ADOPTS WITH AMENDMENTS:

International Fuel Gas Code 2018 (IFGC 2018)

Heads up: There are no amended sections in this chapter.

User note:

About this chapter: Chapter 4 addresses all aspects of fuel gas piping including the allowed materials, design and sizing, piping support, pressure requirements, controls, connections to appliances, installation requirements, purging and testing. Also addressed are motor vehicle fuel dispensing systems. The overarching intent is to prevent gas leakage, overpressures and underpressures and prevent accidents.

This chapter shall govern the design, installation, modification and maintenance of piping systems. The applicability of this code to piping systems extends from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems.
Utility service piping located within buildings shall be installed in accordance with the structural safety and fire protection provisions of the International Building Code.
The storage system for liquefied petroleum gas shall be designed and installed in accordance with the International Fire Code and NFPA 58.
In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter.
Where an additional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be provided.
For other than steel pipe, exposed piping shall be identified by a yellow label marked "Gas" in black letters. The marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served.
Where two or more meters are installed on the same premises but supply separate consumers, the piping systems shall not be interconnected on the outlet side of the meters.
Piping from multiple meter installations shall be marked with an approved permanent identification by the installer so that the piping system supplied by each meter is readily identifiable.
Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402.

Each length of pipe and tubing and each pipe fitting, utilized in a fuel gas system, shall bear the identification of the manufacturer.

Exceptions:

  1. Steel pipe sections that are 2 feet (610 mm) and less in length and are cut from longer sections of pipe.
  2. Steel pipe fittings 2 inches and less in size.
  3. Where identification is provided on the product packaging or crating.
  4. Where other approved documentation is provided.

Piping, tubing and fittings shall be manufactured to the applicable referenced standards, specifications and performance criteria listed in Section 403 and shall be identified in accordance with Section 401.9.

Piping systems shall be of such size and so installed as to provide a supply of gas sufficient to meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance.

The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the appliances served.

The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to be based on such loads.

The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation.

Gas piping shall be sized in accordance with one of the following:

  1. Pipe sizing tables or sizing equations in accordance with Section 402.4 or 402.5 as applicable.
  2. The sizing tables included in a listed piping system's manufacturer's installation instructions.
  3. Other approved engineering methods.

This section applies to piping materials other than noncorrugated stainless steel tubing. Where Tables 402.4(1) through 402.4(37) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3.

Where Equations 4-1 and 4-2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3.

  1. Low-pressure gas equation [Less than 11/2 pounds per square inch (psi) (10.3 kPa)]:

    (Equation 4-1)

  2. High-pressure gas equation [11/2 psi (10.3 kPa) and above]:

    (Equation 4-2)

    where:

    D = Inside diameter of pipe, inches (mm).

    Q = Input rate appliance(s), cubic feet per hour at 60°F (16°C) and 30-inch mercury column.

    P1 = Upstream pressure, psia (P1 + 14.7).

    P2 = Downstream pressure, psia (P2 + 14.7).

    L = Equivalent length of pipe, feet.

    ΔH = Pressure drop, inch water column (27.7-inch water column = 1 psi).

TABLE 402.4

Cr AND Y VALUES FOR NATURAL GAS AND UNDILUTED PROPANE AT STANDARD CONDITIONS

GASEQUATION FACTORS
CrY
Natural gas0.60940.9992
Undiluted propane1.24620.9910

For SI: 1 cubic foot = 0.028 m3, 1 foot = 305 mm, 1-inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W.

TABLE 402.4(1)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.3 in. w.c.
Specific Gravity0.60
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/2345681012
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.0265.0476.0657.98110.02011.938
Length (ft)Capacity in Cubic Feet of Gas Per Hour
101312735141,0601,5803,0504,8608,58017,50031,70051,300105,000191,000303,000
20901883537261,0902,0903,3405,90012,00021,80035,30072,400132,000208,000
30721512845838731,6802,6804,7409,66017,50028,30058,200106,000167,000
40621292434997471,4402,2904,0508,27015,00024,20049,80090,400143,000
50551142154426621,2802,0303,5907,33013,30021,50044,10080,100127,000
60501041954006001,1601,8403,2606,64012,00019,50040,00072,600115,000
7046951793685521,0601,6903,0006,11011,10017,90036,80066,800106,000
8042891673435149891,5802,7905,68010,30016,70034,20062,10098,400
9040831573224829281,4802,6105,3309,65015,60032,10058,30092,300
10038791483044558771,4002,4705,0409,11014,80030,30055,10087,200
12533701312694037771,2402,1904,4608,08013,10026,90048,80077,300
15030631192443667041,1201,9804,0507,32011,90024,30044,20070,000
17528581092243366481,0301,8203,7206,73010,90022,40040,70064,400
20026541022093136029601,7003,4606,26010,10020,80037,90059,900
2502348901852775348511,5003,0705,5508,99018,50033,50053,100
3002143821682514847711,3602,7805,0308,15016,70030,40048,100
3501940751542314457091,2502,5604,6307,49015,40028,00044,300
4001837701432154146601,1702,3804,3106,97014,30026,00041,200
4501735661352023896191,0902,2304,0406,54013,40024,40038,600
5001633621271913675851,0302,1103,8206,18012,70023,10036,500
5501531591211813495569822,0003,6205,87012,10021,90034,700
6001430561151733335309371,9103,4605,60011,50020,90033,100
6501429541101653185088971,8303,3105,36011,00020,00031,700
7001327521061593064888621,7603,1805,15010,60019,20030,400
7501326501021532954708301,6903,0604,96010,20018,50029,300
800122648991482854548021,6402,9604,7909,84017,90028,300
850122546951432754397761,5802,8604,6409,53017,30027,400
900112445931392674267521,5302,7804,5009,24016,80026,600
950112344901352594137311,4902,7004,3708,97016,30025,800
1,000112343871312524027111,4502,6204,2508,72015,80025,100
1,100102140831242403826751,3802,4904,0308,29015,10023,800
1,200NA2039791192293646441,3102,3803,8507,91014,40022,700
1,300NA2037761142193496171,2602,2803,6807,57013,70021,800
1,400NA1935731092103355921,2102,1903,5407,27013,20020,900
1,500NA1834701052033235711,1602,1103,4107,01012,70020,100
1,600NA1833681021963125511,1202,0303,2906,77012,30019,500
1,700NA173266981893025331,0901,9703,1906,55011,90018,800
1,800NA163164951842935171,0501,9103,0906,35011,50018,300
1,900NA163062931782845021,0201,8503,0006,17011,20017,700
2,000NA162960901732764881,0001,8002,9206,00010,90017,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. NA means a flow of less than 10 cfh.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(2)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.5 in. w.c.
Specific Gravity0.60
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/2345681012
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.0265.0476.0657.98110.02011.938
Length (ft)Capacity in Cubic Feet of Gas Per Hour
101723606781,3902,0904,0206,40011,30023,10041,80067,600139,000252,000399,000
201182474669571,4302,7604,4007,78015,90028,70046,50095,500173,000275,000
30951993747681,1502,2203,5306,25012,70023,00037,30076,700139,000220,000
40811703206579851,9003,0205,35010,90019,70031,90065,600119,000189,000
50721512845838731,6802,6804,7409,66017,50028,30058,200106,000167,000
60651372575287911,5202,4304,2908,76015,80025,60052,70095,700152,000
70601262374867281,4002,2303,9508,05014,60023,60048,50088,100139,000
80561172204526771,3002,0803,6707,49013,60022,00045,10081,900130,000
90521102074246351,2201,9503,4507,03012,70020,60042,30076,900122,000
100501041954006001,1601,8403,2606,64012,00019,50040,00072,600115,000
12544921733555321,0201,6302,8905,89010,60017,20035,40064,300102,000
15040831573224829281,4802,6105,3309,65015,60032,10058,30092,300
17537771442964438541,3602,4104,9108,88014,40029,50053,60084,900
20034711342754127941,2702,2404,5608,26013,40027,50049,90079,000
25030631192443667041,1201,9804,0507,32011,90024,30044,20070,000
30027571082213316381,0201,8003,6706,63010,70022,10040,10063,400
3502553992033055879351,6503,3706,1009,88020,30036,90058,400
4002349921892835468701,5403,1405,6809,19018,90034,30054,300
4502246861772665128161,4402,9405,3308,62017,70032,20050,900
5002143821682514847711,3602,7805,0308,15016,70030,40048,100
5502041781592394597321,2902,6404,7807,74015,90028,90045,700
6001939741522284386991,2402,5204,5607,38015,20027,50043,600
6501838711452184206691,1802,4104,3607,07014,50026,40041,800
7001736681402094036431,1402,3204,1906,79014,00025,30040,100
7501735661352023896191,0902,2304,0406,54013,40024,40038,600
8001634631301953755981,0602,1603,9006,32013,00023,60037,300
8501633611261893635791,0202,0903,7806,11012,60022,80036,100
9001532591221833525619922,0203,6605,93012,20022,10035,000
9501531581181783425459631,9603,5505,76011,80021,50034,000
1,0001430561151733335309371,9103,4605,60011,50020,90033,100
1,1001428531091643165038901,8103,2805,32010,90019,80031,400
1,2001327511041563014808491,7303,1305,07010,40018,90030,000
1,3001226491001502894608131,6603,0004,8609,98018,10028,700
1,400122547961442774427811,5902,8804,6709,59017,40027,600
1,500112445931392674267521,5302,7804,5009,24016,80026,600
1,600112344891342584117271,4802,6804,3408,92016,20025,600
1,700112242861302503987031,4302,5904,2008,63015,70024,800
1,800102241841262423866821,3902,5204,0708,37015,20024,100
1,900102140811222353756621,3502,4403,9608,13014,80023,400
2,000NA2039791192293646441,3102,3803,8507,91014,40022,700

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. NA means a flow of less than 10 cfh.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(3)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop3.0 in. w.c.
Specific Gravity0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0-INCH W.C. OR GREATER
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Cubic Feet of Gas Per Hour
104549491,7903,6705,50010,60016,90029,80060,800
203126521,2302,5203,7807,28011,60020,50041,800
302505249862,0303,0305,8409,31016,50033,600
402144488441,7302,6005,0007,97014,10028,700
501903977481,5402,3004,4307,07012,50025,500
601723606781,3902,0904,0206,40011,30023,100
701583316241,2801,9203,7005,89010,40021,200
801473085801,1901,7903,4405,4809,69019,800
901382895441,1201,6803,2305,1409,09018,500
1001312735141,0601,5803,0504,8608,58017,500
1251162424569361,4002,7004,3007,61015,500
1501052194138481,2702,4503,9006,89014,100
175962023807801,1702,2503,5906,34012,900
200901883537261,0902,0903,3405,90012,000
250801663136439641,8602,9605,23010,700
300721512845838731,6802,6804,7409,700
350661392615368031,5502,4704,3608,900
400621292434997471,4402,2904,0608,300
450581212284687011,3502,1503,8007,800
500551142154426621,2802,0303,5907,300
550521092044206291,2101,9303,4107,000
600501041954006001,1601,8403,2606,640
65047991873845751,1101,7603,1206,360
70046951793685521,0601,7003,0006,110
75044921733555321,0201,6302,8905,890
80042891673435149891,5802,7905,680
85041861623324979571,5302,7005,500
90040831573224829281,4802,6205,330
95039811523124689011,4402,5405,180
1,00038791483044558771,4002,4705,040
1,10036751412894328331,3302,3504,780
1,20034711342754127941,2702,2404,560
1,30033681282643957611,2102,1404,370
1,40031651232533797311,1702,0604,200
1,50030631192443667041,1201,9804,050
1,60029611152363536801,0801,9203,910
1,70028591112283426581,0501,8503,780
1,80027571082213316381,0201,8003,670
1,90027561052153226199871,7503,560
2,00026541022093136029601,7003,460

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(4)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop6.0 in. w.c.
Specific Gravity0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0-INCH W.C. OR GREATER
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Cubic Feet of Gas Per Hour
106601,3802,6005,3408,00015,40024,60043,40088,500
204549491,7903,6705,50010,60016,90029,90060,800
303647621,4402,9504,4208,50013,60024,00048,900
403126521,2302,5203,7807,28011,60020,50041,800
502765781,0902,2403,3506,45010,30018,20037,100
602505249862,0303,0305,8409,31016,50033,600
702304829071,8602,7905,3808,57015,10030,900
802144488441,7302,6005,0007,97014,10028,700
902014207921,6302,4404,6907,48013,20027,000
1001903977481,5402,3004,4307,07012,50025,500
1251683526631,3602,0403,9306,26011,10022,600
1501533196011,2301,8503,5605,67010,00020,500
1751402935531,1401,7003,2805,2209,23018,800
2001312735141,0601,5803,0504,8608,58017,500
2501162424569361,4002,7004,3007,61015,500
3001052194138481,2702,4503,9006,89014,100
350962023807801,1702,2503,5906,34012,900
400901883537261,0902,0903,3405,90012,000
450841763326811,0201,9703,1305,54011,300
500801663136439641,8602,9605,23010,700
550761582976119151,7602,8104,97010,100
600721512845838731,6802,6804,7409,660
650691442725588361,6102,5704,5409,250
700661392615368031,5502,4704,3608,890
750641342525167741,4902,3804,2008,560
800621292434997471,4402,2904,0608,270
850601252354837231,3902,2203,9208,000
900581212284687011,3502,1503,8007,760
950561182214546811,3102,0903,7007,540
1,000551142154426621,2802,0303,5907,330
1,100521092044206291,2101,9303,4106,960
1,200501041954006001,1601,8403,2606,640
1,30047991873845751,1001,7603,1206,360
1,40046951793685521,0601,7003,0006,110
1,50044921733555321,0201,6302,8905,890
1,60042891673435149891,5802,7905,680
1,70041861623324979571,5302,7005,500
1,80040831573224829281,4802,6205,330
1,90039811523124689011,4402,5405,180
2,00038791483044558771,4002,4705,040

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(5)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity0.60
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Cubic Feet of Gas Per Hour
101,5103,0405,56011,40017,10032,90052,50092,800189,000
201,0702,1503,9308,07012,10023,30037,10065,600134,000
308691,7603,2106,5909,88019,00030,30053,600109,000
407531,5202,7805,7108,55016,50026,30046,40094,700
506731,3602,4905,1107,65014,70023,50041,50084,700
606151,2402,2704,6606,98013,50021,40037,90077,300
705691,1502,1004,3206,47012,50019,90035,10071,600
805321,0801,9704,0406,05011,70018,60032,80067,000
905021,0101,8503,8105,70011,00017,50030,90063,100
1004629341,7103,5105,26010,10016,10028,50058,200
1254148361,5303,1404,7009,06014,40025,50052,100
1503727511,3702,8204,2208,13013,00022,90046,700
1753446951,2702,6013,9107,53012,00021,20043,300
2003186421,1702,4103,6106,96011,10019,60040,000
2502795831,0402,1403,2106,1809,85017,40035,500
3002535289451,9402,9105,6008,92015,80032,200
3502324868691,7902,6705,1508,21014,50029,600
4002164528091,6602,4904,7907,64013,50027,500
4502034247591,5602,3304,5007,17012,70025,800
5001924017171,4702,2104,2506,77012,00024,400
5501823816811,4002,0904,0306,43011,40023,200
6001743636501,3302,0003,8506,13010,80022,100
6501663486221,2801,9103,6805,87010,40021,200
7001603345981,2301,8403,5405,6409,97020,300
7501543225761,1801,7703,4105,4409,61019,600
8001493115561,1401,7103,2905,2509,28018,900
8501443015381,1001,6503,1905,0808,98018,300
9001392925221,0701,6003,0904,9308,71017,800
9501352835071,0401,5603,0004,7808,46017,200
1,0001322754931,0101,5202,9204,6508,22016,800
1,1001252624689601,4402,7704,4207,81015,900
1,2001192504469171,3702,6404,2207,45015,200
1,3001142394278781,3202,5304,0407,14014,600
1,4001102304118431,2602,4303,8806,86014,000
1,5001062213968121,2202,3403,7406,60013,500
1,6001022143827841,1802,2603,6106,38013,000
1,700992073707591,1402,1903,4906,17012,600
1,800962003587361,1002,1203,3905,98012,200
1,900931953487151,0702,0603,2905,81011,900
2,000911893396951,0402,0103,2005,65011,500

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(6)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet Pressure3.0 psi
Pressure Drop2.0 psi
Specific Gravity0.60
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Cubic Feet of Gas Per Hour
102,3504,9209,27019,00028,50054,90087,500155,000316,000
201,6203,3806,37013,10019,60037,70060,100106,000217,000
301,3002,7205,11010,50015,70030,30048,30085,400174,000
401,1102,3204,3808,99013,50025,90041,30073,100149,000
509852,0603,8807,97011,90023,00036,60064,800132,000
608921,8703,5207,22010,80020,80033,20058,700120,000
708211,7203,2306,6409,95019,20030,50054,000110,000
807641,6003,0106,1809,26017,80028,40050,200102,000
907171,5002,8205,8008,68016,70026,70047,10096,100
1006771,4202,6705,4708,20015,80025,20044,50090,800
1256001,2502,3604,8507,27014,00022,30039,50080,500
1505441,1402,1404,4006,59012,70020,20035,70072,900
1755001,0501,9704,0406,06011,70018,60032,90067,100
2004659731,8303,7605,64010,90017,30030,60062,400
2504128621,6203,3305,0009,62015,30027,10055,300
3003747811,4703,0204,5308,72013,90024,60050,100
3503447191,3502,7804,1708,02012,80022,60046,100
4003206691,2602,5903,8707,46011,90021,00042,900
4503006271,1802,4303,6407,00011,20019,70040,200
5002835931,1202,2903,4306,61010,50018,60038,000
5502695631,0602,1803,2606,28010,00017,70036,100
6002575371,0102,0803,1105,9909,55016,90034,400
6502465149691,9902,9805,7409,15016,20033,000
7002364949311,9102,8605,5108,79015,50031,700
7502284768971,8402,7605,3108,47015,00030,500
8002204608661,7802,6605,1308,18014,50029,500
8502134458381,7202,5804,9607,91014,00028,500
9002064318121,6702,5004,8107,67013,60027,700
9502004197891,6202,4304,6707,45013,20026,900
1,0001954077671,5802,3604,5507,24012,80026,100
1,1001853877291,5002,2404,3206,89012,20024,800
1,2001773696951,4302,1404,1206,57011,60023,700
1,3001693536661,3702,0503,9406,29011,10022,700
1,4001623406401,3101,9703,7906,04010,70021,800
1,5001563276161,2701,9003,6505,82010,30021,000
1,6001513165951,2201,8303,5305,62010,00020,300
1,7001463065761,1801,7703,4105,4409,61019,600
1,8001422965581,1501,7203,3105,2709,32019,000
1,9001382885421,1101,6703,2105,1209,05018,400
2,0001342805271,0801,6203,1204,9808,80018,000

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(7)

SCHEDULE 40 METALLIC PIPE

GasNatural
Inlet Pressure5.0 psi
Pressure Drop3.5 psi
Specific Gravity0.60
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Cubic Feet of Gas Per Hour
103,1906,43011,80024,20036,20069,700111,000196,000401,000
202,2504,5508,32017,10025,60049,30078,600139,000283,000
301,8403,7206,79014,00020,90040,30064,200113,000231,000
401,5903,2205,88012,10018,10034,90055,60098,200200,000
501,4302,8805,26010,80016,20031,20049,70087,900179,000
601,3002,6304,8009,86014,80028,50045,40080,200164,000
701,2002,4304,4509,13013,70026,40042,00074,300151,000
801,1502,3304,2608,54012,80024,70039,30069,500142,000
901,0602,1503,9208,05012,10023,20037,00065,500134,000
1009791,9803,6207,43011,10021,40034,20060,400123,000
1258761,7703,2406,6409,95019,20030,60054,000110,000
1507861,5902,9105,9608,94017,20027,40048,50098,900
1757281,4702,6905,5208,27015,90025,40044,90091,600
2006731,3602,4905,1007,65014,70023,50041,50084,700
2505581,1702,2004,5106,76013,00020,80036,70074,900
3005061,0601,9904,0906,13011,80018,80033,30067,800
3504659731,8303,7605,64010,90017,30030,60062,400
4004339051,7103,5005,25010,10016,10028,50058,100
4504068491,6003,2904,9209,48015,10026,70054,500
5003848021,5103,1004,6508,95014,30025,20051,500
5503647621,4402,9504,4208,50013,60024,00048,900
6003487271,3702,8104,2108,11012,90022,90046,600
6503336961,3102,6904,0307,77012,40021,90044,600
7003206691,2602,5903,8807,46011,90021,00042,900
7503086441,2102,4903,7307,19011,50020,30041,300
8002986221,1702,4103,6106,94011,10019,60039,900
8502886021,1302,3303,4906,72010,70018,90038,600
9002795841,1002,2603,3806,52010,40018,40037,400
9502715671,0702,1903,2906,33010,10017,80036,400
1,0002645511,0402,1303,2006,1509,81017,30035,400
1,1002505249872,0303,0305,8409,32016,50033,600
1,2002395009411,9302,9005,5808,89015,70032,000
1,3002294789011,8502,7705,3408,51015,00030,700
1,4002204608661,7802,6605,1308,18014,50029,500
1,5002124438341,7102,5704,9407,88013,90028,400
1,6002054288061,6502,4804,7707,61013,40027,400
1,7001984147801,6002,4004,6207,36013,00026,500
1,8001924017561,5502,3304,4807,14012,60025,700
1,9001863907341,5102,2604,3506,93012,30025,000
2,0001813797141,4702,2004,2306,74011,90024,300

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(8)

SEMIRIGID COPPER TUBING

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.3 in. w.c.
Specific Gravity0.60
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
102042851482104488061,2702,650
201429581021443085548731,820
30112347821162474457011,460
4010204070992113816001,250
50NA173562881873375321,110
60NA163256791703064821,000
70NA14295273156281443924
80NA13274868145262413859
90NA13264564136245387806
100NA12244360129232366761
125NA11223853114206324675
150NA10203448103186294612
175NANA18314595171270563
200NANA17294189159251523
250NANA15263778141223464
300NANA13233371128202420
350NANA12223165118186387
400NANA11202861110173360
450NANA11192757103162338
500NANA1018255497153319
550NANANA17245192145303
600NANANA16234988139289
650NANANA15224784133277
700NANANA15214581128266
750NANANA14204378123256
800NANANA14204275119247
850NANANA13194073115239
900NANANA13183971111232
950NANANA13183869108225
1,000NANANA12173767105219
1,100NANANA12163563100208
1,200NANANA1116346095199
1,300NANANA1115325891190
1,400NANANA1014315688183
1,500NANANANA14305484176
1,600NANANANA13295282170
1,700NANANANA13285079164
1,800NANANANA13274977159
1,900NANANANA12264774155
2,000NANANANA12254672151

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. NA means a flow of less than 10 cfh.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(9)

SEMIRIGID COPPER TUBING

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.5 in. w.c.
Specific Gravity0.60
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
1027551111952765901,0601,6803,490
201838771341904067301,1502,400
301530611071523265869251,930
40132653921312795027911,650
50112347821162474457011,460
60102142741052244036351,320
70NA193968962063715851,220
80NA183663901923455441,130
90NA173459841803245101,060
100NA163256791703064821,000
125NA14285070151271427890
150NA13264564136245387806
175NA12244159125226356742
200NA11223955117210331690
250NANA203448103186294612
300NANA18314494169266554
350NANA16284086155245510
400NANA15263880144228474
450NANA14253575135214445
500NANA13233371128202420
550NANA13223268122192399
600NANA12213064116183381
650NANA12202962111175365
700NANA11202859107168350
750NANA11192757103162338
800NANA1018265599156326
850NANA1018255396151315
900NANANA17245293147306
950NANANA17245090143297
1,000NANANA16234988139289
1,100NANANA15224684132274
1,200NANANA15214480126262
1,300NANANA14204276120251
1,400NANANA13194173116241
1,500NANANA13183971111232
1,600NANANA13183868108224
1,700NANANA12173766104217
1,800NANANA12173664101210
1,900NANANA1116356298204
2,000NANANA1116346095199

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. NA means a flow of less than 10 cfh.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(10)

SEMIRIGID COPPER TUBING

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop1.0 in. w.c.
Specific Gravity0.60
INTENDED USE: SIZING BETWEEN HOUSE LINE REGULATOR AND THE APPLIANCE
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
1039801622834028591,5502,4405,080
2027551111952765901,0601,6803,490
302144891562224748531,3502,800
401838771341904067301,1502,400
501633681191683596471,0202,130
601530611071523265869251,930
70132857991403005398511,770
80132653921312795027911,650
90122449861222624717421,550
100112347821162474457011,460
125NA2041721032193946221,290
150NA183765931983575631,170
175NA173460851833295181,080
200NA163256791703064821,000
250NA14285070151271427890
300NA13264564136245387806
350NA12244159125226356742
400NA11223955117210331690
450NA10213651110197311647
500NANA203448103186294612
550NANA19324698177279581
600NANA18314494169266554
650NANA17304290162255531
700NANA16284086155245510
750NANA16273983150236491
800NANA15263880144228474
850NANA15263678140220459
900NANA14253575135214445
950NANA14243473132207432
1,000NANA13233371128202420
1,100NANA13223268122192399
1,200NANA12213064116183381
1,300NANA12202962111175365
1,400NANA11202859107168350
1,500NANA11192757103162338
1,600NANA1018265599156326
1,700NANA1018255396151315
1,800NANANA17245293147306
1,900NANANA17245090143297
2,000NANANA16234988139289

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. NA means a flow of less than 10 cfh.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(11)

SEMIRIGID COPPER TUBING

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop17.0 in. w.c.
Specific Gravity0.60
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
101903917961,3901,9704,2207,59012,00024,900
201302695479561,3602,9005,2208,23017,100
301052164397681,0902,3304,1906,61013,800
40901853766579321,9903,5905,65011,800
50791643335828261,7703,1805,01010,400
60721483025287491,6002,8804,5409,460
70661372784866891,4702,6504,1808,700
80621272584526411,3702,4603,8908,090
90581192434246011,2802,3103,6507,590
100551132294005681,2102,1803,4407,170
125481002033555031,0801,9403,0506,360
15044901843214569741,7502,7705,760
17540831692964208961,6102,5405,300
20038771572753908341,5002,3704,930
25033691402443467391,3302,1004,370
30030621262213136701,2101,9003,960
35028571162032886161,1101,7503,640
40026531081892685731,0301,6303,390
45024501021772525389681,5303,180
5002347961682385089141,4403,000
5502245911592264828681,3702,850
6002143871522154608291,3102,720
6502041831452064417931,2502,610
7001939801401984237621,2002,500
7501838771351914087341,1602,410
8001837741301843947091,1202,330
8501735721261783816861,0802,250
9001734701221733706651,0502,180
9501633681181683596461,0202,120
1,0001632661151633496289912,060
1,1001531631091553325979411,960
1,2001429601041483165698981,870
1,3001428571001423035458601,790
1,400132755961362915248261,720
1,500132653931312805057961,660
1,600122551891272714877681,600
1,700122449861232624727441,550
1,800112448841192544577211,500
1,900112347811152474447001,460
2,000112245791122404326811,420

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(12)

SEMIRIGID COPPER TUBING

GasNatural
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity0.60
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
102455061,0301,8002,5505,4509,82015,50032,200
201693487081,2401,7603,7506,75010,60022,200
301352795689931,4103,0105,4208,55017,800
401162394868501,2102,5804,6407,31015,200
501032124317541,0702,2804,1106,48013,500
60931923916839692,0703,7305,87012,200
70861773596288911,9003,4305,40011,300
80801643345848291,7703,1905,03010,500
90751543145487781,6602,9904,7209,820
100711462965187351,5702,8304,4509,280
125631292634596511,3902,5003,9508,220
150571172384165901,2602,2703,5807,450
175521082193835431,1602,0903,2906,850
200491002043565051,0801,9403,0606,380
25043891813154489561,7202,7105,650
30039801642864068661,5602,4605,120
35036741502633737971,4302,2604,710
40033691402453477411,3302,1004,380
45031651312303266961,2501,9704,110
50030611242173086571,1801,8703,880
55028581182062926241,1201,7703,690
60027551121962795951,0701,6903,520
65026531081882675701,0301,6203,370
70025511031812565489861,5503,240
75024491001742475289501,5003,120
8002347961682395109171,4503,010
8502246931632314938881,4002,920
9002244901582244788611,3602,830
9502143881532174648361,3202,740
1,0002042851492114528131,2802,670
1,1001940811422014297721,2202,540
1,2001838771351924097371,1602,420
1,3001836741291833927051,1102,320
1,4001735711241763766781,0702,230
1,5001634681201703636531,0302,140
1,6001633661161643506309942,070
1,7001531641121593396109622,000
1,8001530621081543295929331,940
1,9001430601051493195759061,890
2,0001429591021453105598811,830

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(13)

SEMIRIGID COPPER TUBING

GasNatural
Inlet Pressure2.0 psi
Pressure Drop1.5 psi
Specific Gravity0.60
INTENDED USEPipe sizing between point of delivery and the house line regulator.
Total load supplied by a single house line regulator not exceeding 150 cubic feet per hour.
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
103036251,2702,2203,1506,74012,10019,10039,800
202084308741,5302,1704,6308,33013,10027,400
301673457021,2301,7403,7206,69010,60022,000
401432956011,0501,4903,1805,7309,03018,800
501272625329311,3202,8205,0808,00016,700
601152374828431,2002,5604,6007,25015,100
701062184447761,1002,3504,2306,67013,900
80982034137221,0202,1903,9406,21012,900
90921903876779612,0503,6905,82012,100
100871803666409071,9403,4905,50011,500
125771593245678041,7203,0904,88010,200
150701442945147291,5602,8004,4209,200
175641332704726701,4302,5804,0608,460
200601242524406241,3302,4003,7807,870
250531102233905531,1802,1303,3506,980
30048992023535011,0701,9303,0406,320
35044911863254619841,7702,7905,820
40041851733024299161,6502,6005,410
45039801622834028591,5502,4405,080
50036751532683808111,4602,3004,800
55035721462543617711,3902,1904,560
60033681392433447351,3202,0904,350
65032651332323307041,2702,0004,160
70030631282233176761,2201,9204,000
75029601232153056521,1701,8503,850
80028581192082956291,1301,7903,720
85027571152012856091,1001,7303,600
90027551111952765901,0601,6803,490
95026531081892685731,0301,6303,390
1,00025521051842615581,0001,5803,300
1,10024491001752485309541,5003,130
1,2002347951672375059101,4302,990
1,3002245911602274848711,3702,860
1,4002143881532184658371,3202,750
1,5002042851482104488061,2702,650
1,6001940821432024327791,2302,560
1,7001939791381964197531,1902,470
1,8001838771341904067311,1502,400
1,9001837741301843947091,1202,330
2,0001736721261793836901,0902,270

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Where this table is used to size the tubing upstream of a line pressure regulator, the pipe or tubing downstream of the line pressure regulator shall be sized using a pressure drop not greater than 1 inch w.c.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(14)

SEMIRIGID COPPER TUBING

GasNatural
Inlet Pressure5.0 psi
Pressure Drop3.5 psi
Specific Gravity0.60
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Cubic Feet of Gas Per Hour
105111,0502,1403,7505,32011,40020,40032,20067,100
203517241,4702,5803,6507,80014,00022,20046,100
302825821,1802,0702,9306,27011,30017,80037,000
402414981,0101,7702,5105,3609,66015,20031,700
502144418981,5702,2304,7508,56013,50028,100
601944008131,4202,0204,3107,75012,20025,500
701783687481,3101,8603,9607,13011,20023,400
801663426961,2201,7303,6906,64010,50021,800
901563216531,1401,6203,4606,2309,82020,400
1001473036171,0801,5303,2705,8809,27019,300
1251302695479551,3602,9005,2108,22017,100
1501182434958661,2302,6204,7207,45015,500
1751092244567961,1302,4104,3506,85014,300
2001012084247411,0502,2504,0406,37013,300
250901853766579321,9903,5805,65011,800
300811673405958441,8003,2505,12010,700
350751543135477771,6602,9904,7109,810
400691432915097221,5402,7804,3809,120
450651342734786781,4502,6104,1108,560
500621272584516401,3702,4603,8808,090
550581212454296081,3002,3403,6907,680
600561152344095801,2402,2303,5207,330
650531102243925561,1902,1403,3707,020
700511062153765341,1402,0503,2406,740
750491022073625141,1001,9803,1206,490
80048982003504971,0601,9103,0106,270
85046951943394811,0301,8502,9106,070
90045921883284661,0001,7902,8205,880
95043901823194529671,7402,7405,710
1,00042871773104409401,6902,6705,560
1,10040831692954188931,6102,5305,280
1,20038791612813998521,5302,4205,040
1,30037761542693828161,4702,3204,820
1,40035731482593677841,4102,2204,630
1,50034701432493537551,3602,1404,460
1,60033681382413417291,3102,0704,310
1,70032651332333307051,2702,0004,170
1,80031631292263206841,2301,9404,040
1,90030621252193116641,2001,8903,930
2,00029601222133026461,1601,8303,820

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(15)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.5 in. w.c.
Specific Gravity0.60
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Cubic Feet of Gas Per Hour
546631151342252704715468951,0371,7902,0703,6604,140
10324482951611923303836397461,2601,4702,6002,930
15253566771321572673105246151,0301,2002,1402,400
20223158671161372312694565368881,0501,8502,080
25192752601041222062404094827939361,6601,860
3018254755961121882183744427238561,5201,700
401521414783971621883253866257421,3201,470
501319374275871441682923475596651,1801,320
601217343868801311532673185096081,0801,200
701116313663741211412482954715631,0001,110
801015293360691131322322774405279401,040
90101428325765107125219262415498887983
10091326305462101118208249393472843933
150710202342487891171205320387691762
20069182138447182148179277336600661
25058161934396374133161247301538591
3005715173236576795148226275492540

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  2. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(16)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop3.0 in. w.c.
Specific Gravity0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0-INCH W.C. OR GREATER
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Cubic Feet of Gas Per Hour
51201602773275296491,1801,3702,1402,4234,4305,0108,80010,100
10831121972313804628289581,5301,7403,2003,5606,2707,160
1567901611893133796737781,2501,4332,5402,9105,1405,850
2057781401642733295806721,0901,2492,2002,5304,4605,070
2551691251472452955185999781,1231,9602,2704,0004,540
3046631151342252704715468951,0291,7902,0703,6604,140
4039541001161962344074717788971,5501,8003,1803,590
503548891041762103634216988061,3801,6102,8503,210
60324482951611923303836397391,2601,4702,6002,930
70294176881501783063555936861,1701,3602,4202,720
80273871821411672853315556441,0901,2802,2602,540
90263667771331572683115246091,0301,2002,1402,400
100243463731261492542954985799741,1402,0302,280
150192752601041222062404094777939361,6601,860
20017234552911061782073554156868121,4401,610
2501521404682951591843193736137281,2901,440
3001319374275871441682343425596651,1801,320

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  2. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(17)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop6.0 in. w.c.
Specific Gravity0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0-INCH W.C. OR GREATER
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Cubic Feet of Gas Per Hour
51732293894617379111,6901,9503,0003,3756,2807,05012,40014,260
101201602773275296491,1801,3702,1402,4234,4305,0108,80010,100
15961302272674365329601,1101,7601,9963,6104,1007,2108,260
20831121972313804628289581,5301,7403,1203,5606,2707,160
2574991762073424147398551,3701,5642,7903,1905,6206,400
3067901611893133796737781,2501,4332,5402,9105,1405,850
4057781401642733295806721,0901,2492,2002,5304,4605,070
5051691251472452955185999781,1231,9602,2704,0004,540
6046631151342252704715468951,0291,7902,0703,6604,140
7042581061242092504355058309561,6601,9203,3903,840
8039541001161962344074717788971,5501,8003,1803,590
903751941091852213834447358481,4601,7003,0003,390
1003548891041762103634216988061,3801,6102,8503,210
150283973851451722943425736641,1301,3202,3402,630
200243463731261492542954985799741,1402,0302,280
250213057661141342262634475208701,0201,8202,040
300192752601041222062404094777939361,6601,860

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  2. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(18)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasNatural
Inlet Pressure2 psi
Pressure Drop1.0 psi
Specific Gravity0.60
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Cubic Feet of Gas Per Hour
102703535877001,1001,3702,5902,9904,5105,0379,60010,70018,60021,600
251662203744447098761,6201,8702,8903,2586,0406,78011,90013,700
301512003424056508011,4801,7002,6402,9875,5106,20010,90012,500
401291722973515676961,2701,4702,3002,6054,7605,3809,44010,900
501151542663145106241,1401,3102,0602,3434,2604,8208,4709,720
75931242182574205129221,0701,6901,9323,4703,9506,9407,940
80891202112494074968921,0301,6401,8743,3603,8206,7307,690
100791071892223664457959201,4701,6853,0003,4206,0306,880
15064871551823023646467481,2101,3892,4402,8004,9405,620
20055751351572633175576451,0501,2122,1102,4304,2904,870
25049671211412362844975769411,0901,8902,1803,8504,360
30044611101292172604535258629991,7201,9903,5203,980
4003852961111892253904537498711,4901,7303,0603,450
5003446861001702023484045527831,3301,5502,7403,090

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3/4 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.
  2. CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.
  3. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  4. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  5. Table entries have been rounded to three significant digits.

TABLE 402.4(19)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasNatural
Inlet Pressure5.0 psi
Pressure Drop3.5 psi
Specific Gravity0.60
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Cubic Feet of Gas Per Hour
105236741,0801,3002,0002,5304,9205,6608,3009,14018,10019,80034,40040,400
253224206918271,2901,6203,0803,5405,3105,91111,40012,60022,00025,600
302923826327551,1801,4802,8003,2304,8605,42010,40011,50020,10023,400
402513295496541,0301,2802,4202,7904,2304,7278,97010,00017,40020,200
502232934925869261,1502,1602,4903,7904,2518,0208,93015,60018,100
751802384034797639441,7502,0203,1103,5066,5307,32012,80014,800
801742303914637409151,6901,9603,0203,4006,3207,09012,40014,300
1001542053504156658201,5101,7402,7103,0575,6506,35011,10012,800
1501241662873395486721,2301,4202,2202,5214,6005,2009,13010,500
2001071432492944785841,0601,2201,9302,1993,9804,5107,9309,090
250951282232634305249451,0901,7301,9773,5504,0407,1108,140
300861162042403944798609951,5901,8133,2403,6906,5007,430
400741001772083434167428581,3801,5812,8003,2105,6506,440
50066891591863093736627661,0401,4222,5002,8705,0605,760

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3/4 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.
  2. CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.
  3. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  4. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  5. Table entries have been rounded to three significant digits.

TABLE 402.4(20)

POLYETHYLENE PLASTIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.3 in. w.c.
Specific Gravity0.60
PIPE SIZE (inch)
Nominal OD1/23/4111/411/2234
DesignationSDR 9SDR 11SDR 11SDR 10SDR 11SDR 11SDR 11SDR 11
Actual ID0.6600.8601.0771.3281.5541.9432.8643.682
Length (ft)Capacity in Cubic Feet of Gas per Hour
101533055519551,4402,5907,17013,900
201052103796569911,7804,9209,520
30841693045277961,4303,9507,640
40721442604516811,2203,3806,540
50641282314006041,0803,0005,800
60581162093625479832,7205,250
70531071923335039042,5004,830
8050991793104688412,3304,500
9046931682914397892,1804,220
10044881592754157452,0603,990
12539781412433686611,8303,530
15035711272213335981,6603,200
17532651172033065511,5202,940
20030601091892855121,4202,740
2502754971672534541,2602,430
3002448881522294111,1402,200
3502245811392113781,0502,020
4002142751301963529741,880
4501939701221843309141,770
5001837661151743128631,670

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(21)

POLYETHYLENE PLASTIC PIPE

GasNatural
Inlet PressureLess than 2 psi
Pressure Drop0.5 in. w.c.
Specific Gravity0.60
PIPE SIZE (inch)
Nominal OD1/23/4111/411/2234
DesignationSDR 9SDR 11SDR 11SDR 10SDR 11SDR 11SDR 11SDR 11
Actual ID0.6600.8601.0771.3281.5541.9432.8643.682
Length (ft)Capacity in Cubic Feet of Gas per Hour
102014037261,2601,9003,4109,45018,260
201382774998651,3102,3506,49012,550
301112224016951,0501,8805,21010,080
40951903435948981,6104,4608,630
50841693045277961,4303,9507,640
60761532764777211,3003,5806,930
70701402544396631,1903,3006,370
80651312364096171,1103,0705,930
90611232213835791,0402,8805,560
100581162093625479832,7205,250
125511031853214858712,4104,660
15046931682914397892,1804,220
17543861542684047262,0103,880
20040801442493766751,8703,610
25035711272213335981,6603,200
30032641152003025421,5002,900
35029591061842784991,3802,670
4002755991712584641,2802,480
4502651931602424351,2002,330
5002448881522294111,1402,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(22)

POLYETHYLENE PLASTIC PIPE

GasNatural
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity0.60
PIPE SIZE (inch)
Nominal OD1/23/4111/411/2234
DesignationSDR 9SDR 11SDR 11SDR 10SDR 11SDR 11SDR 11SDR 11
Actual ID0.6600.8601.0771.3281.5541.9432.8643.682
Length (ft)Capacity in Cubic Feet of Gas per Hour
101,8603,7206,71011,60017,60031,60087,300169,000
201,2802,5604,6107,99012,10021,70060,000116,000
301,0302,0503,7106,4209,69017,40048,20093,200
408781,7603,1705,4908,30014,90041,20079,700
507781,5602,8104,8707,35013,20036,60070,700
607051,4102,5504,4106,66012,00033,10064,000
706491,3002,3404,0606,13011,00030,50058,900
806031,2102,1803,7805,70010,20028,30054,800
905661,1302,0503,5405,3509,61026,60051,400
1005351,0701,9303,3505,0509,08025,10048,600
1254749491,7102,9704,4808,05022,30043,000
1504298601,5502,6904,0607,29020,20039,000
1753957911,4302,4703,7306,71018,60035,900
2003687361,3302,3003,4706,24017,30033,400
2503266521,1802,0403,0805,53015,30029,600
3002955911,0701,8502,7905,01013,90026,800
3502725449811,7002,5704,61012,80024,700
4002535069131,5802,3904,29011,90022,900
4502374758561,4802,2404,02011,10021,500
5002244488091,4002,1203,80010,50020,300
5502134267681,3302,0103,6109,99019,300
6002034067331,2701,9203,4409,53018,400
6501943897021,2201,8403,3009,13017,600
7001873746741,1701,7603,1708,77016,900
7501803606491,1301,7003,0508,45016,300
8001743486271,0901,6402,9508,16015,800
8501683366071,0501,5902,8507,89015,300
9001633265881,0201,5402,7707,65014,800
9501583175729901,5002,6907,43014,400
1,0001543085569631,4502,6107,23014,000
1,1001462935289151,3802,4806,87013,300
1,2001392795048731,3202,3706,55012,700
1,3001342674828361,2602,2706,27012,100
1,4001282574638031,2102,1806,03011,600
1,5001242474467731,1702,1005,81011,200
1,6001192394317471,1302,0305,61010,800
1,7001152314177231,0901,9605,43010,500
1,8001122244047011,0601,9005,26010,200
1,9001092183936801,0301,8505,1109,900
2,0001062123826621,0001,8004,9709,600

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(23)

POLYETHYLENE PLASTIC TUBING

GasNatural
Inlet PressureLess than 2.0 psi
Pressure Drop0.3 in. w.c.
Specific Gravity0.60
PLASTIC TUBING SIZE (CTS) (inch)
Nominal OD1/23/4
DesignationSDR 7SDR 11
Actual ID0.4450.927
Length (ft)Capacity in Cubic Feet of Gas per Hour
1054372
2037256
3030205
4026176
5023156
6021141
7019130
8018121
9017113
10016107
1251495
1501386
1751279
2001174
2251069
250NA65
275NA62
300NA59
350NA54
400NA51
450NA47
500NA45

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. NA means a flow of less than 10 cfh.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(24)

POLYETHYLENE PLASTIC TUBING

GasNatural
Inlet PressureLess than 2.0 psi
Pressure Drop0.5 in. w.c.
Specific Gravity0.60
PLASTIC TUBING SIZE (CTS) (inch)
Nominal OD1/23/4
DesignationSDR 7SDR 11
Actual ID0.4450.927
Length (ft)Capacity in Cubic Feet of Gas per Hour
1072490
2049337
3039271
4034232
5030205
6027186
7025171
8023159
9022149
10021141
12518125
15017113
17515104
2001497
2251391
2501286
2751182
3001178
3501072
400NA67
450NA63
500NA59

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. NA means a flow of less than 10 cfh.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(25)

SCHEDULE 40 METALLIC PIPE

GasUndiluted Propane
Inlet Pressure10.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USEPipe sizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Thousands of Btu per Hour
103,3206,95013,10026,90040,30077,600124,000219,000446,000
202,2804,7809,00018,50027,70053,30085,000150,000306,000
301,8303,8407,22014,80022,20042,80068,200121,000246,000
401,5703,2806,18012,70019,00036,60058,400103,000211,000
501,3902,9105,48011,30016,90032,50051,70091,500187,000
601,2602,6404,97010,20015,30029,40046,90082,900169,000
701,1602,4304,5709,38014,10027,10043,10076,300156,000
801,0802,2604,2508,73013,10025,20040,10070,900145,000
901,0102,1203,9908,19012,30023,60037,70066,600136,000
1009562,0003,7707,73011,60022,30035,60062,900128,000
1258481,7703,3406,85010,30019,80031,50055,700114,000
1507681,6103,0206,2109,30017,90028,60050,500103,000
1757061,4802,7805,7108,56016,50026,30046,50094,700
2006571,3702,5905,3207,96015,30024,40043,20088,100
2505821,2202,2904,7107,06013,60021,70038,30078,100
3005281,1002,0804,2706,40012,30019,60034,70070,800
3504861,0201,9103,9305,88011,30018,10031,90065,100
4004529451,7803,6505,47010,50016,80029,70060,600
4504248861,6703,4305,1409,89015,80027,90056,800
5004008371,5803,2404,8509,34014,90026,30053,700
5503807951,5003,0704,6108,87014,10025,00051,000
6003637591,4302,9304,4008,46013,50023,90048,600
6503477261,3702,8104,2108,11012,90022,80046,600
7003346981,3102,7004,0407,79012,40021,90044,800
7503216721,2702,6003,9007,50012,00021,10043,100
8003106491,2202,5103,7607,24011,50020,40041,600
8503006281,1802,4303,6407,01011,20019,80040,300
9002916091,1502,3603,5306,80010,80019,20039,100
9502835921,1102,2903,4306,60010,50018,60037,900
1,0002755751,0802,2303,3306,42010,20018,10036,900
1,1002615461,0302,1103,1706,1009,72017,20035,000
1,2002495219822,0203,0205,8209,27016,40033,400
1,3002394999401,9302,8905,5708,88015,70032,000
1,4002294809031,8502,7805,3508,53015,10030,800
1,5002214628701,7902,6805,1608,22014,50029,600
1,6002134468401,7302,5904,9807,94014,00028,600
1,7002064328131,6702,5004,8207,68013,60027,700
1,8002004197891,6202,4304,6707,45013,20026,900
1,9001944077661,5702,3604,5407,23012,80026,100
2,0001893957451,5302,2904,4107,03012,40025,400

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(26)

SCHEDULE 40 METALLIC PIPE

GasUndiluted Propane
Inlet Pressure10.0 psi
Pressure Drop3.0 psi
Specific Gravity1.50
INTENDED USEPipe sizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Thousands of Btu per Hour
105,89012,30023,20047,60071,300137,000219,000387,000789,000
204,0508,46015,90032,70049,00094,400150,000266,000543,000
303,2506,79012,80026,30039,40075,800121,000214,000436,000
402,7805,81011,00022,50033,70064,900103,000183,000373,000
502,4605,1509,71019,90029,90057,50091,600162,000330,000
602,2304,6708,79018,10027,10052,10083,000147,000299,000
702,0504,3008,09016,60024,90047,90076,400135,000275,000
801,9104,0007,53015,50023,20044,60071,100126,000256,000
901,7903,7507,06014,50021,70041,80066,700118,000240,000
1001,6903,5406,67013,70020,50039,50063,000111,000227,000
1251,5003,1405,91012,10018,20035,00055,80098,700201,000
1501,3602,8405,36011,00016,50031,70050,60089,400182,000
1751,2502,6204,93010,10015,20029,20046,50082,300167,800
2001,1602,4304,5809,41014,10027,20043,30076,500156,100
2501,0302,1604,0608,34012,50024,10038,40067,800138,400
3009351,9503,6807,56011,30021,80034,80061,500125,400
3508601,8003,3906,95010,40020,10032,00056,500115,300
4008001,6703,1506,4709,69018,70029,80052,600107,300
4507511,5702,9606,0709,09017,50027,90049,400100,700
5007091,4802,7905,7308,59016,50026,40046,60095,100
5506731,4102,6505,4508,16015,70025,00044,30090,300
6006421,3402,5305,2007,78015,00023,90042,20086,200
6506151,2902,4204,9807,45014,40022,90040,50082,500
7005911,2402,3304,7807,16013,80022,00038,90079,300
7505691,1902,2404,6006,90013,30021,20037,40076,400
8005501,1502,1704,4506,66012,80020,50036,20073,700
8505321,1102,1004,3006,45012,40019,80035,00071,400
9005161,0802,0304,1706,25012,00019,20033,90069,200
9505011,0501,9704,0506,07011,70018,60032,90067,200
1,0004871,0201,9203,9405,90011,40018,10032,00065,400
1,1004639681,8203,7405,61010,80017,20030,40062,100
1,2004429231,7403,5705,35010,30016,40029,00059,200
1,3004238841,6703,4205,1209,87015,70027,80056,700
1,4004068491,6003,2804,9209,48015,10026,70054,500
1,5003918181,5403,1604,7409,13014,60025,70052,500
1,6003787901,4903,0604,5808,82014,10024,80050,700
1,7003667651,4402,9604,4308,53013,60024,00049,000
1,8003557411,4002,8704,3008,27013,20023,30047,600
1,9003447201,3602,7804,1708,04012,80022,60046,200
2,0003357001,3202,7104,0607,82012,50022,00044,900

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(27)

SCHEDULE 40 METALLIC PIPE

GasUndiluted Propane
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USEPipe sizing between 2 psig service and line pressure regulator.
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Thousands of Btu per Hour
102,6805,59010,50021,60032,40062,40099,500176,000359,000
201,8403,8507,24014,90022,30042,90068,400121,000247,000
301,4803,0905,82011,90017,90034,50054,90097,100198,000
401,2602,6404,98010,20015,30029,50047,00083,100170,000
501,1202,3404,4109,06013,60026,10041,70073,700150,000
601,0102,1204,0008,21012,30023,70037,70066,700136,000
709341,9503,6807,55011,30021,80034,70061,400125,000
808691,8203,4207,02010,50020,30032,30057,100116,000
908151,7003,2106,5909,88019,00030,30053,600109,000
1007701,6103,0306,2309,33018,00028,60050,600103,000
1256821,4302,6905,5208,27015,90025,40044,90091,500
1506181,2902,4405,0007,49014,40023,00040,70082,900
1755691,1902,2404,6006,89013,30021,20037,40076,300
2005291,1102,0804,2806,41012,30019,70034,80071,000
2504699811,8503,7905,68010,90017,40030,80062,900
3004258891,6703,4405,1509,92015,80027,90057,000
3503918171,5403,1604,7409,12014,50025,70052,400
4003647601,4302,9404,4108,49013,50023,90048,800
4503417141,3402,7604,1307,96012,70022,40045,800
5003226741,2702,6103,9107,52012,00021,20043,200
5503066401,2102,4803,7107,14011,40020,10041,100
6002926111,1502,3603,5406,82010,90019,20039,200
6502805851,1002,2603,3906,53010,40018,40037,500
7002695621,0602,1703,2606,2709,99017,70036,000
7502595411,0202,0903,1406,0409,63017,00034,700
8002505239852,0203,0305,8309,30016,40033,500
8502425069531,9602,9305,6409,00015,90032,400
9002354909241,9002,8405,4708,72015,40031,500
9502284768971,8402,7605,3108,47015,00030,500
1,0002224638731,7902,6805,1708,24014,60029,700
1,1002104408291,7002,5504,9107,83013,80028,200
1,2002014207911,6202,4304,6807,47013,20026,900
1,3001924027571,5502,3304,4907,15012,60025,800
1,4001853867271,4902,2404,3106,87012,10024,800
1,5001783727011,4402,1604,1506,62011,70023,900
1,6001723596771,3902,0804,0106,39011,30023,000
1,7001663486551,3402,0103,8806,18010,90022,300
1,8001613376351,3001,9503,7606,00010,60021,600
1,9001573276171,2701,9003,6505,82010,30021,000
2,0001523186001,2301,8403,5505,66010,00020,400

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(28)

SCHEDULE 40 METALLIC PIPE

GasUndiluted Propane
Inlet Pressure11.0 in. w.c.
Pressure Drop0.5 in. w.c.
Specific Gravity1.50
INTENDED USEPipe sizing between single- or second-stage (low pressure) regulator and appliance.
PIPE SIZE (inch)
Nominal1/23/4111/411/2221/234
Actual ID0.6220.8241.0491.3801.6102.0672.4693.0684.026
Length (ft)Capacity in Thousands of Btu per Hour
102916081,1502,3503,5206,79010,80019,10039,000
202004187871,6202,4204,6607,43013,10026,800
301603366321,3001,9403,7505,97010,60021,500
401372875411,1101,6603,2105,1109,03018,400
501222554809851,4802,8404,5308,00016,300
601102314348921,3402,5704,1007,25014,800
801012124008211,2302,3703,7706,67013,600
100941973727631,1402,2003,5106,21012,700
125891853497161,0702,0703,2905,82011,900
150841753306771,0101,9503,1105,50011,200
175741552926008991,7302,7604,8809,950
200671402655438141,5702,5004,4209,010
250621292435007491,4402,3004,0608,290
300581202274656971,3402,1403,7807,710
350511072014126181,1901,9003,3506,840
40046971823735601,0801,7203,0406,190
45042891673445159911,5802,7905,700
50040831563204799221,4702,6005,300
55037781463004498651,3802,4404,970
60035731382834248171,3002,3004,700
65033701312694037761,2402,1904,460
70032661252573857411,1802,0904,260
75030641202463687091,1302,0004,080
80029611152363546811,0901,9203,920
85028591112273416561,0501,8503,770
90027571072203296341,0101,7903,640
95026551042133196139781,7303,530
1,00025531002063095959481,6803,420
1,1002552972003005789211,6303,320
1,2002450951952925628951,5803,230
1,3002348901852775348501,5003,070
1,4002246861762645098111,4302,930
1,5002144821692534877771,3702,800
1,6002042791622434687461,3202,690
1,7001940761562344517191,2702,590
1,8001939741512264366941,2302,500
1,9001838711462194226721,1902,420
2,0001837691422124096521,1502,350

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(29)

SEMIRIGID COPPER TUBING

GasUndiluted Propane
Inlet Pressure10.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USESizing between first stage (high-pressure regulator) and second stage (low-pressure regulator).
TUBE SIZE (in.)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Thousands of Btu per Hour
105131,0602,1503,7605,33011,40020,50032,30067,400
203527271,4802,5803,6707,83014,10022,20046,300
302835841,1902,0802,9406,29011,30017,90037,200
402425001,0201,7802,5205,3809,69015,30031,800
502154439011,5702,2304,7708,59013,50028,200
601944018161,4302,0204,3207,78012,30025,600
701793697511,3101,8603,9807,16011,30023,500
801663436991,2201,7303,7006,66010,50021,900
901563226551,1501,6303,4706,2509,85020,500
1001473046191,0801,5403,2805,9009,31019,400
1251312705499591,3602,9105,2308,25017,200
1501182444978691,2302,6304,7407,47015,600
1751092254577991,1302,4204,3606,88014,300
2001012094267441,0602,2504,0606,40013,300
250901853776599352,0003,6005,67011,800
300811683425978471,8103,2605,14010,700
350751553145497791,6603,0004,7309,840
400701442925117251,5502,7904,4009,160
450651352744806801,4502,6204,1308,590
500621272594536431,3702,4703,9008,120
550591212464306101,3002,3503,7007,710
600561152354105821,2402,2403,5307,350
650541112253935581,1902,1403,3807,040
700511062163785361,1402,0603,2506,770
750501022083645161,1001,9803,1306,520
80048992013514981,0601,9203,0206,290
85046961953404821,0301,8502,9206,090
90045931893304681,0001,8002,8405,910
95044901833204549701,7502,7505,730
1,00042881783114429441,7002,6805,580
1,10040831692964208961,6102,5405,300
1,20038791612824008551,5402,4305,050
1,30037761552703838191,4702,3204,840
1,40035731482603687871,4202,2304,650
1,50034701432503557581,3602,1504,480
1,60033681382413437321,3202,0804,330
1,70032661342343317081,2702,0104,190
1,80031641302273216871,2401,9504,060
1,90030621262203126671,2001,8903,940
2,00029601222143046481,1701,8403,830

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(30)

SEMIRIGID COPPER TUBING

GasUndiluted Propane
Inlet Pressure11.0 in. w.c.
Pressure Drop0.5 in. w.c.
Specific Gravity1.50
INTENDED USESizing between single or second stage (low-pressure regulator) and appliance.
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Thousands of Btu per Hour
1045931883294679971,8002,8305,890
2031641292263216851,2301,9504,050
3025511041822585509911,5603,250
402144891552204718481,3402,780
501939791381954177521,1802,470
601735711251773786811,0702,240
701632661151633486269882,060
801530611071523245839191,910
901428571001423045478621,800
100132754951342875178141,700
125112448841192544587221,500
150102144761082304156541,360
175NA204070992123826021,250
200NA183765921973555601,170
250NA163358821753154961,030
300NA15305274158285449936
350NA14284868146262414861
400NA13264563136244385801
450NA12244260127229361752
500NA11234056120216341710
550NA11223853114205324674
600NA10213651109196309643
650NANA203449104188296616
700NANA193347100180284592
750NANA18324596174274570
800NANA18314493168264551
850NANA17304290162256533
900NANA17294187157248517
950NANA16284085153241502
1,000NANA16273983149234488
1,100NANA15263778141223464
1,200NANA14253575135212442
1,300NANA14243472129203423
1,400NANA13233269124195407
1,500NANA13223166119188392
1,600NANA12213064115182378
1,700NANA12202962112176366
1,800NANA11202860108170355
1,900NANA11192758105166345
2,000NANA11192757102161335

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. NA means a flow of less than 10,000 Btu/h.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(31)

SEMIRIGID COPPER TUBING

GasUndiluted Propane
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USETube sizing between 2 psig service and line pressure regulator.
TUBE SIZE (inch)
NominalK & L1/43/81/25/83/4111/411/22
ACR3/81/25/83/47/811/813/8
Outside0.3750.5000.6250.7500.8751.1251.3751.6252.125
Inside0.3050.4020.5270.6520.7450.9951.2451.4811.959
Length (ft)Capacity in Thousands of Btu per Hour
104138521,7303,0304,3009,17016,50026,00054,200
202845851,1902,0802,9506,31011,40017,90037,300
302284709561,6702,3705,0609,12014,40029,900
401954028181,4302,0304,3307,80012,30025,600
501733567251,2701,8003,8406,92010,90022,700
601573236571,1501,6303,4806,2709,88020,600
701442976051,0601,5003,2005,7609,09018,900
801342765629831,3902,9805,3608,45017,600
901262595289221,3102,7905,0307,93016,500
1001192454988711,2402,6404,7507,49015,600
1251052174427721,1002,3404,2106,64013,800
150951974007009922,1203,8206,02012,500
175881813686449131,9503,5105,54011,500
200821683435998491,8103,2705,15010,700
250721493045317531,6102,9004,5609,510
300661352754816821,4602,6204,1408,610
350601242534426281,3402,4103,8007,920
400561162354115841,2502,2503,5407,370
450531092213865481,1702,1103,3206,920
500501032093655171,1101,9903,1406,530
55047971983464911,0501,8902,9806,210
60045931893304691,0001,8002,8405,920
65043891813164499591,7302,7205,670
70041861743044319211,6602,6205,450
75040821682934158881,6002,5205,250
80039801622834018571,5402,4305,070
85037771572743888291,4902,3504,900
90036751522653768041,4502,2804,750
95035721472583667811,4102,2204,620
1,00034711432513567601,3702,1604,490
1,10032671362383387211,3002,0504,270
1,20031641302273226881,2401,9504,070
1,30030611242173096591,1901,8703,900
1,40028591202092966331,1401,8003,740
1,50027571152012866101,1001,7303,610
1,60026551111942765891,0601,6703,480
1,70026531081882675701,0301,6203,370
1,80025511041822595531,0001,5703,270
1,90024501011772515379661,5203,170
2,0002348991722445229401,4803,090

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
  2. Table entries have been rounded to three significant digits.

TABLE 402.4(32)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasUndiluted Propane
Inlet Pressure11.0 in. w.c.
Pressure Drop0.5 in. w.c.
Specific Gravity1.50
INTENDED USE: SIZING BETWEEN SINGLE- OR SECOND-STAGE (Low-Pressure) REGULATOR AND THE APPLIANCE SHUTOFF VALVE
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Thousands of Btu per Hour
572991812113554267448631,4201,6382,8303,2705,7806,550
1050691291502543035216059711,1791,9902,3204,1104,640
1539551041212082484224907759721,6201,9003,3703,790
203449911061832163654256618471,4001,6502,9303,290
25304282941641923253795837621,2501,4802,6302,940
30283974871511772973445286981,1401,3502,4002,680
40233364741311532562974496109881,1702,0902,330
50203058661181372272653975488841,0501,8702,080
60192653601071262072413595028059611,7101,900
7017254957991171912223304667458901,5901,760
8015234552941091782083074386968331,4901,650
9015224450901021691972864146567871,4001,550
1001420414785981591862703936217461,3301,480
1501115313666751231432173245066111,0901,210
200914283360691121291832834385319481,050
2508122530536199117163254390476850934
3008112326505790107147234357434777854

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  2. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  3. Table entries have been rounded to three significant digits.

TABLE 402.4(33)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasUndiluted Propane
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USE: SIZING BETWEEN 2 PSI SERVICE AND THE LINE PRESSURE REGULATOR
TUBE SIZE (EHD)
Flow
Designation
1315181923253031373946486062
Length (ft)Capacity in Thousands of Btu per Hour
104265589271,1101,7402,1704,1004,7207,1307,95815,20016,80029,40034,200
252623475917011,1201,3802,5602,9504,5605,1479,55010,70018,80021,700
302383165406401,0301,2702,3302,6904,1804,7198,7109,79017,20019,800
402032714695548961,1002,0102,3203,6304,1167,5308,50014,90017,200
501812434204968069861,7902,0703,2603,7026,7307,61013,40015,400
751471963444066638091,4601,6902,6803,0535,4806,23011,00012,600
801401893333936437681,4101,6302,5902,9615,3006,04010,60012,200
1001241692983505787031,2601,4502,3302,6624,7405,4109,53010,900
1501011372452874775751,0201,1801,9102,1953,8604,4307,8108,890
200861182132484155018801,0201,6601,9153,3403,8406,7807,710
250771051912223734487859101,4901,7222,9803,4406,0806,900
30069961732033434117168291,3601,5782,7203,1505,5606,300
40060821511752983556167161,1601,3762,3502,7304,8305,460
50053721351582683195506381,0301,2372,1002,4504,3304,880

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1/2 psi (based on 13 in. w.c. outlet pressure), DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.
  2. CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guidance.
  3. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  4. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  5. Table entries have been rounded to three significant digits.

TABLE 402.4(34)

CORRUGATED STAINLESS STEEL TUBING (CSST)

GasUndiluted Propane
Inlet Pressure5.0 psi
Pressure Drop3.5 psi
Specific Gravity1.50
TUBE SIZE (EHD)
Flow Designation1315181923253031373946486062
Length (ft)Capacity in Thousands of Btu per Hour
108261,0701,7102,0603,1504,0007,8308,95013,10014,44128,60031,20054,40063,800
255096641,0901,3102,0402,5504,8605,6008,4009,33918,00019,90034,70040,400
304616039991,1901,8702,3404,4305,1007,6808,56416,40018,20031,70036,900
403965208671,0301,6302,0303,8204,4006,6807,46914,20015,80027,60032,000
503524637779261,4601,8203,4103,9305,9906,71712,70014,10024,70028,600
752843766377571,2101,4902,7703,1904,9205,53910,30011,60020,30023,400
802753636187311,1701,4502,6803,0904,7705,3729,99011,20019,60022,700
1002433245536561,0501,3002,3902,7604,2804,8308,93010,00017,60020,300
1501962624535358661,0601,9402,2403,5103,9837,2708,21014,40016,600
2001692263934647559231,6801,9303,0503,4746,2907,13012,50014,400
2501502023524156798281,4901,7302,7403,1245,6206,39011,20012,900
3001361833223796227571,3601,5702,5102,8655,1205,84010,30011,700
4001171582793285426571,1701,3602,1802,4984,4305,0708,92010,200
5001041402512944885891,0501,2101,9502,2473,9604,5408,0009,110

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Notes:

  1. Table does not include effect of pressure drop across line regulator. Where regulator loss exceeds 1 psi, DO NOT USE THIS TABLE. Consult with the regulator manufacturer for pressure drops and capacity factors. Pressure drop across regulator may vary with the flow rate.
  2. CAUTION: Capacities shown in the table might exceed maximum capacity of selected regulator. Consult with the tubing manufacturer for guidance.
  3. Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation: L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.
  4. EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
  5. Table entries have been rounded to three significant digits.

TABLE 402.4(35)

POLYETHYLENE PLASTIC PIPE

GasUndiluted Propane
Inlet Pressure11.0 in. w.c.
Pressure Drop0.5 in. w.c.
Specific Gravity1.50
INTENDED USEPE pipe sizing between integral two-stage regulator at tank or second stage (low-pressure regulator) and building.
PIPE SIZE (inch)
Nominal OD1/23/4111/411/2234
DesignationSDR 9SDR 11SDR 11SDR 10SDR 11SDR 11SDR 11SDR 11
Actual ID0.6600.8601.0771.3281.5541.9432.8643.682
Length (ft)Capacity in Thousands of Btu per Hour
103406801,2302,1303,2105,77016,00030,900
202334688441,4602,2103,97011,00021,200
301873756771,1701,7703,1808,81017,000
401603215801,0001,5202,7307,54014,600
501422855148901,3402,4206,68012,900
601292584668071,2202,1906,05011,700
701192374287421,1202,0105,57010,800
801102213986901,0401,8705,18010,000
901032073746489781,7604,8609,400
100981963536129241,6604,5908,900
125871733135428191,4704,0707,900
150781572844917421,3303,6907,130
175721452614526831,2303,3906,560
200671352434206351,1403,1606,100
250601192153735631,0102,8005,410
300541081953385109162,5304,900
35050991793114698432,3304,510
40046921672894367842,1704,190
45043871572714097362,0403,930
50041821482563876951,9203,720

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(36)

POLYETHYLENE PLASTIC PIPE

GasUndiluted Propane
Inlet Pressure2.0 psi
Pressure Drop1.0 psi
Specific Gravity1.50
INTENDED USEPE pipe sizing between 2 psig service regulator and line pressure regulator.
PIPE SIZE (inch)
Nominal OD1/23/4111/411/2234
DesignationSDR 9SDR 11SDR 11SDR 10SDR 11SDR 11SDR 11SDR 11
Actual ID0.6600.8601.0771.3281.5541.9432.8643.682
Length (ft)Capacity in Thousands of Btu per Hour
103,1306,26011,30019,60029,50053,100147,000284,000
202,1504,3007,76013,40020,30036,500101,000195,000
301,7303,4506,23010,80016,30029,30081,100157,000
401,4802,9605,3309,24014,00025,10069,400134,100
501,3102,6204,7308,19012,40022,20061,500119,000
601,1902,3704,2807,42011,20020,10055,700108,000
701,0902,1803,9406,83010,30018,50051,30099,100
801,0102,0303,6706,3509,59017,20047,70092,200
909521,9103,4405,9609,00016,20044,70086,500
1008991,8003,2505,6308,50015,30042,30081,700
1257971,6002,8804,9907,53013,50037,50072,400
1507221,4502,6104,5206,83012,30033,90065,600
1756641,3302,4004,1606,28011,30031,20060,300
2006181,2402,2303,8705,84010,50029,00056,100
2505481,1001,9803,4305,1809,30025,70049,800
3004969941,7903,1104,6908,43023,30045,100
3504579141,6502,8604,3207,76021,50041,500
4004258511,5302,6604,0207,22012,00038,600
4503997981,4402,5003,7706,77018,70036,200
5003777541,3602,3603,5606,39017,70034,200
5503587161,2902,2403,3806,07016,80032,500
6003416831,2302,1403,2205,79016,00031,000
6503276541,1802,0403,0905,55015,40029,700
7003146281,1301,9602,9705,33014,70028,500
7503026051,0901,8902,8605,14014,20027,500
8002925851,0501,8302,7604,96013,70026,500
8502835661,0201,7702,6704,80013,30025,700
9002745499901,7102,5904,65012,90024,900
9502665339611,6702,5204,52012,50024,200
1,0002595189351,6202,4504,40012,20023,500
1,1002464928881,5402,3204,17011,50022,300
1,2002344708471,4702,2203,98011,00021,300
1,3002254508111,4102,1203,81010,60020,400
1,4002164327791,3502,0403,66010,10019,600
1,5002084167511,3001,9603,5309,76018,900
1,6002014027251,2601,9003,4109,43018,200
1,7001943897021,2201,8403,3009,13017,600
1,8001883776801,1801,7803,2008,85017,100
1,9001833666611,1401,7303,1108,59016,600
2,0001783566431,1101,6803,0208,36016,200

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m3/h, 1 degree = 0.01745 rad.

Note: Table entries have been rounded to three significant digits.

TABLE 402.4(37)

POLYETHYLENE PLASTIC TUBING

GasUndiluted Propane
Inlet Pressure11.0 in. w.c.
Pressure Drop0.5 in. w.c.
Specific Gravity1.50
INTENDED USEPE pipe sizing between integral two-stage regulator at tank or second stage (low-pressure regulator) and building.
Plastic Tubing Size (CTS) (inch)
Nominal OD1/21
DesignationSDR 7SDR 11
Actual ID0.4450.927
Length (ft)Capacity in Cubic Feet of Gas per Hour
10121828
2083569
3067457
4057391
5051347