International Energy Conservation Code 2015 (IECC 2015)

IECC — Commercial Provisions

IECC — Residential Provisions

Heads up: There are no amended sections in this chapter.

Part 1 — Scope and Application

C101.1 Title

AMENDMENT
This section has been amended by the state, county, or city.
This code shall be known and cited as the "Michigan Energy Code." It is referred to herein as "this code."

R 408.31088a
This code applies to commercial buildings and the buildings' sites and associated systems and equipment.

C101.3 Intent

AMENDMENT
This section has been amended by the state, county, or city.
This code shall regulate the design and construction of buildings for the use and conservation of energy over the life of each building. This code is intended to provide flexibility to permit the use of innovative approaches and techniques to achieve this objective. This code is not intended to abridge safety, health or environmental requirements contained in other applicable codes or ordinances.
Where, in any specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern.
Where a building includes both residential and commercial occupancies, each occupancy shall be separately considered and meet the applicable provisions of IECC—Commercial Provisions or IECC—Residential Provisions.
Residential buildings shall meet the provisions of IECC—Residential Provisions. Commercial buildings shall meet the provisions of IECC—Commercial Provisions.
The code official shall be permitted to approve specific computer software, worksheets, compliance manuals and other similar materials that meet the intent of this code.
This code is not intended to prevent the use of any material, method of construction, design or insulating system not specifically prescribed herein, provided that such construction, design or insulating system has been approved by the code official as meeting the intent of this code.

C102.1.1 Above Code Programs

AMENDMENT
This section has been amended by the state, county, or city.
The state construction code commission may evaluate and approve a national, state, or local energy efficiency program to exceed the energy efficiency required by this code. Buildings approved in writing by an energy efficiency program, such as ICC 700-2012 "silver" or energy star version 3 (rev. 07), shall be considered in compliance with this code. The requirements identified as "mandatory" in chapter 4 shall be met.

R 408.31092

Part 2 — Administration and Enforcement

C103.1 General Submittal Documents

AMENDMENT
This section has been amended by the state, county, or city.
Construction documents, special inspection and structural programs, and other data shall meet both of the following requirements:
  1. Be submitted in 1 or more sets with each application for a permit.
  2. Be prepared by, or under the direct supervision of, a registered design professional when required by Occupational Code, 1980 PA 299, MCL 339.101 to 339.2919.
Where special conditions exist, the building official may require additional construction documents to be prepared by a registered design professional.

R 408.31092
Construction documents shall be drawn to scale upon suitable material. Electronic media documents are permitted to be submitted where approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed, and show in sufficient detail pertinent data and features of the building, systems and equipment as herein governed. Details shall include, but are not limited to, the following as applicable:
  1. Insulation materials and their R-values.
  2. Fenestration U-factors and solar heat gain coefficients (SHGCs).
  3. Area-weighted U-factor and solar heat gain coefficient (SHGC) calculations.
  4. Mechanical system design criteria.
  5. Mechanical and service water heating system and equipment types, sizes and efficiencies.
  6. Economizer description.
  7. Equipment and system controls.
  8. Fan motor horsepower (hp) and controls.
  9. Duct sealing, duct and pipe insulation and location.
  10. Lighting fixture schedule with wattage and control narrative.
  11. Location of daylight zones on floor plans.
  12. Air sealing details.
The building's thermal envelope shall be represented on the construction drawings.
The code official shall examine or cause to be examined the accompanying construction documents and shall ascertain whether the construction indicated and described is in accordance with the requirements of this code and other pertinent laws or ordinances. The code official is authorized to utilize a registered design professional, or other approved entity not affiliated with the building design or construction, in conducting the review of the plans and specifications for compliance with the code.
When the code official issues a permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "Reviewed for Code Compliance. " Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.

One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, kept at the site of work and shall be open to inspection by the code official or a duly authorized representative.
This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.
The code official shall have the authority to issue a permit for the construction of part of an energy conservation system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holders of such permit shall proceed at their own risk without assurance that the permit for the entire energy conservation system will be granted.
Changes made during construction that are not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents.
One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws.
Construction or work for which a permit is required shall be subject to inspection by the code official or his or her designated agent, and such construction or work shall remain accessible and exposed for inspection purposes until approved. It shall be the duty of the permit applicant to cause the work to remain accessible and exposed for inspection purposes. Neither the code official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of any material, product, system or building component required to allow inspection to validate compliance with this code.

C104.2 Required Energy Efficiency Inspections

AMENDMENT
This section has been amended by the state, county, or city.
The code official or his or her designated agent, upon notification, shall make the inspections set forth in Sections C104.2.1 through C104.2.6.

R 408.31092a
Inspections associated with footings and foundations shall verify compliance with the code as to R-value, location, thickness, depth of burial and protection of insulation as required by the code and approved plans and specifications.
Inspections at framing and rough-in shall be made before application of interior finish and shall verify compliance with the code as to types of insulation and corresponding R-values and their correct location and proper installation; fenestration properties (U-factor, SHGC and VT) and proper installation; and air leakage controls as required by the code and approved plans and specifications.
Inspections at plumbing rough-in shall verify compliance as required by the code and approved plans and specifications as to types of insulation and corresponding R-values and protection; required controls; and required heat traps.
Inspections at mechanical rough-in shall verify compliance as required by the code and approved plans and specifications as to installed HVAC equipment type and size; required controls, system insulation and corresponding R-value; system and damper air leakage; and required energy recovery and economizers.
Inspections at electrical rough-in shall verify compliance as required by the code and approved plans and specifications as to installed lighting systems, components and controls; and installation of an electric meter for each dwelling unit.
The building shall have a final inspection and shall not be occupied until approved. The final inspection shall include verification of the installation and proper operation of all required building controls, and documentation verifying activities associated with required building commissioning have been conducted and findings of noncompliance corrected. Buildings, or portions thereof, shall not be considered for a final inspection until the code official has received a letter of transmittal from the building owner acknowledging that the building owner has received the Preliminary Commissioning Report as required in Section C408.2.4.
A building shall be reinspected when determined necessary by the code official.
The code official is authorized to accept reports of third-party inspection agencies not affiliated with the building design or construction, provided such agencies are approved as to qualifications and reliability relevant to the building components and systems they are inspecting.
It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made to achieve compliance with this code. The work or installation shall then be resubmitted to the code official for inspection and testing.
After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official.
The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the certificate is issued in error, or on the basis of incorrect information supplied, or where it is determined that the building or structure, premise, or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.

C104.8 Administrative Requirements

AMENDMENT
This section has been amended by the state, county, or city.
Administrative requirements relating to permits, enforcement, interpretations, and appeals shall be pursuant to the Stille-DeRossett-Hale Single State Construction Code Act, 1972 PA 230, MCL 125.1501 to 125.1531.

R 408.31090
If a portion of this code is held to be illegal or void, such a decision shall not affect the validity of the remainder of this code.
The codes and standards referenced in this code shall be those listed in Chapter 6, and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections C106.1.1 and C106.1.2.
Where conflicts occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply.
Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the referenced code or standard.
References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.

C107.1 Payment of Fees

AMENDMENT
This section has been amended by the state, county, or city.
The fees prescribed by the Stille-DeRossett-Hale Single State Construction Code Act, 1972 PA 230, MCL 125.1501 to 125.1531 shall be paid to the enforcing agency of the jurisdiction before a permit to begin work for new construction, alteration, removal, demolition, or other building operation may be issued. In addition, an amendment to a permit requiring an additional fee shall not be approved until the additional fee has been paid.

R 408.31093

C107.2 Schedule of Permit Fees

AMENDMENT
This section has been amended by the state, county, or city.

C107.3 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended by the state, county, or city.

C107.4 Related Fees

AMENDMENT
This section has been amended by the state, county, or city.

C107.5 Refunds

AMENDMENT
This section has been amended by the state, county, or city.

C108.1 Authority Stop Work Orders

AMENDMENT
This section has been amended by the state, county, or city.
Notice shall be in accordance with the Stille-DeRossett-Hale Single State Construction Code Act, 1972 PA 203, MCL 125.1501 to 125.1531. A person who is served with a stop work order, except for the work that the person is directed to perform to remove a violation or unsafe condition, is subject to the penalty provisions prescribed by the act.

R 408.31094

C108.2 Issuance

AMENDMENT
This section has been amended by the state, county, or city.

C108.3 Emergencies

AMENDMENT
This section has been amended by the state, county, or city.

C108.4 Failure to Comply

AMENDMENT
This section has been amended by the state, county, or city.

C109.1 General Means of Appeal

AMENDMENT
This section has been amended by the state, county, or city.
  1. An interested person may appeal a decision of the enforcing agency to the board of appeals in accordance with the act.
  2. The decision of a local board of appeals may be appealed to the construction code commission in accordance with the act and time frames contained in the act.
R 408.31095
An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply or an equally good or better form of construction is proposed. The board shall not have authority to waive requirements of this code.

C109.3 Qualifications

AMENDMENT
This section has been amended by the state, county, or city.
The board of appeals shall consist of members who are qualified in accordance with the act.

R 408.31060c
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING