied. The joint shall be made while the cement is wet, and in accordance with ASTM D 2846 or ASTM F 493. Solvent cement joints shall be permitted above or below ground.

P2906.9.1.3 CPVC/AL/CPVC Pipe

AMENDMENT
This section has been amended at the state or city level.
Joint surfaces shall be clean and free from moisture, and an approved primer shall be applied. Solvent cement, orange in color and conforming to ASTM F 493, shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and in accordance with ASTM D 2846 or ASTM F 493. Solvent-cement joints shall be installed above or below ground.

Exception: A primer shall not be required where all of the following conditions apply:
  1. The solvent cement used is third-party certified as conforming to ASTM F 493.
  2. The solvent cement used is yellow in color.
  3. The solvent cement is used only for joining 1/2-inch (12.7 mm) through 1-inch (25 mm) diameter CPVC/AL/CPVC pipe and CPVC fittings.
  4. The CPVC fittings are manufactured in accordance with ASTM D 2846.

P2906.9.1.4 PVC Plastic Pipe

AMENDMENT
This section has been amended at the state or city level.
A purple primer that conforms to ASTM F 656 shall be applied to PVC solvent-cemented joints. Solvent cement for PVC plastic pipe conforming to ASTM D 2564 shall be applied to all joint surfaces.

P2906.9.1.5 Cross-Linked Polyethylene Plastic (PEX)

AMENDMENT
This section has been amended at the state or city level.
Joints between cross-linked polyethylene plastic tubing or fittings shall comply with Section P2906.9.1.5.1 or Section P2906.9.1.5.2.

P2906.9.1.5.1 Flared Joints

AMENDMENT
This section has been amended at the state or city level.
Flared pipe ends shall be made by a tool designed for that operation.

P2906.9.1.5.2 Mechanical Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical joints shall be installed in accordance with the manufacturer's instructions. Fittings for cross-linked polyethylene (PEX) plastic tubing shall comply with the applicable standards indicated in Table P2906.6 and shall be installed in accordance with the manufacturer's instructions. PEX tubing shall be factory marked with the applicable standards for the fittings that the PEX manufacturer specifies for use with the tubing.

P2906.10 Polypropylene (PP) Plastic

AMENDMENT
This section has been amended at the state or city level.
Joints between polypropylene plastic pipe and fittings shall comply with Section P2906.10.1 or P2906.10.2.

P2906.10.1 Heat-Fusion Joints

AMENDMENT
This section has been amended at the state or city level.
Heat fusion joints for polypropylene pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or electrofusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389.

P2906.10.2 Mechanical and Compression Sleeve Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions.

P2906.11 Cross-Linked Polyethylene/Aluminum/Cross-Linked Polyethylene

AMENDMENT
This section has been amended at the state or city level.
Joints between polyethylene/aluminum/polyethylene (PE-AL-PE) and cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe and fittings shall comply with Section P2906.11.1.

P2906.11.1 Mechanical Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical joints shall be installed in accordance with the manufacturer's instructions. Fittings for PE-AL-PE and PEX-AL-PEX as described in ASTM F 1974, ASTM F 1281, ASTM F 1282, CSA B137.9 and CSA B137.10 shall be installed in accordance with the manufacturer's instructions.

P2906.12 Stainless Steel

AMENDMENT
This section has been amended at the state or city level.
Joints between stainless steel pipe and fittings shall comply with Section P2906.12.1 or P2906.12.2.

P2906.12.1 Mechanical Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical joints shall be installed in accordance with the manufacturer's instructions.

P2906.12.2 Welded Joints

AMENDMENT
This section has been amended at the state or city level.
Joint surfaces shall be cleaned. The joint shall be welded autogenously or with an approved filler metal in accordance with ASTM A 312.

P2906.13 Threaded Pipe Joints

AMENDMENT
This section has been amended at the state or city level.
Threaded joints shall conform to American National Taper Pipe Thread specifications. Pipe ends shall be deburred and chips removed. Pipe joint compound shall be used only on male threads.

P2906.14 Soldered and Brazed Joints

AMENDMENT
This section has been amended at the state or city level.
Soldered joints in copper and copper alloy tubing shall be made with fittings approved for water piping and shall conform to ASTM B 828. Surfaces to be soldered shall be cleaned bright. Fluxes for soldering shall be in accordance with ASTM B 813. Brazing fluxes shall be in accordance with AWS A5.31M/A5.31. Solders and fluxes used in potable water-supply systems shall have a lead content of not greater than 0.2 percent.

P2906.15 Flared Joints

AMENDMENT
This section has been amended at the state or city level.
Flared joints in water tubing shall be made with approved fittings. The tubing shall be reamed and then expanded with a flaring tool.

P2906.16 Above-Ground Joints

AMENDMENT
This section has been amended at the state or city level.
Joints within the building between copper pipe or CPVC tubing, in any combination with compatible outside diameters, shall be permitted to be made with the use of approved push-in mechanical fittings of a pressure-lock design.

P2906.17 Joints Between Different Materials

AMENDMENT
This section has been amended at the state or city level.
Joints between different piping materials shall be made in accordance with Section P2906.17.1, P2906.17.2 or P2906.17.3, or with a mechanical joint of the compression or mechanical sealing type having an elastomeric seal conforming to ASTM D 1869 or ASTM F 477. Joints shall be installed in accordance with the manufacturer's instructions.

P2906.17.1 Copper or Copper-Alloy Tubing to Galvanized Steel Pipe

AMENDMENT
This section has been amended at the state or city level.
Joints between copper or copper-alloy tubing and galvanized steel pipe shall be made with a copper alloy fitting or dielectric fitting. The copper tubing shall be joined to the fitting in an approved manner, and the fitting shall be screwed to the threaded pipe.

P2906.17.2 Plastic Pipe or Tubing to Other Piping Material

AMENDMENT
This section has been amended at the state or city level.
Joints between different types of plastic pipe or between plastic pipe and other piping material shall be made with an approved adapter fitting.

P2906.17.3 Stainless Steel

AMENDMENT
This section has been amended at the state or city level.
Joints between stainless steel and different piping materials shall be made with a mechanical joint of the compression or mechanical-sealing type or a dielectric fitting.

P2906.18 Press-Connect Joints

AMENDMENT
This section has been amended at the state or city level.
Press-connect joints shall conform to one of the standards indicated in Table P2906.6. Press-type mechanical joints in copper tubing shall be made in accordance with the manufacturer's instructions. Cut tube ends shall be reamed to the full inside diameter of the tube end. Joint surfaces shall be cleaned. The tube shall be fully inserted into the press connect fitting. Press-connect joints shall be pressed with a tool certified by the manufacturer.

P2906.19 Polyethylene of Raised Temperature Plastic

AMENDMENT
This section has been amended at the state or city level.
Joints between polyethylene of raised temperature plastic tubing and fittings shall be in accordance with Section P2906.19.1.

P2906.19.1 Mechanical Joints

AMENDMENT
This section has been amended at the state or city level.
Mechanical joints shall be installed in accordance with the manufacturer's instructions. Fittings for polyethylene of raised temperature plastic tubing shall comply with the applicable standards listed in Table P2906.6 and shall be installed in accordance with the manufacturer's instructions. Polyethylene of raised temperature plastic tubing shall be factory marked with the applicable standards for the fittings that the manufacturer of the tubing specifies for use with the tubing.

Section P2907 Changes in Direction

AMENDMENT
This section has been amended at the state or city level.

P2907.1 Bends

AMENDMENT
This section has been amended at the state or city level.
Changes in direction in copper tubing shall be permitted to be made with bends having a radius of not less than four diameters of the tube, provided that such bends are made by use of forming equipment that does not deform or create loss in cross-sectional area of the tube.

Section P2908 Support

AMENDMENT
This section has been amended at the state or city level.

P2908.1 General

AMENDMENT
This section has been amended at the state or city level.
Pipe and tubing support shall conform to Section P2605.

Section P2909 Drinking Water Treatment Units

AMENDMENT
This section has been amended at the state or city level.

P2909.1 Design

AMENDMENT
This section has been amended at the state or city level.
Drinking water treatment units shall meet the requirements of NSF42, NSF 44, NSF 53, NSF 60 or CSA B483.1.

P2909.2 Reverse Osmosis Drinking Water Treatment Units

AMENDMENT
This section has been amended at the state or city level.
Point-of-use reverse osmosis drinking water treatment units, designed for residential use, shall meet the requirements of NSF 58 or CSA B483.1. Waste or discharge from reverse osmosis drinking water treatment units shall enter the drainage system through an air gap or an air gap device that meets the requirements of NSF 58.

P2909.3 Connection Tubing

AMENDMENT
This section has been amended at the state or city level.
The tubing to and from drinking water treatment units shall be of a size and material as recommended by the manufacturer. The tubing shall comply with NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61.

Section P2910 Nonpotable Water Systems

AMENDMENT
This section has been amended at the state or city level.

P2910.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall govern the materials, design, construction and installation of systems for the collection, storage, treatment and distribution of nonpotable water. The use and application of nonpotable water shall comply with laws, rules and ordinances applicable in the jurisdiction.

P2910.2 Water Quality

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water for each end use application shall meet the minimum water quality requirements as established for the intended application by the laws, rules and ordinances applicable in the jurisdiction. Where nonpotable water from different sources is combined in a system, the system shall comply with the most stringent requirements of this code applicable to such sources.

P2910.2.1 Residual Disinfectants

AMENDMENT
This section has been amended at the state or city level.
Where chlorine is used for disinfection, the nonpotable water shall contain not more than 4 ppm (4 mg/L) of chloramines or free chlorine. Where ozone is used for disinfection, the nonpotable water shall not contain gas bubbles having elevated levels of ozone at the point of use.

Exception: Reclaimed water sources shall not be required to comply with the requirements of this section.

P2910.2.2 Filtration Required

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water utilized for water closet and urinal flushing applications shall be filtered by a 100 micron or finer filter.

Exception: Reclaimed water sources shall not be required to comply with the requirements of this section.

P2910.3 Signage Required

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water outlets such as hose connections, open-ended pipes and faucets shall be identified at the point of use for each outlet with signage that reads as follows: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER. DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant, waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and in colors contrasting the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure P2910.3 shall appear on the signage required by this section.


FIGURE P2910.3
PICTOGRAPH—DO NOT DRINK

P2910.4 Permits

AMENDMENT
This section has been amended at the state or city level.
Permits shall be required for the construction, installation, alteration and repair of nonpotable water systems. Construction documents, engineering calculations, diagrams and other such data pertaining to the nonpotable water system shall be submitted with each permit application.

P2910.5 Potable Water Connections

AMENDMENT
This section has been amended at the state or city level.
Where a potable system is connected to a nonpotable water system, the potable water supply shall be protected against backflow in accordance with Section P2902.

P2910.6 Approved Components and Materials

AMENDMENT
This section has been amended at the state or city level.
Piping, plumbing components and materials used in collection and conveyance systems shall be manufactured of material approved for the intended application and compatible with any disinfection and treatment systems used.

P2910.7 Insect and Vermin Control

AMENDMENT
This section has been amended at the state or city level.
The system shall be protected to prevent the entrance of insects and vermin into storage tanks and piping systems. Screen materials shall be compatible with contacting system components and shall not accelerate the corrosion of system components.

P2910.8 Freeze Protection

AMENDMENT
This section has been amended at the state or city level.
Where sustained freezing temperatures occur, provisions shall be made to keep storage tanks and the related piping from freezing.

P2910.9 Nonpotable Water Storage Tanks

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water storage tanks shall comply with Sections P2910.9.1 through P2910.9.11.

P2910.9.1 Sizing

AMENDMENT
This section has been amended at the state or city level.
The holding capacity of the storage tank shall be sized in accordance with the anticipated demand.

P2910.9.2 Location

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be installed above or below grade. Above-grade storage tanks shall be protected from direct sunlight and shall be constructed using opaque, UV-resistant materials such as, but not limited to, heavily tinted plastic, lined metal, concrete and wood; or painted to prevent algae growth; or shall have specially constructed sun barriers including, but not limited to, installation in garages, crawlspaces or sheds. Storage tanks and their manholes shall not be located directly under any soil piping, waste piping or any source of contamination.

P2910.9.3 Materials

AMENDMENT
This section has been amended at the state or city level.
Where collected on site, water shall be collected in an approved tank constructed of durable, nonabsorbent and corrosion-resistant materials. The storage tank shall be constructed of materials compatible with any disinfection systems used to treat water upstream of the tank and with any systems used to maintain water quality within the tank. Wooden storage tanks that are not equipped with a makeup water source shall be provided with a flexible liner.

P2910.9.4 Foundation and Supports

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be supported on a firm base capable of withstanding the weight of the storage tank when filled to capacity. Storage tanks shall be supported in accordance with this code.

P2910.9.4.1 Ballast

AMENDMENT
This section has been amended at the state or city level.
Where the soil can become saturated, an underground storage tank shall be ballasted or otherwise secured to prevent the tank from floating out of the ground when empty. The combined weight of the tank and hold-down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the storage tank weight when full, consistent with the bearing capability of adjacent soil.

P2910.9.4.2 Structural Support

AMENDMENT
This section has been amended at the state or city level.
Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage and with minimal deformation when empty or filled with water.

P2910.9.5 Makeup Water

AMENDMENT
This section has been amended at the state or city level.
Where an uninterrupted nonpotable water supply is required for the intended application, potable or reclaimed water shall be provided as a source of makeup water for the storage tank. The makeup water supply shall be protected against backflow by means of an air gap not less than 4 inches (102 mm) above the overflow or an approved backflow device in accordance with Section P2902. A full-open valve located on the makeup water supply line to the storage tank shall be provided. Inlets to the storage tank shall be controlled by fill valves or other automatic supply valves installed to prevent the tank from overflowing and to prevent the water level from dropping below a predetermined point. Where makeup water is provided, the water level shall be prohibited from dropping below the source water inlet or the intake of any attached pump.

P2910.9.5.1 Inlet Control Valve Alarm

AMENDMENT
This section has been amended at the state or city level.
Makeup water systems shall be fitted with a warning mechanism that alerts the user to a failure of the inlet control valve to close correctly. The alarm shall activate before the water within the storage tank begins to discharge into the overflow system.

P2910.9.6 Overflow

AMENDMENT
This section has been amended at the state or city level.
The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table P2910.9.6. The overflow outlet shall discharge at a point not less than 6 inches (152 mm) above the roof or roof drain; floor or floor drain; or over an open water-supplied fixture. The overflow outlet shall be covered with a corrosion-resistant screen of not less than 16 by 20 mesh per inch (630 by 787 mesh per m) and by 1/4-inch (6.4 mm) hardware cloth or shall terminate in a horizontal angle seat check valve. Drainage from overflow pipes shall be directed to prevent freezing on roof walks. The overflow drain shall not be equipped with a shutoff valve. Not less than one cleanout shall be provided on each overflow pipe in accordance with Section P3005.2.

TABLE P2910.9.6
SIZE OF DRAIN PIPES FOR WATER TANKS
TANK CAPACITY
(gallons)
DRAIN PIPE
(inches)
Up to 750 1
751 to 1500 11/2
1501 to 3000 2
3001 to 5000 21/2
5001 to 7500 3
Over 7500 4

For SI: 1 gallon = 3.875 liters, 1 inch = 25.4 mm.

P2910.9.7 Access

AMENDMENT
This section has been amended at the state or city level.
Not less than one access opening shall be provided to allow inspection and cleaning of the tank interior. Access openings shall have an approved locking device or other approved method of securing access. Below-grade storage tanks, located outside of the building, shall be provided with a manhole either not less than 24 inches (610 mm) square or with an inside diameter not less than 24 inches (610 mm). Manholes shall extend not less than 4 inches (102 mm) above ground or shall be designed to prevent water infiltration. Finished grade shall be sloped away from the manhole to divert surface water. Manhole covers shall be secured to prevent unauthorized access. Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter and shall be not less than 4 inches (102 mm) above the finished grade level. The service port shall be secured to prevent unauthorized access.

Exception: Storage tanks under 800 gallons (3028 L) in volume installed below grade shall not be required to be equipped with a manhole, but shall have a service port not less than 8 inches (203 mm) in diameter.

P2910.9.8 Venting

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be provided with a vent sized in accordance with Chapter 31 and based on the aggregate diameter of all tank influent pipes. The reservoir vent shall not be connected to sanitary drainage system vents. Vents shall be protected from contamination by means of an approved cap or a U-bend installed with the opening directed downward. Vent outlets shall extend not less than 4 inches (102 mm) above grade, or as necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the entrance of vermin and insects in accordance with the requirements of Section P2902.7.

P2910.9.9 Drain

AMENDMENT
This section has been amended at the state or city level.
A drain shall be located at the lowest point of the storage tank. The tank drain pipe shall discharge as required for overflow pipes and shall not be smaller in size than specified in Table P2910.9.6. Not less than one cleanout shall be provided on each drain pipe in accordance with Section P3005.2.

P2910.10 Marking and Signage

AMENDMENT
This section has been amended at the state or city level.
Each nonpotable water storage tank shall be labeled with its rated capacity. The contents of storage tanks shall be identified with the words "CAUTION: NONPOTABLE WATER—DO NOT DRINK." Where an opening is provided that could allow the entry of personnel, the opening shall be marked with the words, "DANGER—CONFINED SPACE." Markings shall be indelibly printed on the tank, or on a tag or sign constructed of corrosion-resistant waterproof material that is mounted on the tank. The letters of the words shall be not less than 0.5 inches (12.7 mm) in height and shall be of a color in contrast with the background on which they are applied.

P2910.11 Storage Tank Tests

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be tested in accordance with the following:
  1. Storage tanks shall be filled with water to the overflow line prior to and during inspection. Seams and joints shall be left exposed and the tank shall remain water tight without leakage for a period of 24 hours.
  2. After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper drainage of the overflow system and leaks do not exist.
  3. Following a successful test of the overflow, the water level in the tank shall be reduced to a level that is 2 inches (51 mm) below the makeup water trigger point by using the tank drain. The tank drain shall be observed for proper operation. The makeup water system shall be observed for proper operation, and successful automatic shutoff of the system at the refill threshold shall be verified. Water shall not be drained from the overflow at any time during the refill test.

P2910.12 System Abandonment

AMENDMENT
This section has been amended at the state or city level.
If the owner of an on-site nonpotable water reuse system or rainwater collection and conveyance system elects to cease use of or fails to properly maintain such system, the system shall be abandoned and shall comply with the following:
  1. System piping connecting to a utility-provided water system shall be removed or disabled.
  2. The distribution piping system shall be replaced with an approved potable water supply piping system. Where an existing potable water pipe system is already in place, the fixtures shall be connected to the existing system.
  3. The storage tank shall be secured from accidental access by sealing or locking tank inlets and access points, or filled with sand or equivalent.

P2910.13 Separation Requirements for Nonpotable Water Piping

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water collection and distribution piping and reclaimed water piping shall be separated from the building sewer and potable water piping underground by 5 feet (1524 mm) of undisturbed or compacted earth. Nonpotable water collection and distribution piping shall not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits. Buried nonpotable water piping shall comply with the requirements of Section P2604.

Exceptions:
  1. The required separation distance shall not apply where the bottom of the nonpotable water pipe within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conforms to Table P3002.2.
  2. The required separation distance shall not apply where the bottom of the potable water service pipe within 5 feet (1524 mm) of the nonpotable water pipe is not less than 12 inches (305 mm) above the top of the highest point of the nonpotable water pipe and the pipe materials comply with the requirements of Table P2906.5.
  3. The required separation distance shall not apply where a nonpotable water pipe is located in the same trench with a building sewer that is constructed of materials that comply with the requirements of Table P3002.2.
  4. The required separation distance shall not apply where a nonpotable water pipe crosses a sewer pipe provided that the nonpotable water pipe is sleeved to not less than 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing, with pipe materials that comply with Table P3002.2.
  5. The required separation distance shall not apply where a potable water service pipe crosses a nonpotable water pipe, provided that the potable water service pipe is sleeved for a distance of not less than 5 feet (1524 mm) horizontally from the centerline of the nonpotable pipe on both sides of such crossing, with pipe materials that comply with Table P3002.2.
  6. The required separation distance shall not apply to irrigation piping located outside of a building and downstream of the backflow preventer where nonpotable water is used for outdoor applications.

P2910.14 Outdoor Outlet Access

AMENDMENT
This section has been amended at the state or city level.
Sillcocks, hose bibs, wall hydrants, yard hydrants and other outdoor outlets supplied by nonpotable water shall be located in a locked vault or shall be operable only by means of a removable key.

Section P2911 On-Site Nonpotable Water Reuse Systems

AMENDMENT
This section has been amended at the state or city level.

P2911.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall govern the construction, installation, alteration and repair of on-site nonpotable water reuse systems for the collection, storage, treatment and distribution of on-site sources of nonpotable water as permitted by the jurisdiction.

P2911.2 Sources

AMENDMENT
This section has been amended at the state or city level.
On-site nonpotable water reuse systems shall collect waste discharge only from the following sources: bathtubs, showers, lavatories, clothes washers and laundry trays. Water from other approved nonpotable sources including swimming pool backwash operations, air conditioner condensate, rainwater, foundation drain water, fluid cooler discharge water and fire pump test water shall be permitted to be collected for reuse by on-site nonpotable water reuse systems, as approved by the building official and as appropriate for the intended application.

P2911.2.1 Prohibited Sources

AMENDMENT
This section has been amended at the state or city level.
Reverse osmosis system reject water, water softener backwash water, kitchen sink wastewater, dishwasher wastewater and wastewater containing urine or fecal matter shall not be collected for reuse within an on- site nonpotable water reuse system.

P2911.3 Traps

AMENDMENT
This section has been amended at the state or city level.
Traps serving fixtures and devices discharging waste water to on-site nonpotable water reuse systems shall comply with the Section P3201.2.

P2911.4 Collection Pipe

AMENDMENT
This section has been amended at the state or city level.
On-site nonpotable water reuse systems shall utilize drainage piping approved for use within plumbing drainage systems to collect and convey untreated water for reuse. Vent piping approved for use within plumbing venting systems shall be utilized for vents within the gray-water system. Collection and vent piping materials shall comply with Section P3002.

P2911.4.1 Installation

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying untreated water for reuse shall be installed in accordance with Section P3005.

P2911.4.2 Joints

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying untreated water for reuse shall utilize joints approved for use with the distribution piping and appropriate for the intended applications as specified in Section P3002.

P2911.4.3 Size

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying untreated water for reuse shall be sized in accordance with drainage sizing requirements specified in Section P3005.4.

P2911.4.4 Marking

AMENDMENT
This section has been amended at the state or city level.
Additional marking of collection piping conveying untreated water for reuse shall not be required beyond that required for sanitary drainage, waste and vent piping by the Chapter 30.

P2911.5 Filtration

AMENDMENT
This section has been amended at the state or city level.
Untreated water collected for reuse shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves immediately upstream and downstream to allow for isolation during maintenance.

P2911.6 Disinfection

AMENDMENT
This section has been amended at the state or city level.
Nonpotable water collected on site for reuse shall be disinfected, treated or both to provide the quality of water needed for the intended end-use application. Where the intended end-use application does not have requirements for the quality of water, disinfection and treatment of water collected on site for reuse shall not be required. Nonpotable water collected on site containing untreated gray water shall be retained in collection reservoirs for not more than 24 hours.

P2911.6.1 Gray Water Used for Fixture Flushing

AMENDMENT
This section has been amended at the state or city level.
Gray water used for flushing water closets and urinals shall be disinfected and treated by an on-site water reuse treatment system complying with NSF 350.

P2911.7 Storage Tanks

AMENDMENT
This section has been amended at the state or city level.
Storage tanks utilized in on-site nonpotable water reuse systems shall comply with Section P2910.9 and Sections P2911.7.1 through P2911.7.3.

P2911.7.1 Location

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table P2911.7.1.

TABLE P2911.7.1
LOCATION OF NONPOTABLE WATER REUSE STORAGE TANKS
ELEMENT MINIMUM HORIZONTAL DISTANCE
FROM STORAGE TANK
(feet)
Critical root zone (CRZ) of
protected trees
2
Lot line adjoining private lots 5
Seepage pits 5
Septic tanks 5
Water wells 50
Streams and lakes 50
Water service 5
Public water main 10

For SI: 1 foot = 304.8 mm

P2911.7.2 Inlets

AMENDMENT
This section has been amended at the state or city level.
Storage tank inlets shall be designed to introduce water into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.

P2911.7.3 Outlets

AMENDMENT
This section has been amended at the state or city level.
Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank, and shall not skim water from the surface.

P2911.8 Valves

AMENDMENT
This section has been amended at the state or city level.
Valves shall be supplied on on-site nonpotable water reuse systems in accordance with Sections P2911.8.1 and P2911.8.2.

P2911.8.1 Bypass Valve

AMENDMENT
This section has been amended at the state or city level.
One three-way diverter valve certified to NSF 50 or other approved device shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated on-site reuse sources to the sanitary sewer to allow servicing and inspection of the system. Bypass valves shall be installed downstream of fixture traps and vent connections. Bypass valves shall be labeled to indicate the direction of flow, connection and storage tank or drainfield connection. Bypass valves shall be installed in accessible locations. Two shutoff valves shall not be installed to serve as a bypass valve.

P2911.8.2 Backwater Valve

AMENDMENT
This section has been amended at the state or city level.
Backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section P3008.

P2911.9 Pumping and Control System

AMENDMENT
This section has been amended at the state or city level.
Mechanical equipment including pumps, valves and filters shall be accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with Section P2903.

P2911.10 Water-Pressure-Reducing Valve or Regulator

AMENDMENT
This section has been amended at the state or city level.
Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the nonpotable water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1.

P2911.11 Distribution Pipe

AMENDMENT
This section has been amended at the state or city level.
Distribution piping utilized in on-site nonpotable water reuse systems shall comply with Sections P2911.11.1 through P2911.11.3.

Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

P2911.11.1 Materials, Joints and Connections

AMENDMENT
This section has been amended at the state or city level.
Distribution piping shall conform to the standards and requirements specified in Section P2906 for nonpotable water.

P2911.11.2 Design

AMENDMENT
This section has been amended at the state or city level.
On-site nonpotable water reuse distribution piping systems shall be designed and sized in accordance with Section P2903 for the intended application.

P2911.11.3 Marking

AMENDMENT
This section has been amended at the state or city level.
On-site nonpotable water distribution piping labeling and marking shall comply with Section P2901.2.

P2911.12 Tests and Inspections

AMENDMENT
This section has been amended at the state or city level.
Tests and inspections shall be performed in accordance with Sections P2911.12.1 through P2911.12.6.

P2911.12.1 Collection Pipe and Vent Test

AMENDMENT
This section has been amended at the state or city level.
Drain, waste and vent piping used for on-site water reuse systems shall be tested in accordance with Section P2503.

P2911.12.2 Storage Tank Test

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be tested in accordance with Section P2910.11.

P2911.12.3 Water Supply System Test

AMENDMENT
This section has been amended at the state or city level.
The testing of makeup water supply piping and distribution piping shall be conducted in accordance with Section P2503.7.

P2911.12.4 Inspection and Testing of Backflow Prevention Assemblies

AMENDMENT
This section has been amended at the state or city level.
The testing of backflow preventers and backwater valves shall be conducted in accordance with Section P2503.8.

P2911.12.5 Inspection of Vermin and Insect Protection

AMENDMENT
This section has been amended at the state or city level.
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section P2910.7.

P2911.12.6 Water Quality Test

AMENDMENT
This section has been amended at the state or city level.
The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.

P2911.13 Operation and Maintenance Manuals

AMENDMENT
This section has been amended at the state or city level.
Operation and maintenance materials shall be supplied with nonpotable on-site water reuse systems in accordance with Sections P2911.13.1 through P2911.13.4.

P2911.13.1 Manual

AMENDMENT
This section has been amended at the state or city level.
A detailed operations and maintenance manual shall be supplied in hard-copy form for each system.

P2911.13.2 Schematics

AMENDMENT
This section has been amended at the state or city level.
The manual shall include a detailed system schematic, the location of system components and a list of system components that includes the manufacturers and model numbers of the components.

P2911.13.3 Maintenance Procedures

AMENDMENT
This section has been amended at the state or city level.
The manual shall provide a schedule and procedures for system components requiring periodic maintenance. Consumable parts including filters shall be noted along with part numbers.

P2911.13.4 Operations Procedures

AMENDMENT
This section has been amended at the state or city level.
The manual shall include system startup and shutdown procedures. The manual shall include detailed operating procedures for the system.

Section P2912 Nonpotable Rainwater Collection and Distribution Systems

AMENDMENT
This section has been amended at the state or city level.

P2912.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall govern the construction, installation, alteration, and repair of rainwater collection and conveyance systems for the collection, storage, treatment and distribution of rainwater for nonpotable applications, as permitted by the jurisdiction.

P2912.2 Collection Surface

AMENDMENT
This section has been amended at the state or city level.
Rainwater shall be collected only from above-ground impervious roofing surfaces constructed from approved materials. Collection of water from vehicular parking or pedestrian walkway surfaces shall be prohibited except where the water is used exclusively for landscape irrigation. Overflow and bleed-off pipes from roof-mounted appliances including, but not limited to, evaporative coolers, water heaters and solar water heaters shall not discharge onto rainwater collection surfaces.

P2912.3 Debris Excluders

AMENDMENT
This section has been amended at the state or city level.
Downspouts and leaders shall be connected to a roof washer and shall be equipped with a debris excluder or equivalent device to prevent the contamination of collected rainwater with leaves, sticks, pine needles and similar material. Debris excluders and equivalent devices shall be self-cleaning.

P2912.4 Roof Washer

AMENDMENT
This section has been amended at the state or city level.
An amount of rainwater shall be diverted at the beginning of each rain event, and not allowed to enter the storage tank, to wash accumulated debris from the collection surface. The amount of rainfall to be diverted shall be field adjustable as necessary to minimize storage tank water contamination. The roof washer shall not rely on manually operated valves or devices, and shall operate automatically. Diverted rainwater shall not be drained to the roof surface, and shall be discharged in a manner consistent with the storm water runoff requirements of the jurisdiction. Roof washers shall be accessible for maintenance and service.

P2912.5 Roof Gutters and Downspouts

AMENDMENT
This section has been amended at the state or city level.
Gutters and downspouts shall be constructed of materials that are compatible with the collection surface and the rainwater quality for the desired end use. Joints shall be watertight.

P2912.5.1 Slope

AMENDMENT
This section has been amended at the state or city level.
Roof gutters, leaders and rainwater collection piping shall slope continuously toward collection inlets and shall be free of leaks. Gutters and downspouts shall have a slope of not less than 1/8 inch per foot (10.4 mm/m) along their entire length. Gutters and downspouts shall be installed so that water does not pool at any point.

P2912.5.2 Cleanouts

AMENDMENT
This section has been amended at the state or city level.
Cleanouts shall be provided in the water conveyance system to allow access to filters, flushes, pipes and downspouts.

P2912.6 Drainage

AMENDMENT
This section has been amended at the state or city level.
Water drained from the roof washer or debris excluder shall not be drained to the sanitary sewer. Such water shall be diverted from the storage tank and shall discharge to a location that will not cause erosion or damage to property. Roof washers and debris excluders shall be provided with an automatic means of self-draining between rain events and shall not drain onto roof surfaces.

P2912.7 Collection Pipe

AMENDMENT
This section has been amended at the state or city level.
Rainwater collection and conveyance systems shall utilize drainage piping approved for use within plumbing drainage systems to collect and convey captured rainwater. Vent piping approved for use within plumbing venting systems shall be utilized for vents within the rainwater system. Collection and vent piping materials shall comply with Section P3002.

P2912.7.1 Installation

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying captured rainwater shall be installed in accordance with Section P3005.3.

P2912.7.2 Joints

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying captured rainwater shall utilize joints approved for use with the distribution piping and appropriate for the intended applications as specified in Section P3003.

P2912.7.3 Size

AMENDMENT
This section has been amended at the state or city level.
Collection piping conveying captured rainwater shall be sized in accordance with drainage-sizing requirements specified in Section P3005.4.

P2912.7.4 Marking

AMENDMENT
This section has been amended at the state or city level.
Additional marking of collection piping conveying captured rainwater for reuse shall not be required beyond that required for sanitary drainage, waste, and vent piping by Chapter 30.

P2912.8 Filtration

AMENDMENT
This section has been amended at the state or city level.
Collected rainwater shall be filtered as required for the intended end use. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves installed immediately upstream and downstream to allow for isolation during maintenance.

P2912.9 Disinfection

AMENDMENT
This section has been amended at the state or city level.
Where the intended application for rainwater requires disinfection or other treatment or both, it shall be disinfected as needed to ensure that the required water quality is delivered at the point of use.

P2912.10 Storage Tanks

AMENDMENT
This section has been amended at the state or city level.
Storage tanks utilized in nonpotable rainwater collection and conveyance systems shall comply with Section P2910.9 and Sections P2912.10.1 through P2912.10.3.

P2912.10.1 Location

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table P2912.10.1.

TABLE P2912.10.1
LOCATION OF RAINWATER STORAGE TANKS
ELEMENT MINIMUM HORIZONTAL DISTANCE
FROM STORAGE TANK
(feet)
Critical root zone (CRZ) of protected trees 2
Lot line adjoining private lots 5
Seepage pits 5
Septic tanks 5

For SI: 1 foot = 304.8 mm

P2912.10.2 Inlets

AMENDMENT
This section has been amended at the state or city level.
Storage tank inlets shall be designed to introduce collected rainwater into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.

P2912.10.3 Outlets

AMENDMENT
This section has been amended at the state or city level.
Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.

P2912.11 Valves

AMENDMENT
This section has been amended at the state or city level.
Valves shall be supplied on rainwater collection and conveyance systems in accordance with Sections P2912.11.1 and P2912.11.2.

P2912.11.1 Influent Diversion

AMENDMENT
This section has been amended at the state or city level.
A means shall be provided to divert storage tank influent to allow for maintenance and repair of the storage tank system.

P2912.11.2 Backwater Valve

AMENDMENT
This section has been amended at the state or city level.
Backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section P3008.

P2912.12 Pumping and Control System

AMENDMENT
This section has been amended at the state or city level.
Mechanical equipment including pumps, valves and filters shall be easily accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall appropriate for the application and in accordance with Section P2903.

P2912.13 Water-Pressure-Reducing Valve or Regulator

AMENDMENT
This section has been amended at the state or city level.
Where the water pressure supplied by the pumping system exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the rainwater distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1.

P2912.14 Distribution Pipe

AMENDMENT
This section has been amended at the state or city level.
Distribution piping utilized in rainwater collection and conveyance systems shall comply with Sections P2912.14.1 through P2912.14.3.

Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

P2912.14.1 Materials, Joints and Connections

AMENDMENT
This section has been amended at the state or city level.
Distribution piping shall conform to the standards and requirements specified in Section P2906 for nonpotable water.

P2912.14.2 Design

AMENDMENT
This section has been amended at the state or city level.
Distribution piping systems shall be designed and sized in accordance with the Section P2903 for the intended application.

P2912.14.3 Labeling and Marking

AMENDMENT
This section has been amended at the state or city level.
Nonpotable rainwater distribution piping labeling and marking shall comply with Section P2901.2.

P2912.15 Tests and Inspections

AMENDMENT
This section has been amended at the state or city level.
Tests and inspections shall be performed in accordance with Sections P2912.15.1 through P2912.15.8.

P2912.15.1 Roof Gutter Inspection and Test

AMENDMENT
This section has been amended at the state or city level.
Roof gutters shall be inspected to verify that the installation and slope is in accordance with Section P2912.5.1. Gutters shall be tested by pouring not less than one gallon of water (3.8 L) into the end of the gutter opposite the collection point. The gutter being tested shall not leak and shall not retain standing water.

P2912.15.2 Roofwasher Test

AMENDMENT
This section has been amended at the state or city level.
Roofwashers shall be tested by introducing water into the gutters. Proper diversion of the first quantity of water in accordance with the requirements of Section P2912.4 shall be verified.

P2912.15.3 Collection Pipe and Vent Test

AMENDMENT
This section has been amended at the state or city level.
Drain, waste and vent piping used for rainwater collection and conveyance systems shall be tested in accordance with Section P2503.

P2912.15.4 Storage Tank Test

AMENDMENT
This section has been amended at the state or city level.
Storage tanks shall be tested in accordance with the Section P2910.11.

P2912.15.5 Water Supply System Test

AMENDMENT
This section has been amended at the state or city level.
The testing of makeup water supply piping and distribution piping shall be conducted in accordance with Section P2503.7.

P2912.15.6 Inspection and Testing of Backflow Prevention Assemblies

AMENDMENT
This section has been amended at the state or city level.
The testing of backflow preventers and backwater valves shall be conducted in accordance with Section P2503.8.

P2912.15.7 Inspection of Vermin and Insect Protection

AMENDMENT
This section has been amended at the state or city level.
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section P2910.7.

P2912.15.8 Water Quality Test

AMENDMENT
This section has been amended at the state or city level.
The quality of the water for the intended application shall be verified at the point of use in accordance with the requirements of the jurisdiction.

P2912.16 Operation and Maintenance Manuals

AMENDMENT
This section has been amended at the state or city level.
Operation and maintenance manuals shall be supplied with rainwater collection and conveyance systems in accordance with Sections P2912.16.1 through P2912.16.4.

P2912.16.1 Manual

AMENDMENT
This section has been amended at the state or city level.
A detailed operations and maintenance manual shall be supplied in hard-copy form for each system.

P2912.16.2 Schematics

AMENDMENT
This section has been amended at the state or city level.
The manual shall include a detailed system schematic, the location of system components and a list of system components that includes the manufacturers and model numbers of the components.

P2912.16.3 Maintenance Procedures

AMENDMENT
This section has been amended at the state or city level.
The manual shall provide a maintenance schedule and procedures for system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.

P2912.16.4 Operations Procedures

AMENDMENT
This section has been amended at the state or city level.
The manual shall include system startup and shutdown procedures, and detailed operating procedures.

Section P2913 Reclaimed Water Systems

AMENDMENT
This section has been amended at the state or city level.

P2913.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of this section shall govern the construction, installation, alteration and repair of systems supplying nonpotable reclaimed water.

P2913.2 Water-Pressure-Reducing Valve or Regulator

AMENDMENT
This section has been amended at the state or city level.
Where the reclaimed water pressure supplied to the building exceeds 80 psi (552 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the reclaimed water distribution system piping to 80 psi (552 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section P2903.3.1

P2913.3 Reclaimed Water Systems

AMENDMENT
This section has been amended at the state or city level.
The design of the reclaimed water systems shall conform to accepted engineering practice.

P2913.3.1 Distribution Pipe

AMENDMENT
This section has been amended at the state or city level.
Distribution piping shall comply with Sections P2913.3.1.1 through P2913.3.1.3.

Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.

P2913.3.1.1 Materials, Joints and Connections

AMENDMENT
This section has been amended at the state or city level.
Distribution piping conveying reclaimed water shall conform to standards and requirements specified in Section P2905 for nonpotable water.

P2913.3.1.2 Design

AMENDMENT
This section has been amended at the state or city level.
Distribution piping systems shall be designed and sized in accordance with Section P2903 for the intended application.

P2913.3.1.3 Labeling and Marking

AMENDMENT
This section has been amended at the state or city level.
Nonpotable rainwater distribution piping labeling and marking shall comply with Section P2901.2.

P2913.4 Tests and Inspections

AMENDMENT
This section has been amended at the state or city level.
Tests and inspections shall be performed in accordance with Sections P2913.4.1 and P2913.4.2.

P2913.4.1 Water Supply System Test

AMENDMENT
This section has been amended at the state or city level.
The testing of makeup water supply piping and reclaimed water distribution piping shall be conducted in accordance with Section P2503.7.

P2913.4.2 Inspection and Testing of Backflow Prevention Assemblies

AMENDMENT
This section has been amended at the state or city level.
The testing of backflow preventers shall be conducted in accordance with Section P2503.8.