User note:
About this chapter: Chapter 3 covers general regulations for energy conservation features of buildings. The climate zone for a building is established by geographic location tables and figures in this chapter.
Climate zones from Figure R301.1 or Table R301.1 shall be used for determining the applicable requirements from Chapter 4. Locations not indicated in Table R301.1 shall be assigned a climate zone in accordance with Section R301.3.

CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID DESIGNATIONS BY STATE, COUNTY AND TERRITORY
Key: A — Moist, B — Dry, C — Marine. Absence of moisture designation indicates moisture regime is irrelevant. Asterisk (*) indicates a warm-humid location.
US STATES |
ALABAMA |
3A Autauga* |
2A Baldwin* |
3A Barbour* |
3A Bibb |
3A Blount |
3A Bullock* |
3A Butler* |
3A Calhoun |
3A Chambers |
3A Cherokee |
3A Chilton |
3A Choctaw* |
3A Clarke* |
3A Clay |
3A Cleburne |
3A Coffee* |
3A Colbert |
3A Conecuh* |
3A Coosa |
3A Covington* |
3A Crenshaw* |
3A Cullman |
3A Dale* |
3A Dallas* |
3A DeKalb |
3A Elmore* |
3A Escambia* |
3A Etowah |
3A Fayette |
3A Franklin |
3A Geneva* |
3A Greene |
3A Hale |
3A Henry* |
3A Houston* |
3A Jackson |
3A Jefferson |
3A Lamar |
3A Lauderdale |
3A Lawrence |
3A Lee |
3A Limestone |
3A Lowndes* |
3A Macon* |
3A Madison |
3A Marengo* |
3A Marion |
3A Marshall |
2A Mobile* |
3A Monroe* |
3A Montgomery* |
3A Morgan |
3A Perry* |
3A Pickens |
3A Pike* |
3A Randolph |
3A Russell* |
3A Shelby |
3A St. Clair |
3A Sumter |
3A Talladega |
3A Tallapoosa |
3A Tuscaloosa |
3A Walker |
3A Washington* |
3A Wilcox* |
3A Winston |
ALASKA |
7 Aleutians East |
7 Aleutians West |
7 Anchorage |
8 Bethel |
7 Bristol Bay |
7 Denali |
8 Dillingham |
8 Fairbanks North Star |
7 Haines |
7 Juneau |
7 Kenai Peninsula |
7 Ketchikan Gateway |
7 Kodiak Island |
7 Lake and Peninsula |
7 Matanuska-Susitna |
8 Nome |
8 North Slope |
8 Northwest Arctic |
7 Prince of Wales Outer Ketchikan |
7 Sitka |
7 Skagway-Hoonah-Angoon |
8 Southeast Fairbanks |
7 Valdez-Cordova |
8 Wade Hampton |
7 Wrangell-Petersburg |
7 Yakutat |
8 Yukon-Koyukuk |
ARIZONA |
5B Apache |
3B Cochise |
5B Coconino |
4B Gila |
3B Graham |
3B Greenlee |
2B La Paz |
2B Maricopa |
3B Mohave |
5B Navajo |
2B Pima |
2B Pinal |
3B Santa Cruz |
4B Yavapai |
2B Yuma |
ARKANSAS |
3A Arkansas |
3A Ashley |
4A Baxter |
4A Benton |
4A Boone |
3A Bradley |
3A Calhoun |
4A Carroll |
3A Chicot |
3A Clark |
3A Clay |
3A Cleburne |
3A Cleveland |
3A Columbia* |
3A Conway |
3A Craighead |
3A Crawford |
3A Crittenden |
3A Cross |
3A Dallas |
3A Desha |
3A Drew |
3A Faulkner |
3A Franklin |
4A Fulton |
3A Garland |
3A Grant |
3A Greene |
3A Hempstead* |
3A Hot Spring |
3A Howard |
3A Independence |
4A Izard |
3A Jackson |
3A Jefferson |
3A Johnson |
3A Lafayette* |
3A Lawrence |
3A Lee |
3A Lincoln |
3A Little River* |
3A Logan |
3A Lonoke |
4A Madison |
4A Marion |
3A Miller* |
3A Mississippi |
3A Monroe |
3A Montgomery |
3A Nevada |
4A Newton |
3A Ouachita |
3A Perry |
3A Phillips |
3A Pike |
3A Poinsett |
3A Polk |
3A Pope |
3A Prairie |
3A Pulaski |
3A Randolph |
3A Saline |
3A Scott |
4A Searcy |
3A Sebastian |
3A Sevier* |
3A Sharp |
3A St. Francis |
4A Stone |
3A Union* |
3A Van Buren |
4A Washington |
3A White |
3A Woodruff |
3A Yell |
CALIFORNIA |
3C Alameda |
6B Alpine |
4B Amador |
3B Butte |
4B Calaveras |
3B Colusa |
3B Contra Costa |
4C Del Norte |
4B El Dorado |
3B Fresno |
3B Glenn |
4C Humboldt |
2B Imperial |
4B Inyo |
3B Kern |
3B Kings |
4B Lake |
5B Lassen |
3B Los Angeles |
3B Madera |
3C Marin |
4B Mariposa |
3C Mendocino |
3B Merced |
5B Modoc |
6B Mono |
3C Monterey |
3C Napa |
5B Nevada |
3B Orange |
3B Placer |
5B Plumas |
3B Riverside |
3B Sacramento |
3C San Benito |
3B San Bernardino |
3B San Diego |
3C San Francisco |
3B San Joaquin |
3C San Luis Obispo |
3C San Mateo |
3C Santa Barbara |
3C Santa Clara |
3C Santa Cruz |
3B Shasta |
5B Sierra |
5B Siskiyou |
3B Solano |
3C Sonoma |
3B Stanislaus |
3B Sutter |
3B Tehama |
4B Trinity |
3B Tulare |
4B Tuolumne |
3C Ventura |
3B Yolo |
3B Yuba |
COLORADO |
5B Adams |
6B Alamosa |
5B Arapahoe |
6B Archuleta |
4B Baca |
5B Bent |
5B Boulder |
5B Broomfield |
6B Chaffee |
5B Cheyenne |
7 Clear Creek |
6B Conejos |
6B Costilla |
5B Crowley |
6B Custer |
5B Delta |
5B Denver |
6B Dolores |
5B Douglas |
6B Eagle |
5B Elbert |
5B El Paso |
5B Fremont |
5B Garfield |
5B Gilpin |
7 Grand |
7 Gunnison |
7 Hinsdale |
5B Huerfano |
7 Jackson |
5B Jefferson |
5B Kiowa |
5B Kit Carson |
7 Lake |
5B La Plata |
5B Larimer |
4B Las Animas |
5B Lincoln |
5B Logan |
5B Mesa |
7 Mineral |
6B Moffat |
5B Montezuma |
5B Montrose |
5B Morgan |
4B Otero |
6B Ouray |
7 Park |
5B Phillips |
7 Pitkin |
5B Prowers |
5B Pueblo |
6B Rio Blanco |
7 Rio Grande |
7 Routt |
6B Saguache |
7 San Juan |
6B San Miguel |
5B Sedgwick |
7 Summit |
5B Teller |
5B Washington |
5B Weld |
5B Yuma |
CONNECTICUT |
5A (all) |
DELAWARE |
4A (all) |
DISTRICT OF COLUMBIA |
4A (all) |
FLORIDA |
2A Alachua* |
2A Baker* |
2A Bay* |
2A Bradford* |
2A Brevard* |
1A Broward* |
2A Calhoun* |
2A Charlotte* |
2A Citrus* |
2A Clay* |
2A Collier* |
2A Columbia* |
2A DeSoto* |
2A Dixie* |
2A Duval* |
2A Escambia* |
2A Flagler* |
2A Franklin* |
2A Gadsden* |
2A Gilchrist* |
2A Glades* |
2A Gulf* |
2A Hamilton* |
2A Hardee* |
2A Hendry* |
2A Hernando* |
2A Highlands* |
2A Hillsborough* |
2A Holmes* |
2A Indian River* |
2A Jackson* |
2A Jefferson* |
2A Lafayette* |
2A Lake* |
2A Lee* |
2A Leon* |
2A Levy* |
2A Liberty* |
2A Madison* |
2A Manatee* |
2A Marion* |
2A Martin* |
1A Miami-Dade* |
1A Monroe* |
2A Nassau* |
2A Okaloosa* |
2A Okeechobee* |
2A Orange* |
2A Osceola* |
2A Palm Beach* |
2A Pasco* |
2A Pinellas* |
2A Polk* |
2A Putnam* |
2A Santa Rosa* |
2A Sarasota* |
2A Seminole* |
2A St. Johns* |
2A St. Lucie* |
2A Sumter* |
2A Suwannee* |
2A Taylor* |
2A Union* |
2A Volusia* |
2A Wakulla* |
2A Walton* |
2A Washington* |
GEORGIA |
2A Appling* |
2A Atkinson* |
2A Bacon* |
2A Baker* |
3A Baldwin |
4A Banks |
3A Barrow |
3A Bartow |
3A Ben Hill* |
2A Berrien* |
3A Bibb |
3A Bleckley* |
2A Brantley* |
2A Brooks* |
2A Bryan* |
3A Bulloch* |
3A Burke |
3A Butts |
3A Calhoun* |
2A Camden* |
3A Candler* |
3A Carroll |
4A Catoosa |
2A Charlton* |
2A Chatham* |
3A Chattahoochee* |
4A Chattooga |
3A Cherokee |
3A Clarke |
3A Clay* |
3A Clayton |
2A Clinch* |
3A Cobb |
3A Coffee* |
2A Colquitt* |
3A Columbia |
2A Cook* |
3A Coweta |
3A Crawford |
3A Crisp* |
4A Dade |
4A Dawson |
2A Decatur* |
3A DeKalb |
3A Dodge* |
3A Dooly* |
3A Dougherty* |
3A Douglas |
3A Early* |
2A Echols* |
2A Effingham* |
3A Elbert |
3A Emanuel* |
2A Evans* |
4A Fannin |
3A Fayette |
4A Floyd |
3A Forsyth |
4A Franklin |
3A Fulton |
4A Gilmer |
3A Glascock |
2A Glynn* |
4A Gordon |
2A Grady* |
3A Greene |
3A Gwinnett |
4A Habersham |
4A Hall |
3A Hancock |
3A Haralson |
3A Harris |
3A Hart |
3A Heard |
3A Henry |
3A Houston* |
3A Irwin* |
3A Jackson |
3A Jasper |
2A Jeff Davis* |
3A Jefferson |
3A Jenkins* |
3A Johnson* |
3A Jones |
3A Lamar |
2A Lanier* |
3A Laurens* |
3A Lee* |
2A Liberty* |
3A Lincoln |
2A Long* |
2A Lowndes* |
4A Lumpkin |
3A Macon* |
3A Madison |
3A Marion* |
3A McDuffie |
2A McIntosh* |
3A Meriwether |
2A Miller* |
2A Mitchell* |
3A Monroe |
3A Montgomery* |
3A Morgan |
4A Murray |
3A Muscogee |
3A Newton |
3A Oconee |
3A Oglethorpe |
3A Paulding |
3A Peach* |
4A Pickens |
2A Pierce* |
3A Pike |
3A Polk |
3A Pulaski* |
3A Putnam |
3A Quitman* |
4A Rabun |
3A Randolph* |
3A Richmond |
3A Rockdale |
3A Schley* |
3A Screven* |
2A Seminole* |
3A Spalding |
4A Stephens |
3A Stewart* |
3A Sumter* |
3A Talbot |
3A Taliaferro |
2A Tattnall* |
3A Taylor* |
3A Telfair* |
3A Terrell* |
2A Thomas* |
3A Tift* |
2A Toombs* |
4A Towns |
3A Treutlen* |
3A Troup |
3A Turner* |
3A Twiggs* |
4A Union |
3A Upson |
4A Walker |
3A Walton |
2A Ware* |
3A Warren |
3A Washington |
2A Wayne* |
3A Webster* |
3A Wheeler* |
4A White |
4A Whitfield |
3A Wilcox* |
3A Wilkes |
3A Wilkinson |
3A Worth* |
HAWAII |
1A (all)* |
IDAHO |
5B Ada |
6B Adams |
6B Bannock |
6B Bear Lake |
5B Benewah |
6B Bingham |
6B Blaine |
6B Boise |
6B Bonner |
6B Bonneville |
6B Boundary |
6B Butte |
6B Camas |
5B Canyon |
6B Caribou |
5B Cassia |
6B Clark |
5B Clearwater |
6B Custer |
5B Elmore |
6B Franklin |
6B Fremont |
5B Gem |
5B Gooding |
5B Idaho |
6B Jefferson |
5B Jerome |
5B Kootenai |
5B Latah |
6B Lemhi |
5B Lewis |
5B Lincoln |
6B Madison |
5B Minidoka |
5B Nez Perce |
6B Oneida |
5B Owyhee |
5B Payette |
5B Power |
5B Shoshone |
6B Teton |
5B Twin Falls |
6B Valley |
5B Washington |
ILLINOIS |
5A Adams |
4A Alexander |
4A Bond |
5A Boone |
5A Brown |
5A Bureau |
5A Calhoun |
5A Carroll |
5A Cass |
5A Champaign |
4A Christian |
5A Clark |
4A Clay |
4A Clinton |
5A Coles |
5A Cook |
4A Crawford |
5A Cumberland |
5A DeKalb |
5A De Witt |
5A Douglas |
5A DuPage |
5A Edgar |
4A Edwards |
4A Effingham |
4A Fayette |
5A Ford |
4A Franklin |
5A Fulton |
4A Gallatin |
5A Greene |
5A Grundy |
4A Hamilton |
5A Hancock |
4A Hardin |
5A Henderson |
5A Henry |
5A Iroquois |
4A Jackson |
4A Jasper |
4A Jefferson |
5A Jersey |
5A Jo Daviess |
4A Johnson |
5A Kane |
5A Kankakee |
5A Kendall |
5A Knox |
5A Lake |
5A La Salle |
4A Lawrence |
5A Lee |
5A Livingston |
5A Logan |
5A Macon |
4A Macoupin |
4A Madison |
4A Marion |
5A Marshall |
5A Mason |
4A Massac |
5A McDonough |
5A McHenry |
5A McLean |
5A Menard |
5A Mercer |
4A Monroe |
4A Montgomery |
5A Morgan |
5A Moultrie |
5A Ogle |
5A Peoria |
4A Perry |
5A Piatt |
5A Pike |
4A Pope |
4A Pulaski |
5A Putnam |
4A Randolph |
4A Richland |
5A Rock Island |
4A Saline |
5A Sangamon |
5A Schuyler |
5A Scott |
4A Shelby |
5A Stark |
4A St. Clair |
5A Stephenson |
5A Tazewell |
4A Union |
5A Vermilion |
4A Wabash |
5A Warren |
4A Washington |
4A Wayne |
4A White |
5A Whiteside |
5A Will |
4A Williamson |
5A Winnebago |
5A Woodford |
INDIANA |
5A Adams |
5A Allen |
5A Bartholomew |
5A Benton |
5A Blackford |
5A Boone |
4A Brown |
5A Carroll |
5A Cass |
4A Clark |
5A Clay |
5A Clinton |
4A Crawford |
4A Daviess |
4A Dearborn |
5A Decatur |
5A De Kalb |
5A Delaware |
4A Dubois |
5A Elkhart |
5A Fayette |
4A Floyd |
5A Fountain |
5A Franklin |
5A Fulton |
4A Gibson |
5A Grant |
4A Greene |
5A Hamilton |
5A Hancock |
4A Harrison |
5A Hendricks |
5A Henry |
5A Howard |
5A Huntington |
4A Jackson |
5A Jasper |
5A Jay |
4A Jefferson |
4A Jennings |
5A Johnson |
4A Knox |
5A Kosciusko |
5A LaGrange |
5A Lake |
5A La Porte |
4A Lawrence |
5A Madison |
5A Marion |
5A Marshall |
4A Martin |
5A Miami |
4A Monroe |
5A Montgomery |
5A Morgan |
5A Newton |
5A Noble |
4A Ohio |
4A Orange |
5A Owen |
5A Parke |
4A Perry |
4A Pike |
5A Porter |
4A Posey |
5A Pulaski |
5A Putnam |
5A Randolph |
4A Ripley |
5A Rush |
4A Scott |
5A Shelby |
4A Spencer |
5A Starke |
5A Steuben |
5A St. Joseph |
4A Sullivan |
4A Switzerland |
5A Tippecanoe |
5A Tipton |
5A Union |
4A Vanderburgh |
5A Vermillion |
5A Vigo |
5A Wabash |
5A Warren |
4A Warrick |
4A Washington |
5A Wayne |
5A Wells |
5A White |
5A Whitley |
IOWA |
5A Adair |
5A Adams |
6A Allamakee |
5A Appanoose |
5A Audubon |
5A Benton |
6A Black Hawk |
5A Boone |
6A Bremer |
6A Buchanan |
6A Buena Vista |
6A Butler |
6A Calhoun |
5A Carroll |
5A Cass |
5A Cedar |
6A Cerro Gordo |
6A Cherokee |
6A Chickasaw |
5A Clarke |
6A Clay |
6A Clayton |
5A Clinton |
5A Crawford |
5A Dallas |
5A Davis |
5A Decatur |
6A Delaware |
5A Des Moines |
6A Dickinson |
5A Dubuque |
6A Emmet |
6A Fayette |
6A Floyd |
6A Franklin |
5A Fremont |
5A Greene |
6A Grundy |
5A Guthrie |
6A Hamilton |
6A Hancock |
6A Hardin |
5A Harrison |
5A Henry |
6A Howard |
6A Humboldt |
6A Ida |
5A Iowa |
5A Jackson |
5A Jasper |
5A Jefferson |
5A Johnson |
5A Jones |
5A Keokuk |
6A Kossuth |
5A Lee |
5A Linn |
5A Louisa |
5A Lucas |
6A Lyon |
5A Madison |
5A Mahaska |
5A Marion |
5A Marshall |
5A Mills |
6A Mitchell |
5A Monona |
5A Monroe |
5A Montgomery |
5A Muscatine |
6A O'Brien |
6A Osceola |
5A Page |
6A Palo Alto |
6A Plymouth |
6A Pocahontas |
5A Polk |
5A Pottawattamie |
5A Poweshiek |
5A Ringgold |
6A Sac |
5A Scott |
5A Shelby |
6A Sioux |
5A Story |
5A Tama |
5A Taylor |
5A Union |
5A Van Buren |
5A Wapello |
5A Warren |
5A Washington |
5A Wayne |
6A Webster |
6A Winnebago |
6A Winneshiek |
5A Woodbury |
6A Worth |
6A Wright |
KANSAS |
4A Allen |
4A Anderson |
4A Atchison |
4A Barber |
4A Barton |
4A Bourbon |
4A Brown |
4A Butler |
4A Chase |
4A Chautauqua |
4A Cherokee |
5A Cheyenne |
4A Clark |
4A Clay |
5A Cloud |
4A Coffey |
4A Comanche |
4A Cowley |
4A Crawford |
5A Decatur |
4A Dickinson |
4A Doniphan |
4A Douglas |
4A Edwards |
4A Elk |
5A Ellis |
4A Ellsworth |
4A Finney |
4A Ford |
4A Franklin |
4A Geary |
5A Gove |
5A Graham |
4A Grant |
4A Gray |
5A Greeley |
4A Greenwood |
5A Hamilton |
4A Harper |
4A Harvey |
4A Haskell |
4A Hodgeman |
4A Jackson |
4A Jefferson |
5A Jewell |
4A Johnson |
4A Kearny |
4A Kingman |
4A Kiowa |
4A Labette |
5A Lane |
4A Leavenworth |
4A Lincoln |
4A Linn |
5A Logan |
4A Lyon |
4A Marion |
4A Marshall |
4A McPherson |
4A Meade |
4A Miami |
5A Mitchell |
4A Montgomery |
4A Morris |
4A Morton |
4A Nemaha |
4A Neosho |
5A Ness |
5A Norton |
4A Osage |
5A Osborne |
4A Ottawa |
4A Pawnee |
5A Phillips |
4A Pottawatomie |
4A Pratt |
5A Rawlins |
4A Reno |
5A Republic |
4A Rice |
4A Riley |
5A Rooks |
4A Rush |
4A Russell |
4A Saline |
5A Scott |
4A Sedgwick |
4A Seward |
4A Shawnee |
5A Sheridan |
5A Sherman |
5A Smith |
4A Stafford |
4A Stanton |
4A Stevens |
4A Sumner |
5A Thomas |
5A Trego |
4A Wabaunsee |
5A Wallace |
4A Washington |
5A Wichita |
4A Wilson |
4A Woodson |
4A Wyandotte |
KENTUCKY |
4A (all) |
LOUISIANA |
2A Acadia* |
2A Allen* |
2A Ascension* |
2A Assumption* |
2A Avoyelles* |
2A Beauregard* |
3A Bienville* |
3A Bossier* |
3A Caddo* |
2A Calcasieu* |
3A Caldwell* |
2A Cameron* |
3A Catahoula* |
3A Claiborne* |
3A Concordia* |
3A De Soto* |
2A East Baton Rouge* |
3A East Carroll |
2A East Feliciana* |
2A Evangeline* |
3A Franklin* |
3A Grant* |
2A Iberia* |
2A Iberville* |
3A Jackson* |
2A Jefferson* |
2A Jefferson Davis* |
2A Lafayette* |
2A Lafourche* |
3A La Salle* |
3A Lincoln* |
2A Livingston* |
3A Madison* |
3A Morehouse |
3A Natchitoches* |
2A Orleans* |
3A Ouachita* |
2A Plaquemines* |
2A Pointe Coupee* |
2A Rapides* |
3A Red River* |
3A Richland* |
3A Sabine* |
2A St. Bernard* |
2A St. Charles* |
2A St. Helena* |
2A St. James* |
2A St. John the Baptist* |
2A St. Landry* |
2A St. Martin* |
2A St. Mary* |
2A St. Tammany* |
2A Tangipahoa* |
3A Tensas* |
2A Terrebonne* |
3A Union* |
2A Vermilion* |
3A Vernon* |
2A Washington* |
3A Webster* |
2A West Baton Rouge* |
3A West Carroll |
2A West Feliciana* |
3A Winn* |
MAINE |
6A Androscoggin |
7 Aroostook |
6A Cumberland |
6A Franklin |
6A Hancock |
6A Kennebec |
6A Knox |
6A Lincoln |
6A Oxford |
6A Penobscot |
6A Piscataquis |
6A Sagadahoc |
6A Somerset |
6A Waldo |
6A Washington |
6A York |
MARYLAND |
4A Allegany |
4A Anne Arundel |
4A Baltimore |
4A Baltimore (city) |
4A Calvert |
4A Caroline |
4A Carroll |
4A Cecil |
4A Charles |
4A Dorchester |
4A Frederick |
5A Garrett |
4A Harford |
4A Howard |
4A Kent |
4A Montgomery |
4A Prince George's |
4A Queen Anne's |
4A Somerset |
4A St. Mary's |
4A Talbot |
4A Washington |
4A Wicomico |
4A Worcester |
MASSACHSETTS |
5A (all) |
MICHIGAN |
6A Alcona |
6A Alger |
5A Allegan |
6A Alpena |
6A Antrim |
6A Arenac |
7 Baraga |
5A Barry |
5A Bay |
6A Benzie |
5A Berrien |
5A Branch |
5A Calhoun |
5A Cass |
6A Charlevoix |
6A Cheboygan |
7 Chippewa |
6A Clare |
5A Clinton |
6A Crawford |
6A Delta |
6A Dickinson |
5A Eaton |
6A Emmet |
5A Genesee |
6A Gladwin |
7 Gogebic |
6A Grand Traverse |
5A Gratiot |
5A Hillsdale |
7 Houghton |
6A Huron |
5A Ingham |
5A Ionia |
6A Iosco |
7 Iron |
6A Isabella |
5A Jackson |
5A Kalamazoo |
6A Kalkaska |
5A Kent |
7 Keweenaw |
6A Lake |
5A Lapeer |
6A Leelanau |
5A Lenawee |
5A Livingston |
7 Luce |
7 Mackinac |
5A Macomb |
6A Manistee |
6A Marquette |
6A Mason |
6A Mecosta |
6A Menominee |
5A Midland |
6A Missaukee |
5A Monroe |
5A Montcalm |
6A Montmorency |
5A Muskegon |
6A Newaygo |
5A Oakland |
6A Oceana |
6A Ogemaw |
7 Ontonagon |
6A Osceola |
6A Oscoda |
6A Otsego |
5A Ottawa |
6A Presque Isle |
6A Roscommon |
5A Saginaw |
6A Sanilac |
7 Schoolcraft |
5A Shiawassee |
5A St. Clair |
5A St. Joseph |
5A Tuscola |
5A Van Buren |
5A Washtenaw |
5A Wayne |
6A Wexford |
MINNESOTA |
7 Aitkin |
6A Anoka |
7 Becker |
7 Beltrami |
6A Benton |
6A Big Stone |
6A Blue Earth |
6A Brown |
7 Carlton |
6A Carver |
7 Cass |
6A Chippewa |
6A Chisago |
7 Clay |
7 Clearwater |
7 Cook |
6A Cottonwood |
7 Crow Wing |
6A Dakota |
6A Dodge |
6A Douglas |
6A Faribault |
6A Fillmore |
6A Freeborn |
6A Goodhue |
7 Grant |
6A Hennepin |
6A Houston |
7 Hubbard |
6A Isanti |
7 Itasca |
6A Jackson |
7 Kanabec |
6A Kandiyohi |
7 Kittson |
7 Koochiching |
6A Lac qui Parle |
7 Lake |
7 Lake of the Woods |
6A Le Sueur |
6A Lincoln |
6A Lyon |
7 Mahnomen |
7 Marshall |
6A Martin |
6A McLeod |
6A Meeker |
7 Mille Lacs |
6A Morrison |
6A Mower |
6A Murray |
6A Nicollet |
6A Nobles |
7 Norman |
6A Olmsted |
7 Otter Tail |
7 Pennington |
7 Pine |
6A Pipestone |
7 Polk |
6A Pope |
6A Ramsey |
7 Red Lake |
6A Redwood |
6A Renville |
6A Rice |
6A Rock |
7 Roseau |
6A Scott |
6A Sherburne |
6A Sibley |
6A Stearns |
6A Steele |
6A Stevens |
7 St. Louis |
6A Swift |
6A Todd |
6A Traverse |
6A Wabasha |
7 Wadena |
6A Waseca |
6A Washington |
6A Watonwan |
7 Wilkin |
6A Winona |
6A Wright |
6A Yellow Medicine |
MISSISSIPPI |
3A Adams* |
3A Alcorn |
3A Amite* |
3A Attala |
3A Benton |
3A Bolivar |
3A Calhoun |
3A Carroll |
3A Chickasaw |
3A Choctaw |
3A Claiborne* |
3A Clarke |
3A Clay |
3A Coahoma |
3A Copiah* |
3A Covington* |
3A DeSoto |
3A Forrest* |
3A Franklin* |
3A George* |
3A Greene* |
3A Grenada |
2A Hancock* |
2A Harrison* |
3A Hinds* |
3A Holmes |
3A Humphreys |
3A Issaquena |
3A Itawamba |
2A Jackson* |
3A Jasper |
3A Jefferson* |
3A Jefferson Davis* |
3A Jones* |
3A Kemper |
3A Lafayette |
3A Lamar* |
3A Lauderdale |
3A Lawrence* |
3A Leake |
3A Lee |
3A Leflore |
3A Lincoln* |
3A Lowndes |
3A Madison |
3A Marion* |
3A Marshall |
3A Monroe |
3A Montgomery |
3A Neshoba |
3A Newton |
3A Noxubee |
3A Oktibbeha |
3A Panola |
2A Pearl River* |
3A Perry* |
3A Pike* |
3A Pontotoc |
3A Prentiss |
3A Quitman |
3A Rankin* |
3A Scott |
3A Sharkey |
3A Simpson* |
3A Smith* |
2A Stone* |
3A Sunflower |
3A Tallahatchie |
3A Tate |
3A Tippah |
3A Tishomingo |
3A Tunica |
3A Union |
3A Walthall* |
3A Warren* |
3A Washington |
3A Wayne* |
3A Webster |
3A Wilkinson* |
3A Winston |
3A Yalobusha |
3A Yazoo |
MISSOURI |
5A Adair |
5A Andrew |
5A Atchison |
4A Audrain |
4A Barry |
4A Barton |
4A Bates |
4A Benton |
4A Bollinger |
4A Boone |
5A Buchanan |
4A Butler |
5A Caldwell |
4A Callaway |
4A Camden |
4A Cape Girardeau |
4A Carroll |
4A Carter |
4A Cass |
4A Cedar |
5A Chariton |
4A Christian |
5A Clark |
4A Clay |
5A Clinton |
4A Cole |
4A Cooper |
4A Crawford |
4A Dade |
4A Dallas |
5A Daviess |
5A DeKalb |
4A Dent |
4A Douglas |
4A Dunklin |
4A Franklin |
4A Gasconade |
5A Gentry |
4A Greene |
5A Grundy |
5A Harrison |
4A Henry |
4A Hickory |
5A Holt |
4A Howard |
4A Howell |
4A Iron |
4A Jackson |
4A Jasper |
4A Jefferson |
4A Johnson |
5A Knox |
4A Laclede |
4A Lafayette |
4A Lawrence |
5A Lewis |
4A Lincoln |
5A Linn |
5A Livingston |
5A Macon |
4A Madison |
4A Maries |
5A Marion |
4A McDonald |
5A Mercer |
4A Miller |
4A Mississippi |
4A Moniteau |
4A Monroe |
4A Montgomery |
4A Morgan |
4A New Madrid |
4A Newton |
5A Nodaway |
4A Oregon |
4A Osage |
4A Ozark |
4A Pemiscot |
4A Perry |
4A Pettis |
4A Phelps |
5A Pike |
4A Platte |
4A Polk |
4A Pulaski |
5A Putnam |
5A Ralls |
4A Randolph |
4A Ray |
4A Reynolds |
4A Ripley |
4A Saline |
5A Schuyler |
5A Scotland |
4A Scott |
4A Shannon |
5A Shelby |
4A St. Charles |
4A St. Clair |
4A St. Francois |
4A St. Louis |
4A St. Louis (city) |
4A Ste. Genevieve |
4A Stoddard |
4A Stone |
5A Sullivan |
4A Taney |
4A Texas |
4A Vernon |
4A Warren |
4A Washington |
4A Wayne |
4A Webster |
5A Worth |
4A Wright |
MONTANA |
6B (all) |
NEBRASKA |
5A (all) |
NEVADA |
5B Carson City (city) |
5B Churchill |
3B Clark |
5B Douglas |
5B Elko |
5B Esmeralda |
5B Eureka |
5B Humboldt |
5B Lander |
5B Lincoln |
5B Lyon |
5B Mineral |
5B Nye |
5B Pershing |
5B Storey |
5B Washoe |
5B White Pine |
NEW HAMPSHIRE |
6A Belknap |
6A Carroll |
5A Cheshire |
6A Coos |
6A Grafton |
5A Hillsborough |
6A Merrimack |
5A Rockingham |
5A Strafford |
6A Sullivan |
NEW JERSEY |
4A Atlantic |
5A Bergen |
4A Burlington |
4A Camden |
4A Cape May |
4A Cumberland |
4A Essex |
4A Gloucester |
4A Hudson |
5A Hunterdon |
5A Mercer |
4A Middlesex |
4A Monmouth |
5A Morris |
4A Ocean |
5A Passaic |
4A Salem |
5A Somerset |
5A Sussex |
4A Union |
5A Warren |
NEW MEXICO |
4B Bernalillo |
5B Catron |
3B Chaves |
4B Cibola |
5B Colfax |
4B Curry |
4B DeBaca |
3B Dona Ana |
3B Eddy |
4B Grant |
4B Guadalupe |
5B Harding |
3B Hidalgo |
3B Lea |
4B Lincoln |
5B Los Alamos |
3B Luna |
5B McKinley |
5B Mora |
3B Otero |
4B Quay |
5B Rio Arriba |
4B Roosevelt |
5B Sandoval |
5B San Juan |
5B San Miguel |
5B Santa Fe |
4B Sierra |
4B Socorro |
5B Taos |
5B Torrance |
4B Union |
4B Valencia |
NEW YORK |
5A Albany |
6A Allegany |
4A Bronx |
6A Broome |
6A Cattaraugus |
5A Cayuga |
5A Chautauqua |
5A Chemung |
6A Chenango |
6A Clinton |
5A Columbia |
5A Cortland |
6A Delaware |
5A Dutchess |
5A Erie |
6A Essex |
6A Franklin |
6A Fulton |
5A Genesee |
5A Greene |
6A Hamilton |
6A Herkimer |
6A Jefferson |
4A Kings |
6A Lewis |
5A Livingston |
6A Madison |
5A Monroe |
6A Montgomery |
4A Nassau |
4A New York |
5A Niagara |
6A Oneida |
5A Onondaga |
5A Ontario |
5A Orange |
5A Orleans |
5A Oswego |
6A Otsego |
5A Putnam |
4A Queens |
5A Rensselaer |
4A Richmond |
5A Rockland |
5A Saratoga |
5A Schenectady |
6A Schoharie |
6A Schuyler |
5A Seneca |
6A Steuben |
6A St. Lawrence |
4A Suffolk |
6A Sullivan |
5A Tioga |
6A Tompkins |
6A Ulster |
6A Warren |
5A Washington |
5A Wayne |
4A Westchester |
6A Wyoming |
5A Yates |
NORTH CAROLINA |
4A Alamance |
4A Alexander |
5A Alleghany |
3A Anson |
5A Ashe |
5A Avery |
3A Beaufort |
4A Bertie |
3A Bladen |
3A Brunswick* |
4A Buncombe |
4A Burke |
3A Cabarrus |
4A Caldwell |
3A Camden |
3A Carteret* |
4A Caswell |
4A Catawba |
4A Chatham |
4A Cherokee |
3A Chowan |
4A Clay |
4A Cleveland |
3A Columbus* |
3A Craven |
3A Cumberland |
3A Currituck |
3A Dare |
3A Davidson |
4A Davie |
3A Duplin |
4A Durham |
3A Edgecombe |
4A Forsyth |
4A Franklin |
3A Gaston |
4A Gates |
4A Graham |
4A Granville |
3A Greene |
4A Guilford |
4A Halifax |
4A Harnett |
4A Haywood |
4A Henderson |
4A Hertford |
3A Hoke |
3A Hyde |
4A Iredell |
4A Jackson |
3A Johnston |
3A Jones |
4A Lee |
3A Lenoir |
4A Lincoln |
4A Macon |
4A Madison |
3A Martin |
4A McDowell |
3A Mecklenburg |
5A Mitchell |
3A Montgomery |
3A Moore |
4A Nash |
3A New Hanover* |
4A Northampton |
3A Onslow* |
4A Orange |
3A Pamlico |
3A Pasquotank |
3A Pender* |
3A Perquimans |
4A Person |
3A Pitt |
4A Polk |
3A Randolph |
3A Richmond |
3A Robeson |
4A Rockingham |
3A Rowan |
4A Rutherford |
3A Sampson |
3A Scotland |
3A Stanly |
4A Stokes |
4A Surry |
4A Swain |
4A Transylvania |
3A Tyrrell |
3A Union |
4A Vance |
4A Wake |
4A Warren |
3A Washington |
5A Watauga |
3A Wayne |
4A Wilkes |
3A Wilson |
4A Yadkin |
5A Yancey |
NORTH DAKOTA |
6A Adams |
7 Barnes |
7 Benson |
6A Billings |
7 Bottineau |
6A Bowman |
7 Burke |
6A Burleigh |
7 Cass |
7 Cavalier |
6A Dickey |
7 Divide |
6A Dunn |
7 Eddy |
6A Emmons |
7 Foster |
6A Golden Valley |
7 Grand Forks |
6A Grant |
7 Griggs |
6A Hettinger |
7 Kidder |
6A LaMoure |
6A Logan |
7 McHenry |
6A McIntosh |
6A McKenzie |
7 McLean |
6A Mercer |
6A Morton |
7 Mountrail |
7 Nelson |
6A Oliver |
7 Pembina |
7 Pierce |
7 Ramsey |
6A Ransom |
7 Renville |
6A Richland |
7 Rolette |
6A Sargent |
7 Sheridan |
6A Sioux |
6A Slope |
6A Stark |
7 Steele |
7 Stutsman |
7 Towner |
7 Traill |
7 Walsh |
7 Ward |
7 Wells |
7 Williams |
OHIO |
4A Adams |
5A Allen |
5A Ashland |
5A Ashtabula |
5A Athens |
5A Auglaize |
5A Belmont |
4A Brown |
5A Butler |
5A Carroll |
5A Champaign |
5A Clark |
4A Clermont |
5A Clinton |
5A Columbiana |
5A Coshocton |
5A Crawford |
5A Cuyahoga |
5A Darke |
5A Defiance |
5A Delaware |
5A Erie |
5A Fairfield |
5A Fayette |
5A Franklin |
5A Fulton |
4A Gallia |
5A Geauga |
5A Greene |
5A Guernsey |
4A Hamilton |
5A Hancock |
5A Hardin |
5A Harrison |
5A Henry |
5A Highland |
5A Hocking |
5A Holmes |
5A Huron |
5A Jackson |
5A Jefferson |
5A Knox |
5A Lake |
4A Lawrence |
5A Licking |
5A Logan |
5A Lorain |
5A Lucas |
5A Madison |
5A Mahoning |
5A Marion |
5A Medina |
5A Meigs |
5A Mercer |
5A Miami |
5A Monroe |
5A Montgomery |
5A Morgan |
5A Morrow |
5A Muskingum |
5A Noble |
5A Ottawa |
5A Paulding |
5A Perry |
5A Pickaway |
4A Pike |
5A Portage |
5A Preble |
5A Putnam |
5A Richland |
5A Ross |
5A Sandusky |
4A Scioto |
5A Seneca |
5A Shelby |
5A Stark |
5A Summit |
5A Trumbull |
5A Tuscarawas |
5A Union |
5A Van Wert |
5A Vinton |
5A Warren |
4A Washington |
5A Wayne |
5A Williams |
5A Wood |
5A Wyandot |
OKLAHOMA |
3A Adair |
3A Alfalfa |
3A Atoka |
4B Beaver |
3A Beckham |
3A Blaine |
3A Bryan |
3A Caddo |
3A Canadian |
3A Carter |
3A Cherokee |
3A Choctaw |
4B Cimarron |
3A Cleveland |
3A Coal |
3A Comanche |
3A Cotton |
3A Craig |
3A Creek |
3A Custer |
3A Delaware |
3A Dewey |
3A Ellis |
3A Garfield |
3A Garvin |
3A Grady |
3A Grant |
3A Greer |
3A Harmon |
3A Harper |
3A Haskell |
3A Hughes |
3A Jackson |
3A Jefferson |
3A Johnston |
3A Kay |
3A Kingfisher |
3A Kiowa |
3A Latimer |
3A Le Flore |
3A Lincoln |
3A Logan |
3A Love |
3A Major |
3A Marshall |
3A Mayes |
3A McClain |
3A McCurtain |
3A McIntosh |
3A Murray |
3A Muskogee |
3A Noble |
3A Nowata |
3A Okfuskee |
3A Oklahoma |
3A Okmulgee |
3A Osage |
3A Ottawa |
3A Pawnee |
3A Payne |
3A Pittsburg |
3A Pontotoc |
3A Pottawatomie |
3A Pushmataha |
3A Roger Mills |
3A Rogers |
3A Seminole |
3A Sequoyah |
3A Stephens |
4B Texas |
3A Tillman |
3A Tulsa |
3A Wagoner |
3A Washington |
3A Washita |
3A Woods |
3A Woodward |
OREGON |
5B Baker |
4C Benton |
4C Clackamas |
4C Clatsop |
4C Columbia |
4C Coos |
5B Crook |
4C Curry |
5B Deschutes |
4C Douglas |
5B Gilliam |
5B Grant |
5B Harney |
5B Hood River |
4C Jackson |
5B Jefferson |
4C Josephine |
5B Klamath |
5B Lake |
4C Lane |
4C Lincoln |
4C Linn |
5B Malheur |
4C Marion |
5B Morrow |
4C Multnomah |
4C Polk |
5B Sherman |
4C Tillamook |
5B Umatilla |
5B Union |
5B Wallowa |
5B Wasco |
4C Washington |
5B Wheeler |
4C Yamhill |
PENNSYLVANIA |
5A Adams |
5A Allegheny |
5A Armstrong |
5A Beaver |
5A Bedford |
5A Berks |
5A Blair |
5A Bradford |
4A Bucks |
5A Butler |
5A Cambria |
6A Cameron |
5A Carbon |
5A Centre |
4A Chester |
5A Clarion |
6A Clearfield |
5A Clinton |
5A Columbia |
5A Crawford |
5A Cumberland |
5A Dauphin |
4A Delaware |
6A Elk |
5A Erie |
5A Fayette |
5A Forest |
5A Franklin |
5A Fulton |
5A Greene |
5A Huntingdon |
5A Indiana |
5A Jefferson |
5A Juniata |
5A Lackawanna |
5A Lancaster |
5A Lawrence |
5A Lebanon |
5A Lehigh |
5A Luzerne |
5A Lycoming |
6A McKean |
5A Mercer |
5A Mifflin |
5A Monroe |
4A Montgomery |
5A Montour |
5A Northampton |
5A Northumberland |
5A Perry |
4A Philadelphia |
5A Pike |
6A Potter |
5A Schuylkill |
5A Snyder |
5A Somerset |
5A Sullivan |
6A Susquehanna |
6A Tioga |
5A Union |
5A Venango |
5A Warren |
5A Washington |
6A Wayne |
5A Westmoreland |
5A Wyoming |
4A York |
RHODE ISLAND |
5A (all) |
SOUTH CAROLINA |
3A Abbeville |
3A Aiken |
3A Allendale* |
3A Anderson |
3A Bamberg* |
3A Barnwell* |
3A Beaufort* |
3A Berkeley* |
3A Calhoun |
3A Charleston* |
3A Cherokee |
3A Chester |
3A Chesterfield |
3A Clarendon |
3A Colleton* |
3A Darlington |
3A Dillon |
3A Dorchester* |
3A Edgefield |
3A Fairfield |
3A Florence |
3A Georgetown* |
3A Greenville |
3A Greenwood |
3A Hampton* |
3A Horry* |
3A Jasper* |
3A Kershaw |
3A Lancaster |
3A Laurens |
3A Lee |
3A Lexington |
3A Marion |
3A Marlboro |
3A McCormick |
3A Newberry |
3A Oconee |
3A Orangeburg |
3A Pickens |
3A Richland |
3A Saluda |
3A Spartanburg |
3A Sumter |
3A Union |
3A Williamsburg |
3A York |
SOUTH DAKOTA |
6A Aurora |
6A Beadle |
5A Bennett |
5A Bon Homme |
6A Brookings |
6A Brown |
6A Brule |
6A Buffalo |
6A Butte |
6A Campbell |
5A Charles Mix |
6A Clark |
5A Clay |
6A Codington |
6A Corson |
6A Custer |
6A Davison |
6A Day |
6A Deuel |
6A Dewey |
5A Douglas |
6A Edmunds |
6A Fall River |
6A Faulk |
6A Grant |
5A Gregory |
6A Haakon |
6A Hamlin |
6A Hand |
6A Hanson |
6A Harding |
6A Hughes |
5A Hutchinson |
6A Hyde |
5A Jackson |
6A Jerauld |
6A Jones |
6A Kingsbury |
6A Lake |
6A Lawrence |
6A Lincoln |
6A Lyman |
6A Marshall |
6A McCook |
6A McPherson |
6A Meade |
5A Mellette |
6A Miner |
6A Minnehaha |
6A Moody |
6A Pennington |
6A Perkins |
6A Potter |
6A Roberts |
6A Sanborn |
6A Shannon |
6A Spink |
6A Stanley |
6A Sully |
5A Todd |
5A Tripp |
6A Turner |
5A Union |
6A Walworth |
5A Yankton |
6A Ziebach |
TENNESSEE |
4A Anderson |
4A Bedford |
4A Benton |
4A Bledsoe |
4A Blount |
4A Bradley |
4A Campbell |
4A Cannon |
4A Carroll |
4A Carter |
4A Cheatham |
3A Chester |
4A Claiborne |
4A Clay |
4A Cocke |
4A Coffee |
3A Crockett |
4A Cumberland |
4A Davidson |
4A Decatur |
4A DeKalb |
4A Dickson |
3A Dyer |
3A Fayette |
4A Fentress |
4A Franklin |
4A Gibson |
4A Giles |
4A Grainger |
4A Greene |
4A Grundy |
4A Hamblen |
4A Hamilton |
4A Hancock |
3A Hardeman |
3A Hardin |
4A Hawkins |
3A Haywood |
3A Henderson |
4A Henry |
4A Hickman |
4A Houston |
4A Humphreys |
4A Jackson |
4A Jefferson |
4A Johnson |
4A Knox |
3A Lake |
3A Lauderdale |
4A Lawrence |
4A Lewis |
4A Lincoln |
4A Loudon |
4A Macon |
3A Madison |
4A Marion |
4A Marshall |
4A Maury |
4A McMinn |
3A McNairy |
4A Meigs |
4A Monroe |
4A Montgomery |
4A Moore |
4A Morgan |
4A Obion |
4A Overton |
4A Perry |
4A Pickett |
4A Polk |
4A Putnam |
4A Rhea |
4A Roane |
4A Robertson |
4A Rutherford |
4A Scott |
4A Sequatchie |
4A Sevier |
3A Shelby |
4A Smith |
4A Stewart |
4A Sullivan |
4A Sumner |
3A Tipton |
4A Trousdale |
4A Unicoi |
4A Union |
4A Van Buren |
4A Warren |
4A Washington |
4A Wayne |
4A Weakley |
4A White |
4A Williamson |
4A Wilson |
TEXAS |
2A Anderson* |
3B Andrews |
2A Angelina* |
2A Aransas* |
3A Archer |
4B Armstrong |
2A Atascosa* |
2A Austin* |
4B Bailey |
2B Bandera |
2A Bastrop* |
3B Baylor |
2A Bee* |
2A Bell* |
2A Bexar* |
3A Blanco* |
3B Borden |
2A Bosque* |
3A Bowie* |
2A Brazoria* |
2A Brazos* |
3B Brewster |
4B Briscoe |
2A Brooks* |
3A Brown* |
2A Burleson* |
3A Burnet* |
2A Caldwell* |
2A Calhoun* |
3B Callahan |
2A Cameron* |
3A Camp* |
4B Carson |
3A Cass* |
4B Castro |
2A Chambers* |
2A Cherokee* |
3B Childress |
3A Clay |
4B Cochran |
3B Coke |
3B Coleman |
3A Collin* |
3B Collingsworth |
2A Colorado* |
2A Comal* |
3A Comanche* |
3B Concho |
3A Cooke |
2A Coryell* |
3B Cottle |
3B Crane |
3B Crockett |
3B Crosby |
3B Culberson |
4B Dallam |
3A Dallas* |
3B Dawson |
4B Deaf Smith |
3A Delta |
3A Denton* |
2A DeWitt* |
3B Dickens |
2B Dimmit |
4B Donley |
2A Duval* |
3A Eastland |
3B Ector |
2B Edwards |
3A Ellis* |
3B El Paso |
3A Erath* |
2A Falls* |
3A Fannin |
2A Fayette* |
3B Fisher |
4B Floyd |
3B Foard |
2A Fort Bend* |
3A Franklin* |
2A Freestone* |
2B Frio |
3B Gaines |
2A Galveston* |
3B Garza |
3A Gillespie* |
3B Glasscock |
2A Goliad* |
2A Gonzales* |
4B Gray |
3A Grayson |
3A Gregg* |
2A Grimes* |
2A Guadalupe* |
4B Hale |
3B Hall |
3A Hamilton* |
4B Hansford |
3B Hardeman |
2A Hardin* |
2A Harris* |
3A Harrison* |
4B Hartley |
3B Haskell |
2A Hays* |
3B Hemphill |
3A Henderson* |
2A Hidalgo* |
2A Hill* |
4B Hockley |
3A Hood* |
3A Hopkins* |
2A Houston* |
3B Howard |
3B Hudspeth |
3A Hunt* |
4B Hutchinson |
3B Irion |
3A Jack |
2A Jackson* |
2A Jasper* |
3B Jeff Davis |
2A Jefferson* |
2A Jim Hogg* |
2A Jim Wells* |
3A Johnson* |
3B Jones |
2A Karnes* |
3A Kaufman* |
3A Kendall* |
2A Kenedy* |
3B Kent |
3B Kerr |
3B Kimble |
3B King |
2B Kinney |
2A Kleberg* |
3B Knox |
3A Lamar* |
4B Lamb |
3A Lampasas* |
2B La Salle |
2A Lavaca* |
2A Lee* |
2A Leon* |
2A Liberty* |
2A Limestone* |
4B Lipscomb |
2A Live Oak* |
3A Llano* |
3B Loving |
3B Lubbock |
3B Lynn |
2A Madison* |
3A Marion* |
3B Martin |
3B Mason |
2A Matagorda* |
2B Maverick |
3B McCulloch |
2A McLennan* |
2A McMullen* |
2B Medina |
3B Menard |
3B Midland |
2A Milam* |
3A Mills* |
3B Mitchell |
3A Montague |
2A Montgomery* |
4B Moore |
3A Morris* |
3B Motley |
3A Nacogdoches* |
3A Navarro* |
2A Newton* |
3B Nolan |
2A Nueces* |
4B Ochiltree |
4B Oldham |
2A Orange* |
3A Palo Pinto* |
3A Panola* |
3A Parker* |
4B Parmer |
3B Pecos |
2A Polk* |
4B Potter |
3B Presidio |
3A Rains* |
4B Randall |
3B Reagan |
2B Real |
3A Red River* |
3B Reeves |
2A Refugio* |
4B Roberts |
2A Robertson* |
3A Rockwall* |
3B Runnels |
3A Rusk* |
3A Sabine* |
3A San Augustine* |
2A San Jacinto* |
2A San Patricio* |
3A San Saba* |
3B Schleicher |
3B Scurry |
3B Shackelford |
3A Shelby* |
4B Sherman |
3A Smith* |
3A Somervell* |
2A Starr* |
3A Stephens |
3B Sterling |
3B Stonewall |
3B Sutton |
4B Swisher |
3A Tarrant* |
3B Taylor |
3B Terrell |
3B Terry |
3B Throckmorton |
3A Titus* |
3B Tom Green |
2A Travis* |
2A Trinity* |
2A Tyler* |
3A Upshur* |
3B Upton |
2B Uvalde |
2B Val Verde |
3A Van Zandt* |
2A Victoria* |
2A Walker* |
2A Waller* |
3B Ward |
2A Washington* |
2B Webb |
2A Wharton* |
3B Wheeler |
3A Wichita |
3B Wilbarger |
2A Willacy* |
2A Williamson* |
2A Wilson* |
3B Winkler |
3A Wise |
3A Wood* |
4B Yoakum |
3A Young |
2B Zapata |
2B Zavala |
UTAH |
5B Beaver |
6B Box Elder |
6B Cache |
6B Carbon |
6B Daggett |
5B Davis |
6B Duchesne |
5B Emery |
5B Garfield |
5B Grand |
5B Iron |
5B Juab |
5B Kane |
5B Millard |
6B Morgan |
5B Piute |
6B Rich |
5B Salt Lake |
5B San Juan |
5B Sanpete |
5B Sevier |
6B Summit |
5B Tooele |
6B Uintah |
5B Utah |
6B Wasatch |
3B Washington |
5B Wayne |
5B Weber |
VERMONT |
6A (all) |
VIRGINIA |
4A (all) |
WASHINGTON |
5B Adams |
5B Asotin |
5B Benton |
5B Chelan |
4C Clallam |
4C Clark |
5B Columbia |
4C Cowlitz |
5B Douglas |
6B Ferry |
5B Franklin |
5B Garfield |
5B Grant |
4C Grays Harbor |
4C Island |
4C Jefferson |
4C King |
4C Kitsap |
5B Kittitas |
5B Klickitat |
4C Lewis |
5B Lincoln |
4C Mason |
6B Okanogan |
4C Pacific |
6B Pend Oreille |
4C Pierce |
4C San Juan |
4C Skagit |
5B Skamania |
4C Snohomish |
5B Spokane |
6B Stevens |
4C Thurston |
4C Wahkiakum |
5B Walla Walla |
4C Whatcom |
5B Whitman |
5B Yakima |
WEST VIRGINIA |
5A Barbour |
4A Berkeley |
4A Boone |
4A Braxton |
5A Brooke |
4A Cabell |
4A Calhoun |
4A Clay |
5A Doddridge |
5A Fayette |
4A Gilmer |
5A Grant |
5A Greenbrier |
5A Hampshire |
5A Hancock |
5A Hardy |
5A Harrison |
4A Jackson |
4A Jefferson |
4A Kanawha |
5A Lewis |
4A Lincoln |
4A Logan |
5A Marion |
5A Marshall |
4A Mason |
4A McDowell |
4A Mercer |
5A Mineral |
4A Mingo |
5A Monongalia |
4A Monroe |
4A Morgan |
5A Nicholas |
5A Ohio |
5A Pendleton |
4A Pleasants |
5A Pocahontas |
5A Preston |
4A Putnam |
5A Raleigh |
5A Randolph |
4A Ritchie |
4A Roane |
5A Summers |
5A Taylor |
5A Tucker |
4A Tyler |
5A Upshur |
4A Wayne |
5A Webster |
5A Wetzel |
4A Wirt |
4A Wood |
4A Wyoming |
WISCONSIN |
6A Adams |
7 Ashland |
6A Barron |
7 Bayfield |
6A Brown |
6A Buffalo |
7 Burnett |
6A Calumet |
6A Chippewa |
6A Clark |
6A Columbia |
6A Crawford |
6A Dane |
6A Dodge |
6A Door |
7 Douglas |
6A Dunn |
6A Eau Claire |
7 Florence |
6A Fond du Lac |
7 Forest |
6A Grant |
6A Green |
6A Green Lake |
6A Iowa |
7 Iron |
6A Jackson |
6A Jefferson |
6A Juneau |
6A Kenosha |
6A Kewaunee |
6A La Crosse |
6A Lafayette |
7 Langlade |
7 Lincoln |
6A Manitowoc |
6A Marathon |
6A Marinette |
6A Marquette |
6A Menominee |
6A Milwaukee |
6A Monroe |
6A Oconto |
7 Oneida |
6A Outagamie |
6A Ozaukee |
6A Pepin |
6A Pierce |
6A Polk |
6A Portage |
7 Price |
6A Racine |
6A Richland |
6A Rock |
6A Rusk |
6A Sauk |
7 Sawyer |
6A Shawano |
6A Sheboygan |
6A St. Croix |
7 Taylor |
6A Trempealeau |
6A Vernon |
7 Vilas |
6A Walworth |
7 Washburn |
6A Washington |
6A Waukesha |
6A Waupaca |
6A Waushara |
6A Winnebago |
6A Wood |
WYOMING |
6B Albany |
6B Big Horn |
6B Campbell |
6B Carbon |
6B Converse |
6B Crook |
6B Fremont |
5B Goshen |
6B Hot Springs |
6B Johnson |
6B Laramie |
7 Lincoln |
6B Natrona |
6B Niobrara |
6B Park |
5B Platte |
6B Sheridan |
7 Sublette |
6B Sweetwater |
7 Teton |
6B Uinta |
6B Washakie |
6B Weston |
US TERRITORIES |
AMERICAN SAMOA |
1A (all)* |
GUAM |
1A (all)* |
NORTHERN MARIANA ISLANDS |
1A (all)* |
PUERTO RICO |
1A (all)* |
VIRGIN ISLANDS |
1A (all)* |
In Table R301.1, warm humid counties are identified by an asterisk.
The climate zone for any location outside the United States shall be determined by applying Table R301.3(1) and then Table R301.3(2).
INTERNATIONAL CLIMATE ZONE DEFINITIONS
MAJOR CLIMATE TYPE DEFINITIONS |
Marine (C) Definition—Locations meeting all four criteria:
|
Dry (B) Definition—Locations meeting the following criteria: Not marine and P in < 0.44 × (TF - 19.5) [Pcm < 2.0 × (TC + 7) in SI units] where: P in = Annual precipitation in inches (cm) T = Annual mean temperature in °F (°C) |
Moist (A) Definition—Locations that are not marine and not dry. |
Warm-humid Definition—Moist (A) locations where either of the following wet-bulb temperature conditions shall occur during the warmest six consecutive months of the year:
|
For SI: °C = [(°F) - 32]/1.8, 1 inch = 2.54 cm.
INTERNATIONAL CLIMATE ZONE DEFINITIONS
ZONE NUMBER | THERMAL CRITERIA | |
IP Units | SI Units | |
1 | 9000 < CDD50°F | 5000 < CDD10°C |
2 | 6300 < CDD50°F ≤ 9000 | 3500 < CDD10°C ≤ 5000 |
3A and 3B | 4500 < CDD50°F ≤ 6300 AND HDD65°F ≤ 5400 | 2500 < CDD10°C ≤ 3500 AND HDD18°C ≤ 3000 |
4A and 4B | CDD50°F ≤ 4500 AND HDD65°F ≤ 5400 | CDD10°C ≤ 2500 AND HDD18°C ≤ 3000 |
3C | HDD65°F ≤ 3600 | HDD18°C ≤ 2000 |
4C | 3600 < HDD65°F ≤ 5400 | 2000 < HDD18°C ≤ 3000 |
5 | 5400 < HDD65°F ≤ 7200 | 3000 < HDD18°C ≤ 4000 |
6 | 7200 < HDD65°F ≤ 9000 | 4000 < HDD18°C ≤ 5000 |
7 | 9000 < HDD65°F ≤ 12600 | 5000 < HDD18°C ≤ 7000 |
8 | 12600 < HDD65°F | 7000 < HDD18°C |
For SI: °C = [(°F) - 32]/1.8.
The tropical climate zone shall be defined as:
- Hawaii, Puerto Rico, Guam, American Samoa, U.S. Virgin Islands, Commonwealth of Northern Mariana Islands; and
- Islands in the area between the Tropic of Cancer and the Tropic of Capricorn.
The interior design temperatures used for heating and cooling load calculations shall be a maximum of 72°F (22°C) for heating and minimum of 75°F (24°C) for cooling.
Materials, systems and equipment shall be identified in a manner that will allow a determination of compliance with the applicable provisions of this code.
An R-value identification mark shall be applied by the manufacturer to each piece of building thermal envelope insulation that is 12 inches (305 mm) or greater in width. Alternatively, the insulation installers shall provide a certification that indicates the type, manufacturer and R-value of insulation installed in each element of the building thermal envelope. For blown-in or sprayed fiberglass and cellulose insulation, the initial installed thickness, settled thickness, settled R-value, installed density, coverage area and number of bags installed shall be indicated on the certification. For sprayed polyurethane foam (SPF) insulation, the installed thickness of the areas covered and the R-value of the installed thickness shall be indicated on the certification. For insulated siding, the R-value shall be on a label on the product's package and shall be indicated on the certification. The insulation installer shall sign, date and post the certification in a conspicuous location on the job site.
Exception: For roof insulation installed above the deck, the R-value shall be labeled as required by the material standards specified in Table 1508.2 of the International Building Code or Table R906.2 of the International Residential Code, as applicable.
The thickness of blown-in or sprayed fiberglass and cellulose roof and ceiling insulation shall be written in inches (mm) on markers that are installed at not less than one for every 300 square feet (28 m2) throughout the attic space. The markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness with numbers not less than 1 inch (25 mm) in height. Each marker shall face the attic access opening. The thickness and installed R-value of sprayed polyurethane foam insulation shall be indicated on the certification provided by the insulation installer.
Insulating materials shall be installed such that the manufacturer's R-value mark is readily observable at inspection.
U-factors of fenestration products such as windows, doors and skylights shall be determined in accordance with NFRC 100.
Exception: Where required, garage door U-factors shall be determined in accordance with either NFRC 100 or ANSI/DASMA 105.
U-factors shall be determined by an accredited, independent laboratory, and labeled and certified by the manufacturer.
Products lacking such a labeled U-factor shall be assigned a default U-factor from Table R303.1.3(1) or R303.1.3(2). The solar heat gain coefficient (SHGC) and visible transmittance (VT) of glazed fenestration products such as windows, glazed doors and skylights shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC or VT shall be assigned a default SHGC or VT from Table R303.1.3(3).
DEFAULT GLAZED WINDOW, GLASS DOOR AND SKYLIGHT U-FACTORS
FRAME TYPE | WINDOW AND GLASS DOOR | SKYLIGHT | ||
Single pane | Double pane | Single | Double | |
Metal | 1.20 | 0.80 | 2.00 | 1.30 |
Metal with Thermal Break | 1.10 | 0.65 | 1.90 | 1.10 |
Nonmetal or Metal Clad | 0.95 | 0.55 | 1.75 | 1.05 |
Glazed Block | 0.60 |
DEFAULT OPAQUE DOOR U-FACTORS
DOOR TYPE | OPAQUE U-FACTOR |
Uninsulated Metal | 1.20 |
Insulated Metal | 0.60 |
Wood | 0.50 |
Insulated, nonmetal edge, not exceeding 45% glazing, any glazing double pane | 0.35 |
The thermal resistance, R-value, of insulation shall be determined in accordance with Part 460 of US-FTC CFR Title 16 in units of h • ft2 • °F/Btu at a mean temperature of 75°F (24°C).
The thermal resistance, R-value, of insulated siding shall be determined in accordance with ASTM C1363. Installation for testing shall be in accordance with the manufacturer's instructions.
Materials, systems and equipment shall be installed in accordance with the manufacturer's instructions and the International Building Code or the International Residential Code, as applicable.
Insulation applied to the exterior of basement walls, crawl space walls and the perimeter of slab-on-grade floors shall have a rigid, opaque and weather-resistant protective covering to prevent the degradation of the insulation's thermal performance. The protective covering shall cover the exposed exterior insulation and extend not less than 6 inches (153 mm) below grade.
Maintenance instructions shall be furnished for equipment and systems that require preventive maintenance. Required regular maintenance actions shall be clearly stated and incorporated on a readily accessible label. The label shall include the title or publication number for the operation and maintenance manual for that particular model and type of product.