ADOPTS WITH AMENDMENTS:

International Residential Code 2015 (IRC 2015)

Part I — Administrative

Part II — Definitions

Part III — Building Planning and Construction

Part IV — Energy Conservation

Part V — Mechanical

Part VI — Fuel Gas

Part VII — Plumbing

Part IX — Referenced Standards

Heads up: There are no amended sections in this chapter.
Hydronic piping shall conform to Table M2101.1. Approved piping, valves, fittings and connections shall be installed in accordance with the manufacturer's instructions. Pipe and fittings shall be rated for use at the operating temperature and pressure of the hydronic system. Used pipe, fittings, valves or other materials shall be free of foreign materials.
TABLE M2101.1
HYDRONIC PIPING MATERIALS
MATERIAL USE
CODEa
STANDARDb JOINTS NOTES
Acrylonitrile butadiene styrene
   (ABS) plastic pipe
1, 5 ASTM D1527;
ASTM F2806;
ASTM F2969
Solvent cement joints  
Brass pipe 1 ASTM B43 Brazed, welded, threaded, mechanical and
flanged fittings
 
Brass tubing 1 ASTM B135 Brazed, soldered and mechanical fittings  
Chlorinated poly (vinyl chloride)
   (CPVC) pipe and tubing
1, 2, 3 ASTM D2846 Solvent cement joints, compression joints and threaded adapters  
Copper pipe 1 ASTM B42,
B302
Brazed, soldered and mechanical fittings
threaded, welded and flanged
 
Copper tubing (type K, Lor M) 1, 2 ASTM B75,
B88, B251,
B306
Brazed, soldered and flared mechanical
fittings
Joints embedded in concrete
Cross-linked polyethylene (PEX) 1, 2, 3 ASTM F876,
F877
(See PEX fittings) Install in accordance with
manufacturer's instructions
Cross-linked polyethylene/
   aluminum/cross -linked
   polyethylene-(PEX-AL-PEX)
   pressure pipe
1, 2 ASTM F1281 or
CAN/CSA
B137.10
Mechanical, crimp/insert Install in accordance with
manufacturer's instructions
PEX fittings   ASTM F 877
ASTM F 1807
ASTM F 1960
ASTM F 2098
ASTM F 2159
ASTM F 2735
Copper-crimp/insert fittings, cold expansion
fittings, stainless steel clamp, insert
fittings
Install in accordance with
manufacturer's instructions
Polybutylene (PB) pipe and tubing 1, 2, 3 ASTM D3309 Heat-fusion, crimp/insert and compression Joints in concrete shall be
heat-fused
Polyethylene/aluminum/polyethylene
   (PE-AL-PE) pressure pipe
1, 2, 3 ASTM F1282
CSA B 137.9
Mechanical, crimp/insert  
Polypropylene (PP) 1, 2, 3 ISO 15874
ASTM F 2389
Heat-fusion joints, mechanical fittings,
threaded adapters, compression joints
 
Raised temperature polyethylene
   PE-RT)
1, 2, 3 ASTM F2623
ASTM F2769
Copper crimp/insert fitting stainless steel
clamp, insert fittings
 
Raised temperature polyethylene
   PE-RT) fittings
1, 2, 3 ASTM F1807
ASTM F2159
ASTM F2735
ASTM F2769
ASTM F2098
Copper crimp/insert fitting stainless steel
clamp, insert fittings
 
Steel pipe 1, 2 ASTM A53,
A106
Brazed, welded, threaded, flanged and
mechanical fittings
Joints in concrete shall be
welded. Galvanized pipe
shall not be welded or
brazed.
Steel tubing 1 ASTM A 254 Mechanical fittings, welded  
For SI: °C = [(°F)-32]/1.8.
  1. Use code:
    1. Above ground.
    2. Embedded in radiant systems.
    3. Temperatures below 180°F only.
    4. Low temperature (below 130°F) applications only.
    5. Temperatures below 160°F only.
  2. Standards as listed in Chapter 44.
Hydronic piping systems shall be installed to permit draining of the system. Where the system drains to the plumbing drainage system, the installation shall conform to the requirements of Chapters 25 through 32 of this code.

Exception: The buried portions of systems embedded underground or under floors.
The potable water system shall be protected from backflow in accordance with the provisions listed in Section P2902.
Openings through concrete or masonry building elements shall be sleeved.
A hydronic piping system shall not be in direct contact with any building material that causes the piping material to degrade or corrode.
Wood-framed structural members shall be drilled, notched or altered in accordance with the provisions of Sections R502.8, R602.6, R602.6.1 and R802.7. Holes in load bearing members of cold-formed steel light-frame construction shall be permitted only in accordance with Sections R505.2.6, R603.2.6 and R804.2.6. In accordance with the provisions of Sections R505.3.5, R603.3.4 and R804.3.3, cutting and notching of flanges and lips of load-bearing members of cold-formed steel lightframe construction shall not be permitted. Structural insulated panels (SIPs) shall be drilled and notched or altered in accordance with the provisions of Section R610.7.
Fluid in the supply side of a hydronic system shall not enter a tee fitting through the branch opening.
Piping shall be installed so that piping, connections and equipment shall not be subjected to excessive strains or stresses. Provisions shall be made to compensate for expansion, contraction, shrinkage and structural settlement.
Hangers and supports shall be of material of sufficient strength to support the piping, and shall be fabricated from materials compatible with the piping material. Piping shall be supported at intervals not exceeding the spacing specified in Table M2101.9.
TABLE M2101.9
HANGER SPACING INTERVALS
PIPING MATERIAL MAXIMUM
HORIZONTAL
SPACING
(feet)
MAXIMUM
VERTICAL
SPACING
(feet)
ABS 4 10a
CPVC ≤ 1-inch pipe or tubing 3 5a
CPVC ≥ 1 1/4 inches 4 10a
Copper or copper alloy pipe 12 10
Copper or copper alloy tubing 6 10
PB pipe or tubing 2.67 4
PE pipe or tubing 2.67 4
PE-RT ≤ 1 inch 2.67 10a
PE-RT ≥ 1 1/4 inches 4 10a
PEX tubing 2.67 4
PP < 1-inch pipe or tubing 2.67 4
PP > 1 1/4 inches 4 10a
PVC 4 10a
Steel pipe 12 15
Steel tubing 8 10
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. For sizes 2 inches and smaller, a guide shall be installed midway between required vertical supports. Such guides shall prevent pipe movement in a direction perpendicular to the axis of the pipe.
Hydronic piping systems shall be tested hydrostatically at a pressure of one and one-half times the maximum system design pressure, but not less than 100 pounds per square inch (689 kPa). The duration of each test shall be not less than 15 minutes and not more than 20 minutes.
Baseboard convectors shall be installed in accordance with the manufacturer's instructions. Convectors shall be supported independently of the hydronic piping.
Piping for embedment in concrete or gypsum materials shall be standard-weight steel pipe, copper and copper alloy pipe and tubing, cross-linked polyethylene/ aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe, chlorinated polyvinyl chloride (CPVC), polybutylene, cross-linked polyethylene (PEX) tubing, polyethylene of raised temperature (PE-RT) or polypropylene (PP) with a minimum rating of 100 psi at 180°F (690 kPa at 82°C).
Radiant floor heating systems shall have a thermal barrier in accordance with Sections M2103.2.1 through M2103.2.4.

Exception: Insulation shall not be required in engineered systems where it can be demonstrated that the insulation will decrease the efficiency or have a negative effect on the installation.
Radiant piping used in slab-on-grade applications shall have insulating materials having a minimum R-value of 5 installed beneath the piping.
In suspended floor applications, insulation shall be installed in the joist bay cavity serving the heating space above and shall consist of materials having a minimum R-value of 11.
A thermal break consisting of asphalt expansion joint materials or similar insulating materials shall be provided at a point where a heated slab meets a foundation wall or other conductive slab.
Insulating materials used in thermal barriers shall be installed so that the manufacturer's R-value mark is readily observable upon inspection.
Copper and copper alloy systems shall be soldered in accordance with ASTM B828. Fluxes for soldering shall be in accordance with ASTM B813. Brazing fluxes shall be in accordance with AWS A5.31. Piping joints that are embedded shall be installed in accordance with the following requirements:
  1. Steel pipe joints shall be welded.
  2. Copper tubing shall be joined by brazing complying with Section P3003.6.1.
  3. Polybutylene pipe and tubing joints shall be installed with socket-type heat-fused polybutylene fittings.
  4. CPVC tubing shall be joined using solvent cement joints.
  5. Polypropylene pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings.
  6. Cross-linked polyethylene (PEX) tubing shall be joined using cold expansion, insert or compression fittings.
  7. Raised temperature polyethylene (PE-RT) tubing shall be joined using insert or compression fittings.
Piping or tubing to be embedded shall be tested by applying a hydrostatic pressure of not less than 100 psi (690 kPa). The pressure shall be maintained for 30 minutes, during which, the joints shall be visually inspected for leaks.
Low temperature piping for embedment in concrete or gypsum materials shall be as indicated in Table M2101.1.
Piping joints, other than those in Section M2103.3, that are embedded shall comply with the following requirements:
  1. Cross-linked polyethylene (PEX) tubing shall be installed in accordance with the manufacturer's instructions.
  2. Polyethylene tubing shall be installed with heat fusion joints.
  3. Polypropylene (PP) tubing shall be installed in accordance with the manufacturer's instructions.
  4. Raised temperature polyethylene (PE-RT) shall be installed in accordance with the manufacturer's instructions.
Joints between raised temperature polyethylene tubing and fittings shall conform to Sections M2104.3.1, M2104.3.2 and M2104.3.3. Mechanical joints shall be installed in accordance with the manufacturer's instructions.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting such inserts and ferrules or O-rings.
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE-RT pipe.
PE-RT insert fittings shall be installed in accordance with the manufacturer's instructions.
Joints between polyethylene/aluminum/ polyethylene pressure pipe and fittings shall conform to Sections M2104.4.1 and M2104.4.2. Mechanical joints shall be installed in accordance with the manufacturer's instructions.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting such inserts and ferrules or O-rings.
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE-AL-PE pipe.
Plastic piping and tubing material used in water-based ground-source heat-pump ground-loop systems shall conform to the standards specified in this section.
Reused pipe, fittings, valves, and other materials shall not be used in ground-source heat-pump loop systems.
Pipe and tubing shall be rated for the operating temperature and pressure of the ground-source heat-pump loop system. Fittings shall be suitable for the pressure applications and recommended by the manufacturer for installation with the pipe and tubing material installed. Where used underground, materials shall be suitable for burial.
Groundsource heat-pump ground-loop pipe and tubing shall conform to the standards listed in Table M2105.4.
TABLE M2105.4
GROUND-SOURCE LOOP PIPE
MATERIAL STANDARD
Chlorinated polyvinyl chloride
   (CPVC)
ASTM D2846; ASTM F437; ASTM F438; ASTM F439; ASTM F441;
ASTM F442; CSA B 137.6
Cross -linked polyethylene (PEX) ASTM F876; ASTM F877, CSA B137.5
Polyethylene/aluminum/polyethylene
   (PE-AL-PE) pressure pipe
ASTM F1282; CSA B 137.9; AWWA C903
High-density polyethylene (HDPE) ASTM D2737; ASTM D3035; ASTM F714; AWWA C901; CSA B137.1; CSA C448; NSF 358-1
Polypropylene (PP-R) ASTM F2389; CSA B 137.11
Polyvinyl chloride (PVC) ASTM D1785; ASTM D2241; CSA 137.3
Raised temperature polyethylene
   (PE-RT)
ASTM F2623; ASTM F2769
Ground-source heat-pump pipe fittings shall be approved for installation with the piping materials to be installed, shall conform to the standards listed in Table M2105.5 and, where installed underground, shall be suitable for burial.
TABLE M2105.5
GROUND-SOURCE LOOP PIPE FITTINGS
PIPE MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) ASTM D2846; ASTM F437; ASTM F438; ASTM F439; ASTM F1970; CSA B137.6
Cross-linked polyethylene (PEX) ASTM F877; ASTM F1807; ASTM F1960; ASTM F2080;
ASTM F2159; ASTM F2434; CSA B137.5
Polyethylene/aluminum/polyethylene
   (PE-AL-PE)
ASTM F2434; ASTM F1282; CSA B137.9
High-density polyethylene (HDPE) ASTM D2683; ASTM D3261; ASTM F1055; CSA B137.1; CSA C448 ; NSF 358-1
Polypropylene (PP-R) ASTM F2389; CSA B137.11; NSF 358-2
Polyvinyl chloride (PVC) ASTM D2464; ASTM D2466; ASTM D2467; ASTM F1970, CSA B137.2; CSA B137.3
Raised temperature polyethylene (PE-RT) ASTM D3261; ASTM F1807; ASTM F2159; F2769 ; B137.1
Joints and connections shall be of an approved type. Joints and connections shall be tight for the pressure of the ground-source loop system. Joints used underground shall be approved for such applications.
Joints between different piping materials shall be made with approved transition fittings.
Pipe shall be cut square, reamed, and shall be free of burrs and obstructions. CPVC, PE and PVC pipe shall be chamfered. Pipe ends shall have full-bore openings and shall not be undercut.
Where required by Sections M2105.9 through M2105.11, the preparation and installation of mechanical and thermoplastic-welded joints shall comply with Sections M2105.8.1 and M2015.8.2.
Mechanical joints shall be installed in accordance with the manufacturer's instructions.
Joint surfaces for thermoplastic-welded joints shall be cleaned by an approved procedure. Joints shall be welded in accordance with the manufacturer's instructions.
Joints between CPVC plastic pipe or fittings shall be solvent-cemented in accordance with Section P2906.9.1.2. Threaded joints between fittings and CPVC plastic pipe shall be in accordance with Section M2105.9.1.
Threads shall conform to ASME B1.20.1. The pipe shall be Schedule 80 or heavier plastic pipe and shall be threaded with dies specifically designed for plastic pipe. Thread lubricant, pipe-joint compound or tape shall be applied on the male threads only and shall be approved for application on the piping material.
Joints between cross-linked polyethylene plastic tubing and fittings shall comply with Sections M2105.10.1 and M2105.10.2. Mechanical joints shall comply with Section M2105.8.1.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to plastic pipe or tubing.
Joints between polyethylene plastic pipe and tubing or fittings for ground-source heat-pump loop systems shall be heat-fusion joints complying with Section M2105.11.1, electrofusion joints complying with Section M2105.11.2, or stab-type insertion joints complying with Section M2105.11.3.
Joints shall be of the socket-fusion, saddle-fusion or butt-fusion type, and joined in accordance with ASTM D2657. Joint surfaces shall be clean and free of moisture. Joint surfaces shall be heated to melt temperatures and joined. The joint shall be undisturbed until cool. Fittings shall be manufactured in accordance with ASTM D2683 or ASTM D3261.
Joints shall be of the electrofusion type. Joint surfaces shall be clean and free of moisture, and scoured to expose virgin resin. Joint surfaces shall be heated to melt temperatures for the period of time specified by the manufacturer. The joint shall be undisturbed until cool. Fittings shall be manufactured in accordance with ASTM F1055.
Joint surfaces shall be clean and free of moisture. Pipe ends shall be chamfered and inserted into the fittings to full depth. Fittings shall be manufactured in accordance with ASTM F1924.
Joints between PP plastic pipe and fittings shall comply with Sections M2105.12.1 and M2105.12.2.
Heat-fusion joints for polypropylene (PP) pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, electrofusion polypropylene fittings or by butt fusion. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F2389.
Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions.
Joints between raised temperature polyethylene tubing and fittings shall comply with Sections M2105.13.1 and M2105.13.2. Mechanical joints shall comply with Section M2105.8.1.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PE-RT pipe or tubing.
Joints between PVC plastic pipe or fittings shall be solvent-cemented in accordance with Section P2906.9.1.4. Threaded joints between fittings and PVC plastic pipe shall be in accordance with Section M2105.9.1.
Shutoff valves shall be installed in ground-source loop piping systems in the locations indicated in Sections M2105.15.1 through M2105.15.6.
Shutoff valves shall be installed on the supply and return side of a heat exchanger.

Exception: Shutoff valves shall not be required where heat exchangers are integral with a boiler or are a component of a manufacturer's boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves required by Section M2001.3.
Shutoff valves shall be installed on the building supply and return of a central utility system.
Shutoff valves shall be installed on the connection to any pressure vessel.
Shutoff valves shall be installed on both sides of a pressure-reducing valve.
Shutoff valves shall be installed on connections to mechanical equipment and appliances. This requirement does not apply to components of ground-source loop systems such as pumps, air separators, metering devices, and similar equipment.
Shutoff valves shall be installed at connections to nondiaphragm-type expansion tanks.
A pressure relief valve shall be installed on the low-pressure side of a hydronic piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with Section M2002.
Piping, valves, fittings, and connections shall be installed in accordance with the manufacturer's instructions.
Where ground-source heat-pump ground-loop systems have a connection to a potable water supply, the potable water system shall be protected from backflow in accordance with Section P2902.
Openings for pipe penetrations in walls, floors and ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building elements shall be sleeved. The annular space surrounding pipe penetrations shall be protected in accordance with Section P2606.1.
A pipe in a ground-source heat pump piping system having an exterior surface temperature exceeding 250°F (121°C) shall have a clearance of not less than 1 inch (25 mm) from combustible materials.
A ground-source heat-pump ground-loop piping system shall not be in direct contact with building materials that cause the piping or fitting material to degrade or corrode, or that interfere with the operation of the system.
Piping shall be installed so as to prevent detrimental strains and stresses in the pipe. Provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement. Piping shall be installed so as to avoid structural stresses or strains within building components.
Piping located in a flood hazard area shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation.
Pipe shall be supported in accordance with Section M2101.9.
Ground-source heat-pump ground-loop systems shall be designed so that the flow velocities do not exceed the maximum flow velocity recommended by the pipe and fittings manufacturer. Flow velocities shall be controlled to reduce the possibility of water hammer.
Ground-source heat-pump ground-loop system piping shall be marked with tape, metal tags or other methods where it enters a building. The marking shall state the following words: "GROUNDSOURCE HEAT-PUMP LOOP SYSTEM." The marking shall indicate if antifreeze is used in the system and shall indicate the chemicals by name and concentration.
Antifreeze and other materials used in the system shall be chemically compatible with the pipe, tubing, fittings and mechanical systems.
The transfer fluid shall be compatible with the makeup water supplied to the system.
Before connection header trenches are backfilled, the assembled loop system shall be pressure tested with water at 100 psi (689 kPa) for 15 minutes without observed leaks. Flow and pressure loss testing shall be performed and the actual flow rates and pressure drops shall be compared to the calculated design values. If actual flow rate or pressure drop values differ from calculated design values by more than 10 percent, the cause shall be identified and corrective action taken.
Ground-source heat-pump ground-loop piping to be embedded in concrete shall be pressure tested prior to pouring concrete. During pouring, the pipe shall be maintained at the proposed operating pressure.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING