52.1* General

AMENDMENT
This section has been amended at the state or city level.
A52.1 Chapter 52 applies to the installation of battery storage systems. These systems can be installed within new or existing buildings, or as a stand-alone application without a building structure. If the battery storage system is installed within a building or on a foundation, the fire department should work closely with the building department to ensure all applicable regulations of the building and fire codes are satisfied. Attention should be given to reviewing the risk analysis and considering means of responding to fire or other emergency incidents in battery storage system buildings or sites.

52.1.1

AMENDMENT
This section has been amended at the state or city level.
Energy storage systems shall comply with Chapter 52

52.1.2 Permits

AMENDMENT
This section has been amended at the state or city level.

52.1.2.1

AMENDMENT
This section has been amended at the state or city level.
Permits, where required, shall comply with Section 1.12.

52.1.2.2

AMENDMENT
This section has been amended at the state or city level.
Prior to installation, plans shall be submitted and approved by the AHJ.

52.2 Permits

AMENDMENT
This section has been amended at the state or city level.

52.2.1

AMENDMENT
This section has been amended at the state or city level.

52.2.2

AMENDMENT
This section has been amended at the state or city level.

52.2* Lead-Acid and Nickel-Cadmium Batteries

AMENDMENT
This section has been amended at the state or city level.
A52.2 The requirements in Section 52.2 supersede all the hazardous material designations, permits, and requirements in Chapter 60.

52.2.1 General

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems having an electrolyte capacity of more than 100 gal. (378.5 L) in sprinklered buildings or 50 gal. (189.3 L) in unsprinklered buildings for flooded lead-acid, nickel-cadmium, and valve-regulated lead-acid (VRLA) batteries used for facility standby power, emergency power, or uninterrupted power supplies shall be in accordance with Section 52.2 and Table 52.2.1.
Table 52.2.1 Battery Requirements
Requirement Nonrecombinant Batteries Recombinant Batteries
Flooded Lead-Acid Flooded Nickel-Cadmium (Ni-Cd) Valve-Regulated Lead-Acid (VRLA)
Safety caps Venting caps Venting caps Self-resealing flame-arresting caps
Thermal runaway management Not required Not required Required
Spill control Required Required Not required
Neutralization Required Required Required
Ventilation Required Required Required
Signage Required Required Required
Seismic control Required Required Required
Fire detection Required Required Required

52.2.2 Safety Features

AMENDMENT
This section has been amended at the state or city level.

52.2.2.1 Safety Venting

AMENDMENT
This section has been amended at the state or city level.
Batteries shall be provided with safety venting caps per 52.2.2.1.1 and 52.2.2.1.2.

52.2.2.1.1 Nonrecombinant Batteries

AMENDMENT
This section has been amended at the state or city level.
Vented lead-acid and nickel-cadmium shall be provided with safety venting caps.

52.2.2.1.2 Recombinant Batteries

AMENDMENT
This section has been amended at the state or city level.
VRLA shall be equipped with self-resealing flame-arresting safety vents.

52.2.2.2 Thermal Runaway

AMENDMENT
This section has been amended at the state or city level.
VRLA systems shall be provided with a listed device or other approved method to preclude, detect, and control thermal runaway.

52.2.2.3 Location and Occupancy Separation

AMENDMENT
This section has been amended at the state or city level.

52.2.2.3.1

AMENDMENT
This section has been amended at the state or city level.
Battery systems shall be permitted in the same room as the equipment that they support.

52.2.2.3.2

AMENDMENT
This section has been amended at the state or city level.
Battery systems shall be housed in a noncombustible, locked cabinet or other enclosure to prevent access by unauthorized personnel, unless located in a separate equipment room accessible only to authorized personnel.

52.2.2.3.3

AMENDMENT
This section has been amended at the state or city level.
In other than assembly, educational, detention, and correction facilities; health care, ambulatory health care, and day care centers; and residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a one hour fire barrier.

52.2.2.3.4

AMENDMENT
This section has been amended at the state or city level.
In assembly, educational, detention and correction facilities; health care, ambulatory health care, and day care centers; and, residential board and care and residential occupancies, battery systems shall be located in a room separated from other portions of the building by a minimum of a two-hour fire barrier.

52.2.2.4 Spill Control

AMENDMENT
This section has been amended at the state or city level.

52.2.2.4.1

AMENDMENT
This section has been amended at the state or city level.
Rooms, buildings, or areas containing free-flowing liquid electrolyte in individual vessels having a capacity of more than 55 gal. (208 L) or multiple vessels having an aggregate capacity exceeding 1000 gal. (3785 L) shall be provided with spill control to prevent the flow of liquids to adjoining areas.

52.2.2.4.2*

AMENDMENT
This section has been amended at the state or city level.
An approved method and materials for the control of a spill of electrolyte shall be provided that will be capable of controlling a spill from the single largest vessel.

A52.2.2.4.2 Methods of achieving this protection can include, but are not limited to, the following:
  1. Liquidtight sloped or recessed floors in indoor locations or similar areas in outdoor locations
  2. Liquidtight floors in indoor locations or similar areas in outdoor locations provided with liquidtight raised or recessed sills or dikes
  3. Sumps and collection systems
  4. Spill containment systems such as that described in A52.2.2.5.1.

52.2.2.4.3

AMENDMENT
This section has been amended at the state or city level.
VRLA batteries with immobilized electrolyte shall not require spill control.

52.2.2.5 Neutralization

AMENDMENT
This section has been amended at the state or city level.

52.2.2.5.1*

AMENDMENT
This section has been amended at the state or city level.
An approved method to neutralize spilled electrolyte shall be provided.

A52.2.2.5.1 One method to determine compliance with the neutralization requirements of this subsection is found in Underwriters Laboratories Subject 2436, Outline of Investigation for Spill Containment for Stationary Lead Acid Battery Systems. Subject 2436 investigates the liquid tightness, level of electrolyte absorption, pH neutralization capability, and flame spread resistance of spill containment systems.

52.2.2.5.2

AMENDMENT
This section has been amended at the state or city level.
For VRLA batteries, the method shall be capable of neutralizing a spill from the largest battery to a pH between 7.0 and 9.0.

52.2.2.6* Ventilation

AMENDMENT
This section has been amended at the state or city level.
For flooded lead-acid, flooded nickel-cadmium, and VRLA batteries, ventilation shall be provided for rooms and cabinets in accordance with the Mechanical Code and one of the following:
  1. A52.2.2.6 Information on battery room ventilation can be found in IEEE 1635/ASHRAE 21, Guide to Battery Room Ventilation and Thermal Management.
    1. The ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0% of the total volume of the room during the worst-case event of simultaneous "boost" charging of all the batteries, in accordance with nationally recognized standards.
    2. Continuous ventilation shall be provided at a rate of not less than 1 ft.3/min/ft.2 (5.1 L/sec/m2) of floor area of the room or cabinet.

52.2.2.7 Environment

AMENDMENT
This section has been amended at the state or city level.
The battery environment shall be controlled or analyzed to maintain temperature in a safe operating range for the specific battery technology used.

52.2.2.8 Signs

AMENDMENT
This section has been amended at the state or city level.

52.2.2.8.1

AMENDMENT
This section has been amended at the state or city level.
Doors or accesses into the following shall be provided with approved signs:
  1. Battery storage buildings;
  2. Rooms containing stationary storage battery systems; and
  3. Other areas containing stationary storage battery systems.

52.2.2.8.2

AMENDMENT
This section has been amended at the state or city level.
For rooms that contain VRLA batteries, the signs required by 52.2.2.8.1 shall state the following:
  1. This room contains:
    1. Stationary storage battery systems
    2. Energized electrical circuits

52.2.2.8.3

AMENDMENT
This section has been amended at the state or city level.
For rooms that contain flooded lead-acid or flooded Ni-Cd batteries, the signs required by 52.2.2.8.1 shall state the following:
  1. This room contains:
    1. Stationary storage battery systems
    2. Energized electrical circuits
    3. Corrosive battery electrolyte

52.2.2.8.4

AMENDMENT
This section has been amended at the state or city level.
Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number of the system and electrical rating (i.e., voltage and current) of the contained battery system.

52.2.2.8.5

AMENDMENT
This section has been amended at the state or city level.
Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

52.2.2.9 Seismic Protection

AMENDMENT
This section has been amended at the state or city level.
Battery systems shall be seismically braced in accordance with the building code.

52.2.2.10 Smoke Detection

AMENDMENT
This section has been amended at the state or city level.
An approved automatic smoke detection system shall be installed in rooms containing stationary battery storage systems in accordance with NFPA 72.

52.2.2.10.1

AMENDMENT
This section has been amended at the state or city level.
The required automatic smoke detection system shall be supervised by an approved central, proprietary, or remote station service or a local alarm that will give an audible signal at a constantly attended location.

52.2.2.10.2

AMENDMENT
This section has been amended at the state or city level.
Normally unoccupied, stand-alone telecommunications structures with a gross floor area of less than 1,500 ft.2 (140 m2) shall not be required to have the detection as indicated in 52.2.2.10.

52.3 Safety Features

AMENDMENT
This section has been amended at the state or city level.

52.3.1 Safety Venting

AMENDMENT
This section has been amended at the state or city level.

52.3.1.1 Nonrecombinant Batteries

AMENDMENT
This section has been amended at the state or city level.

52.3.1.2 Recombinant Batteries

AMENDMENT
This section has been amended at the state or city level.

52.3.1.3

AMENDMENT
This section has been amended at the state or city level.

52.3.2 Thermal Runaway

AMENDMENT
This section has been amended at the state or city level.

52.3.3 Location and Occupancy Separation

AMENDMENT
This section has been amended at the state or city level.

52.3.3.1

AMENDMENT
This section has been amended at the state or city level.

52.3.3.2

AMENDMENT
This section has been amended at the state or city level.

52.3.3.3

AMENDMENT
This section has been amended at the state or city level.

52.3.3.4

AMENDMENT
This section has been amended at the state or city level.

52.3.4 Spill Control

AMENDMENT
This section has been amended at the state or city level.

52.3.4.1

AMENDMENT
This section has been amended at the state or city level.

52.3.4.2*

AMENDMENT
This section has been amended at the state or city level.

52.3.4.3

AMENDMENT
This section has been amended at the state or city level.

52.3.5 Neutralization

AMENDMENT
This section has been amended at the state or city level.

52.3.5.1*

AMENDMENT
This section has been amended at the state or city level.

52.3.5.2

AMENDMENT
This section has been amended at the state or city level.

52.3.5.3

AMENDMENT
This section has been amended at the state or city level.

52.3.6* Ventilation

AMENDMENT
This section has been amended at the state or city level.

52.3.6.1

AMENDMENT
This section has been amended at the state or city level.

52.3.7 Environment

AMENDMENT
This section has been amended at the state or city level.

52.3.8 Signs

AMENDMENT
This section has been amended at the state or city level.

52.3.8.1

AMENDMENT
This section has been amended at the state or city level.

52.3.8.2

AMENDMENT
This section has been amended at the state or city level.

52.3.8.3

AMENDMENT
This section has been amended at the state or city level.

52.3.8.4

AMENDMENT
This section has been amended at the state or city level.

52.3.8.5

AMENDMENT
This section has been amended at the state or city level.

52.3.9 Seismic Protection

AMENDMENT
This section has been amended at the state or city level.

52.3.10 Smoke Detection

AMENDMENT
This section has been amended at the state or city level.

52.3* Additional Battery Technologies

AMENDMENT
This section has been amended at the state or city level.
A52.3 The requirements in Section 52.3 supersede all the hazardous material designations, permits, and requirements in Chapter 60.

52.3.1 General

AMENDMENT
This section has been amended at the state or city level.
Energy storage systems having a capacity greater than the quantities listed in Table 52.3.1 shall be in accordance with Section 52.3 and where used as a legally required emergency or standby power system, shall also comply with 11.7.3.
Table 52.3.1 Energy Storage System Threshold Quantities
Type Capacitya
Lithium batteries, all types 20 KWh (18.0 Mega joules)
Sodium batteries, all types 20 KWh (18.0 Mega joules)c
Flow batteriesb 20 KWh (18.0 Mega joules)
Other battery technologies 10 KWh (10.8 Mega joules)
Capacitors 70 KWh (25.2 Mega joules)
Notes:
  1. For batteries and capacitors rated in Amp-Hours, KWh should equal rated voltage times amp-hour rating divided by 1000.
  2. Includes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies.
  3. Or 70 KWh (25.2 Mega joules) for sodium-ion technologies.

52.3.2* Stationary Storage Battery Systems

AMENDMENT
This section has been amended at the state or city level.

A52.3.2 This section covers stationary battery systems that are typically used for facility standby power, emergency power, uninterrupted power supplies, and load/shedding/load balancing applications.

Stationary storage battery systems that exceed the amounts specified in Table 52.3.1 pose potential hazards that are significant enough to require compliance with the requirements in Chapter 52. It is not the intent of Chapter 52 to regulate equipment with integral standby power systems below the amounts in Table 52.3.1, such as emergency lighting units, fire alarm control units, and other appliances and equipment.

52.3.2.1 Location and Occupancy Separation

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems shall be located and constructed in accordance with this section.

52.3.2.1.1

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems shall be housed in a noncombustible, locked cabinet or other enclosure to prevent access by unauthorized personnel, unless located in a separate equipment room accessible only to authorized personnel.

52.3.2.1.2 Location

AMENDMENT
This section has been amended at the state or city level.

52.3.2.1.2.1

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems shall not be located in areas where the floor is located more than 75 ft. (22,860 mm) above the lowest level of fire department vehicle access, or where the floor level is more than 30 ft. (9144 mm) below the finished floor of the lowest level of exit discharge, unless otherwise permitted by 52.3.2.1.2.

52.3.2.1.2.2

AMENDMENT
This section has been amended at the state or city level.
Installations on noncombustible rooftops of buildings exceeding 75 ft. (22,860 mm) in height that do not obstruct fire department rooftop operations shall be permitted when approved by the AHJ.

52.3.2.1.3 Separation

AMENDMENT
This section has been amended at the state or city level.
Rooms containing stationary storage battery systems shall be located in high-hazard occupancies, or shall be separated from other areas of the building as stated in 52.3.2.1.3.1 and 52.3.2.1.3.2. Stationary storage battery systems shall be allowed to be in the same room with the equipment they support.

52.3.2.1.3.1

AMENDMENT
This section has been amended at the state or city level.
In other than assembly, educational, detention, and correction facilities; health care, ambulatory health care, and day care centers; and residential board and care and residential occupancies, stationary storage battery systems shall be located in a room separated from other portions of the building by a minimum of a one hour fire barrier.

52.3.2.1.3.2

AMENDMENT
This section has been amended at the state or city level.
In assembly, educational, detention, and correction facilities; health care, ambulatory health care, and day care centers; and residential board and care and residential occupancies, stationary storage battery systems shall be located in a room separated from other portions of the building by a minimum of a two-hour fire barrier.

52.3.2.1.4 Outdoor Installations

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems located outdoors shall comply with this paragraph, in addition to all applicable requirements of Section 52.3.

52.3.2.1.4.1

AMENDMENT
This section has been amended at the state or city level.
Installations in outdoor enclosures or containers that are occupied for servicing, testing, maintenance, and other functions shall be treated as stationary storage battery system rooms.

52.3.2.1.4.2

AMENDMENT
This section has been amended at the state or city level.
Battery arrays in noncombustible containers shall not be required to be spaced 3 ft. (914 mm) from the container walls.

52.3.2.1.4.3

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems located outdoors shall be separated by a minimum 5 ft. (1524 mm) from the following:
  1. Lot lines;
  2. Public ways;
  3. Buildings;
  4. Stored combustible materials;
  5. Hazardous materials;
  6. High-piled stock; and
  7. Other exposure hazards.

52.3.2.1.4.4

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to authorize smaller separation distances if large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory is provided showing that a fire involving the system will not adversely impact occupant egress from adjacent buildings, or adversely impact adjacent stored materials or structures.

52.3.2.1.4.5 Means of Egress

AMENDMENT
This section has been amended at the state or city level.

52.3.2.1.4.5.1

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems located outdoors shall be separated from any means of egress as required by the AHJ to ensure safe egress under fire conditions, but in no case less than 10 ft. (3048 mm).

52.3.2.1.4.5.2

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to authorize smaller separation distances if large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory is provided showing that a fire involving the system will not adversely impact occupant egress.

52.3.2.1.4.6 Security of Areas

AMENDMENT
This section has been amended at the state or city level.
Outdoor areas in which stationary storage battery systems are located shall be secured against unauthorized entry in an approved manner.

52.3.2.2 Maximum Allowable Quantities

AMENDMENT
This section has been amended at the state or city level.

52.3.2.2.1

AMENDMENT
This section has been amended at the state or city level.
Fire areas within buildings containing stationary storage battery systems exceeding the maximum allowable quantities in Table 52.3.2.2.1 shall comply with all applicable ordinary-hazard and high-hazard requirements as identified in 6.2.2 of NFPA 101 and the building code.
Table 52.3.2.2.1
Type Maximum Allowable Quantitiesa Hazard Classification
Lithium batteries, all types

600 KWh

High hazardc
Sodium batteries, all types

600 KWh

High hazardc
Flow batteriesb

600 KWh

High hazardc
Other battery technologies

200 KWh

High hazardc
Notes:
  1. For batteries and capacitors rated in Amp-Hours, KWh should equal rated voltage times amp-hour rating divided by 1000.
  2. Includes vanadium, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies.
  3. Can be permitted to be ordinary hazard classification if approved by the AHJ based on (1) a hazard mitigation analysis conducted in accordance with 52.3.2.4 and (2) large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory that shows that a fire involving the stationary storage battery system is contained within the room for a duration equal to the fire resistance rating of the room separation required in 52.3.2.1.3.1 or 52.3.2.1.3.2, as applicable.

52.3.2.2.2

AMENDMENT
This section has been amended at the state or city level.
Where approved by the AHJ, areas containing stationary storage battery systems that exceed the amounts in Table 52.3.2.2.1 shall be permitted to be treated as an ordinary-hazard and not a high-hazard classification based on a hazardous mitigation analysis in accordance with 52.3.2.4 and large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory.

52.3.2.2.3

AMENDMENT
This section has been amended at the state or city level.
Where areas within buildings contain a combination of energy system technologies, the total aggregate quantities shall be determined based on the sum of percentages of each type divided by the maximum allowable quantity of each type. If the sum of the percentages exceeds 100%, the area shall be treated as a high-hazard classification in accordance with Table 52.3.2.2.1.

52.3.2.3* Battery Arrays

AMENDMENT
This section has been amended at the state or city level.
A52.3.2.3 A stationary battery array is an arrangement of individual stationary storage batteries in close proximity to each other, mounted on storage racks or in modules, battery cabinets, or other enclosures.

52.3.2.3.1

AMENDMENT
This section has been amended at the state or city level.
Battery arrays shall comply with 52.3.2.3.2 and 52.3.2.3.3, unless otherwise permitted by 52.3.2.3.4 or 52.3.2.3.5.

52.3.2.3.2

AMENDMENT
This section has been amended at the state or city level.
Storage batteries, prepackaged stationary storage battery systems, and pre-engineered stationary storage battery systems shall be segregated into arrays not exceeding 50 KWh (180 Mega joules) each.

52.3.2.3.3

AMENDMENT
This section has been amended at the state or city level.
Each array shall be spaced a minimum 3 ft. (914 mm) from other arrays and from walls in the storage room or area. The storage arrangements shall comply with the egress provisions in NFPA 101.

52.3.2.3.4

AMENDMENT
This section has been amended at the state or city level.
Listed pre-engineered stationary storage battery systems and prepackaged stationary storage battery systems shall not exceed 250 KWh (900 Mega joules) each.

52.3.2.3.5

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to approve listed pre-engineered and prepackaged battery arrays with larger capacities orsmaller battery array spacing if large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory is provided showing that a fire involving one array will not propagate to an adjacent array, and be contained within the room for a duration equal to the fire resistance rating of the room separation required by 52.3.2.1.3.

52.3.2.4 Hazard Mitigation Analysis

AMENDMENT
This section has been amended at the state or city level.
A failure mode and effects analysis (FMEA) or other approved hazard mitigation analysis shall be provided to the AHJ when any of the following conditions are present:
  1. Battery technologies not specifically identified in Table 52.3.1 are provided.
  2. More than one stationary storage battery technology is provided in a room or indoor area where there is a potential for adverse interaction between technologies.
  3. When allowed as a basis for increasing maximum allowable quantities as specified in Table 52.3.2.2.1.

52.3.2.4.1

AMENDMENT
This section has been amended at the state or city level.
The analysis shall evaluate the consequences of the following failure modes, and others deemed necessary by the AHJ. Only single failure modes shall be considered for each mode:
  1. Thermal runaway condition in a single module or array
  2. Failure of a battery management system
  3. Failure of a required ventilation system
  4. Voltage surges on the primary electric supply
  5. Short circuits on the load side of the stationary battery storage system
  6. Failure of the smoke detection, fire suppression, or gas detection system

52.3.2.4.2

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to approve the hazardous mitigation analysis provided the consequences of the FMEA demonstrate the following:
  1. Fires or explosions will be contained within unoccupied stationary storage battery system rooms for the minimum duration of the fire resistance rating specified in 52.3.2.1.3.1 or 52.3.2.1.3.2, as applicable
  2. Fires and explosions in stationary storage battery system cabinets in occupied work centers allow occupants to safely evacuate
  3. Toxic and highly toxic gases released during charging, discharging, and normal operation shall not exceed the permissible exposure limit (PEL)
  4. Toxic and highly toxic gases released during fires and other fault conditions shall not reach concentrations in access of IDLH level in the building or adjacent means of egress routes during the time deemed necessary to evacuate from that area
  5. Flammable gases released from batteries during charging, discharging, and normal operation shall not exceed 25% of the lower flammable limit (LFL)

52.3.2.4.3

AMENDMENT
This section has been amended at the state or city level.
Construction, equipment, and systems that are required for the stationary storage battery system to comply with the hazardous mitigation analysis shall be installed, maintained, and tested in accordance with nationally recognized standards and specified design parameters.

52.3.2.5 Listings

AMENDMENT
This section has been amended at the state or city level.
Storage batteries shall be listed in accordance with UL 1973, Standard for Batteries for Use in Light Electric Rail (LER) Applications and Stationary Applications. Prepackaged and pre-engineered stationary storage battery systems shall be listed in accordance with UL 9540, Outline of Investigation for Energy Storage Systems and Equipment.

52.3.2.5.1* Prepackaged and Pre-Engineered Systems

AMENDMENT
This section has been amended at the state or city level.
Prepackaged and pre-engineered stationary storage battery systems shall be installed in accordance with their listing and the manufacturer's instructions.

A52.3.2.5.1 A prepackaged stationary storage battery system is designed and investigated as a single unit, assembled in a factory, and shipped to the site. A pre-engineered stationary storage battery system is designed and investigated as a single unit, but is shipped in modular form for assembly at the site.

52.3.2.5.2 Environment

AMENDMENT
This section has been amended at the state or city level.
The storage battery environment shall be controlled to maintain temperatures and conditions within the battery manufacturer's specifications.

52.3.2.6 Installation

AMENDMENT
This section has been amended at the state or city level.

52.3.2.6.1 Battery Management System

AMENDMENT
This section has been amended at the state or city level.
An approved battery management system shall be provided for battery technologies for monitoring and balancing cell voltages, currents, and temperatures within the manufacturer's specifications. The system shall transmit an alarm signal to an approved location if potentially hazardous temperatures or other conditions including short circuits, overvoltage (i.e., overcharge) or under voltage (i.e., over discharge) are detected.

52.3.2.6.2 Battery Chargers

AMENDMENT
This section has been amended at the state or city level.
Battery chargers shall be compatible with the battery manufacturer's electrical ratings and charging specifications. Battery chargers shall be listed in accordance with the UL 1564, Standard for Industrial Battery Chargers, or provided as part of a listed pre-engineered or prepackaged stationary storage battery system.

52.3.2.6.3 Vehicle Impact Protection

AMENDMENT
This section has been amended at the state or city level.
Vehicle impact protection shall be provided where stationary storage battery systems are subject to impact by motor vehicles.

52.3.2.6.4 Combustible Storage

AMENDMENT
This section has been amended at the state or city level.

52.3.2.6.4.1

AMENDMENT
This section has been amended at the state or city level.
Combustible materials not related to the stationary storage battery system shall not be stored in battery rooms, cabinets, or enclosures.

52.3.2.6.4.2

AMENDMENT
This section has been amended at the state or city level.
Combustible materials in occupied work centers shall comply with Section 10.18 and shall not be stored within 3 ft. (915 mm) of battery cabinets.

52.3.2.6.5 Signage

AMENDMENT
This section has been amended at the state or city level.

52.3.2.6.5.1

AMENDMENT
This section has been amended at the state or city level.
Approved signage shall be provided on doors or in approved locations near entrances to stationary battery storage system rooms.

52.3.2.6.5.2

AMENDMENT
This section has been amended at the state or city level.
New signage installations shall require the following items:
  1. Hazard identification markings in accordance with NFPA 704.
  2. "This room contains energized battery systems", or the equivalent.
  3. Identification of the type(s) of batteries present
  4. AUTHORIZED PERSONNEL ONLY
  5. Technology-specific markings, if required in 52.3.2.11

52.3.2.6.5.3

AMENDMENT
This section has been amended at the state or city level.
Where the battery storage system disconnecting means is not within sight of the main service disconnect, placards or directories shall be installed at the locations of the main service disconnect to indicate the location of all battery storage disconnecting means in accordance with NFPA 70.

52.3.2.6.5.4

AMENDMENT
This section has been amended at the state or city level.
Existing stationary storage battery systems shall be permitted to include the signage required at the time it was installed.

52.3.2.6.5.5

AMENDMENT
This section has been amended at the state or city level.
Battery cabinets shall be provided with exterior labels that identify the manufacturer and model number of the system and electrical rating (i.e., voltage and current) of the contained battery system.

52.3.2.6.5.6

AMENDMENT
This section has been amended at the state or city level.
Signs shall be provided within battery cabinets to indicate the relevant electrical, chemical, and fire hazard.

52.3.2.6.5.7

AMENDMENT
This section has been amended at the state or city level.
Fire command centers in buildings containing stationary storage battery systems shall include signage or readily available documentation that describes the location of stationary storage battery systems, the types of batteries present, operating voltages, and location of electrical disconnects.

52.3.2.6.6 Seismic Protection

AMENDMENT
This section has been amended at the state or city level.
Battery systems shall be seismically braced in accordance with the Building Code.

52.3.2.6.7 Safety Caps

AMENDMENT
This section has been amended at the state or city level.
Vented batteries shall be provided with flame-arresting safety caps.

52.3.2.6.8* Mixed Battery Systems

AMENDMENT
This section has been amended at the state or city level.
Different types of batteries shall not be installed in the same room or cabinet if there is a potential for unsafe interaction between them, as determined by the AHJ.

A52.3.2.6.8 This section is intended to address unique situations where the installation of different types of batteries in the same room or cabinet could create a situation where there is unacceptable chemical, thermal, or other interaction between them, or where the surrounding environment is not within the battery manufacturers' specifications. The AHJ has the option to require a hazard mitigation analysis, conducted in accordance with 52.3.2.4, to identify hazards and potential solutions that will mitigate the hazards.

52.3.2.7 Suppression and Detection

AMENDMENT
This section has been amended at the state or city level.

52.3.2.7.1 Fire Suppression

AMENDMENT
This section has been amended at the state or city level.
Rooms containing stationary storage battery systems shall be protected by an automatic sprinkler system installed in accordance with Section 13.3.

52.3.2.7.1.1

AMENDMENT
This section has been amended at the state or city level.
Commodity classifications for specific technologies of storage batteries shall be in accordance with Chapter 5 of NFPA 13.

52.3.2.7.1.2

AMENDMENT
This section has been amended at the state or city level.
If the storage battery types are not specifically addressed in Chapter 5 of NFPA 13, the AHJ shall be permitted to approve the fire suppression system based on full-scale fire and fault condition testing conducted or witnessed and reported by an approved laboratory.

52.3.2.7.2 Smoke Detection

AMENDMENT
This section has been amended at the state or city level.
An approved automatic smoke detection system shall be installed in rooms containing stationary battery storage systems in accordance with NFPA 72 and the required automatic smoke detection system shall be supervised by an approved central, proprietary, or remote station service or a local alarm that will give an audible signal at a constantly attended location.

52.3.2.8* Ventilation

AMENDMENT
This section has been amended at the state or city level.
Where required by 52.3.2.11, ventilation shall be provided for rooms and cabinets in accordance with the mechanical code and one of the following:
  1. A52.3.2.8 Information on battery room ventilation can be found in IEEE1635/AHRAE 21, Guide to Battery Room Ventilation and Thermal Management.
    1. The ventilation system shall be designed to limit the maximum concentration of flammable gas to 25% of the lower flammable limit (LFL) of the total volume of the room during the worst-case event of simultaneous "boost" charging of all the batteries, in accordance with nationally recognized standards.
    2. Mechanical ventilation shall be provided at a rate of not less than 1 ft.3/min/ft.2 (5.1 L/sec/m2) of floor area of the room or cabinet. The ventilation can be either continuous, or activated by a gas detection system in accordance with 52.3.2.8.2.

52.3.2.8.1

AMENDMENT
This section has been amended at the state or city level.
Required mechanical ventilation systems for rooms and cabinets containing storage batteries shall be supervised by an approved central, proprietary, or remote station service or shall initiate an audible and visual signal at an approved constantly attended on-site location.

52.3.2.8.2

AMENDMENT
This section has been amended at the state or city level.
Where required by 52.3.2.8(2), rooms containing stationary storage battery systems shall be protected by an approved continuous gas detection system.

52.3.2.8.2.1

AMENDMENT
This section has been amended at the state or city level.
The gas detection system shall be designed to activate when the level of flammable gas exceeds 25% of the lower flammable limit (LFL).

52.3.2.8.2.2

AMENDMENT
This section has been amended at the state or city level.
Activation of the gas detection system shall result in activation of the mechanical ventilation system, which shall remain on until the flammable gas detected is less than 25% of the LFL.

52.3.2.8.2.3

AMENDMENT
This section has been amended at the state or city level.
The gas detection system shall include a minimum two hours of standby power.

52.3.2.8.2.4

AMENDMENT
This section has been amended at the state or city level.
Failure of the gas detection system shall annunciate a trouble signal at an approved central, proprietary, or remote station service, or when approved at a constantly attended on-site location.

52.3.2.9* Spill Control and Neutralization

AMENDMENT
This section has been amended at the state or city level.
Where required by 52.3.2.11, approved methods and materials shall be provided for the control and neutralization of spills of electrolyte or other hazardous materials in rooms containing stationary storage batteries as follows:
  1. A52.3.2.9 Methods of achieving this protection can include, but are not limited to, the following:
    1. Liquidtight sloped or recessed floors in indoor locations or similar areas in outdoor locations
    2. Liquidtight floors in indoor locations or similar areas in outdoor locations provided with liquidtight raised or recessed sills or dikes
    3. Sumps and collection systems
      1. For batteries with free-flowing electrolyte, the method and materials shall be capable of neutralizing a spill of the total capacity from the largest cell or block to a pH between 5.0 and 9.0.
      2. For batteries with immobilized electrolyte, the method and materials shall be capable of neutralizing a spill of 3.0 percent of the capacity of the largest cell or block in the room to a pH between 5.0 and 9.0.

52.3.2.10 Thermal Runaway

AMENDMENT
This section has been amended at the state or city level.
Where required by 52.3.2.11, a listed device or other approved method shall be provided to preclude, detect, and control thermal runaway.

52.3.2.11 Battery Specific Protection

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems shall comply with 52.3.2 through 52.3.2.10 and this section, as applicable.

52.3.2.11.1 Lithium Batteries

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems utilizing lithium batteries shall be provided with thermal runaway protection in accordance with 52.3.2.10.

52.3.2.11.2 Sodium Batteries

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems utilizing sodium batteries shall comply with the following:
  1. Ventilation shall be provided in accordance with 52.3.2.8.
  2. Spill control and neutralization shall be in accordance with 52.3.2.9.
  3. Thermal runaway protection shall be provided for in accordance with 52.3.2.10.
  4. A hazard mitigation analysis shall be provided for systems that utilize sodium sulfur batteries, or other sulfur-type battery systems that operate above ambient temperatures.
  5. The signage required in 52.3.2.6.5 shall include, where applicable, "Water Reactive Hazard - Apply No Water".

52.3.2.11.3 Flow Batteries

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems utilizing flow batteries shall comply with the following:
  1. Ventilation shall be provided in accordance with 52.3.2.8.
  2. Spill control and neutralization shall be in accordance with 52.3.2.9.

52.3.2.11.4 Other Battery Types

AMENDMENT
This section has been amended at the state or city level.
Stationary storage battery systems utilizing battery technologies other than those described in 52.3.2.11.1 through 52.3.2.11.1 shall comply with the following:
  1. Ventilation shall be provided in accordance with 52.3.2.8 where flammable, toxic or highly toxic gases could be present during charging, discharging, and normal system use.
  2. Spill control and neutralization shall be in accordance with 52.3.2.9 where the batteries contain electrolytes that could be released from the batteries.
  3. Thermal runaway protection shall be provided in accordance with 52.3.2.10.
  4. The signage required in 52.3.2.6.5 shall also identify any potential hazards associated with the batteries.

52.3.2.12 Testing, Maintenance, and Repairs

AMENDMENT
This section has been amended at the state or city level.

52.3.2.12.1

AMENDMENT
This section has been amended at the state or city level.
Stationary storage batteries and associated equipment and systemsshall be tested and maintained in accordance with the manufacturer's instructions.

52.3.2.12.2

AMENDMENT
This section has been amended at the state or city level.
Any storage batteries or system components used to replace existing units shall be compatible with the battery charger, battery management systems, other storage batteries, and other safety systems.

52.3.3 Capacitor Energy Storage Systems

AMENDMENT
This section has been amended at the state or city level.

52.3.3.1 Capacity

AMENDMENT
This section has been amended at the state or city level.
Stationary capacitor energy storage systems having capacities greater than those described in Table 52.3.1 shall comply with 52.3.3.

52.3.3.2 Location and Occupancy Separation

AMENDMENT
This section has been amended at the state or city level.
Stationary capacitor energy storage systems shall be located and constructed as required for stationary storage battery system in accordance with 52.3.2.1 through 52.3.2.1.4.3.

52.3.3.3 Maximum Allowable Quantities

AMENDMENT
This section has been amended at the state or city level.
Fire areas within buildings containing capacitor energy storage systems exceeding 600 KWh (2160 mJ) shall comply with all applicable ordinary-hazard and high-hazard requirements as identified in 6.2.2 of NFPA 101 and the Building Code.

52.3.3.4 Capacitor Arrays

AMENDMENT
This section has been amended at the state or city level.

52.3.3.4.1

AMENDMENT
This section has been amended at the state or city level.
Capacitors, prepackaged stationary capacitor energy storage systems, and pre-engineered capacitor energy storage systems shall be segregated into arrays not exceeding 50 KWh (180 Mega joules) each.

52.3.3.4.2

AMENDMENT
This section has been amended at the state or city level.
Each array shall be spaced a minimum 3 ft. (914 mm) from other arrays and from walls in the storage room or area. The storage arrangements shall comply with the egress provisions in NFPA 101.

52.3.3.5 Listings

AMENDMENT
This section has been amended at the state or city level.
Capacitors shall be listed in accordance with UL 1973, Standard for Batteries for Use in Light Electric Rail (LER) Applications and Stationary Applications. Prepackaged and pre-engineered capacitor energy systems shall be listed in accordance with UL 9540, Outline of Investigation for Energy Storage Systems and Equipment.

52.3.3.5.1* Prepackaged and Pre-Engineered Systems

AMENDMENT
This section has been amended at the state or city level.
Prepackaged and pre-engineered capacitor energy storage systems shall be installed in accordance with their listing and the manufacturer's instructions.

A52.3.3.5.1 A prepackaged capacitor energy system is designed and investigated as a single unit, assembled in a factory, and shipped to the site. A pre-engineered capacitor energy system is designed and investigated as a single unit, but is shipped in modular form for assembly at the site.

52.3.3.5.2 Environment

AMENDMENT
This section has been amended at the state or city level.
The environment surrounding the capacitors shall be controlled to maintain temperatures and conditions within the manufacturer's specifications.

52.3.3.6 Chargers

AMENDMENT
This section has been amended at the state or city level.
Capacitor chargers shall be compatible with the capacitor manufacturer's electrical ratings and charging specifications, and shall be listed in accordance with the UL 1564, Standard for Industrial Battery Chargers, or provided as part of a listed pre-engineered or prepackaged capacitor energy storage system.

52.3.3.7 Vehicle Impact Protection

AMENDMENT
This section has been amended at the state or city level.
Vehicle impact protection shall be provided where capacitor energy storage systems are subject to impact by motor vehicles.

52.3.3.8 Combustible Storage

AMENDMENT
This section has been amended at the state or city level.

52.3.3.8.1

AMENDMENT
This section has been amended at the state or city level.
Combustible materials not related to the capacitor energy storage system shall not be stored in capacitor rooms, cabinets, or enclosures.

52.3.3.8.2

AMENDMENT
This section has been amended at the state or city level.
Combustible materials in occupied work centers shall comply with Section 10.18 and shall not be stored within 3 ft. (915 mm) of capacitor cabinets.

52.3.3.9 Signage

AMENDMENT
This section has been amended at the state or city level.
Approved signage shall be provided on doors or in approved locations near entrances to capacitor energy storage systems, and shall include the following:
  1. Hazard identification markings in accordance with NFPA 704;
  2. "This room contains energized capacitor systems", or the equivalent;
  3. Identification of the type(s) of capacitors present; and
  4. AUTHORIZED PERSONNEL ONLY.

52.3.3.9.1

AMENDMENT
This section has been amended at the state or city level.
Where the capacitor energy storage system disconnecting means is not within sight of the main service disconnect, placards or directories shall be installed at the locations of the main service disconnect to indicate the location of all capacitor energy storage system disconnecting means in accordance with NFPA70.

52.3.3.9.2

AMENDMENT
This section has been amended at the state or city level.
Capacitor cabinets shall be provided with exterior labels that identify the manufacturer and model number of the system and electrical rating (i.e., voltage and current) of the contained battery system.

52.3.3.9.3

AMENDMENT
This section has been amended at the state or city level.
Signs shall be provided within capacitor cabinets to indicate the relevant electrical, chemical, and fire hazard.

52.3.3.9.4

AMENDMENT
This section has been amended at the state or city level.
Fire command centers in buildings containing capacitor energy storage systems shall include signage or readily available documentation that describes the location of the systems, the types of capacitors present, operating voltages, and location of electrical disconnects.

52.3.3.10 Seismic Protection

AMENDMENT
This section has been amended at the state or city level.
Capacitor energy storage systems shall be seismically braced in accordance with the Building Code.

52.3.3.11 Testing, Maintenance, and Repairs

AMENDMENT
This section has been amended at the state or city level.

52.3.3.11.1

AMENDMENT
This section has been amended at the state or city level.
Capacitor energy storage systems and associated equipment and systems shall be tested and maintained in accordance with the manufacturer's instructions.

52.3.3.11.2

AMENDMENT
This section has been amended at the state or city level.
Capacitors or system components used to replace existing units shall be compatible with the capacitor charger, other capacitors, and other safety systems.