The provisions of this chapter establish general requirements for new and existing buildings, structures and premises located within wildland-urban interface areas.
The objective of this chapter is to establish minimum requirements to mitigate the risk to life and property from wildland fire exposures, exposures from adjacent structures and to mitigate structure fires from spreading to wildland fuels.

Section 602 Automatic Sprinkler Systems

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

602.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
An approved automatic sprinkler system shall be installed in all occupancies in new buildings required to meet the requirements for Class 1 ignition-resistant construction in Chapter 5. The installation of the automatic sprinkler systems shall be in accordance with nationally recognized standards.
Provisions of this section are intended to modify the fuel load in areas adjacent to structures to create a defensible space.
Buildings or structures, constructed in compliance with the conforming defensible space category of Table 503.1, shall comply with the fuel modification distances contained in Table 603.2. For all other purposes the fuel modification distance shall not be less than 30 feet (9144 mm) or to the lot line, whichever is less. Distances specified in Table 603.2 shall be measured on a horizontal plane from the perimeter or projection of the building or structure as shown in Figure 603.2. Distances specified in Table 603.2 are allowed to be increased by the code official because of a site-specific analysis based on local conditions and the fire protection plan.

TABLE 603.2
REQUIRED DEFENSIBLE SPACE

WILDLAND-URBAN
INTERFACE AREA
FUEL MODIFICATION DISTANCE
(feet)a
Moderate hazard30
High hazard50
Extreme hazard100
For SI: 1 foot = 304.8 mm.
a. Distances are allowed to be increased due to site-specific analysis based on local conditions and the fire protection plan.

FIGURE 603.2
MEASUREMENTS OF FUEL MODIFICATION DISTANCE

Persons owning, leasing, controlling, operating or maintaining buildings or structures requiring defensible spaces are responsible for modifying or removing nonfire-resistive vegetation on the property owned, leased or controlled by said person.
Trees are allowed within the defensible space, provided the horizontal distance between crowns of adjacent trees and crowns of trees and structures, overhead electrical facilities or unmodified fuel is not less than 10 feet (3048 mm).
Deadwood and litter shall be regularly removed from trees. Where ornamental vegetative fuels or cultivated ground cover, such as green grass, ivy, succulents or similar plants are used as ground cover, they are allowed to be within the designated defensible space, provided they do not form a means of transmitting fire from the native growth to any structure.

Section 604 Maintenance of Defensible Space

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.

604.1 General

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Defensible spaces required by Section 603 shall be maintained in accordance with Section 604.

604.2 Modified Area

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Nonfire-resistive vegetation or growth shall be kept clear of buildings or structures, in accordance with Section 603, in such a manner as to provide a clear area for fire suppression operations.

604.3 Responsibility

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Persons owning, leasing, controlling, operating or maintaining buildings or structures are responsible for maintenance of defensible spaces. Maintenance of the defensible space shall include modifying or removing nonfire-resistive vegetation and keeping leaves, needles and other dead vegetative material regularly removed from roofs of buildings and structures.

604.4 Trees

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Tree crowns extending to within 10 feet (3048 mm) of any structure shall be pruned to maintain a minimum horizontal clearance of 10 feet (3048 mm). Tree crowns within the defensible space shall be pruned to remove limbs located less than 6 feet (1829 mm) above the ground surface adjacent to the trees.

604.4.1 Chimney Clearance

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Portions of tree crowns that extend to within 10 feet (3048 mm) of the outlet of a chimney shall be pruned to maintain a minimum horizontal clearance of 10 feet (3048 mm).

604.4.2 Deadwood Removed

AMENDMENT
This section has been amended at the state or city level. Amendments are shown in green text.
Deadwood and litter shall be regularly removed from trees.
Chimneys serving fireplaces, barbecues, incinerators or decorative heating appliances in which solid or liquid fuel is used, shall be provided with a spark arrester. Spark arresters shall be constructed of woven or welded wire screening of 12 USA standard gage wire (0.1046 inch) (2.66 mm) having openings not exceeding 1/2 inch (12.7 mm).
The net free area of the spark arrester shall not be less than four times the net free area of the outlet of the chimney.
The storage of liquefied petroleum gas (LP-gas) and the installation and maintenance of pertinent equipment shall be in accordance with the International Fire Code or, in the absence thereof, recognized standards.
LP-gas containers or tanks shall be located within the defensible space in accordance with the International Fire Code.
Firewood and combustible material shall not be stored in unenclosed spaces beneath buildings or structures, or on decks or under eaves, canopies or other projections or overhangs. When required by the code official, storage of firewood and combustible material stored in the defensible space shall be located a minimum of 20 feet (6096 mm) from structures and separated from the crown of trees by a minimum horizontal distance of 15 feet (4572 mm).
Firewood and combustible materials not for consumption on the premises shall be stored so as to not pose a hazard. See Appendix A.