Heads up: There are no amended sections in this chapter.
Hot work shall comply with NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, and this chapter.

41.1.1.1 Terms

AMENDMENT
This section has been amended at the state or city level.
As used in Chapter 41, the enclosed terms shall have the following meaning assigned to them.
  1. Hot Work. Work involving, burning, welding, or a similar operation that is capable of initiating fires or explosions. [51B:3.3.2]
  2. Hot Work Operator. A qualified person and if required, shall be certified pursuant to the provisions of this chapter and standards referenced in this chapter.
  3. Qualified Person. A person who has successfully completed the training criteria pursuant to Section 41.7.
  4. Management. For the purpose of hot work, all persons, including owners, contractors, educators, and so on, who are responsible for hot work operations. [51B:3.3.2]
  5. Permissible Areas.
    1. Designated Area. A specific location designed and approved for hot work operations that is maintained fire-safe, such as a maintenance shop or a detached outside location, that is of noncombustible or fire-resistive construction, essentially free of combustible and flammable contents, and suitably segregated from adjacent areas. [51B:3.3.3.1]
    2. Permit-required Area. Any location other than a designated area that is approved for hot work and is made fire-safe by removing or protecting combustibles from ignition sources. [51B:3.3.3.2]
  6. Permit. For the purposes of hot work, a document issued, by the AHJ, to a qualified person as defined in Section 41.1.1.1(3) for the purpose of authorizing that individual to carry out the activity of hot work.
  7. Permit Authorizing Individual (PAI). An individual designated by management to authorize hot work. [51B:3.3.5*]
  8. Welding and Allied Processes. Processes such as arc welding, oxy-fuel gas welding, open-flame soldering, brazing, thermal spraying, oxygen cutting, and arc cutting. [51B, 3.3.6*]
Chapter 41 shall apply to the following hot work processes:
  1. Welding and allied processes
  2. Heat treating
  3. Grinding
  4. Thawing pipe
  5. Powder-driven fasteners
  6. Hot riveting
  7. *Torch-applied roofing in conjunction with the requirements of Section 16.6
  8. Similar applications producing or using a spark, flame, or heat [51B:1.3.1]
Chapter 41 shall not apply to the following:
  1. Candles
  2. Pyrotechnics or special effects
  3. Cooking operations
  4. Electric soldering irons
  5. Design and installation of gas cutting equipment and welding equipment covered in NFPA 51, Standard for the Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes
  6. Additional requirements for hot work operations in confined spaces
  7. Lockout/tagout procedures during hot work [51B:1.3.2]
Acetylene cylinder charging plants shall comply with NFPA 51A, Standard for Acetylene Cylinder Charging Plants.
Permits, where required, shall comply with Section 1.12.
Where an approved facility hot work permit program exists that meets the requirements of Chapter 41, the permit shall be permitted to be issued for an entire facility.

41.1.5.3 Hot Work Permit

AMENDMENT
This section has been amended at the state or city level.
Hot work permits, where required shall comply with Section 1.12 and Chapter 41.
Management or a designated agent shall be responsible for the safe operations of hot work activity. [51B:4.1]
Management shall establish permissible areas for hot work. [51B:4.1.1]
Management shall designate a permit authorizing individual (PAI). [51B:4.1.2]
All equipment shall be examined to ensure it is in a safe operating condition. [51B:4.1.3]
When found to be incapable of reliable safe operation, the equipment shall be repaired by qualified personnel prior to its next use or be withdrawn from service and tagged out of service. [51B:4.1.4]
Management shall ensure that only approved apparatus, such as torches, manifolds, regulators or pressure-reducing valves, and acetylene generators, are used. [51B:4.1.5]
Management shall ensure that all individuals involved in the hot work operations, including contractors, are familiar with the provisions of Chapter 41. [51B:4.1.6]
Individuals involved in hot work operations shall be trained in the safe operation of their equipment and in the safe use of the process. [51B:4.1.6.1]
Individuals involved in hot work operations shall have an awareness of the inherent risks involved and understand the emergency procedures in the event of a fire. [51B:4.1.6.2]
Management shall advise all contractors about site-specific flammable materials, hazardous processes or conditions, or other potential fire hazards. [51B:4.1.7]

41.2.1.8

AMENDMENT
This section has been amended at the state or city level.
Management shall ensure that the contractor has evidence of financial responsibility, which can take the form of an insurance certificate or other document at testing to coverage or responsibility, a copy and an education certification of completion shall be submitted to the AHJ when requested.

41.2.1.9

AMENDMENT
This section has been amended at the state or city level.
Management shall assure that welders and their supervisors are trained in the safe operation of their equipment, the safe use of the process, and emergency procedures and maintain education certificates of completion on file and if requested submit to the AHJ.

41.2.1.10

AMENDMENT
This section has been amended at the state or city level.
Management or designated agent shall select contractors to perform welding who provide trained and qualified personnel, and who have an awareness of the risks involved. [ANSI Z49, 2012]

41.2.2 Permit Authorizing Individual (PAI)

AMENDMENT
This section has been amended at the state or city level.
In conjunction with management and in consultation with the AHJ if required, the PAI shall be responsible for the safe operation of hot work activities.
The PAI shall consider the safety of the hot work operator and fire watch with respect to personal protective equipment (PPE) for other special hazards beyond hot work. (See 41.3.1.) [51B:4.2.1]
The PAI shall determine site-specific flammable materials, hazardous processes, or other potential fire hazards that are present or likely to be present in the work location. [51B:4.2.2]
The PAI shall ensure the protection of combustibles from ignition by the following means:
  1. *Considering alternative methods to hot work
  2. Moving the work to a location that is free from combustibles
  3. If the work cannot be moved, moving the combustibles to a safe distance or having the combustibles properly shielded against ignition
  4. Scheduling hot work so that operations that could expose combustibles to ignition are not begun during hot work operations [51B:4.2.3]
If the criteria of 41.2.2.3(1) through 41.2.2.3(4) cannot be met, hot work shall not be performed. [51B:4.2.4]
The PAI shall determine that fire protection and extinguishing equipment are properly located at the site. [51B:4.2.5]
Where a fire watch is required (see 41.3.5), the PAI shall be responsible for ensuring that a fire watch is at the site. [51B:4.2.6]
Where a fire watch is not required, the PAI shall make a final check 1/2 hour after the completion of hot work operations to detect and extinguish smoldering fires. [51B:4.2.7]

41.2.3 Hot Work Operator

AMENDMENT
This section has been amended at the state or city level.
The hot work operator shall handle equipment safely and use it as follows so as not to endanger lives and property:
  1. The operator shall have the PAT's approval before starting hot work operations.
  2. All equipment shall be examined to ensure it is in a safe operating condition, and, if found to be incapable of reliable safe operation, the equipment shall be repaired by qualified personnel prior to its next use or be withdrawn from service.
  3. The operator shall cease hot work operations if unsafe conditions develop and shall notify management, the area supervisor, or the PAI for reassessment of the situation. [51B:4.3]
  4. The hot work operator shall be permitted to be the PAI, however, in those cases, the hot works operator shall not be permitted to issue a hot work permit for the work to be performed by himself, see the provisions of Section 41.4(1) or 41.4(2).
The fire watch shall be trained to understand the inherent hazards of the work site and of the hot work. [51B:4.4.1]
The fire watch shall ensure that safe conditions are maintained during hot work operations. [51B:4.4.2]
The fire watch shall have the authority to stop the hot work operations if unsafe conditions develop. [51B:4.4.3]
The fire watch shall have fire-extinguishing equipment readily available and shall be trained in its use. [51B:4.4.4]
The fire watch shall be familiar with the facilities and procedures for sounding an alarm in the event of a fire. [51B:4.4.5]
The fire watch shall watch for fires in all exposed areas and try to extinguish them only when the fires are obviously within the capacity of the equipment available. If the fire watch determines that the fire is not within the capacity of the equipment, the fire watch shall sound the alarm immediately. [51B:4.4.6]
The fire watch shall be permitted to perform additional tasks, but those tasks shall not distract him or her from his or her fire watch responsibilities, except as outlined in Section 41.4. [51B:4.4.7]

41.2.4.8

AMENDMENT
This section has been amended at the state or city level.
A fire watch, when required, shall be maintained for at least 1/2 hour after completion of hot work operations in order to detect and extinguish smoldering fires. The duration of the fire watch shall be permitted to be extended if the PAI or the AHJ determines the fire hazards warrant the extension.

41.2.4.8.1

AMENDMENT
This section has been amended at the state or city level.
More than one fire watch shall be required if determined by the AHJ that combustible materials could be ignited by the hot work operation which cannot be directly observed by the initial fire watch.
Before starting any hot work, contractors and their clients shall discuss the planned project completely, including the type of hot work to be conducted and the hazards in the area. [51B:4.5]

41.2.5.1 Certificates

AMENDMENT
This section has been amended at the state or city level.
A hot work training certificate shall be carried on person at all times, and shall be produced upon request.
Management, contractors, the PAI, the fire watch, and the operators shall recognize their mutual responsibility for safety in hot work operations. [51B:4.6]
Clothing shall be selected to minimize the potential for ignition, burning, trapping hot sparks, and electric shock. [51B:5.1]
Hot work shall be permitted only in areas that are or have been made fire safe. [51B:5.2.1]
In order for a location to be a designated area, the area shall meet the requirements in 41.3.4.2. [51B:5.2.2.1.1]
Prior to the start of any hot work in a designated area, at a minimum, the hot work operator shall perform the following:
  1. The location is verified as fire resistant.
  2. The requirements of 41.3.4.2(3) are met.
  3. Fire extinguishers are in working condition and readily available.
  4. Ventilation is working properly.
  5. Equipment is in working order. [51B:5.2.2.1.3]
Permanent areas designated for hot work shall be reviewed at least annually by the PAL [51B:5.2.2.1.3]
Signs shall be posted designating hot work areas as deemed necessary by the PAI. [51B:5.2.2.2]
Hot work shall not be permitted in the following areas:
  1. In areas not authorized by management
  2. In sprinklered buildings where sprinklers are impaired, unless the requirements of NFPA 25 are met
  3. In the presence of explosive atmospheres (i.e., where mixtures of flammable gases, vapors, liquids, or dusts with air exist)
  4. In the presence of uncleaned or improperly prepared equipment, drums, tanks, or other containers that have previously contained materials that could develop explosive atmospheres
  5. In areas with an accumulation of combustible dusts that could develop explosive atmospheres [51B:5.3]
Before hot work operations begin in a nondesignated location, a written hot work permit by the PAI shall be required. [51B:5.4.1]

41.3.4.1.1

AMENDMENT
This section has been amended at the state or city level.
The decision tree in Figure 41.3.4.1.1 shall be permitted to be used to determine if a hot work permit is necessary.
Figure 41.3.4.1.1 Hot Work Permit Decision Tree

41.3.4.1.1.1

AMENDMENT
This section has been amended at the state or city level.
A Hot Work Permit shall be used when hot work is to be carried out in a Permitted Required Area.
41.3.4.1.1.1 Sample Hot Work Permit

41.3.4.2

AMENDMENT
This section has been amended at the state or city level.
Before a hot work permit is issued the following conditions shall be verified by the PAI, and with the AHJ if required:
  1. The hot work equipment to be used shall be in satisfactory operating condition and in good repair.
  2. Where combustible materials, such as paper clippings, wood shavings, or textile fibers. are on the floor. the floor shall be swept clean for a radius of 35 ft (11 m) and the following criteria also shall be met:
    1. Combustible floors shall be kept wet, covered with damp sand, or protected by a listed welding blanket, welding pad, or equivalent.
    2. Where floors have been wet down, personnel operating arc welding equipment or cutting equipment shall be protected from possible shock.
  3. *All combustible shall be relocated at least 35 ft (11 m) in all directions from the work site, and the following criteria also shall be met:
    1. If relocation is impractical, combustibles shall be protected by a listed welding blanket, welding pad, or equivalent.
    2. To prevent the entrance of sparks, the edges of covers at the floor shall be tight including at the point at which several covers overlap where a large pile is being protected.
  4. Openings or cracks in walls, floors, or ducts within 35 ft (11 m) of the site shall be covered or sealed with listed fire-rated or noncombustible material to prevent the passage of sparks to adjacent areas.
  5. Ducts and conveyor systems that might carry sparks to distant combustibles shall be shielded, or shut down, or both.
  6. If hot work is done near walls, partitions, ceilings, or roofs of combustible construction. they shall be protected by a listed welding curtain, welding blanket, welding pad, or equivalent.
  7. If hot work is done on one side of a wall, partition, ceiling, or roof, one of the following criteria shall be met:
    1. Precautions shall be taken to prevent ignition of combustibles on the other side by relocating the combustibles.
    2. If it is impractical to relocate combustibles, a fire watch shall be provided on the side opposite from where the work is being performed.
  8. Hot work shall not be attempted on a partition, wall, ceiling, or roof that has a combustible covering or insulation, or on walls or partitions of combustible sandwich-type panel construction.
  9. Hot work that is performed on pipes or other metal that is in contact with combustible walls, partitions, ceilings, roofs, or other combustibles shall not be undertaken if the work is close enough to cause ignition by conduction.
  10. Fully charged and operable fire extinguishers that are appropriate for the type of possible fire shall be available immediately at the work area.
  11. If existing hose lines are located within the hot work area defined by the permit, they shall be connected and ready for service but shall not be required to be unrolled or charged.
  12. The following shall apply to hot work done in close proximity to a sprinkler head:
    1. A wet rag shall be laid over the sprinkler head and then removed at the conclusion of the welding or cutting operation.
    2. During hot work, special precautions shall be taken to avoid accidental operation of automatic fire detection or suppression systems (e.g., special extinguishing systems or sprinklers).
  13. The operator and nearby personnel shall be suitably protected against dangers such as heat, sparks, and slag.
  14. *In instances where the scope of work and the tools used to conduct hot work result in possible travel of slag, sparks, spatter, or similar mobile sources of ignition farther than 35 ft (11 m), the PAI shall be permitted to extend the distances and areas addressed in 41.3.4.2(2) through 41.3.4.2(4).
  15. *In instances where the scope of work and tools used to conduct hot work are known to be incapable of generating slag, sparks, spatter or similar mobile sources of ignition capable of leaving the immediate area of the applied hot work, the PAI shall be permitted to do the following:
    1. Reduce the distances and areas addressed in 41.3.4.2(2) through 41.3.4.2(4) to distances and areas that he or she considers fire safe for the intended operation.
    2. Describe those distances and areas on the hot work permit. [51B:5.4.2]

41.3.4.3

AMENDMENT
This section has been amended at the state or city level.
The PAI in consultation with the AHJ, if required shall determine the length of the period for which the hot work permit is valid.
The hot work permit shall not be valid for a period exceeding 24 hours. [51B:5.4.3.1]
The area shall be inspected by the PAI at least once per shift while the hot work permit is in effect to ensure that it is a fire-safe area. [51B:5.4.4]

41.3.5.1*

AMENDMENT
This section has been amended at the state or city level.
A fire watch shall be required by the PAI in consultation with the AHJ, when hot work is performed in a location where other than a minor fire might develop or where the following conditions exist:
  1. *Combustible materials in building construction or contents are closer than 35 ft (11 m) to the point of operation.
  2. Combustible materials are more than 35 ft (11 m) away from the point of operation but are easily ignited by sparks.
  3. Wall or floor openings within an 35 ft (11 m) radius expose combustible materials in adjacent areas, including concealed spaces in walls or floors.
  4. Combustible materials are adjacent to the opposite side of partitions, walls, ceilings, or roofs and are likely to be ignited. [51B:5.5.1]

41.3.5.1.1

AMENDMENT
This section has been amended at the state or city level.
Table 41.3.5.1.1 entitled Fire Watch Tree shall be permitted to be used by the PAI and AHJ to determine if a fire watch is necessary.
Table 41.3.5.1.1 Fire Watch Decision Tree
Afire watch shall be maintained for at least 1/2 hour after completion of hot work operations in order to detect and extinguish smoldering fires. The duration of the fire watch shall be extended if the PAI determines the fire hazards warrant the extension. [51B:5.5.2]
More than one fire watch shall be required if combustible materials that could be ignited by the hot work operation cannot be directly observed by the initial fire watch. [51B:5.5.3]
Hot tapping or other cutting and welding on a flammable gas or liquid transmission or distribution utility pipeline shall be performed by a crew that is qualified to make hot taps. [51B:5.6]
Cylinder use and storage shall be in accordance with Chapter 63. [51B:5.7]

41.4 Sole Proprietors and Individual Operators

AMENDMENT
This section has been amended at the state or city level.
UpCodes note: There seems to be a misprint on the Massachusetts Amendments to NFPA ®1, 2015 . There are two modifications for Section 41.4.1. It says:

"41.4 Sole Proprietors and Individual Operators.

41.4.1 All hot work operations shall require a permit from the Head of the Fire Department unless specifically otherwise allowed by 41.4.1(1) through (3):
.
.
.
41.4.1* Replace with the following:

41.4.1 Assignment of PAI and Fire Watch. Sole proprietors and individual operators as
provided in Sections 41.4(1) and (2)shall be permitted to serve as PAI, fire watch and operator."

We determinted that the original section 41.4.1 was moved to 41.4.2 and the new 41.4.1 was created as a result of the amendment as show below.

41.4.1* Assignment of PAI and Fire Watch

AMENDMENT
This section has been amended at the state or city level.
All hot work operations shall require a permit from the Head of the Fire Department unless specifically otherwise allowed by 41.4.1(1) through (3):

(1) Hot Work Operations Conducted by Persons Licensed by Other Jurisdictions

AMENDMENT
This section has been amended at the state or city level.
Pursuant to Section 1.1.2, a hot work permit shall not be required from the fire department when the hot work activity is performed by a person, or under the direct supervision of a person, licensed and permitted pursuant to a specialized code as defined in M.G.L. c. 143, § 96. Any licensed person performing hot work must have obtained training for hot work safetyeither:
  1. by obtaining training approved by the authority issuing them a license to perform specialized code work; or
  2. by meeting the requirements of Section 41.7 of Chapter 41.

(2) Hot Work Operations Conducted by Persons on Their Own Equipment on Their Own Premises

AMENDMENT
This section has been amended at the state or city level.
A permit from the Head of the Fire Department for hot works shall not be required by individuals who conduct hot work operations on their own equipment on their own premises. Any person performing such hot work shall be trained as provided by 41.7 of Chapter 41.

(3) Homeowners and Hobbyists

AMENDMENT
This section has been amended at the state or city level.
Homeowners and hobbyists are exempt from the permit requirements as provided by 1.12, and the training requirementsrequired in 41.7 of Chapter 41. See exhibitions 41.5.

41.4.2 Written Hot Work Permit

AMENDMENT
This section has been amended at the state or city level.

41.4.2 Assignment of PAI and Fire Watch

AMENDMENT
This section has been amended at the state or city level.
Sole proprietors and individual operators as provided in 41.4.1(1) and (2) shall be permitted to serve as PAI, fire watch and operator.

41.4.3 Written Hot Work Permit

AMENDMENT
This section has been amended at the state or city level.
A checklist shall be permitted to serve as the written hot work permit.
The provisions of Section 41.5 shall apply to oxy-fuel gas welding and cutting operations at public exhibitions, demonstrations, displays, and trade shows, referred to hereinafter as the "site," in order to promote the safe use of compressed gases in public gatherings. [51B:7.1]
Installation and operation of welding, cutting, and related equipment shall be done by, or under the supervision of, a competent operator, to ensure the personal protection of viewers and demonstrators as well as the protection from fire of materials in and around the site and the building itself. [51B:7.2]
Sites involving the use and storage of compressed gases shall be located so as not to interfere with egress during an emergency. [51B:7.3.1]
The site shall be constructed, equipped, and operated in such a manner that the demonstration minimizes the possibility of injury to viewers. [51B:7.3.2]
Each site shall be provided with a portable fire extinguisher of appropriate size and type in accordance with NFPA 10, Standard for Portable Fire Extinguishers. [51B:7.4.1]
The public, combustible materials, and compressed gas cylinders at the site shall be protected from flames, sparks, and molten metal. [51B:7.4.2]
The fire department shall be notified in advance of the use of a site for public exhibitions, demonstrations, and trade shows. [51B:7.4.3]

41.5.4.4 Inspection by the AHJ

AMENDMENT
This section has been amended at the state or city level.

41.5.4.4.1

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to require annual inspection for designated areas.

41.5.4.4.2

AMENDMENT
This section has been amended at the state or city level.
The AHJ shall be permitted to inspect a premise for compliance before any hot work is carried out.
Cylinders containing compressed gases for use at the site shall not be charged in excess of one-half their maximum permissible content. [51B:7.5.1.1]
Cylinders of nonliquefied gases and acetylene shall be charged to not more than one-half their maximum permissible charged gauge pressure [psi (kPa)]. [51B:7.5.1.2]
Cylinders of liquefied gases shall be charged to not more than one-half the maximum permissible capacity [lb (kg)]. [51B:7.5.1.3]
Cylinders located at the site shall be connected for use. [51B:7.5.2.1]
A sufficient number of additional cylinders shall be permitted to be stored at the site to furnish approximately one day's consumption of each gas used. [51B:7.5.2.2]
Other cylinders shall be stored in an approved storage area, but not near a building exit. [51B:7.5.2.3]
Cylinders in excess of 40 lb (18 kg) total weight being transported to or from the site shall be carried on a hand truck or motorized truck. [51B:7.5.3]
Process hose shall be located and protected so that they will not be physically damaged. [51B:7.5.4]
Cylinder valves shall be closed when equipment is unattended. [51B:7.5.5]
If cylinders are designed to be equipped with valve protection caps, such caps shall be in place, except when the cylinders are in service or are connected and ready for service. [51B:7.5.6]
Cylinders shall be secured so that they cannot be knocked over. [51B:7.5.7]
Electrical equipment shall be of an approved type and shall be installed and used in accordance with Section 11.1 and manufacturers' requirements.
Damaged cables shall be removed from service until repaired or replaced.

41.7 Qualifications

AMENDMENT
This section has been amended at the state or city level.
An individual to be qualified to be a PAI, perform fire watches, perform, supervise or delegate any activities of hot work as defined in this chapter shall first provide documentation that he or she has successfully completed training approved by the State Fire Marshal in the following areas:
  1. 527 CMR 1.00: Massachusetts Comprehensive Fire Safety Code, Chapter 41: Hot Work Operations;
  2. 29 CFR 1910.252 Subpart Q: Welding, Cutting and Brazing;
  3. NFPA 51B: Standard for Fire Prevention During Welding, Cutting, and Other Hot Work;
  4. NFPA 241: Standard for Safeguarding Construction, Alteration, and Demolition Operations;
  5. ANSI Z49: Safety in Welding, Cutting, and Allied Processes.

41.7.1

AMENDMENT
This section has been amended at the state or city level.
Successfully completed as used here means training successfully completed on the currently adopted standard as provided in 41.7(1) through (5).

41.7.2

AMENDMENT
This section has been amended at the state or city level.
A certificate of completion shall be issued to the individual with the date of completion on the certificate and a providers/instructors signature acknowledging such individual attended and completed the training as provided in 41.7(1) through (5).
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING