The provisions of this chapter shall govern the design, materials, construction and quality of
roof assemblies, and
rooftop structures.
The following terms are defined in
Chapter 2:
AGGREGATE.
Roof decks shall be covered with
approved roof coverings secured to the building or structure in accordance with the provisions of this chapter.
Roof coverings shall be designed and installed in accordance with this code and the
approved manufacturer’s instructions such that the
roof covering shall serve to protect the building or structure.
Flashing shall be installed in such a manner so as to prevent moisture entering the
wall and roof through
joints in copings, through moisture-permeable materials and at intersections with
parapet walls and other penetrations through the roof plane.
Flashing shall be installed at
wall and roof intersections, at gutters, wherever there is a change in roof slope or direction and around roof openings. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inch (0.483 mm) (No. 26 galvanized sheet).
Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width no less than the thickness of the
parapet wall.
Design and installation of roof drainage systems shall comply with Minnesota Rules, Chapter 4715,
Minnesota Plumbing Code, and the following provisions:
1. Where required.
All roofs shall drain into a separate storm sewer system or to an approved place of disposal. For one- and two-family dwellings, and where approved, storm water is permitted to discharge onto flat areas, such as streets or lawns, provided that the storm water flows away from the building.
2. Roof design.
Roofs shall be designed for the maximum possible depth of water that will pond thereon as determined by the relative levels of roof deck and overflow weirs, scuppers, edges, or serviceable drains in combination with the deflected structural elements. In determining the maximum possible depth of water, all primary roof drainage means shall be assumed to be blocked.
3. Secondary drainage required.
Secondary (emergency) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason.
4. Separate systems required.
Secondary (emergency) roof drain systems shall have piping and point of discharge separate from the primary system. Discharge shall be above grade in a location which would normally be observed by the building occupants or maintenance personnel.
5. Sizing of secondary drains.
Secondary (emergency) roof drain systems shall be sized in accordance with the Minnesota State Plumbing Code. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by this code. Scuppers shall not have an opening dimension of less than 4 inches (102 mm). The flow through the primary system shall not be considered when sizing the secondary roof drainage system.
When
scuppers are used for secondary (emergency overflow) roof drainage, the quantity, size, location and inlet elevation of the
scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by
Section 1611.1.
Scuppers shall not have an opening dimension of less than 4 inches (102 mm). The flow through the primary system shall not be considered when locating and sizing
scuppers.
Gutters and leaders placed on the outside of buildings, other than Group R-3, private garages and buildings of
Type V construction, shall be of noncombustible material or a minimum of Schedule 40 plastic pipe.
Intake and exhaust vents shall be provided in accordance with
Section 1203.2.and the manufacturer’s installation instructions.
A cricket or saddle shall be installed on the ridge side of any
chimney or penetration greater than 30 inches (762 mm) wide as measured perpendicular to the slope. Cricket or saddle coverings shall be sheet metal or of the same material as the
roof covering.
Exception: Unit skylights installed in accordance with
Section 2405.5.and flashed in accordance with the manufacturer’s instructions shall be permitted to be installed without a cricket or saddle.
Roof decks and
roof coverings shall be designed for wind
loads in accordance with
Chapter 16.and Sections
1504.2,
1504.3.and
1504.4.
Asphalt shingles shall comply with
Section 1507.2.7.
Wind
loads on clay and
concrete tile
roof coverings shall be in accordance with
Section 1609.5.
Roof coverings installed on roofs in accordance with
Section 1507.that are mechanically attached or adhered to the
roof deck shall be designed to resist the design wind load pressures for components and cladding in accordance with
Section 1609.
Roof systems with built-up, modified bitumen, fully adhered or mechanically attached single-ply through fastened metal
panel roof systems, and other types of membrane
roof coverings shall also be tested in accordance with FM 4474, UL 580 or UL 1897.
Metal
panel roof systems through fastened or standing seam shall be tested in accordance with UL 580 or ASTM E1592.
Exception: Metal roofs constructed of cold-formed steel, where the
roof deck acts as the
roof covering and provides both weather protection and support for structural
loads, shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in
Section 2210.1.
Ballasted low-slope (roof slope < 2:12) single-ply roof system coverings installed in accordance with Sections
1507.12.and
1507.13.shall be designed in accordance with
Section 1504.8.and ANSI/SPRI RP-4.
Low-slope built-up, modified bitumen and single-ply roof system metal edge securement, except gutters, shall be designed and installed for wind
loads in accordance with
Chapter 16.and tested for resistance in accordance with Test Methods RE-1, RE-2 and RE-3 of ANSI/SPRI ES-1, except
Vult wind speed shall be determined from Figure 1609A, 1609B, or
1609C as applicable.
Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with
Section 1507.shall demonstrate physical integrity over the working life of the roof based upon 2,000 hours of exposure to accelerated weathering tests conducted in accordance with ASTM G152, ASTM G155 or ASTM G154. Those
roof coverings that are subject to cyclical flexural response due to wind
loads shall not demonstrate any significant loss of tensile
strength for unreinforced membranes or breaking
strength for reinforced membranes when tested as herein required.
Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with
Section 1507.shall resist impact damage based on the results of tests conducted in accordance with ASTM D3746, ASTM D4272, CGSB 37-GP-52M or the “Resistance to Foot Traffic Test” in Section 5.5 of FM 4470.
Aggregate used as surfacing for
roof coverings and aggregate, gravel or stone used as
ballast shall not be used on the roof of a building located in a hurricane-prone region as defined in
Section 202, or on any other building with a mean roof height exceeding that permitted by Table 1504.8.based on the exposure category and basic wind speed at the
site.
TABLE 1504.8
MAXIMUM ALLOWABLE MEAN ROOF HEIGHT PERMITTED FOR
BUILDINGS WITH AGGREGATE ON THE ROOF IN AREAS
OUTSIDE A HURRICANE-PRONE REGION
NOMINAL DESIGN WIND SPEED, Vasd (mph)b, d | MAXIMUM MEAN ROOF HEIGHT (ft)a, c |
Exposure category |
B | C | D |
85 | 170 | 60 | 30 |
90 | 110 | 35 | 15 |
95 | 75 | 20 | NP |
100 | 55 | 15 | NP |
105 | 40 | NP | NP |
110 | 30 | NP | NP |
115 | 20 | NP | NP |
120 | 15 | NP | NP |
Greater than 120 | NP | NP | NP |
For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. |
a. Mean roof height as defined in ASCE 7. |
b. For intermediate values of Vasd, the height associated with the next higher value of Vasd shall be used, or direct interpolation is permitted. |
c. NP = gravel and stone not permitted for any roof height. |
Roof assemblies shall be divided into the classes defined below. Class A, B and C
roof assemblies and
roof coverings required to be listed by this section shall be tested in accordance with ASTM E108 or UL 790. In addition,
fire-retardant-treated wood roof coverings shall be tested in accordance with ASTM D2898. The minimum
roof coverings installed on buildings shall comply with Table 1505.1.based on the type of construction of the building.
TABLE 1505.1a, b
MINIMUM ROOF COVERING CLASSIFICATION
FOR TYPES OF CONSTRUCTION
IA | IB | IIA | IIB | IIIA | IIIB | IV | VA | VB |
B | B | B | Cc | B | Cc | B | B | Cc |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2. |
b. Nonclassified roof coverings shall be permitted on buildings of Group R-3 and Group U occupancies, where there is a minimum fire-separation distance of 6 feet measured from the leading edge of the roof. |
c. Buildings that are not more than two stories above grade plane and having not more than 6,000 square feet of projected roof area and where there is a minimum 10-foot fire-separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1 cedar or redwood shakes and No. 1 shingles. |
Class A
roof assemblies are those that are effective against severe fire test exposure. Class A
roof assemblies and
roof coverings shall be
listed and identified as Class A by an
approved testing agency. Class A
roof assemblies shall be permitted for use in buildings or structures of all types of construction.
Exceptions:
1. Class A roof assemblies include those with coverings of brick, masonry or an exposed concrete roof deck.
2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
3. Class A roof assemblies include minimum 16 oz/sq. ft. (0.0416 kg/m2) copper sheets installed over combustible decks.
Class B
roof assemblies are those that are effective against moderate fire-test exposure. Class B
roof assemblies and
roof coverings shall be
listed and identified as Class B by an
approved testing agency.
Class C
roof assemblies are those that are effective against light fire-test exposure. Class C
roof assemblies and
roof coverings shall be
listed and identified as Class C by an
approved testing agency.
Nonclassified roofing is
approved material that is not
listed as a Class A, B or C
roof covering.
Fire-retardant-treated wood shakes and shingles shall be treated by impregnation with chemicals by the full-
cell vacuum-pressure process, in accordance with AWPA C1. Each bundle shall be marked to identify the manufactured unit and the manufacturer, and shall also be
labeled to identify the classification of the material in accordance with the testing required in
Section 1505.1, the treating company and the quality control agency.
Special purpose wood shingle or wood shake roofing shall conform with the grading and application requirements of
Section 1507.8.or
1507.9. In addition, an
underlayment of
5/
8-inch (15.9 mm) Type X water-resistant gypsum
backing board or gypsum sheathing shall be placed under minimum
nominal 1/
2-inch-thick (12.7 mm)
wood structural panel solid sheathing or 1-inch (25 mm)
nominal spaced sheathing.
Rooftop installed photovoltaic systems that are adhered or attached to the
roof covering or
photovoltaic modules/shingles installed as
roof coverings shall be
labeled to identify their fire classification in accordance with the testing required in
Section 1505.1.
The requirements set forth in this section shall apply to the application of roof-covering materials specified herein.
Roof coverings shall be applied in accordance with this chapter and the manufacturer’s installation instructions. Installation of
roof coverings shall comply with the applicable provisions of
Section 1507.
Roofs and
roof coverings shall be of materials that are compatible with each other and with the building or structure to which the materials are applied.
Roof-covering materials shall conform to the applicable standards listed in this chapter. In the absence of applicable standards or where materials are of questionable suitability, testing by an approved agency shall be required by the building code official to determine the character, quality and limitations of application of the materials.
Roof-covering materials shall be delivered in packages bearing the manufacturer’s identifying marks and
approved testing agency
labels required in accordance with
Section 1505. Bulk shipments of materials shall be accompanied with the same information issued in the form of a certificate or on a bill of lading by the manufacturer.
Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer’s installation instructions.
The installation of asphalt shingles shall comply with the provisions of this section.
Asphalt shingles shall be fastened to solidly sheathed decks.
Asphalt shingles shall only be used on roof slopes of two units vertical in 12 units horizontal (17-percent slope) or greater. For roof slopes from two units vertical in 12 units horizontal (17-percent slope) up to four units vertical in 12 units horizontal (33-percent slope), double
underlayment application is required in accordance with
Section 1507.2.8.
Unless otherwise noted, required
underlayment shall conform to ASTM D226,
Type I, ASTM D 4869,
Type I, or ASTM D6757.
Self-adhering polymer modified bitumen sheet shall comply with ASTM D1970.
Asphalt shingles shall comply with ASTM D225 or ASTM D3462.
Fasteners for asphalt shingles shall be galvanized, stainless steel, aluminum or copper roofing nails, minimum 12 gage [0.105 inch (2.67 mm)] shank with a minimum 3/8 inch-diameter (9.5 mm) head, of a length to penetrate through the roofing materials and a minimum of 3/4 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 3/4 inch (19.1 mm) thick, the nails shall penetrate through the sheathing. Fasteners shall comply with ASTM F1667.
Asphalt shingles shall have the minimum number of fasteners required by the manufacturer, but not less than four fasteners per strip shingle or two fasteners per individual shingle. Where the roof slope exceeds 21 units vertical in 12 units horizontal (21:12), shingles shall be installed as required by the manufacturer.
Asphalt shingles shall be tested in accordance with ASTM D7158. Asphalt shingles shall meet the classification requirements of Table 1507.2.7.1(1) for the appropriate maximum basic wind speed. Asphalt shingle packaging shall bear a
label to indicate compliance with ASTM D7158 and the required classification in Table 1507.2.7.1(1).
Exception: Asphalt shingles not included in the scope of ASTM D7158 shall be tested and
labeled to indicate compliance with ASTM D3161 and the required classification in Table 1507.2.7.1(2).
TABLE 1507.2.7.1(1)
CLASSIFICATION OF ASPHALT
ROOF SHINGLES PER ASTM D7158a
NOMINAL DESIGN WIND SPEED, Vasdb (mph) | CLASSIFICATION REQUIREMENT |
85 | D, G or H |
90 | D, G or H |
100 | G or H |
110 | G or H |
120 | G or H |
130 | H |
140 | H |
150 | H |
For SI: 1 foot = 304.8 mm; 1 mph = 0.447 m/s. |
a. The standard calculations contained in ASTM D7158 assume exposure category B or C and building height of 60 feet or less. Additional calculations are required for conditions outside of these assumptions. |
TABLE 1507.2.7.1(2)
CLASSIFICATION OF ASPHALT SHINGLES PER ASTM D3161
NOMINAL DESIGN WIND SPEED, Vasda (mph) | CLASSIFICATION REQUIREMENT |
85 | A, D or F |
90 | A, D or F |
100 | A, D or F |
110 | F |
120 | F |
130 | F |
140 | F |
150 | F |
For SI: 1 mph = 0.447 m/s. |
For roof slopes from two units vertical in 12 units horizontal (17-percent slope) and up to four units vertical in 12 units horizontal (33-percent slope),
underlayment shall be two layers applied in the following manner. Apply a minimum 19-inch-wide (483 mm) strip of
underlayment felt parallel with and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply 36-inch-wide (914 mm) sheets of
underlayment overlapping successive sheets 19 inches (483 mm), by fastened sufficiently to hold in place. Distortions in the
underlayment shall not interfere with the ability of the shingles to seal. For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater,
underlayment shall be one layer applied in the following manner.
Underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches (51 mm), fastened sufficiently to hold in place. Distortions in the
underlayment shall not interfere with the ability of the shingles to seal.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer's instructions. Fasteners are to be applied along the overlap at a maximum spacing of 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II, ASTM D4869
Type IV, or ASTM D6757. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with
Section 1507.2.8.except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer modified bitumen sheet shall be used in lieu of normal
underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Flashing for asphalt shingles shall comply with this section. Flashing shall be applied in accordance with this section and the asphalt shingle manufacturer’s printed instructions.
Base and cap flashing shall be installed in accordance with the manufacturer’s instructions. Base flashing shall be of either corrosion-resistant metal of minimum
nominal 0.019-inch (0.483 mm) thickness or mineral-surfaced roll roofing weighing a minimum of 77 pounds per 100 square feet (3.76 kg/m
2). Cap flashing shall be corrosion-resistant metal of minimum
nominal 0.019-inch (0.483 mm) thickness.
Valley linings shall be installed in accordance with the manufacturer’s instructions before applying shingles. Valley linings of the following types shall be permitted:
1. For open valleys (valley lining exposed) lined with metal, the valley lining shall be at least 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table 1507.2.9.2.
2. For open valleys, valley lining of two plies of mineral-surfaced roll roofing complying with ASTM D3909 or ASTM D6380 shall be permitted. The bottom layer shall be 18 inches (457 mm) and the top layer a minimum of 36 inches (914 mm) wide.
3. For closed valleys (valleys covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380, and at least 36 inches (914 mm) wide or types as described in Item 1 or 2 above shall be permitted. Self-adhering polymer modified bitumen underlayment complying with ASTM D1970 shall be permitted in lieu of the lining material.
TABLE 1507.2.9.2
VALLEY LINING MATERIAL
MATERIAL | MINIMUM THICKNESS | GAGE | WEIGHT |
Aluminum | 0.024 in. | — | — |
Cold-rolled copper | 0.0216 in. | — | ASTM B370, 16 oz. per square ft. |
Copper | — | — | 16 oz |
Galvanized steel | 0.0179 in. | 26 (zinc-coated G90) | — |
High-yield copper | 0.0162 in. | — | ASTM B370, 12 oz. per square ft. |
Lead | — | — | 2.5 pounds |
Lead-coated copper | 0.0216 in. | — | ASTM B101, 16 oz. per square ft. |
Lead-coated high-yield copper | 0.0162 in. | — | ASTM B101, 12 oz. per square ft. |
Painted terne | — | — | 20 pounds |
Stainless steel | — | 28 | — |
Zinc alloy | 0.027 in. | — | — |
For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg, 1 ounce = 28.35 g, 1 square foot = 0.093 m2. |
Provide drip edge at eaves and gables of shingle roofs. Overlap to be a minimum of 2 inches (51 mm). Eave drip edges shall extend 1/4 inch (6.4 mm) below sheathing and extend back on the roof a minimum of 2 inches (51 mm). Drip edge shall be mechanically fastened a maximum of 12 inches (305 mm) o.c.
The installation of clay and
concrete tile shall comply with the provisions of this section.
Concrete and clay tile shall be installed only over
solid sheathing or spaced structural sheathing boards.
Clay and
concrete roof tile shall be installed on roof slopes of 2
1/
2 units vertical in 12 units horizontal (21-percent slope) or greater. For roof slopes from 2
1/
2 units vertical in 12 units horizontal (21-percent slope) to four units vertical in 12 units horizontal (33-percent slope), double
underlayment application is required in accordance with
Section 1507.3.3.
Unless otherwise noted, required
underlayment shall conform to: ASTM D226,
Type II; ASTM D2626 or ASTM D6380, Class M mineral-surfaced roll roofing.
For roof slopes from 2
1/
2 units vertical in 12 units horizontal (21-percent slope), up to four units vertical in 12 units horizontal (33-percent slope),
underlayment shall be a minimum of two layers applied as follows:
1. Starting at the eave, a 19-inch (483 mm) strip of underlayment shall be applied parallel with the eave and fastened sufficiently in place.
2. Starting at the eave, 36-inch-wide (914 mm) strips of underlayment felt shall be applied overlapping successive sheets 19 inches (483 mm) and fastened sufficiently in place.
For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater,
underlayment shall be a minimum of one layer of
underlayment felt applied shingle fashion, parallel to, and starting from the eaves and lapped 2 inches (51 mm), fastened only as necessary to hold in place.
Underlayment applied in areas subject to high wind [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with Sections
1507.3.3.1.and
1507.3.3.2.except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
Clay roof tile shall comply with ASTM C1167.
Concrete roof tile shall comply with ASTM C1492.
Tile fasteners shall be corrosion resistant and not less than 11 gage,
5/
16-inch (8.0 mm) head, and of sufficient length to penetrate the deck a minimum of
3/
4 inch (19.1 mm) or through the thickness of the deck, whichever is less. Attaching wire for clay or
concrete tile shall not be smaller than 0.083 inch (2.1 mm). Perimeter fastening areas include three tile courses but not less than 36 inches (914 mm) from either side of hips or ridges and edges of eaves and gable rakes.
Clay and
concrete roof tiles shall be fastened in accordance with Table 1507.3.7.
TABLE 1507.3.7
CLAY AND CONCRETE TILE ATTACHMENTa, b, c
GENERAL - CLAY OR CONCRETE ROOF TILE |
Maximum Nominal Design Wind Speed, Vasdf (mph) | Mean roof height (feet) | Roof slope < 3:12 | Roof slope 3:12 and over |
85 | 0-60 | One fastener per tile. Flat tile without vertical laps, two fas teners per tile. | Two fasteners per tile. Only one fastener on slopes of 7:12 and less for tiles with installed weight exceeding 7.5 lbs./sq. ft. having a width no greater than 16 inches. |
100 | 0-40 |
100 | >40-60 | The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be set in a bead of roofer’s mastic. |
110 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
120 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
130 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
All | >60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGSd, e (Installations on spaced/solid sheathing with battens or spaced sheathing) |
Maximum Nominal Design Wind Speed, Vasdf (mph) | Mean roof height (feet) | Roof slope < 5:12 | Roof slope 5:12 < 12:12 | Roof slope 12:12 and over |
85 | 0-60 | Fasteners are not required. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. | One fastener per tile every other row. All perimeter tiles require one fastener. Tiles with installed weight less than 9 lbs./sq. ft. require a mini- mum of one fastener per tile. | One fastener required for every tile. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. |
100 | 0-40 |
100 | >40-60 | The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofer's mastic. |
110 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
120 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
130 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
All | >60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS (Installations on solid sheathing without battens) |
Maximum Nominal Design Wind Speed, Vasdf (mph) | Mean roof height (feet) | All roof slopes |
85 | 0-60 | One fastener per tile. |
100 | 0-40 | One fastener per tile. |
100 | > 40-60 | The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofer’s mastic. |
110 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
120 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
130 | 0-60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
All | > 60 | The fastening system shall resist the wind forces in Section 1609.5.3. |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 4.882 kg/m2. |
a. Minimum fastener size. Corrosion-resistant nails not less than No. 11 gage with 5/16-inch head. Fasteners shall be long enough to penetrate into the sheathing 3/4 inch or through the thickness of the sheathing, whichever is less. Attaching wire for clay and concrete tile shall not be smaller than 0.083 inch. |
b. Snow areas. A minimum of two fasteners per tile are required or battens and one fastener. |
c. Roof slopes greater than 24:12. The nose of all tiles shall be securely fastened. |
d. Horizontal battens. Battens shall be not less than 1 inch by 2 inch nominal. Provisions shall be made for drainage by a minimum of 1/8-inch riser at each nail or by 4-foot-long battens with at least a 1/2-inch separation between battens. Horizontal battens are required for slopes over 7:12. |
e. Perimeter fastening areas include three tile courses but not less than 36 inches from either side of hips or ridges and edges of eaves and gable rakes. |
Tile shall be applied according to the manufacturer's installation instructions, based on the following:
1. Climatic conditions.
2. Roof slope.
3. Underlayment system.
4. Type of tile being installed.
At the juncture of the roof vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm)
underlayment of either one layer of
Type I underlayment running the full length of the valley, or a self-adhering polymer-modified bitumen sheet complying with ASTM D1970, in addition to other required
underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing
underlayment shall be
solid cemented to the roofing
underlayment for slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed.
The installation of
metal roof panels shall comply with the provisions of this section.
Metal roof panel roof coverings shall be applied to a
solid or closely fitted deck, except where the
roof covering is specifically designed to be applied to spaced supports.
Minimum slopes for
metal roof panels shall comply with the following:
1. The minimum slope for lapped, nonsoldered seam metal roofs without applied lap sealant shall be three units vertical in 12 units horizontal (25-percent slope).
2. The minimum slope for lapped, nonsoldered seam metal roofs with applied lap sealant shall be one-half unit vertical in 12 units horizontal (4-percent slope). Lap sealants shall be applied in accordance with the approved manufacturer’s installation instructions.
3. The minimum slope for standing seam of roof systems shall be one-quarter unit vertical in 12 units horizontal (2-percent slope).
Metal-sheet
roof covering systems that incorporate supporting structural members shall be designed in accordance with
Chapter 22. Metal-sheet
roof coverings installed over structural decking shall comply with Table 1507.4.3(1). The materials used for metal-sheet
roof coverings shall be naturally corrosion resistant or provided with
corrosion resistance in accordance with the standards and minimum thicknesses shown in Table 1507.4.3(2).
TABLE 1507.4.3(1)
METAL ROOF COVERINGS
ROOF COVERING TYPE | STANDARD APPLICATION RATE/THICKNESS |
Aluminum | ASTM B209, 0.024 inch minimum thick ness for roll-formed panels and 0.019 inch minimum thickness for press-formed shingles. |
Aluminum-zinc alloy coated steel | ASTM A792 AZ 50 |
Cold-rolled copper | ASTM B370 minimum 16 oz./sq. ft. and 12 oz./sq. ft. high yield copper for metal-sheet roof covering systems: 12 oz./sq. ft. for preformed metal shingle systems. |
Copper | 16 oz./sq. ft. for metal-sheet roof-covering systems; 12 oz./sq. ft. for preformed metal shingle systems. |
Galvanized steel | ASTM A653 G-90 zinc-coateda. |
Hard lead | 2 lbs./sq. ft. |
Lead-coated copper | ASTM B101 |
Prepainted steel | ASTM A755 |
Soft lead | 3 lbs./sq. ft. |
Stainless steel | ASTM A240, 300 Series Alloys |
Steel | ASTM A924 |
Terne and terne coated stainless | Terne coating of 40 lbs. per double base box, field painted where applicable in accordance with manufacturer’s installa tion instructions. |
Zinc | 0.027 inch minimum thickness; 99.995% electrolytic high grade zinc with alloy addi- tives of copper (0.08% - 0.20%), titanium (0.07% - 0.12%) and aluminum (0.015%). |
For SI: 1 ounce per square foot = 0.0026 kg/m2, 1 pound per square foot = 4.882 kg/m2, 1 inch = 25.4 mm, 1 pound = 0.454 kg. |
a. For Group U buildings, the minimum coating thickness for ASTM A653 galvanized steel roofing shall be G-60. |
TABLE 1507.4.3(2)
MINIMUM CORROSION RESISTANCE
55% Aluminum-zinc alloy coated steel | ASTM A792 AZ 50 |
5% Aluminum alloy-coated steel | ASTM A875 GF60 |
Aluminum-coated steel | ASTM A463 T2 65 |
Galvanized steel | ASTM A653 G-90 |
Prepainted steel | ASTM A755a |
a. Paint systems in accordance with ASTM A755 shall be applied over steel products with corrosion-resistant coatings complying with ASTM A792, ASTM A875, ASTM A463 or ASTM A653. |
Metal roof panels shall be secured to the supports in accordance with the
approved manufacturer’s fasteners. In the absence of manufacturer recommendations, the following fasteners shall be used:
1. Galvanized fasteners shall be used for steel roofs.
2. Copper, brass, bronze, copper alloy or 300 series stainless-steel fasteners shall be used for copper roofs.
3. Stainless-steel fasteners are acceptable for all types of metal roofs.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II, ASTM D4869
Type IV, or ASTM D1970. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
The installation of
metal roof shingles shall comply with the provisions of this section.
Metal roof shingles shall be applied to a
solid or closely fitted deck, except where the
roof covering is specifically designed to be applied to spaced sheathing.
Metal roof shingles shall not be installed on roof slopes below three units vertical in 12 units horizontal (25-percent slope).
Underlayment shall comply with ASTM D226,
Type I or ASTM D4869.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II or ASTM D4869
Type IV. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch spacing (152 mm) at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal
underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Metal roof shingle roof coverings shall comply with
Table 1507.4.3(1). The materials used for metal-roof shingle
roof coverings shall be naturally corrosion resistant or provided with
corrosion resistance in accordance with the standards and minimum thicknesses specified in the standards listed in
Table 1507.4.3(2).
Metal roof shingles shall be secured to the roof in accordance with the
approved manufacturer’s installation instructions.
Roof valley flashing shall be of corrosion-resistant metal of the same material as the
roof covering or shall comply with the standards in
Table 1507.4.3(1). The valley flashing shall extend at least 8 inches (203 mm) from the centerline each way and shall have a splash diverter rib not less than
3/
4 inch (19.1 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing shall have a 36-inch-wide (914 mm)
underlayment directly under it consisting of either one layer of
underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D1970, in addition to
underlayment required for
metal roof shingles. The metal valley flashing
underlayment shall be solidly cemented to the roofing
underlayment for roof slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed.
The installation of mineral-surfaced roll roofing shall comply with this section.
Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs.
Mineral-surfaced roll roofing shall not be applied on roof slopes below one unit vertical in 12 units horizontal (8-percent slope).
Underlayment shall comply with ASTM D226,
Type I or ASTM D4869.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal
underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380.
The installation of slate shingles shall comply with the provisions of this section.
Slate shingles shall be fastened to solidly sheathed roofs.
Slate shingles shall only be used on slopes of four units vertical in 12 units horizontal (4:12) or greater.
Underlayment shall comply with ASTM D226,
Type I or ASTM D4869.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II or ASTM D4869
Type IV. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Slate shingles shall comply with ASTM C406.
Minimum headlap for slate shingles shall be in accordance with Table 1507.7.6. Slate shingles shall be secured to the roof with two fasteners per slate.
TABLE 1507.7.6
SLATE SHINGLE HEADLAP
SLOPE | HEADLAP (inches) |
4:12 < slope < 8:12 | 4 |
8:12 < slope < 20:12 | 3 |
slope ? 20:12 | 2 |
For SI: 1 inch = 25.4 mm. |
Flashing and counterflashing shall be made with sheet metal. Valley flashing shall be a minimum of 15 inches (381 mm) wide. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.455 mm) zinc-coated G90.
Chimneys, stucco or
brick walls shall have a minimum of two plies of felt for a cap flashing consisting of a 4-inch-wide (102 mm) strip of felt set in plastic cement and extending 1 inch (25 mm) above the first felt and a top coating of plastic cement. The felt shall extend over the base flashing 2 inches (51 mm).
The installation of wood shingles shall comply with the provisions of this section and Table 1507.8.
TABLE 1507.8
WOOD SHINGLE AND SHAKE INSTALLATION
ROOF ITEM | WOOD SHINGLES | WOOD SHAKES |
1. Roof slope | Wood shingles shall be installed on slopes of three units vertical in 12 units horizontal (3:12) or greater. | Wood shakes shall be installed on slopes of four units vertical in 12 units horizontal (4:12) or greater. |
2. Deck requirement |
Temperate climate | Shingles shall be applied to roofs with solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be less than 1?× 4? nominal dimensions and shall be spaced on center equal to the weather exposure to coincide with the placement of fasteners. | Shakes shall be applied to roofs with solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be less than 1?× 4? nominal dimensions and shall be spaced on center equal to the weather exposure to coincide with the placement of fasteners. When 1? × 4? spaced sheathing is installed at 10 inches, boards must be installed between the sheathing boards. |
In areas where the average daily temperature in January is 25°F or less or where there is a possibility of ice forming along the eaves causing a backup of water. | Solid sheathing required. | Solid sheathing is required. |
3. Interlayment | No requirements. | Interlayment shall comply with ASTM D226, Type 1. |
4. Underlayment | | |
Temperate climate | Underlayment shall comply with ASTM D226, Type 1. | Underlayment shall comply with ASTM D226, Type 1. |
In areas where there is a possibility of ice forming along the eaves causing a backup of water. | An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend from the eave's edge to a point at least 24 inches inside the exterior wall line of the building. | An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend from the lowest edges of all roof surfaces to a point at least 24 inches inside the exterior wall line of the building. |
5. Application | | |
Attachment | Fasteners for wood shingles shall be hotdipped galvanized or Type 304 (Type 316 for coastal areas) stainless steel with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. | Fasteners for wood shakes shall be hot-dipped galvanized or Type 304 (Type 316 for coastal areas) with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. |
No. of fasteners | Two per shingle. | Two per shake. |
Exposure | Weather exposures shall not exceed those set forth in Table 1507.8.7. | Weather exposures shall not exceed those set forth in Table 1507.9.8. |
Method | Shingles shall be laid with a side lap of not less than 1.5 inches between joints in courses, and no two joints in any three adjacent courses shall be in direct alignment. Spacing between shingles shall be 0.25 to 0.375 inch. | Shakes shall be laid with a side lap of not less than 1.5 inches between joints in adjacent courses. Spacing between shakes shall not be less than 0.375 inch or more than 0.625 inch for shakes and taper sawn shakes of naturally durable wood and shall be 0.25 to 0.375 inch for preservative-treated taper sawn shakes. |
Flashing | In accordance with Section 1507.8.8. | In accordance with Section 1507.9.9. |
For SI: 1 inch = 25.4 mm, °C = [(°F) - 32]/1.8. |
Wood shingles shall be installed on
solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be less than 1-inch by 4-inch (25 mm by 102 mm)
nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners.
Solid sheathing is required in areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water.
Wood shingles shall be installed on slopes of three units vertical in 12 units horizontal (25-percent slope) or greater.
Underlayment shall comply with ASTM D226,
Type I or ASTM D4869.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II or ASTM D4869
Type IV. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal
underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Wood shingles shall be of
naturally durable wood and comply with the requirements of Table 1507.8.5.
TABLE 1507.8.5
WOOD SHINGLE MATERIAL REQUIREMENTS
MATERIAL | APPLICABLE MINIMUM GRADES | GRADING RULES |
Wood shingles of naturally durable wood | 1, 2 or 3 | CSSB |
CSSB = Cedar Shake and Shingle Bureau |
Fasteners for wood shingles shall be corrosion resistant with a minimum penetration of 3/4 inch (19.1 mm) into the sheathing. For sheathing less than 1/2 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shingle shall be attached with a minimum of two fasteners.
Wood shingles shall be laid with a side lap not less than 1
1/
2 inches (38 mm) between
joints in adjacent courses, and not be in direct alignment in alternate courses. Spacing between shingles shall be
1/
4 to
3/
8 inches (6.4 to 9.5 mm). Weather exposure for wood shingles shall not exceed that set in Table 1507.8.7.
TABLE 1507.8.7
WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE
ROOFING MATERIAL | LENGTH (inches) | GRADE | EXPOSURE (inches) |
3:12 pitch to < 4:12 | 4:12 pitch or steeper |
Shingles of naturally durable wood | 16 | No. 1 | 3.75 | 5 |
No. 2 | 3.5 | 4 |
No. 3 | 3 | 3.5 |
18 | No. 1 | 4.25 | 5.5 |
No. 2 | 4 | 4.5 |
No. 3 | 3.5 | 4 |
24 | No. 1 | 5.75 | 7.5 |
No. 2 | 5.5 | 6.5 |
No. 3 | 5 | 5.5 |
For SI: 1 inch = 25.4 mm. |
At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm)
underlayment of either one layer of
Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D1970, in addition to other required
underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing
underlayment shall be solidly cemented to the roofing
underlayment for slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed.
The installation of wood shakes shall comply with the provisions of this section and
Table 1507.8.
Wood shakes shall only be used on
solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be less than 1-inch by 4-inch (25 mm by 102 mm)
nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25 mm by 102 mm) spaced sheathing is installed at 10 inches (254 mm) o.c., additional 1-inch by 4-inch (25 mm by 102 mm) boards shall be installed between the sheathing boards.
Solid sheathing is required in areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water.
Wood shakes shall only be used on slopes of four units vertical in 12 units horizontal (33-percent slope) or greater.
Underlayment shall comply with ASTM D226,
Type I or ASTM D4869.
Underlayment applied in areas subject to high winds [
Vasd greater than 110 mph (49 m/s) as determined in accordance with
Section 1609.3.1] shall be applied with corrosion-resistant fasteners in accordance with the manufacturer’s installation instructions. Fasteners are to be applied along the overlap not farther apart than 36 inches (914 mm) on center.
Underlayment installed where
Vasd, in accordance with
Section 1609.3.1, equals or exceeds 120 mph (54 m/s) shall comply with ASTM D226
Type II or ASTM D4869
Type IV. The
underlayment shall be attached in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at the side laps.
Underlayment shall be applied in accordance with the manufacturer’s installation instructions except all laps shall be a minimum of 4 inches (102 mm).
Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25 mm) with a thickness of at least 32-gauge [0.0134 inch (0.34 mm)] sheet metal. The cap nail shank shall be a minimum of 12 gauge [0.105 inch (2.67 mm)] with a length to penetrate through the roof sheathing or a minimum of
3/
4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered
underlayment complying with ASTM D1970 shall be permitted.
In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of
underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal
underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the
exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
Interlayment shall comply with ASTM D226,
Type I.
Wood shakes shall comply with the requirements of Table 1507.9.6.
TABLE 1507.9.6
WOOD SHAKE MATERIAL REQUIREMENTS
CSSB = Cedar Shake and Shingle Bureau. |
TFS = Forest Products Laboratory of the Texas Forest Services. |
Fasteners for wood shakes shall be corrosion resistant with a minimum penetration of 3/4 inch (19.1 mm) into the sheathing. For sheathing less than 1/2 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shake shall be attached with a minimum of two fasteners.
Wood shakes shall be laid with a side lap not less than 1
1/
2 inches (38 mm) between
joints in adjacent courses. Spacing between shakes in the same course shall be
3/
8 to
5/
8 inches (9.5 to 15.9 mm) for shakes and taper sawn shakes of
naturally durable wood and shall be
1/
4 to
3/
8 inch (6.4 to 9.5 mm) for preservative taper sawn shakes. Weather exposure for wood shakes shall not exceed those set in Table 1507.9.8.
At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm)
underlayment of either one layer of
Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D1970, in addition to other required
underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing
underlayment shall be solidly cemented to the roofing
underlayment for slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed.
The installation of built-up roofs shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2, built-up roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage, except for coal-tar built-up roofs that shall have a design slope of a minimum one-eighth unit vertical in 12 units horizontal (1-percent slope).
Built-up roof covering materials shall comply with the standards in Table 1507.10.2.or UL 55A.
TABLE 1507.10.2
BUILT-UP ROOFING MATERIAL STANDARDS
MATERIAL STANDARD | STANDARD |
Acrylic coatings used in roofing | ASTM D6083 |
Aggregate surfacing | ASTM D1863 |
Asphalt adhesive used in roofing | ASTM D3747 |
Asphalt cements used in roofing | ASTM D3019; D2822; D4586 |
Asphalt-coated glass fiber base sheet | ASTM D4601 |
Asphalt coatings used in roofing | ASTM D1227; D2823; D2824; D4479 |
Asphalt glass felt | ASTM D2178 |
Asphalt primer used in roofing | ASTM D41 |
Asphalt-saturated and asphalt-coated organic felt base sheet | ASTM D2626 |
Asphalt-saturated organic felt (perforated) | ASTM D226 |
Asphalt used in roofing | ASTM D312 |
Coal-tar cements used in roofing | ASTM D4022; D5643 |
Coal-tar saturated organic felt | ASTM D227 |
Coal-tar pitch used in roofing | ASTM D450; Type I or II |
Coal-tar primer used in roofing, dampproofing and waterproofing | ASTM D43 |
Glass mat, coal tar | ASTM D4990 |
Glass mat, venting type | ASTM D4897 |
Mineral-surfaced inorganic cap sheet | ASTM D3909 |
Thermoplastic fabrics used in roofing | ASTM D5665, D5726 |
The installation of modified bitumen roofing shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2, modified bitumen membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage.
Modified bitumen roof coverings shall comply with CGSB 37-GP-56M, ASTM D6162, ASTM D6163, ASTM D6164, ASTM D6222, ASTM D6223, ASTM D6298 or ASTM D6509.
The installation of thermoset single-ply roofing shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2, thermoset
single-ply membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage.
Thermoset single-ply
roof coverings shall comply with ASTM D4637, ASTMD 5019 or CGSB 37-GP-52M.
Ballasted thermoset low-slope roofs (roof slope < 2:12) shall be installed in accordance with this section and
Section 1504.4. Stone used as
ballast shall comply with ASTM D448.
The installation of thermoplastic single-ply roofing shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2, thermoplastic
single-ply membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage.
Thermoplastic single-ply
roof coverings shall comply with ASTM D4434, ASTM D6754, ASTM D6878 or CGSB CAN/CGSB 37-54.
Ballasted thermoplastic low-slope roofs (roof slope < 2:12) shall be installed in accordance with this section and
Section 1504.4. Stone used as
ballast shall comply with ASTM D448.
The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2, sprayed polyurethane foam roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage.
Spray-applied polyurethane foam insulation shall comply with
Type III or IV as defined in ASTM C1029.
Foamed-in-place roof insulation shall be installed in accordance with the manufacturer's instructions. A
liquid-applied protective coating that complies with Table 1507.14.3.shall be applied no less than 2 hours nor more than 72 hours following the application of the foam.
TABLE 1507.14.3
PROTECTIVE COATING MATERIAL STANDARDS
MATERIAL | STANDARD |
Acrylic coating | ASTM D6083 |
Silicone coating | ASTM D6694 |
Moisture-cured polyurethane coating | ASTM D6947 |
Foam plastic materials and installation shall comply with
Chapter 26.
The installation of
liquid-applied roofing shall comply with the provisions of this section.
Unless designed for water accumulation in accordance with
Section 1611.2,
liquid-applied roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope).
Liquid-applied roofing shall comply with ASTM C836, ASTM C957, ASTM D1227 or ASTM D3468, ASTM D6083, ASTM D6694 or ASTM D6947.
Roof gardens and landscaped roofs shall comply with the requirements of this chapter and Sections
1607.12.3.and
1607.12.3.1.and the
International Fire Code.
The structural frame and roof construction supporting the load imposed upon the roof by the roof gardens or landscaped roofs shall comply with the requirements of
Table 601.
The installation of
photovoltaic modules/shingles shall comply with the provisions of this section.
Photovoltaic modules/shingles shall be listed and
labeled in accordance with UL 1703.
Photovoltaic modules/shingles shall be attached in accordance with the manufacturer’s installation instructions.
Photovoltaic modules/shingles shall be tested in accordance with procedures and acceptance criteria in ASTM D3161.
Photovoltaic modules/shingles shall comply with the classification requirements of
Table 1507.2.7.1(2) for the appropriate maximum
nominal design wind speed. Photovoltaic modules/shingle packaging shall bear a
label to indicate compliance with the procedures in ASTM D3161 and the required classification from
Table 1507.2.7.1(2).
The use of above-deck thermal insulation shall be permitted provided such insulation is covered with an
approved roof covering and passes the tests of FM 4450 or UL 1256 when tested as an assembly.
Exceptions:
1. Foam plastic roof insulation shall conform to the material and installation requirements of Chapter 26.
2. Where a concrete roof deck is used and the above-deck thermal insulation is covered with an approved roof covering.
Cellulosic
fiberboard roof insulation shall conform to the material and installation requirements of
Chapter 23.
Above-deck thermal insulation board shall comply with the standards in Table 1508.2.
TABLE 1508.2
MATERIAL STANDARDS FOR ROOF INSULATION
The provisions of this section shall govern the construction of
rooftop structures.
A
penthouse or other projection above the roof in structures of other than
Type I construction shall not exceed 28 feet (8534 mm) above the roof where used as an enclosure for tanks or for elevators that run to the roof and in all other cases shall not extend more than 18 feet (5486 mm) above the roof. The aggregate area of
penthouses and other
rooftop structures shall not exceed one-third the area of the supporting roof. A
penthouse, bulkhead, or any other similar projection above the roof shall not be used for purposes other than shelter of mechanical equipment or shelter of vertical
shaft openings in the roof.
Exception: Accessory uses necessary for the maintenance of building systems shall be permitted when the
penthouse is sprinkled in accordance with
Section 903.1.1.
Provisions such as louvers, louver blades, or flashing shall be made to protect the mechanical equipment and the building interior from the elements. Penthouses or bulkheads used for purposes other than permitted by this section shall conform to the requirements of this code for an additional story. The restrictions of this section shall not prohibit the placing of wood flagpoles or similar structures on the roof of any building.
Penthouses constructed on buildings of other than
Type I construction shall not exceed 18 feet (5486 mm) in height above the
roof deck as measured to the average height of the roof of the
penthouse.
Exceptions:
1. Where used to enclose tanks or elevators that travel to the roof level, penthouses shall be permitted to have a maximum height of 28 feet (8534 mm) above the roof deck.
2. Penthouses located on the roof of buildings of Type I construction shall not be limited in height.
The aggregate area of
penthouses and other enclosed
rooftop structures shall not exceed one-third the area of the supporting
roof deck. Such
penthouses and other enclosed
rooftop structures shall not be required to be included in determining the
building area or number of
stories as regulated by
Section 503.1. The area of such
penthouses shall not be included in determining the
fire area specified in
Section 901.7.
Penthouses shall not be used for purposes other than shelter of mechanical or electrical equipment, tanks, or vertical
shaft openings in the
roof assembly.
Exception: Accessory uses necessary for the maintenance of building systems shall be permitted when the
penthouse is sprinkled in accordance with
Section 903.1.1.
Provisions such as louvers, louver blades or flashing shall be made to protect the mechanical and electrical equipment and the building interior from the elements.
Penthouses shall be constructed with
walls, floors and roofs as required for the type of construction of the building on which such
penthouses are built.
Exceptions:
1. On buildings of Type I construction, the exterior walls and roofs of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating. The exterior walls and roofs of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall not be required to have a fire-resistance rating.
2. On buildings of Type I construction two stories or less in height above grade plane or of Type II construction, the exterior walls and roofs of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating or a lesser fire-resistance rating as required by Table 602.and be constructed of fire-retardant-treated wood. The exterior walls and roofs of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall be permitted to be constructed of fire-retardant-treated wood and shall not be required to have a fire-resistance rating. Interior framing and walls shall be permitted to be constructed of fire-retardant-treated wood.
3. On buildings of Type III, IV or V construction, the exterior walls of penthouses with a fire separation distance greater than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be permitted to have not less than a 1-hour fire-resistance rating or a lesser fire-resistance rating as required by Table 602. On buildings of Type III, IV or VA construction, the exterior walls of penthouses with a fire separation distance of 20 feet (6096 mm) or greater shall be permitted to be of Type IV or noncombustible construction or fire-retardant-treated wood and shall not be required to have a fire-resistance rating.
Tanks having a capacity of more than 500 gallons (2 m
3) located on the
roof deck of a building shall be supported on
masonry, reinforced
concrete, steel or
Type IV construction provided that, where such supports are located in the building above the lowest
story, the support shall be fire-resistance rated as required for Type IA construction.
In the bottom or on the side near the bottom of the tank, a pipe or outlet, fitted with a suitable quick-opening valve for discharging the contents into a drain in an emergency shall be provided.
Tanks shall not be placed over or near a
stairway or an elevator
shaft, unless there is a
solid roof or floor underneath the tank.
Unenclosed roof tanks shall have covers sloping toward the perimeter of the tanks.
Cooling towers located on the
roof deck of a building and greater than 250 square feet (23.2 m
2) in base area or greater than 15 feet (4572 mm) in height above the
roof deck, as measured to the highest point on the cooling tower, where the roof is greater than 50 feet (15 240 mm) in height above
grade plane shall be constructed of noncombustible materials. The base area of cooling towers shall not exceed one-third the area of the supporting
roof deck.
Exception: Drip boards and the enclosing construction shall be permitted to be of wood not less than 1 inch (25 mm)
nominal thickness, provided the wood is covered on the exterior of the tower with noncombustible material.
Towers, spires, domes and cupolas shall be of a type of construction having
fire-resistance ratings not less than required for the building on top of which such tower, spire, dome or cupola is built. Towers, spires, domes and cupolas greater than 85 feet (25 908 mm) in height above
grade plane as measured to the highest point on such structures, and either greater than 200 square feet (18.6 m
2) in horizontal area or used for any purpose other than a belfry or an architectural embellishment, shall be constructed of and supported on
Type I or II construction.
Towers, spires, domes and cupolas greater than 60 feet (18 288 mm) in height above the highest point at which such structure contacts the roof as measured to the highest point on such structure, or that exceeds 200 square feet (18.6 m
2) in area at any horizontal section, or which is intended to be used for any purpose other than a belfry or architectural embellishment, or is located on the top of a building greater than 50 feet (1524 mm) in
building height shall be constructed of and supported by noncombustible materials and shall be separated from the building below by construction having a
fire-resistance rating of not less than 1.5 hours with openings protected in accordance with
Section 712. Such structures located on the top of a building greater than 50 feet (15 240 mm) in
building height shall be supported by noncombustible construction.
Enclosed towers and spires shall have
exterior walls constructed as required for the building on top of which such towers and spires are built. The
roof covering of spires shall not be less than the same class of
roof covering required for the building on top of which the spire is located.
Mechanical equipment screens shall be constructed of the materials specified for the
exterior walls in accordance with the type of construction of the building. Where the
fire separation distance is greater than 5 feet (1524 mm),
mechanical equipment screens shall not be required to comply with the
fire-resistance rating requirements.
Mechanical equipment screens shall not exceed 18 feet (5486 mm) in height above the
roof deck, as measured to the highest point on the
mechanical equipment screen.
Regardless of the requirements in
Section 1509.6,
mechanical equipment screens shall be permitted to be constructed of combustible materials where located on the
roof decks of building of
Type I, II, III or IV construction in accordance with any one of the following limitations:
1. The fire separation distance shall not be less than 20 feet (6096 mm) and the height of the mechanical equipment screen above the roof deck shall not exceed 4 feet (1219 mm) as measured to the highest point on the mechanical equipment screen.
2. The fire separation distance shall not be less than 20 feet (6096 mm) and the mechanical equipment screen shall be constructed of fire-retardant-treated wood complying with Section 2303.2.for exterior installation.
3. Where exterior wall covering panels are used, the panels shall have a flame spread index of 25 or less when tested in the minimum and maximum thicknesses intended for use with each face tested independently in accordance with ASTM E84 or UL 723. The panels shall be tested in the minimum and maximum thicknesses intended for use in accordance with, and shall comply with the acceptance criteria of, NFPA 285 and shall be installed as tested. Where the panels are tested as part of an exterior wall assembly in accordance with NFPA 285, the panels shall be installed on the face of the mechanical equipment screen supporting structure in the same manner as they were installed on the tested exterior wall assembly.
The height of
mechanical equipment screens located on the
roof decks of buildings of
Type V construction, as measured from
grade plane to the highest point on the
mechanical equipment screen, shall be permitted to exceed the maximum
building height allowed for the building by other provisions of this code where complying with any one of the following limitations, provided the
fire separation distance is greater than 5 feet (1524 mm):
1. Where the fire separation distance is not less than 20 feet (6096 mm), the height above grade plane of the mechanical equipment screen shall not exceed 4 feet (1219 mm) more than the maximum building height allowed;
2. The mechanical equipment screen shall be constructed of noncombustible materials;
3. The mechanical equipment screen shall be constructed of fire-retardant-treated wood complying with Section 2303.2.for exterior installation; or
4. Where the fire separation distance is not less than 20 feet (6096 mm), the mechanical equipment screen shall be constructed of materials having a flame spread index of 25 or less when tested in the minimum and maximum thicknesses intended for use with each face tested independently in accordance with ASTM E84 or UL 723.
Rooftop mounted photovoltaic systems shall be designed in accordance with this section.
Rooftop mounted photovoltaic systems shall be designed for wind
loads for component and cladding in accordance with
Chapter 16.using an effective wind area based on the
dimensions of a single unit frame.
Rooftop mounted photovoltaic systems shall have the same fire classification as the
roof assembly required by
Section 1505.
Rooftop mounted photovoltaic systems shall be installed in accordance with the manufacturer’s installation instructions.
Photovoltaic
panels and modules mounted on top of a roof shall be listed and
labeled in accordance with UL 1703 and shall be installed in accordance with the manufacturer’s installation instructions.
Rooftop structures not regulated by Sections
1509.2.through
1509.7.shall comply with Sections
1509.8.1.through
1509.8.5.as applicable.
Aerial supports shall be constructed of noncombustible materials.
Exception: Aerial supports not greater than 12 feet (3658 mm) in height as measured from the
roof deck to the highest point on the aerial supports shall be permitted to be constructed of combustible materials.
Bulkheads used for the shelter of mechanical or electrical equipment or vertical
shaft openings in the
roof assembly shall comply with
Section 1509.2.as
penthouses. Bulkheads used for any other purpose shall be considered as an additional
story of the building.
Dormers shall be of the same type of construction as required for the roof in which such dormers are located or the
exterior walls of the building.
Fences and similar structures shall comply with
Section 1509.6.as
mechanical equipment screens.
Flagpoles and similar structures shall not be required to be constructed of noncombustible materials and shall not be limited in height or number.
Materials and methods of application used for recovering or replacing an existing
roof covering shall comply with the requirements of
Chapter 15.
Exception: Reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2-percent slope) in
Section 1507.for roofs that provide
positive roof drainage.
Structural roof components shall be capable of supporting the roof-covering system and the material and equipment
loads that will be encountered during installation of the system.
New
roof coverings shall not be installed without first removing all existing layers of
roof coverings down to the
roof deck where any of the following conditions occur:
1. Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing.
2. Where the existing roof covering is wood shake, slate, clay, cement or asbestos-cement tile.
3. Where the existing roof has two or more applications of any type of roof covering.
Exceptions:
1. Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building’s structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings.
2. Metal panel, metal shingle and concrete and clay tile roof coverings shall be permitted to be installed over existing wood shake roofs when applied in accordance with Section 1510.4.
3. The application of a new protective coating over an existing spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings.
4. Where the existing roof assembly includes an ice barrier membrane that is adhered to the roof deck, the existing ice barrier membrane shall be permitted to remain in place and covered with an additional layer of ice barrier membrane in accordance with Section 1507.
Where the application of a new
roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with
gypsum board,
mineral fiber, glass fiber or other
approved materials securely fastened in place.
Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars and metal counterflashings shall not be reinstalled where rusted, damaged or deteriorated. Aggregate surfacing materials shall not be reinstalled unless such aggregate complies with the gradation requirements of ASTM C33 Standard Specification for
Concrete Aggregate.
Flashings shall be reconstructed in accordance with approved manufacturer’s installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation.
Solar photovoltaic
panels/modules installed upon a roof or as an integral part of a
roof assembly shall comply with the requirements of this code.
The structural frame and roof construction supporting the load imposed upon the roof by the photovoltaic
panels/modules shall comply with the requirements of
Table 601.