The provisions of this chapter shall govern the
quality, workmanship and requirements for materials covered.
Materials of construction and tests shall conform to the
applicable standards listed in this code.
New building materials, equipment,
appliances, systems or methods of construction not provided
for in this code, and any material of questioned suitability
proposed for use in the construction of a building or structure,
shall be subjected to the tests prescribed in this chapter and in
the approved rules to determine character, quality and limitations
of use.
The following terms are defined in Chapter
2:
APPROVED AGENCY.
APPROVED FABRICATOR.
CERTIFICATE OF COMPLIANCE.
DESIGNATED SEISMIC SYSTEM.
FABRICATED ITEM.
INTUMESCENT FIRE-RESISTANT COATINGS.
MAIN WINDFORCE-RESISTING SYSTEM.
MASTIC FIRE-RESISTANT COATINGS.
SPECIAL INSPECTION.
SPECIAL INSPECTOR.
SPRAYED FIRE-RESISTANT MATERIALS.
STRUCTURAL OBSERVATION.
APPROVED AGENCY.
APPROVED FABRICATOR.
CERTIFICATE OF COMPLIANCE.
DESIGNATED SEISMIC SYSTEM.
FABRICATED ITEM.
INTUMESCENT FIRE-RESISTANT COATINGS.
MAIN WINDFORCE-RESISTING SYSTEM.
MASTIC FIRE-RESISTANT COATINGS.
SPECIAL INSPECTION.
SPECIAL INSPECTOR.
SPRAYED FIRE-RESISTANT MATERIALS.
STRUCTURAL OBSERVATION.
An approved agency shall provide
all information as necessary for the building official to determine
that the agency meets the applicable requirements specified
in Sections 1703.1.1 through 1703.1.3.
An approved agency shall be
objective, competent and independent from the contractor
responsible for the work being inspected. The agency shall
also disclose to the building official and the registered
design professional in responsible charge possible conflicts
of interest so that objectivity can be confirmed.
An approved agency shall have
adequate equipment to perform required tests. The equipment
shall be periodically calibrated.
An approved agency shall employ
experienced personnel educated in conducting, supervising
and evaluating tests and special inspections.
Any material, appliance, equipment,
system or method of construction meeting the requirements
of this code shall be approved in writing after
satisfactory completion of the required tests and submission
of required test reports.
For any material, appliance,
equipment, system or method of construction that has been
approved, a record of such approval, including the conditions
and limitations of the approval, shall be kept on file in the
building official's office and shall be available for public
review at appropriate times.
Specific information consisting of test
reports conducted by an approved agency in accordance with
the appropriate referenced standards, or other such information
as necessary, shall be provided for the building official to
determine that the product, material or assembly meets the
applicable code requirements.
Sufficient technical
data shall be submitted to the building official to substantiate
the proposed use of any product, material or
assembly. If it is determined that the evidence submitted is
satisfactory proof of performance for the use intended, the
building official shall approve the use of the product,
material or assembly subject to the requirements of this
code. The costs, reports and investigations required under
these provisions shall be paid by the owner or the owner's
authorized agent.
Supporting data, where necessary
to assist in the approval of products, materials or
assemblies not specifically provided for in this code, shall
consist of valid research reports from approved sources.
An approved agency shall test a representative
sample of the product, material or assembly
being labeled to the relevant standard or standards. The
approved agency shall maintain a record of the tests performed.
The record shall provide sufficient detail to verify
compliance with the test standard.
The label shall contain the
manufacturer's identification, model number, serial number
or definitive information describing the performance
characteristics of the product, material or assembly and the
approved agency's identification.
Information required to be
permanently identified on the product, material or assembly
shall be acid etched, sand blasted, ceramic fired, laser
etched, embossed or of a type that, once applied, cannot be
removed without being destroyed.
Where structural components or other items regulated by this
code are not visible for inspection after completion of a prefabricated
assembly, the owner or the owner's authorized
agent shall submit a report of each prefabricated assembly.
The report shall indicate the complete details of the assembly,
including a description of the assembly and its components,
the basis upon which the assembly is being evaluated, test
results and similar information and other data as necessary
for the building official to determine conformance to this
code. Such a report shall be approved by the building official.
The owner or the owner's
authorized agent shall provide for special inspections of
fabricated items in accordance with Section 1704.2.5.
Copies of necessary
test and special inspection records shall be filed with
the building official.
Special inspections and tests, statements of
special inspections, responsibilities of contractors, submittals
to the building official and structural observations shall meet
the applicable requirements of this section.
Where application is
made to the building official for construction as specified in
Section 105, the owner or the owner's authorized agent, other
than the contractor, shall employ one or more approved agencies
to provide special inspections and tests during construction on the types of work specified in Section 1705 and
identify the approved agencies to the building official. These
special inspections and tests are in addition to the inspections
by the building official that are identified in Section 110.
Exceptions:
- Special inspections and tests are not required for construction of a minor nature or as warranted by conditions in the jurisdiction as approved by the building official.
- Unless otherwise required by the building official, special inspections and tests are not required for Group U occupancies that are accessory to a residential occupancy including, but not limited to, those listed in Section 312.1.
- Special inspections and tests are not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2211.7 or the conventional light-frame construction provisions of Section 2308.
- The contractor is permitted to employ the approved agencies where the contractor is also the owner.
Prior to the
start of the construction, the approved agencies shall provide
written documentation to the building official demonstrating
the competence and relevant experience or
training of the special inspectors who will perform the
special inspections and tests during construction. Experience
or training shall be considered relevant where the
documented experience or training is related in complexity
to the same type of special inspection or testing activities
for projects of similar complexity and material qualities.
These qualifications are in addition to qualifications specified
in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
The construction
or work for which special inspection or testing is required
shall remain accessible and exposed for special inspection
or testing purposes until completion of the required special
inspections or tests.
The applicant
shall submit a statement of special inspections in accordance
with Section 107.1 as a condition for permit issuance.
This statement shall be in accordance with Section
1704.3.
Exception: A statement of special inspections is not
required for portions of structures designed and constructed
in accordance with the cold-formed steel light-frame
construction provisions of Section 2211.7 or the
conventional light-frame construction provisions of
Section 2308.
Approved agencies shall
keep records of special inspections and tests. The
approved agency shall submit reports of special inspections
and tests to the building official and to the registered
design professional in responsible charge. Reports shall
indicate that work inspected or tested was or was not completed
in conformance to approved construction documents.
Discrepancies shall be brought to the immediate
attention of the contractor for correction. If they are not
corrected, the discrepancies shall be brought to the attention
of the building official and to the registered design
professional in responsible charge prior to the completion
of that phase of the work. A final report documenting
required special inspections and tests, and correction of
any discrepancies noted in the inspections or tests, shall be
submitted at a point in time agreed upon prior to the start
of work by the owner or the owner's authorized agent to
the building official.
Where
fabrication of structural, load-bearing or lateral loadresisting
members or assemblies is being conducted on the
premises of a fabricator's shop, special inspections of the
fabricated items shall be performed during fabrication.
Exceptions:
- Special inspections during fabrication are not required where the fabricator maintains approved detailed fabrication and quality control procedures that provide a basis for control of the workmanship and the fabricator's ability to conform to approved construction documents and this code. Approval shall be based upon review of fabrication and quality control procedures and periodic inspection of fabrication practices by the building official.
- Special inspections are not required where the fabricator is registered and approved in accordance with Section 1704.2.5.1.
Special inspections
during fabrication are not required where the work is
done on the premises of a fabricator registered and
approved to perform such work without special inspection.
Approval shall be based upon review of the fabricator's
written procedural and quality control manuals
and periodic auditing of fabrication practices by an
approved agency. At completion of fabrication, the
approved fabricator shall submit a certificate of compliance
to the owner or the owner's authorized agent for
submittal to the building official as specified in Section
1704.5 stating that the work was performed in accordance
with the approved construct ion documents.
Where special
inspections or tests are required by Section 1705, the registered
design professional in responsible charge shall prepare
a statement of special inspections in accordance with Section
1704.3.1 for submittal by the applicant in accordance with
Section 1704.2.3.
Exception: The statement of special inspections is permitted
to be prepared by a qualified person approved by the building official for construction not designed by a registered
design professional.
The statement of special inspections shall identify the following:
- The materials, systems, components and work required to have special inspections or tests by the building official or by the registered design professional responsible for each portion of the work.
- The type and extent of each special inspection.
- The type and extent of each test.
- Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705.11, 1705.12 and 1705.13.
- For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
Where Section 1705.12 or 1705.13 specifies
special inspections or tests for seismic resistance, the
statement of special inspections shall identify the designated
seismic systems and seismic force-resisting systems
that are subject to the special inspections or tests.
Where Section 1705.11 specifies special
inspection for wind resistance, the statement of special
inspections shall identify the main windforce-resisting
systems and wind-resisting components that are subject to
special inspections.
Each contractor responsible
for the construction of a main wind- or seismic force-resisting
system, designated seismic system or a wind- or
seismic force-resisting component listed in the statement of
special inspections shall submit a written statement of
responsibility to the building official and the owner or the
owner's authorized agent prior to the commencement of work
on the system or component. The contractor's statement of
responsibility shall contain acknowledgement of awareness
of the special requirements contained in the statement of special
inspections.
In addition to the
submittal of reports of special inspections and tests in accordance
with Section 1704.2.4, reports and certificates shall be
submitted by the owner or the owner's authorized agent to the
building official for each of the following:
- Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the premises of a registered and approved fabricator in accordance with Section 1704.2.5.1.
- Certificates of compliance for the seismic qualification of nonstructural components, supports and attachments in accordance with Section 1705.13.2.
- Certificates of compliance for designated seismic systems in accordance with Section 1705.13.3.
- Reports of preconstruction tests for shotcrete in accordance with Section 1908.5.
- Certificates of compliance for open web steel joists and joist girders in accordance with Section 2207.5.
- Reports of material properties verifying compliance with the requirements of AWS D1.4 for weldability as specified in Section 26.6.4 of ACI 318 for reinforcing bars in concrete complying with a standard other than ASTM A706 that are to be welded; and
- Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying with ASTM A615 and used to resist earthquakeinduced flexural or axial forces in the special moment frames, special structural walls or coupling beams connecting special structural walls of seismic force-resisting systems in structures assigned to Seismic Design Category B, C, D, E or F.
Where required by the provisions
of Section 1704.6.1 or 1704.6.2, the owner or the
owner's authorized agent shall employ a registered design
professional to perform structural observations. Structural
observation does not include or waive the responsibility for
the inspections in Section 110 or the special inspections in
Section 1705 or other sections of this code.
Prior to the commencement of observations, the structural observer shall submit to the building official a written statement identifying the frequency and extent of structural observations.
At the conclusion of the work included in the permit, the structural observer shall submit to the building official a written statement that the site visits have been made and identify any reported deficiencies that, to the best of the structural observer's knowledge, have not been resolved.
Prior to the commencement of observations, the structural observer shall submit to the building official a written statement identifying the frequency and extent of structural observations.
At the conclusion of the work included in the permit, the structural observer shall submit to the building official a written statement that the site visits have been made and identify any reported deficiencies that, to the best of the structural observer's knowledge, have not been resolved.
Structural observations shall be provided for those structures
assigned to Seismic Design Category D, E or F
where one or more of the following conditions exist:
- The structure is classified as Risk Category III or IV.
- The height of the structure is greater than 75 feet (22,860 mm) above the base as defined in ASCE 7.
- The structure is assigned to Seismic Design Category E, is classified as Risk Category I or II, and is greater than two stories above grade plane.
- When so designated by the registered design professional responsible for the structural design.
- When such observation is specifically required by the building official.
Structural observations shall be provided for those
structures sited where Vasd as determined in accordance
with Section 1609.3.1 exceeds 110 mph (49 m/sec), where
one or more of the following conditions exist:
- The structure is classified as Risk Category III or IV.
- The building height is greater than 75 feet (22,860 mm).
- When so designated by the registered design professional responsible for the structural design.
- When such observation is specifically required by the building official.
Special inspections and tests of elements
and nonstructural components of buildings and structures
shall meet the applicable requirements of this section.
Special inspections and tests shall
be required for proposed work that is, in the opinion of the
building official, unusual in its nature, such as, but not
limited to, the following examples:
- Construction materials and systems that are alternatives to materials and systems prescribed by this code.
- Unusual design applications of materials described in this code.
- Materials and systems required to be installed in accordance with additional manufacturer's instructions that prescribe requirements not contained in this code or in standards referenced by this code.
The special inspections and nondestructive
testing of steel construction in buildings, structures,
and portions thereof shall be in accordance with this
section.
Exception: Special inspections of the steel fabrication
process shall not be required where the fabricator does not
perform any welding, thermal cutting or heating operation
of any kind as part of the fabrication process. In such
cases, the fabricator shall be required to submit a detailed
procedure for material control that demonstrates the fabricator's
ability to maintain suitable records and procedures
such that, at any time during the fabrication process, the
material specification and grade for the main stress-carrying
elements are capable of being determined. Mill test
reports shall be identifiable to the main stress-carrying elements
when required by the approved construction documents.
Special inspections and nondestructive
testing of structural steel elements in buildings,
structures and portions thereof shall be in accordance with
the quality assurance inspection requirements of AISC
360.
Exception: Special inspection of railing systems composed
of structural steel elements shall be limited to
welding inspection of welds at the base of cantilevered
rail posts.
Special inspections and
qualification of welding special inspectors for cold-formed
steel floor and roof deck shall be in accordance with the
quality assurance inspection requirements of SDI QA/QC.
Special inspections of open-web steel joists and joist girders in buildings, structures and portions thereof shall be in accordance with Table 1705.2.3.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
REFERENCED STANDARDa |
1. Installation of open-web steel joists and joist girders. | |||
a. End connections - welding or bolted. | - | X | SJI specifications listed in Section 2207.1. |
b. Bridging - horizontal or diagonal. | - | ||
1. Standard bridging. | - | X | SJI specifications listed in Section 2207.1. |
2. Bridging that differs from the SJI specifications listed in Section 2207.1. | X |
For SI: 1 inch = 25.4 mm.
- Where applicable, see also Section 1705.12, Special inspections for seismic resistance.
Where a cold-formed steel truss clear span is 60
feet (18288 mm) or greater, the special inspector shall
verify that the temporary installation restraint/bracing and
the permanent individual truss member restraint/bracing
are installed in accordance with the approved truss submittal
package.
Special inspections and tests
of concrete construction shall be performed in accordance
with this section and Table 1705.3.
For SI: 1 inch = 25.4 mm.
Exception: Special inspections and tests shall not be
required for:
- Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock.
- Continuous concrete footings supporting walls of
buildings three stories or less above grade plane that
are fully supported on earth or rock where:
- The footings support walls of light-frame construction.
- The footings are designed in accordance with Table 1809.7.
- The structural design of the footing is based on a specified compressive strength, f 'c, not more than 2,500 pounds per square inch (psi) (17.2 MPa), regardless of the compressive strength specified in the approved construction documents or used in the footing construction.
- Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 MPa).
- Concrete foundation walls constructed in accordance with Table 1807.1.6.2.
- Concrete patios, driveways and sidewalks, on grade.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
REFERENCED STANDARDa |
IBC REFERENCE |
|
- | X | ACI 318 Ch. 20, 25.2, 25.3, 26.6.1-26.6.3 |
1908.4 |
|
- X |
X X |
AWS D1.4 ACI 318: 26.6.4 |
- |
|
- | X | ACI 318: 17.8.2 | - |
X |
X |
ACI 318: 17.8.2.4 ACI 318: 17.8.2 |
- | |
|
- | X | ACI 318: Ch. 19,26.4.3, 26.4.4 | 1904.1, 1904.2,1908.2, 1908.3 |
X | - | ASTM C172 ASTM C31 ACI 318: 26.4, 26.12 |
1908.10 | |
|
X | - | ACI 318: 26.5 | 1908.6, 1908.7, 1908.8 |
|
- | X | ACI 318: 26.5.3-26.5.5 | 1908.9 |
|
X X |
- - |
ACI 318: 26.10 | - |
|
- | X | ACI 318: Ch. 26.8 | - |
- | X | ACI 318: 26.11.2 | - | |
|
- | X | ACI 318: 26.11.1.2(b) | - |
- Where applicable, see also Section 1705.12, Special inspections for seismic resistance.
- Specific requirements for special inspection shall be included in the research report for the anchor issued by an approved source in accordance with 17.8.2 in ACI 318, or other qualification procedures. Where specific requirements are not provided, special inspection requirements shall be specified by the registered design professional and shall be approved by the building official prior to the commencement of the work.
Special inspections
of welding and qualifications of special inspectors
for reinforcing bars shall be in accordance with the
requirements of AWS D1.4 for special inspection and of
AWS D1.4 for special inspector qualification.
In the absence of sufficient data
or documentation providing evidence of conformance to
quality standards for materials in Chapters 19 and 20 of
ACI 318, the building official shall require testing of materials
in accordance with the appropriate standards and criteria
for the material in Chapters 19 and 20 of ACI 318.
Special inspections and tests
of masonry construction shall be performed in accordance
with the quality assurance program requirements of TMS
402/ACI 530/ASCE 5 and TMS 602/ACI 530.1/ASCE 6.
Exception: Special inspections and tests shall not be
required for:
- Empirically designed masonry, glass unit masonry or masonry veneer designed in accordance with Section 2109, 2110 or Chapter 14, respectively, where they are part of a structure classified as Risk Category I, II or III.
- Masonry foundation walls constructed in accordance with Table 1807.1.6.3(1), 1807.1.6.3(2), 1807.1.6.3(3) or 1807.1.6.3(4).
- Masonry fireplaces, masonry heaters or masonry chimneys installed or constructed in accordance with Section 2111, 2112 or 2113, respectively.
Special inspections and tests for empirically designed
masonry, glass unit masonry or masonry veneer designed
in accordance with Section 2109, 2110 or Chapter 14,
respectively, where they are part of a structure classified
as Risk Category IV shall be performed in accordance with
TMS 402/ACI 530/ASCE 5, Level B Quality Assurance.
Special inspections of prefabricated
wood structural elements and assemblies shall be in
accordance with Section 1704.2.5. Special inspections of sitebuilt
assemblies shall be in accordance with this section.
High-load diaphragms
designed in accordance with Section 2306.2 shall be
installed with special inspections as indicated in Section
1704.2. The special inspector shall inspect the wood structural
panel sheathing to ascertain whether it is of the grade
and thickness shown on the approved construction documents.
Additionally, the special inspector must verify the
nominal size of framing members at adjoining panel
edges, the nail or staple diameter and length, the number
of fastener lines and that the spacing between fasteners in
each line and at edge margins agrees with the approved
construction documents.
Where a truss clear span is 60 feet (18288 mm) or greater, the special inspector shall verify that
the temporary installation restraint/bracing and the permanent
individual truss member restraint/bracing are
installed in accordance with the approved truss submittal
package.
Special inspections and tests of existing site soil
conditions, fill placement and load-bearing requirements
shall be performed in accordance with this section and Table
1705.6. The approved geotechnical report and the construction
documents prepared by the registered design professionals shall be used to determine compliance. During fill
placement, the special inspector shall verify that proper materials
and procedures are used in accordance with the provisions
of the approved geotechnical report.
Exception: Where Section 1803 does not require reporting
of materials and procedures for fill placement, the special
inspector shall verify that the in-place dry density of
the compacted fill is not less than 90 percent of the maximum
dry density at optimum moisture content determined
in accordance with ASTM D1557.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
|
- | X |
|
- | X |
|
- | X |
|
x | - |
|
- | X |
Special inspections and
tests shall be performed during installation of driven deep
foundation elements as specified in Table 1705.7. The
approved geotechnical report and the construction documents
prepared by the registered design professionals shall be used
to determine compliance.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
|
X | - |
|
X | - |
|
x | - |
|
x | - |
|
- | - |
|
- | - |
|
- | - |
Special inspections
and tests shall be performed during installation of cast-in-place
deep foundation elements as specified in Table 1705.8.
The approved geotechnical report and the construction documents
prepared by the registered design professionals shall
be used to determine compliance.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
|
X | - |
|
X | - |
|
- | - |
Continuous special inspections
shall be performed during installation of helical pile
foundations. The information recorded shall include installation
equipment used, pile dimensions, tip elevations, final
depth, final installation torque and other pertinent installation data as required by the registered design professional in
responsible charge. The approved geotechnical report and
the construction documents prepared by the registered design
professional shall be used to determine compliance.
Special inspections of fabricated
items shall be performed in accordance with Section
1704.2.5.
Special
inspections for wind resistance specified in Sections
1705.11.1 through 1705.11.3, unless exempted by the exceptions
to Section 1704.2, are required for buildings and structures
constructed in the following areas:
- In wind Exposure Category B, where Vasd as determined in accordance with Section 1609.3.1 is 120 miles per hour (52.8 m/sec) or greater.
- In wind Exposure Category C or D, where Vasd as determined in accordance with Section 1609.3.1 is 110 mph (49 m/sec) or greater.
Continuous special inspection
is required during field gluing operations of elements
of the main windforce-resisting system. Periodic special
inspection is required for nailing, bolting, anchoring and
other fastening of elements of the main windforce-resisting
system, including wood shear walls, wood diaphragms,
drag struts, braces and hold-downs.
Exception: Special inspections are not required for
wood shear walls, shear panels and diaphragms, including
nailing, bolting, anchoring and other fastening to
other elements of the main windforce-resisting system,
where the fastener spacing of the sheathing is more
than 4 inches (102 mm) on center.
Periodic special inspection is required for welding operations
of elements of the main windforce-resisting system.
Periodic special inspection is required for screw attachment,
bolting, anchoring and other fastening of elements
of the main windforce-resisting system, including shear
walls, braces, diaphragms, collectors (drag struts) and
hold-downs.
Exception: Special inspections are not required for
cold-formed steel light-frame shear walls and diaphragms,
including screwing, bolting, anchoring and
other fastening to components of the windforce resisting
system, where either of the following applies:
- The sheathing is gypsum board or fiberboard.
- The sheathing is wood structural panel or steel sheets on only one side of the shear wall, shear panel or diaphragm assembly and the fastener spacing of the sheathing is more than 4 inches (102 mm) on center (o.c.).
Periodic special
inspection is required for fastening of the following systems
and components:
- Roof covering, roof deck and roof framing connections.
- Exterior wall covering and wall connections to roof and floor diaphragms and framing.
Special
inspections for seismic resistance shall be required as specified
in Sections 1705.12.1 through 1705.12.9, unless
exempted by the exceptions of Section 1704.2.
Exception: The special inspections specified in Sections
1705.12.1 through 1705.12.9 are not required for structures
designed and constructed in accordance with one of
the following:
- The structure consists of light-frame construction; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.3.4, does not exceed 0.5; and the building height of the structure does not exceed 35 feet (10668 mm).
- The seismic force-resisting system of the structure consists of reinforced masonry or reinforced concrete; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.3.4, does not exceed 0.5; and the building height of the structure does not exceed 25 feet (7620 mm).
- The structure is a detached one-or two-family dwelling not exceeding two stories above grade plane and does not have any of the following horizontal or vertical irregularities in accordance with Section 12.3 of ASCE 7:
Special inspections for seismic
resistance shall be in accordance with Section
1705.12.1.1 or 1705.12.1.2, as applicable.
Special
inspections of structural steel in the seismic force-resisting
systems of buildings and structures assigned
to Seismic Design Category B, C, D, E or F shall be
performed in accordance with the quality assurance
requirements of AISC 341.
Exception: Special inspections are not required in
the seismic force-resisting systems of buildings and
structures assigned to Seismic Design Category B or
C that are not specifically detailed for seismic resistance,
with a response modification coefficient, R, of
3 or less, excluding cantilever column systems.
Special inspections
of structural steel elements in the seismic force-resisting
systems of buildings and structures assigned
to Seismic Design Category B, C, D, E or F other than
those covered in Section 1705.12.1.1, including struts,
collectors, chords and foundation elements, shall be
performed in accordance with the quality assurance
requirements of AISC 341.
Exception: Special inspections of structural steel
elements are not required in the seismic force-resisting
systems of buildings and structures assigned to
Seismic Design Category B or C with a response
modification coefficient, R, of 3 or less.
For the seismic force-resisting
systems of structures assigned to Seismic Design Category
C, D, E or F:
- Continuous special inspection shall be required during field gluing operations of elements of the seismic force-resisting system.
- Periodic special inspection shall be required for nailing, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including wood shear walls, wood diaphragms, drag struts, braces, shear panels and hold-downs.
Exception: Special inspections are not required for
wood shear walls, shear panels and diaphragms, including
nailing, bolting, anchoring and other fastening to
other elements of the seismic force-resisting system,
where the fastener spacing of the sheathing is more
than 4 inches (102 mm) on center.
For the seismic force-resisting systems of structures
assigned to Seismic Design Category C, D, E or F, periodic
special inspection shall be required:
- For welding operations of elements of the seismic force-resisting system; and
- For screw attachment, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including shear walls, braces, diaphragms, collectors (drag struts) and hold-downs.
Exception: Special inspections are not required for
cold-formed steel light-frame shear walls and diaphragms,
including screw installation, bolting, anchoring
and other fastening to components of the seismic
force-resisting system, where either of the following
applies:
- The sheathing is gypsum board or fiberboard.
- The sheathing is wood structural panel or steel sheets on only one side of the shear wall, shear panel or diaphragm assembly and the fastener spacing of the sheathing is more than 4 inches (102 mm) on center.
For structures
assigned to Seismic Design Category C, D, E or F, the special
inspector shall examine designated seismic systems
requiring seismic qualification in accordance with Section
13.2.2 of ASCE 7 and verify that the label, anchorage and
mounting conform to the certificate of compliance.
Periodic special
inspection is required for the erection and fastening of
exterior cladding, interior and exterior nonbearing walls
and interior and exterior veneer in structures assigned to
Seismic Design Category D, E or F.
Exception: Periodic special inspection is not required
for the following:
- Exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer 30 feet (9144 mm) or less in height above grade or walking surface.
- Exterior cladding and interior and exterior veneer weighing 5 psf (24.5 N/m2) or less.
- Interior nonbearing walls weighing 15 psf (73.5 N/m2) or less.
Periodic special inspection
is required for the anchorage of access floors in structures
assigned to Seismic Design Category D, E or F.
Periodic special inspection of plumbing, mechanical
and electrical components shall be required for the
following:
- Anchorage of electrical equipment for emergency and standby power systems in structures assigned to Seismic Design Category C, D, E or F.
- Anchorage of other electrical equipment in structures assigned to Seismic Design Category E or F.
- Installation and anchorage of piping systems designed to carry hazardous materials and their associated mechanical units in structures assigned to Seismic Design Category C, D, E or F.
- Installation and anchorage of ductwork designed to carry hazardous materials in structures assigned to Seismic Design Category C, D, E or F.
- Installation and anchorage of vibration isolation systems in structures assigned to Seismic Design Category C, D, E or F where the approved construction documents require a nominal clearance of 1/4 inch (6.4 mm) or less between the equipment support frame and restraint.
Periodic special inspection is
required for the anchorage of storage racks that are 8 feet
(2438 mm) or greater in height in structures assigned to
Seismic Design Category D, E or F.
Periodic special
inspection shall be provided for seismic isolation systems
in seismically isolated structures assigned to Seismic
Design Category B, C, D, E or F during the fabrication
and installation of isolator units and energy dissipation
devices.
Periodic special inspection shall be provided for
the installation of cold-formed steel special bolted moment
frames in the seismic force-resisting systems of structures
assigned to Seismic Design Category D, E or F.
Testing for seismic
resistance shall be required as specified in Sections 1705.13.1
through 1705.13.4, unless exempted from special inspections
by the exceptions of Section 1704.2.
Nondestructive testing for
seismic resistance shall be in accordance with Section
1705.13.1.1 or 1705.13.1.2, as applicable.
Nondestructive
testing of structural steel in the seismic force-resisting
systems of buildings and structures assigned
to Seismic Design Category B, C, D, E or F shall be
performed in accordance with the quality assurance
requirements of AISC 341.
Exception: Nondestructive testing is not required in
the seismic force-resisting systems of buildings and
structures assigned to Seismic Design Category B or
C that are not specifically detailed for seismic resistance,
with a response modification coefficient, R, of
3 or less, excluding cantilever column systems.
Nondestructive
testing of structural steel elements in the seismic force-resisting
systems of buildings and structures assigned
to Seismic Design Category B, C, D, E or F other than
those covered in Section 1705.13.1.1, including struts,
collectors, chords and foundation elements, shall be
performed in accordance with the quality assurance
requirements of AISC 341.
Exception: Nondestructive testing of structural
steel elements is not required in the seismic force-resisting
systems of buildings and structures
assigned to Seismic Design Category B or C with a
response modification coefficient, R, of 3 or less.
For structures
assigned to Seismic Design Category B, C, D, E or F,
where the requirements of Section 13.2.1 of ASCE 7 for
nonstructural components, supports or attachments are
met by seismic qualification as specified in Item 2 therein,
the registered design professional shall specify on the
approved construction documents the requirements for seismic qualification by analysis, testing or experience
data. Certificates of compliance for the seismic qualification
shall be submitted to the building official as specified
in Section 1704.5.
For structures
assigned to Seismic Design Category C, D, E or F and
with designated seismic systems that are subject to the
requirements of Section 13.2.2 of ASCE 7 for certification,
the registered design professional shall specify on
the approved construction documents the requirements to
be met by analysis, testing or experience data as specified
therein. Certificates of compliance documenting that the
requirements are met shall be submitted to the building
official as specified in Section 1704.5.
Seismic isolation
systems in seismically isolated structures assigned to Seismic
Design Category B, C, D, E or F shall be tested in
accordance with Section 17.8 of ASCE 7.
Special
inspections and tests of sprayed fire-resistant materials
applied to floor, roof and wall assemblies and structural
members shall be performed in accordance with Sections
1705.14.1 through 1705.14.6. Special inspections shall be
based on the fire-resistance design as designated in the
approved construction documents. The tests set forth in this
section shall be based on samplings from specific floor, roof
and wall assemblies and structural members. Special inspections
and tests shall be performed after the rough installation
of electrical, automatic sprinkler, mechanical and plumbing
systems and suspension systems for ceilings, where applicable.
The special
inspections and tests shall include the following to demonstrate
compliance with the listing and the fire-resistance
rating:
- Condition of substrates.
- Thickness of application.
- Density in pounds per cubic foot (kg/m3).
- Bond strength adhesion/cohesion.
- Condition of finished application.
The surfaces shall be prepared in accordance with the
approved fire-resistance design and the written instructions
of approved manufacturers. The prepared surface of
structural members to be sprayed shall be inspected by the
special inspector before the application of the sprayed fireresistant
material.
The substrate shall have a
minimum ambient temperature before and after application
as specified in the written instructions of approved
manufacturers. The area for application shall be ventilated
during and after application as required by the written
instructions of approved manufacturers.
No more than 10 percent of
the thickness measurements of the sprayed fire-resistant
materials applied to floor, roof and wall assemblies and structural members shall be less than the thickness
required by the approved fire-resistance design, but in no
case less than the minimum allowable thickness required
by Section 1705.14.4.1.
For
design thicknesses 1 inch (25 mm) or greater, the minimum
allowable individual thickness shall be the design
thickness minus 1/4 inch (6.4 mm). For design thicknesses
less than 1 inch (25 mm), the minimum allowable
individual thickness shall be the design thickness
minus 25 percent. Thickness shall be determined in
accordance with ASTM E605. Samples of the sprayed
fire-resistant materials shall be selected in accordance
with Sections 1705.14.4.2 and 1705.14.4.3.
Thickness measurements
shall be selected from a square area, 12 inches by
12 inches (305 mm by 305 mm) in size. A minimum of
four measurements shall be made, located symmetrically
within the square area.
Thickness measurements
shall be selected from a square area, 12 inches by
12 inches (305 mm by 305 mm) in size. A minimum of
four measurements shall be made, located symmetrically
within the square area, including one each of the
following: valley, crest and sides. The average of the
measurements shall be reported.
The thickness
of the sprayed fire-resistant material applied to structural
members shall be determined in accordance with
ASTM E605. Thickness testing shall be performed on
not less than 25 percent of the structural members on
each floor.
At beams and
girders thickness measurements shall be made at nine
locations around the beam or girder at each end of a 12-
inch (305 mm) length.
At joists and
trusses, thickness measurements shall be made at seven
locations around the joist or truss at each end of a 12-
inch (305 mm) length.
At wide-flanged
columns, thickness measurements shall be
made at 12 locations around the column at each end of
a 12-inch (305 mm) length.
At hollow structural section and pipe columns,
thickness measurements shall be made at a minimum
of four locations around the column at each end
of a 12-inch (305 mm) length.
The density of the sprayed fire-resistant
material shall not be less than the density specified
in the approved fire-resistance design. Density of the
sprayed fire-resistant material shall be determined in
accordance with ASTM E605. The test samples for determining
the density of the sprayed fire-resistant materials
shall be selected as follows:
- From each floor, roof and wall assembly at the rate of not less than one sample for every 2,500 square feet (232 m2) or portion thereof of the sprayed area in each story.
- From beams, girders, trusses and columns at the rate of not less than one sample for each type of structural member for each 2,500 square feet (232 m2) of floor area or portion thereof in each story.
The cohesive/adhesive
bond strength of the cured sprayed fire-resistant material
applied to floor, roof and wall assemblies and structural
members shall not be less than 150 pounds per square foot
(psf) (7.18 kN/m2). The cohesive/adhesive bond strength
shall be determined in accordance with the field test specified
in ASTM E736 by testing in-place samples of the
sprayed fire-resistant material selected in accordance with
Sections 1705.14.6.1 through 1705.14.6.3.
The test samples for determining the cohesive/adhesive
bond strength of the sprayed fire-resistant materials
shall be selected from each floor, roof and wall assembly
at the rate of not less than one sample for every
2,500 square feet (232 m2) of the sprayed area, or portion
thereof, in each story.
The test samples
for determining the cohesive/adhesive bond
strength of the sprayed fire-resistant materials shall be
selected from beams, girders, trusses, columns and
other structural members at the rate of not less than one
sample for each type of structural member for each
2,500 square feet (232 m2) of floor area or portion
thereof in each story.
Bond tests to qualify a primer, paint or
encapsulant shall be conducted when the sprayed fire-resistant
material is applied to a primed, painted or
encapsulated surface for which acceptable bondstrength
performance between these coatings and the
fire-resistant material has not been determined. A bonding
agent approved by the SFRM manufacturer shall be
applied to a primed, painted or encapsulated surface
where the bond strengths are found to be less than
required values.
Special inspections and tests for mastic and intumescent
fire-resistant coatings applied to structural elements and
decks shall be performed in accordance with AWCI 12-B.
Special inspections and tests shall be based on the fire-resistance
design as designated in the approved construction documents.
Special inspections shall be required for all EIFS applications.
Exceptions:
- Special inspections shall not be required for EIFS applications installed over a water-resistive barrier with a means of draining moisture to the exterior.
- Special inspections shall not be required for EIFS applications installed over masonry or concrete walls.
A water-resistive
barrier coating complying with ASTM E2570
requires special inspection of the water-resistive barrier
coating when installed over a sheathing substrate.
In
high-rise buildings or in buildings assigned to Risk Category
III or IV, special inspections for through-penetrations, membrane
penetration firestops, fire-resistant joint systems and
perimeter fire barrier systems that are tested and listed in
accordance with Sections 714.3.1.2, 714.4.2, 715.3 and
715.4 shall be in accordance with Section 1705.17.1 or
1705.17.2.
Inspections of penetration
firestop systems that are tested and listed in accordance
with Sections 714.3.1.2 and 714.4.2 shall be
conducted by an approved agency in accordance with
ASTM E2174.
Inspection
of fire-resistant joint systems that are tested and listed in
accordance with Sections 715.3 and 715.4 shall be conducted
by an approved agency in accordance with ASTM
E2393.
Smoke control systems
shall be tested by a special inspector.
The test scope shall be as
follows:
- During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location.
- Prior to occupancy and after sufficient completion for the purposes of pressure difference testing, flow measurements and detection and control verification.
Approved agencies for
smoke control testing shall have expertise in fire protection
engineering, mechanical engineering and certification
as air balancers.
The design strengths
and permissible stresses of any structural material that are
identified by a manufacturer's designation as to manufacture
and grade by mill tests, or the strength and stress grade is otherwise
confirmed to the satisfaction of the building official, shall conform to the specifications and methods of design of
accepted engineering practice or the approved rules in the
absence of applicable standards.
For materials that are not specific ally
provided for in this code, the design strengths and permissible
stresses shall be established by tests as provided for in Section
1707.
In the absence of approved rules or other
approved standards, the building official shall make, or cause
to be made, the necessary tests and investigations; or the
building official shall accept duly authenticated reports from
approved agencies in respect to the quality and manner of use
of new materials or assemblies as provided for in Section
104.11. The cost of all tests and other investigations required
under the provisions of this code shall be borne by the owner
or the owner's authorized agent.
Whenever there is a reasonable doubt as to
the stability or load-bearing capacity of a completed building,
structure or portion thereof for the expected loads, an engineering
assessment shall be required. The engineering assessment
shall involve either a structural analysis or an in-situ load test, or both. The structural analysis shall be based on
actual material properties and other as-built conditions that
affect stability or load-bearing capacity, and shall be conducted
in accordance with the applicable design standard. If
the structural assessment determines that the load-bearing
capacity is less than that required by the code, load tests shall
be conducted in accordance with Section 1708.2. If the building,
structure or portion thereof is found to have inadequate
stability or load-bearing capacity for the expected loads,
modifications to ensure structural adequacy or the removal of
the inadequate construction shall be required.
Structural components and assemblies
shall be tested in accordance with the appropriate referenced
standards. In the absence of a standard that contains an
applicable load test procedure, the test procedure shall be
developed by a registered design professional and approved.
The test procedure shall simulate loads and conditions of
application that the completed structure or portion thereof
will be subjected to in normal use.
In-situ load tests shall be conducted
in accordance with Section 1708.3.1 or 1708.3.2 and
shall be supervised by a registered design professional. The
test shall simulate the applicable loading conditions specified
in Chapter 16 as necessary to address the concerns regarding
structural stability of the building, structure or portion
thereof.
Where a referenced
standard contains an applicable load test procedure
and acceptance criteria, the test procedure and acceptance criteria in the standard shall apply. In the absence of specific
load factors or acceptance criteria, the load factors
and acceptance criteria in Section 1708.3.2 shall apply.
In the
absence of applicable load test procedures contained
within a standard referenced by this code or acceptance
criteria for a specific material or method of construction,
such existing structure shall be subjected to a test procedure
developed by a registered design professional that
simulates applicable loading and deformation conditions.
For components that are not a part of the seismic force-resisting
system, at a minimum the test load shall be equal
to the specified factored design loads. For materials such
as wood that have strengths that are dependent on load
duration, the test load shall be adjusted to account for the
difference in load duration of the test compared to the
expected duration of the design loads being considered.
For statically loaded components, the test load shall be left
in place for a period of 24 hours. For components that
carry dynamic loads (e.g., machine supports or fall arrest
anchors), the load shall be left in place for a period consistent
with the component's actual function. The structure
shall be considered to have successfully met the test
requirements where the following criteria are satisfied:
- Under the design load, the deflection shall not exceed the limitations specified in Section 1604.3.
- Within 24 hours after removal of the test load, the structure shall have recovered not less than 75 percent of the maximum deflection.
- During and immediately after the test, the structure shall not show evidence of failure.
Where proposed construction is not capable
of being designed by approved engineering analysis, or
where proposed construction design method does not comply
with the applicable material design standard, the system of
construction or the structural unit and the connections shall
be subjected to the tests prescribed in Section 1709. The
building official shall accept certified reports of such tests
conducted by an approved testing agency, provided that such
tests meet the requirements of this code and approved procedures.
Where specific load
test procedures, load factors and acceptance criteria are
included in the applicable referenced standards, such test procedures,
load factors and acceptance criteria shall apply. In
the absence of specific test procedures, load factors or acceptance
criteria, the corresponding provisions in Section 1709.3
shall apply.
Where load test
procedures are not specified in the applicable referenced standards,
the load-bearing and deformation capacity of structural
components and assemblies shall be determined on the basis
of a test procedure developed by a registered design professional
that simulates applicable loading and deformation conditions. For components and assemblies that are not a part of
the seismic force-resisting system, the test shall be as specified
in Section 1709.3.1. Load tests shall simulate the applicable
loading conditions specified in Chapter 16.
The test assembly shall be subjected
to an increasing superimposed load equal to not less
than two times the superimposed design load. The test
load shall be left in place for a period of 24 hours. The
tested assembly shall be considered to have successfully
met the test requirements if the assembly recovers not less
than 75 percent of the maximum deflection within 24
hours after the removal of the test load. The test assembly
shall then be reloaded and subjected to an increasing
superimposed load until either structural failure occurs or
the superimposed load is equal to two and one-half times
the load at which the deflection limitations specified in
Section 1709.3.2 were reached, or the load is equal to two
and one-half times the superimposed design load. In the
case of structural components and assemblies for which
deflection limitations are not specified in Section
1709.3.2, the test specimen shall be subjected to an
increasing superimposed load until structural failure
occurs or the load is equal to two and one-half times the
desired superimposed design load. The allowable superimposed
design load shall be taken as the lesser of:
- The load at the deflection limitation given in Section 1709.3.2.
- The failure load divided by 2.5.
- The maximum load applied divided by 2.5.
The deflection of structural members
under the design load shall not exceed the limitations in
Section 1604.3.
Load-bearing wall
and partition assemblies shall sustain the test load both with
and without window framing. The test load shall include all
design load components. Wall and partition assemblies shall
be tested both with and without door and window framing.
The design
pressure rating of exterior windows and doors in buildings
shall be determined in accordance with Section 1709.5.1 or
1709.5.2. For the purposes of this section, the required design
pressure shall be determined using the allowable stress design
load combinations of Section 1605.3.
Exception: Structural wind load design pressures for window
units smaller than the size tested in accordance with
Section 1709.5.1 or 1709.5.2 shall be permitted to be
higher than the design value of the tested unit provided
such higher pressures are determined by accepted engineering
analysis. All components of the small unit shall be
the same as the tested unit. Where such calculated design
pressures are used, they shall be validated by an additional
test of the window unit having the highest allowable
design pressure.
Exterior windows
and sliding doors shall be tested and labeled as conforming
to AAMA/WDMA/CSA101/I.S.2/A440. The label
shall state the name of the manufacturer, the approved labeling agency and the product designation as specified in
AAMA/WDMA/CSA101/I.S.2/A440. Exterior side-hinged
doors shall be tested and labeled as conforming to
AAMA/WDMA/CSA101/I.S.2/A440 or comply with Section
1709.5.2. Products tested and labeled as conforming
to AAMA/WDMA/CSA101/I.S.2/A440 shall not be subject
to the requirements of Sections 2403.2 and 2403.3.
Exterior window and
door assemblies shall be tested in accordance with ASTM
E330. Structural performance of garage doors and rolling
doors shall be determined in accordance with either
ASTM E330 or ANSI/DASMA 108, and shall meet the
acceptance criteria of ANSI/DASMA 108. Exterior window
and door assemblies containing glass shall comply
with Section 2403. The design pressure for testing shall be
calculated in accordance with Chapter 16. Each assembly
shall be tested for 10 seconds at a load equal to 1.5 times
the design pressure.
Skylights and sloped
glazing shall comply with the requirements of Chapter 24.
Test specimens and construction
shall be representative of the materials, workmanship and
details normally used in practice. The properties of the materials
used to construct the test assembly shall be determined
on the basis of tests on samples taken from the load assembly
or on representative samples of the materials used to construct
the load test assembly. Required tests shall be conducted
or witnessed by an approved agency.