UpCodes logo
Table of contentsContents
The requirements of this chapter shall govern the venting of fuel-burning appliances.
Low-heat and medium-heat gas appliances shall be vented in accordance with this chapter. Other gas appliances shall be vented in accordance with NFPA 211 or other applicable standards.
Appliances fueled by fuels other than gas shall be vented in accordance with NFPA 211 and the appliance manufacturer's instructions.
Type B and Type B-W gas vents shall comply with UL 441, Type L gas vents shall comply with UL 641.
Listed vents shall be installed in accordance with this chapter and the manufacturer's installation instructions. [NFPA 54:12.2.1]
Appliance vents shall not discharge into a space enclosed by screens having openings less than 1/4 of an inch (6.4 mm) mesh.
Except as permitted in Section 802.2.1 through Section 802.2.8, all appliances shall be connected to venting systems. [NFPA 54:12.3.1]
The following appliances shall not be required to be vented:
  1. Listed ranges.
  2. Built-in domestic cooking units listed and marked for optional venting.
  3. Listed hot plates and listed laundry stoves.
  4. Listed Type 1 clothes dryers exhausted in accordance with Section 504.4.
  5. A single listed booster-type (automatic instantaneous) water heater, when designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the appliance is installed with the draft hood in place and unaltered, if a draft hood is required, in a commercial kitchen having a mechanical exhaust system; where installed in this manner, the draft hood outlet shall not be less than 36 inches (914 mm) vertically and 6 inches (152 mm) horizontally from any surface other than the appliance.
  6. Listed refrigerators.
  7. Counter appliances.
  8. Room heaters listed for unvented use.
  9. Direct gas-fired makeup air heaters.
  10. Other appliances listed for unvented use and not provided with flue collars.
  11. Specialized appliances of limited input such as laboratory burners or gas lights. [NFPA 54:12.3.2]
Where any or all of the appliances in Section 802.2.1(5) through Section 802.2.1(11) are installed so the aggregate input rating exceeds 20 Btu/hr/ft3 (207 W/m3) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for conveying the vent gases to the outdoors so the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu/hr/ft3 (207 W/m3). [NFPA 54:12.3.2.1]
Where the calculation includes the volume of an adjacent room or space, the room or space in which the appliances are installed shall be directly connected to the adjacent room or space by a doorway, archway, or other opening of comparable size that cannot be closed. [NFPA 54:12.3.2.2]
Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications and to vent industrial appliances, particularly where the process itself requires fume disposal. [NFPA 54:12.3.3]
The operation of industrial appliances such that its flue gases are discharged directly into a large and well-ventilated space shall be permitted. [NFPA 54:12.3.4]
Listed direct-vent appliances shall be installed in accordance with the manufacturer's installation instructions and Section 802.8.2. [NFPA 54:12.3.5]
Appliances incorporating integral venting means shall be installed in accordance with the manufacturer's installation instructions, Section 802.8, and Section 802.8.1. [NFPA 54:12.3.6]
Commercial industrial-type incinerators shall be vented in accordance with NFPA 82. [NFPA 54:12.3.7]
Venting systems shall be designed and constructed to convey flue and vent gases to the outdoors. [NFPA 54:12.1]
A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer's instructions. [NFPA 54:12.4.1]
Appliances required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Section 802.4 through Section 802.15.1. [NFPA 54:12.4.2]
Mechanical draft systems shall be listed and installed in accordance with both the appliance and the mechanical draft system manufacturer's installation instructions. [NFPA 54:12.4.3.1]
Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. [NFPA 54:12.4.3.2]
Forced draft systems and portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. [NFPA 54:12.4.3.3]
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. [NFPA 54:12.4.3.4]
Where a mechanical draft system is employed, provision shall be made to prevent the flow of gas to the main burners where the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance. [NFPA 54:12.4.3.5]
The exit terminals of mechanical draft systems shall be not less than 7 feet (2134 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 802.8 and Section 802.8.1. [NFPA 54:12.4.3.6]
Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications. [NFPA 54:12.4.4.1]
Where automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners where the damper is open to a position to properly vent the appliance and where the power means of exhaust is in operation. [NFPA 54:12.4.4.2]
Venting systems shall not extend into or pass through a fabricated air duct or furnace plenum. [NFPA 54:12.4.5.1]
Where a venting system passes through an above-ceiling air space or other nonducted portion of an air-handling system, it shall conform to one of the following requirements:
  1. The venting system shall be a listed special gas vent, other system serving a Category III or Category IV appliance, or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer's instructions.
  2. The vent system shall be installed such that no fittings or joints between sections are installed in the above-ceiling space.
  3. The venting system shall be installed in a conduit or enclosure with joints between the interior of the enclosure and the ceiling space sealed. [NFPA 54:12.4.5.2]
The type of venting system to be used shall be in accordance with Table 802.4. [NFPA 54:12.5.1]
TABLE 802.4 TYPE OF VENTING SYSTEM TO BE USED
[NFPA 54: TABLE 12.5.1]
APPLIANCES TYPE OF VENTING SYSTEM LOCATION OF REQUIREMENTS
Listed Category I appliances Type B gas vent Section 802.6
Listed appliances equipped with draft hood Chimney Section 802.5
Appliances listed for use with Type B gas vent Single-wall metal pipe Section 802.7
Listed chimney lining system for gas venting Section 802.5.3
Special gas vent listed for these appliances Section 802.4.3
Listed vented wall furnaces Type B-W gas vent Section 802.6, Section 907.0
Category II appliances
Category III appliances
Category IV appliances
As specified or furnished by manufacturers of listed appliances Section 802.4.1 and Section 802.4.3
Incinerators Single-wall metal pipe NFPA 82
Appliances that can be converted to use of solid fuel

Unlisted combination gas- and oil-burning appliances

Combination gas- and solid-fuel-burning appliances

Appliances listed for use with chimneys only

Unlisted appliances
Chimney Section 802.5
Listed combination gas- and oil-burning appliances Type L vent Section 802.6
Chimney Section 802.5
Decorative appliances in vented fireplace Chimney Section 911.2
Gas-fired toilets Single-wall metal pipe Section 802.7, Section 929.3
Direct-vent appliances Section 802.2.6
Appliances with integral vents Section 802.2.7
Where plastic piping is used to vent an appliance, the appliance shall be listed for use with such venting materials and the appliance manufacturer's installation instructions shall identify the specific plastic piping material. [NFPA 54:12.5.2]
Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer's installation instructions. Where primer is required, it shall be of a contrasting color. [NFPA 54:12.5.3]
Special gas vents shall be listed and installed in accordance with the special gas vent manufacturer's installation instructions. [NFPA 54:12.5.4]
Factory-built chimneys shall be installed in accordance with the manufacturer's installation instructions. Factory-built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such application. [NFPA 54:12.6.1.1]
Decorative shrouds addressed in Section 802.5.4.3 shall be listed or labeled in accordance with UL 103 for factory-built residential chimneys, UL 127 for factory-built fireplaces, or UL 1482 for solid-fuel room heaters.
Factory-built chimneys shall comply with the requirements of UL 103 or of UL 959. Factory-built chimneys for use with wood-burning appliances shall comply with the Type HT requirements of UL 103. [NFPA 211:6.1.3.1, 6.1.3.2]
Metal chimneys shall be built and installed in accordance with NFPA 211. [NFPA 54:12.6.1.2]
Masonry chimneys shall be built and installed in accordance with NFPA 211 and lined with approved clay flue lining, a listed chimney lining system, or other approved material that resists corrosion, erosion, softening, or cracking from vent gases at temperatures not exceeding 1800°F (982°C).
Exception: Masonry chimney flues lined with a chimney lining system specifically listed for use with listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be permitted. The liner shall be installed in accordance with the liner manufacturer's installation instructions. A permanent identifying label shall be attached at the point where the connection is to be made to the liner. The label shall read: "This chimney liner is for appliances that burn gas only. Do not connect to solid-or liquid-fuel-burning appliances or incinerators." [NFPA 54:12.6.1.3]
A chimney for a residential-type or low-heat appliance shall extend not less than 3 feet (914 mm) above the highest point where it passes through a roof of a building and not less than 2 feet (610 mm) higher than a portion of a building within a horizontal distance of 10 feet (3048 mm). (See Figure 802.5.4) [NFPA 54:12.6.2.1]
 
FIGURE 802.5.4
TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE-WALL METAL PIPES SERVING RESIDENTIAL-TYPE AND LOW-HEAT APPLIANCE
[NFPA 54: FIGURE A.12.6.2.1]
 
A chimney for medium-heat appliance shall extend at least less than 10 feet (3048 mm) higher than any portion of any building within 25 feet (7620 mm). [NFPA 54:12.6.2.2]
A chimney shall extend not less than 5 feet (1524 mm) above the highest connected appliance draft hood outlet or flue collar. [NFPA 54:12.6.2.3]
Decorative shrouds shall not be installed at the termination of factory-built chimneys except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with the manufacturer's installation instructions. [NFPA 54:12.6.2.4]
The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be in accordance with one of the following methods:
  1. Those listed in Section 803.0.
  2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent connector and chimney flue shall be not less than the area of the appliance flue collar or draft hood outlet or greater than seven times the draft hood outlet area.
  3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or greater than seven times the smaller draft hood outlet area.
  4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods.
  5. Other approved engineering methods. [NFPA 54:12.6.3.1]
This inspection shall be made after chimneys, vents, or parts thereof, authorized by the permit, have been installed and before such vent or part thereof has been covered or concealed.
Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and shall be cleaned where previously used for venting solid- or liquid-fuel-burning appliances or fireplaces. [NFPA 54:12.6.4.1]
Chimneys shall be lined in accordance with NFPA 211.
Exception: Existing chimneys shall be permitted to have their use continued when an appliance is replaced by an appliance of similar type, input rating, and efficiency, where the chimney complies with Section 802.5.7 through Section 802.5.7.3 and the sizing of the chimney is in accordance with Section 802.5.5. [NFPA 54:12.6.4.2]
Cleanouts shall be examined to determine that they will remain tightly closed where not in use. [NFPA 54:12.6.4.3]
Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined, or replaced with a vent or chimney in accordance with NFPA 211, and shall be approved for the appliances to be attached. [NFPA 54:12.6.4.4]
An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. [NFPA 54:12.6.5.1]
Where one chimney serves gas appliances and liquid fuel-burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the gas appliance is automatically controlled, it shall be equipped with a safety shutoff device. [NFPA 54:12.6.5.2]
A listed combination gas- and solid-fuel-burning appliance connected to a single chimney flue shall be equipped with a manual reset device to shut off gas to the main burner in the event of sustained backdraft or flue gas spillage. The chimney flue shall be sized to properly vent the appliance. [NFPA 54:12.6.5.3]
A single chimney flue serving a listed combination gas- and oil-burning appliance shall be sized to properly vent the appliance. [NFPA 54:12.6.5.4]
All portions of chimneys shall be supported for the design and weight of the materials employed. Listed factory-built chimneys shall be supported and spaced in accordance with the manufacturer's installation instructions. [NFPA 54:12.6.6]
Where a chimney that formerly carried flue products from liquid or solid fuel-burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight-fitting cover and be installed so its upper edge is not less than 6 inches (152 mm) below the lower edge of the lowest chimney inlet opening. [NFPA 54:12.6.7]
The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry chimney shall not be used to vent another appliance.
Exception: The insertion of another liner or vent within the chimney as provided in this code and the liner or vent manufacturer's instructions. [NFPA 54:12.6.8.1]
The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal or factory-built chimney flue shall not be used to supply combustion air.
Exception: Direct-vent appliances designed for installation in a solid-fuel-burning fireplace where installed in accordance with the manufacturer's installation instructions. [NFPA 54:12.6.8.2]
The installation of gas vents shall meet the following requirements:
  1. Gas vents shall be installed in accordance with the manufacturer's installation instructions.
  2. A Type B-W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected.
  3. Gas vents installed within masonry chimneys shall be installed in accordance with the manufacturer's installation instructions. Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following language: "This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel—burning appliances or incinerators."
  4. Screws, rivets, and other fasteners shall not penetrate the inner wall of double-wall gas vents, except at the transition from the appliance draft hood outlet, flue collar, or single-wall metal connector to a double-wall vent. [NFPA 54:12.7.1]
A gas vent shall terminate in accordance with one of the following:
  1. Gas vents that are 12 inches (300 mm) or less in size and located not less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall terminate above the roof in accordance with Figure 802.6.1 and Table 802.6.1.
  2. Gas vents that are over 12 inches (300 mm) in size or are located less than 8 feet (2438 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet (610 mm) above the highest point where they pass through the roof and not less than 2 feet (610 mm) above a portion of a building within 10 feet (3048 mm) horizontally.
  3. Industrial appliances as provided in Section 802.2.5.
  4. Direct-vent systems as provided in Section 802.2.6.
  5. Appliance with integral vents as provided in Section 802.2.7.
  6. Mechanical draft systems as provided in Section 802.3.3 through Section 802.3.3.5.
  7. Ventilating hoods and exhaust systems as provided in Section 802.3.4 and Section 802.3.4.1. [NFPA 54:12.7.2(1)]
FIGURE 802.6.1
GAS VENT TERMINATION LOCATIONS FOR LISTED CAPS 12 INCHES OR LESS IN SIZE NOT LESS THAN 8 FEET FROM A VERTICAL WALL
[NFPA 54: FIGURE 12.7.2]

TABLE 802.6.1
ROOF PITCH HEIGHT
[NFPA 54: TABLE 12.7.2]
ROOF PITCH H (minimum) (feet)
Flat to 6/12 1.0
Over 6/12 to 7/12 1.25
Over 7/12 to 8/12 1.5
Over 8/12 to 9/12 2.0
Over 9/12 to 10/12 2.5
Over 10/12 to 11/12 3.25
Over 11/12 to 12/12 4.0
Over 12/12 to 14/12 5.0
Over 14/12 to 16/12 6.0
Over 16/12 to 18/12 7.0
Over 18/12 to 20/12 7.5
Over 20/12 to 21/12 8.0
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
A Type B or a Type L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. [NFPA 54:12.7.2(2)]
A Type B-W gas vent shall terminate not less than 12 feet (3658 mm) in vertical height above the bottom of the wall furnace. [NFPA 54:12.7.2(3)]
A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Section 802.2.6 and Section 802.3.3 through Section 802.3.3.5. [NFPA 54:12.7.2(4)]
Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer's installation instructions. [NFPA 54:12.7.2(5)]
A gas vent shall extend through the roof flashing, roof jack, or roof thimble and terminate with a listed cap or listed roof assembly. [NFPA 54:12.7.2(6)]
A gas vent shall terminate not less than 3 feet (914 mm) above a forced air inlet located within 10 feet (3048 mm). [NFPA 54:12.7.2(7)]
Where a vent passes through an insulated assembly, an approved metal shield shall be installed between the vent and insulation. The shield shall extend not less than 2 inches (51 mm) above the insulation and be secured to the structure in accordance with the manufacturer's installation instructions.
Venting systems shall be sized and constructed in accordance with Section 803.0 or other approved engineering methods and the gas vent and the appliance manufacturer's instructions. [NFPA 54:12.7.3]
The sizing of natural draft venting systems serving one or more listed appliances equipped with a draft hood or appliances listed for use with a Type B gas vent, installed in a single story of a building, shall be in accordance with one of the following:
  1. The provisions of Section 803.0.
  2. Vents serving fan-assisted combustion system appliances, or combinations of fan-assisted combustion system and draft hood-equipped appliances shall be sized in accordance with Section 803.0 or other approved engineering methods.
  3. For sizing an individual gas vent for a single, draft hood-equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet or exceeding seven times the draft hood outlet area.
  4. For sizing a gas vent connected to two appliances, with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or exceeding seven times the smaller draft hood outlet area.
  5. Approved engineering practices. [NFPA 54:12.7.3.1]
Type B and Type L vents sized in accordance with Section 802.6.2.1(3) or Section 802.6.2.1 (4) shall extend in a generally vertical direction with offsets not exceeding 45 degrees except that a vent system having not more than one 60 degree offset shall be permitted. Any angle greater than 45 degrees from the vertical is considered horizontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft hood-equipped appliances shall not be greater than 75 percent of the vertical height of the vent. [NFPA 54:12.7.3.2]
The sizing of gas vents for Category II, Category III, and Category IV appliances shall be in accordance with the appliance manufacturer's instructions. The sizing of plastic pipe specified by the appliance manufacturer as a venting material for Category II, Category III, and Category IV appliances shall be in accordance with the appliance manufacturers' instructions. [NFPA 54:12.7.3.3]
Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. [NFPA 54:12.7.3.4]
A common vent shall be permitted in multistory installations to vent Category I appliances located on more than one floor level, provided the venting system is designed and installed in accordance with approved engineering methods.
For the purpose of this section, crawl spaces, basements, and attics shall be considered as floor levels. [NFPA 54:12.7.4.1]
Appliances connected to the common vent shall be located in rooms separated from an occupiable space. Each of these rooms shall have provisions for an adequate supply of combustion, ventilation, and dilution air that is not supplied from an occupiable space. (See Figure 802.6.3.1) [NFPA 54:12.7.4.2]
FIGURE 802.6.3.1
PLAN VIEW OF PRACTICAL SEPARATION METHOD FOR MULTISTORY GAS VENTING [NFPA 54: FIGURE A.12.7.4.2]
The size of the connectors and common segments of multistory venting systems for appliances listed for use with a Type B double-wall gas vent shall be in accordance with Table 803.2(1), provided all of the following apply:
  1. The available total height (H) for each segment of a multistory venting system is the vertical distance between the level of the highest draft hood outlet or flue collar on that floor and the centerline of the next highest interconnection tee.
  2. The size of the connector for a segment is determined from the appliance's gas input rate and available connector rise, and shall not be smaller than the draft hood outlet or flue collar size.
  3. The size of the common vertical vent segment, and of the interconnection tee at the base of that segment, is based on the total appliance's gas input rate entering that segment and its available total height. [NFPA 54:12.7.4.3]
 
FIGURE 802.6.3.2
USE OF MANIFOLDED COMMON VENT CONNECTOR
[NFPA 54: FIGURE F.1(k)]
 
Gas vents shall be supported and spaced in accordance with the manufacturer's installation instructions. [NFPA 54:12.7.5]
In those localities where solid and liquid fuels are used extensively, gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: "This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel-burning appliances or incinerators." The Authority Having Jurisdiction shall determine whether its area constitutes such a locality. [NFPA 54:12.7.6]
Single-wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 of an inch (0.7722 mm) thick or of other approved, noncombustible, corrosion-resistant material. [NFPA 54:12.8.1]
Uninsulated single-wall metal pipe shall not be used outdoors for venting appliances in regions where the 99 percent winter design temperature is below 32°F (0°C). [NFPA 54:12.8.2]
The termination of single-wall metal pipe shall meet the following requirements:
  1. Single-wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar.
  2. Single-wall metal pipe shall extend at least 2 feet (610 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm). (See Figure 802.5.4)
  3. An approved cap or roof assembly shall be attached to the terminus of a single-wall metal pipe. [NFPA 54:12.8.3]
Single-wall metal pipe shall not be used as a vent in dwellings and residential occupancies. [NFPA 54:12.8.4.1]
Single-wall metal pipe shall be used for runs directly from the space in which the appliance is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. [NFPA 54:12.8.4.2]
Single-wall metal pipe shall not originate in an unoccupied attic or concealed space and shall not pass through an attic, inside wall, concealed space, or floor. [NFPA 54:12.8.4.3]
Minimum clearances from single-wall metal pipe to combustible material shall be in accordance with Table 802.7.3.3. Reduced clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors in Table 303.10.1. [NFPA 54:12.8.4.4]
TABLE 802.7.3.3
CLEARANCE FOR CONNECTORS*
[NFPA 54: TABLE 12.8.4.4]
MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches)
APPLIANCE LISTED TYPE B GAS VENT MATERIAL LISTED TYPE L VENT MATERIAL SINGLE-WALL METAL PIPE FACTORY-BUILT CHIMNEY SECTIONS
Listed appliance with draft hoods and appliance listed for use with Type B gas vents As listed As listed 6 As listed
Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 6 9 As listed
Residential appliances listed for use with Type L vents Not permitted As listed 9 As listed
Listed gas-fired toilets Not permitted As listed As listed As listed
Unlisted residential appliances with draft hood Not permitted 6 9 As listed
Residential and low-heat appliance other than those above Not permitted 9 18 As listed
Medium-heat appliance Not permitted Not permitted 36 As listed
For SI units: 1 inch = 25.4 mm
* These clearances shall apply unless the installation instructions of a listed appliance or connector specify different clearances, in which case the listed clearances shall apply.
Single-wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:
  1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (102 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet (1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (51 mm) larger in diameter than the metal pipe.
  2. For unlisted appliances having draft hoods, the thimble shall be a minimum of 6 inches (152 mm) larger in diameter than the metal pipe.
  3. For residential and low-heat appliances, the thimble shall be a minimum of 12 inches (305 mm) larger in diameter than the metal pipe.
Exception: In lieu of thimble protection, combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such opening shall be noncombustible. [NFPA 54:12.8.4.6]
Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches (457 mm) above and 6 inches (152 mm) below the roof with the annular space open at the bottom and closed at the top. The thimble shall be sized in accordance with Section 802.7.3.4. [NFPA 54:12.8.4.5]
Single-wall metal piping shall comply with Section 802.7.4.1 through Section 802.7.4.3. [NFPA 54:12.8.5]
A venting system of a single-wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer's instructions:
  1. For a draft hood-equipped appliance, in accordance with Section 803.0.
  2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall not be less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall not exceed seven times the draft hood outlet area.
  3. Other approved engineering methods. [NFPA 54:12.8.5(1)]
Where a single-wall metal pipe is used and has a shape other than round, it shall have an effective area equal to the effective area of the round pipe for which it is substituted, and the internal dimension of the pipe shall be not less than 2 inches (51 mm). [NFPA 54:12.8.5(2)]
The vent cap or a roof assembly shall have a venting capacity not less than that of the pipe to which it is attached. [NFPA 54:12.8.5(3)]
Portions of single-wall metal pipe shall be supported for the design and weight of the material employed. [NFPA 54:12.8.6]
Single-wall metal pipe shall comply with the marking provisions of Section 802.6.5. [NFPA 54:12.8.7]
A mechanical draft venting system shall terminate at least 3 feet (914 mm) above any forced air inlet located within 10 feet (3048 mm). (See Figure 802.8).
Exceptions:
  1. This provision shall not apply to the combustion-air intake of a direct-vent appliance.
  2. This provision shall not apply to the separation of the integral outdoor-air inlet and flue gas discharge of listed outdoor appliances. [NFPA 54:12.9.1]

FIGURE 802.8
EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEMS [NFPA 54:FIGURE A.12.9]
Upcodes Diagrams
A mechanical draft venting system of other than direct-vent type shall terminate not less than 4 feet (1219 mm) below, 4 feet (1219 mm) horizontally from, or 1 foot (305 mm) above a door, operable window, or gravity air inlet into a building. The bottom of the vent terminal shall be located not less than 12 inches (305 mm) above finished ground level. [NFPA 54:12.9.2]
Upcodes Diagrams
The vent terminal of a direct-vent appliance with an input of 10 000 Btu/h (3 kW) or less shall be located at least 6 inches (152 mm) from any air opening into a building, an appliance with an input over 10 000 Btu/h (3 kW) but not over 50 000 Btu/h (14.7 kW) shall be installed with a 9 inch (229 mm) vent termination clearance, and an appliance with an input exceeding 50 000 Btu/h (14.7 kW) shall have at least a 12 inch (305 mm) vent termination clearance. The bottom of the vent terminal and the air intake shall be located at least 12 inches (305 mm) above finished ground level. [NFPA 54:12.9.3]
Upcodes Diagrams
Through-the-wall vents for Category II and Category IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that condensate is a problem with Category I and Category III appliances, this provision shall also apply.
Drains for condensate shall be installed in accordance with the appliance and the vent manufacturer's installation instructions. [NFPA 54:12.9.4]
Upcodes Diagrams
Where vents, including those for direct-vent appliances or combustion air intake pipes, penetrate outside walls of buildings, the annular spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the building. [NFPA 54:12.9.5]
Vent systems for Category IV appliances that terminate through an outside wall of a building and discharge flue gases perpendicular to the adjacent wall shall be located not less than 10 feet (3048 mm) horizontally from an operable opening in an adjacent building.
Exception: This shall not apply to vent terminals that are 2 feet (610 mm) or more above or 25 feet (7620 mm) or more below operable openings. [NFPA 54:12.9.6]
Provision shall be made to collect and dispose of condensate from venting systems serving Category II and Category IV appliances and noncategorized condensing appliances in accordance with Section 802.8.3. [NFPA 54:12.10.1]
Where local experience indicates that condensation is a problem, provision shall be made to drain off and dispose of condensate from venting systems serving Category I and Category III appliances in accordance with Section 802.8.3. [NFPA 54:12.10.2]
A vent connector shall be used to connect an appliance to a gas vent, chimney, or single-wall metal pipe, except where the gas vent, chimney, or single-wall metal pipe is directly connected to the appliance. [NFPA 54:12.11.1]
A vent connector shall be made of noncombustible, corrosion resistant material capable of withstanding the vent gas temperature produced by the appliance and of a thickness to withstand physical damage. [NFPA 54:12.11.2.1]
Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through an unconditioned area, attic or crawl space, that portion of the vent connector shall be listed Type B, Type L, or listed vent material having equivalent insulation qualities.

Exception: Single-wall metal pipe located within the exterior walls of the building and located in an unconditioned area other than an attic or a crawl space having a local 99 percent winter design temperature of 5°F (-15°C) or higher. [NFPA 54:12.11.2.2]
Vent connectors for residential-type appliances shall comply with the following:
  1. Vent connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners, and Category I appliances that are not installed in attics, crawl spaces, or other unconditioned areas shall be one of the following:
    1. Type B or Type L vent material.
    2. Galvanized sheet steel not less than 0.018 of an inch (0.457 mm) thick.
    3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 of an inch (0.686 mm) thick.
    4. Stainless steel sheet not less than 0.012 of an inch (0.305 mm) thick.
    5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Section 802.10.1.2(1)(b), Section 802.10.1.2(1)(c), or Section 802.10.1.2(1)(d).
    6. A listed vent connector.
  2. Vent connectors shall not be covered with insulation.
Exception: Listed insulated vent connectors shall be installed in accordance with the manufacturer's installation instructions. [NFPA 54:12.11.2.3]
A vent connector for a nonresidential low-heat appliance shall be a factory-built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 802.10.1.3. Factory-built chimney sections shall be joined together in accordance with the chimney manufacturer's instructions. [NFPA 54:12.11.2.4]

TABLE 802.10.1.3
MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW-HEAT APPLIANCES
[NFPA 54: TABLE 12.11.2.4]
DIAMETER OF CONNECTOR
(inches)
MINIMUM THICKNESS
(inches)
Less than 6 0.019
6 to less than 10 0.023
10 to 12 inclusive 0.029
14 to 16 inclusive 0.034
Over 16 0.056
For SI units: 1 inch = 25.4 mm, 1 square inch = 0.000645 m2
Vent connectors for medium-heat appliances shall be constructed of factory-built, medium-heat chimney sections or steel of a thickness not less than that specified in Table 802.10.1.4 and shall comply with the following:
  1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000°F (538°C) measured at the entrance to the connector shall be lined with medium-duty fire brick or the equivalent.
  2. The lining shall be at least 21/2 inches (64 mm) thick for a vent connector having a diameter or greatest cross-sectional dimension of 18 inches (457 mm) or less.
  3. The lining shall be at least 41/2 inches (114 mm) thick laid on the 41/2 inches (114 mm) bed for a vent connector having a diameter or greatest cross-sectional dimension greater than 18 inches (457 mm).
  4. Factory-built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer's instructions. [NFPA 54:12.11.2.5]
TABLE 802.10.1.4
MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM-HEAT APPLIANCES
[NFPA 54:TABLE 12.11.2.5]
VENT CONNECTOR SIZE
DIAMETER
(inches)
AREA
(square inches)
MINIMUM THICKNESS
(inches)
Up to 14 Up to 154 0.053
Over 14 to 16 154 to 201 0.067
Over 16 to 18 201 to 254 0.093
Over 18 Larger than 254 0.123
For SI units: 1 inch= 25.4 mm, 1 square inch= 0.000645 m2
A vent connector for an appliance with a single draft hood or for a Category I fan-assisted combustion system appliance shall be sized and installed in accordance with Section 803.0 or other approved engineering methods. [NFPA 54:12.11.3.1]
For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternative method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets, and the vent connectors shall have a minimum 1 foot (305 mm) rise. [NFPA 54:12.11.3.2]
Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 803.0 or other approved engineering methods. [NFPA 54:12.11.3.3]
As an alternative method applicable where the appliances are draft hood-equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. [NFPA 54:12.11.3.4]
Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highest level consistent with available headroom and clearance to combustible material and sized in accordance with Section 803.0 or other approved engineering methods. [NFPA 54:12.11.3.5]
As an alternative method applicable only where there are two draft hood-equipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 50 percent of the area of the smaller flue collar outlet. [NFPA 54:12.11.3.6]
Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. [NFPA 54:12.11.3.7
Where two or more openings are provided into one chimney flue or vent, either of the following shall apply:
  1. The openings shall be at different levels.
  2. The connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees or less relative to the vertical. [NFPA 54:12.11.4.1]
Where two or more vent connectors enter a common vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. [NFPA 54:12.11.4.2]
Vent connectors serving Category I appliances shall not be connected to a portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. [NFPA 54:12.11.4.3]
Minimum clearances from vent connectors to combustible material shall comply with Table 802.7.3.3.
Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 303.10.1. [NFPA 54:12.11.5]
Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods:
  1. Sheet metal screws.
  2. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer's instructions.
  3. Other approved means. [NFPA 54:12.11.6]
A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least 1/4 inch per foot (20.8 mm/m).
Exception: Vent connectors attached to a mechanical draft system installed in accordance with appliance and the draft system manufacturers' instructions. [NFPA 54:12.11.7]
The length of vent connectors shall comply with Section 802.10.7.1 or Section 802.10.7.2.
The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent except for engineered systems. [NFPA 54:12.11.8.1]
The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent. [NFPA 54:12.11.8.2]
A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. [NFPA 54:12.11.9]
Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the connector shall be attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue. [NFPA 54:12.11.10]
The entire length of a vent connector shall be readily accessible for inspection, cleaning, and replacement. [NFPA 54:12.11.11]
A vent connector shall not be connected to a chimney flue serving a fireplace unless the fireplace flue opening is permanently sealed. [NFPA 54:12.11.12]
A vent connector shall not pass through a ceiling, floor, or fire-resistance-rated wall. A single-wall metal pipe connector shall not pass through an interior wall.
Exception: Vent connectors made of listed Type B or Type L vent material and serving listed appliances with draft hoods and other appliances listed for use with Type B gas vents that pass through walls or partitions constructed of combustible material shall be installed with not less than the listed clearance to combustible material.
Vent connectors for medium-heat appliances shall not pass through walls or partitions constructed of combustible material. [NFPA 54:12.11.13.2]
The vent connectors for Category II, Category III, and Category IV appliances shall be in accordance with Section 802.4 through Section 802.4.3. [NFPA 54:12.12]
Vented appliances shall be installed with draft hoods.
Exception: Dual oven-type combination ranges; incinerators; direct-vent appliances; fan-assisted combustion system appliances; appliances requiring chimney draft for operation; single firebox boilers equipped with conversion burners with inputs exceeding 400 000 Btu/h (117 kW); appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods; and appliances designed for forced venting.
A draft hood supplied with or forming a part of listed vented appliances shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. [NFPA 54:12.13.2]
Where a draft hood is not supplied by the appliance manufacturer where one is required, a draft hood shall be installed, be of a listed or approved type, and, in the absence of other instructions, be of the same size as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. [NFPA 54:12.13.2.1]
Where a draft hood of special design is needed or preferable, the installation shall be approved and in accordance with the recommendations of the appliance manufacturer. [NFPA 54:12.13.2.2]
Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer's instructions. In the absence of manufacturer's instructions, the device shall be attached to the flue collar of the appliance or as near to the appliance as practical. [NFPA 54:12.13.3]
Appliances requiring controlled chimney draft shall be permitted to be equipped with listed double-acting barometric draft regulators installed and adjusted in accordance with the manufacturer's installation instructions. [NFPA 54:12.13.4]
Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent a difference in pressure between the hood or regulator and the combustion air supply. [NFPA 54:12.13.5]
Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by a part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checking vent operation. [NFPA 54:12.13.6]
A draft hood shall be located so that its relief opening is not less than 6 inches (152 mm) from a surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser clearance is indicated on the appliance label, the clearance shall not be less than that specified on the label. Such clearances shall not be reduced. [NFPA 54:12.13.7]
A manually operated damper shall not be placed in an appliance vent connector. Fixed baffles shall not be classified as manually operated dampers. [NFPA 54:12.14]
Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney, or vent. The following shall not be considered as obstructions:
  1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the manufacturer's installation instructions.
  2. Approved draft regulators and safety controls designed and installed in accordance with approved engineering methods.
  3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the manufacturer's installation instructions.
  4. Vent dampers serving listed appliances installed in accordance with Section 803.1 or Section 803.2 or other approved engineering methods.
  5. Approved economizers, heat reclaimers, and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided the appliance manufacturer's installation instructions cover the installation of such a device in the venting system and performance in accordance with Section 802.3 and Section 802.3.1 is obtained. [NFPA 54:12.16]
An automatically operated vent damper shall be of a listed type. [NFPA 54:12.15]
Automatically operated vent dampers for oil-fired appliances shall comply with UL 17. The automatic damper control shall comply with UL 378.
Table 803.1.2(1) through Table 803.1.2(6) shall not be used where obstructions are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer's installation instructions or in accordance with the following:
  1. The maximum capacity of the vent system shall be determined using the NAT Max column.
  2. The minimum capacity shall be determined as though the appliance were a fan-assisted appliance, using the FAN Min column to determine the minimum capacity of the vent system. Where the corresponding "FAN Min" is "NA", the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. [NFPA 54:13.1.1]
Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the use of the smaller size shall be permitted provided that the installation is in accordance with the following requirements:
  1. The total vent height (H) is not less than 10 feet (3048 mm).
  2. Vents for appliance draft hood outlets or flue collars 12 inches (305mm) in diameter or smaller are not reduced more than one table size.
  3. Vents for appliance draft hood outlets or flue collars exceeding 12 inches (305 mm) in diameter are not reduced more than two table sizes.
  4. The maximum capacity listed in the tables for a fan-assisted appliance is reduced by 10 percent (0.90 × maximum table capacity).
  5. The draft hood outlet exceeds 4 inches (102 mm) in diameter. A 3 inch (76 mm) diameter vent shall not be connected to a 4 inch (102 mm) diameter draft hood outlet. This provision shall not apply to fan-assisted appliances. [NFPA 54:13.1.2]
Single-appliance venting configurations with zero (0) lateral lengths in Table 803.1.2(1), Table 803.1.2(2), and Table 803.1.2(5) shall not have elbows in the venting system. Single-appliance venting with lateral length, include two 90 degree elbows. For each additional elbow up to and including 45 degrees, the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees up to and including 90 degrees, the maximum capacity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Table 803.1.2(1) through Table 803.1.2(5). [NFPA 54:13.1.3]
99% Winter Design Temperatures for the Contiguous United States
This map is a necessarily generalized guide to temperatures in the contiguous United States. Temperatures shown for areas such as mountainous regions and large urban centers may not be accurate. The data used to develop this map are from the 1993 ASHRAE Handbook — Fundamentals (Chapter 24, Table 1: Climate Conditions for the United States).
For 99% winter design temperatures in Alaska, consult the ASHRAE Handbook — Fundamentals.
99% winter design temperatures for Hawaii are greater than 37°F
For SI units: °C = (°F—32)/1.8
FIGURE 803.1.2(6)
RANGE OF WINTER DESIGN TEMPERATURES USED IN ANALYZING EXTERIOR MASONRY CHIMNEYS IN THE UNITED STATES
[NFPA 54: FIGURE F.2.4]

 
TABLE 803.1.2(1)
TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)]*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT
  VENT DIAMETER — D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6
0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285
2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217
4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211
6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205
8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320
2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247
5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237
8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227
10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345
2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273
5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263
10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245
15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390
2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316
5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300
10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288
15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275
20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430
2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346
5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337
10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321
15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308
20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295
30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475
2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394
5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385
10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371
15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357
20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343
30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321
50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518
2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445
5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438
10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426
15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413
20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401
30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376
100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560
2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510
5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504
10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493
15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482
20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471
30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449
50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(1)
TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)] (continued)
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT
  VENT DIAMETER — D (inch)
8 9 10 12 14
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0 0 698 370 0 897 470 0 1121 570 0 1645 850 0 2267 1170
2 53 425 285 63 543 370 75 675 455 103 982 650 138 1346 890
4 79 419 279 93 536 362 110 668 445 147 975 640 191 1338 880
6 93 413 273 110 530 354 128 661 435 171 967 630 219 1330 870
8 0 0 780 415 0 1006 537 0 1261 660 0 1858 970 0 2571 1320
2 50 483 322 60 619 418 71 770 515 98 1124 745 130 1543 1020
5 83 473 313 99 607 407 115 758 503 154 1110 733 199 1528 1010
8 99 463 303 117 596 396 137 746 490 180 1097 720 231 1514 1000
10 0 0 847 450 0 1096 585 0 1377 720 0 2036 1060 0 2825 1450
2 48 533 355 57 684 457 68 852 560 93 1244 850 124 1713 1130
5 81 522 346 95 671 446 112 839 547 149 1229 829 192 1696 1105
10 104 504 330 122 651 427 142 817 525 187 1204 795 238 1669 1080
15 0 0 970 525 0 1263 682 0 1596 840 0 2380 1240 0 3323 1720
2 45 633 414 53 815 544 63 1019 675 86 1495 985 114 2062 1350
5 76 620 403 90 800 529 105 1003 660 140 1476 967 182 2041 1327
10 99 600 386 116 777 507 135 977 635 177 1446 936 227 2009 1289
15 115 580 373 134 755 491 155 953 610 202 1418 905 257 1976 1250
20 0 0 1057 575 0 1384 752 0 1756 930 0 2637 1350 0 3701 1900
2 41 711 470 50 917 612 59 1150 755 81 1694 1100 107 2343 1520
5 73 697 460 86 902 599 101 1133 738 135 1674 1079 174 2320 1498
10 95 675 443 112 877 576 130 1105 710 172 1641 1045 220 2282 1460
15 111 654 427 129 853 557 150 1078 688 195 1609 1018 248 2245 1425
20 125 634 410 145 830 537 167 1052 665 217 1578 990 273 2210 1390
30 0 0 1173 650 0 1548 855 0 1977 1060 0 3004 1550 0 4252 2170
2 33 826 535 42 1072 700 54 1351 865 74 2004 1310 98 2786 1800
5 69 811 524 82 1055 688 96 1332 851 127 1981 1289 164 2759 1775
10 91 788 507 107 1028 668 125 1301 829 164 1944 1254 209 2716 1733
15 105 765 490 124 1002 648 143 1272 807 187 1908 1220 237 2674 1692
20 119 743 473 139 977 628 160 1243 784 207 1873 1185 260 2633 1650
30 149 702 444 171 929 594 195 1189 745 246 1807 1130 305 2555 1585
50 0 0 1297 708 0 1730 952 0 2231 1195 0 3441 1825 0 4934 2550
2 26 975 615 33 1276 813 41 1620 1010 66 2431 1513 86 3409 2125
5 65 960 605 77 1259 798 90 1600 996 118 2406 1495 151 3380 2102
10 86 935 589 101 1230 773 118 1567 972 154 2366 1466 196 3332 2064
15 100 911 572 117 1203 747 136 1536 948 177 2327 1437 222 3285 2026
20 113 888 556 131 1176 722 151 1505 924 195 2288 1408 244 3239 1987
30 141 844 522 161 1125 670 183 1446 876 232 2214 1349 287 3150 1910
100 0 0 1411 770 0 1908 1040 0 2491 1310 0 3925 2050 0 5729 2950
2 21 1155 700 25 1536 935 30 1975 1170 44 3027 1820 72 4313 2550
5 60 1141 692 71 1519 926 82 1955 1159 107 3002 1803 136 4282 2531
10 80 1118 679 94 1492 910 108 1923 1142 142 2961 1775 180 4231 2500
15 93 1095 666 109 1465 895 126 1892 1124 163 2920 1747 206 4182 2469
20 105 1073 653 122 1438 880 141 1861 1107 181 2880 1719 226 4133 2438
30 131 1029 627 149 1387 849 170 1802 1071 215 2803 1663 265 4037 2375
50 197 944 575 217 1288 787 241 1688 1000 292 2657 1550 350 3856 2250
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
 
TABLE 803.1.2(1)
TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(a)] (continued)
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: CONNECTED DIRECTLY TO VENT
  VENT DIAMETER — D (inch)
16 18 20 22 24
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0 0 2983 1530 0 3802 1960 0 4721 2430 0 5737 2950 0 6853 3520
2 178 1769 1170 225 2250 1480 296 2782 1850 360 3377 2220 426 4030 2670
4 242 1761 1160 300 2242 1475 390 2774 1835 469 3370 2215 555 4023 2660
6 276 1753 1150 341 2235 1470 437 2767 1820 523 3363 2210 618 4017 2650
8 0 0 3399 1740 0 4333 2220 0 5387 2750 0 6555 3360 0 7838 4010
2 168 2030 1340 212 2584 1700 278 3196 2110 336 3882 2560 401 4634 3050
5 251 2013 1330 311 2563 1685 398 3180 2090 476 3863 2545 562 4612 3040
8 289 2000 1320 354 2552 1670 450 3163 2070 537 3850 2530 630 4602 3030
10 0 0 3742 1925 0 4782 2450 0 5955 3050 0 7254 3710 0 8682 4450
2 161 2256 1480 202 2868 1890 264 3556 2340 319 4322 2840 378 5153 3390
5 243 2238 1461 300 2849 1871 382 3536 2318 458 4301 2818 540 5132 3371
10 298 2209 1430 364 2818 1840 459 3504 2280 546 4268 2780 641 5099 3340
15 0 0 4423 2270 0 5678 2900 0 7099 3620 0 8665 4410 0 10 393 5300
2 147 2719 1770 186 3467 2260 239 4304 2800 290 5232 3410 346 6251 4080
5 229 2696 1748 283 3442 2235 355 4278 2777 426 5204 3385 501 6222 4057
10 283 2659 1712 346 3402 2193 432 4234 2739 510 5159 3343 599 6175 4019
15 318 2623 1675 385 3363 2150 479 4192 2700 564 5115 3300 665 6129 3980
20 0 0 4948 2520 0 6376 3250 0 7988 4060 0 9785 4980 0 11 753 6000
2 139 3097 2000 175 3955 2570 220 4916 3200 269 5983 3910 321 7154 4700
5 219 3071 1978 270 3926 2544 337 4885 3174 403 5950 3880 475 7119 4662
10 273 3029 1940 334 3880 2500 413 4835 3130 489 5896 3830 573 7063 4600
15 306 2988 1910 372 3835 2465 459 4786 3090 541 5844 3795 631 7007 4575
20 335 2948 1880 404 3791 2430 495 4737 3050 585 5792 3760 689 6953 4550
30 0 0 5725 2920 0 7420 3770 0 9341 4750 0 11 483 5850 0 13 848 7060
2 127 3696 2380 159 4734 3050 199 5900 3810 241 7194 4650 285 8617 5600
5 206 3666 2350 252 4701 3020 312 5863 3783 373 7155 4622 439 8574 5552
10 259 3617 2300 316 4647 2970 386 5803 3739 456 7090 4574 535 8505 5471
15 292 3570 2250 354 4594 2920 431 5744 3695 507 7026 4527 590 8437 5391
20 319 3523 2200 384 4542 2870 467 5686 3650 548 6964 4480 639 8370 5310
30 369 3433 2130 440 4442 2785 540 5574 3565 635 6842 4375 739 8239 5225
50 0 0 6711 3440 0 8774 4460 0 11 129 5635 0 13 767 6940 0 16 694 8430
2 113 4554 2840 141 5864 3670 171 7339 4630 209 8980 5695 251 10 788 6860
5 191 4520 2813 234 5826 3639 283 7295 4597 336 8933 5654 394 10 737 6818
10 243 4464 2767 295 5763 3585 355 7224 4542 419 8855 5585 491 10 652 6749
15 274 4409 2721 330 5701 3534 396 7155 4511 465 8779 5546 542 10 570 6710
20 300 4356 2675 361 5641 3481 433 7086 4479 506 8704 5506 586 10 488 6670
30 347 4253 2631 412 5523 3431 494 6953 4421 577 8557 5444 672 10 328 6603
100 0 0 7914 4050 0 10 485 5300 0 13 454 6700 0 16 817 8600 0 20 578 10 300
2 95 5834 3500 120 7591 4600 138 9577 5800 169 11 803 7200 204 14 264 8800
5 172 5797 3475 208 7548 4566 245 9528 5769 293 11 748 7162 341 14 204 8756
10 223 5737 3434 268 7478 4509 318 9447 5717 374 11 658 7100 436 14 105 8683
15 252 5678 3392 304 7409 4451 358 9367 5665 418 11 569 7037 487 14 007 8610
20 277 5619 3351 330 7341 4394 387 9289 5613 452 11 482 6975 523 13 910 8537
30 319 5505 3267 378 7209 4279 446 9136 5509 514 11 310 6850 592 13 720 8391
50 415 5289 3100 486 6956 4050 572 8841 5300 659 10 979 6600 752 13 354 8100
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
 
TABLE 803.1.2(2)
TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(b)]*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR
  VENT DIAMETER — D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0 38 77 45 59 151 85 85 249 140 126 373 204 165 522 284
2 39 51 36 60 96 66 85 156 104 123 231 156 159 320 213
4 NA NA 33 74 92 63 102 152 102 146 225 152 187 313 208
6 NA NA 31 83 89 60 114 147 99 163 220 148 207 307 203
8 0 37 83 50 58 164 93 83 273 154 123 412 234 161 580 319
2 39 56 39 59 108 75 83 176 119 121 261 179 155 363 246
5 NA NA 37 77 102 69 107 168 114 151 252 171 193 352 235
8 NA NA 33 90 95 64 122 161 107 175 243 163 223 342 225
10 0 37 87 53 57 174 99 82 293 165 120 444 254 158 628 344
2 39 61 41 59 117 80 82 193 128 119 287 194 153 400 272
5 52 56 39 76 111 76 105 185 122 148 277 186 190 388 261
10 NA NA 34 97 100 68 132 171 112 188 261 171 237 369 241
15 0 36 93 57 56 190 111 80 325 186 116 499 283 153 713 388
2 38 69 47 57 136 93 80 225 149 115 337 224 148 473 314
5 51 63 44 75 128 86 102 216 140 144 326 217 182 459 298
10 NA NA 39 95 116 79 128 201 131 182 308 203 228 438 284
15 NA NA NA NA NA 72 158 186 124 220 290 192 272 418 269
20 0 35 96 60 54 200 118 78 346 201 114 537 306 149 772 428
2 37 74 50 56 148 99 78 248 165 113 375 248 144 528 344
5 50 68 47 73 140 94 100 239 158 141 363 239 178 514 334
10 NA NA 41 93 129 86 125 223 146 177 344 224 222 491 316
15 NA NA NA NA NA 80 155 208 136 216 325 210 264 469 301
20 NA NA NA NA NA NA 186 192 126 254 306 196 309 448 285
30 0 34 99 63 53 211 127 76 372 219 110 584 334 144 849 472
2 37 80 56 55 164 111 76 281 183 109 429 279 139 610 392
5 49 74 52 72 157 106 98 271 173 136 417 271 171 595 382
10 NA NA NA 91 144 98 122 255 168 171 397 257 213 570 367
15 NA NA NA 115 131 NA 151 239 157 208 377 242 255 547 349
20 NA NA NA NA NA NA 181 223 NA 246 357 228 298 524 333
30 NA NA NA NA NA NA NA NA NA NA NA NA 389 477 305
50 0 33 99 66 51 213 133 73 394 230 105 629 361 138 928 515
2 36 84 61 53 181 121 73 318 205 104 495 312 133 712 443
5 48 80 NA 70 174 117 94 308 198 131 482 305 164 696 435
10 NA NA NA 89 160 NA 118 292 186 162 461 292 203 671 420
15 NA NA NA 112 148 NA 145 275 174 199 441 280 244 646 405
20 NA NA NA NA NA NA 176 257 NA 236 420 267 285 622 389
30 NA NA NA NA NA NA NA NA NA 315 376 NA 373 573 NA
100 0 NA NA NA 49 214 NA 69 403 NA 100 659 395 131 991 555
2 NA NA NA 51 192 NA 70 351 NA 98 563 373 125 828 508
5 NA NA NA 67 186 NA 90 342 NA 125 551 366 156 813 501
10 NA NA NA 85 175 NA 113 324 NA 153 532 354 191 789 486
15 NA NA NA 132 162 NA 138 310 NA 188 511 343 230 764 473
20 NA NA NA NA NA NA 168 295 NA 224 487 NA 270 739 458
30 NA NA NA NA NA NA 231 264 NA 301 448 NA 355 685 NA
50 NA NA NA NA NA NA NA NA NA NA NA NA 540 584 NA
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(2)
TYPE B DOUBLE-WALL GAS VENT [NFPA 54: TABLE 13.1(b)] (continued)*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR
  VENT DIAMETER — D (inch)
8 9 10 12
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 0 211 695 369 267 894 469 371 1118 569 537 1639 849
2 201 423 284 251 541 368 347 673 453 498 979 648
4 237 416 277 295 533 360 409 664 443 584 971 638
6 263 409 271 327 526 352 449 656 433 638 962 627
8 0 206 777 414 258 1002 536 360 1257 658 521 1852 967
2 197 482 321 246 617 417 339 768 513 486 1120 743
5 245 470 311 305 604 404 418 754 500 598 1104 730
8 280 458 300 344 591 392 470 740 486 665 1089 715
10 0 202 844 449 253 1093 584 351 1373 718 507 2031 1057
2 193 531 354 242 681 456 332 849 559 475 1242 848
5 241 518 344 299 667 443 409 834 544 584 1224 825
10 296 497 325 363 643 423 492 808 520 688 1194 788
15 0 195 966 523 244 1259 681 336 1591 838 488 2374 1237
2 187 631 413 232 812 543 319 1015 673 457 1491 983
5 231 616 400 287 795 526 392 997 657 562 1469 963
10 284 592 381 349 768 501 470 966 628 664 1433 928
15 334 568 367 404 742 484 540 937 601 750 1399 894
20 0 190 1053 573 238 1379 750 326 1751 927 473 2631 1346
2 182 708 468 227 914 611 309 1146 754 443 1689 1098
5 224 692 457 279 896 596 381 1126 734 547 1665 1074
10 277 666 437 339 866 570 457 1092 702 646 1626 1037
15 325 640 419 393 838 549 526 1060 677 730 1587 1005
20 374 616 400 448 810 526 592 1028 651 808 1550 973
30 0 184 1168 647 229 1542 852 312 1971 1056 454 2996 1545
2 175 823 533 219 1069 698 296 1346 863 424 1999 1308
5 215 806 521 269 1049 684 366 1324 846 524 1971 1283
10 265 777 501 327 1017 662 440 1287 821 620 1927 1243
15 312 750 481 379 985 638 507 1251 794 702 1884 1205
20 360 723 461 433 955 615 570 1216 768 780 1841 1166
30 461 670 426 541 895 574 704 1147 720 937 1759 1101
50 0 176 1292 704 220 1724 948 295 2223 1189 428 3432 1818
2 168 971 613 209 1273 811 280 1615 1007 401 2426 1509
5 204 953 602 257 1252 795 347 1591 991 496 2396 1490
10 253 923 583 313 1217 765 418 1551 963 589 2347 1455
15 299 894 562 363 1183 736 481 1512 934 668 2299 1421
20 345 866 543 415 1150 708 544 1473 906 741 2251 1387
30 442 809 502 521 1086 649 674 1399 848 892 2159 1318
100 0 166 1404 765 207 1900 1033 273 2479 1300 395 3912 2042
2 158 1152 698 196 1532 933 259 1970 1168 371 3021 1817
5 194 1134 688 240 1511 921 322 1945 1153 460 2990 1796
10 238 1104 672 293 1477 902 389 1905 1133 547 2938 1763
15 281 1075 656 342 1443 884 447 1865 1110 618 2888 1730
20 325 1046 639 391 1410 864 507 1825 1087 690 2838 1696
30 418 988 NA 491 1343 824 631 1747 1041 834 2739 1627
50 617 866 NA 711 1205 NA 895 1591 NA 1138 2547 1489
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(3)
MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)]*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
  TYPE B DOUBLE-WALL CONNECTOR DIAMETER — D (inch)
TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM
3 4 5 6 7
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180
5 NA NA 25 NA NA 49 NA NA 82 NA NA 117 NA NA 165
8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 198
5 NA NA 26 NA NA 52 NA NA 88 NA NA 134 NA NA 183
8 NA NA 24 NA NA 48 NA NA 83 NA NA 127 NA NA 175
10 2 NA NA 31 NA NA 61 NA NA 103 NA NA 162 NA NA 221
5 NA NA 28 NA NA 57 NA NA 96 NA NA 148 NA NA 204
10 NA NA 25 NA NA 50 NA NA 87 NA NA 139 NA NA 191
15 2 NA NA 35 NA NA 67 NA NA 114 NA NA 179 53 475 250
5 NA NA 35 NA NA 62 NA NA 107 NA NA 164 NA NA 231
10 NA NA 28 NA NA 55 NA NA 97 NA NA 153 NA NA 216
15 NA NA NA NA NA 48 NA NA 89 NA NA 141 NA NA 201
20 2 NA NA 38 NA NA 74 NA NA 124 NA NA 201 51 522 274
5 NA NA 36 NA NA 68 NA NA 116 NA NA 184 80 503 254
10 NA NA NA NA NA 60 NA NA 107 NA NA 172 NA NA 237
15 NA NA NA NA NA NA NA NA 97 NA NA 159 NA NA 220
20 NA NA NA NA NA NA NA NA 83 NA NA 148 NA NA 206
30 2 NA NA 41 NA NA 82 NA NA 137 NA NA 216 47 581 303
5 NA NA NA NA NA 76 NA NA 128 NA NA 198 75 561 281
10 NA NA NA NA NA 67 NA NA 115 NA NA 184 NA NA 263
15 NA NA NA NA NA NA NA NA 107 NA NA 171 NA NA 243
20 NA NA NA NA NA NA NA NA 91 NA NA 159 NA NA 227
30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 188
50 2 NA NA NA NA NA 92 NA NA 161 NA NA 251 NA NA 351
5 NA NA NA NA NA NA NA NA 151 NA NA 230 NA NA 323
10 NA NA NA NA NA NA NA NA 138 NA NA 215 NA NA 304
15 NA NA NA NA NA NA NA NA 127 NA NA 199 NA NA 282
20 NA NA NA NA NA NA NA NA NA NA NA 185 NA NA 264
30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA
Minimum internal area of chimney
(square inches)
12 19 28 38 50
Maximum internal area of chimney
(square inches)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(3)
MASONRY CHIMNEY [NFPA 54: TABLE 13.1(c)] (continued)*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
  TYPE B DOUBLE-WALL CONNECTOR DIAMETER — D (inch)
TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM
8 9 10 12
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 2 NA NA 247 NA NA 320 NA NA 401 NA NA 581
5 NA NA 231 NA NA 298 NA NA 376 NA NA 561
8 2 NA NA 266 84 590 350 100 728 446 139 1024 651
5 NA NA 247 NA NA 328 149 711 423 201 1007 640
8 NA NA 239 NA NA 318 173 695 410 231 990 623
10 2 68 519 298 82 655 388 98 810 491 136 1144 724
5 NA NA 277 124 638 365 146 791 466 196 1124 712
10 NA NA 263 155 610 347 182 762 444 240 1093 668
15 2 64 613 336 77 779 441 92 968 562 127 1376 841
5 99 594 313 118 759 416 139 946 533 186 1352 828
10 126 565 296 148 727 394 173 912 567 229 1315 777
15 NA NA 281 171 698 375 198 880 485 259 1280 742
20 2 61 678 375 73 867 491 87 1083 627 121 1548 953
5 95 658 350 113 845 463 133 1059 597 179 1523 933
10 122 627 332 143 811 440 167 1022 566 221 1482 879
15 NA NA 314 165 780 418 191 987 541 251 1443 840
20 NA NA 296 186 750 397 214 955 513 277 1406 807
30 2 57 762 421 68 985 558 81 1240 717 111 1793 1112
5 90 741 393 106 962 526 125 1216 683 169 1766 1094
10 115 709 373 135 927 500 158 1176 648 210 1721 1025
15 NA NA 353 156 893 476 181 1139 621 239 1679 981
20 NA NA 332 176 860 450 203 1103 592 264 1638 940
30 NA NA 288 NA NA 416 249 1035 555 318 1560 877
50 2 51 840 477 61 1106 633 72 1413 812 99 2080 1243
5 83 819 445 98 1083 596 116 1387 774 155 2052 1225
10 NA NA 424 126 1047 567 147 1347 733 195 2006 1147
15 NA NA 400 146 1010 539 170 1307 702 222 1961 1099
20 NA NA 376 165 977 511 190 1269 669 246 1916 1050
30 NA NA 327 NA NA 468 233 1196 623 295 1832 984
Minimum internal area of chimney
(square inches)
63 78 95 132
Maximum internal area of chimney
(square inches)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(4)
MASONRY CHIMNEY [NFPA 54: TABLE 13.1(d)]*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR
  SINGLE-WALL METAL CONNECTOR DIAMETER — D (inch)
TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM
3 4 5 6 7
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180
5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164
8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197
5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182
8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174
10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220
5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203
10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189
15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249
5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230
10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214
15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198
20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273
5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 NA NA 252
10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235
15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217
20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202
30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302
5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279
10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260
15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240
20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223
30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182
50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350
5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321
10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301
15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278
20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258
30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA
Minimum internal area of chimney
(square inches)
12 19 28 38 50
Maximum internal area of chimney
(square inches)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 square inch = 0.000645 m2
* NA: Not applicable.
 
TABLE 803.1.2(4)
MASONRY CHIMNEY [NFPA 54: TABLE 13.1(d)] (continued)*
  NUMBER OF APPLIANCES: SINGLE
APPLIANCE TYPE: CATEGORY I
APPLIANCE VENT CONNECTION: SINGLE-WALL METAL CONNECTOR
  SINGLE-WALL METAL CONNECTOR DIAMETER — D (inch)
TO BE USED WITH CHIMNEY AREAS WITHIN THE SIZE LIMITS AT BOTTOM
8 9 10 12
APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR
HEIGHT
H
(feet)
LATERAL
L
(feet)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 2 NA NA 247 NA NA 319 NA NA 400 NA NA 580
5 NA NA 230 NA NA 297 NA NA 375 NA NA 560
8 2 NA NA 265 NA NA 349 382 725 445 549 1021 650
5 NA NA 246