CODES

ADOPTS WITH AMENDMENTS:

International Mechanical Code 2015 (IMC 2015)

Chapter 1 Scope and Administration

Part 1 — Scope and Application
Part 2 — Administration and Enforcement

Chapter 2 Definitions

Chapter 3 General Regulations

Chapter 4 Ventilation

Chapter 5 Exhaust Systems

Chapter 6 Duct Systems

Chapter 7 Combustion Air

Chapter 8 Chimneys and Vents

Chapter 9 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment

Chapter 10 Boilers, Water Heaters and Pressure Vessels

Chapter 11 Refrigeration

Chapter 12 Hydronic Piping

Chapter 13 Fuel Oil Piping and Storage

Chapter 14 Solar Systems

Chapter 15 Referenced Standards

Appendix A Chimney Connector Pass-Throughs

Appendix B Recommended Permit Fee Schedule

Chapter 1 Scope and Administration

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

Section 101 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

101.1 Title

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
These regulations shall be known as the Mechanical Code of [NAME OF JURISDICTION], hereinafter referred to as "this code."

101.2 Scope

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
This code shall regulate the design, installation, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall be regulated by the International Fuel Gas Code.

Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the International Residential Code.

101.2.1 Appendices

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Provisions in the appendices shall not apply unless specifically adopted.

101.3 Intent

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The purpose of this code is to establish minimum standards to provide a reasonable level of safety, health, property protection and public welfare by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of mechanical systems.

101.4 Severability

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
If a section, subsection, sentence, clause or phrase of this code is, for any reason, held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this code.

Section 102 Applicability

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

102.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.

102.2 Existing Installations

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Except as otherwise provided for in this chapter, a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, a mechanical system lawfully in existence at the time of the adoption of this code.

102.3 Maintenance

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Mechanical systems, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe and sanitary condition. Devices or safeguards that are required by this code shall be maintained in compliance with the edition of the code under which they were installed. The owner or the owner's authorized agent shall be responsible for maintenance of mechanical systems. To determine compliance with this provision, the code official shall have the authority to require a mechanical system to be reinspected.

The inspection for maintenance of HVAC systems shall be performed in accordance with ASHRAE/ACCA/ANSI Standard 180.

102.4 Additions, Alterations or Repairs

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Additions, alterations, renovations or repairs to a mechanical system shall conform to that required for a new mechanical system without requiring the existing mechanical system to comply with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing mechanical system to become unsafe, hazardous or overloaded.

Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.

102.5 Change in Occupancy

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
It shall be unlawful to make a change in the occupancy of any structure which will subject the structure to any special provision of this code applicable to the new occupancy without approval. The code official shall certify that such structure meets the intent of the provisions of law governing building construction for the proposed new occupancy and that such change of occupancy does not result in any hazard to the public health, safety or welfare.

102.6 Historic Buildings

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local jurisdiction as historic buildings where such buildings or structures are judged by the code official to be safe and in the public interest of health, safety and welfare regarding any proposed construction, alteration, repair, enlargement, restoration, relocation or moving of buildings.

102.7 Moved Buildings

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Except as determined by Section 102.2, mechanical systems that are a part of buildings or structures moved into or within the jurisdiction shall comply with the provisions of this code for new installations.

102.8 Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The codes and standards referenced herein shall be those that are listed in Chapter 15 and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.8.1 and 102.8.2.

Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing and the manufacturer's installation instructions shall apply.

102.8.1 Conflicts

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where conflicts occur between provisions of this code and the referenced standards, the provisions of this code shall apply.

102.8.2 Provisions in Referenced Codes and Standards

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the referenced code or standard.

102.9 Requirements Not Covered by This Code

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Requirements necessary for the strength, stability or proper operation of an existing or proposed mechanical system, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the code official.

102.10 Other Laws

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.

102.11 Application of References

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Reference to chapter section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.

Section 103 Department of Mechanical Inspection

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

103.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The department of mechanical inspection is hereby created and the executive official in charge thereof shall be known as the code official.

103.2 Appointment

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall be appointed by the chief appointing authority of the jurisdiction.

103.3 Deputies

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
In accordance with the prescribed procedures of this jurisdiction and with the concurrence of the appointing authority, the code official shall have the authority to appoint a deputy code official, other related technical officers, inspectors and other employees. Such employees shall have powers as delegated by the code official.

103.4 Liability

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official, member of the board of appeals or employee charged with the enforcement of this code, while acting for the jurisdiction in good faith and without malice in the discharge of the duties required by this code or other pertinent law or ordinance, shall not thereby be rendered civilly or criminally liable personally, and is hereby relieved from personal liability for any damage accruing to persons or property as a result of an act or by reason of an act or omission in the discharge of official duties.

103.4.1 Legal Defense

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Any suit or criminal complaint instituted against any officer or employee because of an act performed by that officer or employee in the lawful discharge of duties and under the provisions of this code shall be defended by the legal representatives of the jurisdiction until the final termination of the proceedings. The code official or any subordinate shall not be liable for costs in an action, suit or proceeding that is instituted in pursuance of the provisions of this code.

Section 104 Duties and Powers of the Code Official

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

104.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is hereby authorized and directed to enforce the provisions of this code. The code official shall have the authority to render interpretations of this code and to adopt policies and procedures in order to clarify the application of its provisions. Such interpretations, policies and procedures shall be in compliance with the intent and purpose of this code. Such policies and procedures shall not have the effect of waiving requirements specifically provided for in this code.

104.2 Applications and Permits

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall receive applications, review construction documents and issue permits for the installation and alteration of mechanical systems, inspect the premises for which such permits have been issued and enforce compliance with the provisions of this code.

104.3 Inspections

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall make all of the required inspections, or shall accept reports of inspection by approved agencies or individuals. Reports of such inspections shall be in writing and be certified by a responsible officer of such approved agency or by the responsible individual. The code official is authorized to engage such expert opinion as deemed necessary to report upon unusual technical issues that arise, subject to the approval of the appointing authority.

104.4 Right of Entry

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where it is necessary to make an inspection to enforce the provisions of this code, or where the code official has reasonable cause to believe that there exists in a building or upon any premises any conditions or violations of this code that make the building or premises unsafe, insanitary, dangerous or hazardous, the code official shall have the authority to enter the building or premises at all reasonable times to inspect or to perform the duties imposed upon the code official by this code. If such building or premises is occupied, the code official shall present credentials to the occupant and request entry. If such building or premises is unoccupied, the code official shall first make a reasonable effort to locate the owner, the owner's authorized agent or other person having charge or control of the building or premises and request entry. If entry is refused, the code official has recourse to every remedy provided by law to secure entry.

Where the code official has first obtained a proper inspection warrant or other remedy provided by law to secure entry, an owner, the owner's authorized agent or occupant or person having charge, care or control of the building or premises shall not fail or neglect, after proper request is made as herein provided, to promptly permit entry therein by the code official for the purpose of inspection and examination pursuant to this code.

104.5 Identification

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall carry proper identification when inspecting structures or premises in the performance of duties under this code.

104.6 Notices and Orders

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall issue all necessary notices or orders to ensure compliance with this code.

104.7 Department Records

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall keep official records of applications received, permits and certificates issued, fees collected, reports of inspections, and notices and orders issued. Such records shall be retained in the official records for the period required for retention of public records.

Section 105 Approval

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

105.1 Modifications

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where there are practical difficulties involved in carrying out the provisions of this code, the code official shall have the authority to grant modifications for individual cases upon application of the owner or owner's authorized agent, provided that the code official shall first find that special individual reason makes the strict letter of this code impractical and the modification is in compliance with the intent and purpose of this code and does not lessen health, life and fire safety requirements. The details of action granting modifications shall be recorded and entered in the files of the mechanical inspection department.

105.2 Alternative Materials, Methods, Equipment and Appliances

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The provisions of this code are not intended to prevent the installation of any material or to prohibit any method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material or method of construction shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, not less than the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. Where the alternative material, design or method of construction is not approved, the code official shall respond in writing, stating the reasons the alternative was not approved.

105.2.1 Research Reports

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.

105.3 Required Testing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where there is insufficient evidence of compliance with the provisions of this code, or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the code official shall have the authority to require tests as evidence of compliance to be made at no expense to the jurisdiction.

105.3.1 Test Methods

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the code official shall approve the testing procedures.

105.3.2 Testing Agency

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Tests shall be performed by an approved agency.

105.3.3 Test Reports

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Reports of tests shall be retained by the code official for the period required for retention of public records.

105.4 Approved Materials and Equipment

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Materials, equipment and devices approved by the code official shall be constructed and installed in accordance with such approval.

105.5 Material, Equipment and Appliance Reuse

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Materials, equipment, appliances and devices shall not be reused unless such elements have been reconditioned, tested and placed in good and proper working condition and approved.

Section 106 Permits

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

106.1 Where Required

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
An owner, owner's authorized agent or contractor who desires to erect, install, enlarge, alter, repair, remove, convert or replace a mechanical system, the installation of which is regulated by this code, or to cause such work to be performed, shall first make application to the code official and obtain the required permit for the work.

Exception: Where equipment and appliance replacements or repairs must be performed in an emergency situation, the permit application shall be submitted within the next working business day of the department of mechanical inspection.

106.1.1 Annual Permit

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Instead of an individual construction permit for each alteration to an already approved system or equipment or application installation, the code official is authorized to issue an annual permit upon application therefor to any person, firm or corporation regularly employing one or more qualified tradespersons in the building, structure or on the premises owned or operated by the applicant for the permit.

106.1.2 Annual Permit Records

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The person to whom an annual permit is issued shall keep a detailed record of alterations made under such annual permit. The code official shall have access to such records at all times or such records shall be filed with the code official as designated.

106.2 Permits Not Required

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Permits shall not be required for the following:

1. Portable heating appliances.

2. Portable ventilation appliances and equipment.

3. Portable cooling units.

4. Steam, hot water or chilled water piping within any heating or cooling equipment or appliances regulated by this code.

5. The replacement of any minor part that does not alter the approval of equipment or an appliance or make such equipment or appliance unsafe.

6. Portable evaporative coolers.

7. Self-contained refrigeration systems that contain 10 pounds (4.5 kg) or less of refrigerant, or that are actuated by motors of 1 horsepower (0.75 kW) or less.

8. Portable fuel cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid.

Exemption from the permit requirements of this code shall not be deemed to grant authorization for work to be done in violation of the provisions of this code or other laws or ordinances of this jurisdiction.

106.3 Application for Permit

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Each application for a permit, with the required fee, shall be filed with the code official on a form furnished for that purpose and shall contain a general description of the proposed work and its location. The application shall be signed by the owner or the owner's authorized agent. The permit application shall indicate the proposed occupancy of all parts of the building and of that portion of the site or lot, if any, not covered by the building or structure and shall contain such other information required by the code official.

106.3.1 Construction Documents

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Construction documents, engineering calculations, diagrams and other data shall be submitted in two or more sets with each application for a permit. The code official shall require construction documents, computations and specifications to be prepared and designed by a registered design professional where required by state law. Where special conditions exist, the code official is authorized to require additional construction documents to be prepared by a registered design professional. Construction documents shall be drawn to scale and shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that the work conforms to the provisions of this code. Construction documents for buildings more than two stories in height shall indicate where penetrations will be made for mechanical systems, and the materials and methods for maintaining required structural safety, fireresistance rating and fireblocking.

Exception: The code official shall have the authority to waive the submission of construction documents, calculations or other data if the nature of the work applied for is such that reviewing of construction documents is not necessary to determine compliance with this code.

106.3.2 Preliminary Inspection

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Before a permit is issued, the code official is authorized to inspect and evaluate the systems, equipment, buildings, devices, premises and spaces or areas to be used.

106.3.3 Time Limitation of Application

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
An application for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the code official shall have the authority to grant one or more extensions of time for additional periods not exceeding 180 days each. The extension shall be requested in writing and justifiable cause demonstrated.

106.4 Permit Issuance

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The application, construction documents and other data filed by an applicant for a permit shall be reviewed by the code official. If the code official finds that the proposed work conforms to the requirements of this code and all laws and ordinances applicable thereto, and that the fees specified in Section 106.5 have been paid, a permit shall be issued to the applicant.

106.4.1 Approved Construction Documents

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
When the code official issues the permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "APPROVED." Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.

The code official shall have the authority to issue a permit for the construction of part of a mechanical system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holder of such permit shall proceed at his or her own risk without assurance that the permit for the entire mechanical system will be granted.

106.4.2 Validity

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The issuance of a permit or approval of construction documents shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of other ordinances of the jurisdiction. A permit presuming to give authority to violate or cancel the provisions of this code shall be invalid.

The issuance of a permit based upon construction documents and other data shall not prevent the code official from thereafter requiring the correction of errors in said construction documents and other data or from preventing building operations from being carried on thereunder where in violation of this code or of other ordinances of this jurisdiction.

106.4.3 Expiration

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Every permit issued by the code official under the provisions of this code shall expire by limitation and become null and void if the work authorized by such permit is not commenced within 180 days from the date of such permit, or if the work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days. Before such work recommences, a new permit shall be first obtained and the fee therefor shall be one-half the amount required for a new permit for such work, provided that changes have not been made and will not be made in the original construction documents for such work, and provided further that such suspension or abandonment has not exceeded one year.

106.4.4 Extensions

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A permittee holding an unexpired permit shall have the right to apply for an extension of the time within which the permittee will commence work under that permit when work is unable to be commenced within the time required by this section for good and satisfactory reasons. The code official shall extend the time for action by the permittee for a period not exceeding 180 days if there is reasonable cause. A permit shall not be extended more than once. The fee for an extension shall be one-half the amount required for a new permit for such work.

106.4.5 Suspension or Revocation of Permit

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall have the authority to suspend or revoke a permit issued under the provisions of this code wherever the permit is issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any ordinance or regulation or any of the provisions of this code.

106.4.6 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws. One set of approved construction documents shall be returned to the applicant, and said set shall be kept on the site of the building or job at all times during which the work authorized thereby is in progress.

106.4.7 Previous Approvals

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.

106.4.8 Posting of Permit

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The permit or a copy shall be kept on the site of the work until the completion of the project.

106.5 Fees

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A permit shall not be issued until the fees prescribed in Section 106.5.2 have been paid, nor shall an amendment to a permit be released until the additional fee, if any, due to an increase of the mechanical system, has been paid.

106.5.1 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Any person who commences work on a mechanical system before obtaining the necessary permits shall be subject to 100 percent of the usual permit fee in addition to the required permit fees.

106.5.2 Fee Schedule

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The fees for mechanical work shall be as indicated in the following schedule.

[JURISDICTION TO INSERT
APPROPRIATE SCHEDULE]

106.5.3 Fee Refunds

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall authorize the refunding of fees as follows.

1. The full amount of any fee paid hereunder which was erroneously paid or collected.

2. Not more than [SPECIFY PERCENTAGE] percent of the permit fee paid where work has not been done under a permit issued in accordance with this code.

3. Not more than [SPECIFY PERCENTAGE] percent of the plan review fee paid where an application for a permit for which a plan review fee has been paid is withdrawn or canceled before any plan review effort has been expended.

The code official shall not authorize the refunding of any fee paid, except upon written application filed by the original permittee not later than 180 days after the date of fee payment.

Section 107 Inspections and Testing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

107.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to conduct such inspections as are deemed necessary to determine compliance with the provisions of this code. Construction or work for which a permit is required shall be subject to inspection by the code official, and such construction or work shall remain accessible and exposed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. Inspections presuming to give authority to violate or cancel the provisions of this code or of other ordinances of the jurisdiction shall not be valid.

107.2 Required Inspections and Testing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official, upon notification from the permit holder or the permit holder's agent, shall make the following inspections and other such inspections as necessary, and shall either release that portion of the construction or shall notify the permit holder or the permit holder's agent of violations that must be corrected. The holder of the permit shall be responsible for the scheduling of such inspections.

1. Underground inspection shall be made after trenches or ditches are excavated and bedded, piping installed, and before backfill is put in place. Where excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site.

2. Rough-in inspection shall be made after the roof, framing, fireblocking and bracing are in place and all ducting and other components to be concealed are complete, and prior to the installation of wall or ceiling membranes.

3. Final inspection shall be made upon completion of the mechanical system.

Exception: Ground-source heat pump loop systems tested in accordance with Section 1210.10 shall be permitted to be backfilled prior to inspection.

The requirements of this section shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and before any portion of such equipment or appliances is concealed by any permanent portion of the structure.

107.2.1 Other Inspections

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
In addition to the inspections specified in Section 107.2, the code official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced.

107.2.2 Inspection Requests

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.

107.2.3 Approval Required

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official.

107.2.4 Approved Inspection Agencies

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to accept reports of approved agencies, provided that such agencies satisfy the requirements as to qualifications and reliability.

107.2.5 Evaluation and Follow-Up Inspection Services

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Prior to the approval of a prefabricated construction assembly having concealed mechanical work and the issuance of a mechanical permit, the code official shall require the submittal of an evaluation report on each prefabricated construction assembly, indicating the complete details of the mechanical system, including a description of the system and its components, the basis upon which the system is being evaluated, test results and similar information, and other data as necessary for the code official to determine conformance to this code.

107.2.5.1 Evaluation Service

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall designate the evaluation service of an approved agency as the evaluation agency, and review such agency's evaluation report for adequacy and conformance to this code.

107.2.5.2 Follow-Up Inspection

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Except where ready access is provided to mechanical systems, service equipment and accessories for complete inspection at the site without disassembly or dismantling, the code official shall conduct the in-plant inspections as frequently as necessary to ensure conformance to the approved evaluation report or shall designate an independent, approved inspection agency to conduct such inspections. The inspection agency shall furnish the code official with the follow-up inspection manual and a report of inspections upon request, and the mechanical system shall have an identifying label permanently affixed to the system indicating that factory inspections have been performed.

107.2.5.3 Test and Inspection Records

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Required test and inspection records shall be available to the code official at all times during the fabrication of the mechanical system and the erection of the building; or such records as the code official designates shall be filed.

107.3 Testing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Mechanical systems shall be tested as required in this code and in accordance with Sections 107.3.1 through 107.3.3. Tests shall be made by the permit holder and observed by the code official.

107.3.1 New, Altered, Extended or Repaired Systems

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
New mechanical systems and parts of existing systems, which have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects.

107.3.2 Apparatus, Material and Labor for Tests

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Apparatus, material and labor required for testing a mechanical system or part thereof shall be furnished by the permit holder.

107.3.3 Reinspection and Testing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the code official for inspection and testing.

107.4 Approval

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official.

107.4.1 Revocation

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the notice is issued in error, on the basis of incorrect information supplied, or where it is determined that the building or structure, premise or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.

107.5 Temporary Connection

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall have the authority to authorize the temporary connection of a mechanical system to the sources of energy for the purpose of testing mechanical systems or for use under a temporary certificate of occupancy.

107.6 Connection of Service Utilities

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A person shall not make connections from a utility, source of energy, fuel or power to any building or system that is regulated by this code for which a permit is required, until authorized by the code official.

Section 108 Violations

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

108.1 Unlawful Acts

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
It shall be unlawful for a person, firm or corporation to erect, construct, alter, repair, remove, demolish or utilize a mechanical system, or cause same to be done, in conflict with or in violation of any of the provisions of this code.

108.2 Notice of Violation

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall serve a notice of violation or order to the person responsible for the erection, installation, alteration, extension, repair, removal or demolition of mechanical work in violation of the provisions of this code, or in violation of a detail statement or the approved construction documents thereunder, or in violation of a permit or certificate issued under the provisions of this code. Such order shall direct the discontinuance of the illegal action or condition and the abatement of the violation.

108.3 Prosecution of Violation

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
If the notice of violation is not complied with promptly, the code official shall request the legal counsel of the jurisdiction to institute the appropriate proceeding at law or in equity to restrain, correct or abate such violation, or to require the removal or termination of the unlawful occupancy of the structure in violation of the provisions of this code or of the order or direction made pursuant thereto.

108.4 Violation Penalties

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter or repair mechanical work in violation of the approved construction documents or directive of the code official, or of a permit or certificate issued under the provisions of this code, shall be guilty of a [SPECIFY OFFENSE], punishable by a fine of not more than [AMOUNT] dollars or by imprisonment not exceeding [NUMBER OF DAYS], or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.

108.5 Stop Work Orders

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Upon notice from the code official that mechanical work is being performed contrary to the provisions of this code or in a dangerous or unsafe manner, such work shall immediately cease. Such notice shall be in writing and shall be given to the owner of the property, or to the owner's authorized agent, or to the person doing the work. The notice shall state the conditions under which work is authorized to resume. Where an emergency exists, the code official shall not be required to give a written notice prior to stopping the work. Any person who shall continue any work on the system after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable for a fine of not less than [AMOUNT] dollars or more than [AMOUNT] dollars.

108.6 Abatement of Violation

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The imposition of the penalties herein prescribed shall not preclude the legal officer of the jurisdiction from instituting appropriate action to prevent unlawful construction or to restrain, correct or abate a violation, or to prevent illegal occupancy of a building, structure or premises, or to stop an illegal act, conduct, business or utilization of the mechanical system on or about any premises.

108.7 Unsafe Mechanical Systems

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A mechanical system that is unsafe, constitutes a fire or health hazard, or is otherwise dangerous to human life, as regulated by this code, is hereby declared as an unsafe mechanical system. Use of a mechanical system regulated by this code constituting a hazard to health, safety or welfare by reason of inadequate maintenance, dilapidation, fire hazard, disaster, damage or abandonment is hereby declared an unsafe use. Such unsafe equipment and appliances are hereby declared to be a public nuisance and shall be abated by repair, rehabilitation, demolition or removal.

108.7.1 Authority to Condemn Mechanical Systems

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Whenever the code official determines that any mechanical system, or portion thereof, regulated by this code has become hazardous to life, health, property, or has become insanitary, the code official shall order in writing that such system either be removed or restored to a safe condition. A time limit for compliance with such order shall be specified in the written notice. A person shall not use or maintain a defective mechanical system after receiving such notice.

Where such mechanical system is to be disconnected, written notice as prescribed in Section 108.2 shall be given. In cases of immediate danger to life or property, such disconnection shall be made immediately without such notice.

108.7.2 Authority to Order Disconnection of Energy Sources

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall have the authority to order disconnection of energy sources supplied to a building, structure or mechanical system regulated by this code, where it is determined that the mechanical system or any portion thereof has become hazardous or unsafe. Written notice of such order to disconnect service and the causes therefor shall be given within 24 hours to the owner, the owner's authorized agent and occupant of such building, structure or premises, provided, however, that in cases of immediate danger to life or property, such disconnection shall be made immediately without such notice. Where energy sources are provided by a public utility, the code official shall immediately notify the serving utility in writing of the issuance of such order to disconnect.

108.7.3 Connection After Order to Disconnect

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A person shall not make energy source connections to mechanical systems regulated by this code which have been disconnected or ordered to be disconnected by the code official, or the use of which has been ordered to be discontinued by the code official until the code official authorizes the reconnection and use of such mechanical systems.

Where a mechanical system is maintained in violation of this code, and in violation of a notice issued pursuant to the provisions of this section, the code official shall institute appropriate action to prevent, restrain, correct or abate the violation.

Section 109 Means of Appeal

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

109.1 Application for Appeal

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A person shall have the right to appeal a decision of the code official to the board of appeals. An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equally good or better form of construction is proposed. The application shall be filed on a form obtained from the code official within 20 days after the notice was served.

109.1.1 Limitation of Authority

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board of appeals shall not have authority relative to interpretation of the administration of this code nor shall such board be empowered to waive requirements of this code.

109.2 Membership of Board

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board of appeals shall consist of five members appointed by the chief appointing authority as follows: one for 5 years; one for 4 years; one for 3 years; one for 2 years; and one for 1 year. Thereafter, each new member shall serve for 5 years or until a successor has been appointed.

109.2.1 Qualifications

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board of appeals shall consist of five individuals, one from each of the following professions or disciplines.

1. Registered design professional who is a registered architect; or a builder or superintendent of building construction with not less than 10 years' experience, 5 of which shall have been in responsible charge of work.

2. Registered design professional with structural engineering or architectural experience.

3. Registered design professional with mechanical and plumbing engineering experience; or a mechanical contractor with not less than 10 years' experience, 5 of which shall have been in responsible charge of work.

4. Registered design professional with electrical engineering experience; or an electrical contractor with not less than 10 years' experience, 5 of which shall have been in responsible charge of work.

5. Registered design professional with fire protection engineering experience; or a fire protection contractor with not less than 10 years' experience, 5 of which shall have been in responsible charge of work.

109.2.2 Alternate Members

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The chief appointing authority shall appoint two alternate members who shall be called by the board chairman to hear appeals during the absence or disqualification of a member. Alternate members shall possess the qualifications required for board membership and shall be appointed for 5 years, or until a successor has been appointed.

109.2.3 Chairman

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board shall annually select one of its members to serve as chairman.

109.2.4 Disqualification of Member

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
A member shall not hear an appeal in which that member has a personal, professional or financial interest.

109.2.5 Secretary

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The chief administrative officer shall designate a qualified clerk to serve as secretary to the board. The secretary shall file a detailed record of all proceedings in the office of the chief administrative officer.

109.2.6 Compensation of Members

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Compensation of members shall be determined by law.

109.3 Notice of Meeting

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board shall meet upon notice from the chairman, within 10 days of the filing of an appeal, or at stated periodic meetings.

109.4 Open Hearing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Hearings before the board shall be open to the public. The appellant, the appellant's representative, the code official and any person whose interests are affected shall be given an opportunity to be heard.

109.4.1 Procedure

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board shall adopt and make available to the public through the secretary procedures under which a hearing will be conducted. The procedures shall not require compliance with strict rules of evidence, but shall mandate that only relevant information be received.

109.5 Postponed Hearing

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
When five members are not present to hear an appeal, either the appellant or the appellant's representative shall have the right to request a postponement of the hearing.

109.6 Board Decision

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The board shall modify or reverse the decision of the code official by a concurring vote of three members.

109.6.1 Resolution

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The decision of the board shall be by resolution. Certified copies shall be furnished to the appellant and to the code official.

109.6.2 Administration

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official shall take immediate action in accordance with the decision of the board.

109.7 Court Review

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Any person, whether or not a previous party of the appeal, shall have the right to apply to the appropriate court for a writ of certiorari to correct errors of law. Application for review shall be made in the manner and time required by law following the filing of the decision in the office of the chief administrative officer.

Section 110 Temporary Equipment, Systems and Uses

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

110.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to issue a permit for temporary equipment, systems and uses. Such permits shall be limited as to time of service, but shall not be permitted for more than 180 days. The code official is authorized to grant extensions for demonstrated cause.

110.2 Conformance

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Temporary equipment, systems and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure the public health, safety and general welfare.

110.3 Temporary Utilities

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to give permission to temporarily supply utilities before an installation has been fully completed and the final certificate of completion has been issued. The part covered by the temporary certificate shall comply with the requirements specified for temporary lighting, heat or power in the code.

110.4 Termination of Approval

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
The code official is authorized to terminate such permit for temporary equipment, systems or uses and to order the temporary equipment, systems or uses to be discontinued.
Resources
Help us
keep law free