C101.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this appendix shall apply exclusively to agricultural buildings. Such buildings shall be classified as Group U and shall include the following uses:
  1. Livestock shelters or buildings, including shade structures and milking barns.
  2. Poultry buildings or shelters.
  3. Barns.
  4. Storage of equipment and machinery used exclusively in agriculture.
  5. Horticultural structures, including detached production greenhouses and crop protection shelters.
  6. Sheds.
  7. Grain silos.
  8. Stables.
  9. Riding arenas as defined in amended Subsection 312.1.
Buildings classified as Group U Agricultural shall not exceed the area or height limits specified in Table C102.1.

TABLE C102.1
BASIC ALLOWABLE AREA FOR A GROUP U, ONE STORY IN HEIGHT AND MAXIMUM HEIGHT OF SUCH OCCUPANCY

IIIIII and IVV
ABABIII A and IVIII BAB
ALLOWABLE AREA (square feet)a
Unlimited60,00027,10018,00027,10018,00021,10012,000
MAXIMUM HEIGHT IN STORIES
Unlimited12424232
MAXIMUM HEIGHT IN FEET
Unlimited160655565555040
For SI: 1 square foot = 0.0929 m2.
  1. See Section C102 for unlimited area under certain conditions.
The area of a one-story Group U agricultural building shall not be limited if the building is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width.
The area of a two-story Group U agricultural building shall not be limited if the building is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width and is provided with an approved automatic sprinkler system throughout in accordance with Section 903.3.1.1.
Mixed occupancies shall be protected in accordance with Section 508.

C104.1 Exit Facilities

AMENDMENT
This section has been amended at the state or city level.
Exits shall be provided in accordance with Chapters 10 and 11.
Exceptions:
  1. The maximum travel distance from any point in the building to an approved exit shall not exceed 300 feet (91 440 mm).
  2. One exit is required for each 15,000 square feet (1393.5 m2) of area or fraction thereof. The portion of riding arena buildings where riding will occur or where spectators may be present or seating is provided shall be provided with a minimum of four exits directly to the outside, with the exits located in a manner acceptable to the department that enhances exit from spectator areas. Exits from this portion of the building shall not be provided with a latch or lock unless it is panic hardware.
  3. Exit doors for riding arenas shall not be less than 3 feet wide by 6 feet 8 inches high.