TABLE C-1
RECOMMENDED CAPACITIES FOR DOMESTIC KITCHEN EXHAUST HOODS

HOOD SIZE
AREA (Sq. Ft.)
EQUIPMENT WITH GRILLS OR DEEP FRYERS
(Number of Exposed Sides)
RANGES AND OVENS
(Number of Exposed Sides)
Four
(CFM)
Three
(CFM)
Four
(CFM)
Three
(CFM)
Up to 4Up to 400Up to 300Up to 300Up to 200
4400300300200
4.5450338338225
5500375375250
5.5550413413275
6600450450300
6.5650488488325
7700525525350
7.5750563563375
8800600600400
8.5850638638425
9900675675450
9.5950713713475
101,000750750500
10.51,050788788525
111,100825825550
11.51,150863863575
121,200900900600
12.51,250938938625
131,300975975650
13.51,3501,0131,013675
141,4001,0501,050700
14.51,4501,0881,088725
151,5001,1251,125750
15.51,5501,1631,163775
161,6001,2001,200800