(This is a normative appendix and is part of this standard.)

This normative appendix contains the climatic data necessary to determine building envelope and mechanical requirements for various US, Canadian, and international locations. (See Section 5.1.4 for additional information regarding the selection of climatic data.) The following definition applies: N.A. = Not Available.

TABLE D-1 US and US Territory Climatic Data

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating DesignTemperatureCooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
Alabama (AL)
Alexander City32.95 N85.93 W64029105102N.A.N.A.N.A.N.A.
Anniston FAA AP33.58 N85.85 W61128545217199376N.A.
Auburn Agronomy Farm32.60 N85.50 W65226125428N.A.N.A.N.A.N.A.
Birmingham FAA AP33.57 N86.75 W62529185206189275760
Dothan31.32 N85.45 W40017036659289376N.A.
Gadsden Steam Plant34.03 N86.00 W56533174805N.A.N.A.N.A.N.A.
Huntsville WSO AP34.65 N86.77 W62433234855159274N.A.
Mobile WSO AP30.68 N88.25 W21117026761269276774
Montgomery WSO AP32.30 N86.40 W22122245990249376734
Selma32.42 N87.00 W14722496080N.A.N.A.N.A.N.A.
Talladega33.43 N86.08 W55527905097N.A.N.A.N.A.N.A.
Tuscaloosa FAA AP33.23 N87.62 W16926615624209477N.A.
Alaska (AK)
Anchorage WSCMO AP61.17 N150.02 W11410,570688–146857521
Barrow WSO AP71.30 N156.78 W3120,2260–415249N.A.
Fairbanks WSFO AP64.82 N147.87 W43613,9401040–477759682
Juneau AP58.37 N134.58 W12889755946958540
Kodiak WSO AP57.75 N152.50 W111881745176556384
Nome WSO AP64.50 N165.43 W1314,129274-316555210
Arizona (AZ)
Douglas FAA AP31.47 N109.60 W409827674786N.A.N.A.N.A.N.A.
Flagstaff WSO AP35.13 N111.67 W70067131166118355N.A.
Kingman35.20 N114.02 W353932125040229763N.A.
Nogales31.42 N110.95 W356029284554N.A.N.A.N.A.N.A.
Phoenix WSFO AP33.43 N112.02 W1110135084253410870746

TABLE D-1 US and US Territory Climatic Data(continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Arizona cont.)
Prescott34.57 N112.43 W520549952875159160725
Tucson WSO AP32.13 N110.93 W2584167869213110265716
Winslow WSO AP35.02 N110.73 W489047763681109360634
Yuma WSO AP32.67 N114.60 W20692788974010972697
Arkansas (AR)
Blytheville AFB35.97 N89.95 W25636565133129577N.A.
Camden33.60 N92.82 W11629535309N.A.N.A.N.A.N.A.
Fayetteville36.00 N94.17 W12504040445269375N.A.
Ft Smith WSO AP35.33 N94.37 W44934785078139676547
Hot Springs34.52 N93.05 W68031815243N.A.N.A.N.A.N.A.
Jonesboro35.88 N90.70 W39035045118N.A.N.A.N.A.N.A.
Little Rock FAA AP34.73 N92.23 W25731555299169577626
Pine Bluff34.22 N92.02 W21530165467N.A.N.A.N.A.N.A.
Texarkana FAA AP33.45 N94.00 W36122956152209577N.A.
California (CA)
Bakersfield WSO AP35.42 N119.05 W495218260493210169848
Blythe FAA Airport33.62 N114.72 W39011448789N.A.N.A.N.A.N.A.
Burbank Hollywood34.20 N118.37 W77412045849399569N.A.
Chico University Farm39.70 N121.82 W18529534454N.A.N.A.N.A.N.A.
Crescent City41.77 N124.20 W4043971628N.A.N.A.N.A.N.A.
El Centro32.77 N115.57 W–3011568132N.A.N.A.N.A.N.A.
Eureka WSO City40.80 N124.17 W6044961529N.A.N.A.N.A.N.A.
Fairfield/Travis AFB38.27 N121.93 W6225564223319467N.A.
Fresno WSO AP36.77 N119.72 W328255653503010170785
Laguna Beach33.55 N117.78 W3521573881N.A.N.A.N.A.N.A.
Livermore37.67 N121.77 W48029093810N.A.N.A.N.A.N.A.
Lompoc34.65 N120.45 W9526513240N.A.N.A.N.A.N.A.
Long Beach WSO AP33.82 N118.15 W34143052814088671502
Los Angeles WSO AP33.93 N118.38 W100145847774381641849
Merced/Castle AFB37.37 N120.57 W18726874694309769N.A.
Monterey36.60 N121.90 W38531252574N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(California cont.)
Napa State Hospital38.28 N122.27 W6028443463N.A.N.A.N.A.N.A.
Needles FAA Airport34.77 N114.62 W91413098645N.A.N.A.N.A.N.A.
Oakland/Intl37.73 N122.20 W726443126N.A.N.A.N.A.1905
Oceanside Marina33.22 N117.40 W1020104069N.A.N.A.N.A.N.A.
Ontario/Intl34.05 N117.62 W96114885823359870N.A.
Oxnard34.20 N119.18 W4919923980397964N.A.
Palm Springs33.83 N116.50 W4259858555N.A.N.A.N.A.N.A.
Palmdale34.58 N118.10 W259629484863N.A.N.A.N.A.N.A.
Pasadena34.15 N118.15 W86414535476N.A.N.A.N.A.N.A.
Petaluma Fire Stn 338.23 N122.63 W2730503188N.A.N.A.N.A.N.A.
Pomona Cal Poly34.07 N 117.82 W74017135145N.A.N.A.N.A.N.A.
Redding WSO40.50 N122.30 W50228554964N.A.N.A.N.A.N.A.
Redlands34.05 N117.18 W131818755435N.A.N.A.N.A.N.A.
Richmond37.93 N122.35 W5525743285N.A.N.A.N.A.N.A.
Riverside/March AFB33.90 N117.25 W153518615295349868N.A.
Sacramento FAA AP38.52 N121.50 W1827494474309768990
Salinas FAA AP36.67 N121.60 W6929642951337862N.A.
San Bernardino/Norton34.10 N117.23 W1155182154503410170N.A.
San Diego WSO AP32.73 N117.17 W13125652234481671911
San Francisco WSO AP37.62 N122.38 W8301628833778621796
San Jose37.35 N121.90 W6723873935358966N.A.
San Luis Obispo Poly35.30 N120.67 W31524983492N.A.N.A.N.A.N.A.
Santa Ana Fire Station33.75 N117.87 W13512385430N.A.N.A.N.A.N.A.
Santa Barbara FAA AP34.43 N119.83 W924383449348064N.A.
Santa Cruz36.98 N122.02 W13029692913N.A.N.A.N.A.N.A.
Santa Maria WSO AP34.90 N120.45 W254298429183282622016
Santa Monica Pier34.00 N118.50 W1418194145N.A.N.A.N.A.N.A.
Santa Paula34.32 N119.15 W23720394114N.A.N.A.N.A.N.A.
Santa Rosa38.45 N122.70 W16728833432N.A.N.A.N.A.N.A.
Stockton WSO AP37.90 N121.25 W2227074755309768N.A.
Ukiah39.15 N123.20 W62329543868N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(California cont.)
Visalia36.33 N119.30 W32525115186N.A.N.A.N.A.N.A.
Yreka41.72 N122.63 W262553862611N.A.N.A.N.A.N.A.
Colorado (CO)
Alamosa WSO AP37.45 N105.87 W753687491374–178255N.A.
Boulder40.03 N105.28 W542055542820N.A.N.A.N.A.N.A.
Colorado Sprgs WSO AP38.82 N104.72 W609064152312–28758725
Denver WSFO AP39.77 N104.87 W528660202732–39059739
Durango37.28 N107.88 W660069111942N.A.N.A.N.A.N.A.
Ft Collins40.58 N105.08 W500463682411N.A.N.A.N.A.N.A.
Grand Junction WSO AP39.10 N108.55 W48495548363229460518
Greeley UNC40.42 N104.70 W471563062698N.A.N.A.N.A.N.A.
La Junta FAA AP38.05 N103.52 W419052653795N.A.N.A.N.A.N.A.
Pueblo WSO AP38.28 N104.52 W464054133358–19462720
Sterling40.62 N103.22 W393865412809N.A.N.A.N.A.N.A.
Trinidad FAA AP37.25 N104.33 W574654832976–29060N.A.
Connecticut (CT)
Bridgeport WSO AP41.17 N73.13 W105537299788472N.A.
Hartford-Brainard Fld41.73 N72.65 W156155276828872598
Norwalk Gas Plant41.12 N73.42 W3758652768N.A.N.A.N.A.N.A.
Norwich Pub Util Plt41.53 N72.07 W2058692687N.A.N.A.N.A.N.A.
Delaware (DE)
Dover39.15 N75.52 W3043373894148975N.A.
Wilmington WSO AP39.67 N75.60 W7949373557108974617
Florida (FL)
Belle Glade Exp Stn26.67 N80.63 W164518285N.A.N.A.N.A.N.A.
Daytona Beach WSO AP29.18 N81.05 W299097567349077641
Ft Lauderdale26.07 N80.15 W101719735469078N.A.
Ft Myers FAA AP26.58 N81.87 W154188924429377N.A.
Ft Pierce27.47 N80.35 W254908448N.A.N.A.N.A.N.A.
Gainesville Mun AP29.68 N82.27 W13812677009309277N.A.
Jacksonville WSO AP30.50 N81.70 W2614346847299377674

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Florida cont.)
Key West WSO AP24.55 N81.75 W410010,174558979N.A.
Lakeland28.02 N81.92 W1455888472N.A.N.A.N.A.N.A.
Miami WSCMO AP25.80 N80.30 W122009474469077259
Ocala29.20 N82.08 W759307696N.A.N.A.N.A.N.A.
Orlando WSO Mc Coy28.43 N81.33 W916868227379376571
Panama City/Tyndall30.07 N85.58 W1612167023338979N.A.
Pensacola FAA AP30.47 N87.20 W11216176816289278N.A.
St Augustine WFOY29.90 N81.32 W810407261N.A.N.A.N.A.N.A.
St Petersburg27.77 N82.63 W86038537439379N.A.
Tallahassee WSO AP30.38 N84.37 W5517056639259376747
Tampa WSCMO AP27.97 N82.53 W197258239369177592
West Palm Beach WSO AP26.68 N80.12 W183239049439078308
Georgia (GA)
Albany31.53 N84.13 W18022056020279576N.A.
Americus32.05 N84.25 W49024305634N.A.N.A.N.A.N.A.
Athens WSO AP33.95 N83.32 W80228935079209275N.A.
Atlanta WSO AP33.65 N84.43 W101029915038189174749
Augusta WSO AP33.37 N81.97 W14825655519219476774
Brunswick31.17 N81.50 W1315786729309179N.A.
Columbus WSO AP32.52 N84.95 W44922616052239375N.A.
Dalton34.75 N84.95 W70035524546N.A.N.A.N.A.N.A.
Dublin32.50 N82.90 W21524765664N.A.N.A.N.A.N.A.
Gainesville34.30 N83.85 W117035004310N.A.N.A.N.A.N.A.
La Grange33.05 N85.02 W71526675216N.A.N.A.N.A.N.A.
Macon WSO AP32.70 N83.65 W35423345826239475787
Savannah WSO AP32.13 N81.20 W4618476389269376N.A.
Valdosta/Moody AFB30.97 N83.20 W23315527216309477N.A.
Waycross31.25 N82.32 W14520256172299476N.A.
Hawaii (HI)
Hilo (Hawaii)19.72 N155.07 W3608759618474153
Honolulu WSFO AP (Oahu)21.33 N157.92 W70994961887369
Kaneohe Mauka (Oahu)21.42 N157.82 W19008955678574N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
Idaho (ID)
Boise WSFO AP43.57 N116.22 W28385861280729463647
Burley FAA AP42.53 N113.77 W415767452174–59062N.A.
Coeur D'Alene R S47.68 N116.75 W215862392216N.A.N.A.N.A.N.A.
Idaho Falls FAA AP43.52 N112.07 W473080631853–128960N.A.
Lewiston WSO AP46.38 N117.02 W14365270296469364748
Moscow-Univ of Idaho46.73 N116.97 W266067821789N.A.N.A.N.A.N.A.
Mountain Home43.13 N115.70 W31906176272509662N.A.
Pocatello WSO AP42.92 N112.60 W445471802142–79060546
Twin Falls WSO42.55 N114.35 W396067691995N.A.N.A.N.A.N.A.
Illinois (IL)
Aurora41.75 N88.35 W64466992880N.A.N.A.N.A.N.A.
Belleville/Scott AFB38.55 N89.85 W4534878414639377N.A.
Carbondale Sewage Plt37.73 N89.17 W39048653934N.A.N.A.N.A.N.A.
Champaign40.03 N88.28 W75556893697N.A.N.A.N.A.N.A.
Chicago Midway AP41.73 N87.77 W62061763251N.A.N.A.N.A.N.A.
Chicago O'Hare WSO AP41.98 N87.90 W67465362941–68873613
Chicago University41.78 N87.60 W59457533391N.A.N.A.N.A.N.A.
Danville40.13 N87.65 W55856103471–49077N.A.
Decatur39.83 N89.02 W62055223652–29175N.A.
Dixon41.83 N89.52 W70068732965N.A.N.A.N.A.N.A.
Freeport Waste Wtr Plt42.30 N89.60 W75071692739N.A.N.A.N.A.N.A.
Galesburg40.95 N90.38 W77163143249N.A.N.A.N.A.N.A.
Joliet Brandon Rd Dam41.50 N88.10 W54364633025N.A.N.A.N.A.N.A.
Moline WSO AP41.45 N90.50 W58264743207–89074640
Mt Vernon38.35 N88.87 W49051893818N.A.N.A.N.A.N.A.
Peoria WSO AP40.67 N89.68 W65061483339–68974N.A.
Quincy FAA AP39.93 N91.20 W76357633574–49175N.A.
Rantoul40.32 N88.17 W74061833288N.A.N.A.N.A.N.A.
Rockford WSO AP42.20 N89.10 W72469692852–108873N.A.
Springfield WSO AP39.85 N89.68 W59456883635–49175600
Waukegan42.35 N87.88 W 70071362515N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design TemperatureNo. Hrs.
8 a.m.–4 p.m.
Dry-BulbWet-Bulb
99.6%1.0%1.0%55 < Tdb < 69
Indiana (IN)
Anderson Sewage Plant40.10 N85.72 W84759163091N.A.N.A.N.A.N.A.
Bloomington Indiana U39.17 N86.52 W 82553093585N.A.N.A.N.A.N.A.
Columbus39.20 N85.92 W62155363353N.A.N.A.N.A.N.A.
Evansville WSO AP38.05 N87.53 W3804708407439276611
Ft Wayne WSO AP41.00 N85.20 W7976273 3077–48873601
Goshen College41.57 N85.83 W80562822941N.A.N.A.N.A.N.A.
Hobart41.53 N87.25 W60060433168N.A.N.A.N.A.N.A.
Indianapolis WSFO39.73 N86.27 W79256153453–38874N.A.
Kokomo40.42 N86.05 W85564292978N.A.N.A.N.A.N.A.
Lafayette40.35 N86.87 W60062283069–59075N.A.
Marion40.57 N85.67 W79062602996N.A.N.A.N.A.N.A.
Muncie Ball State Univ40.22 N85.42 W94060273196N.A.N.A.N.A.N.A.
Peru/Grissom AFB40.65 N86.15 W81459083439–38975N.A.
Richmond Wtr Wks39.88 N84.88 W101559633004N.A.N.A.N.A.N.A.
Shelbyville Sewage Plt39.52 N85.78 W75057843291N.A.N.A.N.A.N.A.
South Bend WSO AP41.70 N86.32 W77363312920–28772635
Terre Haute39.35 N87.42 W55555813490–39076N.A.
Valparaiso Waterworks41.52 N87.03 W80062672942N.A.N.A.N.A.N.A.
Iowa (IA)
Ames42.03 N93.80 W109967763079N.A.N.A.N.A.N.A.
Burlington40.78 N91.12 W 59759433601–49176649
Cedar Rapids FAA AP41.88 N 91.70 W86369243003–118974N.A.
Clinton41.80 N90.27 W58563243291N.A.N.A.N.A.N.A.
Des Moines WSFO AP41.53 N93.65 W93864973371–99074667
Dubuque WSO AP42.40 N 90.70 W106573272672N.A.N.A.N.A.N.A.
Ft Dodge42.50 N94.20 W111572612902–138873N.A.
Iowa City41.65 N91.53 W64062273434N.A.N.A.N.A.N.A.
Keokuk Lock and Dam40.40 N91.37 W52759693467N.A.N.A.N.A.N.A.
Marshalltown42.07 N92.93 W87071702813N.A.N.A.N.A.N.A.
Mason City FAA AP43.17 N93.33 W119478372653–158873610

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Iowa cont.)
Newton41.70 N93.05 W93867833131N.A.N.A.N.A.N.A.
Ottumwa Airport41.10 N92.45 W8426269 3414–59275N.A.
Sioux City WSO AP42.40 N96.38 W110368933149–119074602
Waterloo WSO AP42.55 N92.40 W868 7406 2813–148873N.A.
Kansas (KS)
Atchison39.57 N 95.12 W94551843940N.A.N.A.N.A.N.A.
Chanute FAA Airport37.67 N95.48 W97846504226N.A.N.A.N.A.N.A.
Dodge City WSO AP37.77 N99.97 W25825001409009770637
El Dorado37.82 N96.83 W134045874317N.A.N.A.N.A.N.A.
Garden City FAA AP37.93 N100.72 W288252163936–39769N.A.
Goodland WSO AP39.37 N101.70 W365059743018–39466625
Great Bend38.35 N98.77 W185046794425N.A.N.A.N.A.N.A.
Hutchinson37.93 N98.03 W157051034106N.A.N.A.N.A.N.A.
Liberal37.05 N100.92 W283447064185N.A.N.A.N.A.N.A.
Manhattan39.20 N96.58 W106550434155N.A.N.A.N.A.N.A.
Parsons37.37 N95.28 W91046064339N.A.N.A.N.A.N.A.
Russell FAA AP38.87 N98.82 W186453383939–49672N.A.
Salina FAA AP38.80 N97.63 W125751014167–39773N.A.
Topeka WSFO AP39.07 N95.63 W87752653880–29375608
Wichita WSO AP37.65 N97.43 W13214791435129773N.A.
Kentucky (KY)
Ashland38.45 N82.62 W55552253280N.A.N.A.N.A.N.A.
Bowling Green FAA AP36.97 N86.42 W5474328413279175N.A.
Covington WSO AP39.07 N84.67 W8695248348818973661
Hopkinsville/Campbell36.67 N87.50 W57139284654N.A.N.A.N.A.N.A.
Lexington WSO AP38.03 N84.60 W9664783375448973618
Louisville WSFO AP38.18 N85.73 W 4774514400069075636
Madisonville37.35 N87.52 W 44041674290N.A.N.A.N.A.N.A.
Owensboro37.77 N87.15 W40543344222N.A.N.A.N.A.N.A.
Paducah WSO37.07 N88.77 W 4104279431779376N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
Louisiana (LA)
Alexandria31.32 N92.47 W8720036407279478N.A.
Baton Rouge WSO AP30.53 N 91.13 W6416696845279277677
Bogalusa30.78 N89.87 W10019116457N.A.N.A.N.A.N.A.
Houma29.58 N90.73 W1514296974N.A.N.A.N.A.N.A.
Lafayette FAA AP30.20 N91.98 W3815876877289378N.A.
Lake Charles WSO AP30.12 N93.22 W916166813299178668
Minden32.58 N93.28 W18525335823N.A.N.A.N.A.N.A.
Monroe FAA AP32.52 N92.05 W7824076039229478N.A.
Natchitoches31.77 N93.08 W13021526273N.A.N.A.N.A.N.A.
New Orleans WSCMO AP29.98 N90.25 W415136910309278789
Shreveport WSO AP32.47 N93.82 W2542,2646166229577697
Maine (ME)
Augusta FAA AP44.32 N69.80 W35075502093–38469N.A.
Bangor FAA AP44.80 N68.82 W16379301916–78469669
Caribou WSO AP46.87 N68.02 W62496511470–148267692
Lewiston44.10 N70.22 W18072442261N.A.N.A.N.A.N.A.
Millinocket45.65 N68.70 W36089021708N.A.N.A.N.A.N.A.
Portland WSMO AP43.65 N70.32 W577378 1943–38370665
Waterville Pmp Stn44.55 N69.65 W907382 2180N.A.N.A.N.A.N.A.
Maryland (MD)
Baltimore WSO AP39.18 N76.67 W19647073709119174N.A.
Cumberland39.63 N78.75 W73050363432N.A.N.A.N.A.N.A.
Hagerstown39.65 N77.73 W66052933341N.A.N.A.N.A.N.A.
Salisbury38.37 N 75.58 W1040274002139076N.A.
Massachusetts (MA)
Boston WSO AP42.37 N71.03 W205641289778771713
Clinton42.40 N71.68 W 39866982457N.A.N.A.N.A.N.A.
Framingham42.28 N71.42 W17062622695N.A.N.A.N.A.N.A.
Lawrence42.70 N71.17 W5763222648N.A.N.A.N.A.N.A.
Lowell42.65 N71.37 W11063392715N.A.N.A.N.A.N.A.
New Bedford41.63 N70.93 W12054262973N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Massachusetts cont.)
Springfield42.10 N72.58 W19057543037N.A.N.A.N.A.N.A.
Taunton41.90 N71.07 W2063462461N.A.N.A.N.A.N.A.
Worcester WSO AP42.27 N71.87 W9866979220308369N.A.
Michigan (MI)
Adrian41.92 N84.02 W76067372586N.A.N.A.N.A.N.A.
Alpena WSO AP45.07 N83.57 W68982841779–78469695
Battle Creek/Kellogg42.30 N85.23 W94264163399N.A.N.A.N.A.N.A.
Benton Harbor AP42.13 N86.43 W64963032829N.A.N.A.N.A.N.A.
Detroit City Airport42.42 N83.02 W6256167 304608772N.A.
Escanaba45.75 N87.03 W60085931664N.A.N.A.N.A.N.A.
Flint WSO AP42.97 N83.75 W76669792451–28671634
Grand Rapids WSO AP42.88 N85.52 W7076973253708671622
Holland42.80 N86.12 W61067472536N.A.N.A.N.A.N.A.
Jackson FAA AP42.27 N84.45 W100567912707–38673N.A.
Kalamazoo State Hosp42.28 N85.60 W94562303015N.A.N.A.N.A.N.A.
Lansing WSO AP42.77 N84.60 W84171012449–38672N.A.
Marquette46.55 N87.38 W66583561730–138267N.A.
Mt Pleasant University43.58 N84.77 W79674362319N.A.N.A.N.A.N.A.
Muskegon WSO AP43.17 N86.23 W6286924236138370N.A.
Pontiac State Hospital42.65 N83.30 W98266532770N.A.N.A.N.A.N.A.
Port Huron42.98 N82.42 W59068982541N.A.N.A.N.A.N.A.
Saginaw FAA AP43.53 N84.08 W6607139247608772N.A.
Sault Ste Marie WSO46.47 N84.37 W72493161421–128068733
Traverse City FAA AP44.73 N85.58 W62377492127–38670679
Ypsilanti East Mich U42.25 N83.62 W77964662878N.A.N.A.N.A.N.A.
Minnesota (MN)
Albert Lea43.62 N93.42 W123081462608N.A.N.A.N.A.N.A.
Alexandria FAA AP45.87 N 95.38 W141689992316–208670N.A.
Bemidji Airport47.50 N94.93 W1377102001781N.A.N.A.N.A.N.A.
Brainerd46.37 N94.20 W118094371958–248568N.A.
Duluth WSO AP46.83 N92.18 W142898181536–218167650

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design TemperatureNo. Hrs.
8 a.m.–4 p.m.
Dry-BulbWet-Bulb
99.6%1.0%1.0%55 < Tdb < 69
(Minnesota cont.)
Faribault44.30 N93.27 W94082792498N.A.N.A.N.A.N.A.
International Falls WSO AP48.57 N93.38 W 117910,4871630–298367656
Mankato44.15 N94.02 W83680052691N.A.N.A.N.A.N.A.
Minneapolis-St Paul WSO AP44.88 N 93.22 W83479812680–168871566
Rochester WSO AP43.92 N92.50 W129782502376–178571652
St Cloud WSO AP45.55 N94.07 W103789282149–208871N.A.
Virginia47.50 N92.55 W143510,0241583N.A.N.A.N.A.N.A.
Willmar State Hospital45.13 N95.02 W112886372465N.A.N.A.N.A.N.A.
Winona44.05 N91.63 W65276942695N.A.N.A.N.A.N.A.
Mississippi (MS)
Biloxi/Keesler AFB30.42 N88.92 W2614866946319178N.A.
Clarksdale34.20 N90.57 W17331885357N.A.N.A.N.A.N.A.
Columbus AFB33.65 N88.45 W22027695565209478N.A.
Greenville33.38 N91.02 W13227785661N.A.N.A.N.A.N.A.
Greenwood FAA AP33.50 N90.08 W15526985760209478N.A.
Hattiesburg31.32 N89.30 W16121806085N.A.N.A.N.A.N.A.
Jackson WSFO AP32.32 N 90.08 W33024675900219376640
Laurel31.68 N89.12 W22523275893N.A.N.A.N.A.N.A.
McComb FAA AP31.23 N90.47 W41321156025239276N.A.
Meridian WSO AP32.33 N88.75 W29424445804219476719
Natchez31.55 N91.38 W19519036378N.A.N.A.N.A.N.A.
Tupelo WSO AP34.27 N88.73 W36130795224189476N.A.
Vicksburg Military Pk32.35 N 90.85 W2552196 6059N.A.N.A.N.A.N.A.
Missouri (MO)
Cape Girardeau FAA AP37.23 N89.57 W3374386435969477N.A.
Columbia WSO AP38.82 N92.22 W 88752123752–19275633
Farmington37.70 N90.38 W93550413653N.A.N.A.N.A.N.A.
Hannibal39.72 N91.37 W71256283685N.A.N.A.N.A.N.A.
Jefferson City Wtr Plt38.58 N92.15 W67053023705N.A.N.A.N.A.N.A.
Joplin FAA AP37.17 N94.50 W9804303441739475N.A.
Kansas City WSO AP39.32 N94.72 W97353933852–19375N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Missouri cont.)
Kirksville Radio KIRX40.22 N92.58 W97058673494N.A.N.A.N.A.N.A.
Mexico39.18 N91.88 W77555903664N.A.N.A.N.A.N.A.
Moberly Radio KWIX39.40 N92.43 W84052043948N.A.N.A.N.A.N.A.
Poplar Bluff R S36.77 N90.42 W3804328436889276N.A.
Rolla38.13 N91.77 W114847484186N.A.N.A.N.A.N.A.
Rolla Univ of MO37.95 N91.77 W118049593986N.A.N.A.N.A.N.A.
St Joseph39.77 N94.92 W81155903783N.A.N.A.N.A.N.A.
St Louis WSCMO AP38.75 N90.37 W5354758428329375N.A.
Montana (MT)
Billings WSO AP45.80 N108.53 W356771642466–139062617
Bozeman45.82 N110.88 W59509908672–208760N.A.
Butte FAA AP45.95 N112.50 W554095171152–228456N.A.
Cut Bank FAA AP48.60 N112.37 W383889041475–218459672
Glasgow WSO AP48.22 N106.62 W 228487452244–229063570
Glendive47.10 N104.72 W207681782619N.A.N.A.N.A.N.A.
Great Falls WSCMO AP47.48 N111.37 W366377411993–198860641
Havre WSO AP48.55 N109.77 W258484472132–259062N.A.
Helena WSO AP46.60 N112.00 W389380311922–188759651
Kalispell WSO AP48.30 N114.27 W296583781345–128661N.A.
Lewistown FAA AP47.07 N109.45 W413284791580–188660673
Livingston FAA AP45.70 N110.45 W465372201900N.A.N.A.N.A.N.A.
Miles City FAA AP46.43 N105.87 W262877962680–199365565
Missoula WSO AP46.92 N114.08 W319077921679–98861658
Nebraska (NE)
Chadron FAA AP42.83 N03.08 W331270202692N.A.N.A.N.A.N.A.
Columbus41.47 N97.33 W145065433345N.A.N.A.N.A.N.A.
Fremont41.43 N96.48 W 118061403421N.A.N.A.N.A.N.A.
Grand Island WSO AP40.97 N98.32 W184164213243–89372611
Hastings40.58 N98.35 W192565063217N.A.N.A.N.A.N.A.
Kearney40.73 N99.02 W213065483090N.A.N.A.N.A.N.A.
Lincoln WSO AP40.85 N96.75 W119062783455–79474N.A.
Mc Cook40.22 N100.58 W258061153236N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Nebraska cont.)
Norfolk WSO AP41.98 N97.43 W155168733072–119272N.A.
North Platte WSO AP41.13 N100.68 W277568592737–109269592
Omaha (Eppley Field)41.30 N95.90 W98063003398–79275N.A.
Scottsbluff WSO AP41.87 N103.60 W394567292680–119264620
Sidney41.23 N103.00 W4,32069662409–89263N.A.
Nevada (NV)
Carson City39.15 N119.77 W465156912312N.A.N.A.N.A.N.A.
Elko FAA AP40.83 N115.78 W507570772144–59259569
Ely WSO AP39.28 N114.85 W626276211717–68756683
Las Vegas WSO AP36.08 N115.17 W2162240767452710666719
Lovelock FAA AP40.07 N118.55 W390058692886N.A.N.A.N.A.606
Reno WSFO AP39.50 N119.78 W44045674250489260752
Tonopah AP38.07 N117.08 W54265733284079257660
Winnemucca WSO AP40.90 N117.80 W42976315237919460608
New Hampshire (NH)
Berlin44.45 N71.18 W93086451718N.A.N.A.N.A.N.A.
Concord WSO AP43.20 N71.50 W34675542087–88770683
Keene42.92 N72.27 W48069482398N.A.N.A.N.A.N.A.
Portsmouth/Pease AFB43.08 N70.82 W1026572241848570N.A.
New Jersey (NJ)
Atlantic City WSO AP39.45 N74.57 W1385169319888873N.A.
Long Branch Oakhurst40.27 N74.00 W3052533057N.A.N.A.N.A.N.A.
Newark WSO AP40.70 N74.17 W3048883748109073644
New Mexico (NM)
Alamogordo/Holloman32.85 N106.10 W409432324726209663N.A.
Albuquerque WSFO AP35.05 N106.62 W532644253908139360703
Artesia32.77 N104.38 W332035274583N.A.N.A.N.A.N.A.
Carlsbad FAA AP32.33 N104.27 W323228125512199866N.A.
Clovis/Cannon AFB34.38 N103.32 W429539834178109364N.A.
Farmington36.73 N108.23 W55025464330789260N.A.
Gallup FAA AP35.52 N108.78 W646862442355–18756N.A.
Grants Airport35.17 N107.90 W652059072481N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(New Mexico cont.)
Hobbs32.70 N103.13 W361528515160N.A.N.A.N.A.N.A.
Raton Filter Plant36.92 N104.43 W693261032187N.A.N.A.N.A.N.A.
Roswell FAA AP33.30 N104.53 W366932674962149665677
Socorro34.08 N106.88 W458540743845N.A.N.A.N.A.N.A.
Tucumcari35.20 N103.68 W40863912419699565710
New York (NY)
Albany WSFO AP42.75 N73.80 W27568942525–78670605
Auburn42.92 N76.53 W77067822531N.A.N.A.N.A.N.A.
Batavia42.98 N78.18 W89066572536N.A.N.A.N.A.N.A.
Binghamton WSO AP42.22 N75.98 W160072732193–28269662
Buffalo WSCMO AP42.93 N78.73 W7056747246828469697
Cortland42.60 N76.18 W112971682225N.A.N.A.N.A.N.A.
Elmira/Chemung Co42.17 N76.90 W95168452420–28771N.A.
Geneva Research Farm42.88 N77.03 W71869392364N.A.N.A.N.A.N.A.
Glens Falls FAA AP43.35 N73.62 W32176352182–108571N.A.
Gloversville43.05 N74.35 W81276642118N.A.N.A.N.A.N.A.
Ithaca Cornell Univ42.45 N76.45 W96072072117N.A.N.A.N.A.N.A.
Lockport43.18 N78.65 W52067032482N.A.N.A.N.A.N.A.
Massena FAA AP44.93 N74.85 W21482552046–158471627
NY Central Pk WSO City40.78 N73.97 W13248053634N.A.N.A.N.A.790
NY Kennedy WSO AP40.65 N73.78 W1650273342118872N.A.
NY La Guardia WSO AP40.77 N73.90 W1149103547138973790
Oswego East43.47 N76.50 W35067332431N.A.N.A.N.A.N.A.
Plattsburgh AFB44.65 N73.47 W16578372175–98369N.A.
Poughkeepsie FAA AP41.63 N73.88 W1556391266328872N.A.
Rochester WSO AP43.12 N77.67 W5476734240618671608
Rome/Griffiss AFB43.23 N75.40 W50572442344–58670N.A.
Schenectady42.83 N73.92 W22068812500N.A.N.A.N.A.N.A.
Syracuse WSO AP43.12 N76.12 W42168342399–38571730
Utica43.10 N75.28 W50070662354N.A.N.A.N.A.N.A.
Watertown43.97 N75.87 W49775402294–128370N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
North Carolina (NC)
Asheville WSO AP35.43 N82.55 W214043083365118571915
Charlotte WSO AP35.22 N80.93 W70033414704189174777
Durham36.03 N78.97 W40638674159N.A.N.A.N.A.N.A.
Elizabeth City FAA AP36.27 N76.18 W1031394765N.A.N.A.N.A.N.A.
Fayetteville/Pope AFB35.17 N79.02 W21729175308229476N.A.
Goldsboro35.33 N77.97 W10930405018229476N.A.
Greensboro WSO AP36.08 N79.95 W88638654144159074718
Greenville35.62 N77.38 W3031294824N.A.N.A.N.A.N.A.
Henderson36.37 N78.42 W48040384002N.A.N.A.N.A.N.A.
Hickory FAA AP35.73 N81.38 W114337284199189172N.A.
Jacksonville/New River34.70 N77.43 W2624565678239278N.A.
Lumberton34.70 N79.07 W13032124723N.A.N.A.N.A.N.A.
New Bern FAA AP35.07 N77.05 W1827425262229278N.A.
Raleigh-Durham WSFO AP35.87 N78.78 W37634574499169075740
Rocky Mount35.90 N77.72 W11033214586N.A.N.A.N.A.N.A.
Wilmington WSO AP34.27 N77.90 W7224705557239178N.A.
North Dakota (ND)
Bismarck WSFO AP46.77 N100.77 W164789682144–219067556
Devils Lake KDLR48.12 N98.87 W146499501973–238767N.A.
Dickinson FAA AP46.78 N102.80 W258186572152N.A.N.A.N.A.N.A.
Fargo WSO AP46.90 N96.80 W90092542289–228870546
Grand Forks FAA AP47.95 N97.17 W84797332084–208869N.A.
Jamestown FAA AP46.92 N98.68 W149291682262N.A.N.A.N.A.N.A.
Minot FAA AP48.27 N101.28 W171591932135–208866581
Ohio (OH)
Akron-Canton WSO AP40.92 N81.43 W12086160277908571680
Ashtabula41.85 N80.80 W69064292604N.A.N.A.N.A.N.A.
Bowling Green41.38 N83.62 W67564822876N.A.N.A.N.A.N.A.
Cambridge40.02 N81.58 W80054883118N.A.N.A.N.A.N.A.
Cincinnati-Abbe WSO39.15 N84.52 W7604988373359075N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Ohio cont.)
Cleveland WSFO AP41.42 N81.87 W7706201275518672N.A.
Columbus WSO AP40.00 N82.88 W8125708311918873708
Dayton WSCMO AP39.90 N84.20 W99557083249–18873611
Defiance41.28 N84.38 W70066282810N.A.N.A.N.A.N.A.
Findlay FAA AP41.02 N83.67 W79763022907–28772N.A.
Fremont41.33 N83.12 W60064392823N.A.N.A.N.A.N.A.
Lancaster39.73 N82.63 W86059882935N.A.N.A.N.A.N.A.
Lima Sewage Plant40.72 N84.13 W85062533050N.A.N.A.N.A.N.A.
Mansfield WSO AP40.82 N82.52 W129562582818–18572N.A.
Marion40.62 N83.13 W96564072836N.A.N.A.N.A.N.A.
Newark Water Works40.08 N82.42 W83556573107N.A.N.A.N.A.N.A.
Norwalk41.27 N82.62 W67064342715N.A.N.A.N.A.N.A.
Portsmouth38.75 N82.88 W54049133581N.A.N.A.N.A.N.A.
Sandusky41.45 N82.72 W58461312986N.A.N.A.N.A.N.A.
Springfield New Wtr Wk39.97 N83.82 W93062542790N.A.N.A.N.A.N.A.
Steubenville40.38 N80.63 W99257003054N.A.N.A.N.A.N.A.
Toledo Express WSO AP41.58 N83.80 W66965792720–28772652
Warren41.20 N80.82 W90064022546N.A.N.A.N.A.N.A.
Wooster Exp Station40.78 N81.92 W102063792570N.A.N.A.N.A.N.A.
Youngstown WSO AP41.25 N80.67 W117865442536–18570679
Zanesville FAA AP39.95 N81.90 W8815714301328873N.A.
Oklahoma (OK)
Ada34.78 N96.68 W101531825317N.A.N.A.N.A.N.A.
Altus AFB34.65 N99.27 W1378315157081310073N.A.
Ardmore34.20 N97.15 W86027025978N.A.N.A.N.A.N.A.
Bartlesville36.75 N96.00 W71537774976N.A.N.A.N.A.N.A.
Chickasha Exp Station35.05 N97.92 W108533665298N.A.N.A.N.A.N.A.
Enid36.42 N97.87 W12453788511959874N.A.
Lawton34.62 N98.45 W115034575268129773N.A.
McAlester FAA AP34.88 N95.78 W76033545233109676N.A.
Muskogee35.77 N95.33 W58334135185N.A.N.A.N.A.N.A.
Norman35.18 N97.45 W11093,2955272N.A.N.A.N.A.N.A.
Oklahoma City WSFO AP35.40 N97.60 W12803659497299674733

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Oklahoma cont.)
Ponca City FAA AP36.73 N97.10 W99942264791N.A.N.A.N.A.N.A.
Seminole35.23 N96.67 W86530975552N.A.N.A.N.A.N.A.
Stillwater36.12 N97.10 W89540284718N.A.N.A.N.A.N.A.
Tulsa WSO AP36.18 N95.90 W6683691515099776591
Woodward36.45 N99.38 W190039004884N.A.N.A.N.A.N.A.
Oregon (OR)
Astoria WSO AP46.15 N123.88 W8515814372572621236
Baker FAA AP44.83 N117.82 W336871551741N.A.N.A.N.A.N.A.
Bend44.07 N121.28 W366069261405N.A.N.A.N.A.N.A.
Corvallis State Univ44.63 N123.20 W22549232051N.A.N.A.N.A.N.A.
Eugene WSO AP44.12 N123.22 W36445462354218765N.A.
Grants Pass42.42 N123.33 W96042192986N.A.N.A.N.A.N.A.
Klamath Falls42.20 N121.78 W40986634195448762N.A.
Medford WSO AP42.38 N122.88 W130046112989219566749
Pendleton WSO AP45.68 N118.85 W14925294278739363N.A.
Portland WSFO AP45.60 N122.60 W21452225172286661060
Roseburg KQEN43.20 N123.35 W46543122607N.A.N.A.N.A.N.A.
Salem WSO AP44.92 N123.02 W19549272100208766916
Pennsylvania (PA)
Allentown WSO AP40.65 N75.43 W3885785302858872710
Altoona FAA AP40.30 N78.32 W14766140271958670N.A.
Chambersburg39.93 N77.63 W64055743060N.A.N.A.N.A.N.A.
Erie WSO AP42.08 N80.18 W7326279265228370716
Harrisburg FAA AP40.22 N76.85 W3385347335898973648
Johnstown40.33 N78.92 W121456493028N.A.N.A.N.A.N.A.
Lancaster40.05 N76.28 W27055843079N.A.N.A.N.A.N.A.
Meadville41.63 N80.17 W106569342209N.A.N.A.N.A.N.A.
New Castle41.02 N80.37 W82565422502N.A.N.A.N.A.N.A.
Philadelphia WSCMO AP39.88 N75.23 W1049543623118974646
Pittsburgh WSCMO2 AP40.50 N80.22 W11505968283628670700
Reading40.37 N75.93 W27057963021N.A.N.A.N.A.N.A.
State College40.80 N77.87 W117063642629N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Pennsylvania cont.)
Uniontown39.92 N79.72 W95656842913N.A.N.A.N.A.N.A.
Warren41.85 N79.15 W121068902334N.A.N.A.N.A.N.A.
West Chester39.97 N75.63 W45052833288N.A.N.A.N.A.N.A.
Williamsport WSO AP41.25 N76.92 W5246087279628771N.A.
York Pump Station 2239.92 N76.75 W39052563274N.A.N.A.N.A.N.A.
Rhode Island (RI)
Newport41.52 N71.32 W2056592548N.A.N.A.N.A.N.A.
Providence WSO AP41.73 N71.43 W515884274358671684
South Carolina (SC)
Anderson34.53 N82.67 W80029654900N.A.N.A.N.A.N.A.
Charleston WSO AP32.90 N80.03 W4120136188N.A.N.A.N.A.N.A.
Charleston WSO City32.78 N79.93 W1018666303259277N.A.
Columbia WSFO AP33.95 N81.12 W21326495508219475705
Florence FAA AP34.18 N79.72 W14625855597239476N.A.
Georgetown33.35 N79.25 W1020815947N.A.N.A.N.A.N.A.
Greenville-Spartanburg WSO AP34.90 N82.22 W97332724625199174851
Greenwood34.17 N82.20 W61532884673N.A.N.A.N.A.N.A.
Orangeburg33.50 N80.87 W16025345477N.A.N.A.N.A.N.A.
Spartanburg34.98 N81.88 W84028875046N.A.N.A.N.A.N.A.
Sumter/Shaw AFB33.97 N80.48 W24025065453249375N.A.
South Dakota (SD)
Aberdeen WSO AP45.45 N98.43 W129684462497N.A.N.A.N.A.N.A.
Brookings44.32 N96.77 W164286532228N.A.N.A.N.A.N.A.
Huron WSO AP44.38 N98.22 W128279232709–179171545
Mitchell43.72 N98.00 W127475582925N.A.N.A.N.A.N.A.
Pierre FAA AP44.38 N100.28 W172674112938–149569557
Rapid City WSO AP44.05 N103.07 W316273012412–119165572
Sioux Falls WSFO AP43.57 N96.73 W141878092735–169072599
(South Dakota, cont.)
Watertown FAA AP44.92 N97.15 W174683752499N.A.N.A.N.A.N.A.
Yankton42.88 N97.35 W118073042935N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
Tennessee (TN)
Athens35.43 N84.58 W94040544040N.A.N.A.N.A.N.A.
Bristol WSO AP36.48 N82.40 W15254406362198772N.A.
Chattanooga WSO AP35.03 N85.20 W69235874609159275684
Clarksville Sew Plt36.55 N87.37 W38241594241N.A.N.A.N.A.N.A.
Columbia35.63 N87.08 W65042064047N.A.N.A.N.A.N.A.
Dyersburg FAA AP36.02 N89.40 W33735365010N.A.N.A.N.A.N.A.
Greeneville Exp Stn36.10 N82.85 W132043923710N.A.N.A.N.A.N.A.
Jackson FAA AP35.60 N88.92 W43335404915129376N.A.
Knoxville WSO AP35.80 N84.00 W94939374164139074703
Memphis FAA-AP35.05 N90.00 W26530825467169477851
Murfreesboro35.92 N86.37 W55039924270N.A.N.A.N.A.N.A.
Nashville WSO AP36.12 N86.68 W58037294689109275749
Tullahoma35.35 N86.20 W104836304422N.A.N.A.N.A.N.A.
Texas (TX)
Abilene WSO AP32.42 N99.68 W178425846050169771648
Alice27.73 N98.07 W20110628121N.A.N.A.N.A.N.A.
Amarillo WSO AP35.23 N101.70 W35904258412869466680
Austin WSO AP30.30 N97.70 W59716887171259674664
Bay City Waterworks28.98 N95.98 W5213707211N.A.N.A.N.A.N.A.
Beaumont Research Ctr30.07 N94.28 W2716776703299279N.A.
Beeville28.45 N97.70 W25513727393289877N.A.
Big Spring32.25 N101.45 W250027725621N.A.N.A.N.A.N.A.
Brownsville WSO AP25.90 N97.43 W196358777369477422
Brownwood31.72 N99.00 W138521996479N.A.N.A.N.A.N.A.
Corpus Christi WSO AP27.77 N97.50 W4410168023329478543
Corsicana32.08 N96.47 W42523966133N.A.N.A.N.A.N.A.
Dallas FAA AP32.85 N96.85 W44022596587179874N.A.
Del Rio/Laughlin AFB29.37 N100.78 W107915657207289873732
Denton33.20 N97.10 W63026655816N.A.N.A.N.A.N.A.
Eagle Pass28.70 N100.48 W80514417682N.A.N.A.N.A.N.A.
El Paso WSO AP31.80 N106.40 W391827085488219864735

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Texas cont.)
Ft Worth/Meacham32.82 N97.35 W69223046557199874N.A.
Galveston WSO City29.30 N94.80 W712637378N.A.N.A.N.A.N.A.
Greenville33.20 N96.22 W61029535527N.A.N.A.N.A.N.A.
Harlingen26.20 N97.67 W388138405N.A.N.A.N.A.N.A.
Houston /Hobby29.65 N95.28 W5013717357299377N.A.
Houston-Bush
Intercontinental Airport
29.97 N95.35 W9615996876279477N.A.
Huntsville30.72 N95.55 W49418626697N.A.N.A.N.A.N.A.
Killeen/Robert-Gray31.07 N97.83 W101421276477209673N.A.
Lamesa32.70 N101.93 W296531595107N.A.N.A.N.A.N.A.
Laredo27.57 N99.50 W430102584953210174598
Longview32.47 N94.73 W33024335920N.A.N.A.N.A.N.A.
Lubbock WSFO AP33.65 N101.82 W325434314833119567743
Lufkin FAA AP31.23 N94.75 W28119516527239577681
McAllen26.20 N98.22 W1227788597349876N.A.
Midland/Odessa WSO
AP
31.95 N102.18 W285727515588179767729
Mineral Wells FAA AP32.78 N98.07 W93426256015N.A.N.A.N.A.N.A.
Palestine31.78 N95.60 W46520056454N.A.N.A.N.A.N.A.
Pampa No 235.53 N100.98 W325043584131N.A.N.A.N.A.N.A.
Pecos31.42 N103.50 W261025055992N.A.N.A.N.A.N.A.
Plainview34.18 N101.70 W337037174462N.A.N.A.N.A.N.A.
Port Arthur WSO AP29.95 N94.02 W1614996994N.A.N.A.N.A.697
San Angelo WSO AP31.37 N100.50 W190324146070209770619
San Antonio WSFO29.53 N98.47 W79416447142269673N.A.
Sherman33.63 N96.62 W72028905682N.A.N.A.N.A.721
Snyder32.72 N100.92 W233531855178N.A.N.A.N.A.N.A.
Temple31.08 N97.37 W70021536487N.A.N.A.N.A.N.A.
Tyler32.35 N95.40 W54521946562N.A.N.A.N.A.N.A.
Vernon34.08 N99.30 W120231865605N.A.N.A.N.A.N.A.
Victoria WSO AP28.85 N96.92 W10412967507299476N.A.
Waco WSO AP31.62 N97.22 W50021796668229975622
Wichita Falls WSO AP33.97 N98.48 W99430425717N.A.N.A.N.A.723

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
Utah (UT)
Cedar City FAA AP37.70 N113.10 W56105962277029159629
Logan Utah State Univ41.75 N111.80 W479068542541N.A.N.A.N.A.N.A.
Moab38.60 N109.60 W396544944356N.A.N.A.N.A.N.A.
Ogden Sugar Factory41.23 N112.03 W428059503053N.A.N.A.N.A.N.A.
Richfield Radio KSVC38.77 N112.08 W527063672300N.A.N.A.N.A.N.A.
Saint George37.10 N113.57 W276032155424N.A.N.A.N.A.N.A.
Salt Lake City NWSFO40.78 N111.95 W42225765327669462586
Vernal Airport40.45 N109.52 W526075622334N.A.N.A.N.A.N.A.
Vermont (VT)
Burlington WSO AP44.47 N73.15 W33277712228-118469637
Rutland43.60 N72.97 W62070662345N.A.N.A.N.A.N.A.
Virginia (VA)
Charlottesville38.03 N78.52 W87042243902N.A.N.A.N.A.N.A.
Danville-Bridge St36.58 N79.38 W41039444236N.A.N.A.N.A.N.A.
Fredericksburg Natl Pk38.32 N77.45 W9045543754N.A.N.A.N.A.N.A.
Lynchburg WSO AP37.33 N79.20 W91643403728129074N.A.
Norfolk WSO AP36.90 N76.20 W2234954478209176685
Richmond WSO AP37.50 N77.33 W16439634223149275716
Roanoke WSO AP37.32 N79.97 W114943603715128972713
Staunton Sewage Plant38.15 N79.03 W138552733004N.A.N.A.N.A.N.A.
Winchester39.18 N78.12 W68052693215N.A.N.A.N.A.N.A.
Washington (WA)
Aberdeen46.97 N123.82 W1052851488N.A.N.A.N.A.N.A.
Bellingham FAA AP48.80 N122.53 W14956091508157664N.A.
Bremerton47.57 N122.67 W16251191839N.A.N.A.N.A.N.A.
Ellensburg46.97 N120.55 W148067701999N.A.N.A.N.A.N.A.
Everett47.98 N122.18 W6053111660N.A.N.A.N.A.N.A.
Kennewick46.22 N119.10 W39048953195N.A.N.A.N.A.N.A.
Longview46.15 N122.92 W1250941858N.A.N.A.N.A.N.A.
Olympia WSO AP46.97 N122.90 W19256551558188365985
Port Angeles48.12 N123.40 W4056951257N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Washington cont.)
Seattle EMSU WSO47.65 N122.30 W2046112120N.A.N.A.N.A.N.A.
Seattle-Tacoma
WSCMO AP
47.45 N122.30 W45049082021238164982
Spokane WSO AP47.63 N117.53 W235668422032N.A.N.A.N.A.640
Tacoma/McChord AFB47.15 N122.48 W32251551820188263N.A.
Walla Walla FAA AP46.10 N118.28 W11664958316149565N.A.
Wenatchee47.42 N120.32 W6405579295639265N.A.
Yakima WSO AP46.57 N120.53 W10645967234849264703
West Virginia (WV)
Beckley WSO AP37.78 N81.12 W 250455582690N.A.N.A.N.A.N.A.
Bluefield FAA AP37.30 N81.22 W28705230290758369N.A.
Charleston WSFO AP38.37 N81.60 W10154646365568873704
Clarksburg39.27 N80.35 W94555123014N.A.N.A.N.A.N.A.
Elkins WSO AP38.88 N79.85 W199261202360-28370N.A.
Huntington WSO AP38.37 N82.55 W8274665361568973N.A.
Martinsburg FAA AP39.40 N77.98 W5315192336889173N.A.
Morgantown FAA AP39.65 N79.92 W12405363315548771N.A.
Parkersburg39.27 N81.57 W6155094350748872N.A.
Wisconsin (WI)
Appleton44.25 N88.37 W75076932513N.A.N.A.N.A.N.A.
Ashland Exp Farm46.57 N90.97 W65089601811N.A.N.A.N.A.N.A.
Beloit42.50 N89.03 W78071612737N.A.N.A.N.A.N.A.
Eau Claire FAA AP44.87 N91.48 W88883302407-188771661
Fond du Lac43.80 N88.45 W76075412573N.A.N.A.N.A.N.A.
Green Bay WSO AP44.48 N88.13 W68280892177-138572651
La Crosse FAA AP43.87 N91.25 W65174912790-148873644
Madison WSO AP43.13 N89.33 W8587672389-118772658
Manitowoc44.10 N87.68 W66075972193N.A.N.A.N.A.N.A.
Marinette45.10 N87.63 W60580592272N.A.N.A.N.A.N.A.
Milwaukee WSO AP42.95 N87.90 W67273242388-78672618
Racine42.70 N87.77 W59571672459N.A.N.A.N.A.N.A.
Sheboygan43.75 N87.72 W64870872390N.A.N.A.N.A.N.A.

TABLE D-1 US and US Territory Climatic Data (continued)

State
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-BulbNo. Hrs.
8 a.m.–4 p.m.
99.6%1.0%1.0%55 < Tdb < 69
(Wisconsin cont.)
Stevens Point44.50 N89.57 W107980092325N.A.N.A.N.A.N.A.
Waukesha43.02 N88.23 W86071172658N.A.N.A.N.A.N.A.
Wausau FAA AP44.92 N89.62 W119684272182-158570N.A.
Wyoming (WY)
Casper WSO AP42.92 N106.47 W533876822082-138958535
Cheyenne WSFO AP41.15 N104.82 W612073261886-78557608
Cody44.52 N109.07 W505074312057-148758N.A.
Evanston41.27 N110.95 W681088461285N.A.N.A.N.A.N.A.
Lander WSO AP42.82 N108.73 W537078892184-148758N.A.
Laramie FAA AP41.32 N105.68 W726690081237N.A.N.A.N.A.N.A.
Newcastle43.85 N104.22 W441072672518N.A.N.A.N.A.N.A.
Rawlins FAA AP41.80 N107.20 W673684751605N.A.N.A.N.A.N.A.
Rock Springs FAA AP41.60 N109.07 W674183651734-98454552
Sheridan WSO AP44.77 N106.97 W396478042023-149061574
Torrington Exp Farm42.08 N104.22 W409868792429N.A.N.A.N.A.N.A.
District of Columbia (DC)
R. Reagan Nat'1. Airport38.85 N77.03 W6640474391159276657
Puerto Rico (PR)
San Juan/Isla Verde WSFO18.43 N66.00 W10011,406699078N.A.
Pacific Islands (PI)
Guam (GU) - Andersen AFB13.58 N144.93 E361010,690748779N.A.
Marshall Island (MH) - Kwajalein Atoll8.73 N167.73 E26011,670768879N.A.
Midway Island (MH) - Midway Island NAF28.22 N177.37 W131348323598675N.A.
Samoa (WS) - Pago Pago WSO Airport14.33 S170.72 W9011,018728880N.A.
Wake Island - Wake Island WSO Airport19.28 N166.65 E12011,097718979N.A.
Philippines
Philippines (PH) - Angeles, Clark AFB15.18 N120.55 E475011,280689577N.A.

TABLE D-2 Canadian Climatic Data

Province
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
Alberta (AB)
Calgary International A51.12 N114.02 W353398851167-228059
Edmonton International A53.30 N113.58 W234511,0231069-28.17862
Grande Prairie A55.18 N118.88 W218511,2401031-327860
Jasper52.88 N118.07 W348010,244848N.A.N.A.N.A.
Lethbridge A49.63 N112.80 W304787831730-228461
Medicine Hat A50.02 N110.72 W235289881981-248762
Red Deer A52.18 N113.90 W296910,7651095-277961
British Columbia (BC)
Dawson Creek A55.73 N120.18 W214811,435890N.A.N.A.N.A.
Ft Nelson A58.83 N122.58 W125312,9411013-337860
Kamloops50.67 N120.33 W124367792335-88863
Nanaimo A49.05 N123.87 W9860541469N.A.N.A.N.A.
New Westminster BC Pen49.22 N122.90 W5955201691N.A.N.A.N.A.
Penticton A49.47 N119.60 W11286500200258764
Prince George53.88 N122.67 W22679495906-257859
Prince Rupert A54.30 N130.43 W111765057276357
Vancouver International A49.18 N123.17 W956821536187464
Victoria Gonzales Hts48.42 N123.32 W22954941286237562
Manitoba (MB)
Brandon CDA49.87 N99.98 W119010,9691661-298466
Churchill A58.73 N94.07 W9116,719275-367260
Dauphin A51.10 N100.05 W100011,2421520-288466
Flin Flon54.77 N101.85 W109912,3071352N.A.N.A.N.A.
Portage La Prairie A49.90 N98.27 W88510,5941807-258567
The Pas A53.97 N101.10 W88912,4901231-327964
Winnipeg International A49.90 N97.23 W78410,8581784-278467
New Brunswick (NB)
Chatham A47.02 N65.45 W11190281531-128367
Fredericton A45.87 N66.53 W5586661631-128368
Moncton A46.12 N64.68 W23287311427-108067
Saint John A45.33 N65.88 W33787761179-97564
Newfoundland (NF)
Corner Brook48.95 N57.95 W1687561075N.A.N.A.N.A.

TABLE D-2 Canadian Climatic Data (continued)

Province
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
(Newfoundland cont.)
Gander International A48.95 N54.57 W4959354956–47663
Goose A53.32 N60.42 W15012,017758–237761
St John's A47.62 N52.73 W439888884837364
Stephenville A48.53 N58.55 W268869952–27164
Northwest Territories (NW)
Ft Smith A60.02 N111.95 W66614,192932–347861
Inuvik A68.30 N133.48 W19318,409489–437559
Yellowknife A62.47 N114.45 W67215,555851–397459
Nova Scotia (NS)
Halifax International A44.88 N63.52 W41681331464–27866
Kentville CDA45.07 N64.48 W16076831665N.A.N.A.N.A.
Sydney A46.17 N60.05 W18383641287–17867
Truro45.37 N63.27 W13185961295–97767
Yarmouth A43.83 N66.08 W1417515118077164
Nunavut
Resolute A74.72 N94.98 W21922,8640–424843
Ontario (ON)
Belleville44.15 N77.40 W24975562252N.A.N.A.N.A.
Cornwall45.02 N74.75 W20980622187N.A.N.A.N.A.
Hamilton RBG43.28 N79.88 W33468722450N.A.N.A.N.A.
Kapuskasing A49.42 N82.47 W74411,7421108–308065
Kenora A49.78 N94.37 W133510,8841626–278165
Kingston A44.22 N76.60 W30578261960N.A.N.A.N.A.
London A43.03 N81.15 W91275652126–38370
North Bay A46.35 N79.43 W117497941509–187866
Oshawa WPCP43.87 N78.83 W27572532106N.A.N.A.N.A.
Ottawa International A45.32 N75.67 W38085712045–138369
Owen Sound MOE44.58 N80.93 W58777301896N.A.N.A.N.A.
Peterborough44.28 N78.32 W63680371975N.A.N.A.N.A.
St Catharines43.20 N79.25 W29867002564N.A.N.A.N.A.
Sudbury A46.62 N80.80 W114199901557–198166
Thunder Bay A48.37 N89.32 W65210,5621198–228066
Timmins A48.57 N81.37 W96711,3741225–288165

TABLE D-2 Canadian Climatic Data (continued)

Province
City
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
(Ontario cont.)
Toronto Downsview A43.75 N79.48 W64973062370–48470
Windsor A42.27 N82.97 W6236619267928671
Prince Edward Island (PE)
Charlottetown A46.28 N63.13 W15785981400–67767
Summerside A46.43 N63.83 W7884111536–57766
Québec (PQ)
Bagotville A48.33 N71.00 W52110,6031300–238065
Drummondville45.88 N72.48 W26986012024N.A.N.A.N.A.
Granby45.38 N72.70 W55183671984N.A.N.A.N.A.
Montreal Dorval International A45.47 N73.75 W10182852146–128370
Québec City A46.80 N71.38 W22994491571–168068
Rimouski48.45 N68.52 W11896651215N.A.N.A.N.A.
Sept-Iles A50.22 N66.27 W18011,287690–206959
Shawinigan46.57 N72.75 W40092461720N.A.N.A.N.A.
Sherbrooke A45.43 N71.68 W78094641372–208068
St Jean de Cherbourg48.88 N67.12 W115111,277801N.A.N.A.N.A.
St Jerome45.80 N74.05 W55791711771N.A.N.A.N.A.
Thetford Mines46.10 N71.35 W125096871425N.A.N.A.N.A.
Trois Rivieres46.37 N72.60 W17391241766N.A.N.A.N.A.
Val d'Or A48.07 N77.78 W110511,2561193–278065
Valleyfield45.28 N74.10 W1508083 2268N.A.N.A.N.A.
Saskatchewan (SK)
Estevan A49.22 N102.97 W187610,0921793–258665
Moose Jaw A50.33 N105.55 W189399891812–278764
North Battleford A52.77 N108.25 W179711,1271473–318263
Prince Albert A53.22 N105.68 W140412,0091252–348164
Regina A50.43 N104.67 W189310,7731620–298564
Saskatoon A52.17 N106.68 W164311,1181537–318463
Swift Current A50.28 N107.68 W268310,1281541–258462
Yorkton A51.27 N102.47 W163311,4311476–308264
Yukon Territory (YT)
Whitehorse A60.72 N135.07 W230612,797611–347355

TABLE D-3 International Climatic Data

Country
City
Province or
Region
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
Argentina
Buenos Aires/Ezeiza34.82S58.53W6622114693319072
Cordoba31.32S64.22W155518165182319172
Tucuman/Pozo26.85S65.10W144414166622N.A.N.A.N.A.
Australia
AdelaideSA34.95S138.53E2020824381399264
Alice SpringsNT23.80S133.90E1782114277773410264
BrisbaneQL27.43S153.08E75457009448672
Darwin AirportNT12.43S130.87E95011,736649276
Perth/GuildfordWA31.92S115.97E5615075353419566
Sydney/K SmithNSW33.95S151.18E2013515259428567
Azores
LajesTerceira38.75N27.08W18012794892467871
Bahamas
Nassau25.05N77.47W10299775579078
Belgium
Brussels Airport50.90N4.47E12854601862157966
Bermuda
St Georges/Kindley32.37N64.68W201708365N.A.N.A.N.A.
Bolivia
La Paz/El Alto16.50S68.18W13,2877189237256244
Brazil
Belem1.43S48.48W79011,552729078
Brasilia15.77S47.93W3809587943488865
Fortaleza3.72S38.55W62111,748729078
Porto Alegre30.08S51.18W239027076409275
Recife/Curado8.13S34.92W36210,951709178
Rio de Janeiro22.90S43.17W16149688599977
Salvador/Ondina13.00S38.52W167010,785688878
Sao Paulo23.50S46.62W26084477219488869
Bulgaria
Sofia42.82N23.38E195256292508108565
Chile
Concepcion36.77S73.05W3935592283357462
Punta Arenas/Chabunco53.03S70.85W1087807395236153

TABLE D-3 International Climatic Data (continued)

Country
City
Province or
Region
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
(Chile cont.)
Santiago/Pedahuel33.38S70.88W157528203471298865
China
Beijing/PekingMunicipalities39.93N116.28E18052524115129272
Hong Kong Intl ArptSpecial Admin. Region22.33N114.18E795437894489179
ShanghaiMunicipalities31.40N121.47E1331825124299280
Shanghai/HongqiaoMunicipalities31.17N121.43E2331845127269282
Tianjin/TientsinMunicipalities39.10N117.17E1649484450149174
AnqingAnhui30.53N117.05E6630935476289480
BengbuAnhui32.95N117.37E723,445053239379
FuyangAnhui32.93N115.83E12836395004239379
Hefei/LuogangAnhui31.87N117.23E11834685110259380
Huang Shan (Mtns)Anhui30.13N118.15E60246723164797065
HuoshanAnhui31.40N116.33E22335164907249480
ChangtingFujian25.85N116.37E102019026289309177
FudingFujian27.33N120.20E12518686277349280
FuzhouFujian26.08N119.28E27913967047409480
Jiuxian ShanFujian25.72N118.10E541739232763237467
LongyanFujian25.10N117.02E111911207248379375
NanpingFujian26.65N118.17E42015516986359578
PingtanFujian25.52N119.78E10214786550438779
PuchengFujian27.92N118.53E90223255940299378
ShaowuFujian27.33N117.43E63020756232299478
XiamenFujian24.48N118.08E45610147,26439179
Yong'AnFujian25.97N117.35E66915706917339577
DunhuangGansu40.15N94.68E37406531327219364
HezuoGansu35.00N102.90E95479760491–57054
HuajialingGansu35.38N105.00E8038927587147056
Jiuquan/SuzhouGansu39.77N98.48E484973162473–28662
LanzhouGansu36.05N103.88E498058492954118763
Mazong Shan (Mount)Gansu41.80N97.03E580791871748–98455
MinqinGansu38.63N103.08E44857045283008961

TABLE D-3 International Climatic Data (continued)

Country
City
Province or
Region
LatitudeLongitudeElev., ftHDD65CDD50Heating Design
Temperature
Cooling Design Temperature
Dry-BulbWet-Bulb
99.6%1.0%1.0%
(China cont.)
PingliangGansu35.55N106.67E44236248240798464
Ruo'ergaiGansu33.58N102.97E11,28910,826232–86552
TianshuiGansu34.58N105.75E375051923073178767
WuduGansu33.40N104.92E354034194250289068
Wushaoling (Pass)Gansu37.20N102.87E998711,697263–56450
XifengzhenGansu35.73N107.63E466964712388108263
YumenzhenGansu40.27N97.03E501076142367–38660
ZhangyeGansu38.93N100.43E486572882439–28862
FogangGuangdong23.87N113.53E22310637709399279
GaoyaoGuangdong23.05N112.47E397208493449380
Guangzhou/BaiyunGuangdong23.13N113.32E267378352429380
HeyuanGuangdong23.73N114.68E1359028079409379
Lian XianGuangdong24.78N112.38E32216607018359479
LianpingGuangdong24.37N114.48E70213017189369278
MeixianGuangdong24.30N116.12E2769378016399479
Shangchuan IslandGuangdong21.73N112.77E595148621468981
ShantouGuangdong23.40N116.68E107797743459080
ShanweiGuangdong22.78N115.37E165288272468979
ShaoguanGuangdong24.80N113.58E22313707565379479
ShenzhenGuangdong22.55N114.10E595318597449280
XinyiGuangdong22.35N110.93E2765708763439379
YangjiangGuangdong21.87N111.97E725478470459080
ZhangjiangGuangdong21.22N110.40E924239002469280
BeihaiGuangxi21.48N109.10E526218826