ADOPTS WITH AMENDMENTS:

International Building Code 2012 (IBC 2012)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall control the classification of all buildings and structures as to use and occupancy.
Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed in this section. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically provided for in this code, such structure shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved.
  1. Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5
  2. Business (see Section 304): Group B
  3. Educational (see Section 305): Group E
  4. Factory and Industrial (see Section 306): Groups F-1 and F-2
  5. High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5
  6. Institutional (see Section 308): Groups I-1, I-2, I-3 and I-4
  7. Mercantile (see Section 309): Group M
  8. Residential (see Section 310): Groups R-1, R-2, R-3 and R-4
  9. Storage (see Section 311): Groups S-1 and S-2
  10. Utility and Miscellaneous (see Section 312): Group U
Occupancies for care facilities shall be classified in accordance with the following table.

TABLE 302.2
CARE FACILITIES

TYPE OF LICENSED FACILITYNUMBER OR
TYPE OF RESIDENTS
IBC
OCCUPANCY CLASSIFICATION
Child Care
(Day Care)
Family Child Care Home10 occupants maximum with
≤ 6 below school age
R-3
dwelling unit
Group Child Care Home
< 24 hours per day
11 — 14 occupants maximumR-3
dwelling unit
Child Care Center
< 24 hours per day
> 5 but ≤ 100 children < 2.5
years of age and each room at,
and with, an exit at the level of
exit discharge
E
Child Care Center
< 24 hours per day
More than 5 children > 2.5
years of age
E
Child Care Center
< 24 hours per day
More than 5 children ≤ 2.5
years of age
I-4
Adult Day CareFamily Adult Day Services≤ 8 impaired adultsR-3
dwelling unit
Adult Day Care Center
< 24 hours per day
6 or more occupants, all may or
may not be capable of self preservation
I-4
Adult Day Care Center
< 24 hours per day
6 or more occupants, but having
no more than 50 percent of the
occupants who are not capable
of self-preservation
E

(continued)

TABLE 302.2—continued
CARE FACILITIES

TYPE OF LICENSED FACILITYNUMBER OR
TYPE OF RESIDENTS
IBC
OCCUPANCY CLASSIFICATION
Supervised Living FacilitiesClass A-16 or fewer residents; all of
whom are capable of self-preservation
R-3
dwelling unit
Class A-27 to 16 residents; all of whom
are capable of self-preservation
R-4
Class A-2More than 16 residents; all of
whom are capable of self-preservation
I-1
Class B-16 or fewer residents; all of
whom may not be capable of
self-preservation
R-3
Class B-27 to 16 residents; all of whom
may not be capable of self-preservation
R-4
Class B-3More than 16 residents; all of
whom may not be capable of
self-preservation
I-2
HospiceResidential Hospice Facility1 — 5 terminally ill personsR-3
Residential Hospice facility6 — 12 terminally ill personsR-4
Adult Foster CareAdult Foster Care Home1 — 5 impaired adultsR-3
dwelling unit
Child Foster CareFoster Care1 — 6 foster children without
sever disability or assisted
medical technology
R-3
dwelling unit
Foster Care1 — 4 foster children with medical or special care servicesR-3
dwelling unit
Housing with Services FacilityHousing with Services
Establishment
Housing with Services
Establishment Providing
Assisted Living Services
1 — 5 adult residents ≥ 80 percent
55 years of age or older unless
registered under MN Statutes,
Section 144D.025
R-3
dwelling unit
Housing with Services
Establishment
Housing with Services
Establishment Providing
Assisted Living Services
6 — 16 adult residents ≥ 80 percent
55 years of age or older unless
registered under MN Statutes,
Section 144D.025
R-4
Housing with Services
Establishment
Housing with Services
Establishment Providing
Assisted Living Services
16 adult residents ≥ 80 percent
55 years of age or older unless
registered under MN Statutes,
Section 144D.025
I-1
Boarding CareBoarding Care Home< 5 residentsR-3
dwelling unit
Boarding Care Home6 — 16 residentsR-4
Boarding Care Home> 16 residentsI-1
Boarding and LodgingBoarding and Lodging≤ 16 residents in sleeping rooms
or ≤ 2 dwelling units in one
building
R-3
Boarding and Lodging> 16 residents in sleeping rooms
or > 2 dwelling units in one
building
R-2

(continued)

TABLE 302.2—continued
CARE FACILITIES

TYPE OF LICENSED FACILITYNUMBER OR
TYPE OF RESIDENTS
IBC
OCCUPANCY CLASSIFICATION
Boarding and LodgingBoarding and Lodging
< 30 days
Bed and breakfast with 6 or
more sleeping units boarding
houses with > 10 occupants
R-1
Boarding and Lodging
< 30 days
Bed and Breakfast with 5 or
fewer sleeping units boarding
houses with ≤ 10 occupants
R-3
dwelling unit
Senior HousingSenior Housing (See IBC 310)More than 2 dwelling units in
one building
R-2
Senior Housing (See IBC 310)2 dwelling units in one buildingR-3
Senior Housing (See IBC 310)1 dwelling unitR-3
dwelling unit
Congregate ResidenceCongregate Residence≤ 16 residentsR-3
Congregate Residence17 or more residentsR-2
Day ServicesDay Services FacilityAdults (over 18)I-4
Day Services FacilityAges 13 — 18I-4
Chemical Dependency
Treatment Programs
Chemical Dependency
Treatment Program—
Outpatient (< 24 hours)
Not regulatedB
Chemical Dependency
Treatment Program—Residential
< 5 residentsR-3
dwelling unit
Chemical Dependency
Treatment Program—Residential
6 — 16 residentsR-4
Chemical Dependency
Treatment Program—Residential
> 16 residentsI-1
Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation.
A building or tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B occupancy.
The following rooms and spaces shall not be classified as Assembly occupancies:
  1. A room or space used for assembly purposes with an occupant load of less than 50 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
  2. A room or space used for assembly purposes that is less than 750 square feet (70 m2) in area and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy.
Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100 are not considered separate occupancies.
Assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:
Motion picture theaters
Symphony and concert halls
Television and radio studios admitting an audience
Theaters
Assembly uses intended for food and/or drink consumption including, but not limited to:
Banquet halls
Casinos (gaming areas)
Nightclubs
Restaurants, cafeterias and similar dining facilities (including associated commercial kitchens)
Taverns and bars
Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:
Amusement arcades
Art galleries
Bowling alleys
Community halls
Courtrooms
Dance halls (not including food or drink consumption)
Exhibition halls
Funeral parlors
Gymnasiums (without spectator seating)
Indoor swimming pools (without spectator seating)
Indoor tennis courts (without spectator seating)
Lecture halls
Libraries
Museums
Pool and billiard parlors
Waiting areas in transportation terminals
Assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:
Arenas
Skating rinks
Tennis courts
Assembly uses intended for participation in or viewing outdoor activities including, but not limited to:
Amusement park structures
Stadiums

304.1 Business Group B

ILLUSTRATION
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following:
Airport traffic control towers
Animal hospitals, kennels and pounds
Banks
Barber and beauty shops
Car wash
Civic administration
Dry cleaning and laundries: pick-up and delivery stations and self-service
Educational occupancies for students above the 12th grade
Electronic data processing
Laboratories: testing and research
Motor vehicle showrooms
Post offices
Print shops
Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
Radio and television stations
Telephone exchanges
Training and skill development not within a school or academic program
Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade.
Religious educational rooms and religious auditoriums, which are accessory to places of religious worship in accordance with Section 303.1.4.and have occupant loads of less than 100, shall be classified as Group A-3 occupancies.
This group includes buildings and structures or portions thereof occupied by more than five children older than 21/2 years of age who receive educational, supervision or personal care services for fewer than 24 hours per day.
Rooms and spaces within places of religious worship providing such day care during religious functions shall be classified as part of the primary occupancy.
A facility having five or fewer children receiving such day care shall be classified as part of the primary occupancy.
A facility such as the above within a dwelling unit and having five or fewer children receiving such day care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H hazardous or Group S storage occupancy.
Factory industrial uses which are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:
Aircraft (manufacturing, not to include repair)
Appliances
Athletic equipment
Automobiles and other motor vehicles
Bakeries
Beverages: over 16-percent alcohol content
Bicycles
Boats
Brooms or brushes
Business machines
Cameras and photo equipment
Canvas or similar fabric
Carpets and rugs (includes cleaning)
Clothing
Construction and agricultural machinery
Disinfectants
Dry cleaning and dyeing
Electric generation plants
Electronics
Engines (including rebuilding)
Food processing and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities
Furniture
Hemp products
Jute products
Laundries
Leather products
Machinery
Metals
Millwork (sash and door)
Motion pictures and television filming (without spectators)
Musical instruments
Optical goods
Paper mills or products
Photographic film
Plastic products
Printing or publishing
Recreational vehicles
Refuse incineration
Shoes
Soaps and detergents
Textiles
Tobacco
Trailers
Upholstering
Wood; distillation
Woodworking (cabinet)
Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials which during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:

Beverages: up to and including 16-percent alcohol content

Brick and masonry

Ceramic products

Foundries

Glass products

Gypsum

Ice

Metal products (fabrication and assembly)

High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the International Fire Code. Hazardous materials stored, or used on top of roofs or canopies shall be classified as outdoor storage or use and shall comply with the International Fire Code.
Exception: The following shall not be classified as Group H, but shall be classified as the occupancy that they most nearly resemble.
  1. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the International Fire Code.
  2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the International Fire Code.
  3. Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment.
  4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707.or 1-hour horizontal assemblies constructed in accordance with Section 711, or both.
  5. Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
  6. Liquor stores and distributors without bulk storage.
  7. Refrigeration systems.
  8. The storage or utilization of materials for agricultural purposes on the premises.
  9. Stationary batteries utilized for facility emergency power, uninterruptable power supply or telecommunication facilities, provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the International Mechanical Code.
  10. Corrosives shall not include personal or household products in their original packaging used in retail display or commonly used building materials.
  11. Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the International Fire Code.
  12. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
  13. The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the International Fire Code.

[F] TABLE 307.1(1)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, p

MATERIALCLASSGROUP
WHEN THE
MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
STORAGEbUSE-CLOSED SYSTEMSbUSE-OPEN SYSTEMSb
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas (cubic
feet at NTP)
Solid pounds
(cubic feet)
Liquid
gallons
(pounds)
Gas (cubic
feet at NTP)
Solid
pounds
(cubic feet)
Liquid
gallons
(pounds)
Combustible dustN/AH-2Note qN/AN/ANote qN/AN/ANote qN/A
Combustible liquidc, iII
IIIA
IIIB
H-2 or H-3
H-2 or H-3
N/A
N/A120d, e
330d, e
13,200e, f
N/AN/A120d
330d
13,200f
N/AN/A30d
80d
3,300f
Combustible fiberLoose
Baledo
H-3(100)
(1,000)
N/AN/A(100)
(1,000)
N/AN/A(20)
(200)
N/A
Consumer fireworks 1.4GH-3125d, e, lN/AN/AN/AN/AN/AN/AN/A
Cryogenics,
flammable
N/AH-2N/A45dN/AN/A45dN/AN/A10d
Cryogenics, inertN/AN/A N/AN/ANLN/AN/ANLN/AN/A
Cryogenics,
oxidizing
N/AH-3N/A45dN/AN/A45dN/AN/A10d
ExplosivesDivision 1.1H-11e, g(1)e, gN/A0.25g(0.25)gN/A0.25g(0.25)g
Division 1.2H-11e, g(1)e, gN/A0.25g(0.25)gN/A0.25g(0.25)g
Division 1.3H-1 or H-25e, g(5)e, gN/A1g(1)gN/A1g(1)g
Division 1.4H-350e, g(50)e, gN/A50g(50)gN/AN/A N/A
Division 1.4GH-3125d, e, lN/AN/AN/AN/AN/AN/AN/A
Division 1.5H-11e, g(1)e, gN/A0.25g(0.25)gN/A0.25g(0.25)g
Division 1.6H-11d, e, gN/AN/AN/AN/AN/AN/AN/A
Flammable gasGaseous
Liquefied
H-2N/AN/A
(150)d,e
1,000d,e
N/A
N/AN/A
(150)d,e
1,000d,e
N/A
N/AN/A
Flammable liquidc1A
1B and 1C
H-2
or H-3
N/A30d, e
120d, e
N/AN/A30d
120d
N/AN/A10d
30d
Flammable liquid,
combination
(1A, 1B, 1C)
N/AH-2
or H-3
N/A120d, e, hN/AN/A120d, hN/AN/A30d, h
Flammable solidN/AH-3125d, eN/AN/A125dN/AN/A25dN/A
Inert gasGaseousN/AN/AN/ANLN/AN/ANLN/AN/A
LiquefiedN/AN/AN/ANLN/AN/ANLN/AN/A
Organic peroxideUDH-11e, g(1)e, gN/A0.25g(0.25)gN/A0.25g(0.25)g
IH-25d, e(5)d, eN/A1d(1)dN/A1d(1)d
IIH-350d, e(50)d, eN/A50d(50)dN/A10d(10)d
IIIH-3125d, e(125)d, eN/A125d(125)dN/A25d(25)d
IVN/ANLNLN/ANLNLN/ANLNL
VN/ANLNLN/ANLNLN/ANLNL
Oxidizer4H-11e, g(1)e, gN/A0.25g(0.25)gN/A0.25g(0.25)g
3kH-2 or H-310d, e(10)d, eN/A2d(2)dN/A2d(2)d
2H-3250d, e(250)d, eN/A250d(250)dN/A50d(50)d
1N/A4,000e, f(4,000)e, fN/A4,000f(4,000)fN/A1,000f(1,000)f

(continued)

[F] TABLE 307.1(1)—(continued)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa, j, m, n, p

MATERIALCLASSGROUP
WHEN THE
MAXIMUM
ALLOWABLE
QUANTITY IS
EXCEEDED
STORAGEbUSE-CLOSED SYSTEMSbUSE-OPEN SYSTEMSb
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)
Gas
(cubic feet
at NTP)
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)
Gas
(cubic feet
at NTP)
Solid
pounds
(cubic
feet)
Liquid
gallons
(pounds)
Oxidizing gasGaseousH-3N/AN/A1,500d,eN/AN/A1,500d,eN/AN/A
LiquefiedN/A(150)d,eN/AN/A(150)d,eN/AN/AN/A
Pyrophoric materialN/AH-24e, g(4)e, g50e,g1g(1)g10g00
Unstable (reactive)4H-11e, g(1)e, g10g0.25g(0.25)g2e, g0.25g(0.25)g
3H-1 or H-25d, e(5)d, e50d, e1d(1)d10d, e1d(1)d
2H-350d, e(50)d, e250d, e50d(50)d250d, e10d(10)d
1N/ANLNLNLNLNLNLNLNL
Water reactive3H-25d, e(5)d, eN/A5d(5)dN/A1d(1)d
2H-350d, e(50)d, eN/A50d(50)dN/A10d(10)d
1N/ANLNLN/ANLNLN/ANLNL
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L. NL = Not Limited; N/A = Not Applicable; UD = Unclassified Detonable
  1. For use of control areas, see Section 414.2.
  2. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
  3. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
  4. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  5. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10.f the International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
  6. The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  7. Permitted only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  8. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids.
  9. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2.f the International Fire Code.
  10. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
  11. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment. Storage containers and the manner of storage shall be approved.
  12. Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used.
  13. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code.
  14. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
  15. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
  16. The following shall not be included in determining the maximum allowable quantities:
    1. Liquid or gaseous fuel in fuel tanks on vehicles.
    2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this code.
    3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code.
    4. Liquid fuels in piping systems and fixed appliances regulated by the International Mechanical Code.
  17. Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.

[F] TABLE 307.1(2)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARDa, b, c, i

MATERIALSTORAGEdUSE-CLOSED SYSTEMSdUSE-OPEN SYSTEMSd
Solid pounds
(cubic feet)
Liquid gallons
(pounds)e, f
Gas (cubic feet
at NTP)e
Solid poundseLiquid gallons
(pounds)e
Gas (cubic feet at NTP)eSolid poundseLiquid gallons
(pounds)
e
Corrosive5,000500Gaseous 810f
Liquefied
(150)h
5,000500Gaseous 810f
Liquefied
(150)h
1,000100
Highly toxic10(10)hGaseous 20g
Liquefied
(4)g,h
10(10)iGaseous 20g
Liquefied
(4)g,h
3(3)i
Toxic500(500)hGaseous 810f
Liquefied
(150)f,h
500(500)iGaseous 810f
Liquefied
(150)f,h
125(125)
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
  1. For use of control areas, see Section 414.2.
  2. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
  3. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
  4. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
  5. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively.
  6. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the International Fire Code. Where Note e also applies, the increase for both notes shall be applied accumulatively.
  7. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the International Fire Code.
  8. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
  9. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the International Fire Code.
Hazardous materials in any quantity shall conform to the requirements of this code, including Section 414, and the International Fire Code.
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:
Detonable pyrophoric materials
Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6

Organic peroxides, unclassified detonable

Oxidizers, Class 4

Unstable (reactive) materials, Class 3 detonable and Class 4

The following occupancies containing explosive materials shall be classified as follows:
  1. Division 1.3 explosive materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
  2. Articles, including articles packaged for shipment, that are not regulated as a Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Exoplosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.
Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids which are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 psi (103.4 kPa) gage
Combustible dusts where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3
Cryogenic fluids, flammable
Flammable gases
Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or sytems pressurized at more than 15 psi (103 kPa) gage
Pyrophoric liquids, solids and gases, nondetonable
Unstable (reactive) materials, Class 3, nondetonable
Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103.4 kPa) or less
Consumer fireworks, 1.4G (Class C, Common)
Cryogenic fluids, oxidizing
Organic peroxides, Class II and III
Oxidizers, Class 2
Oxidizers, Class 3, that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103 kPa) or less
Oxidizing gases
Unstable (reactive) materials, Class 2
Buildings and structures which contain materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:
Highly toxic materials
Toxic materials
Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and constructed in accordance with Section 415.10.
Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which care or supervision is provided to persons who are or are not capable of self-preservation without physical assistance or in which persons are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.
This occupancy shall include buildings, structures, or portions thereof for more than 16 persons who reside on a 24-hour basis in a supervised environment and receive custodial care. The persons receiving care are capable of self-preservation. Examples of this group include the following:
Alcohol and drug centers
Assisted living facilities
Boarding care
Congregate care facilities
Convalescent facilities
Halfway houses
Housing with services establishment
Residential board and care facilities
Social rehabilitation facilities
Supervised living facilities Class A-2
A facility such as the above with five or fewer persons receiving such care shall be classified as Group R-3.
A facility such as above housing not fewer than six and not more than 16 persons receiving such care, shall be classified as Group R-4.
This occupancy shall include buildings and structures used for medical care on a 24-hour basis for more than five persons who are incapable of self-preservation. Examples of this group include the following:
Hospitals
Psychiatric hospitals
Supervised living facilities Class B-3
A facility such as the above with five or fewer persons receiving such care shall be classified as Group R-3.
This occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. An I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control. This group shall include, but not be limited to, the following:
Correctional centers
Detention centers
Jails
Prerelease centers
Prisons
Reformatories

Buildings of Group I-3 shall be classified as one of the occupancy conditions indicated in Sections 308.5.1.through 308.5.5.(see Section 408.1).

This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits.
This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote-controlled release of means of egress from such a smoke compartment to another smoke compartment.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
This group shall include buildings and structures occupied by more than five persons of any age who receive custodial care for fewer than 24 hours per day by persons other than parents or guardians, relatives by blood, marriage or adoption, and in a place other than the home of the person cared for. This group shall include, but not be limited to, the following:
Adult day care
Child day care
A child day care facility that provides care for more than five but no more than 100 children 21/2 years or less of age, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E.
Rooms and spaces within places of religious worship providing such care during religious functions shall be classified as part of the primary occupancy.
A facility having five or fewer persons receiving custodial care shall be classified as part of the primary occupancy.
A facility such as the above within a dwelling unit and having five or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy.
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof, for the display and sale of merchandise and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:
Department stores
Drug stores
Markets
Retail or wholesale stores
Sales rooms
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I. This group shall not include buildings regulated by Chapter 1309, the International Residential Building Code (IRC). However, the licensed uses specified in Sections 310.5.and 310.6, as amended by this part, are applicable to a building constructed in accordance with the IRC that houses a use that is required to be licensed.
R-1 Residential occupancies containing sleeping units where the occupants are primarily transient in nature, including:
Bed and breakfast facilities with six or more guest rooms. A facility with fewer than six guest rooms shall be classified as a Group R-3 occupancy.
Boarding houses (transient) with more than ten occupants
Congregate living facilities (transient) with more than ten occupants
Hotels (transient)
Motels (transient)
R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
Apartment houses
Boarding houses (nontransient) with more than 16 occupants
Congregate living facilities (nontransient) with more than 16 occupants
Convents
Fraternities and sororities
Hotels (nontransient)
Monasteries
Motels (nontransient)
Vacation timeshare properties
R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as R-1, R-2, R-4, or I including:
Assisted living
Boarding care homes
Boarding houses (nontransient) with 16 or fewer occupants
Boarding houses (transient) with 10 or fewer occupants
Care facilities that provide accommodations for five or fewer persons receiving care
Congregate living facilities (nontransient) with 16 or fewer occupants
Congregate living facilities (transient) with 10 or fewer occupants
Dwelling units in mixed occupancy buildings
Family adult foster homes
Foster care
Housing with services establishment
Residential hospice with five or fewer occupants

In new construction, Group R-3 occupancies shall meet the requirements for building durability of Chapter 1309, the International Residential Building Code, parts 1309.0402; 1309.0406, subpart 2; 1309.0702, subpart 2; 1309.0703, subpart 2a; 1309.0703, subpart 9, items A, B, and C; 1309.0903; and 2012 IRC Section R703.8.1.

This occupancy shall include buildings, structures, or portions thereof for more than five but not more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. The persons receiving care are capable of self-preservation. This group shall include the following:
Alcohol and drug centers
Assisted living
Boarding care homes
Congregate care facilities
Halfway houses
Housing with services establishment (including those that provide assisted living services)
Residential board and care facilities
Residential hospice with 12 or fewer occupants
Social rehabilitation facilities

Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in this code.

Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy.
Buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following:
Aerosols, Levels 2 and 3
Aircraft hangar (storage and repair)
Bags: cloth, burlap and paper
Bamboos and rattan
Baskets
Belting: canvas and leather
Books and paper in rolls or packs
Boots and shoes
Buttons, including cloth covered, pearl or bone
Cardboard and cardboard boxes
Clothing, woolen wearing apparel
Cordage
Dry boat storage (indoor)
Furniture
Furs
Glues, mucilage, pastes and size
Grains
Horns and combs, other than celluloid
Leather
Linoleum
Lumber
Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 307.1(1) (see Section 406.8)
Photo engravings
Resilient flooring
Silks
Soaps
Sugar
Tobacco, cigars, cigarettes and snuff
Upholstery and mattresses
Wax candles
Includes, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:
Asbestos
Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
Cement in bags
Chalk and crayons
Dairy products in nonwaxed coated paper containers
Dry cell batteries
Electrical coils
Electrical motors
Empty cans
Food products
Foods in noncombustible containers
Fresh fruits and vegetables in nonplastic trays or containers
Frozen foods
Glass
Glass bottles, empty or filled with noncombustible liquids
Inert pigments
Ivory
Meats
Metal cabinets
Metal desks with plastic tops and trim
Metal parts
Metals
Mirrors
Oil-filled and other types of distribution transformers
Parking garages, open or enclosed
Porcelain and pottery
Stoves
Talc and soapstones
Washers and dryers
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:
Aircraft hangars, accessory to a one- or two-family residence (see Section 412.5)
Barns
Carports
Fences more than 6 feet (1829 mm) in height
Grain silos, accessory to a residential occupancy
Greenhouses
Livestock shelters
Private garages
Retaining walls
Sheds
Stables
Tanks
Towers
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING