This chapter shall apply to any of the following situations:
  1. Miscellaneous storage of Class I through Class IV commodities up to 12 ft (3.7 m) in height
  2. Miscellaneous storage of Group A plastics up to 12 ft (3.7 m) in height
  3. Miscellaneous storage of rubber tires up to 12 ft (3.7 m) in height
  4. Miscellaneous storage of rolled paper up to 12 ft (3.7 m) in height
  5. Storage of Class I through Class IV commodities up to 12 ft (3.7 m) in height as directed by 14.2.3.1 and 16.2.1.2.1
  6. Storage of Group A plastics up to 5 ft (1.5 m) in height as directed by 15.2.1 and 17.2.1.1
Hose connections shall not be required for the protection of miscellaneous storage.
For storage of Class I through Class IV 12 ft (3.7 m) or less in height that does not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 16.1.6, and ceiling sprinkler protection shall be provided in accordance with Chapter 13.
For storage of Group A Plastics 5 ft (1.5 m) or less in height that does not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 17.1.5, and ceiling sprinkler protection shall be provided in accordance with Chapter 13.
The protection criteria shall be selected from Table 13.2.1 and Figure 13.2.1.

Table 13.2.1 Discharge Criteria for Miscellaneous Storage Up to 12 ft (3.7 m) in Height

Commodity Type of Storage Storage Height Maximum Ceiling Height Design Curve Figure 13.2.1 Note Inside Hose Total Combined Inside and Outside Hose Duration (minutes)
ft m ft m gpm L/min gpm L/min
Class I to Class IV
Class I Solid-piled, palletized, bin box, shelf, single-, double-, multiple-row rack, and back-to-back shelf storage ≤12 ≤3.7 OH1 0, 50, 100 0, 190, 380 250 950 90
Class II ≤10 ≤3.0 OH1 0, 50, 100 0, 190, 380 250 950 90
Class II >10 to ≤12 >3.0 to ≤3.7 OH2 0, 50, 100 0, 190, 380 250 950 90
Class III ≤12 ≤3.7 OH2 0, 50, 100 0, 190, 380 250 950 90
Class IV ≤10 ≤3.0 OH2 0, 50, 100 0,190, 380 250 950 90
Class IV Palletized, bin box, shelf, and solid-piled >10 to ≤12 >3.0 to ≤3.7 32 10 OH2 0, 50, 100 0, 190, 380 250 950 90
Single-, double-, multiple-row rack and back-to-back shelf storage >10 to ≤12 >3.0 to ≤3.7 32 10 EH1 0, 50, 100 0, 190, 380 500 1900 120
Group A Plastic Storage
Cartoned Unexpanded and expanded Solid-piled, palletized, bin box, shelf, single-, double-, multiple-row rack, and back-to-back shelf storage ≤5 ≤1.5 OH2 0, 50, 100 0, 190, 380 250 950 90
>5 to ≤10 >1.5 to ≤3.0 15 4.6 EH1 0, 50, 100 0, 190, 380 500 1900 120
>5 to ≤10 >1.5 to ≤3.0 20 6.1 EH2 0, 50, 100 0, 190, 380 500 1900 120
>10 to ≤12 >3.0 to ≤3.7 17 5.2 EH2 0, 50, 100 0, 190, 380 500 1900 120
Solid-piled, palletized, bin box, shelf, and back-to-back shelf storage >10 to ≤12 >3.0 to ≤3.7 32 10 EH2 0, 50, 100 0, 190, 380 500 1900 120
Single-, double-, multiple-row rack >10 to ≤12 >3.0 to ≤3.7 32 10 OH2 +1 level of in-rack 0, 50, 100 0, 190, 380 250 950 90
Exposed Solid-piled, palletized, bin box, shelf, single-, double-, multiple-row rack, and back-to-back shelf storage ≤5 ≤1.5 OH2 0, 50, 100 0, 190, 380 250 950 90
Solid-piled, palletized, bin box, shelf, and back-to-back shelf storage >5 to ≤8 >1.5 to ≤2.4 28 8.5 EH2 0, 50, 100 0, 190, 380 500 1900 120
Solid-piled, palletized, bin box, shelf, single-, double-, multiple-row rack, and back-to-back shelf storage >5 to ≤10 >1.5 to ≤3.0 15 4.6 EH2 0, 50, 100 0, 190, 380 500 1900 120
Unexpanded Solid-piled, palletized, bin box, shelf, single-, double-, multiple-row rack, and back-to-back shelf storage >5 to ≤10 >1.5 to ≤3.0 20 6.1 EH2 0, 50, 100 0, 190, 380 500 1900 120
Expanded Single-, double-, multiple-row rack >5 to ≤10 >1.5 to ≤3.0 20 6.1 OH2 +1 level of in-rack 0, 50, 100 0, 190, 380 250 950 90
Unexpanded and expanded Solid-piled, palletized, bin box, shelf, and back-to-back shelf storage >10 to ≤12 >3.0 to ≤3.7 17 5.2 EH2 0, 50, 100 0, 190, 380 500 1900 120
Single-, double-, multiple-row rack >10 to ≤12 >3.0 to ≤3.7 17 5.2 EH2 0, 50, 100 0, 190, 380 500 1900 120
>10 to ≤12 >3.0 to ≤3.7 32 10 OH2 +1 level of in-rack 0, 50, 100 0, 190, 380 250 950 90
Tire Storage
Tires On floor, on side >5 to ≤12 >1.5 to ≤3.7 32 10 EH1 0, 50, 100 0, 190, 380 500 1900 120
On floor, on tread, or on side ≤5 ≤1.5 OH2 0, 50, 100 0, 190, 380 250 950 90
Single-, double-, or multiple-row racks on tread or on side ≤5 ≤1.5 OH2 0, 50, 100 0, 190, 380 250 950 90
Single-row rack, portable, on tread or on side >5 to ≤12 >1.5 to ≤3.7 32 10 EH1 0, 50, 100 0, 190, 380 500 1900 120
Single-row rack, fixed, on tread or on side >5 to ≤12 >1.5 to ≤3.7 32 10 EH1 0, 50, 100 0, 190, 380 500 1900 120
>5 to ≤12 >1.5 to ≤3.7 32 10 OH2 +1 level of in-rack 0, 50, 100 0, 190, 380 250 950 90
Rolled Paper Storage
Heavyweight and mediumweight On end ≤10 ≤3.0 30 9.1 OH2 0, 50, 100 0, 190, 380 250 950 90
Tissue and lightweight On end ≤10 ≤3.0 30 9.1 EH1 0, 50, 100 0, 190, 380 250 950 120

FIGURE 13.2.1 Miscellaneous Storage Up to 12 ft (3.7 m) in Height — Design Curves (see Table 13.2.1).

Installation criteria as permitted by NFPA 13 and design criteria and modifiers as permitted by the density/area method of Chapter 11 for ordinary hazard Group 1, ordinary hazard Group 2, extra hazard Group 1, and extra hazard Group 2 occupancies shall be applicable.
Where K-11.2 (160) or larger sprinklers are used with EH1 or EH2 design curves from Figure 13.2.1, the design area shall be permitted to be reduced by 25 percent but not below 2000 ft2 (186 m2), regardless of temperature rating.
In-rack sprinklers required by Table 13.2.1 shall meet the requirements of this section and the applicable storage protection and arrangement sections of this chapter.
In-rack sprinklers shall have a K-factor of 5.6 (80) or larger and operate at a minimum of 15 psi (1 bar).
Where one level of in-rack sprinklers is installed for miscellaneous storage, water demand shall be based on simultaneous operation of the hydraulically most demanding four adjacent sprinklers.
In-rack sprinklers for miscellaneous storage shall be located at the first tier level at or above one-half of the storage height.
Horizontal spacing of in-rack sprinklers shall not exceed 8 ft (2.4 m).
In-rack sprinklers shall be located in the longitudinal flue at the intersection of the transverse flues while not exceeding the maximum spacing rules.
If no longitudinal flue is provided in single- and double-row racks, in-rack sprinklers shall be located within 12 in. (300 mm) of the center of the rack while not exceeding the maximum spacing.
Where distances between transverse flues exceed the maximum allowable distances, sprinklers shall be installed at the intersection of the transverse and longitudinal flues and additional sprinklers shall be installed between transverse flues to meet the maximum distance rules.
Where no transverse flues exist, in-rack sprinklers shall not exceed the maximum spacing rules.